Y22-7015-RC_Drawing.PDF
PDF 12 MB Posted
- Solicitation number
- Y22-7015-RC
- Issued by
- Orange County, Orlando City, Florida
About this file
These construction documents are for the Orange County Public Works Roofing Replacement Project, specifically involving Buildings 2 and 5 located at 4200 S. John Young Parkway in Orlando, Florida. The project involves a comprehensive roof replacement utilizing standing seam metal roof panels, with work to be completed on two county buildings totaling approximately 26,661 square feet of roofing area. The documents, prepared by Jay Ammon Architect, Inc. on February 9, 2021, outline a detailed scope of work including complete roof system replacement, removal of existing roofing components, installation of new metal roof panels, gutters, downspouts, underlayment, insulation, and lightning protection systems. The project requires a 20-year No Dollar Limit (NDL) manufacturer's warranty against defects and leaks, with the contractor also providing a 5-year NDL warranty.
The project is competitively bid with an estimated cost of $1,000,000.00, to be solicited through Orange County's OpenGov e-Procurement Platform. Sealed offers are to be submitted electronically by 4:00 pm EST on Thursday, October 6, 2022. The comprehensive scope includes engineering pull tests, wind uplift calculations, substrate preparation, and installation of a new roofing assembly that complies with the 2020 Florida Building Code and meets wind resistance requirements for an ultimate design wind speed of 150 mph. The project specifications require all work to be performed by licensed contractors and include detailed performance requirements for materials, installation techniques, and adherence to industry standards such as NRCA roofing manuals and SMACNA architectural sheet metal guidelines.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Y22-7015-RC_Specifications.PDF | ||
| Part_G_-_AGREEMENT_ASSUMING_RISK_OF_INJURY_OR_DAMAGE.pdf | ||
| Y22-7015-RC.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONSTRUCTION DOCUMENTS
BOARD OF COUNTY COMMISSIONERS:
DISTRICT 1 - BETSY VANDERLEY
DISTRICT 2 - CHRISTINE MOORE
DISTRICT 3 - MAYRA URIBE
DISTRICT 4 - MARIBEL GOMEZ CORDERO
DISTRICT 5 - EMILY BONILLA
DISTRICT 6 - VICTORIA P. SIPLIN
MAYOR:
JERRY L. DEMINGS
N
ORANGE COUNTY PUBLIC WORKS
BUILDINGS 2 AND 5
4200 S. JOHN YOUNG PARKWAY
ORLANDO, FLORIDA 32839
S
J O
H N
Y O
U N
G P
A R
K W
A Y
SITE VICINITY MAP
ORANGE COUNTY - PUBLIC WORKS
BUILDING 2 AND BUILDING 5
ROOFING REPLACEMENT PROJECT
PREPARED FOR:
FEBRUARY 9, 2021
4200 S. JOHN YOUNG PARKWAY
ORLANDO, FLORIDA 32839
STATEMENT OF COMPLIANCE
TO THE BEST OF OUR KNOWLEDGE THESE
DRAWINGS ARE COMPLETE AND COMPLY WITH
THE FLORIDA BUILDING CODE 2017 (6TH ED), AND
REFERENCED STATUTES, CODES, RULES AND
REGULATIONS REFERENCED THEREIN.
DRAWING INDEX
SHEET NUMBER SHEET TITLE ORIGINAL
DATE
REVISION
NUMBER REVISION DATE
G1.0 COVER SHEET 2/9/2021 0 NA
G1.1
SYMBOLS, ABBREVIATIONS AND
CODE INFORMATION
2/9/2021 0 NA
G1.2 GENERAL NOTES 2/9/2021 0 NA
G1.3 SCOPE OF WORK 2/9/2021 0 NA
G1.4 OVERALL SITE PLAN AND AERIAL VIEW 2/9/2021 0 NA
A2.1 BUILDING 2 - PROPOSED ROOF PLAN 2/9/2021 0 NA
A2.1.1 BUILDING 2 - WIND UPLIFT PRESSURE ROOF PLAN 2/9/2021 0 NA
A2.1.2 BUILDING 2 - PROPOSED ROOF DRAINAGE PLAN 2/9/2021 0 NA
A2.2 BUILDING 5 - PROPOSED ROOF PLAN 2/9/2021 0 NA
A2.2.1 BUILDING 5 - WIND UPLIFT PRESSURE ROOF PLAN 2/9/2021 0 NA
A2.2.2 BUILDING 5 - PROPOSED ROOF DRAINAGE PLAN 2/9/2021 0 NA
A3.1 BUILDING 2 - PROPOSED BUILDING ELEVATIONS 2/9/2021 0 NA
A3.2 BUILDING 5 - PROPOSED BUILDING ELEVATIONS 2/9/2021 0 NA
A4.1 BUILDINGS 2 & 5 - WALL SECTIONS 2/9/2021 0 NA
A5.1 ROOF DETAILS 2/9/2021 0 NA
A5.2 ROOF DETAILS 2/9/2021 0 NA
A5.3 ROOF DETAILS 2/9/2021 0 NA
A5.4 ROOF DETAILS 2/9/2021 0 NA
A5.5 ROOF DETAILS 2/9/2021 0 NA
A5.6 ROOF DETAILS 2/9/2021 0 NA
A5.7 ROOF DETAILS 2/9/2021 0 NA
A6.1 PHOTOGRAPHS 2/9/2021 0 NA G1.0N.T.S.
