YWCA Hartford Region - Specs - Roof.pdf

PDF 23 MB Posted

Attached to
Roof Replacement
Solicitation number
37653
Issued by
Hartford County, Connecticut

About this file

This is a technical specification document and bid invitation for a roof replacement project at YWCA Hartford Region, located at 135 Broad Street in Hartford, Connecticut, prepared by Northeast Collaborative Architects. The project consists of the installation of a new membrane roof system and replacement of skylights on the existing flat roof of the two-story office building, with the eight-story residential tower excluded from the scope of work. The specification document, dated April 8, 2026, establishes comprehensive requirements across multiple divisions including procurement and contracting requirements, general requirements, existing conditions, concrete, wood and composites, thermal and moisture protection, openings, and related construction elements. The work requires furnishing all labor, materials, and equipment necessary to complete the roofing system installation. Supporting documentation includes a Lead-Based Paint Inspection and Risk Assessment Report dated December 20, 2024, which was conducted by Eagle Environmental, Inc. within areas of the building associated with a proposed early childcare program; this inspection tested 235 painted surfaces and identified only three actionable readings on metal I-beam supports in a mechanical room scheduled for removal, with no toxic lead-based paint found in the proposed childcare areas.

The specifications establish detailed requirements for bid submission including a Bid Form, Bid Bond, Contractor Qualification Statement, Non-Collusion Certification, and Nondiscrimination Certification. Performance and Payment Bonds are required, along with compliance with wage rate requirements and Minority Business Enterprise provisions. The document incorporates AIA standard contract documents including General Conditions of the Contract for Construction (A201-2007) and related forms. Unit price procedures, substitution procedures, and contract modification procedures are detailed within the specifications. Submittal procedures, quality requirements, payment procedures, and project closeout requirements are established, including photographic documentation and project record documents. The specifications address temporary facilities and controls, product requirements, and execution standards. Additional compliance requirements include CHRO Good Faith Efforts requirements and prevailing wage rate schedules applicable to the Connecticut jurisdiction.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

TECHNICAL SPECIFICATIONS

YWCA HARTFORD REGION

Roof Recovery

135 Broad St.

Hartford, CT. 06105

CD Specifications 4/8/2026

ARCHITECT

Northeast Collaborative Architects 11 Silver St. #116

Middletown, CT 06457 NCA Project #24011

SECTION 000110

TABLE OF CONTENTS

APRIL 8, 2026 YWCA HARTFORD REGION ROOF

PROJECT MANUAL: SPECIFICATIONS

Section 000100 Cover

Section 000110 Table of Contents Section 000115 Drawing Sheet list

DIVISION 00 – PROCUREMENT AND CONTRACTING REQUIREMENTS

Section 001116 Invitation to Bid Section 003126 Existing Hazardous Material Information Section 004113 Bid Form Section 004313 Bid Bond (A310) Section 004513 Contractor Qualification Statement (A305) Section 004519 Non-Collusion Section 004533. Nondiscrimination Certification Section 006113 Performance & Payment Bonds Section 006519.16 Release of Liens (AIA Document G706A) Section 006519.19 Contractor’s Final Payment (AIA Document G707-1994) Section 007200 General Conditions of the Contract for Construction (AIA Document A201- 2007) Section 007336 CHRO Good Faith Efforts Shor Form Plan Section 007339 Minority Business Enterprise Requirements Section 007343 Wage Rate Requirements Section 007343 Wage Rate Schedules

DIVISION 01 – GENERAL REQUIREMENTS

Section 011100 Summary of Work Section 012200 Unit Prices Section 012500 Substitution Procedures Section 012600 Contract Modification Procedures Section 012900 Payment Procedures Section 013100 Project Management and Coordination Section 013233 Photographic Documentation Section 013300 Submittal Procedures Section 014000 Quality Requirements Section 015000 Temporary Facilities and Controls Section 015800 Project Sign Section 016000 Product Requirements Section 017300 Execution Section 017700 Closeout Procedures Section 017823 Operation and Maintenance Data Section 017839 Project Record Documents

DIVISION 02 – EXISTING CONDITIONS

Section 024119 Selective Demolition

SECTION 000110

DIVISION 03 – CONCRETE

Section 034500 Precast Architectural Concrete

DIVISION 06 – WOODS, PLASTICS AND COMPOSITES

Section 061053 Miscellaneous Rough Carpentry

DIVISION 07 – THERMAL AND MOISTURE PROTECTION

Section 070150 Rehabilitation of Mod Bit Membrane Roofing Section 072100 Thermal Insulation Section 075423 Thermoplastic-Polyolefin (TPO) Roofing Section 076200 Sheet Metal Flashing and Trim Section 077200 Roof Accessories Section 079200 Joint Sealants

DIVISION 08 – OPENINGS

Section 086200 Unit Skylights

SECTION 000115

DRAWING SHEET LIST

DRAWING SHEET LIST

GENERAL

A-001 COVER SHEET

AD-100 ROOF DEMOLITION PLAN

A-100 ROOF CONSTRUCTION PLAN

A-301 BUILDING SECTIONS

A-401 ROOF DETAILS

Industrial Hygiene / IAQ Hazardous Building Materials Environmental Assessments Laboratory Services & Training

8 SOUTH MAIN STREET, SUITE 3 • TERRYVILLE, CT 06786

PHONE (860) 589-8257 • FAX (860) 585-7034

December 20, 2024

Mr. Todd Whitaker Facilities Manager YWCA Hartford Region 135 Broad Street Hartford, CT 06105

RE: Lead-Based Paint Inspection and Risk Assessment Report

Hartford, Connecticut Eagle Project No. 24-208.10T1

Dear Mr. Whitaker:

Please find the report for the Lead-Based Paint Inspection and Radon testing conducted at 135 Broad Street in Hartford, Connecticut (Site). The Lead-Based Paint Inspection and radon testing services were performed as part of the YWCA’s due diligence for proposed renovation activities to convert select areas within the Site building into early childcare program. The Client identified select locations that will be licensed under the childcare program.

Please do not hesitate to contact if you have any questions regarding the contents of this report.

Sincerely, Eagle Environmental, Inc.

Report Prepared By:

William Petrucci Environmental Consultant I

Report Reviewed By:

Chris Liberti Vice President of Operations

X:\2024 Files\2024 Reports\YWCA Hartford\135 Broad St - LIRA - Daycare.doc

EAGLE ENVIRONMENTAL, INC.

PHONE (860) 589-8257 • FAX (860) 585-7034

TABLE OF CONTENTS

1.0 INTRODUCTION

1.1 Introduction

2.0 BACKGROUND INFORMATION

2.1 Scope of Inspection

2.2 Building Information

3.0 LEAD-BASED PAINT INSPECTION

3.1 Inspection Results

3.2 Risk Assessment

4.0 ENVIRONMENTAL SAMPLING

4.1 Dust Sampling Results

4.2 Soil Assessment Results

4.3 Water Sampling Results

4.4 Radon Testing Results

5.0 REGULATORY REQUIREMENTS

6.0 EXECUTIVE SUMMARY

APPENDICES

Appendix A Floor Plans Appendix B Standard Operating Procedures Appendix C XRF Lead-Based Paint Inspection Reports Appendix D Dust and Water Sample Laboratory Reports Appendix E Radon Testing Reports Appendix F Eagle Environmental, Inc. Certificates and License Appendix G Laboratory Certificate

PHONE (860) 589-8257 • FAX (860) 585-7034 1

1.0 INTRODUCTION

1.1 Introduction

Eagle Environmental, Inc. (Eagle) was retained by the YWCA Hartford Region to perform a lead-based paint inspection and radon testing for 135 Broad Street in Hartford, Connecticut (Site). The inspection was performed within the areas of the building which will be associated with a proposed the early childcare program. The lead-based paint inspection and risk assessment was performed on November 21, 2024 by William Petrucci; a State of Connecticut Department of Public Health (CT DPH) licensed Lead Inspector (license #002295).

2.0 BACKGROUND INFORMATION

2.1 Scope of Inspection

The scope of services included Lead-based paint testing utilizing an LPA-1 X-Ray Fluorescence (XRF) paint analyzer, dust sampling, lead-drinking-water sampling and radon testing. The Client’s representative identified the areas throughout the Basement and First-Floor level, which will be included in the childcare program’s licensing.

Additional areas outside the childcare program were inspected concurrently with this assessment in order to properly support the proposed renovation activities.

The following locations will be included in the licensed childcare program:

Basement level – Gymnasium Basement level – Corridors First Floor level – Soromundi Room Two (2) Stairwells First Floor level – Two (2) classrooms First Floor level – Restrooms First Floor level – Corridors and Closets

Floor plans identifying the childcare locations are attached in Appendix B.

2.2 Building Information

The Site building was constructed in 1974. The Basement consists of mechanical rooms, storage rooms, gym, pool, and locker rooms. The first-floor level consists of the entry lobby and offices. The second-floor level consists of mainly offices and conference rooms. The floors are concrete and covered with various types of vinyl flooring materials and carpet. The walls are masonry block and poured concrete in the mechanical rooms and of sheetrock and joint compound construction in most areas of the building. The ceilings consist of several types of suspended ceiling systems.

3.0 LEAD-BASED PAINT INSPECTION

3.1 Inspection Results

The lead-based paint inspection was performed utilizing an X-Ray Fluorescence (XRF) Sci-Apps X-550pb Lead Paint Analyzer (LPA 1), serial number 02230 within the limits of the inspection area(s). Room numbers designated by Eagle correspond to the attached

PHONE (860) 589-8257 • FAX (860) 585-7034 2

Lead-Based Paint Inspection XRF Report, located in Appendix C, and the floor plans attached in Appendix B. The “A” side is considered the front of the building with the “B”, “C” and “D” sides following in a clockwise direction.

For the purpose of this inspection, two hundred thirty-five (235) painted surfaces and components were tested with three (3) actionable readings. The actionable readings were identified on the metal I-beam frame supports to the overhead air handler unit within a mechanical room (Room 0-05) which is scheduled to be removed during the overall renovation project. The mechanical room is not located within the child-occupied areas associated with the proposed daycare.

At the time of the inspection, stairwell ST-2 was locked and inaccessible. The components appeared similar to those in stairwell ST-1 but additional testing will be required within the stairwell if it will be included within the childcare program’s licensing.

The lead-based paint inspection for the proposed childcare areas did not identify any of the tested components/surfaces to contain toxic levels of lead-based paint. The exterior proposed playground area was investigated, no painted surfaces or bare soil areas were identified. The exterior building facades included unpainted masonry walls and concrete columns.

Eagle did not test under any rigid enclosures. Components and or surfaces concealed under rigid enclosures are assumed to contain toxic levels of lead-based paint until tested and proven negative.

3.2 Risk Assessment

For the purpose of this inspection, toxic levels of lead-based paint were not identified within the proposed areas that will be converted into a childcare area. The XRF Lead Inspection Report is located in Appendix C.

4.0 ENVIRONMENTAL SAMPLING

4.1 Dust Sampling Results

Dust samples were collected from the floors and window sills within the inspected area of the proposed daycare and the adjoining hallways that are likely to be frequented by children under the age of six (6) years old. Dust sample results with concentrations of lead equal to or exceeding 10 µg/ft² on floors and 100 µg/ft² on window sills are considered to be dust-lead hazards.

The location of dust samples and results are provided in the following table:

Sample Number Location/Surface Sample Size Result 11-21-WP-01 1-09 D side floor 288 in² <1.0 µg/ft² 11-21-WP-02 1-09 B side floor 288 in² <1.0 µg/ft² 11-21-WP-03 1-09 A floor 288 in² <1.0 µg/ft² 11-21-WP-04 1-09 B floor 288 in² <1.0 µg/ft² 11-21-WP-05 1-08 D side floor 288 in² <1.0 µg/ft² 11-21-WP-06 1-08 B side floor 288 in² <1.0 µg/ft² 11-21-WP-07 1-17 floor 288 in² <1.0 µg/ft² 11-21-WP-08 1-18 floor 288 in² <1.0 µg/ft² 11-21-WP-09 1-10 Hallway floor 288 in² <1.0 µg/ft²

PHONE (860) 589-8257 • FAX (860) 585-7034 3

Sample Number Location/Surface Sample Size Result 11-21-WP-10 Field Blank N/A <10 µg/wipe 11-21-WP-11 Field Blank N/A <10 µg/wipe

No dust lead-hazards were identified in the areas where dust samples were collected.

4.2 Soil Assessment Results

A soil assessment was completed by Eagle during the lead-based paint inspection and risk assessment. Within the area of the proposed playground and rear entry, no bare soil was identified. Ground surfaces were covered by concrete walkways and bark mulch.

4.3 Water Sampling Results

Eagle collected two (2) first draw water samples and two (2) flush water samples from two (2) sinks located within the proposed daycare location. The first draw samples were confirmed by the building staff to have been sitting in the pipes for at least six (6) hours prior to sampling. The samples were collected in a one (1) Liter plastic collection bottle.

The sample was kept cool until analyzed by the laboratory.

The USEPA has set an action level of fifteen (15) parts per billion (ppb) (0.015 mg/Kg) as the lead in drinking water standard. Sample results that exceed this level may be harmful and pose a hazard to the consumer.

The location of the water sample and the result is provided in the following table:

The concentration of lead in the water samples collected from the sinks within Rooms 1- 09A and 1-09B were below the USEPA threshold of fifteen (15) ppb. No further action is necessary regarding lead in water.

4.4 Radon Testing Results

Radon is measured in PicoCuries per Liter of air or pCi/L. The USEPA has set an action level of 4.0 pCi/L. Ambient concentrations of radon are approximately 0.4 pCi/L of radon for outside air. The USEPA recommends that short term tests that have results of 4.0 pCi/L or greater be confirmed with a second short-term test. Two (2) short-term tests with results equal to or greater than 4.0 pCi/L require that radon mitigation be performed.

The charcoal canisters were sent to Radon Testing Corporation of America (RTCA) of Elmsford, New York for analysis. RTCA is listed in the USEPA Radon Measurement Proficiency (RMP) Program.

The location of the radon samples and the results are provided in the following table:

Sample Number Location Result 11-21-WP-CFD01 1-09A Sink – first draw 0.0022 mg/L (2.2 ppb) 11-21-WP-CF02 1-09A Sink – flush <0.0005 mg/L (<0.5ppb)

11-21-WP-BFD03 1-09B Left sink – first draw <0.0005 mg/L (<0.5ppb) 11-21-WP-BF04 1-09B Left sink – flush <0.0005 mg/L (<0.5ppb)

PHONE (860) 589-8257 • FAX (860) 585-7034 4

Canister ID# Test Start Test Stop Location Results (pCi/L)

4933842 11/21/2024 09:15

11/25/2024 08:11 Basement - Room 0-02 0.2

4934300 11/21/2024 09:20

11/25/2024 08:12

Basement - Room 0-06 (Left) 0.2

4934074 11/21/2024 09:22

11/25/2024 08:13

Basement Room 0-06 (Right) 0.3

4934327 11/21/2024 09:23

11/25/2024 08:13

Basement Room 0-06 (Right) - Duplicate 0.3

4934106 11/21/2024 09:26

11/25/2024 08:17 1st Floor Hallway 0.4

4934104 11/21/2024 09:30

11/25/2024 08:21

1st Floor - Proposed Daycare 0.1

4934078 11/21/2024 09:32

11/25/2024 08:21 Blank 0.1

Based on the results of this testing, all results fell below the USEPA action level of 4.0 pCi/L. No further testing is required at this time.

5.0 REGULATORY REQUIREMENTS

A Lead-Based Paint Correction Plan is not required for proposed daycare location as toxic levels of lead-based paint was not identified. No further action is required as it pertains to painted surfaces within the identified proposed daycare rooms.

A copy of this report should be maintained on Site in the event regulatory agencies request information pertaining to the inspected areas.

6.0 EXECUTIVE SUMMARY

Eagle Environmental, Inc. (Eagle) was retained by the YWCA Hartford Region to perform a lead-based paint inspection and risk assessment for the rooms associated with the proposed daycare within the Site building located at 135 Broad Street in Hartford, Connecticut (Site). The lead-based paint inspection and risk assessment was performed on November 21, 2024 by William Petrucci; a State of Connecticut Department of Public Health (CT DPH) licensed Lead Inspector (license #002295).

Lead-based paint equal to or exceeding 1.0 mg/cm² was not identified within the inspected area of the proposed daycare.

A complete list of components tested is identified in the Lead Paint Inspection Report located in Appendix C.

No dust-lead hazard was identified in the areas where dust wipes were collected.

PHONE (860) 589-8257 • FAX (860) 585-7034 5

No bare soils were identified within the proposed playground area during the soil assessment.

The concentration of lead in the water samples collected from Rooms 1-09A and 1-09B were below the USEPA threshold of fifteen (15) ppb. No further action is necessary regarding lead in water.

Any of the areas outside of the proposed childcare area, both interior and exterior, that have not been tested and confirmed to be negative for lead-based paint must be assumed to contain toxic levels of lead in paint and should be placed on the management plan to ensure all painted surfaces remain in intact condition. Components and surfaces concealed behind rigid enclosures or are otherwise inaccessible for testing must be assumed to contain toxic levels of lead-based paint for the purpose of this report.

A copy of this report should be maintained on Site in the event regulatory agencies request information pertaining to the inspected areas.

APPENDIX A

FLOOR PLANS

8 SOUTH MAIN STREET, SUITE 3

TERRYVILLE, CONNECTICUT 06786

860-589-8257

BP-1 BASEMENT

FP-1 FIRST FLOOR

DECEMBER 17, 2024

EAGLE PROJECT NUMBER: 24-208.10T1

135 BROAD STREET

HARTFORD, CONNECTICUT

Z:\2024 Files\2024 AutoCAD\YWCA\135 Broad Street\LBP Inspection\CAD\135 Broad Street.dwg

LOCATION MAP

Y.W.C.A. HARTFORD

INDEX OF DRAWINGS

KEY:

= LIMITS LEAD-BASED PAINT

INSPECTION AND RISK ASSESSMENT

= EAGLE ROOM NUMBER0-00

BASEMENT

NOT TO SCALE

BP-1

S

O U

T H

M

A I N

S

R

E E

T

S

U I T

E

T E

R R

Y V

I L

L E

C

O N

N E

C T

I C

U

L E

A D

B

A S

E D

P

I N

T

I N

S P

E C

T I O

N

A

R

S

K

A

S S

E S

S M

E N

T

Y W

C

A

H

A R

T F

O R

D

B R

O A

D S

TR

EE

T H

A R

TF

O

R D

, C O

N N

EC

TI

C U

T

PR

O

JE

C

T N

O

-2

.1

0T

D A

TE

: 1

2/

/2

D R

A W

N B

Y : B

B

R

EV

IE

W

ED

B

Y : P

F

SHEET OF

SHEET NO.

S I D

E D

SIDE-A (STREET SIDE)

SIDE-C

S I D

E B

1 2

Z:\2024 Files\2024 AutoCAD\YWCA\135 Broad Street\LBP Inspection\CAD\135 Broad Street.dwg

0-05

0-06

0-07

ST-2

0-02

0-01

ST-1

0-04

0-03

KEY:

= LIMITS LEAD-BASED PAINT

INSPECTION AND RISK ASSESSMENT

= EAGLE ROOM NUMBER0-00

FIRST FLOOR

NOT TO SCALE

FP-1

S

O U

H

M

S

R

E E

T

S

U I T

E

T E

R R

Y V

I L

L E

C

O N

N E

C T

I C

U

L E

A D

B

A S

E

P

I N

T

I N

S P

E C

T I O

N

A

R

S

K

A

S S

E S

S M

E N

T

Y W

C

A

H

A R

T F

O R

D

B R

O A

D S

TR

EE

T H

A R

TF

O

R D

, C O

N N

EC

TI

C U

T

PR

O

JE

C

T N

O

-2

.1

0T

D A

TE

: 1

2/

/2

D R

A W

N B

Y : B

B

R

EV

IE

W

ED

B

Y : P

F

SHEET OF

SHEET NO.

S I D

E D

SIDE-A (STREET SIDE)

SIDE-C

S I D

E B

2 2

Z:\2024 Files\2024 AutoCAD\YWCA\135 Broad Street\LBP Inspection\CAD\135 Broad Street.dwg

1-19

ST-1

1-14

1-09 1-08 1-18

1-17

ST-2

1-09B 1-09A

1-10

1-12

1-11

E

1-15

1-19

APPENDIX B

LEAD-BASED PAINT INSPECTION AND RISK ASSESSMENT

STANDARD OPERATING PROCEDURES

LEAD-BASED PAINT INSPECTION AND RISK ASSESSMENT

STANDARD OPERATING PROCEDURES

PART I – INTRODUCTION

A. PRINCIPLES OF LEAD-BASED PAINT INSPECTIONS AND RISK ASSESSMENTS

The intent of the lead-based paint inspection is to determine the presence or absence of hazardous levels of lead-based paint within the subject property. The intent of the risk assessment is to determine the nature and severity of health risks associated with the hazardous levels of lead.

The actual process of performing the combined lead inspection and risk assessment can be broken down into four (4) major components that include: 1. documentation of building and tenant data including family use patterns; 2. environmental sampling; 3. visually assessing the condition of painted surfaces and soil areas; and 4. presenting lead hazard control options.

The data collected from the first three components of the lead inspection and risk assessment helps the Risk Assessor identify the existence, source, location and severity of lead-based paint hazards and lead exposure pathways. This allows the Lead Designer/Planner to provide appropriate and efficient options for correcting lead hazards.

B. SCOPE OF INSPECTION

The inspection report provides a description of completed work within the executive summary.

The introduction section within the report identifies the location of the inspection site and scope of services within that location, as well as the date(s) of service. The name(s) of the lead inspector/risk assessors providing inspection services and appropriate State of Connecticut license number(s) are also incorporated in the report.

PART II – BACKGROUND INFORMATION

A. BUILDING INFORMATION

In general, building information is comprised of the current building description and construction history. Data collected in the field from the tenants or owner in addition to the information collected by the inspector aids in a general knowledge of building components and age of the structure. A site diagram is drawn and rooms are designated with numbers to correspond to the XRF inspection report. This information also assists in the development of management and control plans.

C. IDENTIFICATION OF DAYCARE AREAS

The inspector interviews the daycare administrators to find out exactly where the children will be within the building and on the grounds during the course of a normal day. Potential rooms tested include classrooms, cafeterias, hallways, stairwells, bathrooms, exterior entryways and play areas. The inspector relies upon the daycare administrators to accurately communicate this information.

PART III – LEAD-BASED PAINT INSPECTION

A. INSPECTION PROTOCOL

The building site is tested for lead-based paint using selected portions of the inspection protocol of chapter 7 of the Department of Housing and Urban Development (HUD) Guidelines for the

Evaluation and Control of Lead-Based Paint Hazards in Housing (1997 and 2012) Revision and the State of Connecticut Department of Public Health Childhood Lead Poisoning Prevention regulations to determine whether lead-based paint is present in a house, dwelling unit, residential building, or housing development including common areas and exterior surfaces, and, if present, which building components contain lead-based paint.

For the purpose of the inspection, lead-based paint is defined as paint or other surface coatings (stain, shellac or varnish) applied prior to 1978 and containing lead equal to or exceeding 1.0 milligrams per square centimeter (under the Environmental Protection Agency standards) or 0.5% by weight in a dried state (under Consumer Product Safety Commissioner).

Representative testing is conducted at the site. This includes testing a minimum of one (1) of each type of building component or surface within each room or room equivalent within the inspection area. Within each room, the ceiling and four (4) walls are tested. In addition, one (1) representative component type is tested in each room (i.e. window components, door components, baseboards, etc.). Unique building components are also tested within each room and room equivalent. This testing protocol is in accordance with the State of Connecticut Department of Public Health requirements for a lead-based paint inspection.

For the purpose of the inspection report and labeled as such on the site diagram, the "A" side is considered the front of the building with the "B", "C", and "D" sides following in clockwise order.

B. X-RAY FLUORESCENCE (XRF) TESTING RESULTS

Testing is conducted in accordance with the requirements of American Society for Testing and Materials (ASTM) Designation E2119 - 00, Standard Provisional Practice for Quality Systems for Conducting In Situ Measurements of Lead Content in Paint or Other Coatings Using Field- Portable X-ray Fluorescence (XRF) Devices.

Eagle utilizes SciAps X-550 X-Ray Fluorescence (XRF) Devices with serial numbers 2330 and 2339. Eagle follows the manufacturer recommended warm-up procedures prior to initiating testing. In addition, Eagle utilizes the red 1.03 mg/cm² Standard Reference Material (SRM) paint film, developed by the National Institute of Standards and Technology (NIST). An initial calibration check is performed followed by subsequent calibration checks at the completion of testing in a dwelling unit.

Results are presented in a Lead Paint Inspection Report, which consists of two (2) sections: a coversheet and detailed report. Results of lead based paint components and surfaces with results equal to or above 1.0 mg/cm² are located highlighted in red text throughout the report.

PART IV – VISUAL ASSESSMENT

A. GENERAL

The visual assessment is conducted to locate potential lead based paint hazards and to evaluate the magnitude of the hazard. The visual assessment identifies deteriorated painted surfaces, areas of visible dust accumulation, areas of bare soil, the presence of friction and impact surfaces, and the presence of painted surfaces on which it is possible for a child under six (6) years old to mouth (“chewable surfaces”). The information gathered during the visual assessment is used to identify areas where defective paint is present and to determine where potential dust and soil samples are to be collected and preliminarily evaluate exposure pathways to lead hazards.

B. CONDITION OF PAINTED SURFACES

The Risk Assessor conducts a room-by-room examination of the painted surfaces in the dwelling interior, common areas and exterior of the subject building. Painted surfaces are rated as "intact" or "deteriorated". This rating system is consistent with rating system described in Chapter 5 of the HUD Guidelines. Painted surfaces containing a lead concentration of 1.0 mg/cm² or greater and receiving a rating of "deteriorated" are considered lead hazards while painted surfaces rated as "intact" are not.

The visual assessment also evaluates the potential of factors that may contribute to deteriorated surface coatings, that ultimately result with a “deteriorated” rating such factors are ambient temperature, moisture and water damage.

C. FRICTION AND IMPACT SURFACES

The Risk Assessor evaluates if any painted surfaces containing a lead concentration of 1.0 mg/cm² or greater are subject to friction or impact.

Friction surfaces are surfaces that have moveable parts and rub against one another when operated. Windows and doors are the most common sources of friction surfaces. For example, window sashes, jambs, stops, parting beads and interior portion of sills are components of a window system that rub against one another when operated. The area on a door that comes into contact with the door jamb and stop may also be considered a friction surface. Floors and stair treads are examples of impact surfaces. Impact surfaces are surfaces that are subject to impact by forces such as foot traffic.

Both friction and impact surfaces, if coated with lead-based paint, may have varying degrees of damage and are a potential for generating lead dust or paint chips according to the frequency of paint abrasion.

D. SETTLED DUST ASSESSMENT

During the visual assessment, the Risk Assessor evaluated areas where settled dust may accumulate, such as on window sills, in window wells and on floors. Settled dust, if contaminated with lead, presents an exposure risk to children residing in the dwelling unit.

E. SOIL ASSESSMENT

Areas of bare soil around the dwelling and where children play may be contaminated with lead.

The risk assessment evaluates the potential for exposure to lead from soil. For the purpose of this risk assessment, the yard surrounding the building is evaluated to determine if visible paint chips and/or bare soil areas.

PART V – ENVIRONMENTAL SAMPLING

A. DUST SAMPLING

Eagle Environmental collects samples of settled dust from various locations throughout finished areas within the daycare. Areas where paint is rated as "deteriorated" condition and or areas that contain accumulations of settled dust are generally tested. Areas tested frequently include classrooms, eating areas, primary play areas and most commonly used entries.

The samples are collected utilizing a single-ply disposable ASTM wipe as the sampling media.

The inspector utilizes disposable latex gloves during the sampling procedure to avoid cross-contamination of the samples. Where feasible, samples are collected from hard smooth surfaces such as floors, window sills and window wells. The sampling area is one (1) square foot for floor surfaces or the actual area of the component wiped, for a smaller surface, such as a window sill.

Samples are collected while passing the wipe over the sampling area in an “S” type motion. For floor samples, the first pass is started at the top of the area, working vertically downward. The second pass is started at the side of the area, working laterally. The third pass is made around the edges of the designated sampling area. For window sills or wells, the area is wiped several times with the horizontal “S” type motion. The wipe samples are placed directly into fifty (50) milliliter centrifuge tubes. Two (2) blank wipe samples were submitted to the laboratory for analysis to examine the integrity of the testing process.

Currently, the State of Connecticut risk assessment standards for lead-contaminated dust wipe samples are equal to or exceeding forty (40) micrograms per square foot (µg/ft²) on floors and two-hundred and fifty (250) µg/ft² on window sills. Dust wipe sample results that exceed these levels are considered lead hazards.

B. SOIL SAMPLING

Eagle Environmental evaluates bare soil areas at the site to determine if sampling for lead in soil is warranted. In accordance with the regulations of Connecticut State Lead Poisoning, Prevention and Control Agency (PCSA), if bare soil areas that are not covered by grass, sod, other live ground covering or similar coverings are present, then soil samples should be collected. For the purposes of the evaluation, the site is characterized by areas of similar function and usage such as the dripline of the building, mid-yard, and children’s play areas.

Composite soil samples are collected where required. This entails collecting approximately five

(5) sub-samples within the area of evaluation and combining them. Sub-samples are only combined from similar evaluation areas (i.e. dripline samples are not composited with play areas, etc.).

The soil sampling is performed in accordance with the ASTM 1727 designation, Standard Practice for Field Collection of Soil Samples for Lead Determination by Atomic Absorption Spectrometry (AAS) Techniques, or its HUD approved equivalent.

The EPA states the following levels of concern for lead concentration levels present in bare soil:

equal to or above 400mg/kg in bare areas of soil, concentrations equal to or greater than 1,200 mg/Kg in child play area and equal to or exceeding 5,000 mg/kg will require permanent abatement under the EPA’s guidance.

C. PAINT CHIP SAMPLING

Paint chip sampling includes painted surfaces that were determined to be in the low positive range (1.0 mg/cm2) for the SciAps X-550 XRF inspection instrument. Paint chip sampling is performed in accordance with the requirements of the American Society of Testing and Materials standard E 1729 Standard Practice for Field Collection of Dried Paint Samples for Lead Determination by Atomic Absorption Spectrometry Techniques. Paint chip samples are analyzed by flame Atomic Absorption Spectrometry (AAS) utilizing the USEPA SW 846, 7420 method.

Specifically, a paint chip is collected to include all layers of paint on a surface, but not to include the substrate. Paint chips shall include a minimum of one (1) square inch of paint.

Paint chip analysis results that are equal to or exceed 0.5% lead by weight defined by Consumer Product Safety Commissioner are considered positive (lead-based). Paint chip analysis results below 0.5% lead by weight are negative.

D. WATER SAMPLING

Drinking water is sampled at primary sources of drinking water, including water fountains and kitchen sinks. First draw water samples are collected after allowing the water to stand in the pipes for at least six (6) hours. First draw samples evaluate the lead content that is leaching into the water supply from the domestic piping in the building. First draw samples also detect lead that may have leached from plumbing fixtures at the point of use.

Samples are collected in one (1) Liter plastic collection and kept cool in an ice filled cooler or refrigerated until analyzed by the laboratory. The standard USEPA threshold used for evaluation of results is fifteen (15) parts per billion (PPB) lead.

PART VII – DISCLOSURES AND NOTIFICATIONS

Certain federal and state requirements apply when lead hazards are found in a daycare site, For example, Eagle Environmental is required to notify the local health department when toxic levels of lead are identified. Eagle Environmental identifies the applicable regulations and explains the requirements within the body of the inspection report.

PART VIII – LABORATORY SERVICES

Dust, soil and paint chip samples are analyzed by EMSL Analytical of Carle Place, New York and Scientific Analytical Institute (SAI) of Greensboro, North Carolina.

Lead in drinking water samples are analyzed by Phoenix Environmental Laboratories, Inc. of Manchester, Connecticut.

Z:\SOP\Lead\SOP - (LIRA) use for Daycare with SciAps.doc

APPENDIX C

XRF LEAD-BASED PAINT INSPECTION REPORT

Lead-Based Paint Inspection Report

Inspection Site: YWCA Hartford Inspection Date: 11/20/2024 - 11/21/2024 Unit Started: 11/20/2024 08:55:08

135 Broad Street, Total Readings: 235 Unit Ended: 11/21/2024 01:37:38

Hartford, CT 06105 Action Level: 1.0 (mg/cm²) Classification Level: 1.0 (mg/cm²)

Test # Room Wall Structure Components Substrate Position Color Conditition Result Lead Mode Notes (mg/cm²)

743 (CAL) PCS Pass 1.0 Timed

744 (CAL) PCS Pass 1.0 Timed

745 (CAL) PCS Pass 1.0 Timed

746 (CAL) PCS Pass 1.0 Timed

748 0-01 Pipe Metal Red Intact Negative 0.0 Quick

749 0-01 Pipe Metal Red Intact Negative 0.0 Quick

750 0-01 Pipe Metal Right Red Intact Negative 0.3 Quick

751 0-01 Pipe Metal Left Red Intact Negative 0.4 Quick

752 0-01 Pipe Metal Middle Red Intact Negative 0.1 Quick

753 0-01 Pipe Metal Middle Red Intact Negative 0.1 Quick

755 0-01 D Pipe Metal Right Red Intact Negative 0.0 Quick

756 0-01 D Pipe Metal Right Red Intact Negative 0.4 Quick

757 0-01 D Pipe Metal Middle Red Intact Negative 0.3 Quick

758 0-01 D Pipe Metal Middle Red Defective Negative 0.0 Quick

759 0-01 D Pipe Metal Left Red Defective Negative 0.8 Quick

760 0-01 D Pipe Metal Left Red Defective Negative -0.0 Quick

761 0-04 D Wall CMU White Intact Negative 0.0 Quick

762 0-04 C Wall CMU White Intact Negative -0.0 Quick

763 0-04 A Door Casing Metal White Intact Negative 0.0 Quick

764 0-04 A Door Jamb Metal White Intact Negative 0.1 Quick

Eagle Environmental, Inc 8 South Main Street, Suite #3, Terryville, CT 06786

Inspection Site: YWCA Hartford Inspection Date: 11/20/2024 - 11/21/2024 Unit Started: 11/20/2024 08:55:08

135 Broad Street, Total Readings: 235 Unit Ended: 11/21/2024 01:37:38

Hartford, CT 06105 Action Level: 1.0 (mg/cm²) Classification Level: 1.0 (mg/cm²)

Test # Room Wall Structure Components Substrate Position Color Conditition Result Lead Mode Notes (mg/cm²)

765 0-04 A Door Stop Metal White Intact Negative 0.1 Quick

766 0-04 A Door Header Metal White Intact Negative 0.0 Quick

767 0-03 Ceiling Track Metal White Intact Negative 0.0 Quick

768 0-03 A Wall CMU White Intact Negative 0.0 Quick

769 0-03 D Wall CMU White Intact Negative 0.0 Quick

770 0-03 A Door Casing Metal White Intact Negative 0.0 Quick

771 0-03 A Door Jamb Metal White Intact Negative 0.1 Quick

772 0-03 A Door Stop Metal White Intact Negative 0.0 Quick

773 0-03 A Door Header Metal White Intact Negative 0.0 Quick

774 0-02 A Wall CMU White Intact Negative -0.0 Quick

775 0-02 B Wall CMU White Intact Negative 0.0 Quick

776 0-02 C Wall CMU White Intact Negative -0.0 Quick

777 0-02 D Wall CMU White Intact Negative 0.0 Quick

778 0-02 A Door Casing Metal Left White Intact Negative 0.0 Quick

779 0-02 A Door Jamb Metal Left White Intact Negative 0.0 Quick

780 0-02 A Door Stop Metal Left White Intact Negative 0.0 Quick

781 0-02 A Door Casing Metal Right White Intact Negative 0.0 Quick

782 0-02 A Door Jamb Metal Right Blue Defective Negative 0.0 Quick

783 0-02 A Door Stop Metal Right White Intact Negative 0.0 Quick

784 0-02 B Door Casing Metal Left White Intact Negative 0.0 Quick

Inspection Site: YWCA Hartford Inspection Date: 11/20/2024 - 11/21/2024 Unit Started: 11/20/2024 08:55:08

135 Broad Street, Total Readings: 235 Unit Ended: 11/21/2024 01:37:38

Hartford, CT 06105 Action Level: 1.0 (mg/cm²) Classification Level: 1.0 (mg/cm²)

Test # Room Wall Structure Components Substrate Position Color Conditition Result Lead Mode Notes (mg/cm²)

785 0-02 B Door Stop Metal Left White Intact Negative 0.1 Quick

786 0-02 B Door Jamb Metal Left White Intact Negative 0.0 Quick

787 0-02 B Door Casing Metal Left Center White Intact Negative 0.0 Quick

788 0-02 B Door Jamb Metal Left Center White Intact Negative 0.0 Quick

789 0-02 B Door Stop Metal Left Center White Intact Negative 0.0 Quick

790 0-02 B Door Casing Metal Right Center White Intact Negative 0.0 Quick

791 0-02 B Door Jamb Metal Right Center White Intact Negative 0.0 Quick

792 0-02 B Door Stop Metal Right Center White Intact Negative 0.0 Quick

793 0-02 B Door Stop Metal Right White Intact Negative 0.1 Quick

794 0-02 B Door Jamb Metal Right White Intact Negative 0.0 Quick

795 0-02 B Door Stop Metal Right White Intact Negative 0.1 Quick

796 0-02 B Door Metal Right White Intact Negative 0.0 Quick

797 0-02 C Door Casing Metal Left White Intact Negative 0.0 Quick

798 0-02 C Door Jamb Metal Left White Intact Negative 0.0 Quick

799 0-02 C Door Stop Metal Left White Intact Negative 0.1 Quick

800 0-02 D Door Casing Metal White Intact Negative 0.0 Quick

801 0-02 D Door Stop Metal Blue Defective Negative 0.0 Quick

802 0-02 D Door Jamb Metal Blue Defective Negative 0.0 Quick

803 0-02 D Door Casing Metal Right Maroon Intact Negative 0.1 Quick

805 0-06 B Pipe Metal White Intact Negative 0.0 Quick

Inspection Site: YWCA Hartford Inspection Date: 11/20/2024 - 11/21/2024 Unit Started: 11/20/2024 08:55:08

135 Broad Street, Total Readings: 235 Unit Ended: 11/21/2024 01:37:38

Hartford, CT 06105 Action Level: 1.0 (mg/cm²) Classification Level: 1.0 (mg/cm²)

Test # Room Wall Structure Components Substrate Position Color Conditition Result Lead Mode Notes (mg/cm²)

806 0-06 B Closet Ceiling Metal No Paint Intact Negative 0.0 Quick

807 0-02 Column Metal Right White Intact Negative -0.0 Quick

808 0-02 Column Concrete Right White Intact Negative 0.0 Quick

809 0-07 A Wall CMU Yellow Defective Negative 0.0 Quick

810 0-07 B Wall CMU Yellow Defective Negative 0.0 Quick

811 0-07 C Wall CMU Yellow Intact Negative 0.0 Quick

812 0-07 D Wall CMU Yellow Intact Negative 0.0 Quick

813 0-07 D Column Concrete Yellow Intact Negative -0.0 Quick

814 0-07 A Door Casing Metal Blue Defective Negative 0.0 Quick

815 0-07 A Door Jamb Metal Blue Defective Negative 0.0 Quick

816 0-07 A Door Stop Metal Blue Defective Negative 0.0 Quick

817 0-07 B Door Casing Metal Brown Defective Negative 0.0 Quick

818 0-07 B Door Jamb Metal Brown Defective Negative 0.0 Quick

819 0-07 B Door Stop Metal Brown Defective Negative 0.0 Quick

820 0-07 C Door Casing Metal Brown Defective Negative 0.0 Quick

821 0-07 C Door Jamb Metal Brown Defective Negative 0.0 Quick

822 0-07 C Door Stop Metal Brown Defective Negative 0.0 Quick

823 0-07 D Door Casing Metal Brown Defective Negative 0.1 Quick

824 0-07 D Door Jamb Metal Brown Defective Negative 0.0 Quick

825 0-07 D Door Stop Metal Brown Defective Negative 0.0 Quick

Inspection Site: YWCA Hartford Inspection Date: 11/20/2024 - 11/21/2024 Unit Started: 11/20/2024 08:55:08

135 Broad Street, Total Readings: 235 Unit Ended: 11/21/2024 01:37:38

Hartford, CT 06105 Action Level: 1.0 (mg/cm²) Classification Level: 1.0 (mg/cm²)

Test # Room Wall Structure Components Substrate Position Color Conditition Result Lead Mode Notes (mg/cm²)

826 0-07 D Door Metal Brown Defective Negative 0.0 Quick

827 0-07 A Door Metal Red Intact Negative 0.0 Quick

828 0-07 B Door Metal Brown Defective Negative 0.0 Quick

829 0-05 I-Beam Metal Green Defective Positive 1.4 Quick

830 0-05 I-Beam Metal Left Green Defective Positive 1.2 Quick

831 0-05 I-Beam Metal Rear Green Defective Negative 0.7 Quick

832 0-05 I-Beam Metal Rear Green Defective Positive 1.6 Quick

833 0-05 I-Beam Metal Upper Green Defective Negative 0.7 Quick

834 0-05 Air Handler Unit Metal Left Blue Defective Negative 0.0 Quick

835 0-05 Air Handler Unit Metal Right Blue Defective Negative 0.3 Quick

836 0-05 Pipe Metal Right Red Defective Negative 0.0 Quick

837 0-05 B Door Casing Metal Brown Defective Negative 0.0 Quick

838 0-05 B Door Stop Metal Brown Defective Negative 0.0 Quick

839 0-05 B Door Stop Metal Brown Defective Negative 0.0 Quick

840 0-05 A Stairs Railing Metal Brown Defective Negative 0.6 Quick

841 0-05 A Stairs Stringer Metal Brown Defective Negative 0.6 Quick

842 0-05 A Stairs Tread Metal Brown Defective Negative 0.1 Quick

843 ST-01 B Door Casing Metal White Intact Negative 0.0 Quick

844 ST-01 B Door Jamb Metal White Intact Negative 0.0 Quick

845 ST-01 B Door Stop Metal White Intact Negative 0.1 Quick

Inspection Site: YWCA Hartford Inspection Date: 11/20/2024 - 11/21/2024 Unit Started: 11/20/2024 08:55:08

135 Broad Street, Total Readings: 235 Unit Ended: 11/21/2024 01:37:38

Hartford, CT 06105 Action Level: 1.0 (mg/cm²) Classification Level: 1.0 (mg/cm²)

Test # Room Wall Structure Components Substrate Position Color Conditition Result Lead Mode Notes (mg/cm²)

846 ST-01 A Wall CMU White Intact Negative -0.0 Quick

847 ST-01 B Wall CMU White Intact Negative 0.0 Quick

848 ST-01 C Wall CMU White Intact Negative 0.0 Quick

849 ST-01 D Wall CMU White Intact Negative 0.0 Quick

850 ST-01 B Door Metal White Intact Negative 0.0 Quick

851 ST-01 Stairs Tread Metal Maroon Intact Negative 0.0 Quick

852 ST-01 Stairs Riser Metal Black Intact Negative 0.2 Quick

853 ST-01 Stairs Stringer Metal Brown Defective Negative 0.5 Quick

854 ST-01 Ceiling Sheetrock White Intact Negative 0.0 Quick

855 ST-01 D Door Casing Metal Maroon Defective Negative 0.0 Quick

856 ST-01 D Door Jamb Metal Maroon Defective Negative 0.0 Quick

857 ST-01 D Door Stop Metal Maroon Defective Negative 0.0 Quick

858 1-10 C Door Casing Metal Brown Intact Negative 0.0 Quick

859 1-10 C Door Jamb Metal Brown Defective Negative 0.0 Quick

860 1-10 C Door Stop Metal Brown Defective Negative 0.0 Quick

861 1-10 D Door Casing Metal Left Brown Defective Negative 0.0 Quick

862 1-10 C Door Metal Brown Defective Negative 0.0 Quick

863 1-10 C Door Metal Maroon Defective Negative 0.1 Quick

864 1-10 C Door Jamb Metal Maroon Defective Negative 0.1 Quick

865 1-10 C Door Stop Metal Maroon Defective Negative 0.1 Quick

Inspection Site: YWCA Hartford Inspection Date: 11/20/2024 - 11/21/2024 Unit Started: 11/20/2024 08:55:08

135 Broad Street, Total Readings: 235 Unit Ended: 11/21/2024 01:37:38

Hartford, CT 06105 Action Level: 1.0 (mg/cm²) Classification Level: 1.0 (mg/cm²)

Test # Room Wall Structure Components Substrate Position Color Conditition Result Lead Mode Notes (mg/cm²)

866 1-10 D Wall CMU Yellow Intact Negative 0.0 Quick

867 1-10 B Wall CMU Yellow Intact Negative -0.0 Quick

868 1-10 B Door Casing Metal Right Maroon Intact Negative 0.0 Quick

869 1-10 B Door Jamb Metal Right Maroon Intact Negative 0.0 Quick

870 1-10 B Door Stop Metal Right Maroon Intact Negative 0.0 Quick

871 1-10 B Door Casing Metal Left Maroon Intact Negative 0.0 Quick

872 1-10 B Door Jamb Metal Left Maroon Intact Negative 0.0 Quick

873 1-10 B Door Stop Metal Left Maroon Defective Negative 0.0 Quick

874 1-10 B Wall Sheetrock White Intact Negative 0.0 Quick

875 1-10 A Window Frame Metal Brown Intact Negative 0.0 Quick

876 1-10 A Window Sash Metal Brown Intact Negative 0.0 Quick

877 1-10 A Door Casing Metal Brown Intact Negative -0.0 Quick

878 1-10 A Door Jamb Metal Brown Intact Negative 0.0 Quick

879 1-10 A Door Stop Metal Brown Intact Negative 0.0 Quick

880 1-10 A Door Metal Brown Intact Negative 0.0 Quick

881 1-10 C Door Metal Right Maroon Intact Negative 0.0 Quick

882 1-10 D Door Casing Metal Right Maroon Intact Negative 0.0 Quick

883 1-10 D Door Jamb Metal Right Maroon Defective Negative 0.0 Quick

884 1-10 D Door Stop Metal Right Maroon Defective Negative 0.0 Quick

885 1-10 A Wall CMU Yellow Intact Negative 0.0 Quick

Inspection Site: YWCA Hartford Inspection Date: 11/20/2024 - 11/21/2024 Unit Started: 11/20/2024 08:55:08

135 Broad Street, Total Readings: 235 Unit Ended: 11/21/2024 01:37:38

Hartford, CT 06105 Action Level: 1.0 (mg/cm²) Classification Level: 1.0 (mg/cm²)

Test # Room Wall Structure Components Substrate Position Color Conditition Result Lead Mode Notes (mg/cm²)

886 1-10 A Window Sill Metal Brown Defective Negative 0.0 Quick

887 1-10 A Window Casing Metal Brown Defective Negative 0.1 Quick

888 1-08/1-09 C Wall Sheetrock Yellow Defective Negative 0.0 Quick

889 1-08/1-09 C Wall CMU Yellow Intact Negative 0.0 Quick

890 1-08 B Wall Sheetrock Yellow Defective Negative 0.0 Quick

891 1-08 B Wall CMU Yellow Defective Negative -0.0 Quick

892 1-18 B Wall Sheetrock Yellow Defective Negative 0.0 Quick

893 1-18 C Wall Sheetrock Yellow Defective Negative 0.0 Quick

894 1-17 B Wall Sheetrock Yellow Intact Negative 0.0 Quick

895 1-17 A Wall Sheetrock Yellow Defective Negative 0.0 Quick

896 1-17 D Shelf Support Wood White Defective Negative 0.0 Quick

897 1-17 C Wall Sheetrock Yellow Defective Negative 0.0 Quick

898 1-17 C Wall CMU Yellow Defective Negative -0.0 Quick

899 1-17 B Wall Sheetrock Yellow Defective Negative 0.0 Quick

900 1-15 A Wall Sheetrock Yellow Intact Negative 0.0 Quick

901 1-15 B Wall Sheetrock Yellow Intact Negative 0.0 Quick

902 1-15 C Wall Sheetrock Yellow Intact Negative 0.0 Quick

903 1-15 D Wall Sheetrock Yellow Defective Negative -0.0 Quick

904 1-15 D Door Casing Metal Brown Defective Negative 0.0 Quick

905 1-15 D Door Jamb Metal Brown Defective Negative 0.0 Quick

Inspection Site: YWCA Hartford Inspection Date: 11/20/2024 - 11/21/2024 Unit Started: 11/20/2024 08:55:08

135 Broad Street, Total Readings: 235 Unit Ended: 11/21/2024 01:37:38

Hartford, CT 06105 Action Level: 1.0 (mg/cm²) Classification Level: 1.0 (mg/cm²)

Test # Room Wall Structure Components Substrate Position Color Conditition Result Lead Mode Notes (mg/cm²)

906 1-15 D Door Stop Metal Brown Defective Negative 0.0 Quick

907 1-16 A Wall Sheetrock Yellow Defective Negative 0.0 Quick

908 1-16 B Wall Sheetrock Yellow Defective Negative -0.0 Quick

909 1-16 D Wall Sheetrock Yellow Defective Negative 0.0 Quick

910 1-11 A Window Sash Metal Brown Intact Negative 0.0 Quick

911 1-11 A Window Casing Metal Brown Intact Negative 0.0 Quick

912 1-14 A Wall CMU Yellow Intact Negative 0.0 Quick

913 1-14 B Wall CMU Yellow Intact Negative 0.0 Quick

914 1-14 D Wall CMU Yellow Intact Negative -0.0 Quick

915 1-14 C Wall CMU Yellow Intact Negative -0.0 Quick

916 1-14 A Door Casing Metal Maroon Intact Negative 0.0 Quick

917 1-14 A Door Jamb Metal Maroon Intact Negative 0.0 Quick

918 1-14 A Door Stop Metal Maroon Intact Negative 0.0 Quick

919 1-14 A Door Metal Maroon Intact Negative 0.0 Quick

920 1-14 B Door Metal Maroon Intact Negative 0.0 Quick

921 1-14 B Door Casing Metal Maroon Intact Negative 0.0 Quick

922 1-14 B Door Stop Metal Maroon Intact Negative 0.1 Quick

923 1-14 B Door Jamb Metal Maroon Intact Negative 0.1 Quick

924 1-14 D Door Casing Metal Maroon Intact Negative 0.1 Quick

925 1-14 D Door Stop Metal Maroon Intact Negative 0.0 Quick

Inspection Site: YWCA Hartford Inspection Date: 11/20/2024 - 11/21/2024 Unit Started: 11/20/2024 08:55:08

