The Department of Veterans Affairs Veterans Health Administration (VA) is seeking a contractor to upgrade pressure reducing valves (PRVs) at the Stratton VA Medical Center in Albany, New York. The project involves providing and replacing 4 PRVs located in room S-21 of building 2's subbasement, with a specific requirement to replace all cast iron fittings with carbon steel components. Contractors must be licensed and insured to complete steam pipe work, conforming to all ASME codes and standards, and VHA directives. A site visit is recommended prior to submitting a price proposal, with the response deadline set for May 5, 2025. The technical evaluation will likely focus on the contractor's ability to meet detailed equipment specifications, including providing Spence main valves and pilots, carbon steel components, and various gate valves, strainers, and associated piping.

There is no specific set-aside designation for this contract opportunity. The work must be performed with minimal disruption to hospital operations, with steam shutdown work restricted to nights and weekends, and preparatory work allowed during normal business hours. The project falls under NAICS category 332919 (Other Metal Valve and Pipe Fitting Manufacturing) and Product Service Code 4810 (Powered Valves). While no specific budget range is mentioned, the comprehensive list of required components suggests a significant procurement investment. The period of performance requires careful coordination with VA medical center administration, with all shutdowns to be coordinated with the Contracting Officer's Representative (COR) and Facility Management Services (FMS) administration. The contractor will need to provide experienced steam pipefitters and ensure all work is completed as quickly and safely as possible.

Notice text

Statement of Work

S-21 Pressure Reducing Valve (PRV) Upgrade.

Albany Stratton VAMC

Introduction Stratton VAMC s mission is to provide world class healthcare for veterans in the capital region and upstate New York.

Background /Objective The Stratton VA Medical Center 113 Holland Ave, Albany NY is currently seeking the purchase and installation of 2 new cast steel PRVs. A recent change in the national Boiler Plant operations requirement mandates that all cast iron fittings will be replaced with cast steel as they reach the end of their useful life.

Place of Performance Building 2 subbasement room S-21.

Period of Performance All work requiring a steam shutdown to the hospital must be done on nights/weekends and shall be as done as quick as safely possible. All preparatory work may be done during normal business hours 7 AM -4 PM Monday thru Friday.

Scope -

Contractor will provide and replace 4 PRVs located in room S-21 in the subbasement of building 2.

Specific Tasks

parts

Contractor will provide: Spence main valves and pilots. All valves and flanges shall be carbon steel.

Three 4-inch ASNE flanged 150 Y strainers carbon Steel with 1/8-inch perforated screen, 1-1/2 blow down valve connection.

three 1 ½ inch cast steel ball valves for blow down.

One ¾ cast steel ball valve for blow down.

Two 3-inch ASNE 150 25 main prv valve cast steel.

2 25p pressure pilot cast steel with yellow spring 3-30 psi

2 pressure pilot cast steel 60 psi spring

Four 4-inch pressure gauges 0-100 psi with two isolation valves and ring syphon s

Four (4) 4-inch carbon steel gate valves with 4-150 Flexatalic gaskets.

Two 3 to 4inch flanged spools.

three 4-inch flanged spools. Length do be determined. During installation.

One 2.5 inch flanged spool Length do be determined. During installation.

All necessary piping to connect downstream piping to pilot assemblies, and all necessary blow down piping.

One 2.5-inch ASNE flanged 150 Y strainers carbon Steel with 1/8-inch perforated screen, ¾ npt blow down valve connection.

One 2.5 inch ASNE 150 25 carbon steel main valve 2.5 150 Flexatalic gaskets

One 4 inch 150 25 main prv valve carbon steel.

One 4 inch carbon steel gate valve with 4-150 Flexatalic gaskets.

One 2.5 inch carbon steel gate valve 2.5 150 Flexatalic gaskets.

One 8 inch carbon steel gate valve

One 10 inch carbon steel gate valve

All associated gaskets need for installation.