COVER SHEET
SHEET
REVISIONS
NUMBER TYPE DATE:
CONSTRUCTION DOCUMENTS
PLOT:
FAX: (407) 333-4686
3246 LAKEVIEW OAKS DRIVE LONGWOOD, FLORIDA 32779
JAY AMMON ARCHITECT, INC.
(407) 333-1977 E MAIL: JAY@JAYAMMON.COM
CAS / NHR
APPROVED BY:
DRAWN BY:
JPA CONSTRUCTION DOCS
PROJECT NUMBER:
PHASE:
19-066
ENGINEER: FEBRUARY 9, 2021DATE:
ORLANDO, FLORIDA
ORANGE COUNTY - PUBLIC WORKS
ROOFING REPLACEMENT PROJECT
BUILDINGS 2 AND 5
ARCHITECTURAL ABBREVIATIONS SYMBOLSMATERIALS LEGEND
CODE INFORMATION
APPLICABLE BUILDING CODES
BUILDING 2
BUILDING 5
G1.1N.T.S.
SYMBOLS, ABBREVIATIONS
& CODE INFORMATION
SHEET
REVISIONS
NUMBER TYPE DATE:
CONSTRUCTION DOCUMENTS
PLOT:
FAX: (407) 333-4686
3246 LAKEVIEW OAKS DRIVE LONGWOOD, FLORIDA 32779
JAY AMMON ARCHITECT, INC.
(407) 333-1977 E MAIL: JAY@JAYAMMON.COM
CAS / NHR
APPROVED BY:
DRAWN BY:
JPA CONSTRUCTION DOCS
PROJECT NUMBER:
PHASE:
19-066
ENGINEER: FEBRUARY 9, 2021DATE:
ORLANDO, FLORIDA
ORANGE COUNTY - PUBLIC WORKS
ROOFING REPLACEMENT PROJECT
BUILDINGS 2 AND 5
AutoCAD SHX Text
C.M.U. ( SECTION )
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text
LETTER FOR DETAIL
AutoCAD SHX Text
NUMBER FOR SECTION
AutoCAD SHX Text
SHEET ON WHICH
AutoCAD SHX Text
SHEET ON WHICH ELEVATION OCCURS
AutoCAD SHX Text
NUMBER
AutoCAD SHX Text
WALL SECTION
AutoCAD SHX Text
ELEVATION
AutoCAD SHX Text
LETTERS FOR DETAILS
AutoCAD SHX Text
SHEET ON WHICH DETAIL OCCURS
AutoCAD SHX Text
NUMBER
AutoCAD SHX Text
DETAIL
AutoCAD SHX Text
SECTION OCCURS
AutoCAD SHX Text
OVERALL BUILDING SECTION
AutoCAD SHX Text
SECTION OCCURS
AutoCAD SHX Text
SHEET ON WHICH
AutoCAD SHX Text
NUMBER
AutoCAD SHX Text A
AutoCAD SHX Text A2.1
AutoCAD SHX Text
AutoCAD SHX Text A3.1
AutoCAD SHX Text
AutoCAD SHX Text A4.1
AutoCAD SHX Text
AutoCAD SHX Text A4.1
AutoCAD SHX Text
AutoCAD SHX Text A4.1
AutoCAD SHX Text
AutoCAD SHX Text A4.1
AutoCAD SHX Text
NUMBERS FOR FLOOR, ENLARGED UNIT FLOOR PLANS & PHOTOS
AutoCAD SHX Text
EARTH
AutoCAD SHX Text
CONCRETE MASONRY
AutoCAD SHX Text
CONCRETE
AutoCAD SHX Text
COMPRESSIBLE FILLER
AutoCAD SHX Text
PORTLAND CEMENT
AutoCAD SHX Text
PLASTER OVER METAL LATH
AutoCAD SHX Text
UNIT
AutoCAD SHX Text
PORTLAND
AutoCAD SHX Text
BATT INSULATION
AutoCAD SHX Text
ACOUSTICAL TILE
AutoCAD SHX Text
ACOUSTICAL INSULATION
AutoCAD SHX Text
MOTOR CONTROL CENTER
AutoCAD SHX Text
MATERIAL
AutoCAD SHX Text
MODIFIED BITUMINOUS SHEET ROOFING
AutoCAD SHX Text
MAINTENANCE
AutoCAD SHX Text
HOSE BIBB
AutoCAD SHX Text
HOLLOW METAL
AutoCAD SHX Text
INSIDE DIAMETER
AutoCAD SHX Text
HORIZONTAL
AutoCAD SHX Text
HEATING VENTILATING & AIR CONDITIONING
AutoCAD SHX Text
KITCHEN EQUIPMENT CONTRACTOR
AutoCAD SHX Text
MAX
AutoCAD SHX Text
MCC
AutoCAD SHX Text
MBSR
AutoCAD SHX Text
MATL
AutoCAD SHX Text
MAINT
AutoCAD SHX Text
KEC
AutoCAD SHX Text
MAXIMUM
AutoCAD SHX Text
INSUL
AutoCAD SHX Text
ID
AutoCAD SHX Text
HT
AutoCAD SHX Text
HB
AutoCAD SHX Text
HM
AutoCAD SHX Text
HORIZ
AutoCAD SHX Text
INSULATION
AutoCAD SHX Text
MEMBER
AutoCAD SHX Text
FINISH SYSTEM
AutoCAD SHX Text
PLYWOOD
AutoCAD SHX Text
WOOD BLOCKING
AutoCAD SHX Text
CONTINUOUS WOOD
AutoCAD SHX Text
FINISHED WOOD MEMBER
AutoCAD SHX Text
EXTERIOR INSULATION &
AutoCAD SHX Text
GLASS
AutoCAD SHX Text
GYPSUM BOARD
AutoCAD SHX Text
RIGID INSULATION
AutoCAD SHX Text
METAL
AutoCAD SHX Text
WATER RESISTANT
AutoCAD SHX Text
WORK POINT
AutoCAD SHX Text
WALL COVERING OR WATER CLOSET
AutoCAD SHX Text
WOOD
AutoCAD SHX Text
VINYL COMPOSITION TILE
AutoCAD SHX Text
UPHOLSTERY
AutoCAD SHX Text
TOP OF PARAPET
AutoCAD SHX Text
TOP OF WALL
AutoCAD SHX Text
UNLESS NOTED OTHERWISE
AutoCAD SHX Text
TOP OF STEEL
AutoCAD SHX Text
WD
AutoCAD SHX Text
WR
AutoCAD SHX Text
WP
AutoCAD SHX Text W/
AutoCAD SHX Text W/O
AutoCAD SHX Text
WC
AutoCAD SHX Text W
AutoCAD SHX Text
WITH
AutoCAD SHX Text
WIDE
AutoCAD SHX Text
WITHOUT
AutoCAD SHX Text
VCT
AutoCAD SHX Text
VERT
AutoCAD SHX Text
UPH
AutoCAD SHX Text
UNO
AutoCAD SHX Text
TYP
AutoCAD SHX Text
TOP
AutoCAD SHX Text
TOS
AutoCAD SHX Text
TOW
AutoCAD SHX Text
VERTICAL
AutoCAD SHX Text
TYPICAL
AutoCAD SHX Text
CARPET
AutoCAD SHX Text
CPT
AutoCAD SHX Text
EXPOSED
AutoCAD SHX Text
EXP
AutoCAD SHX Text
GLASS FIBER REINFORCED CONCRETE
AutoCAD SHX Text
FLOOR DRAIN
AutoCAD SHX Text
FINISH FLOOR
AutoCAD SHX Text
FIRE HOSE CABINET
AutoCAD SHX Text
FACE OF CONCRETE
AutoCAD SHX Text
FACE OF FINISH
AutoCAD SHX Text
FACE OF MASONRY
AutoCAD SHX Text
FACE OF STUD
AutoCAD SHX Text
FIBERGLASS REINFORCED PLASTIC
AutoCAD SHX Text FLOOR SINK or FINISH SEALER
AutoCAD SHX Text
GALVANIZED
AutoCAD SHX Text
GLASS FIBER REINFORCED GYPSUM
AutoCAD SHX Text
FOS
AutoCAD SHX Text
GA
AutoCAD SHX Text
GFRG
AutoCAD SHX Text H
AutoCAD SHX Text
GALV
AutoCAD SHX Text
GFRC
AutoCAD SHX Text
FT
AutoCAD SHX Text
FS
AutoCAD SHX Text
FRP
AutoCAD SHX Text
GAUGE
AutoCAD SHX Text
HIGH
AutoCAD SHX Text
FEET
