6665--Indoor Air Quality Monitoring Equipment for the Manhattan & Brooklyn VAMC.
Closed Pre-Solicitation Posted
Not the latest version. See the latest solicitation from .
- Solicitation number
- 36C24223Q1014
- Agency
-
Veterans Integrated Service Network 2
Veterans Health Administration, Department of Veterans Affairs
- Responses due
- Set-aside
- No set-aside
Opportunity facts
- NAICS code
- 334519 Other Measuring and Controlling Device Manufacturing
- Place of performance
- Margaret Cochran Corbin VA Medical Center Manhattan Campus New York, New York 10010, United States
Notice details come from SAM.gov. Updated .
About this opportunity
The Department of Veterans Affairs is seeking qualified businesses to provide two complete sets of Indoor Air Quality (IAQ) monitoring equipment for deployment at the Manhattan VAMC and Brooklyn VAMC. The equipment must be capable of testing for various parameters related to IAQ, including total volatile organic compounds, carbon monoxide, formaldehyde, ethylene oxide, particulate matter, and differential pressure. The contract also includes an extended service contract for necessary annual equipment calibrations.
Products and Services to be provided:
- Two complete sets of Indoor Air Quality (IAQ) monitoring equipment.
- Equipment capable of testing for total volatile organic compounds, carbon monoxide, formaldehyde, ethylene oxide, particulate matter, and differential pressure.
- Provision of all necessary equipment for reliable and accurate testing.
- Extended service contract including necessary annual equipment calibrations.
- Two-year calibration service to ensure continued accuracy/reliability of the equipment.
Notice text
TITLE: 38-Sources Sought Notice
SOL: 36C24223Q1014
DUE: 07/28/2023 at 16:00 EST
NAICS: 334519
AGENCY: Department of Veterans Affairs, Margaret Cochran Corbin VA Medical Center, Manhattan Campus
423 East 23rd Street, New York, NY 10010. New York Harbor Healthcare System, Brooklyn VAMC, Engineering (138), 800 Poly Place, Brooklyn, NY 11209.
Email all responses only to: Jonatan.rondon@va.gov
DESCRIPTION: This Sources Sought Notice is for informational and planning purposes only and shall not be construed as a solicitation or as an obligation or commitment by the Government at this time. This notice is intended strictly for market research. The purpose of this Sources Sought notice is to determine interest and capability of potential qualifications of all businesses relative to the North American Industry Classification Code (NAICS) 334519. The Department of Veteran s Affairs is seeking all qualified business manufacturer or distributors of small business manufacturers to all the following specifications:
Requirement: The New York Harbor Safety Department & Engineering Service requires two (2) complete sets of IAQ (Indoor Air Quality) monitoring equipment. One set will be deployed at the Manhattan VAMC, and a second deployed at the Brooklyn VAMC. The Service will accept brand name or equal based on the salient characteristics and specifications described below:
At a minimum, the equipment must be capable of testing for the following parameters related to IAQ: total volatile organic compounds (TVOC); carbon monoxide; formaldehyde; ethylene oxide; particulate matter; and differential pressure.
The Safety Department currently does not have equipment to reliably test for these parameters. The contractor shall furnish all equipment necessary to provide reliable and accurate testing for the above parameters. An extended service contract including necessary annual equipment calibrations service is included in the scope of services required.
Sensors: The sensors used in the air quality monitoring equipment are critical. They shall be high-quality, accurate, and reliable.
Measurement Range: The indoor air quality monitoring equipment should have a broad measurement range to provide accurate real-time reading of the indoor air environment. Refer to specific numerical ranges stipulated in the table below.
Data Visualization and User Interface: The indoor air quality monitoring system should have a comprehensive visual display of the real-time measurement taken, digital graphical representation, and summary statistics of the environment.
Analytical Specifications: Two (2) full sets of each device are required. Each device must have a data-recording capable compatible with Microsoft Windows, so that data may be downloaded for technical reporting. Provide USB-compatible capability. Devices must be battery-powered for portable use in the field.
The device(s) must be capable of testing for the following parameters and must achieve the accuracy shown:
PARAMETER
MINIMUM ANALYTICAL DETECTION RANGE (in parts per million or ppm)
SENSITIVITY
Carbon Monoxide
0-400 ppm
10 ppm detection limit
Total VOCs
0 10 ppm
1 ppm detection limit
Formaldehyde
0 1 ppm
0.1 ppm detection limit
Ethylene Oxide
0-20 ppm
1 ppm detection limit
Particle Counter
Must quantify PM2.5 and PM10 standard analyses
0.3 micron threshold
Differential Pressure
N/A
0.01 inches of water
Air Velocity
N/A
5 feet per minute minimum
Temperature
60-150 degrees F
1 degree
Service/Calibration: The vendor s submittal shall include a two-year calibration service to ensure continued accuracy/reliability of the equipment. Provide expedited ship back calibration service (maximum 30-day turnaround). Provide documented calibration reports.
THIS IS NOT A SOLICITATION AND DOES NOT OBLIGATE THE GOVERNMENT TO ISSUE A SOLICITATION. Please be advised that the Government will not pay for any information submitted under this announcement. The applicable North American Classification System (NAICS) Code for this requirement is 334519 (Other Measuring and Controlling Device Manufacturing).
Response Email should contain the following information: Name of firm, Socio-Economic category of the firm, complete address, phone & fax number of contacts.
Files
| File | Type | Posted |
|---|---|---|
| 36C24223Q1014.docx | DOCX document |
Notice history
| Notice | Type | Posted |
|---|---|---|
| 6665--Direct Sense Indoor Air Quality Core Monitoring Equipment for the New York Harbor Healthcare. (Brand name or equal) | Solicitation | |
| 6665--Indoor Air Quality Monitoring Equipment for the Margaret Cochran Corbin VAMC (Manhattan Campus) & Brooklyn Campus. | Special Notice | |
| This notice | Pre-Solicitation |
Similar open opportunities
| Opportunity | Agency | Set-aside | Responses due |
|---|---|---|---|
| 6835--VISN 2 Prosthetics Downstate Home Oxygen Services | Veterans Integrated Service Network 2 | No set-aside | |
| 6550--Cepheid GeneXpert Testing Supplies | Veterans Integrated Service Network 5 | No set-aside |
On GovTribe
Work this opportunity
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity