Y26-734_Drawings.pdf
PDF 3 MB Posted
- Attached to
- Corrections Video Visitation Generator
- Solicitation number
- Y26-734
- Issued by
- Orange County, Orlando City, Florida
About this file
These are engineering drawings and specifications for Orange County, Florida's Corrections Video Visitation Center generator installation project (Y26-734). The project involves installing a new 100 kW/125 kVA standby generator set with an automatic transfer switch to provide emergency power for the facility located at 3000 39th Street, Orlando, Florida. The design basis specifies a natural gas generator as the primary option, with a diesel generator available as an additive alternate. The scope of work includes electrical installation of the generator, associated conduit and wiring, an automatic transfer switch, a new service entrance disconnect switch rated at 800 amperes, generator annunciator panels, remote monitoring capabilities, concrete pad construction, chain-link fencing around the equipment, grounding systems, and natural gas piping connections. The project is designed in accordance with the 2023 Florida Building Code, 2020 National Electrical Code, and applicable Florida fuel gas codes. Sealed bids are due by 4:00 pm EST on Tuesday, May 19, 2026, with electronic submissions required through the OpenGov e-Procurement Platform. Questions must be submitted by Tuesday, May 5, 2026 at 5:00 pm EST.
The estimated project cost is $355,000. The drawings include electrical schematics, panel schedules, one-line diagrams, grounding details, natural gas piping plans, and construction details prepared by Hanson Professional Services Inc. The existing electrical system serves the facility at 208Y/120V, three-phase with a current peak demand of 150.86 amperes and 54.35 kVA. The contractor is responsible for coordinating with Orange County utilities for natural gas service extension and meter installation, verifying field conditions, obtaining all necessary inspections, and completing as-built documentation. All work must comply with local codes and ordinances, and the contractor must employ licensed and qualified subcontractors for all divisions of work.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Corrections_Video_Visitation_Generator.pdf | ||
| Y26-734_Specifications.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Engineering | Planning | Allied Services
Offices Nationwide www.hanson-inc.com
Hanson Professional Services Inc.
CONSULTANTS
EB0007061
AA0003116
IB0001058
SHEET TITLE
REVIEWED BY:
DRAWN BY:
DESIGN BY:
PROJECT NO:
ISSUE:
© Copyright Hanson Professional Services Inc. 2024
SEAL
MARK DATE DESCRIPTION
/9
/2
:0 :2
P
M
C
R e vi t_ L o c a l_
\E
-O C
G e n e ra to r
R e lo c a ti o n -2 b m a ld o n a d o X
W
.r v t
2300 Maitland Center Parkway, Suite 310 Maitland, FL 32751
(407) 790-7397
ORANGE COUNTY
CORRECTIONS -
VIDEO VISITATION
CENTER - NEW
GENERATOR
3000 39th Street, Orlando, FL 32839
COVER SHEET
G-001
06/09/2025
19G0181
BM
BM
AJT
100% CD
DRAWING INDEX
SHEET
NO. SHEET NAME
G-001 COVER SHEET
E-001 GENERAL ELECTRICAL NOTES, LEGEND AND ABBREVIATIONS
E-101 ELECTRICAL OVERALL PLAN
E-201 ELECTRICAL ENLARGED PLAN
E-501 ONE-LINE DIAGRAMS AND PANEL SCHEDULE
E-601 DETAILS
E-602 DETAILS
M-101 MECHANICAL NATURAL GAS PIPING PLAN
3000 39th Street, Orlando, FL 32839
100% CD
June 9, 2025
ORANGE COUNTY CORRECTIONS - VIDEO
VISITATION CENTER - NEW GENERATOR
HANSON PROFESSIONAL SERVICES INC.
2300 Maitland Center Parkway, Suite 310
Maitland, FL 32751
(407) 790-7397
CODES IN EFFECT AT TIME OF DRAWING SUBMITTAL
FLORIDA BUILDING CODE, EIGHTH EDITION (2023)
FLORIDA ENERGY CONSERVATION CODE, EIGHTH EDITION (2023)
FLORIDA FUEL GAS CODE, EIGHTH EDITION (2023)
NEC (NFPA 70) 2020 EDITION
TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THE PLANS AND SPECIFICATIONS
COMPLY WITH THE 2023 FLORIDA BUILDING CODE WITH ALL CURRENT
AMENDMENTS.
PROJECT INFORMATION
SCOPE OF WORK
ELECTRICAL:
PROVIDING EMERGENCY POWER BY INSTALLING A NEW GENERATOR SET AND
AUTOMATIC TRANSFER SWITCH.
BASIS OF DESIGN: NATURAL GAS GENERATOR
ALTERNATIVE: DIESEL GENERATOR
MEP ENGINEERS
ORANGE COUNTY MAYOR
Jerry L. Demings
DISTRICT 1 COMMISSIONER
Nicole H. Wilson
DISTRICT 2 COMMISSIONER
Christine Moore
DISTRICT 5 COMMISSIONER
Kelly Semrad
DISTRICT 6 COMMISSIONER
Michael "Mike" Scott
DISTRICT 4 COMMISSIONER
Maribel Gomez Cordero
DISTRICT 3 COMMISSIONER
Mayra Uribe
PROJECT LOCATION
NOTE: SOME SYMBOLS SHOWN IN ELECTRICAL LEGEND MAY NOT APPLY TO THIS PROJECT.
ELECTRICAL SYMBOL LEGEND
ELECTRICAL SYMBOL NOTES
*** DISTANCE TO HIGHEST OPERABLE PART OF EQUIPMENT
ALL DISTANCES ARE TO CENTER OF DEVICE OR EQUIPMENT UNLESS OTHERWISE NOTED. DEVICES INDICATED AT 48" MAY NOT BE INSTALLED WITH ANY OPERABLE PART HIGHER THAN 48". DEVICES MAY BE INSTALLED IN CONCRETE MASONRY UNITS WITH THE TOP OF THE DEVICE AT 48". * DISTANCE ABOVE TOP OF DOOR FRAME ** DISTANCE TO TOP OF EQUIPMENT OR DEVICE **** DISTANCE BELOW CEILING
PP2-6c d
1,3,5
SF-1
2,4,6
T1
PP2
DEVICES. "PP2" INDICATES PANEL, "6" INDICATES THE CIRCUIT NUMBER(S). THE SWITCH DESIGNATION (IF APPLICABLE) IS INDICATED BY A LOWER CASE LETTER. EXAMPLE: SPLIT DUPLEX RECEPTACLE IS CONNECTED TO CIRCUIT 6 IN PANEL PP2 AND ONE RECEPTACLE OUTLET IS CONTROLLED BY SWITCH "c".
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER. EXAMPLE:
3 WAY SWITCH "d" TO CONTROL LIGHTING FIXTURES INDICATED BY "d".
SPECIAL CONNECTIONS. THE EQUIPMENT IS INDICATED BY A NUMBER IN A CIRCLE. SEE
THE MOTOR AND EQUIPMENT SCHEDULE FOR THE LOAD DESCRIPTION AND TYPE OF
CONNECTION. THE CIRCUIT DESIGNATION IS INDICATED BY A NUMBER(S) ADJACENT TO
THE SYMBOL. EXAMPLE: EQUIPMENT NO. 1; 3 PHASE CONNECTION TO CIRCUITS 1, 3, 5.
MOTOR CONNECTIONS. THE MOTOR IS INDICATED BY A NUMBER WITHIN OR
CHARACTERS ADJACENT TO THE MOTOR SYMBOL. SEE THE MOTOR AND EQUIPMENT
SCHEDULE FOR THE MOTOR DESCRIPTION AND ELECTRICAL REQUIREMENTS. THE
CIRCUIT DESIGNATION IS INDICATED BY A NUMBER(S) ADJACENT TO THE SYMBOL.
EXAMPLE: MOTOR SF-1; 3 PHASE CONNECTION TO CIRCUITS 2, 4, 6.
TRANSFORMERS. THE TRANSFORMER TYPE IS INDICATED BY A NUMBER FOLLOWING
THE UPPER CASE LETTER "T". SEE THE TRANSFORMER SCHEDULE OR THE SINGLE LINE
DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND REQUIREMENTS. EXAMPLE:
TRANSFORMER TYPE "T1".
PANELBOARDS. PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING SIDE OF
RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR DESIGNATION CODES.
CONDUIT SHOWN WITHOUT SLASH MARKS SHALL CONTAIN 2 # 12 CONDUCTORS IN 3/4"
CONDUIT UNLESS SPECIFIC EQUIPMENT REQUIRES A DIFFERENT SIZE.
HOME RUN TO BRANCH CIRCUIT PANELBOARD. THE PANELBOARD DESIGNATION AND
CIRCUITS ARE SHOWN ADJACENT TO THE HOME RUN ARROW. CIRCUIT BREAKER SIZES
(AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANELBOARD SCHEDULE WITH THE
CORRESPONDING PANELBOARD AND CIRCUIT DESIGNATION. EXAMPLE: HOME RUN TO
PANELBOARD RP2; CIRCUITS 1, 3, 5.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE A UNIT
TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
RP2-1,3,5
ELECTRICAL GENERAL NOTES
1. ALL ELECTRICAL WORK SHALL COMPLY WITH THE 2020 NATIONAL ELECTRICAL CODE, THE FLORIDA BUILDING CODE, THE NATIONAL FIRE CODES, STATE REQUIREMENTS AND ALL APPLICABLE LOCAL
CODES AND ORDINANCES.
2. SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION AND ALL REQUIREMENTS NOT INDICATED ON THE
DRAWINGS.
3. IT IS THE INTENT OF THESE PLANS AND SPECIFICATIONS THAT A COMPLETE AND WORKABLE ELECTRICAL INSTALLATION BE PROVIDED FOR ALL THE EQUIPMENT DESCRIBED OR SHOWN AS BEING IN THIS CONTRACT. ANY ITEMS WHICH ARE CLEARLY NECESSARY FOR THE COMPLETION OF THE WORK OR ITS APPURTENANCES SHALL BE CONSIDERED A PORTION OF THE WORK AND SHALL BE PROVIDED AND
INSTALLED BY THE CONTRACTOR EVEN THOUGH NOT DIRECTLY SPECIFIED.
4. THE PLANS AND SPECIFICATIONS ARE COMPLIMENTARY, AND THAT WHICH IS CALLED FOR BY ONE SHALL BE AS BINDING AS IF CALLED FOR BY BOTH. IN THE EVENT THAT THE PLANS AND SPECIFICATIONS CONFLICT, THE MORE STRINGENT SHALL APPLY. ANY DISCREPANCIES IN THE DRAWINGS SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE DESIGN PROFESSIONAL PRIOR TO SUBMITTAL OF BID.
5. THE PLANS INDICATE THE GENERAL ARRANGEMENT OF THE WORK TO BE PERFORMED AND ARE DIAGRAMMATIC ONLY. ALL DIMENSIONS AND EQUIPMENT LOCATIONS SHALL BE VERIFIED IN THE FIELD.
6. VISIT AND CAREFULLY EXAMINE THOSE PORTIONS OF THE BUILDING AND SITE AFFECTED BY THIS WORK BEFORE SUBMITTING PROPOSALS, SO AS TO BECOME FAMILIAR WITH EXISTING CONDITIONS AND DIFFICULTIES THAT WILL AFFECT EXECUTION OF THE WORK. SUBMISSION OF A PROPOSAL WILL BE CONSTRUED AS EVIDENCE THAT SUCH EXAMINATION HAS BEEN MADE AND LATER CLAIMS FOR LABOR, EQUIPMENT OR MATERIALS REQUIRED BECAUSE OF DIFFICULTIES ENCOUNTERED WILL NOT BE
RECOGNIZED.
7. THE CONTRACTOR SHALL THOROUGHLY REVIEW THE PROJECT TO ENSURE THAT ALL WORK SHALL MEET OR EXCEED THE ABOVE REQUIREMENTS. ANY ALLEGED DISCREPANCIES SHALL BE BROUGHT TO
THE OWNER'S AND ENGINEER'S ATTENTION PRIOR TO THE START OF WORK.
8. THE CONTRACTOR IS DIRECTED TO OBTAIN COPIES OF ALL RELATED PLANS, SPECIFICATIONS, SHOP
DRAWINGS AND ADDENDUM TO COORDINATE THE RELATED WORK AND SCHEDULING.
9. VERIFY EXISTING CONDITIONS IN FIELD AND COORDINATE WITH ALL TRADES PRIOR TO INSTALLING OR
FABRICATING EQUIPMENT.
10. DRAWINGS ARE DIAGRAMMATIC IN NATURE. COORDINATE EXACT LOCATION OF ALL CEILING MOUNTED EQUIPMENT SO ALL SERVICEABLE COMPONENTS CAN BE EASILY ACCESSED. REMOVAL OR RELOCATION
OF LIGHTING FIXTURES FOR SERVICE ACCESS IS NOT ACCEPTABLE. THE CONTRACTOR SHALL
REINSTALL EQUIPMENT THAT HAS INADEQUATE OR UNSAFE ACCESSIBILITY. LOCATE ALL OTHER
EQUIPMENT WITH MANUFACTURER RECOMMENDED ACCESS FOR OPERATION AND MAINTENANCE.
11. CONTRACTOR SHALL NOT CONCEAL ANY WORK UNTIL INSPECTED BY ELECTRICAL INSPECTOR AND/OR ARCHITECT/ENGINEER. CONTRACTOR SHALL NOTIFY A/E OF A SCHEDULED INSPECTION TIME WITHIN 72
HOURS. GENERAL CONTRACTOR SHALL NOT CONCEAL WORK UNTIL APPROVED, REGARDLESS OF
SCHEDULE.
12. PRIME CONTRACTOR IS RESPONSIBLE TO HAVE LICENSED AND QUALIFIED SUBCONTRACTORS
PERFORMING ALL WORK.
13. ALL CHANGES MADE IN THE FIELD SHALL BE RECORDED BY THE CONTRACTOR(S) ON AS-BUILT
DRAWINGS, SHOP DRAWINGS, AND IN MAINTENANCE MANUALS.
14. THE SIZE, LOCATION AND ELECTRICAL REQUIREMENTS AND SERVICE CLEARANCES OF EQUIPMENT INSTALLED UNDER DIVISION 26, ELECTRICAL, SHALL BE COORDINATED WITH ALL OTHER TRADES.
15. WHERE CROWDED LOCATIONS EXIST OR WHERE THERE IS A POSSIBILITY OF CONFLICT BETWEEN
TRADES, CONTRACTOR SHALL MAKE COMPOSITE DRAWINGS SHOWING THE EXACT LOCATION OF
PANELBOARDS, SWITCHBOARDS, TRANSFORMERS, CONDUIT AND EQUIPMENT AND MECHANICAL PIPING, DUCTWORK, AND OTHER ARCHITECTURAL APPURTENANCES. DRAWINGS SHALL BE BASED ON FIELD
MEASUREMENTS AND, AFTER CONSULTATION AND AGREEMENT BETWEEN THE TRADES, SHALL BE
APPROVED BY THE ARCHITECT/ENGINEER PRIOR TO INSTALLATION OF THE WORK.
16. NOTIFY ENGINEER OF ANY CONFLICTS PRIOR TO PURCHASING EQUIPMENT AND PRIOR TO CUTTING
OPENINGS.
17. ALL BARE METAL SURFACES SHALL BE PRIMED AND PAINTED TO PREVENT ANY RUST, INCLUDING, BUT
NOT LIMITED TO, ANGLE FRAMING, UNIT SUPPORTS, MOUNTING HARDWARE, ETC.
18. ALL WORK SHALL BE CONSTRUCTED TO MEET ANY PHASING REQUIREMENTS OF THE PROJECT AS MAY
BE OUTLINED IN THE DRAWINGS AND/OR SPECIFICATIONS.
19. RACEWAYS AND ELECTRICAL EQUIPMENT HAVE BEEN LOCATED AND ARRANGED TO MINIMIZE THE
INTERFERENCE OF EQUIPMENT WITH THE STRUCTURE. THE CONTRACTOR SHALL THOROUGHLY
FAMILIARIZE THEMSELVES WITH THE WORK TO BE PERFORMED BY OTHER TRADES AND THE PHYSICAL CHARACTERISTICS OF THE STRUCTURE IN ORDER TO SCHEDULE AND INSTALL EQUIPMENT AND TO MINIMIZE POSSIBLE INTERFERENCE. FAILURE TO PROPERLY COMMUNICATE AND SCHEDULE WORK WITH OTHER TRADES RESULTING IN ADDITIONAL WORK AND MATERIAL, SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. THE MODIFICATIONS REQUIRED TO RESOLVE THE CONFLICT SHALL BE DECIDED BY
THE OWNER AND THE COST OF THE MODIFICATIONS SHALL BE BORNE BY THE CONTRACTOR.
20. ALL PANELBOARDS SHALL BE PROVIDED WITH A PRINTED DIRECTORY SHOWING CIRCUIT NUMBERS AND
A COMPLETE DESCRIPTION OF EACH CIRCUIT.
21. MINIMUM TRADE SIZE CONDUIT PERMITTED SHALL BE 3/4 INCH UNLESS NOTED OTHERWISE. TYPE AC AND TYPE MC CABLE SHALL NOT BE PERMITTED FOR USE ANYWHERE EXCEPT FOR LIGHTING FIXTURE
WHIPS NOT EXCEEDING 6'-0" IN LENGTH.
22. ALL SECONDARY FEEDERS AND BRANCH CIRCUIT CONDUCTORS SHALL BE COPPER WITH 600 VOLT INSULATION TYPE THHN, THW OR THWN. (MINIMUM SIZE SHALL BE NO. 12 AWG.) CONTRACTOR SHALL PROVIDE AND INSTALL ALL PHASE (A, B, C, AS REQUIRED) CONDUCTORS, NEUTRAL CONDUCTORS, AND
GROUND CONDUCTORS AS NECESSARY FOR A COMPLETE AND OPERABLE SYSTEM. NO INDIVIDUAL
CONDUCTOR SPECIFICATION SHALL BE CONSTRUED AS REQUIRING ONLY ONE CONDUCTOR. A
COMPLETE AND OPERABLE SYSTEM IS INTENDED BY THE CONSTRUCTION DOCUMENTS AND THE
CONTRACTOR SHALL PROVIDE AND INSTALL ALL NECESSARY WIRING AND CONDUCTORS AS REQUIRED
TO DELIVER A COMPLETE AND OPERABLE ELECTRICAL SYSTEM TO THE OWNER. NO ADDITIONAL
COMPENSATION WILL BE MADE TO THE CONTRACTOR FOR UNDER-ESTIMATING AND/OR MIS-
CALCULATING THEIR WIRING AND CABLING RESPONSIBILITIES.
23. ALL ELECTRICAL WIRING DEVICES INDICATED TO BE INSTALLED IN MASONRY WALLS OR FLOORS SHALL
BE FLUSH MOUNTED, UNLESS OTHERWISE NOTED.
24. ALL CONDUIT RUNS SHALL BE CONCEALED UNLESS SPECIFICALLY NOTED OTHERWISE OR PRIOR
APPROVED BY OWNER FOR SURFACE MOUNTING.
25. ALL CONDUITS SHALL HAVE A SEPARATE GREEN GROUND CONDUCTOR INSTALLED FOR GROUNDING.
26. ALL FEEDER AND BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED FOR THE MAXIMUM VOLTAGE DROP ALLOWED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, ENERGY CONSERVATION, CHAPTER 4, SECTION C405.7.3. THE ELECTRICAL CONTRACTOR SHALL CALCULATE VOLTAGE DROP AND ADJUST CONDUCTORS AS NEEDED. FOR DESIGN LOADS, A MAXIMUM VOLTAGE DROP OF 2% IS PERMITTED FOR FEEDER CONDUCTORS AND A MAXIMUM VOLTAGE DROP OF 3% IS PERMITTED FOR BRANCH CIRCUIT
CONDUCTORS. CONTRACTOR SHALL NOT DECREASE CONDUCTOR SIZES NOTED ON PLAN.
CONTRACTOR SHALL ONLY INCREASE CONDUCTOR SIZES NOTED IF NEEDED TO MEET MINIMUM CODE
REQUIREMENTS.
27. THE CONTRACTOR SHALL PROVIDE AND INSTALL CHROME FINISHED METAL ESCUTCHEONS TO FINISH THE HOLES OR SLEEVES OFF, INCLUDING THE OUTSIDE AND INSIDE OF THE EXTERIOR WALLS AND ANY OTHER PLACE WHERE THE PENETRATION IS VISIBLE, FOR ALL ELECTRICAL PIPES, CONDUITS, AND PENETRATIONS MADE OR OTHERWISE NECESSARY FOR CONSTRUCTION OF THE ELECTRICAL SYSTEMS.
28. THE CONTRACTOR SHALL MAKE AND PERFORM ALL EXOTHERMIC WELDING PROCEDURES (CADWELD) IN ACCORDANCE WITH THE APPLICABLE ANSI STANDARDS INCLUDING SAFETY IN WELDING AND CUTTING, AND IN STRICT ACCORDANCE WITH THE MANUFACTURER'S WRITTEN INSTALLATION AND HANDLING INSTRUCTIONS. ALL EXOTHERMIC WELDS (CADWELDS) SHALL BE INDIVIDUALLY DOCUMENTED AND CERTIFIED BY THE INSTALLING CONTRACTOR AND SHALL BE UNIQUELY RECORDED ON THE AS-BUILT
DRAWINGS. ALL DOCUMENTATION SHALL BEAR THE CONTRACTORS SIGNED CERTIFICATION OF
PROPERLY COMPLETED WELDS AND SHALL BE SUBMITTED TO THE OWNER FOR THEIR PERMANENT
RECORDS.
29. ALL ELECTRICAL EQUIPMENT FEEDERS, BRANCH CIRCUIT CONDUCTORS, AND DEVICE AND EQUIPMENT
TERMINATIONS SHALL BE RATED FOR A MINIMUM OF 75ºC UNLESS OTHERWISE NOTED.
72"** CIRCUIT BREAKER PANEL
72"**
72"**
T1
POWER OR DISTRIBUTION PANEL
TRANSFORMER (TYPE DENOTED)
SPECIAL CABINET
GENERATOR (KVA DENOTED)25 KVA
VARIABLE FREQUENCY DRIVE
EQUIPMENT
VFD
SR
SYMBOL
LV
UE
EX
UHVE
OHE
OHT
J
HT AFF
FLEXIBLE CONDUIT OR FIXTURE WHIP
UNDERFLOOR RACEWAY SYSTEM
CABLE TRAY (TYPE DENOTED)
CONDUIT TRANSITION DOWN
CONDUIT TRANSITION UP
BRANCH CIRCUIT HOME RUN (NUMBER AND
SIZE OF CONDUCTORS AS PER N.E.C. -
NUMBERS DENOTE PANEL AND CIRCUIT)
UNDERGROUND HIGH VOLTAGE ELECTRICAL
UNDERGROUND ELECTRICAL
LOW VOLTAGE POWER WIRING
EXISTING CONDUIT
OVERHEAD TELEPHONE
OVERHEAD ELECTRIC
CONDUIT EXPOSED
SURFACE RACEWAY
CONDUIT STUBBED OUT
CONDUIT CONCEALED BELOW FLOOR
CONDUIT CONCEALED IN WALL OR OVERHEAD
DESCRIPTION
UNDERGROUND TELEPHONEUT
UCOM UNDERGROUND COMMUNICATIONS
UTV UNDERGROUND CABLE TELEVISION (CATV OR CCTV)
UFIBR UNDERGROUND FIBER OPTIC
CONDUIT SLEEVE (SIZE DENOTED)
A-1, 3, 5
RACEWAY & CONDUCTORS
PUSH BUTTON
SINGLE RECEPT
SPLIT DUPLEX RECEPT
FOURPLEX RECEPT
DUPLEX RECEPT
RECEPT ON EMERGENCY CKT (DUPLEX SHOWN)
ISOLATED GROUND RECEPT (DUPLEX SHOWN)
240 VOLT RECEPT
EQUIPMENT PLUG
RECEPT ON DROP CORD (DUPLEX SHOWN)
RECEPT ON CORD REEL (DUPLEX SHOWN)
FLOOR RECEPT (DUPLEX SHOWN)
AS NOTED J
AS NOTED
72"**
72"**
PS
FS
R
72"**
72"**
72"**
48"
72"**
72"**
BUS DUCT WITH PLUG UN DISCONNECT (FUSED)
ENCLOSED CIRCUIT BREAKER
PRESSURE SWITCH
RELAY
COMB. MOTOR STARTER (NON-FUSED)
MAG MOTOR STARTER OR CONTACTOR
SAFETY DISC SW (FUSED)
SAFETY DISC SW (NON-FUSED)
COMB MOTOR STARTER (FUSED)
MANUAL MTR STR (W/OVERLOADS)
MOTOR (SEE SCHEDULE)
DAMPER MOTOR
AS NOTED
AS NOTED
J J
P
18"
18"
STATIC GROUND RECEPTACLE
SPECIAL CONNECTION (SEE SCHEDULE)
SPECIAL RECEPT OR CONN (SEE SCHEDULE)
JUNCTION BOX
PULL BOX
POWER POLE (OPEN OFFICE STYLE)
MULTIOUTLET ASSEMBLY
MULTIOUTLET ASSEMBLY
48"
18"
18"
18"
18"
18"
18"
18"
FOURPLEX RECEPTACLE ON EMERGENCY CIRCUIT18"
PB
FLOAT SWITCH
DEVICES
SYMBOLHT AFF DESCRIPTION
ASC - APPLICATION SPECIFIC CONTROLLER
ATC - AUTOMATIC TEMPERATURE CONTROL
FAAP - FIRE ALARM ANNUNCIATOR PANEL
GAP - GENERATOR ANNUNCIATOR PANEL
FT - FOOT OR FEET
HP - HORSE POWER
FTU - FAN TERMINAL UNIT
GFI - GROUND FAULT INTERRUPTING
GND - GROUND
HZ - HERTZ (CYCLES PER SECOND)
FCU - FAN COIL UNIT
FLA - FULL LOAD AMPS
EM - EMERGENCY
EWC - ELECTRIC WATER COOLER
EWH - ELECTRIC WATER HEATER
EX - EXISTING
EXTR - EXISTING TO REMAIN
°F - DEGREES FAHRENHEIT
FACP - FIRE ALARM CONTROL PANEL
FATC - FIRE ALARM TERMINAL CABINET
EPO - EMERGENCY POWER OFF
CT - COOLING TOWER
dB - DECIBELS
EF - EXHAUST FAN
EDH - ELECTRIC DUCT HEATER
ELEC - ELECTRIC OR ELECTRICAL
°C - DEGREES CENTIGRADE/CELSIUS
C - CONDUIT
CB - CIRCUIT BREAKER
CCTV - CLOSED CIRCUIT TELEVISION
D/D - DUSK TO DAWN
CONC - CONCRETE
COND - CONDUCTOR
DN - DOWN
AC - ALTERNATING CURRENT
AFG - ABOVE FINISHED GRADE
ATS - AUTOMATIC TRANSFER SWITCH
BG - BELOW GRADE
ABCLG - ABOVE CEILING
APPROX - APPROXIMATELY
BLDG - BUILDING
A/C - AIR CONDITIONING
AHU - AIR HANDLING UNIT
AFF - ABOVE FINISHED FLOOR
AL - ALUMINUM
PTAC - PACKAGED TERMINAL AIR CONDITIONER
UNO - UNLESS NOTED OTHERWISE
WH - WATER HEATER
VAV - VARIABLE AIR VOLUME
VFD - VARIABLE FREQUENCY DRIVE
WP - WEATHERPROOF
TYP - TYPICAL
RLA - RUNNING LOAD AMPS
SHT - SHEET
SF - SUPPLY FAN
RTU - ROOF TOP UNIT
UGE - UNDERGROUND ELECTRIC
TTC - TELEPHONE TERMINAL CABINET
TTB - TELEPHONE TERMINAL BOARD
SCP - SECURITY CONTROL PANEL
R - RELOCATE
IDF - INTERMEDIATE DISTRIBUTION FRAME
MTD - MOUNTED
POAU - PACKAGED OUTDOOR AIR UNIT
OAU - OUTDOOR AIR HANDLING UNIT
P - PUMP
PH - PHASE
NTS - NOT TO SCALE
OHE - OVERHEAD ELECTRIC
NO - NORMALLY OPEN
NL - NIGHT LIGHT
NF - NON-FUSED
NIC - NOT IN CONTRACT
NC - NORMALLY CLOSED
LRA - LOCKED ROTOR AMPS
MCA - MINIMUM CIRCUIT AMPACITY
MIN - MINIMUM
REF - REFRIGERATOR
MAX - MAXIMUM
KW - KILOWATT
LA - LIGHTNING ARRESTOR
MH - MANHOLE
MDF - MAIN DISTRIBUTION FRAME
MB - MAIN BREAKER
IN - INCHES
MLO - MAIN LUGS ONLY
U.N.O. - UNLESS NOTED OTHERWISE
ST - SHUNT TRIP
ABBREVIATIONS
SHEET NOTE. SEE THE SPECIAL NOTES ON
THAT SHEET FOR THE NOTE NUMBER
INDICATED IN THE HEXAGON.
DEMOLITION HATCHING - INDICATES ITEMS TO
BE REMOVED UNLESS OTHERWISE NOTED
ITEMS SHOWN DASHED AND RELATIVELY LIGHT
ARE EXISTING UNLESS NOTED OTHERWISE
REVISION CLOUD AND REFERENCE NUMBER
ROOM NUMBERS
SECTION/DETAIL DESIGNATIONS
X = SECTION (LETTER) OR DETAIL (NUMBER)
Y = SHEET WHERE DETAIL/SECTION IS REFERENCED
Z = SHEET WHERE DETAIL/SECTION IS SHOWN
X
Z
X
ZY
GENERAL SYMBOLS
Engineering | Planning | Allied Services
Offices Nationwide www.hanson-inc.com
Hanson Professional Services Inc.
CONSULTANTS
EB0007061
AA0003116
IB0001058
SHEET TITLE
REVIEWED BY:
DRAWN BY:
DESIGN BY:
PROJECT NO:
ISSUE:
© Copyright Hanson Professional Services Inc. 2024
SEAL
MARK DATE DESCRIPTION
/9
/2
:0 :2
P
M
C
R e vi t_ L o c a l_
\E
-O C
G e n e ra to r
R e lo c a ti o n -2 b m a ld o n a d o X
W
.r v t
2300 Maitland Center Parkway, Suite 310 Maitland, FL 32751
(407) 790-7397
ORANGE COUNTY
CORRECTIONS -
VIDEO VISITATION
CENTER - NEW
GENERATOR
3000 39th Street, Orlando, FL 32839
GENERAL
ELECTRICAL NOTES,
LEGEND AND
ABBREVIATIONS
E-001
06/09/2025
19G0181
BM
BM
AJT
100% CD
C O
N D
. 1 C
O N
D . 2
C O
N D
. 1 C
O N
D . 2
104a
102b
102a
104b data/ monitoring break office clo.
male toilet mech.
female toilet jan.
vending entrance/ lobby control/ property visitation mech elec.
init. apper.
viewing waiting property storage staff toilet clo
AREA OF WORK
GENERATOR
ANNUNCIATOR
ADD ALTERNATE
Engineering | Planning | Allied Services
Offices Nationwide www.hanson-inc.com
Hanson Professional Services Inc.
CONSULTANTS
EB0007061
AA0003116
IB0001058
SHEET TITLE
REVIEWED BY:
DRAWN BY:
DESIGN BY:
PROJECT NO:
ISSUE:
© Copyright Hanson Professional Services Inc. 2024
SEAL
MARK DATE DESCRIPTION
/9
/2
:0 :2
P
M
C
R e vi t_ L o c a l_
\E
-O C
G e n e ra to r
R e lo c a ti o n -2 b m a ld o n a d o X
W
.r v t
2300 Maitland Center Parkway, Suite 310 Maitland, FL 32751
(407) 790-7397
ORANGE COUNTY
CORRECTIONS -
VIDEO VISITATION
CENTER - NEW
GENERATOR
3000 39th Street, Orlando, FL 32839
ELECTRICAL
OVERALL PLAN
E-101
06/09/2025
19G0181
BM
BM
AJT
100% CD
SCALE: 1/8" = 1'-0"1
ELECTRICAL OVERALL PLAN
1. REFER TO ELECTRICAL GENERAL NOTES ON SHEET E-001.
2. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
GENERAL SHEET NOTES
SHEET KEYNOTES
NEW GENERATOR ANNUNCIATOR. CONNECT ANNUNCIATOR TO CONTROL
PANEL LOCATED INSIDE GENERATOR ENCLOSURE. REFER TO DETAIL 4/E-601
FOR ADDITIONAL INFORMATION.
PROVIDE AND INSTALL REMOTE GENERATOR MONITORING PANEL. RUN CAT 6
CABLE IN 1"C FROM PANEL TO COMMUNICATIONS ROOM 107. ORANGE
COUNTY ISS DIVISION TO INSTRUCT CONTRACTOR WHICH RACK TO RUN
CABLE TO AND MAKE FINAL TERMINATIONS. ACCESS TO THE REMOTE
GENERATOR MONITORING PANEL SHALL BE COMPATIBLE WITH ORANGE
COUNTY ISS REGULATIONS/STANDARDS.
4'0 8' 16' visitation mech elec.
visitation mech elec.
E
MDP
NEW ATS
EXISTING
C/T CABINET
EXISTING UTILITY METER
NEW 100KW/125KVA NATURAL
GAS GENERATOR 'NG'
SERVICE ENTRANCE ENCLOSED
CIRCUIT BREAKER DISCONNECT
SWITCH IN NEMA 3R ENCLOSURE
NEW CHAIN LINKED FENCE12
RELOCATED
LIGHT SWITCH
E-22
EXISTING BUILDING
SERVICE 'EPO'
NEW GENERATOR
'EPO'
TRANSITION TO ABOVE GRADE
ABOVE GRADE
CONDUIT (TYPICAL)
ABOVE GRADE CONDUIT
EXISTING IRRIGATION
CONTROLS
EXISTING MAIN
BLDG GROUND
BUS BAR
GENERATOR
CONCRETE PAD
FINISHED GRADE 6" CA-57
CRUSHED LIMESTONE
WITH D3 FILTER FABRIC
20' - 0"
NEW 6'-0" CHAIN
LINKED FENCE GATE.
EXISTING UTILITY METER
EXISTING C/T CABINETE
MDP
EXISTING SWITCH
4EXISTING IRRIGATION CONTROLS
18' - 6"
EXISTING BUILDING SERVICE 'EPO' 6
Engineering | Planning | Allied Services
Offices Nationwide www.hanson-inc.com
Hanson Professional Services Inc.
CONSULTANTS
EB0007061
AA0003116
IB0001058
SHEET TITLE
REVIEWED BY:
DRAWN BY:
DESIGN BY:
PROJECT NO:
ISSUE:
© Copyright Hanson Professional Services Inc. 2024
SEAL
MARK DATE DESCRIPTION
/9
/2
:0 :2
P
M
C
R e vi t_ L o c a l_
\E
-O C
G e n e ra to r
R e lo c a ti o n -2 b m a ld o n a d o X
W
.r v t
2300 Maitland Center Parkway, Suite 310 Maitland, FL 32751
(407) 790-7397
ORANGE COUNTY
CORRECTIONS -
VIDEO VISITATION
CENTER - NEW
GENERATOR
3000 39th Street, Orlando, FL 32839
ELECTRICAL
ENLARGED PLAN
E-201
06/09/2025
19G0181
BM
BM
AJT
100% CD
SCALE: 1/4" = 1'-0"1
ELECTRICAL ENLARGED PLAN - RENOVATION
SCALE: 1/4" = 1'-0"2
ELECTRICAL ENLARGED PLAN - DEMOLITION
1. REFER TO ELECTRICAL GENERAL NOTES ON SHEET E-001.
2. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
3. ABOVE GRADE ELECTRICAL CONDUIT TO BE GALVANIZED RIGID STEEL
CONDUIT.
4. BELOW GRADE ELECTRICAL CONDUIT TO BE SCHEDULE 40 PVC CONDUIT.
5. CONTRACTOR TO USE COMPRESSION FITTINGS WITH EMT CONDUITS.
6. PER SPEC SECTION 26 05 53 "IDENTIFICATION FOR ELECTRICAL SYSTEMS",
CONTRACTOR TO COLOR CODE WIRES END TO END, MUST BE LABELED AND
RECORDED IN THE AS-BUILT PLANS.
7. CONTRACTOR SHALL NOT PENETRATE CMU EXTERIOR WALL WITHOUT FIRST
X-RAYING THE WALL AT EVERY EXTERIOR WALL PENETRATION.
GENERAL SHEET NOTES
SHEET KEYNOTES
DISCONNECT THE FEEDER CONDUCTORS AND CONDUIT TO DISTRIBUTION
PANEL 'MDP' FROM THE C/T CABINET FOR RE-ROUTING. REFER TO
RENOVATION PLAN ON THIS SHEET FOR ADDITIONAL INFORMATION.
DISCONNECT EXISTING LIGHT SWITCH FOR RELOCATION. RETAIN EXISTING
CIRCUIT WIRING AND CONDUIT FOR REUSE. REFER TO RENOVATION PLAN ON
THIS SHEET FOR ADDITIONAL INFORMATION.
LANDSCAPE CONTRACTOR TO REMOVE ALL LANDSCAPING ITEMS IN THIS
AREA, WHICH INCLUDE PALM TREES. THE DIMENSIONS SHOWN ARE
APPROXIMATIONS. CONTRACTOR TO FIELD VERIFY ALL DIMENSIONS.
COORDINATE WITH ORANGE COUNTY FOR FURTHER DIRECTION OF THE
LANDSCAPING ITEMS AFTER REMOVAL. DISCONNECT AND CAP OFF
SPRINKLER HEADS IN THIS AREA ONLY.
IRRIGATION CONTROLS EXISTING TO REMAIN.
COORDINATE WITH UTILITY FOR WORK WITHIN THE C/T CABINET. ROUTE NEW
FEEDER TO SERVICE ENTRANCE CIRCUIT BREAKER DISCONNECT SWITCH.
PROVIDE AND INSTALL PULL BOX ABOVE C/T CABINET TO PERFORM SPLICING
OF EXISTING FEEDER CONDUCTORS. CONDUIT ROUTING SHOWN ON PLAN
FOR REFERENCE ONLY.
DISCONNECT EXISTING BUILDING SERVICE EPO FROM MAIN BUILDING
SERVICE. REFER TO RENOVATION PLAN ON THIS SHEET FOR ADDITIONAL
INFORMATION.
REFER TO GENERATOR CONNECTION DETAIL 3/E-601 FOR ADDITIONAL
INFORMATION.
CONNECT EXISTING BUILDING SERVICE EPO TO NEW SERVICE ENTRANCE
RATED DISCONNECT SWITCH. CONTRACTOR TO MATCH EXISING WIRE AND
CONDUIT. PROVIDE RED PLACARD WITH WHITE LETTER THAT STATES
'SERVICE ENTRANCE OFF'.
GENERATOR STOP PUSH BUTTON TO BE NEMA 3R RATED. PROVIDE RED
PLACARD WITH WHITE LETTER THAT STATES 'GENERATOR OFF'. REFER TO
DETAIL 3/E-601 FOR ADDITIONAL INFORMATION.
INSTALL RELOCATED LIGHT SWITCH APPROXIMATELY 3'-6" WEST OF ORIGINAL
LOCATION. COORDINATE FINAL LOCATION WITH NEW EQUIPMENT BEING
INSTALLED.
MOUNT WALL PACK LIGHT FIXTURE AT 9'-0" A.F.F. LIGHT FIXTURES TO HAVE
INTEGRATED PHOTO CELL. LIGHT FIXTURE TO BE LITHONIA LIGHTING #TWR1
LED ALO 40K MVOLT PE DDBTXD OR APPROVED EQUAL. PROVIDE 2#12, 1#12G,
3/4" RGS CONDUIT FROM PANEL TO LIGHT FIXTURE.
NEW CHAIN LINKED FENCE TO MATCH EXISTING SITE FENCING HEIGHT, TYPE
AND CONSTRUCTION. COORDINATE WITH ORANGE COUNTY FOR ADDITIONAL
INFORMATION.
REFER TO DETAIL 2/E-601 FOR ADDITIONAL DETAILS.
REFER TO SHEET M-101 FOR ADDITIONAL INFORMATION REGARDING THE
NATURAL GAS SERVICE AND CONNECTION TO THE GENERATOR. REFER TO
SHEET E-501 FOR ADDITIONAL INFORMATION ON ADDITIVE ALTERNATE.
0 2' 4' 8'
0 2' 4' 8'
ADDITIVE ALTERNATE BID ITEM
1. THE BASIS OF DESIGN FOR THE GENERATOR SHALL BE OF NATURAL GAS
TYPE. A DIESEL GENERATOR SHALL BE PROVIDED AS AN ADDITIVE ALTERNATE
IF ACCEPTED BY OWNER.
PANEL
'A'
800AF
800AT
3P
INCOMING
UTILITY
M
PANEL
'B'
PANEL
'C'
PANEL
'D'
PANEL
'E'
SPARE SPARE SPARE SPARE
AHU-1 AHU-2 CU-3
'MDP'
EATON, PRL4B, 800A, 208Y/120V, 3Ø 4W
250AF
150AT
3P
250AF
150AT
3P
250AF
150AT
3P
250AF
150AT
3P
250AF
150AT
3P
100AF
80AT
3P
100AF
80AT
3P
100AF
90AT
3P
100AF
90AT
3P
100AF
60AT
3P
100AF
60AT
3P
100AF
90AT
3P
100AF
100AT
3P
100AF
50AT
3P
CU-1 CU-2
C/T
CABINET UTILITY
METER
POLE MOUNTED
UTILITY XFMR
EPO
DISCONNECT FEEDER CIRCUIT AND CONDUIT FROM C/T CABINET TO MDP.
NEMA 1
208/120V, 3Ø
800 AMP, 3-POLE
E
L
N
400A/3P
125 kVA 100 kW 208V, 3Ø
STAND BY
NATURAL GAS
GENERATOR
'NG'
GENERATOR
ENCLOSURE
PANEL
'A'
800AF
800AT
3P
INCOMING
UTILITY
M
PANEL
'B'
PANEL
'C'
PANEL
'D'
PANEL
'E'
SPARE SPARE SPARE SPARE
AHU-1 AHU-2 CU-3
'MDP'
EATON, PRL4B, 800A, 208Y/120V, 3Ø 4W
250AF
150AT
3P
250AF
150AT
3P
250AF
150AT
3P
250AF
150AT
3P
250AF
150AT
3P
100AF
80AT
3P
100AF
80AT
3P
100AF
90AT
3P
100AF
90AT
3P
100AF
60AT
3P
100AF
60AT
3P
100AF
90AT
3P
100AF
100AT
3P
100AF
50AT
3P
CU-1 CU-2
C/T
CABINET UTILITY
METER
POLE MOUNTED
UTILITY XFMR
2 PARALLEL SETS OF 4#500KCMIL,
1#1/0G, IN 3 1/2"C EACH
2 PARALLEL SETS OF
4#500KCMIL, IN 3 1/2"C
EACH
4#500KCMIL, 1#3G,
3-1/2"C
CONTRACTOR TO REMOVE NEUTRAL TO
GROUND BOND WITHIN EQUIPMENT.
800A, 208/120V, 3Ø MAIN CIRCUIT
BREAKER DISCONNECT SWITCH TO
BE SERVICE ENTRANCE RATED IN
NEMA 3R ENCLOSURE WITH 65K AIC
INTERRUPTING RATING AND TO BE
SHUNT-TRIP TYPE.
2 PARALLEL SETS OF 4#500KCMIL,
1#1/0G, IN 3 1/2"C EACH
N G
1#2/0G, 1"C
GROUND TO EXISTING
GROUND BUS BAR LOCATED
IN MECHANICAL ROOM
EXISTING BUILDING
SERVICE EPO
NEW GENERATOR EPO
1#2/0G, 1"C TO NEW GROUND
RING. REFER TO DETAIL 2 ON
SHEET E-602
ADDITIVE ALTERNATE BID ITEM
THE BASIS OF DESIGN FOR THE GENERATOR SHALL BE OF NATURAL GAS TYPE. A
DIESEL GENERATOR SHALL BE PROVIDED AS AN ADDITIVE ALTERNATE IF
ACCEPTED BY OWNER.
(SEE
SCHEDULE
ON THIS
SHEET)
1#2/0G, 1"C TO NEW GROUND
RING. REFER TO DETAIL 2 ON
SHEET E-602
Engineering | Planning | Allied Services
Offices Nationwide www.hanson-inc.com
Hanson Professional Services Inc.
CONSULTANTS
EB0007061
AA0003116
IB0001058
SHEET TITLE
REVIEWED BY:
DRAWN BY:
DESIGN BY:
PROJECT NO:
ISSUE:
© Copyright Hanson Professional Services Inc. 2024
SEAL
MARK DATE DESCRIPTION
/9
/2
:0 :2
P
M
C
R e vi t_ L o c a l_
\E
-O C
G e n e ra to r
R e lo c a ti o n -2 b m a ld o n a d o X
W
.r v t
2300 Maitland Center Parkway, Suite 310 Maitland, FL 32751
(407) 790-7397
ORANGE COUNTY
CORRECTIONS -
VIDEO VISITATION
CENTER - NEW
GENERATOR
3000 39th Street, Orlando, FL 32839
ONE-LINE
DIAGRAMS AND
PANEL SCHEDULE
E-501
06/09/2025
19G0181
BM
BM
AJT
100% CD
* = INDICATES ASSUMED LOAD(S).
NOTES:
C 3530 VA 29 A
B 5620 VA 50 A TOTAL CONNECTED AMPS = 41 APHASE LOADS
A 5640 VA 50 A TOTAL CONNECTED LOAD = 14790 VA
41 SPARE 20 A 1 0 1000 1 20 A BATTERY CHARGER 42
39 SPARE 20 A 1 0 1000 1 20 A FUEL/OIL HEATER 40
37 SPARE 20 A 1 0 1000 1 20 A WATER JACKET HEATER 38
35 SPARE 20 A 1 0 0 1 20 A SPARE 36
33 SPARE 20 A 1 0 0 1 20 A SPARE 34
31 SPARE 20 A 1 0 0 1 20 A SPARE 32
29 SPARE 20 A 1 0 0 1 20 A SPARE 30
27 SPARE 20 A 1 0 0 1 20 A SPARE 28
25 SPARE 20 A 1 0 0 1 20 A SPARE 26
23 SPARE 20 A 1 0 0 1 20 A SPARE 24
21 DAMPER AHU-2 20 A 1 500 40 1 20 A WALL PACKS FOR GENERATOR 22
19 DAMPER AHU-1 20 A 1 500 600 1 20 A WALL DOWNLIGHTS 20
17 RECEPTACLES - IRRIGATION 20 A 1 180 100 1 20 A WALL UPLIGHTS 18
15 RECEPTACLES - MER 20 A 1 360 700 1 20 A WALL DOWNLIGHTS 16
13 RECEPTACLES - NORTH WALL 20 A 1 540 400 1 20 A WALL UPLIGHTS 14
11 RECEPTACLES - WEST WALL 20 A 1 540 1000 1 20 A WALL DOWNLIGHTS 12
9 RECEPTACLES - SW. WALL 20 A 1 720 450 1 20 A WALL UPLIGHTS 10
7 RECEPTACLES - SOUTH WALL 20 A 1 720 1100 1 20 A WALL DOWNLIGHTS 8
5 RECEPTACLES - TV 20 A 1 180 530 1 20 A WALL UPLIGHTS 6
3 RECEPTACLES - EAST WALL 20 A 1 720 1130 1 20 A WALL DOWNLIGHTS 4
1 RECEPTACLES - COND UNIT 20 A 1 180 600 1 20 A WALL UPLIGHTS 2
CKT CIRCUIT DESCRIPTION CB P A (VA) B (VA) C (VA) A (VA) B (VA) C (VA) P CB CIRCUIT DESCRIPTION CKT
MECH. ELEC. 108
SECTIONS: 1 LOCATION
ENCLOSURE: NEMA 1 FED FROM: MDP
MOUNTING: SURFACE VOLTAGE: 208Y/120V, 3Ø, 4W
TYPE: EATON BUS RATING: 225 A
AIC RATING: 22K AIC
EXISTINGPANEL: E
MAINS: 225 A MLO
SCALE:NTS1
ONE-LINE DIAGRAM - EXISTING
SCALE:NTS2
ONE-LINE DIAGRAM - RENOVATION
* OBTAINED FROM UTILITY.
UTILITZATION (%): 19%
12 MONTHS PEAK DEMAND (AMPS): 150.86 A
12 MONTHS PEAK DEMAND (KVA): 54.35 KVA
POWER FACTOR: 0.8
12 MONTHS PEAK DEMAND (KW): 43.48 KW*
BUILDING LOAD
SUMMARY
M
IN
IM
U
M
8" MINIMUM
1" CHAMFER
TYPICAL GRAVEL FILLED
TRENCH AROUND PERIMETER
OF GENERATOR PAD
2'-0"2'-0" +/-12"
#4's @ 12" O.C.
NATURAL GAS
GENERATOR
2 #12, 1#12G, 3/4"C. TO PANEL E, CKT. 42
2 #12 & 1#12G, 3/4"C. TO PANEL E, CKT. 38
ANNUNCIATOR
2 #12, 1"C TO REMOTE
SWITCH
2 #12, 1"C TO TRANSFER
1- 2"C FOR CONTROL WIRING
1- 3-1/2"C FOR POWER FEEDER WIRING
TO TRANSFER SWITCH:
STOP PUSH BUTTON
2 #12, 1"C TO REMOTE
PANEL
GENERATOR CONTROL
CHARGER
BATTERY
HEATER
ENGINE JACKET
COORDINATE REQUIRED WIRING SIZE, TYPE AND QUANTITY WITH
MANUFACTURER.
NOTE:
DIESEL
GENERATOR
2 #12, 1#12G, 3/4"C. TO PANEL E, CKT. 42
2 #12 & 1#12G, 3/4"C. TO PANEL E, CKT. 38
ANNUNCIATOR
2 #12, 1"C TO REMOTE
SWITCH
2 #12, 1"C TO TRANSFER
1- 2"C FOR CONTROL WIRING
1- 3-1/2"C FOR POWER FEEDER WIRING
TO TRANSFER SWITCH:
STOP PUSH BUTTON
2 #12, 1"C TO REMOTE
ANNUNCIATOR
2 #12, 1"C TO REMOTE
SENSOR
LOW FUEL LEVEL
PANEL
GENERATOR CONTROL
CHARGER
BATTERY
HEATER
ENGINE JACKET
2 #12, 1#12G, 3/4"C. TO PANEL E, CKT. 40
HEATER
FUEL/OIL
COORDINATE REQUIRED WIRING SIZE, TYPE AND QUANTITY WITH
MANUFACTURER.
NOTE:
Engineering | Planning | Allied Services
Offices Nationwide www.hanson-inc.com
Hanson Professional Services Inc.
CONSULTANTS
EB0007061
AA0003116
IB0001058
SHEET TITLE
REVIEWED BY:
DRAWN BY:
DESIGN BY:
PROJECT NO:
ISSUE:
© Copyright Hanson Professional Services Inc. 2024
SEAL
MARK DATE DESCRIPTION
/9
/2
:0 :2
P
M
C
R e vi t_ L o c a l_
\E
-O C
G e n e ra to r
R e lo c a ti o n -2 b m a ld o n a d o X
W
.r v t
2300 Maitland Center Parkway, Suite 310 Maitland, FL 32751
(407) 790-7397
ORANGE COUNTY
CORRECTIONS -
VIDEO VISITATION
CENTER - NEW
GENERATOR
3000 39th Street, Orlando, FL 32839
DETAILS
E-601
06/09/2025
19G0181
BM
BM
AJT
100% CD
SCALE:NTS2
GENERATOR PAD DETAIL
SCALE:NTS3
GENERATOR CONNECTION DETAIL FOR NATURAL GAS
SCALE:1
ISOMETRIC
SCALE:NTS4
GENERATOR CONNECTION DETAIL FOR DIESEL
NOTES:
1. VERTICAL POSTS SHALL BE BONDED TO A GROUND
ROD AT EACH CORNER AND AT EVERY GATE POST.
AS A MINIMUM ONE VERTICAL POST SHALL BE
BONDED TO A GROUND ROD IN EVERY 500 FOOT
STRAIGHT RUN.
2. ALL EXISTING SITE FENCING WITHIN 10 FT. OF A
GROUNDING ELECTRODE SHALL BE BONDED TO
NEW FENCE GROUNDING ELECTRODE.
CONNECT #6 BARE STRANDED COPPER
WIRE TO BARBED
WIRE WITH SPLIT-BOLT CONNECTOR
(TYP.)
TOP RAIL #6 BARE STRANDED
COPPER
#2/0 BARE STRANDED COPPER
CABLE, CONNECT TO POST WITH
EXOTHERMIC WELD (TYP.)
CONNECT TO TOP RAIL WITH BURDY TYPE
"GAR" GROUND CLAMP OR EQUAL
BOND TO BOTTOM TENSION WIRE
WITH BRONZE CLAMP (TYP.)
EXOTHERMIC WELD TO
POST (TYP.)
EXOTHERMIC WELD TYPE
CONNECTION (TYP. FOR
BELOW GRADE
CONNECTIONS)
3/4" DIA. x 10'-0" L. UL LISTED
COPPER CLAD STEEL GROUND
ROD
TENSION
WIRE
TOP RAIL #6 BARE STRANDED
COPPER
BOND TO BOTTOM TENSION WIRE WITH
BRONZE CLAMP (TYP.)
EXOTHERMIC WELD
TO POST (TYP.)
3/4" DIA. x 10'-0" L. UL LISTED
COPPER
CLAD STEEL GROUND ROD
SPLIT BOLT CONNECTOR AT BARBED
WIRE AND FENCE MESH FABIC (TYPICAL)
EXOTHERMIC WELD
CONNECTION
(TYPICAL)
#2/0 AWG BARE STRANDED COPPER
CABLE, INSTALL 30" MIN. BELOW
FINISHED GRADE OR PAVEMENT
SURFACE.
NOTE: TYPICAL FOR SWING GATES
AND TILT GATE.
#2/0 AWG STRANDED COPPER
WELDING CABLE (GATE
JUMPER), BOND TO GATE AND GATE
POST WITH EXOTHERMIC WELD
CONNECTION (TYP.)
TENSION
WIRE
BARBED
WIRE
XXX
XX
X X
X
X
XXX XXX
XXX
X X X
XXX
X X X
X XX X
X
X
X
X
XX
X X
X
X
X
X
X
X
X
X
X
X
XX
X X
X
X
X
XX X X
XX X
XXX XX XX X X
X
X
X
X
XX X
XXX
X
X
X XXX XX
X XX X
X
X
X
X
XX
X X
X
X
X
X
X
X
X
XX
X X
X
X
XXX XX
CONNECT TWICE TO
FENCE FABRIC WITH
BRONZE CLAMP (TYP.)
GROUND ROD INSPECTION
WELL AT ALL GROUND ROD
LOCATIONS (TYP.)
GROUND ROD INSPECTION
WELL AT ALL GROUND ROD
LOCATIONS (TYP.)
CONNECT TWICE TO
FENCE FABRIC WITH
BRONZE CLAMP (TYP.)
FENCE GATE POST DETAIL FENCE POST DETAIL
#2/0 BARE COPPER WIRE TO
BUILDING GROUND BUS BAR
IN MAIN ELECTRICAL ROOM.
3' - 0"
3' - 0"
#2/0 BARE COPPER WIRE (TYP.)
GROUND ROD WELL (TYP.)
GENERATOR CONCRETE PAD
FINISHED GRADE 6" CA-57
CRUSHED LIMESTONE
WITH D3 FILTER FABRIC
2' - 0"
2' - 0"
NEUTRAL GROUND POINT
CABLE TO NEXT SYSTEM GROUND
ROD OR EXISTING BUILDING
GROUNDING AS INDICATED ON
DETAIL 2 ON THIS SHEET.
CADWELD EXOTHERMIC
CONNECTION AS
SPECIFIED
3/4" DIA x 10'-0"
COPPER, COPPER
CLAD GROUND ROD
LIGHTNING PROTECTION OR
GROUNDING CONDUCTOR
PRECAST CONCRETE
OR QUAZITE TEST WELL
HEAVY DUTY PARALLEL
CLAMP WITH STAINLESS
STEEL BOLTS
PRESSURE TYPE "TEE" SPLICER
WITH STAINLESS STEEL BOLTS.
SYSTEM CABLE
HEAVY DUTY STRAIT SPLICER
WITH STAINLESS STEEL BOLTS
CABLE END SHALL FACE IN
DIRECTION OF NEAREST
DOWNLEAD
SYSTEM CABLE
' M
IN
IM
U M
8"
OUTSIDE OF SITE INSIDE OF SITE
FDOT INDEX 550-002
FINISHED GRADE 6" CA-57
CRUSHED LIMESTONE
D3 FILTER FABRIC
NATIVE SOIL COMPACTED TO 95%
MAXIMUM DENSITY, STANDARD
PROCTOR
EXISTING GROUND
3,000 PSI CONCRETE
FDOT SECTION 347
PORTLAND CEMENT
CONCRETE-CLASS NS
' M
IN
IM
U M
10"
OUTSIDE OF SITE INSIDE OF SITE
FDOT INDEX 550-002
FINISHED GRADE 6" CA-57
CRUSHED LIMESTONE
D3 FILTER FABRIC
NATIVE SOIL COMPACTED TO 95%
MAXIMUM DENSITY, STANDARD
PROCTOR
EXISTING GROUND
3,000 PSI CONCRETE
FDOT SECTION 347
PORTLAND CEMENT
CONCRETE-CLASS NS
Engineering | Planning | Allied Services
Offices Nationwide www.hanson-inc.com
Hanson Professional Services Inc.
CONSULTANTS
EB0007061
AA0003116
IB0001058
SHEET TITLE
REVIEWED BY:
DRAWN BY:
DESIGN BY:
PROJECT NO:
ISSUE:
© Copyright Hanson Professional Services Inc. 2024
SEAL
MARK DATE DESCRIPTION
/9
/2
:0 :2
P
M
C
R e vi t_ L o c a l_
\E
-O C
G e n e ra to r
R e lo c a ti o n -2 b m a ld o n a d o X
W
.r v t
2300 Maitland Center Parkway, Suite 310 Maitland, FL 32751
(407) 790-7397
ORANGE COUNTY
CORRECTIONS -
VIDEO VISITATION
CENTER - NEW
GENERATOR
3000 39th Street, Orlando, FL 32839
DETAILS
E-602
06/09/2025
19G0181
BM
BM
AJT
100% CD
SCALE:NTS1
TYPICAL FENCE GROUNDING DETAIL
SCALE: 1/2" = 1'-0"2
FENCE GROUNDING DETAIL
SCALE:NTS5
GROUND ROD INSPECTION WELL DETAIL
SCALE:NTS6
SPLICES AND CLAMPS DETAIL
SCALE:NTS4
LINE POST DETAIL
SCALE:NTS3
GATE, CORNER, OR TERMINATION POST DETAIL
visitation mech elec.
6" DIRT LEG
G
GAS PRESSURE REGULATOR
IF REQUIRED AT EQUIPMENT
GAS VALVE
GAS EQUIPMENT
CAP
REDUCERUNION
5 6
1 1/4"
3 4
Engineering | Planning | Allied Services
Offices Nationwide www.hanson-inc.com
Hanson Professional Services Inc.
CONSULTANTS
EB0007061
AA0003116
IB0001058
SHEET TITLE
REVIEWED BY:
DRAWN BY:
DESIGN BY:
PROJECT NO:
ISSUE:
© Copyright Hanson Professional Services Inc. 2024
SEAL
MARK DATE DESCRIPTION
/9
/2
:0 :2
P
M
C
R e vi t_ L o c a l_
\E
-O C
G e n e ra to r
R e lo c a ti o n -2 b m a ld o n a d o X
W
.r v t
2300 Maitland Center Parkway, Suite 310 Maitland, FL 32751
(407) 790-7397
ORANGE COUNTY
CORRECTIONS -
VIDEO VISITATION
CENTER - NEW
GENERATOR
3000 39th Street, Orlando, FL 32839
MECHANICAL
NATURAL GAS
PIPING PLAN
M-101
06/09/2025
19G0181
LW
BM
BWP
100% CD
SCALE:NTS1
NATURAL GAS EQUIPMENT CONNECTION DETAIL
GENERAL SHEET NOTES
SHEET KEYNOTES
NEW NATURAL GAS GENERATOR. NATURAL GAS GENERATOR FUEL SUPPLY
PRESSURE REQUIREMENTS = 6" - 13" W.C.. CONTRACTOR SHALL BE
RESPONSIBLE FOR VERIFYING THESE REQUIREMENTS WITH THE SUPPLIED
GENERATOR. NATURAL GAS PRESSURE AT THE GENERATOR SHALL NOT
EXCEED THE MAXIMUM LISTED BY THE MANUFACTURER.
NEW NATURAL GAS SERVICE PIPING BY UTILITY PROVIDER. THE
CONTRACTOR SHALL COORDINATE WITH THE UTILITY PROVIDER FOR THE
EXTENSION OF THE NEW NATURAL GAS SERVICE TO THIS AREA.
NEW NATURAL GAS METER SHALL BE PROVIDED BY THE UTILITY PROVIDER.
THE CONTRACTOR SHALL COORDINATE WITH THE UTILITY PROVIDER FOR
THE PROVISION OF THE NEW NATURAL GAS METER. UTILITY PROVIDER TO
SUPPLY SHUTOFF VALVES BEFORE/AFTER PER THE UTILITY PROVIDER'S
STANDARD INSTALLATION PROCEDURES. PROVIDE A MINIMUM OF 4'
CLEARANCE FROM THE GENERATOR.
NEW NATURAL GAS PRESSURE REGULATOR SHALL BE PROVIDED BY THE
UTILITY PROVIDER. THE CONTRACTOR SHALL COORDINATE WITH THE
UTILITY PROVIDER FOR THE PROVISION OF THE NEW NATURAL GAS
PRESSURE REGULATOR. REGULATOR SHALL PROVIDE 1 PSI SERVICE
DOWNSTREAM. UTILITY PROVIDER SHALL BE RESPONSIBLE FOR
IDENTIFYING UPSTREAM SERVICE PRESSURE REQUIREMENTS. UTILITY
PROVIDER TO SUPPLY SHUTOFF VALVES BEFORE/AFTER AND ANY OTHER
PIPING ACCESSORIES PER THE UTILITY PROVIDER'S STANDARD
INSTALLATION PROCEDURES. PROVIDE A MINIMUM OF 4' CLEARANCE FROM
THE GENERATOR.
CONTRACTOR SHALL BE RESPONSIBLE FOR EXTENDING NEW 1-1/4”
NATURAL GAS PIPING FROM THE UTILITY PROVIDED EQUIPMENT AND PIPING
TO THE NEW GENERATOR. BELOW GRADE PIPING SHALL MEET THE
MATERIAL, PERFORMANCE, AND INSTALLATION REQUIREMENTS OF UTILITY
PROVIDER FOR BELOW GRADE NATURAL GAS PIPING. ABOVE GRADE PIPING
SHALL BE SCHEDULE 40 TYPE E OR S, GRADE B, STEEL PIPE CONFORMING
TO ASTM A 53/A. ABOVE GRADE FITTINGS SHALL BE MALLEABLE-IRON
THREADED FITTINGS, CLASS 150, CONFORMING TO ASME B16.3. ABOVE
GRADE UNION SHALL BE MALLEABLE IRON WITH BRASS-TO-IRON SEAT,
GROUND JOINT, AND THREADED ENDS, CLASS 150, CONFORMING WITH
ASME B16.39.
CONTRACTOR SHALL COORDINATE WITH THE COUNTY TO DETERMINE
WHETHER THE NATURAL GAS PIPING SHALL BE ROUTED BELOW GRADE TO
THE GENERATOR OR ALONG THE CHAIN LINK FENCE, ABOVE GRADE, TO THE
GENERATOR. ABOVE GRADE OUTDOOR PIPING TO BE PROVIDED WITH PE
PROTECTIVE COATING AT THE JOINTS TO COVER, SEAL AND PROTECT.
ABOVE GRADE PIPING SHALL BE PAINTED. CONTRACTOR TO COORDINATE
WITH COUNTY TO DETERMINE THE DESIRED PIPING PAINT COLOR.
AT GENERATOR, CONTRACTOR SHALL PROVIDE THE RECOMMENDED PIPING
AND ACCESSORIES OF THE GENERATOR MANUFACTURER. A MINIMUM OF
THE FOLLOWING SHALL BE PROVIDED AT THE GENERATOR: SHUTOFF
VALVE, DIRT LEG WITH CAP (MIN. 6" LONG), STRAINER, PRESSURE
REGULATOR WITH UNIONS BEFORE AND AFTER, AND REDUCER. SEE DETAIL
1 ON THIS SHEET FOR MORE INFORMATION.
SHUTOFF VALVES SHALL BE TWO-PIECE, FULL-PORT BRONZE VALVES WITH
BRONZE TRIM CONFORMING TO MSS SP-110. THE VALVE BODY SHALL BE
BRONZE CONFORMING WITH ASTM B 584. THE BALL SHALL BE CHROME-
PLATED BRONZE. THE STEM SHALL BE BRONZE AND BLOWOUT PROOF. THE
SEATS SHALL BE REINFORCED PTFE AND BE BLOWOUT PROOF. VALVE
SHALL BE PROVIDED WITH 600 PSIG CWP RATING.
LINE PRESSURE REGULATOR AT THE GENERATOR SHALL COMPLY WITH
ANSI Z21.80. THE BODY AND DIAPHRAGM CASE SHALL BE CAST IRON OR
DIE-CAST ALUMINUM. THE SPRINGS AND DIAPHRAGM PLATE SHALL BE ZINC-
PLATED STEEL, SPRINGS SHALL BE INTERCHANGEABLE. THE SEAT DISC
SHALL BE NITRILE RUBBER RESISTANT TO GAS IMPURITIES, ABRASION, AND
DEFORMATION AT THE VALVE PORT. THE ORIFICE SHALL BE ALUMINUM AND
BE INTERCHANGEABLE. THE SEAL PLUG SHALL BE ULTRAVIOLET-
STABILIZED, MINERAL-FILLED NYLON. PRESSURE REGULATOR SHALL
MAINTAIN DISCHARGE PRESSURE SETTING DOWNSTREAM. REGULATOR
SHALL BE PROVIDED WITH FACTORY MOUNTED OVERPRESSURE
PROTECTION DEVICE. REGULATOR SHALL BE PROVIDED WITH
ATMOSPHERIC VENT WITH STAINLESS-STEEL SCREEN IN OPENING IF NOT
CONNECTED TO VENT PIPING.
SCALE: 1/4" = 1'-0"2
MECHANICAL ENLARGED PLAN - RENOVATION
0 2' 4' 8'
1. COMPLY WITH THE FLORIDA FUEL GAS CODE FOR INSTALLATION AND
PURGING OF NATURAL-GAS PIPING.
2. INSTALL UNDERGROUND, PE, NATURAL-GAS PIPING IN ACCORDANCE
WITH ASTM D2774, AT LEAST 36 INCHES BELOW FINISHED GRADE. IF
NATURAL-GAS PIPING IS INSTALLED LESS THAN 36 INCHES BELOW
FINISHED GRADE, INSTALL IT IN CONTAINMENT CONDUIT.
3. INSTALL PIPING AT RIGHT ANGLES OR PARALLEL TO BUILDING WALLS.
DIAGONAL RUNS ARE PROHIBITED UNLESS SPECIFICALLY INDICATED
OTHERWISE.
4. INSTALL NATURAL-GAS PIPING AT UNIFORM GRADE OF 2 PERCENT
DOWN TOWARD DRIP AND SEDIMENT TRAPS.
5. INSTALL PIPING FREE OF SAGS AND BENDS.
6. INSTALL FITTINGS FOR CHANGES IN DIRECTION AND BRANCH
CONNECTIONS.
7. SUPPORTS FOR ABOVE GRADE PIPING SHALL BE SPACED NO GREATER
THAN 12 FEET APART.
| Sheets |
| E-001 - GENERAL ELECTRICAL NOTES, LEGEND AND ABBREVIATIONS |
| E-101 - ELECTRICAL OVERALL PLAN |
| E-201 - ELECTRICAL ENLARGED PLAN |
| E-501 - ONE-LINE DIAGRAMS AND PANEL SCHEDULE |
| E-601 - DETAILS |
| E-602 - DETAILS |
| G-001 - COVER SHEET |
| M-101 - MECHANICAL NATURAL GAS PIPING PLAN |