AutoCAD SHX Text
FOF
AutoCAD SHX Text
FOC
AutoCAD SHX Text
FOM
AutoCAD SHX Text
FIN
AutoCAD SHX Text
FLR
AutoCAD SHX Text
FHC
AutoCAD SHX Text
FBR
AutoCAD SHX Text
FD
AutoCAD SHX Text
FF
AutoCAD SHX Text
EXT
AutoCAD SHX Text
FINISH
AutoCAD SHX Text
FLOOR
AutoCAD SHX Text
EXTERIOR
AutoCAD SHX Text
FABRIC
AutoCAD SHX Text
DISTRESSED WOOD PROCESS
AutoCAD SHX Text
CERAMIC TILE
AutoCAD SHX Text
DIAMETER
AutoCAD SHX Text
DOWN SPOUT
AutoCAD SHX Text
DISTRESSED METAL PROCESS
AutoCAD SHX Text
ELECTRICAL DRINKING FOUNTAIN
AutoCAD SHX Text
DIAGONAL
AutoCAD SHX Text
EXTERIOR INSULATION & FINISH SYSTEM
AutoCAD SHX Text
EXPANSION JOINT
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
EQUIPMENT
AutoCAD SHX Text
ELECTRONIC EQUIPMENT ROOM
AutoCAD SHX Text
DS
AutoCAD SHX Text
EER
AutoCAD SHX Text
ELEC
AutoCAD SHX Text
EQUIP
AutoCAD SHX Text
EQ
AutoCAD SHX Text
EIFS
AutoCAD SHX Text
EJ
AutoCAD SHX Text (E)
AutoCAD SHX Text
EA
AutoCAD SHX Text
EDF
AutoCAD SHX Text
EQUAL
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EACH
AutoCAD SHX Text
DMP
AutoCAD SHX Text
DWP
AutoCAD SHX Text
DN
AutoCAD SHX Text
DIAG
AutoCAD SHX Text
DET
AutoCAD SHX Text
DIA
AutoCAD SHX Text
DBL
AutoCAD SHX Text D
AutoCAD SHX Text
CT
AutoCAD SHX Text
DETAIL
AutoCAD SHX Text
DOWN
AutoCAD SHX Text
DEPTH
AutoCAD SHX Text
DOUBLE
AutoCAD SHX Text
ALUMINUM
AutoCAD SHX Text
CONCRETE MASONRY UNIT
AutoCAD SHX Text
ABOVE FINISHED FLOOR
AutoCAD SHX Text AREA DRAIN or AREA DEVELOPMENT
AutoCAD SHX Text ACOUSTICAL CEILING TILE or ACOUSTICAL TREATMENT
AutoCAD SHX Text
AIR CONDITIONING
AutoCAD SHX Text
CONTROL JOINT
AutoCAD SHX Text
CONCRETE
AutoCAD SHX Text
CONTINUOUS
AutoCAD SHX Text
CLG
AutoCAD SHX Text
COL
AutoCAD SHX Text
CONC
AutoCAD SHX Text
CONT
AutoCAD SHX Text
CMU
AutoCAD SHX Text
CLR
AutoCAD SHX Text
CJ
AutoCAD SHX Text
BLDG
AutoCAD SHX Text
CEILING
AutoCAD SHX Text
CLEAR
AutoCAD SHX Text
COLUMN
AutoCAD SHX Text
BUILDING
AutoCAD SHX Text
ALUM
AutoCAD SHX Text
AFF
AutoCAD SHX Text
AD
AutoCAD SHX Text
ACT
AutoCAD SHX Text A/C
AutoCAD SHX Text
OWNER FURNISHED ITEM
AutoCAD SHX Text
OFI
AutoCAD SHX Text
REF
AutoCAD SHX Text
REFERENCE
AutoCAD SHX Text
SANITARY SHEET PLASTIC
AutoCAD SHX Text
TOP OF MASONRY
AutoCAD SHX Text
SURFACED FOUR SIDES
AutoCAD SHX Text
SPECIAL FINISH
AutoCAD SHX Text
RESILIENT FLOOR
AutoCAD SHX Text SQUARE FEET or STONE FACE
AutoCAD SHX Text
ROUGH OPENING
AutoCAD SHX Text
SOLID CORE
