4520--Lyons VAMC Water Heater Replacement Brand Specific to ensure hookups are compatible no additional piping being considered
Closed Pre-Solicitation Posted
This opportunity was awarded. See the award notice from , or the latest solicitation from .
- Solicitation number
- 36C24226Q0588
- Agency
-
Veterans Integrated Service Network 2
Veterans Health Administration, Department of Veterans Affairs
- Responses due
- Set-aside
- No set-aside
Opportunity facts
- NAICS code
- 333414 Heating Equipment (except Warm Air Furnaces) Manufacturing
- PSC
- 4520 Space And Water Heating Equipment
- Place of performance
- Lyons Vamc 151 Knollcroft Road Lyons, New Jersey 07939, United States
- Points of contact
Notice details come from SAM.gov. Updated .
About this opportunity
The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 2 intends to solicit two Patterson-Kelley semi-instantaneous water heaters for Lyons Veterans Affairs Medical Center (Lyons VAMC), with responses due May 11, 2026. The procurement is brand-specific to ensure compatible hookups without additional piping modification.
The first unit is a Model PK-08D rated to deliver 27 gallons per minute of domestic hot water from 40–120F when supplied with 25 psig inlet steam. The second is a Model PK-10D rated to deliver 65 gallons per minute from 40–140F when supplied with 40 psig inlet steam. Both must feature solid copper nickel pressure vessels rated for 150 psi ASME working pressure, 90/10 double wall copper nickel tube bundles rated for 150 psi and 210F test pressure, all-bronze 1/6HP circulator pumps with NYC trim package (115v/1ph/60Hz), Spence pilot-operated self-contained steam control valves, ASME temperature and pressure relief valves, float and thermostatic condensate steam traps, double solenoid high-temperature limit systems with pre-wired control boxes, vertical stands permitting heating section removal without disconnecting domestic water lines, vacuum breakers, dial thermometers, and bundle steam pressure gauges. Both units must include operation and maintenance manuals in electronic form and factory-authorized startup and training.
Place of performance is Lyons VAMC, 151 Knollcroft Road, Lyons, New Jersey 07939-5001. The contracting officer is Corey Swinton (Corey.Swinton@va.gov). Solicitation number is 36C24226Q0588. No set-aside applies.
Notice text
Qty 1 Patterson-Kelley Model PK-08D Semi-Instantaneous Water Heater rated to
provide 27 GPM of Domestic Hot Water from 40-120F when supplied with 25 psig Inlet
Steam and 5 psig in the Coil @ 1122#/hr. Heater to be furnished with the following
features and controls to meet the specified demand:
- Solid Copper Nickel Pressure Vessel rated for 150 psi ASME working
pressure.
- Factory Insulation.
- 90/10 Double Wall Copper Nickel Tube Bundle rated for 150 psi ASME
working pressure and 210F test pressure.
- All bronze circulator pump, 1/6HP, NYC Trim Package, 115v/1ph/60Hz,
with isolation valves, ball and check valves, and venturi tees.
- 1 ½ Spence Pilot Operated, Self-Contained Steam Control Valve.
- 1 ½ Wye Strainer.
- ¾ ASME Temperature & Pressure Relief Valve at 150 psi.
- ¾ ASME Pressure Only Relief Valve (Shipped Loose).
- 1 ½ Float & Thermostatic Condensate Steam Trap & Strainer (Shipped
Loose).
- ½ Auxiliary Drip Tap (Shipped Loose).
- ¾ Drain Valve Factory Installed.
- Double Solenoid High Temperature Limit System with pre-wired control
box.
- Vertical Stand suitable for removal of heating section without
disconnection of domestic water lines.
- ¾ Vacuum Breaker Factory Installed.
- 3 ½ Dial Thermometer & Bundle Steam Pressure Gauge.
- Operation & Maintenance Manuals in electronic form.
- Factory Authorized Start-Up & Training
Tags: 276458 (WH-2)
Qty 1 Patterson-Kelley Model PK-10D Semi-Instantaneous Water Heater rated to
provide 65 GPM of Domestic Hot Water from 40-140F when supplied with 40 psig Inlet
Steam and 25 psig in the Coil @ 3469#/hr. Heater to be furnished with the following
features and controls to meet the specified demand:
- Solid Copper Nickel Pressure Vessel rated for 150 psi ASME working
pressure.
- Factory Insulation.
- 90/10 Double Wall Copper Nickel Tube Bundle rated for 150 psi ASME
working pressure and 210F test pressure.
- All bronze circulator pump, 1/6HP, NYC Trim Package, 115v/1ph/60Hz,
with isolation valves, ball and check valves, and venturi tees.
- 2 ½ Spence Pilot Operated, Self-Contained Steam Control Valve.
- 2 ½ Wye Strainer.
- 1 ASME Temperature & Pressure Relief Valve at 150 psi.
- 1 ½ ASME Pressure Only Relief Valve (Shipped Loose).
- 1 ½ Float & Thermostatic Condensate Steam Trap & Strainer (Shipped
Loose).
- ½ Auxiliary Drip Tap (Shipped Loose).
- ¾ Drain Valve Factory Installed.
- Double Solenoid High Temperature Limit System with pre-wired control
box.
- Vertical Stand suitable for removal of heating section without
disconnection of domestic water lines.
- ¾ Vacuum Breaker Factory Installed.
- 3 ½ Dial Thermometer & Bundle Steam Pressure Gauge
.
Files
| File | Type | Posted |
|---|---|---|
| 36C24226Q0588.docx | DOCX document |
Notice history
| Notice | Type | Posted |
|---|---|---|
| 4520--Equipment - Water Heaters | Award Notice | |
| 4520--Lyons VAMC Water Heater Replacement Brand Specific to ensure hookups are compatible no additional piping being considered | Solicitation | |
| This notice | Pre-Solicitation |
Similar open opportunities
| Opportunity | Agency | Set-aside | Responses due |
|---|---|---|---|
| Heater, water, electric | Construction and Equipment | No set-aside | |
| Heater, water, gas | Construction and Equipment | No set-aside | |
| J045--FY27 Boilers Maintenance & Testing | Veterans Integrated Service Network 8 | Service-Disabled Veteran-Owned Small Business | |
| Heater, water, liquid F | Construction and Equipment | Total Small Business | |
| Heater, water, electric | Construction and Equipment | No set-aside |
On GovTribe
Work this opportunity
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity