Yachats Commons Condition Assessment Report 7-7-23.pdf
PDF 7 MB Posted
- Attached to
- Civic Campus and Parks Master Plan
- Solicitation number
- S-KY0010-00010596
- Issued by
- Klamath County, Oregon
About this file
This document is a Condition Assessment Report prepared by Civil West Engineering Services, Inc. for the City of Yachats, Oregon regarding the Yachats Commons Building. The report provides a detailed assessment of the building's condition, including evaluations of fire code requirements, emergency exit plans, doors and windows, heating and ventilation systems, roof and drainage, electrical systems, and general structural conditions. Key recommendations include addressing issues with emergency exits and signage, repairing the sagging roof and gutter system, replacing the generator's weather enclosure, and removing abandoned equipment and piping. The report identifies both urgent and routine maintenance items that the City should address to allow the building to continue functioning as a community center.
The report does not include any pricing information, set asides, or details on funding sources. However, it does note that some of the recommended improvements, such as the generator enclosure replacement, may need to be added to the City's Capital Improvement Plan. Overall, the document provides a comprehensive assessment of the Yachats Commons Building's current condition and outlines a series of repairs and upgrades that the City should consider to maintain the facility.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFP For Civic Master Plan.docx | DOCX document | |
| CIP Updates five year plan 2024-05-21.xlsx | XLSX spreadsheet | |
| PARKS OPEN SPACES MASTER PLAN.pdf | ||
| Lord and Schryver SOLE SOURCE PUBLIC NOTICE.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 | P a g e
Rogue Valley Office 830 O’Hare Parkway, Ste. 102
Medford, OR 97504 541-326-4828
South Coast Office 486 ‘E’ Street
Coos Bay, OR 97420 541-266-8601
North Coast Office 409 SW 10th Street Newport, OR 97365
541-264-7040
Willamette Valley Office 200 Ferry Street SW
Albany, OR 97321 541-223-5130
Date: July 7, 2023
To: Heidi Hamilton, CIP Manager
From: Timothy Gross, Senior Project Manager, Civil West Engineering Services, Inc.
RE: Yachats Commons Condition Assessment
I. Introduction
On March 20 and 21, representatives from Civil West Engineering Services, inc. conducted an inspection of the Yachats Commons Building located at 441 Hwy 101 N. in the City of Yachats, Lincoln County, Oregon, property tax ID is 14-12-27-DA-04500-00.
The Yachats Commons was built in the 1930s and used as a school until 1983. In 1990, the building was bought by the City of Yachats to serve as a community center and housed the City government offices until they were moved next door to 501 Hwy 101 N. in November of 2020. The Commons hosts a wide variety of events, including monthly free movie nights, play readings and drum circles, seniors' luncheons, and concerts of the Yachats Big Band. Periodically, concerts by the Oregon Coast Chamber Orchestra and plays, musicals, and revues by One of Us Productions are performed on the stage in the large auditorium, and a number of art and craft shows are held at the Commons as well. From May through October the Commons is the site of the outdoor Yachats Farmers Market. (Wikipedia, 2023) Currently the Commons hosts a day care, a teen after hours program, and a community library in the basement.
The City has contracted with Civil West to conduct a condition assessment of the structure and prepare a detailed report with the purpose of identifying any needed improvements or renovations to allow the building to continue to function as a community space. In the following report, various building components and associated conditions are discussed and recommendations for improvements are underlined. In Appendix D a list of all recommendations are included for easy reference.
II. Condition Assessment
The original building was constructed in the 1930’s and the gymnasium and meeting rooms 5, 6, 7, and 8 were added sometime later (Date unknown). The building is a timber framed single story over a basement constructed of cast-in-place concrete. The roofing materials are a combination of composite asphalt shingles over angles portions, and TPO (thermoplastic polyolefin) membrane over the flat roof portions. Siding is primarily cement board (Hardiplank) and all windows have recently been replaced with dual-pane vinyl. The building is equipped with a Perkins 4cylinder 30kw Generator assembly.
A. Fire Code Requirements
All buildings are regulated by the Oregon Fire Code (OFC) (International Code Council, 2022) and are required to have approved means of egress for emergencies as described in Chapter 10, Means of Egress. This structure was
Yachats Commons Condition Assessment
2 | P a g e constructed prior to the issuance of state building code regulations in 1974, and typically the technical details of providing the means of egress is regulated under Chapter 11 of the OFC, Fire and Life Safety Requirements for Buildings Constructed Prior to a State Building Code. However, it is apparent that the building has been modified extensively since its original construction. Changes in use or occupancy require that the structure be upgraded to comply with International Building Code. It is therefore assumed that current requirements for means of egress and accessibility are applicable.
Egress routes, signage and doors were reviewed for general compliance with these chapters of the Oregon Fire Code. The occupancy classification is likely Assembly Group A-3 (OFC 303.4) for most of the building, and occupancy classification Educational Group E for the daycare facility (OFC 305.2) if it serves more than 5 children, which seems to be the case. Chapter 11 of the OFC requires occupancy classification A and E to comply with the sections shown in the excerpt from Table 1103.1 from the OFC below. Of these sections, the Commons Building only has two sections that apply.
Table II-1Excerpt from OFC Table 1103.1 Occupancy and Use Requirements
OFC
Section Section Title
Occupancy Classification
A
Occupancy Classification
E
Applies to Commons Building
1103.2 Emergency Responder Communication
Coverage in Existing Buildings
X X X
1103.3 Existing Elevators X X
1103.4.2 Vertical Openings: Three to Five Stories X X
1103.4.3 Vertical Openings: More than Five Stories X X
1103.4.6 Escalators Connecting Four or Fewer Stories X X
1103.4.7 Escalators Connecting More than Four
Stories X X
1103.4.8 Occupancies other than Groups I-2 and I-3 X X
1103.4.10 Flue Fed Incinerators X X
1103.5.5 Pyroxylin Plastics X X
1103.6.1 Standpipes: Existing Multi-story Buildings X X
1103.6.2 Standpipes: Existing Helistops and Heliports X X
1103.7.1 Fire Alarm Systems – Group E X
1104 Means of Egress for Existing Buildings X X X
These two sections of the OFC were referenced when evaluating fire protection requirements at the Commons Building. Section 1103.2 reads as follows:
1103.2 Emergency responder communication coverage in existing buildings
Existing buildings other than group R-3, that do not have approved in-building, two-way emergency response communication coverage for emergency responders in the building based on existing coverage levels of the public safety communication systems, shall be equipped with such coverage according to one of the following:
1. Where an existing wired communication system cannot be repaired or is being replaced, or where not approved in accordance with section 510.1, Exception 1.
2. Where a time frame established by the adopting authority.
Exception: Where it is determined by the fire code official that the in-building, two-way responder communication system coverage system is not needed.
3 | P a g e
Such a system does not exist in the Commons Building and the local Fire Marshall will make the determination if the structure must come into compliance with this requirement.
Section 1103.7.1 Reads as follows:
1103.7 Fire Alarm Systems.
An approved fire alarm system shall be installed in existing buildings and structures in accordance with Sections 1103.7.1 through 1103.7.6 and provide occupant notification in accordance with Section 907.5 unless other requirements are provided by other section s of this code.
1103.7.1 Group E
A fire alarm system shall be installed in existing Group E occupancies in accordance with sections 907.2.3 Exceptions:
1. A manual fire alarm system is not required in a building with a maximum area of 1,000 square feet that contains a single classroom and is located not closer than 50 feet from another building.
2. A manual fire alarm system is not required in Group E occupancies with an occupant load less than 50.
The structure is already equipped with a manual fire alarm system. This system was evaluated separately by Ace Alarms in 2019 and is not included in this evaluation.
1. Number of Emergency Exits Each space was evaluated for compliance with Chapters 10 and 11 of the OFC for compliance with means of egress, door type and opening, and emergency exit signage. Figure II-1 shows a plan view of the main floor and basement for the Commons Building. This plan shows the square footage for each room, the maximum occupancy of the room based upon the use of the room as determined by Table 1004.5 of the OFC, and the corresponding required number of emergency exits. In accordance with OFC Section 1006.2, building spaces within Occupancy Groups A and E shall have at least one (1) exit or exit access up to an occupancy of 49. Between 49-500 each space shall have three (3) exits. RECOMMENDATION: Rooms no. 3 and 7 each only have one (1) exit but are required to have two (2) based upon calculated occupancy. One solution to this problem is to post the room at a lower occupancy so that only one (1) exit is required.
2. Emergency Exit Signage In accordance with OFC 1013.1 Exits and Exit access doors shall be marked by an approved sign readily visible from any direction of egress travel. Likewise, the pathway of egress travel to exits and within exits shall be marked by readily visible exit signs to indicate the direction of travel in in cases where the exit or path of egress travel is not immediately visible to the occupants. However, exit signs are NOT required in rooms or areas that require only one (1) exit or exit access. Also, in accordance with OFC 1013.3, exit signs shall be internally or externally illuminated and shall be redundantly powered in case of outage (OFC 1104.5). OFC Section 1032.5 states that when a door is adjacent to, constructed similar to and can be confused with a means of egress door, that door shall be identified by an approved sign that identified the room name and use of the room.
Figure II-1 shows where each exit sign and “no exit” sign is located and if it is lit or not. Most exit signs are not lit.
In rooms where only one (1) exit is required this is not a problem since signage is not required anyway.
RECOMMENDATION: Lighted exit signs should be added at emergency exit doors in rooms 1, 3, 7, and 8.
3. Emergency Exit Doors In accordance with OFC 1010.1.2.1, Doors are required to swing outward in the direction of egress for occupancies of 50 or more. Furthermore, door hardware must allow operation from the egress side without the use of a key or special knowledge (OFC 1010.2), the unlatching of the door for egress shall not require more than one motion in a single linear or rotational direction to release all latching and all locking devices (OFC 1010.2.1), 4 | P a g e and swinging doors serving rooms or spaces with an occupancy of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock other than panic hardware or fire exit hardware (OFC 1010.2.9). Figure II-1 shows the doors for each room and direction of swing. Some exit doors swing in the wrong direction.
A summary of the means of egress improvements that are needed are included in TABLE II-2.
B. Fire/Emergency Exit Plan There are Fire/Emergency Exit Plans posted in most rooms of the structure. Unfortunately, this plan is dated and the building configuration is no longer represented correctly in the plan.
RECOMMENDATION: Emergency exit plans should be updated with the correct building footprint and means of egress routes clearly marked on the map. The current maps show all building doors and many of the doors are locked on the preventing access to an exterior door on the other side. For example, the commercial kitchen is normally locked at the doors leading to the gymnasium. This would not be an appropriate means of egress for someone in the gymnasium.
C. Doors, Windows & Security The Commons Building has many different keys that unlock various portions of the building. The Building was keyed at one time to a key hierarchy system with a master key. Over time, locks have been changed and the master key no longer unlocks all doors. In particular, the front doors, old council chambers, room 6 and the old planning office (rm 2) no longer use the master key. Figure II-2 the various keys and key boxes that open different doors.
TABLE II-2Means of Egress Improvements
Room No. Room Description Door Location Improvement needed
1 Counci l Chambers NW corner need l ighted exi t s ign
SE corner need l ighted exi t s ign needs pushbar
Hal lway West needs l ighted exi t s ign needs pushbar
3 multipurpose room south door opens wrong di rection needs secondary emergency exi t needs l ighted exi t s ign
7 multipurpose room south needs l ighted exi t s ign needs pushbar needs secondary emergency exi t
8 multipurpose room east needs l ighted exi t s ign needs pushbar north needs l ighted exi t s ign needs pushbar basement west needs pushbar east needs pushbar
Figure II-1 Fire/Emergency Exit Plan
5 | P a g e
There are several key boxes around the outside of the building and one inside the building next to the Council Chambers door. Each key box contains a key for the adjacent space to allow access to only that part of the building. However, all of the key boxes use the same code so once someone is given the code, they have free access to any part of the building since all of the building can be accessed by keys in one of the key boxes.
RECOMMENDATION: Key box codes should be unique from one another and should be changed regularly.
Windows throughout the building have recently been replaced and all are vinyl double pane windows. Doors are of various type as shown in Figure II-2. Steel doors offer the best security and fire protection. The City may want to consider replacement of some doors to improve security and fire protection when modifying the doors to comply with means of egress requirements.
D. Heating and Ventilation
The Commons Building is heated by various different types of systems and manufacturers. The predominant heating system type are heat pumps system manufactured by Mitsubishi and Fujitsu. The gymnasium and rooms 3, 7 and 8 are heated by a common Mitsubishi heat pump system with multiple control units and a single condenser located at the south end of the building. Rooms 1, 4, 5, and 6 are heated by individual Fujitsu heat pump systems that each have a control unit and associated condenser outside. All control units are mounted up high on the wall and control of the unit is via a cordless remote control. Patron using the gymnasium playing pickleball complained that nobody could ever find a remote to adjust the temperature. During the assessment a
Figure II-2 Doors, Windows & Security (Also Included in Appendix A)
6 | P a g e remote control was found for the system in room 7 and the childcare facility in room 4 had one hanging on the wall. RECOMMENDATION: Permanently mount the remote control in the rooms so heat control is possible and the remotes don’t walk away. The disconnect breakers for the various heat pumps are located outside adjacent to the condensers. All the disconnect boxes were unlocked, allowing passers by to shut off heat to the building.
RECOMMENDATION: Add padlocks or disposable wire lockouts similar to those CLPUD uses on electric meters to the exterior disconnect boxes to prevent vandalism. Condensers and control units all appeared to be in good condition.
In addition to the heat Fujitsu heat pump system, the old Council Chambers (Room 1) has two cadet radiant wall heaters that are operated by a thermostat located in the north-east corner of the room. The southern Cadet still functions but the northern Cadet trips the units overload switch after a few seconds of operation.
The afterschool program room (Rm 2), the public bathrooms, and the basement are all heated by an electric forced air furnace manufactured by Mitsubishi located in the basement. The furnace appears new. In addition to forced air heat, room 2 also has two Cadet electric radiant wall heaters along
Figure II-3 Steel Exit Door in Council Chambers, Needs Push
Bar and Lighted Exit Sign
Figure II-4 Heating Ventilation and Air Conditioning (also included in Appendix A)
7 | P a g e the west wall. Neither Cadet was functional. The western office attached to Room 2 also has a Cadet electric radiant wall heater that does not work. Breakers for all Cadets in this area are located next to this Cadet.
The storage room located south of the gymnasium is heated by a Cadet electric radiant wall heater with built in thermostat. This Cadet works. The gymnasium has a hanging gas heater located in the north-east corner. No thermostat is connected to the heater and it does not appear operational, although it looks in good condition. A cover for a radiant wall heater is located next to the entry doors adjacent to the Council Chambers. The heater has been removed and the cover is empty.
E. Roof Systems and Drainage
The roofing system and attic were assessed for condition. Although previous water intrusion was obvious in the attic space, there were no active leaks at the time of the assessment and it was raining steadily all day. The roof is constructed of composite asphalt shingle on the pitched portions of the roof, and by a TPO membrane on the flat portions of the roof.
1. Roof and Gutter Sag Water was observed to be draining down the wall at the southwest corner where the gymnasium meets the main building into the electrical room. See Figure II-5. The reason for this leaking water is because the roofline of the gymnasium on the west and south sides has no eaves. The gutters are mounted to the edge of the roof which is flush with the wall. The edge of roof and gutter have sagged in this location causing the water to fill the gutter to the top then spill over and run down the wall. The water is causing significant decay in the electrical room. See
Figure II-5 Roof and Drainage (Also available in Appendix A)
8 | P a g e figures Figure II-8 through Figure II-8. RECOMMENDATION: Construct an eave along the south wall of the gymnasium, thereby extending the roof past the underlying wall. The gutters should be rehung to drain correctly along this new roofline.
2. Water Draining into Crawlspace Vents The topography of the site causes the water to run from the east/front of the building to the west/back of the building. The topography also goes uphill as you head north. As rainfall runoff drains around the north end of the building, it runs along the foundation edge and into the crawlspace openings. It is not good practice to allow water to drain along a foundation edge, since it will infiltrate into the crawlspace and tends to cause soil to erode because it channels against the concrete and picks up velocity. In this instance, the fill against the northeast end of the building is also too high, allowing the water to pour into the crawlspace openings. RECOMMENDATION:
Regrade the north end of the building to direct water away from the building foundation. See Figure II-10 and Figure II-10.
LOCATION OF
SAGGING GUTTER
Figure II-8 Sagging Gutter Figure II-8 Water Spilling Down Wall from Low Point on Roof
Figure II-8 Water on Utility/Electrical Room Floor
9 | P a g e
F. Lighting and Electrical Systems/Generator
1. General Electrical Systems Civil West generally reviewed lighting and electrical system, testing outlets, light switches, and identifying breaker box locations. Electrical systems appear in good condition; all observed wiring is new Romex with no exposed wiring, all outlets are functional and have ground terminals, and breaker boxes have modern breakers. Several light switches were non-functional but it was undetermined if that was because the light bulbs were burned out or the switch was functional. It was observed that several bulbs were burned out in the storage room south of the gymnasium and in the storage closet across from room 4.
2. Stage Lighting and Sound Stage lighting and sound systems were generally reviewed for condition and function. Spotlights were not tested. The work lights on stage functioned and the sound system powered up but was not operated. There is a light rack that hangs above the gymnasium floor with spotlights for the stage. These lights are unprotected from activities in the gymnasium. See Figure II-12. Some patrons were observed playing pickleball when the assessment was conducted and they struck the lights several times with the ball. RECOMMENDATION: Remove the spotlights from the gymnasium lightbar when not in use to protect them from damage.
Figure II-10 Drainage Around NE Corner of Building Figure II-10 Runoff Draining into Crawlspace Openings
Figure II-12 Exposed Spotlights
Figure II-12 Unprotected Floor Outlet
10 | P a g e
There is an electrical outlet in the floor at center stage that does not have a cover. RECOMMENDATION: Install a cover as soon as possible to protect both the outlet and stage users.
3. Generator At the time of the assessment the generator was not accessible. Arrangements were made to return to the site on June 14 with a generator technician from Marine Deisel to assess the generator condition. The writeup from the technician is included as Appendix C. The genset (motor and electrical generator) was operated and appears in good condition with low operating hours. The weather enclosure surrounding the genset and the integral fuel tank below the genset are severely degraded by the weather with obvious holes in the enclosure. RECOMMENDATION: Temporarily mend holes with sheet metal to prevent intrusion by vermin which may damage the wiring. The weather enclosure and fuel tank appear beyond repair and should be replaced. The report by Marine Diesel in Appendix C includes estimated costs for enclosure replacement.
G. General Building Structural Condition
The building is in good condition and has obviously been well maintained. There are a few items that were observed that the City may want to add to a maintenance schedule.
1. Concrete popouts Several areas of concrete popouts were observed that were caused by rebar being too close to the surface of the concrete. Since the rebar was close to the concrete surface it began to rust. As the rebar expanded during the corrosion process, it popped the concrete surrounding it causing it to fall off. This process will continue as the rebar continues to rust.
RECOMMENDATION: Chip out the loose concrete, coat the rebar with a rust inhibitor, then patch the concrete to protect the rebar from moisture.
Figure II-13 Generator Weather Enclosure Holes
Figure II-14 Concrete Popouts - Gymnasium S. Wall
Figure II-15 Concrete Popouts - S. Wall by Utility Room
11 | P a g e
2. Missing Siding On the southeast corner of the gymnasium there is a piece of siding missing. RECOMMENDATION: Replace missing siding to prevent water intrusion.
3. Peeling Paint Peeling paint was observed on some of the fascia and wood siding corners. RECOMMENDATION: Strip and paint building trim to prevent rot.
4. Abandoned Piping The building had once been heated by a boiler system. When the boiler was replaced by alternative heating methods, much of the piping was left in place. In the basement, this piping crisscrosses at the ceiling creating headroom obstructions. RECOMMENDATION: Remove old boiler piping to eliminate headroom obstructions and simplify the mechanical systems in the basement to maintenance personnel do not get confused with what systems are live and what systems are abandoned.
5. Abandoned Radiant Wall Heaters As discussed above in Section IIC, Heating Ventilation and Air Conditioning, several obsolete radiant heaters still exist in rooms 1 and 2. Only one of these heaters still functions correctly. These heaters can be turned on by users of the building and represent a risk of causing an electrical fire if left energized. RECOMMENDATION:
Remove the heating element from the box and safely terminate the conductors.
Figure II-16 Missing Siding - S. Wall of Gymnasium
Figure II-17 Peeling Paint
12 | P a g e
Figure II-19 Abandoned Boiler Pipe in Basement
Figure II-18 Non-functional Radiant Wall Heaters
13 | P a g e
III. Summary In general, the condition of the building is very good. The roof and windows appear relatively new and there is no signs of current water intrusion. Only one repair recommendation we would recommend as urgent and that is addressing the sagging roofline and gutter that is causing water to run into the electrical/utility room as described in Section II.E.1. One recommendation will likely need to be added to the Capital Improvement Plan and that is the replacement of the weather enclosure for the generator as described in Section II.F.3. The remaining recommendations can be added to the routine maintenance schedule as discussed above and summarized in TABLE II-3 below.
IV. References International Code Council. (2022). 2022 Oregon Fire Code. Washington DC: International Code Council.
Wikipedia. (2023, June 29). Wikipedia. Retrieved from Yachats, Oregon: https://en.wikipedia.org/wiki/Yachats,_Oregon
NO. RECOMMENDATION
1 A Fire Code Requirements 1 Number of Emergency Exits Rooms no. 3 and 7 each only have one (1) exit but are required to have two (2) based upon calculated occupancy. One solution to this problem is to post the room at a lower occupancy so that only one (1) exit is required.
2 A Fire Code Requirements 2 Emergency Exit Signage Lighted exit signs should be added at emergency exit doors in rooms 1, 3, 7, and 8
4 B Fire/Emergency Exit Plan Emergency exit plans should be updated with the correct building footprint and means of egress routes clearly marked on the map
5 C Doors, Windows & Security Key box codes should be unique from one another and should be changed regularly.
6 D Heating and Ventilation Permanently mount the remote control in the rooms so heat control is possible and the remotes don’t walk away
7 D Heating and Ventilation Add padlocks or disposable wire lockouts similar to those CLPUD uses on electric meters to the exterior disconnect boxes to prevent vandalism.
8 E Roof Systems and Drainage 1 Roof and Gutter Sag Construct an eave along the south wall of the gymnasium, thereby extending the roof past the underlying wall.
The gutters should be rehung to drain correctly along this new roofline
9 E Roof Systems and Drainage 2 Water Draining into Crawlspace Vents Regrade the north end of the building to direct water away from the building foundation 10 F Lighting and Electrical Systems/Generator 2 Stage Lighting and Sound Remove the spotlights lights from the gymnasium lightbar when not in use to protect them from damage.
11 F Lighting and Electrical Systems/Generator Cover missing from floor outlet. Install a cover as soon as possible to protect both the outlet and stage users
12 F Lighting and Electrical Systems/Generator 3 Generator Temporarily mend holes in generator enclosure with sheet metal to prevent intrusion by vermin which may damage the wiring. The weather enclosure and fuel tank appear beyond repair and should be replaced
13 G General Building Structural Condition 1 Concrete popouts Chip out the loose concrete, coat the rebar with a rust inhibitor, then patch the concrete to protect the rebar from moisture
14 G General Building Structural Condition 2 Missing Siding Missing siding should be replaced to prevent water intrusion 15 G General Building Structural Condition 3 Peeling Paint Building trim should be stripped and painted to prevent rot
16 G General Building Structural Condition 4 Abandoned Piping Remove old boiler piping to eliminate headroom obstructions and simplify the mechanical systems in the basement to maintenance personnel do not get confused with what systems are live and what systems are abandoned
17 G General Building Structural Condition 5 Abandoned Radiant Wall Heaters Remove the heating element from the box and safely terminate the conductors.
PARAGRAPHSECTION
Emergency Exit Doors3Fire Code RequirementsA
Room No. Room Description Door Location Improvement needed
1 Counci l Chambers NW corner need l ighted exi t s ign
SE corner need l ighted exi t s ign needs pushbar
Hal lway West needs l ighted exi t s ign needs pushbar
3 multipurpose room south door opens wrong di rection needs secondary emergency exi t needs l ighted exi t s ign
7 multipurpose room south needs l ighted exi t s ign needs pushbar needs secondary emergency exi t
8 multipurpose room east needs l ighted exi t s ign needs pushbar north needs l ighted exi t s ign needs pushbar basement west needs pushbar
TABLE II-1 Summary of Recommendations (Included as Appendix D)
14 | P a g e
Thank you for this opportunity to serve the City of Yachats. Please let me know if you have any questions or need clarification regarding this report.
Sincerely, Civil West Engineering Services, Inc.
Timothy Gross, PE Senior Project Manager North Coast Region - Newport
YACHATS COMMONS - MAIN FLOOR PLAN
YACHATS COMMONS - BASEMENT FLOOR PLAN
1 4
2 3
LEGEND
SMOKE DETECTOR
HEAT DETECTOR
MANUAL PULL
STATION
ANNUNCIATOR
HORN STROBE
FIRE CONTROL
EXTINGUISHER
# ROOM NUMBER
2022 OFC EXCERPT FROM TABLE 1004.5 MAXIMUM FLOOR AREA
ALLOWANCES PER OCCUPANT
EDUCATIONAL: CLASSROOM AREA 20 SF/PERSON
COMMERCIAL KITCHENS 200 SF/PERSON
ASSEMBLY AREAS WITHOUT FIXED
SEATS/CONCENTRATED
7 SF/PERSON
BUSINESS AREAS 150 SF/PERSON
EXCERCISE AREAS 50 SF/PERSON
STAGES AND PLATFORMS 15 SF/PERSON
D at e Sh ee t N o.
w w w .c iv ilw es t.c om
DATE:7/7/23 FILE:O:\CW_Projects\3401 Yachats\3401-009 Yachats Commons Assessment\03 Planning\DWGs\Commons Working 6-29-23.dwg
R
EV
D
AT
E
D
ES
C R
IP
TI
O N
BY
D
ES
IG
N
ED
B
Y:
D
R
AW
N B
Y:
C
H
EC
KE
D
B Y:
PR
O
JE
C
T N
O
N
EW
PO
R
T O
R
SW
0T H
S T.
1-
4-
EX1
YA
C
H
AT
S C
O M
M O
N S
BU
IL
D
IN
G
AS
SE
SS
M
EN
T
C
IT
Y O
F
YA
C H
AT
S
TE
G
TE
G
Va lu e
JULY 2023
H W
Y
N
YA
C H
AT
S, L
IN
C O
LN
C
O U
N
TY
, O R
NO PUSHBAR
NON-LIGHTED EXIT SIGN
NO EXIT SIGN
NO PUSHBAR
NON-LIGHTED EXIT SIGN
NO PUSHBAR
NON-LIGHTED EXIT SIGN
NO PUSHBAR
NON-LIGHTED EXIT SIGN
NO PUSHBAR
LIGHTED EXIT SIGN
MARKED
"NOT AN EXIT"
NO PUSHBAR
NON-LIGHTED EXIT SIGN
LIGHTED EXIT SIGN W/RT ARROW
NO PUSHBAR
NON-LIGHTED EXIT SIGN
PUSHBARS W/
LIGHTED EXIT SIGN
NON-LIGHTED
EXIT SIGNMARKED
"NOT AN EXIT" HANGING LIGHTED EXIT SIGN
(PIVOTED 90°
NO PUSHBAR
NON-LIGHTED EXIT SIGN
PUSHBAR W/
LIGHTED EXIT SIGN
PUSHBARS W/
LIGHTED EXIT SIGN
NON-LIGHTED
EXIT SIGN
NO PUSHBAR
NO EXIT SIGN
NO "NOT AN EXIT" SIGNS
NO PUSHBAR
LIGHTED EXIT SIGN
MARKED
"NOT AN EXIT"
NO PUSHBAR
NO EXIT SIGN
NO "NOT AN EXIT" SIGNS
NO "NOT AN EXIT" SIGNS
NO PUSHBAR
NO EXIT SIGN
NO PUSHBAR
NO EXIT SIGN
MARKED
"NOT AN EXIT"
NO EXIT SIGN
NO "NOT AN EXIT" SIGN
LIGHTED EXIT SIGN W/LT ARROW
MARKED
"NOT AN EXIT"
HANGING
LIGHTED
EXIT SIGN
EMERGENCY MEANS OF EGRESS ROUTES
EX1
SCALE: 1" = 16'
N
PRESCHOOL/CLASSROOM
OCCUP. GROUP "E"
ROOM SF: 960
MAX. OCCUPANCY: 48
NO. EXITS REQUIRED: 1
COMMERCIAL KITCHEN
OCCUP. GROUP "A"
ROOM SF: 984
MAX. OCCUPANCY: 5
NO. EXITS REQUIRED: 1
GYMNASIUM/EXCERCISE AREA
OCCUP. GROUP "A"
ROOM SF: 2,542
MAX. OCCUPANCY: 51
NO. EXITS REQUIRED: 2
STAGE
OCCUP. GROUP "A"
ROOM SF: 738
MAX. OCCUPANCY: 49
NO. EXITS REQUIRED: 1
ASSEMBLY AREA
OCCUP. GROUP "A"
ROOM SF: 405
MAX. OCCUPANCY: 58
NO. EXITS REQUIRED: 2
ASSEMBLY AREA
OCCUP. GROUP "A"
ROOM SF: 1,120
MAX. OCCUPANCY: 160
NO. EXITS REQUIRED: 2
OFFICE/BUSINESS
OCCUP. GROUP "A"
ROOM SF: 180
MAX. OCCUPANCY: 1
NO. EXITS REQUIRED: 1
ASSEMBLY AREA
OCCUP. GROUP "A"
ROOM SF: 725
MAX. OCCUPANCY: 104
NO. EXITS REQUIRED: 2
AFTER SCHOOL
PROGRAM/CLASSROOM
OCCUP. GROUP "E"
ROOM SF: 750
MAX. OCCUPANCY: 38
NO. EXITS REQUIRED: 1
ASSEMBLY AREA
OCCUP. GROUP "A"
ROOM SF: 960
MAX. OCCUPANCY: 137
NO. EXITS REQUIRED: 2
OFFICE/BUSINESS
OCCUP. GROUP "A"
ROOM SF: 54
MAX. OCCUPANCY: 1
NO. EXITS REQUIRED: 1
OFFICE/BUSINESS
OCCUP. GROUP "A"
ROOM SF: 96
MAX. OCCUPANCY: 1
NO. EXITS REQUIRED: 1
ASSEMBLY AREA
OCCUP. GROUP "A"
ROOM SF: 1,650
MAX. OCCUPANCY: 235
NO. EXITS REQUIRED: 2
APPENDIX A
AutoCAD SHX Text
AFTER SCHOOL PROGRAM 30'X25' 12' CEILING
AutoCAD SHX Text CLASSROOM 29'x25' 12' CEILING
AutoCAD SHX Text STORAGE 14'x25'' 12' CEILING
AutoCAD SHX Text
GYMNASIUM 41'X62' 16' CEILING
AutoCAD SHX Text RECREATION ROOM 24'x40' 12' CEILING
AutoCAD SHX Text STAGE 41'x18' 14' CEILING
AutoCAD SHX Text
CLASS ROOM 15'X27' 12' CEILING
AutoCAD SHX Text
8' HALL 12' CEILING
AutoCAD SHX Text OFFICE 15'x12'' 12' CEILING
AutoCAD SHX Text COMMERCIAL KITCHEN/CLASSROOM 41'x24' 12' CEILING
AutoCAD SHX Text DAYCARE/CLASS ROOM 40'x24' 12' CEILING
AutoCAD SHX Text
HANDICAP RAMP
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
HOOD
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
ELEC SERVICE
AutoCAD SHX Text
GENERATOR
AutoCAD SHX Text
PORCH
AutoCAD SHX Text
OPEN ABOVE
AutoCAD SHX Text
6' HALL
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
OPEN TO BELOW
AutoCAD SHX Text STORAGE 5'x9' 12' CLG
AutoCAD SHX Text STORAGE 8'x9' 12' CEILING
AutoCAD SHX Text
ATTIC ACCESS
AutoCAD SHX Text MENS ROOM 17'x9' 12' CEILING
AutoCAD SHX Text WOMENS ROOM 14'x9' 12' CEILING
AutoCAD SHX Text
12' CEILING
AutoCAD SHX Text UNISEX 4'x9'
AutoCAD SHX Text
12' CEILING THROUGHOUT
AutoCAD SHX Text OFFICE 6'x9'
AutoCAD SHX Text OFFICE 12'x8'
AutoCAD SHX Text STORAGE 11'x8'
AutoCAD SHX Text PANTRY 6'x8'
AutoCAD SHX Text COUNCIL CHAMBERS 40'x24' 12' CEILING
AutoCAD SHX Text FOYER 10'x20' 12' CEILING
AutoCAD SHX Text
8' HALL' 12' CEILING
AutoCAD SHX Text
ELEC PANEL
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
ELEC SERVICE
AutoCAD SHX Text
ELEC PANELS
AutoCAD SHX Text
GENERATOR SWITCHGEAR
AutoCAD SHX Text
RESIDENTIAL HOOD
AutoCAD SHX Text
BEAM
AutoCAD SHX Text LIBRARY/CLASSROOM 66'x25' 7' CEILING
AutoCAD SHX Text
BEAM
AutoCAD SHX Text
STAIR ACCESS
AutoCAD SHX Text STORAGE 16'x9'
AutoCAD SHX Text STORAGE 8'x4'
AutoCAD SHX Text UTILITY/ELEC ROOM 14'x25' 7' CEILING
AutoCAD SHX Text
ABANDONED BRICK CHIMNEY
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
EMERGENCY MEANS OF EGRESS ROUTES
1 4
2 3
LEGEND
# ROOM NUMBER
KEY TABLE
NO. MANUFACTURER CODE DOORS
AMERICAN LOCK CO. NONE PAVILION
SCHLAGE 00496-5
MASTER KEY - ALL BUT FRONT DOORS,
OLD COUNCIL CHAMBERS, RM6, OLD
PLANNING OFFICE
SCHLAGE PRIMUS 00496-2A PLANNING DOORS/AFTER SCHOOL
PROGRAM
SCHLAGE PRIMUS 00496-DAB5 FRONT DOOR
SCHLAGE 35858 OFFICE DOOR
SCHLAGE UNMARKED OLD COUNCIL CHAMBERS MAIN
DOOR/RM1
SCHLAGE L00496 CLASSROOM AND BACK HALL/RM3
SCHLAGE 00496-DAB19 KITCHEN/RM5
KEY BOX 5011 CODE IS THE SAME ON ALL BOXES
KB
DOOR TABLE
NO. MATERIAL
STEEL
STEEL CLAD
WOOD
WOOD 3-PANEL
WOOD 6-PANEL
WOOD WITH
GLASS WINDOW
FIBERGLASS
WITH GLASS
WINDOW
HOLLOW CORE
WOOD
SOLID CORE
WOOD
* HAS PUSHBAR
S
STW
W3
W6
WG
FG
HW
SW
D at e Sh ee t N o.
w w w .c iv ilw es t.c om
DATE:7/7/23 FILE:O:\CW_Projects\3401 Yachats\3401-009 Yachats Commons Assessment\03 Planning\DWGs\Commons Working 6-29-23.dwg
R
EV
D
AT
E
D
ES
C R
IP
TI
O N
BY
D
ES
IG
N
ED
B
Y:
D
R
AW
N B
Y:
C
H
EC
KE
D
B Y:
PR
O
JE
C
T N
O
N
EW
PO
R
T O
R
SW
0T H
S T.
1-
4-
EX2
YA
C
H
AT
S C
O M
M O
N S
BU
IL
D
IN
G
AS
SE
SS
M
EN
T
C
IT
Y O
F
YA
C H
AT
S
TE
G
TE
G
Va lu e
JULY 2023
H W
Y
N
YA
C H
AT
S, L
IN
C O
LN
C
O U
N
TY
, O R
NDOORS, WINDOWS & SECURITY
EX2
NO KEYS FOR THESE DOORSNO KEYS FOR THIS DOOR
NO KEYS FOR
THIS DOOR
STW
S
W3
SW
S
S
S*
WG
WG
W6
S
FG S*
SW
SHW
HW
HW
S
S
WG
S*
S
SW
W6
HW
HW
W6
FG
SW
KB
KB
KB
KB
KB
APPENDIX A
AutoCAD SHX Text
AFTER SCHOOL PROGRAM 30'X25' 12' CEILING
AutoCAD SHX Text CLASSROOM 29'x25' 12' CEILING
AutoCAD SHX Text STORAGE 14'x25'' 12' CEILING
AutoCAD SHX Text
GYMNASIUM 41'X62' 16' CEILING
AutoCAD SHX Text RECREATION ROOM 24'x40' 12' CEILING
AutoCAD SHX Text STAGE 41'x18' 14' CEILING
AutoCAD SHX Text
CLASS ROOM 15'X27' 12' CEILING
AutoCAD SHX Text
8' HALL 12' CEILING
AutoCAD SHX Text OFFICE 15'x12'' 12' CEILING
AutoCAD SHX Text COMMERCIAL KITCHEN/CLASSROOM 41'x24' 12' CEILING
AutoCAD SHX Text DAYCARE/CLASS ROOM 40'x24' 12' CEILING
AutoCAD SHX Text
HANDICAP RAMP
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
HOOD
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
ELEC SERVICE
AutoCAD SHX Text
GENERATOR
AutoCAD SHX Text
PORCH
AutoCAD SHX Text
OPEN ABOVE
AutoCAD SHX Text
6' HALL
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
OPEN TO BELOW
AutoCAD SHX Text STORAGE 5'x9' 12' CLG
AutoCAD SHX Text STORAGE 8'x9' 12' CEILING
AutoCAD SHX Text
ATTIC ACCESS
AutoCAD SHX Text MENS ROOM 17'x9' 12' CEILING
AutoCAD SHX Text WOMENS ROOM 14'x9' 12' CEILING
AutoCAD SHX Text
12' CEILING
AutoCAD SHX Text UNISEX 4'x9'
AutoCAD SHX Text
12' CEILING THROUGHOUT
AutoCAD SHX Text OFFICE 6'x9'
AutoCAD SHX Text OFFICE 12'x8'
AutoCAD SHX Text STORAGE 11'x8'
AutoCAD SHX Text PANTRY 6'x8'
AutoCAD SHX Text COUNCIL CHAMBERS 40'x24' 12' CEILING
AutoCAD SHX Text FOYER 10'x20' 12' CEILING
AutoCAD SHX Text
8' HALL' 12' CEILING
AutoCAD SHX Text
ELEC PANEL
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
ELEC SERVICE
AutoCAD SHX Text
ELEC PANELS
AutoCAD SHX Text
GENERATOR SWITCHGEAR
AutoCAD SHX Text
RESIDENTIAL HOOD
AutoCAD SHX Text
BEAM
AutoCAD SHX Text LIBRARY/CLASSROOM 66'x25' 7' CEILING
AutoCAD SHX Text
BEAM
AutoCAD SHX Text
STAIR ACCESS
AutoCAD SHX Text STORAGE 16'x9'
AutoCAD SHX Text STORAGE 8'x4'
AutoCAD SHX Text UTILITY/ELEC ROOM 14'x25' 7' CEILING
AutoCAD SHX Text
ABANDONED BRICK CHIMNEY
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
DOORS, WINDOWS & SECURITY
1 4
2 3
LEGEND
# ROOM NUMBER
HVAC TABLE
NO. MANUFACTURER TYPE
FUJITSU HEAT PUMP
FUJITSU CONDENSER
MITSUBISHI HEAT PUMP
MITSUBISHI CONDENSER
CADET ELECTRIC WALL HEATER
CADET THERMOSTAT
FORCED AIR COLD AIR
RETURN
FORCED AIR HEAT
REGISTER
MITSUBISHI ELECTRIC FORCED AIR
FURNACE
GAS HEATER
FORCED AIR ZONE
MITSUBISHI HEAT PUMP
LARGE CAPACITY ZONE
INDIVIDUAL HEAT PUMP
ZONES
CADET WALL HEATER ZONE
FHP
FC
MHP
MC
CH
CT
CAR
HAR
EFF
GH
D at e Sh ee t N o.
w w w .c iv ilw es t.c om
DATE:7/7/23 FILE:O:\CW_Projects\3401 Yachats\3401-009 Yachats Commons Assessment\03 Planning\DWGs\Commons Working 6-29-23.dwg
R
EV
D
AT
E
D
ES
C R
IP
TI
O N
BY
D
ES
IG
N
ED
B
Y:
D
R
AW
N B
Y:
C
H
EC
KE
D
B Y:
PR
O
JE
C
T N
O
N
EW
PO
R
T O
R
SW
0T H
S T.
1-
4-
EX3
YA
C
H
AT
S C
O M
M O
N S
BU
IL
D
IN
G
AS
SE
SS
M
EN
T
C
IT
Y O
F
YA
C H
AT
S
TE
G
TE
G
Va lu e
JULY 2023
H W
Y
N
YA
C H
AT
S, L
IN
C O
LN
C
O U
N
TY
, O R
NHEATING VENTILATION AND AIR CONDITIONING (HVAC)
EX3
FHP
FC
FHP
FC
FHP
FC
MHP
MHP
GH
MHP
MHP
CH
FHPFC
CH CH
CH
CH CH
CT
CT
CT
MC
HAR
CAR
HAR HAR
HAR
HAR
HAR
HAR
HAR
HAR
HAR
EFF
FHP
FC
APPENDIX A
AutoCAD SHX Text
AFTER SCHOOL PROGRAM 30'X25' 12' CEILING
AutoCAD SHX Text CLASSROOM 29'x25' 12' CEILING
AutoCAD SHX Text STORAGE 14'x25'' 12' CEILING
AutoCAD SHX Text
GYMNASIUM 41'X62' 16' CEILING
AutoCAD SHX Text RECREATION ROOM 24'x40' 12' CEILING
AutoCAD SHX Text STAGE 41'x18' 14' CEILING
AutoCAD SHX Text
CLASS ROOM 15'X27' 12' CEILING
AutoCAD SHX Text
8' HALL 12' CEILING
AutoCAD SHX Text OFFICE 15'x12'' 12' CEILING
AutoCAD SHX Text COMMERCIAL KITCHEN/CLASSROOM 41'x24' 12' CEILING
AutoCAD SHX Text DAYCARE/CLASS ROOM 40'x24' 12' CEILING
AutoCAD SHX Text
HANDICAP RAMP
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
HOOD
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
ELEC SERVICE
AutoCAD SHX Text
GENERATOR
AutoCAD SHX Text
PORCH
AutoCAD SHX Text
OPEN ABOVE
AutoCAD SHX Text
6' HALL
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
OPEN TO BELOW
AutoCAD SHX Text STORAGE 5'x9' 12' CLG
AutoCAD SHX Text STORAGE 8'x9' 12' CEILING
AutoCAD SHX Text
ATTIC ACCESS
AutoCAD SHX Text MENS ROOM 17'x9' 12' CEILING
AutoCAD SHX Text WOMENS ROOM 14'x9' 12' CEILING
AutoCAD SHX Text
12' CEILING
AutoCAD SHX Text UNISEX 4'x9'
AutoCAD SHX Text
12' CEILING THROUGHOUT
AutoCAD SHX Text OFFICE 6'x9'
AutoCAD SHX Text OFFICE 12'x8'
AutoCAD SHX Text STORAGE 11'x8'
AutoCAD SHX Text PANTRY 6'x8'
AutoCAD SHX Text COUNCIL CHAMBERS 40'x24' 12' CEILING
AutoCAD SHX Text FOYER 10'x20' 12' CEILING
AutoCAD SHX Text
8' HALL' 12' CEILING
AutoCAD SHX Text
ELEC PANEL
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
ELEC SERVICE
AutoCAD SHX Text
ELEC PANELS
AutoCAD SHX Text
GENERATOR SWITCHGEAR
AutoCAD SHX Text
RESIDENTIAL HOOD
AutoCAD SHX Text
BEAM
AutoCAD SHX Text LIBRARY/CLASSROOM 66'x25' 7' CEILING
AutoCAD SHX Text
BEAM
AutoCAD SHX Text
STAIR ACCESS
AutoCAD SHX Text STORAGE 16'x9'
AutoCAD SHX Text STORAGE 8'x4'
AutoCAD SHX Text UTILITY/ELEC ROOM 14'x25' 7' CEILING
AutoCAD SHX Text
ABANDONED BRICK CHIMNEY
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
HEATING VENTILATION AND AIR CONDITIONING (HVAC)
AutoCAD SHX Text
220V DUAL CADET WORKS
AutoCAD SHX Text
220V DUAL CADET TRIPS RESET AFTER A FEW SECONDS
AutoCAD SHX Text
DOESN'T WORK BREAKERS FOR CADET HEATERS LOCATED ADJACENT TO UNIT
AutoCAD SHX Text
220V SINGLE CADET DOESN'T WORK
AutoCAD SHX Text
110V CADET WITH THERMOSTAT WORKS
HANGING GAS HEATER NO THERMOSTAT LOOKS NEW DISCONNECTED? WORKS?
1 4
2 3
LEGEND
# ROOM NUMBER
D at e Sh ee t N o.
w w w .c iv ilw es t.c om
DATE:7/7/23 FILE:O:\CW_Projects\3401 Yachats\3401-009 Yachats Commons Assessment\03 Planning\DWGs\Commons Working 6-29-23.dwg
R
EV
D
AT
E
D
ES
C R
IP
TI
O N
BY
D
ES
IG
N
ED
B
Y:
D
R
AW
N B
Y:
C
H
EC
KE
D
B Y:
PR
O
JE
C
T N
O
N
EW
PO
R
T O
R
SW
0T H
S T.
1-
4-
EX4
YA
C
H
AT
S C
O M
M O
N S
BU
IL
D
IN
G
AS
SE
SS
M
EN
T
C
IT
Y O
F
YA
C H
AT
S
TE
G
TE
G
Va lu e
JULY 2023
H W
Y
N
YA
C H
AT
S, L
IN
C O
LN
C
O U
N
TY
, O R
NROOF AND DRAINAGE
EX4
TPO MEMBRANE
TPO MEMBRANE
TPO
MEMBRANE
COMPOSITE ASPHALT
SHINGLES
COMPOSITE ASPHALT
SHINGLES
R O
LL
ED
A
SP
H
AL
T M
EM
BR
AN
E
NOTES:
NO EAVES. GUTTER IS SAGGING AT CENTER CAUSING
WATER TO RUN DOWN OUTSIDE OF WALL AND INTO
ELECTRICAL ROOM. SEE PHOTO 1&2, SHEET EX5.
WATER IS RUNNING ALONG BUILDING FACE AND ENTERING
CRAWLSPACE OPENNINGS. SEE PHOTO 3-5, SHEET EX5
1&2
EX5
3,4&5
EX5
APPENDIX A
AutoCAD SHX Text
AFTER SCHOOL PROGRAM 30'X25' 12' CEILING
AutoCAD SHX Text CLASSROOM 29'x25' 12' CEILING
AutoCAD SHX Text STORAGE 14'x25'' 12' CEILING
AutoCAD SHX Text
GYMNASIUM 41'X62' 16' CEILING
AutoCAD SHX Text RECREATION ROOM 24'x40' 12' CEILING
AutoCAD SHX Text STAGE 41'x18' 14' CEILING
AutoCAD SHX Text
CLASS ROOM 15'X27' 12' CEILING
AutoCAD SHX Text
8' HALL 12' CEILING
AutoCAD SHX Text OFFICE 15'x12'' 12' CEILING
AutoCAD SHX Text COMMERCIAL KITCHEN/CLASSROOM 41'x24' 12' CEILING
AutoCAD SHX Text DAYCARE/CLASS ROOM 40'x24' 12' CEILING
AutoCAD SHX Text
HANDICAP RAMP
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
HOOD
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
ELEC SERVICE
AutoCAD SHX Text
GENERATOR
AutoCAD SHX Text
PORCH
AutoCAD SHX Text
OPEN ABOVE
AutoCAD SHX Text
6' HALL
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
OPEN TO BELOW
AutoCAD SHX Text STORAGE 5'x9' 12' CLG
AutoCAD SHX Text STORAGE 8'x9' 12' CEILING
AutoCAD SHX Text
ATTIC ACCESS
AutoCAD SHX Text MENS ROOM 17'x9' 12' CEILING
AutoCAD SHX Text WOMENS ROOM 14'x9' 12' CEILING
AutoCAD SHX Text
12' CEILING
AutoCAD SHX Text UNISEX 4'x9'
AutoCAD SHX Text
12' CEILING THROUGHOUT
AutoCAD SHX Text OFFICE 6'x9'
AutoCAD SHX Text OFFICE 12'x8'
AutoCAD SHX Text STORAGE 11'x8'
AutoCAD SHX Text PANTRY 6'x8'
AutoCAD SHX Text COUNCIL CHAMBERS 40'x24' 12' CEILING
AutoCAD SHX Text FOYER 10'x20' 12' CEILING
AutoCAD SHX Text
8' HALL' 12' CEILING
AutoCAD SHX Text
ELEC PANEL
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
ROOF AND DRAINAGE
CLEAR CORRUGATED PLASTIC ROOFING
D at e Sh ee t N o.
w w w .c iv ilw es t.c om
DATE:7/7/23 FILE:O:\CW_Projects\3401 Yachats\3401-009 Yachats Commons Assessment\03 Planning\DWGs\Commons Working 6-29-23.dwg
R
EV
D
AT
E
D
ES
C R
IP
TI
O N
BY
D
ES
IG
N
ED
B
Y:
D
R
AW
N B
Y:
C
H
EC
KE
D
B Y:
PR
O
JE
C
T N
O
N
EW
PO
R
T O
R
SW
0T H
S T.
1-
4-
EX5
YA
C
H
AT
S C
O M
M O
N S
BU
IL
D
IN
G
AS
SE
SS
M
EN
T
C
IT
Y O
F
YA
C H
AT
S
TE
G
TE
G
Va lu e
JULY 2023
H W
Y
N
YA
C H
AT
S, L
IN
C O
LN
C
O U
N
TY
, O R
GYM SOUTH ROOF EDGE FACING EAST
EX5
1 GYM SOUTH ROOF EDGE FACING EAST
EX5
NE BUILDING CORNER - NORTH SIDE
EX5
3 NE BUILDING CORNER - NORTH SIDE
EX5
4 NE BUILDING CORNER - NORTH SIDE
EX5
APPENDIX A
DRAINAGE PHOTOS
1 4
2 3
LEGEND
# ROOM NUMBER
D at e Sh ee t N o.
w w w .c iv ilw es t.c om
DATE:7/7/23 FILE:O:\CW_Projects\3401 Yachats\3401-009 Yachats Commons Assessment\03 Planning\DWGs\Commons Working 6-29-23.dwg
R
EV
D
AT
E
D
ES
C R
IP
TI
O N
BY
D
ES
IG
N
ED
B
Y:
D
R
AW
N B
Y:
C
H
EC
KE
D
B Y:
PR
O
JE
C
T N
O
N
EW
PO
R
T O
R
SW
0T H
S T.
1-
4-
EX6
YA
C
H
AT
S C
O M
M O
N S
BU
IL
D
IN
G
AS
SE
SS
M
EN
T
C
IT
Y O
F
YA
C H
AT
S
TE
G
TE
G
Va lu e
JULY 2023
H W
Y
N
YA
C H
AT
S, L
IN
C O
LN
C
O U
N
TY
, O R
N
ELECTRICAL
EX6
E
E ELEC. BREAKER BOX
E
E E
E E
E E E
E
E
E
E
E
E
E
E
BOX E
BOX D
BOX CBOX B
BOX A
E
E
EX8
EX7
EX7
EX7
EX7
EX7
EX7
EX7
EX7
EX7
EX7
EX7
EX8
EX8
EX8
EX8
EX8
EX8
1-8
EX9
APPENDIX A
AutoCAD SHX Text
AFTER SCHOOL PROGRAM 30'X25' 12' CEILING
AutoCAD SHX Text CLASSROOM 29'x25' 12' CEILING
AutoCAD SHX Text STORAGE 14'x25'' 12' CEILING
AutoCAD SHX Text
GYMNASIUM 41'X62' 16' CEILING
AutoCAD SHX Text RECREATION ROOM 24'x40' 12' CEILING
AutoCAD SHX Text STAGE 41'x18' 14' CEILING
AutoCAD SHX Text
CLASS ROOM 15'X27' 12' CEILING
AutoCAD SHX Text
8' HALL 12' CEILING
AutoCAD SHX Text OFFICE 15'x12'' 12' CEILING
AutoCAD SHX Text COMMERCIAL KITCHEN/CLASSROOM 41'x24' 12' CEILING
AutoCAD SHX Text DAYCARE/CLASS ROOM 40'x24' 12' CEILING
AutoCAD SHX Text
HANDICAP RAMP
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
HOOD
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
ELEC SERVICE
AutoCAD SHX Text
GENERATOR
AutoCAD SHX Text
PORCH
AutoCAD SHX Text
OPEN ABOVE
AutoCAD SHX Text
6' HALL
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
OPEN TO BELOW
AutoCAD SHX Text STORAGE 5'x9' 12' CLG
AutoCAD SHX Text STORAGE 8'x9' 12' CEILING
AutoCAD SHX Text
ATTIC ACCESS
AutoCAD SHX Text MENS ROOM 17'x9' 12' CEILING
AutoCAD SHX Text WOMENS ROOM 14'x9' 12' CEILING
AutoCAD SHX Text
12' CEILING
AutoCAD SHX Text UNISEX 4'x9'
AutoCAD SHX Text
12' CEILING THROUGHOUT
AutoCAD SHX Text OFFICE 6'x9'
AutoCAD SHX Text OFFICE 12'x8'
AutoCAD SHX Text STORAGE 11'x8'
AutoCAD SHX Text PANTRY 6'x8'
AutoCAD SHX Text COUNCIL CHAMBERS 40'x24' 12' CEILING
AutoCAD SHX Text FOYER 10'x20' 12' CEILING
AutoCAD SHX Text
8' HALL' 12' CEILING
AutoCAD SHX Text
ELEC PANEL
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
ELEC SERVICE
AutoCAD SHX Text
ELEC PANELS
AutoCAD SHX Text
GENERATOR SWITCHGEAR
AutoCAD SHX Text
RESIDENTIAL HOOD
AutoCAD SHX Text
BEAM
AutoCAD SHX Text LIBRARY/CLASSROOM 66'x25' 7' CEILING
AutoCAD SHX Text
BEAM
AutoCAD SHX Text
STAIR ACCESS
AutoCAD SHX Text STORAGE 16'x9'
AutoCAD SHX Text STORAGE 8'x4'
AutoCAD SHX Text UTILITY/ELEC ROOM 14'x25' 7' CEILING
AutoCAD SHX Text
ABANDONED BRICK CHIMNEY
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
AutoCAD SHX Text
UP
ELECTRICAL
e Sh ee t N o.
w w w .c iv ilw es t.c om
DATE:7/7/23 FILE:O:\CW_Projects\3401 Yachats\3401-009 Yachats Commons Assessment\03 Planning\DWGs\Commons Working 6-29-23.dwg
R
EV
D
AT
E
D
ES
C R
IP
TI
O N
BY
D
ES
IG
N
ED
B
Y:
D
R
AW
N B
Y:
C
H
EC
KE
D
B Y:
PR
O
JE
C
T N
O
N
EW
PO
R
T O
R
SW
0T H
S T.
1-
4-
EX7
YA
C
H
AT
S C
O M
M O
N S
BU
IL
D
IN
G
AS
SE
SS
M
EN
T
C
IT
Y O
F
YA
C H
AT
S
TE
G
TE
G
Va lu e
JULY 2023
H W
Y
N
YA
C H
AT
S, L
IN
C O
LN
C
O U
N
TY
, O R
FUJITSU HEAT PUMP DISCONNECT (TYP)
EX7
1 ROOM 2/OFFICE ELEC. PANEL
EX7
2 HALLWAY BY RM 4 - ELEC. PANEL (E)
EX7
3 RM5 - ELEC. PANEL (D)
EX7
STAGE LEFT - ELEC. PANEL (C)
EX7
5 STAGE RIGHT - ELEC. PANEL (B)
EX7
6 HALLWAY BY RM 8 - ELEC. PANEL (A)
EX7
7 MITSUBISHI HEAT PUMP DISCONNECT
EX7
APPENDIX A
ELECTRICAL PHOTOS
e Sh ee t N o.
w w w .c iv ilw es t.c om
DATE:7/7/23 FILE:O:\CW_Projects\3401 Yachats\3401-009 Yachats Commons Assessment\03 Planning\DWGs\Commons Working 6-29-23.dwg
R
EV
D
AT
E
D
ES
C R
IP
TI
O N
BY
D
ES
IG
N
ED
B
Y:
D
R
AW
N B
Y:
C
H
EC
KE
D
B Y:
PR
O
JE
C
T N
O
N
EW
PO
R
T O
R
SW
0T H
S T.
1-
4-
EX8
YA
C
H
AT
S C
O M
M O
N S
BU
IL
D
IN
G
AS
SE
SS
M
EN
T
C
IT
Y O
F
YA
C H
AT
S
TE
G
TE
G
Va lu e
JULY 2023
H W
Y
N
YA
C H
AT
S, L
IN
C O
LN
C
O U
N
TY
, O R
GYM SOUND RACK
EX8
1 MISC. ELEC. PANEL - W. EXTERIOR
EX8
2 BASEMENT - ELEC. PANEL
EX8
3 UTILITY ROOM - SWITCHGEAR
EX8
UTILITY ROOM - ELEC. PANEL (1)
EX8
5 UTILITY ROOM - ELEC. PANEL (2)
EX8
6 UTILITY ROOM - ELEC. PANEL (3)
EX8
APPENDIX A
ELECTRICAL PHOTOS
e Sh ee t N o.
w w w .c iv ilw es t.c om
DATE:7/7/23 FILE:O:\CW_Projects\3401 Yachats\3401-009 Yachats Commons Assessment\03 Planning\DWGs\Commons Working 6-29-23.dwg
R
EV
D
AT
E
D
ES
C R
IP
TI
O N
BY
D
ES
IG
N
ED
B
Y:
D
R
AW
N B
Y:
C
H
EC
KE
D
B Y:
PR
O
JE
C
T N
O
N
EW
PO
R
T O
R
SW
0T H
S T.
1-
4-
EX9
YA
C
H
AT
S C
O M
M O
N S
BU
IL
D
IN
G
AS
SE
SS
M
EN
T
C
IT
Y O
F
YA
C H
AT
S
TE
G
TE
G
Va lu e
JULY 2023
H W
Y
N
YA
C H
AT
S, L
IN
C O
LN
C
O U
N
TY
, O R
GENERATOR - BOTTOM S. SIDE
EX9
1 GENERATOR - E-SIDE BASE
EX9
2 GENERATOR FACING NORTH
EX9
GENERATOR - NE CORNER
EX9
4 GENERATOR - W. SIDE
EX9
5 Perkins 4cylinder 30kw GenSet
EX9
APPENDIX A
GENERATOR PHOTOS
Civil West Engineering Services, Inc. Yachats Commons Bldg Assessment Photos
Attic facing east attic facing N (2) attic facing N attic facing NW (2) attic facing NW Attic facing south attic facing west (2) attic facing west attic N side facing E (2) attic N Side facing E Attic N side facing N light over top of siding is visible attic N side facing NE attic roof patch (2) Attic roof patch Basement abandoned boiler pipe (2) Basement abandoned boiler pipe (3)
Basement abandoned boiler pipe (4) Basement abandoned boiler pipe (5) Basement abandoned boiler pipe (6) Basement abandoned boiler pipe (7)
Basement abandoned boiler pipe (8) Basement abandoned boiler pipe (9) Basement abandoned boiler pipe (10) Basement abandoned boiler pipe (11)
APPENDIX B
Basement abandoned boiler pipe (12) Basement abandoned boiler pipe (13) Basement abandoned boiler pipe (14) Basement abandoned boiler pipe (15)
Basement abandoned boiler pipe (16) Basement abandoned boiler pipe (17) Basement abandoned boiler pipe (18) Basement abandoned boiler pipe
Basement abandoned boiler pipes E wall
Basement access W wall Basement cold air return E wall Basement condenser and sewer pipe E side
Basement door to storage E side Basement electrical panel N Wall (2) Basement electrical panel N Wall (3) Basement electrical panel N Wall
Basement Exit Door W Wall Basement exit plan Basement heating duct in ceiling Basement Main Door E wall
Basement Mitsubishi Commercial Heat Exch manuals
Basement Mitsubishi forced air furnace (2)
Basement Mitsubishi forced air furnace (3)
Basement Mitsubishi forced air furnace (4)
Basement Mitsubishi forced air furnace
Basement old boiler hot water pipe Basement old thermo loc Basement plumbing E side (2)
Basement plumbing E side Basement sewer connections E wall draining north
Basement storage pipe gallery (2) Basement storage pipe gallery (3)
Basement storage pipe gallery (4) Basement storage pipe gallery (5) Basement storage pipe gallery Basement Under Stair storage door
Basement under stair storage Basement windows exterior S wall (2) Basement windows exterior S Wall Crawl Space below stage - west side (2)
Crawl Space below stage - west side (3)
Crawl Space below stage - west side (4)
Crawl Space below stage - west side E Side Bldg Fire Alarm Controls
E Side of Bldg Exit Door (2) E Side of bldg Exit Door generator base E side Generator Block No
Generator bottom south side (2) Generator bottom south side Generator E side (2) Generator E Side Base generator E side Generator facing north Generator N side (2) generator N side
Generator NE corner (2) Generator NE corner (3) generator NE corner Generator Top generator w side (2) Generator W side (3) Generator W side (4) generator w side and exhaust
Generator w side Generator gym electric panel N wall gym evac plan (2) gym evac plan gym exit door s wall gym fire extinguisher ne corner gym gas heater N wall (2) gym gas heater N wall (3) gym gas heater N wall gym mitsubishi heat exch remote gym mitsubishi heat exch S wall (2) gym mitsubishi heat exch S wall (3) gym mitsubishi heat exch S wall gym n wall old thermostat location (2) gym n wall old thermostat location (3) gym n wall old thermostat location Gym sound rack N Wall gym stage lights gym storage cadet heater N wall gym storage ceiling gym storage e wall gym storage N wall gym storage s and e walls gym storage s wall (2) gym storage s wall Key - Pavilion1 Key E Side of bldg Exit Door Rm3.2
Key E Side of bldg Exit Door Rm3 Key Main Doors1 DAB5 Key Main Doors2 DAB5 Key Master 2
Key Master Key Pavilion2 Key Rm1 2 Key Rm1
Key Rm2 2 Key Rm2 Key Room2 office door Key Room2 office door2
Main Bldg Ext - Concrete Popping - W Side1
Main Bldg Ext - Concrete Popping - W Side2
Mai…
This is the start of the file's text. The full file is on GovTribe.