AutoCAD SHX Text
STAINLESS STEEL
AutoCAD SHX Text
STANDARD
AutoCAD SHX Text
SUSPENDED
AutoCAD SHX Text
TONGUE AND GROOVE
AutoCAD SHX Text
TELEPHONE
AutoCAD SHX Text TOP OF CONCRETE or CURB
AutoCAD SHX Text
SQUARE
AutoCAD SHX Text
SQ
AutoCAD SHX Text T&G
AutoCAD SHX Text
TOM
AutoCAD SHX Text
TOC
AutoCAD SHX Text
TEL
AutoCAD SHX Text T
AutoCAD SHX Text
STD
AutoCAD SHX Text S4S
AutoCAD SHX Text
SUSP
AutoCAD SHX Text
SSP
AutoCAD SHX Text
SS
AutoCAD SHX Text
TREAD
AutoCAD SHX Text
SPF
AutoCAD SHX Text
SIM
AutoCAD SHX Text
SF
AutoCAD SHX Text
SHT
AutoCAD SHX Text
SC
AutoCAD SHX Text
RO
AutoCAD SHX Text
REQD
AutoCAD SHX Text
RM
AutoCAD SHX Text
RF
AutoCAD SHX Text
SIMILAR
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
ROOM
AutoCAD SHX Text
REQUIRED
AutoCAD SHX Text
RESILIENT BASE STRAIGHT
AutoCAD SHX Text
REFLECTED CEILING PLAN
AutoCAD SHX Text
RESILIENT BASE COVE
AutoCAD SHX Text
POINT OF SALE
AutoCAD SHX Text
OWNER FURNISHED CONTRACTOR INSTALLED
AutoCAD SHX Text
OWNER FURNISHED OWNER INSTALLED
AutoCAD SHX Text
POINT OF CONNECTION
AutoCAD SHX Text
PLASTIC LAMINATE
AutoCAD SHX Text
PREPARATION
AutoCAD SHX Text
QUARRY TILE
AutoCAD SHX Text
ROOF DRAIN
AutoCAD SHX Text
PREP
AutoCAD SHX Text R or RAD
AutoCAD SHX Text R
AutoCAD SHX Text
RBS
AutoCAD SHX Text
RCP
AutoCAD SHX Text
RD
AutoCAD SHX Text
RBC
AutoCAD SHX Text
QT
AutoCAD SHX Text
RISER
AutoCAD SHX Text
RADIUS
AutoCAD SHX Text
POC
AutoCAD SHX Text
POS
AutoCAD SHX Text
PR
AutoCAD SHX Text
PLYWD
AutoCAD SHX Text
PNT
AutoCAD SHX Text
PLAM
AutoCAD SHX Text
PL
AutoCAD SHX Text
OFOI
AutoCAD SHX Text
OFCI
AutoCAD SHX Text
OPP
AutoCAD SHX Text
PLYWOOD
AutoCAD SHX Text
PAINT
AutoCAD SHX Text
PAIR
AutoCAD SHX Text
PLATE
AutoCAD SHX Text
OPPOSITE
AutoCAD SHX Text
OPERATOR CONTROL PANEL
AutoCAD SHX Text
OPERATOR CONTROL CONSOLE
AutoCAD SHX Text
MANUFACTURER
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
MEZZANINE
AutoCAD SHX Text
MOISTURE RESISTANT TREATMENT
AutoCAD SHX Text
MISCELLANEOUS
AutoCAD SHX Text
NOT RATED
AutoCAD SHX Text
NOT IN CONTRACT
AutoCAD SHX Text OUTSIDE DIAMETER or OVERFLOW DRAIN
AutoCAD SHX Text
ON CENTER
AutoCAD SHX Text
MRT
AutoCAD SHX Text
OCC
AutoCAD SHX Text
OCP
AutoCAD SHX Text
OD
AutoCAD SHX Text
OC
AutoCAD SHX Text
NIC
AutoCAD SHX Text
NR
AutoCAD SHX Text
MIN
AutoCAD SHX Text
MFR
AutoCAD SHX Text
MISC
AutoCAD SHX Text
MECH
AutoCAD SHX Text
MEZZ
AutoCAD SHX Text
MINIMUM
AutoCAD SHX Text
