619-20-1-5243-0008 Emergency Generator PM & MAINTENANCE (VA-19-00054180)
Closed Solicitation Posted
This opportunity was awarded. See the award notice from .
- Solicitation number
- 36C24720Q0100
- Agency
-
Veterans Integrated Service Network 7
Veterans Health Administration, Department of Veterans Affairs
- Responses due
- Set-aside
- No set-aside
Opportunity facts
Notice details come from SAM.gov. Updated .
About this opportunity
This solicitation seeks preventative maintenance, inspection, and testing services for fifteen diesel generators located at two Department of Veterans Affairs medical campuses in Alabama. The contractor shall provide annual inspections, preventative maintenance in accordance with NFPA standards, and load bank testing at specified levels totaling four continuous hours. The contractor must have five years of generator service experience. Questions are due by December 23, 2019 and proposals are due January 7, 2020. The contract term is one base year with two one-year options.
There is no set-aside designation. The NAICS code is 238210 and PSC code J019. The generators are located at facilities in Tuskegee and Montgomery, Alabama. The work includes annual maintenance for fifteen generators over the base one year contract and two optional one-year periods. Bidders were required to attend a site visit on December 16, 2019 to review the equipment and performance requirements on site.
Notice text
PERFORMANCE BASED WORK STATEMENT
DIESEL GENERATORS
Inspections, Preventive Maintenance, Testing
Central Alabama Veterans Healthcare System (East and West Campuses)
SCOPE OF WORK:
The contractor shall provide all labor, equipment, tools, materials, supervision, test equipment, travel and transportation necessary to perform annual preventive maintenance and inspections of the diesel generators along with checking the switchgears for each of the 15 listed generators in accordance with current NFPA 99 and NFPA 100 testing and maintenance activities.
Inspections shall include, but not limited to, assessing the prime mover s exhaust gas temperature against the minimum temperature recommended by the manufacturer (this information must be on the report).
Annually, the contractor shall provide a minimum of four (4) continuous hours load bank with at least 30% of the nameplate rating to perform test. During the test, the dummy or load bank must be arranged so that it could be disconnected if power was lost to each facility and the generator was needed for Medical Center s use.
This annual inspection (of the generators, etc.) must be accomplished during the month of August.
PERIOD OF PERFORMANCE:
This contract is for a base year with (2) one-year option.
The days and hours of operation is Monday thru Friday 8:00 a.m. to 4:30 p.m. excluding Federal holidays.
III. EQUIPMENT DESCRIPTION:
Diesel Generators with manufacturer, model, location and size located at CAVHCS (East Campus), 2400 Hospital Road Tuskegee, AL and CAVHCS (West Campus), 215 Perry Hill Rd, Montgomery, AL.
WEST CAMPUS
MANUFACTURER
MODEL
LOCATION
KW
VOLTAGE
OUTPUT
Kohler
125RE02JB
Building 14
125 kw
208 V
Kohler
80RE02JF
Building 4
81 kw
277 V
Caterpillar
2A300287
Building 1 Chiller Plant
800 kw
480 V
Caterpillar 1
572RSL2037A-P00 W
Building 1
440 kw
277 V
Caterpillar 2
572RSL2037A-P00 W
Building 1
440 kw
277 V
EAST CAMPUS
MANUFACTURER
MODEL
LOCATION
KW
VOLTAGE
OUTPUT
Kohler
10478911
Building 5
600
750
Perkins 2 EA
2206D-E13TAG3
Building 121
400
500
Cummins
5AT1224552C1
Building 12
350
438
Kohler
80RZI81
Building 15
80kva
Cummins
Kohler
SC534ES
350R0ZD71
Building 120
450
350
563
438
Kohler
600R0ZD
Building 129
600
750
Cummins
500FDR5051FF-W
Building 124
300
375
Kohler
150REOZ5B
Building 90
160
200
Cummins
500FDR5051FF-W
Building 123
300
375
Hi power portable
Building 13
30kva
Hi power portable
Building 13
30kva
Hi power portable
Building 13
30kva
IV. PERFORMANCE REQUIREMENTS:
Diesel powered emergency generators shall be exercised for FOUR (4) continuous hours
annually with supplemental loads of:
30 percent of nameplate rating for sixty (60) minutes, followed by;
50 percent of nameplate rating for sixty (60) minutes, followed by;
75 percent of nameplate rating for 120 minutes for a total of four continuous hours.
The contractor s inspection shall include the following:
Check exciter brushes
Check for ground fault current
Check all safety alarms
Check all shutdown systems
Check operation of emersion heater
Observe operation of governor during start-up, accepting load and shutdown
Check operation of remote safety alarms in Boiler Plant.
The contractor s mechanical personnel shall:
Check over-speed shutdown
Check cylinder head mechanism and make any necessary adjustments
Drain, flush and refill the generator cooling systems every two years, beginning December 2019.
Air filters need to be changed out every 3 years
Oil and fuel filters need to be changed out once a year
Check operation of fuel transfer pumps and day tank systems
Take engine oil sample and have analysis performed. Provide copy of the report to the facility.
The contractor shall make all adjustments and repairs where parts are not required. The contractor shall provide a list of parts required by part number, manufacturer and a source where parts can be purchased.
The contractor shall provide a written report to the Maintenance Supervisor (COR) within 30 days after completion of the inspection. The report will contain information as to the condition, operation, recommendations for corrective action; and analysis report of engine oil sample. Written reporting shall contain but not limited to the following headings:
Lubricating System
Cooling Systems and Hoses
Air Cooled Engines
Fuel System
Air Intake System
Exhaust System
Ignition System (Gas/Gasoline) also provide fuel analysis on each generator.
Engine Electrical System
Engine Generator System
Generator Operation
Transfer Switch Operation
Generator Inspection
Generator Room/Enclosure
Assessment of Evidence of Wet Stacking
The contractor shall provide the Contracting Officer s Representative (COR) notification five (5) working days prior to coming onto the site for inspection.
V. CONTRACTOR QUALIFICATIONS
Contractor shall have a minimum five (5) years of experience servicing generators for various types of facilities.
Contractor shall have a minimum five (5) years of experience servicing the type of generators indicated in section III Equipment Description above.
Contractor shall have Liability Insurance.
VI. SECURITY REQUIREMENTS:
Contractor must report to Building 14, Utilities and Maintenance Supervisor to get access badge starting at 8:00 a.m. and may be accompanied by a VA employee while on station at the COR s discretion. Contractor must report to Building 13, Utilities Supervisor.
Vendors/contractors shall wear VA issued ID badge at all times while on station.
Taking photographs and video is strictly prohibited while on station and on all Federal VA premises.
SITE VISIT: Bidders shall visit the site to confirm location, dimension, and condition of the required for the fulfillment of this contract. The site visit shall be for the purpose of observing first hand any conditions relevant to the fulfillment of this contract. No consideration will be given to claims based on a lack of knowledge of the existing conditions, except where contract documents make definite provisions for adjustment in cost or extension due to existing conditions not readily foreseeable. One (1) site visit will be held on December 16, 2019 at 10:00 am CST. The site visit address is:
CAVHCS
2400 Hospital Road
Building 68, Room 217
Tuskegee, AL 36083
There are two locations (Tuskegee and Montgomery) for the site visit, the government will not provide transportation. The meeting will start at the above address mention in Tuskegee AL.
Questions and Answers: All questions and answers must be in writing. Email all questions to earnest.ellison@va.gov and courtesy copy Yolanda.Bickham@va.gov. Do not contact the Contracting Officer Representative (COR) this will delay a response to RFIs. RFI time period ends 12/23/2019 at 9:30 pm cst.
Incidental Parts and Repairs
The contractor shall provide all labor, equipment, tools material, supervision, test equipment, travel and transportation necessary to perform repairs of the Diesel Generators located in Montgomery and Tuskegee Al, all modifications must be approved by the Contracting Officer prior executing repairs. The contractor shall submit one quote for the repairs to the COR and Contracting Officer.
Files
| File | Type | Posted |
|---|---|---|
| 36C24720Q0100-0004000.docx | DOCX document | |
| 36C24720Q0100-0004001.pdf | ||
| 36C24720Q0100-0003003.docx | DOCX document | |
| 36C24720Q0100-0002000.docx | DOCX document | |
| 36C24720Q0100-0001012.pdf | ||
| 36C24720Q0100-0001011.pdf | ||
| 36C24720Q0100-0001010.docx | DOCX document | |
| 36C24720Q0100-006.pdf | ||
| 36C24720Q0100-005.docx | DOCX document |
Notice history
| Notice | Type | Posted |
|---|---|---|
| J061-- Emergency Generator PM & MAINTENANCE | Award Notice | |
| This notice | Solicitation | |