All mounting hardware in accordance with ASME standards. All fasteners shall Be ASTM Grade A193

labor

Contractor shall remove upper and lower old inlet red toped valves. and shall replace with steel gate valves. and upper and lower discharge gate valves on the 10 psi line

Contractor shall replace both upper and lower spool s length to be determined based on the piping. On the 10 psi line

Contractor will remove and replace upper and lower strainers and main prv valves with steel components. On the 10 psi line

Contractor shall remove upper and lower old inlet valves. and shall replace with steel gate valves. and upper and lower discharge gate valves on the 60 psi line

Contractor shall replace both upper and lower spool s length to be determined based on the piping. On the 60 psi line

Contractor will remove and replace upper and lower strainers and main prv valves with steel components. On the 60 psi line

Contractor will replace and re pipe control pilot assemblies

Contractor will be licensed and insured to complete steam pipe work. all work must conform to All ASME codes and standards, along with all VHA directives pertaining to pipe work.

Contractor will provide personal experienced in steam pipefitting.

Special Instructions - All shutdowns shall be coordinated with the COR. and FMS administration.

Contractor Information:

The Contractor, at no additional cost to the Government, shall obtain all licenses, permits, and insurance required to perform the work in this Contract.

It is advised and recommended that the Contractor shall perform a Field Site Visit in the Hospital to determine the exact number(s) and type (s) of associated equipment and/or devices (s) before the submission of price proposal.

In the conclusion of the site visit the contractor shall provide a detailed list of all associate equipment(s) and /or device (s) to the VHA. The list shall be used as a reference only and shall not to be considered as a complete list of equipment.

Non-Compliance-The Contracting Officer or his/her designee will notify the contractor of any noncompliance with the foregoing provisions and the action to be taken. The Contractor shall, after receipt of such notice, immediately correct the conditions to which attention has been directed. Such notice, when served on the Contractor or his/her representative at the site of the work, shall be deemed sufficient for the purpose aforesaid. If the Contractor fails or refuses to comply promptly, the Contracting Officer may issue an order stopping all and any part of the work and hold the Contractor in default.

Inspection-

Upon completion of the repair service, the COR/POC will perform the inspection in the presence of the contractor personnel, prior to the contractor personnel leaving the facility. This inspection will ensure that all equipment is returned to full functioning condition No invoices will be processed for payment prior to the completion of POC inspection.

Other Related Services (Not Included in the Scope of Work)-

Any services not expressly stated in this statement of work are not authorized. Services such as inspection, Original Equipment Manufacturer (OEM) required maintenance, or other maintenance and repair vital to the continued functioning of the systems may be added only after written modification from the contracting officer, unless they are inclusive to the requested services. No other person, including the COR or any other VA personnel are authorized to request additional work be performed by the contractor. Any additional services performed that are not authorized by the contracting officer will be considered inclusive.

Files

File Type Posted
36C24225Q0580.docx DOCX document

Notice history

Notice Type Posted
4810--36C242-25-AP-2499 | 528-25-2-8893-0318 PRV replacement S-21 Award Award Notice
4810--36C242-25-AP-2499 | 528-25-2-8893-0318 PRV replacement S-21 Latest solicitation Solicitation
This notice Original Pre-Solicitation

Similar open opportunities

Opportunity Agency Set-aside Responses due
J048--NEW - Energy Center Steam Header& Boilers valves, gaskets, and vent replacement Department Of Veterans Affairs VA North Texas Health Care System Dallas TX 75216 · NAICS 238220 Veterans Integrated Service Network 17 Service-Disabled Veteran-Owned Small Business
Y1DZ--replace chilled water pump at the boiler plant Department of Veterans Affairs Network Contracting Office 2 Bronx, New York 10468, United States · NAICS 236220 Veterans Integrated Service Network 2 Service-Disabled Veteran-Owned Small Business
N048-- B41 Isolation Valve Installation Department of Veterans Affairs Veterans Health Administration North Little Rock AR 72114 · NAICS 238220 Veterans Integrated Service Network 16 Service-Disabled Veteran-Owned Small Business
H245--FY27 - VH WNY Backflow Prevention Testing Services VA Western New York Healthcare System Buffalo VA Medical Center Buffalo, New York 14215, United States · NAICS 238220 Veterans Integrated Service Network 2 No set-aside
Y1DA--561-26-103 Upgrade Electrical and Plumbing in Building 18B East Orange, New Jersey 07018, United States · NAICS 236220 Veterans Integrated Service Network 2 Service-Disabled Veteran-Owned Small Business

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity

GovTribe for Federal Contractors