Cooling Tower

Closed Solicitation Posted

Solicitation number
36C26026Q0965
Agency
Responses due
Set-aside
No set-aside

Opportunity facts

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 20 seeks quotes for a new 50-ton cooling tower replacement at the Portland VA Medical Center Building T-51, with proposals due September 4, 2026 at 10:00 AM Pacific Time. The procurement is unrestricted, with no set-aside applied.

Place of performance is Portland, Oregon. The new cooling tower must fit within the existing 48" x 72" x 105" high footprint and 60" x 96" concrete pad, operate with existing chilled water supply at approximately 80 psi city water pressure, and integrate with existing 3-phase/480V/60Hz electrical service (20-amp pump breaker, 8-amp fan breaker). The unit must be Bacnet-compatible for integration with existing Delta Controls building equipment management software and meet seismic resistance requirements. The existing system is an Evapco LSWA2002 evaporative cooling tower; the facility's calculated cooling need is 46 tons. No military standards apply. NAICS code 238220, Plumbing, Heating, and Air-Conditioning Contractors; PSC code 4120, Air Conditioning Equipment.

Three line items are requested: the 50-ton cooling tower replacement, commissioning support services, and transportation, with a combined estimated budget of $19 million. Period of performance is nine months, with delivery coordinated based on production schedule and medical center operational needs. The offer must remain firm for 60 calendar days. Award will be made to the responsible offeror with the lowest price that meets all requirements; partial offers are not accepted. Amendment 0001, effective September 1, 2026, responds to vendor questions regarding voltage information and other site-specific requirements. Offerors must acknowledge receipt of this amendment prior to the proposal deadline.

Notice text

2 versions

Update #2 · Latest ·

The Portland VAMC requires a new 50-ton Cooling Tower. See attached solicitation and amendment for details. IMPORTANT: Amendment 0001 answers vendor questions which clarifies voltage information and provides other information. 

Update #1 ·

The Portland VAMC requires a new 50-ton Cooling Tower. See attached solicitation for details.

Files

File Type Posted
Vendor Questions.pdf PDF
36C26026Q0965 0001.pdf PDF
36C26026Q0965.pdf PDF

Similar open opportunities

Opportunity Agency Set-aside Responses due
648-22-104 Correct HVAC Deficiencies (P&V) Portland, Oregon 97239, United States · NAICS 238220 Veterans Integrated Service Network 20 Service-Disabled Veteran-Owned Small Business
J041--Chillers and Cooling Towers Repairs NAICS 238220 Veterans Integrated Service Network 21 No set-aside
Cooling Tower, Roofing, and Structural Construction District of Columbia 20024, United States · NAICS 236220 Bureau of Engraving and Printing Total Small Business
Amendment CTX Steam Humidifier Temple, Texas 76504, United States · NAICS 238220 Veterans Integrated Service Network 17 Service-Disabled Veteran-Owned Small Business
HVAC repair JV resource_jordan valley NAICS 238220 Oregon-Washington Region Total Small Business

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity