Buckley SFB Chiller Replacement

Closed Pre-Solicitation Posted

Solicitation number
BuckleySFBChillerReplacement
Agency
Responses due
Set-aside
Total Small Business

Opportunity facts

Place of performance
Aurora, Colorado 80011, United States

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of the Air Force, on behalf of the Base Civil Engineer Squadron at Buckley Space Force Base in Colorado, is conducting market research to identify qualified contractors capable of performing a complete chilled water system replacement, with responses due by July 22, 2026. This is a Total Small Business set-aside targeting socio-economic businesses including 8(a), SDVOSB, HUBZone, and WOSB firms.

The existing chiller system serving the facility's server room operates at half capacity with degraded serviceability and frequent downtime, creating mission risk in a 24/7 operations environment. The selected contractor must provide all labor, tools, equipment, and materials to replace the chiller, two Computer Room Air Handlers (CRAHs), and associated distribution piping while maintaining zero downtime to the active server room.

Technical requirements include professional engineering cooling load calculations per UFC 3-410-01, Sections 2-4 and 2-5.6, and standardization on Trane-series equipment per Department of the Air Force Class Justification. The chiller must fit within a concrete pad of 19'-11" L × 12'-8" W × 6'-8" H with a maximum operational weight of 12,000 pounds. CRAHs must navigate a 34" W × 82" H doorway pathway. The system integrates with existing 460V, 60 Hz, 3-Phase electrical power and the Energy Management Control System. Compliance is required with UFC 3-410-02 (DDC for HVAC), UFC 3-501-01, OSHA standards, and base Anti-Terrorism/Force Protection and Operational Security requirements. Qualified technicians must hold certifications specific to Trane chilled water systems and server room cooling operations. All personnel require National Crime Information Center checks and Level I Anti-Terrorism awareness training.

Interested parties must submit a Capability Statement by 3:00 PM Mountain Daylight Time on July 22, 2026, addressing company information, CAGE Code, Unique Entity ID, business size and socio-economic status under NAICS 238220, Trane distributor/installer authorization, relevant 24/7 operations experience, and ability to meet base access and security clearance requirements.

Notice text

PLEASE SEE ATTACHMENTS FOR ADDITIONAL INFORMATION REGARDING THIS REQUIREMENT

Notice Type: Sources Sought (MARKET RESEARCH PURPOSES ONLY)
Title: Secure Facility Chilled Water System Replacement – Federal Installation, CO
NAICS Code: 238220 – Plumbing, Heating, and Air-Conditioning Contractors
Product Service Code (PSC): N041 – Installation of Equipment: Refrigeration, Air Conditioning, and Air Circulating Equipment
Response Date: 22 July 2026

Description:

The Department of the Air Force (DAF), on behalf of the Base Civil Engineer Squadron (CES) at a Federal Installation in Colorado, is conducting market research to identify qualified, experienced, and interested business sources—specifically targeting small and socio-economic businesses (e.g., 8(a), SDVOSB, HUBZone, WOSB)—capable of performing a complete chilled water system replacement in a 24/7 operations facility.

Project Objective: The chilled water system serving the facility's server room currently suffers from degraded serviceability, sub-component failures, and frequent downtime. It is operating at half capacity, which risks the loss of critical cooling for 24/7 operations. The selected contractor must provide all tools, equipment, materials, and certified labor to perform a complete system replacement with zero downtime to the active server room.

Key Scope Items & Technical Specifications:

  1. Design & Sizing: Perform professional engineering cooling system design load calculations in accordance with UFC 3-410-01 (Sections 2-4 and 2-5.6) to determine final system capacity.

  2. Standardization Requirement: In accordance with the DAF Class Justification and Approval (J&A) for HVAC Chiller Replacement Standardization, the design of the new chiller system must be standardized on Trane-series equipment for this installation.

  3. Demolition: Safely decommission, recover refrigerant from, and remove the existing degraded chiller (Technical Systems Model: 30A0LM20-PT, Serial: 02-17-125822-001-001) and two existing Computer Room Air Handlers (CRAHs) (Data Aire Model: GFCU-04634, Serials: 2016-3226-A, 20163225-A).

  4. Equipment Installation: Procure, install, and commission:

    • One (1) new water chiller with an integrated air-cooled condenser (Trane-series).

    • Two (2) new chilled-water Computer Room Air Handlers (CRAHs) inside the secure server room.

  5. Temporary Cooling: Provide continuous, redundant temporary cooling to keep the secure server room strictly within operational temperature limits during the transition phase.

  6. Controls Integration: Fully integrate new controls into the base-wide Energy Management Control System (EMCS) in strict compliance with Base EMCS Standards (dated January 21, 2026) and UFC 3-410-02.

Logistical & Physical Constraints:

  • Chiller Pad Limits: The new chiller must fit the existing concrete pad (19’ - 11” L x 12’- 8” W x 6” to 8” H) and must not exceed the structural wet weight limit of 12,000 lbs. If the equipment footprint exceeds these limits, the pad must be extended.

  • Rigging & Delivery Clearances: CRAHs must be navigated through a restricted interior corridor with doorway clearances measuring exactly 34” W x 82” H.

  • Electrical: Must integrate with the existing 460V, 60 Hz, 3-Phase power supply and comply with UFC 3-501-01.

  • Security & Clearances: All personnel must pass NCIC background checks, comply with strict OPSEC guidelines, and complete AT Level I training prior to facility access.

Files

Similar open opportunities

Opportunity Agency Set-aside Responses due
Troubleshoot & Repair of Portable Chillers Service Requirement Jbsa Lackland, Texas 78236, United States · NAICS 238220 Air Education and Training Command Total Small Business
Brand Name or Equal - WaterFurnace Model: UBH015R for B3631 & B3635 - Turnkey Replacement Jbsa Ft Sam Houston, Texas 78234, United States · NAICS 238220 Air Education and Training Command No set-aside
EROS Removal and replacement of chilled and conden NAICS 238220 Office of Acquisitions and Grants Total Small Business
Y1DZ--PN: 636-27-101, Design-Build, Install Temporary Chillers {OM} FY27 NRM 36C263-27-AP-0586 VA Nebraska-Western Iowa Health Care System Omaha VA Medical Center Omaha, Nebraska 68105, United States · NAICS 238220 Veterans Integrated Service Network 23 Service-Disabled Veteran-Owned Small Business
500-Ton Trailer-Mounted Air-Cooled Chiller Orlando, Florida 32899, United States · NAICS 333415 Kennedy Space Center No set-aside

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity