This performance work statement outlines requirements for preventative maintenance and testing of diesel generators at two Veterans Affairs medical campuses. Fifteen generators across the two sites require annual inspections, load testing for four continuous hours at varying levels, and mechanical service including filter changes, fluid flushes, and analysis reporting. The contractor must be experienced servicing generators and the specified models. The base period of performance is one year with two optional one-year extensions. Site visits are required prior to bidding. Questions must be submitted by December 23rd for the opportunity closing in January 2020. Repairs will be quoted separately as needed.

36C24720Q0100 0001 B2.pdf

View the file

Other files

File Type Posted
36C24720Q0100-0004001.pdf PDF
36C24720Q0100-0004000.docx DOCX document
36C24720Q0100-0003003.docx DOCX document
36C24720Q0100-0002000.docx DOCX document
36C24720Q0100-0001010.docx DOCX document
36C24720Q0100-0001012.pdf PDF
36C24720Q0100-006.pdf PDF
36C24720Q0100-005.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

36C24720Q0100

PERFORMANCE BASED WORK STATEMENT

DIESEL GENERATORS

Inspections, Preventive Maintenance, Testing

Central Alabama Veterans Healthcare System (East and West Campuses)

I. SCOPE OF WORK:

a. The contractor shall provide all labor, equipment, tools, materials, supervision, test equipment, travel and transportation necessary to perform annual preventive maintenance and inspections of the diesel generators along with checking the switchgears for each of the 15 listed generators in accordance with current NFPA 99 and NFPA 100 testing and maintenance activities.

b. Inspections shall include, but not limited to, assessing the prime mover’s exhaust gas temperature against the minimum temperature recommended by the manufacturer (this information must be on the report).

c. Annually, the contractor shall provide a minimum of four (4) continuous hours load bank with at least 30% of the nameplate rating to perform test. During the test, the dummy or load bank must be arranged so that it could be disconnected if power was lost to each facility and the generator was needed for Medical Center’s use.

d. This annual inspection (of the generators, etc.) must be accomplished during the month of August.

II. PERIOD OF PERFORMANCE:

a. This contract is for a base year with (2) one-year option.

b. The days and hours of operation is Monday thru Friday 8:00 a.m. to 4:30 p.m. excluding Federal holidays.

III. EQUIPMENT DESCRIPTION:

Diesel Generators with manufacturer, model, location and size located at CAVHCS (East Campus), 2400 Hospital Road Tuskegee, AL and CAVHCS (West Campus), 215 Perry Hill Rd, Montgomery, AL.

WEST CAMPUS

MANUFACTURER MODEL LOCATION KW

VOLTAGE

OUTPUT

Kohler 125RE02JB Building 14 125 kw 208 V

Kohler 80RE02JF Building 4 81 kw 277 V

Caterpillar 2A300287 Building 1 Chiller Plant

800 kw 480 V

Caterpillar 1 572RSL2037A-P00 W Building 1 440 kw 277 V

Caterpillar 2 572RSL2037A-P00 W Building 1 440 kw 277 V

EAST CAMPUS

MANUFACTURER MODEL LOCATION KW

VOLTAGE

OUTPUT

Kohler 10478911 Building 5 600 750

Perkins 2 EA 2206D-E13TAG3 Building 121 400 500

Cummins 5AT1224552C1 Building 12 350 438

Kohler 80RZI81 Building 15 80kva

Cummins SC534ES Building 120 450 563

Kohler 350R0ZD71 350 438

Kohler 600R0ZD Building 129 600 750

Cummins 500FDR5051FF-W Building 124 300 375

Kohler 150REOZ5B Building 90 160 200

Cummins 500FDR5051FF-W Building 123 300 375

Hi power portable Building 13 30kva

Hi power portable Building 13 30kva

Hi power portable Building 13 30kva

IV. PERFORMANCE REQUIREMENTS:

a. Diesel powered emergency generators shall be exercised for FOUR (4) continuous hours annually with supplemental loads of:

30 percent of nameplate rating for sixty (60) minutes, followed by;

50 percent of nameplate rating for sixty (60) minutes, followed by;

75 percent of nameplate rating for 120 minutes for a total of four continuous hours.

b. The contractor’s inspection shall include the following:

Check exciter brushes

Check for ground fault current

Check all safety alarms

Check all shutdown systems

Check operation of emersion heater

Observe operation of governor during start-up, accepting load and shutdown

Check operation of remote safety alarms in Boiler Plant.

c. The contractor’s mechanical personnel shall:

Check over-speed shutdown

Check cylinder head mechanism and make any necessary adjustments

Drain, flush and refill the generator cooling systems every two years, beginning December 2019.

Air filters need to be changed out every 3 years

Oil and fuel filters need to be changed out once a year

Check operation of fuel transfer pumps and day tank systems

Take engine oil sample and have analysis performed. Provide copy of the report to the facility.

d. The contractor shall make all adjustments and repairs where parts are not required. The contractor shall provide a list of parts required by part number, manufacturer and a source where parts can be purchased.

e. The contractor shall provide a written report to the Maintenance Supervisor (COR) within 30 days after completion of the inspection. The report will contain information as to the condition, operation, recommendations for corrective action; and analysis report of engine oil sample. Written reporting shall contain but not limited to the following headings:

Lubricating System

Cooling Systems and Hoses

Air Cooled Engines

Fuel System

Air Intake System

Exhaust System

Ignition System (Gas/Gasoline) also provide fuel analysis on each generator.

Engine Electrical System

Engine Generator System

Generator Operation

Transfer Switch Operation

Generator Inspection

Generator Room/Enclosure

Assessment of Evidence of Wet Stacking

f. The contractor shall provide the Contracting Officer’s Representative (COR) notification five

(5) working days prior to coming onto the site for inspection.

V. CONTRACTOR QUALIFICATIONS

a. Contractor shall have a minimum five (5) years of experience servicing generators for various types of facilities.

b. Contractor shall have a minimum five (5) years of experience servicing the type of generators indicated in section III Equipment Description above.

c. Contractor shall have Liability Insurance.

VI. SECURITY REQUIREMENTS:

a. Contractor must report to Building 14, Utilities and Maintenance Supervisor to get access badge starting at 8:00 a.m. and may be accompanied by a VA employee while on station at the COR’s discretion. Contractor must report to Building 13, Utilities Supervisor.

b. Vendors/contractors shall wear VA issued ID badge at all times while on station.

c. Taking photographs and video is strictly prohibited while on station and on all Federal VA premises.

SITE VISIT: Bidders shall visit the site to confirm location, dimension, and condition of the required for the fulfillment of this contract. The site visit shall be for the purpose of observing first hand any conditions relevant to the fulfillment of this contract. No consideration will be given to claims based on a lack of knowledge of the existing conditions, except where contract documents make definite provisions for adjustment in cost or extension due to existing conditions not readily foreseeable. One (1) site visit will be held on December 16, 2019 at 10:00 am CST. The site visit address is:

CAVHCS

2400 Hospital Road

Building 68, Room 217

Tuskegee, AL 36083

There are two locations (Tuskegee and Montgomery) for the site visit, the government will not provide transportation. The meeting will start at the above address mention in Tuskegee AL.

Questions and Answers: All questions and answers must be in writing. Email all questions to earnest.ellison@va.gov and courtesy copy Yolanda.Bickham@va.gov. Do not contact the Contracting Officer Representative (COR) this will delay a response to RFIs. RFI time period ends 12/23/2019 at 9:30 pm cst.

Incidental Parts and Repairs

The contractor shall provide all labor, equipment, tools material, supervision, test equipment, travel and transportation necessary to perform repairs of the Diesel Generators located in Montgomery and Tuskegee Al, all modifications must be approved by the Contracting Officer prior executing repairs. The contractor shall submit one quote for the repairs to the COR and Contracting Officer.

B.2 PRICE/COST SCHEDULE

ITEM INFORMATION

ITEM

NUMBER

DESCRIPTION OF

SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT

12.00 MO __________________ __________________

PERFORM MAINTENANCE ON FACILITY EMERGENCY

GENERATORS AT 215 PERRY HILL ROAD,

MONTGOMERY, AL 36109. See SOW section III, Equipment Description, West Campus.

Contract Period: Base POP Begin: 01-06-2020 POP End: 01-05-2021

GENERATORS AT 2400 HOSPITAL ROAD, TUSKEGEE,

AL 36109. See SOW section III, Equipment Description, East Campus.

Contract Period: Base

The contractor shall provide all labor, equipment, tools material, supervision, test equipment, travel and transportation necessary to perform repairs of the Diesel Generators located in Montgomery and Tuskegee Al, all modifications must be approved by the Contracting Officer prior executing repairs. The contractor shall submit one quote for the repairs to the COR and Contracting Officer.

Contract Period: Base Do not provide pricing, pricing will be submitted for each repair. There is no maintenance allowance

GENERATORS AT 215 PERRY HILL ROAD,

MONTGOMERY AL 36109. See SOW section III, Equipment Description, West Campus.

Contract Period: Option 1 POP Begin: 01-06-2021 POP End: 01-05-2022

GENERATORS AT 2400 HOSPITAL ROAD, TUSKEGEE,

AL 36083. See SOW section III, Equipment Description, East Campus.

Contract Period: Option 1 material, supervision, test equipment, travel and transportation necessary to perform repairs of the Diesel Generators located in Montgomery and Tuskegee Al, all modifications must be approved by the Contracting Officer prior executing repairs. The contractor shall submit one quote for the repairs to the COR and Contracting Officer.

Contract Period: Option 1, Do not provide pricing, pricing will be submitted for each repair. There is no maintenance allowance

GENERATORS AT 215 PERRY HILL ROAD,

MONTGOMERY AL 36109. See SOW section III, Equipment Description, West Campus.

Contract Period: Option 2 POP Begin: 01-06-2022 POP End: 01-05-2023

GENERATORS AT 2400 HOSPITAL ROAD, TUSKEGEE,

AL 36083. See SOW section III, Equipment Description, East Campus.

Contract Period: Option 2 material, supervision, test equipment, travel and transportation necessary to perform repairs of the Diesel Generators located in Montgomery and Tuskegee Al, all modifications must be approved by the Contracting Officer prior executing repairs. The contractor shall submit one quote for the repairs to the COR and Contracting Officer.

Contract Period: Option 2, Do not provide pricing, pricing will be submitted for each repair. There is no maintenance allowance

GRAND TOTAL __________________