135 Broad Street, Total Readings: 235 Unit Ended: 11/21/2024 01:37:38

Hartford, CT 06105 Action Level: 1.0 (mg/cm²) Classification Level: 1.0 (mg/cm²)

Test # Room Wall Structure Components Substrate Position Color Conditition Result Lead Mode Notes (mg/cm²)

926 1-14 B Door Casing Metal Right Brown Intact Negative 0.0 Quick

927 1-14 C Door Casing Metal Brown Intact Negative 0.0 Quick

928 1-14 C Door Metal Brown Intact Negative 0.0 Quick

929 1-14 C Door Jamb Metal Brown Intact Negative 0.0 Quick

930 1-14 C Door Stop Metal Brown Intact Negative 0.0 Quick

931 1-10 Ceiling Deck Metal No Paint Intact Negative 0.0 Quick

932 1-13 A Door Casing Metal Maroon Defective Negative 0.0 Quick

933 1-13 A Door Jamb Metal Maroon Defective Negative 0.0 Quick

934 1-13 A Door Stop Metal Maroon Defective Negative 0.0 Quick

935 1-13 A Door Jamb Metal Left Brown Defective Negative 0.0 Quick

936 1-13 A Door Stop Metal Left Brown Defective Negative 0.0 Quick

937 1-13 B Door Casing Metal Left Brown Intact Negative 0.0 Quick

938 1-13 B Door Jamb Metal Left Brown Intact Negative 0.1 Quick

939 1-13 C Door Casing Metal Left Brown Intact Negative 0.0 Quick

940 1-13 C Door Casing Metal Right Brown Intact Negative 0.0 Quick

941 1-13 D Door Casing Metal Brown Intact Negative 0.0 Quick

942 1-13 Ceiling Sheetrock White Intact Negative 0.0 Quick

943 1-13 Ceiling Plaster White Intact Negative -0.0 Quick

944 1-13 B Door Casing Metal Left Brown Intact Negative 0.0 Quick

945 1-13 B Door Jamb Metal Left Brown Intact Negative 0.0 Quick

Inspection Site: YWCA Hartford Inspection Date: 11/20/2024 - 11/21/2024 Unit Started: 11/20/2024 08:55:08

135 Broad Street, Total Readings: 235 Unit Ended: 11/21/2024 01:37:38

Hartford, CT 06105 Action Level: 1.0 (mg/cm²) Classification Level: 1.0 (mg/cm²)

Test # Room Wall Structure Components Substrate Position Color Conditition Result Lead Mode Notes (mg/cm²)

946 1-13 B Door Stop Metal Left Brown Intact Negative 0.0 Quick

947 2-38 A Wall Sheetrock White Intact Negative 0.0 Quick

948 2-38 C Wall Sheetrock White Intact Negative 0.0 Quick

949 2-38 A Door Casing Metal Brown Defective Negative 0.0 Quick

950 2-22 C Wall Sheetrock Gray Intact Negative 0.0 Quick

951 2-22 A Wall Sheetrock Gray Defective Negative 0.0 Quick

952 2-22 D Window Sill Metal Brown Intact Negative 0.0 Quick

953 2-22 D Window Parting Bead Metal Brown Intact Negative 0.0 Quick

954 2-23 A Wall Sheetrock Blue Defective Negative -0.0 Quick

955 2-23 C Wall Sheetrock Blue Defective Negative 0.0 Quick

956 2-36 C Wall Sheetrock Gray Defective Negative -0.0 Quick

957 2-24 D Wall Sheetrock Gray Defective Negative 0.0 Quick

958 2-24 C Wall Sheetrock Gray Defective Negative -0.0 Quick

959 2-24 C Door Casing Metal Yellow Defective Negative 0.0 Quick

960 2-25 C Door Casing Metal Yellow Defective Negative -0.0 Quick

961 2-25 C Wall Sheetrock Gray Defective Negative 0.0 Quick

962 2-25 B Wall Sheetrock Gray Defective Negative 0.0 Quick

963 2-26 B Wall Sheetrock Gray Defective Negative 0.0 Quick

964 2-26 A Wall Sheetrock Gray Defective Negative 0.0 Quick

965 2-34 B Wall Sheetrock Yellow Defective Negative 0.0 Quick

Inspection Site: YWCA Hartford Inspection Date: 11/20/2024 - 11/21/2024 Unit Started: 11/20/2024 08:55:08

135 Broad Street, Total Readings: 235 Unit Ended: 11/21/2024 01:37:38

Hartford, CT 06105 Action Level: 1.0 (mg/cm²) Classification Level: 1.0 (mg/cm²)

Test # Room Wall Structure Components Substrate Position Color Conditition Result Lead Mode Notes (mg/cm²)

966 2-34 C Wall Sheetrock Yellow Defective Negative -0.0 Quick

967 2-20 B Wall Sheetrock Yellow Intact Negative 0.0 Quick

968 2-20 C Wall Sheetrock Yellow Intact Negative 0.0 Quick

969 2-20 D Door Casing Metal Brown Intact Negative 0.0 Quick

970 2-20 A Door Casing Metal Brown Intact Negative 0.0 Quick

971 2-20 B Door Casing Metal Left Brown Intact Negative 0.0 Quick

972 2-20 B Door Casing Metal Right Brown Intact Negative 0.0 Quick

973 2-21 C Wall Sheetrock Yellow Intact Negative 0.0 Quick

974 2-21 B Wall Sheetrock Yellow Intact Negative -0.0 Quick

975 2-30 C Cased Opening Metal Yellow Intact Negative 0.0 Quick

976 2-30 C Wall Sheetrock Beige Intact Negative 0.0 Quick

977 (CAL) PCS Pass 1.1 Timed

978 (CAL) PCS Pass 1.1 Timed

979 (CAL) PCS Pass 1.1 Timed

980 (CAL) PCS Pass 1.1 Timed

--- End of Readings ---

APPENDIX D

DUST AND WATER SAMPLE LABORATORY REPORTS

Analysis for Lead Concentration in Wipe Samples by Flame Atomic Absorption Spectroscopy

EPA SW-846 3050B/6010C/7000B

Customer: Eagle Environmental, Inc 8 South Main Street Suite 3 Terryville, CT 06786

Analysis:

Victoria Farkas Aaron Hatcher Breigh Ashe

10069090Lab Order ID:Attn:

PBW

Date Received: 11/25/2024

Project: YWCA Hartford- 135 Bcoad Street, Hartford Date Reported: 11/26/2024

Sample ID

Lab Sample ID

Description

Lab Notes

Concentration (µg)

Concentration (µg/ft²)

Area (ft²)

Reporting Limit (μg)

11-21-WP-01

10069090_0001

1-09 D side floor 2 <2.0 <1.02.0

11-21-WP-02

10069090_0002

1-09 B side floor 2 <2.0 <1.02.0

11-2…

This is the start of the file's text. The full file is on GovTribe.