CEMENT PLASTER
AutoCAD SHX Text
WDF
AutoCAD SHX Text
WOOD FLOOR
AutoCAD SHX Text
STONE
AutoCAD SHX Text
ST
AutoCAD SHX Text
METAL
AutoCAD SHX Text
MET
AutoCAD SHX Text
BRICK FACE
AutoCAD SHX Text
BF
AutoCAD SHX Text
METAL FACE
AutoCAD SHX Text
MF
AutoCAD SHX Text
PF
AutoCAD SHX Text
PLASTER FACE
AutoCAD SHX Text
WOOD FACE
AutoCAD SHX Text
WF
AutoCAD SHX Text
ELEVATION
AutoCAD SHX Text
EL
AutoCAD SHX Text
MASONRY OPENING
AutoCAD SHX Text
MO
AutoCAD SHX Text
ACRYLIC RESIN FLOORING
AutoCAD SHX Text
ARF
AutoCAD SHX Text
BOARD
AutoCAD SHX Text
BD
AutoCAD SHX Text
BO
AutoCAD SHX Text
BOTTOM OF
AutoCAD SHX Text
BOH
AutoCAD SHX Text
BACK OF HOUSE
AutoCAD SHX Text
BOT
AutoCAD SHX Text
BOTTOM
AutoCAD SHX Text
CONTRACTOR FURNISHED OWNER INSTALLED
AutoCAD SHX Text
CFOI
AutoCAD SHX Text
DRAWING
AutoCAD SHX Text
DWG
AutoCAD SHX Text
DRAWER
AutoCAD SHX Text
DWR
AutoCAD SHX Text
EYEHOOK
AutoCAD SHX Text
EH
AutoCAD SHX Text
FOUNDATION
AutoCAD SHX Text
FDN
AutoCAD SHX Text
FINISH FLOOR ELEVATION
AutoCAD SHX Text
FFE
AutoCAD SHX Text
GLASS
AutoCAD SHX Text
GL
AutoCAD SHX Text
GYPSUM BOARD
AutoCAD SHX Text
GYP BD
AutoCAD SHX Text
HIGH POINT
AutoCAD SHX Text
HP
AutoCAD SHX Text
HEIGHT
AutoCAD SHX Text
HVAC
AutoCAD SHX Text
INT
AutoCAD SHX Text
INTERIOR
AutoCAD SHX Text
JT
AutoCAD SHX Text
JOINT
AutoCAD SHX Text
LAVATORY
AutoCAD SHX Text
LAV
AutoCAD SHX Text
LIVE LOAD
AutoCAD SHX Text
LL
AutoCAD SHX Text
NEW
AutoCAD SHX Text (N)
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
NTS
AutoCAD SHX Text
PROJECTION
AutoCAD SHX Text
PROJ
AutoCAD SHX Text
POUNDS PER SQUARE FPPT
AutoCAD SHX Text
PSF
AutoCAD SHX Text
REINFORCED CONCRETE
AutoCAD SHX Text
RC
AutoCAD SHX Text
ROUGH SAWN
AutoCAD SHX Text
RS
AutoCAD SHX Text
STEEL
AutoCAD SHX Text
STL
AutoCAD SHX Text
STRUCTURAL
AutoCAD SHX Text
STRUCT
AutoCAD SHX Text
VIF
AutoCAD SHX Text
VERIFY IN FIELD
AutoCAD SHX Text
WOOD BASE
AutoCAD SHX Text
WDB
AutoCAD SHX Text
APPROX
AutoCAD SHX Text
APPROXIMATELY
AutoCAD SHX Text
AIR HANDLING UNIT
AutoCAD SHX Text
AHU
AutoCAD SHX Text
CLEAN OUT
AutoCAD SHX Text
CO
AutoCAD SHX Text
DEAD LOAD
AutoCAD SHX Text
DL
AutoCAD SHX Text
FMG
AutoCAD SHX Text
FACTORY MUTUAL GLOBAL
AutoCAD SHX Text
FRT
AutoCAD SHX Text
FIRE RETARDANT TREATED
AutoCAD SHX Text
NATIONAL ROOFING CONTRACTORS ASSOCIATION
AutoCAD SHX Text
NRCA
AutoCAD SHX Text P.S.I.
AutoCAD SHX Text
POUNDS PER SQUARE INCH
AutoCAD SHX Text
PRESSURE TREATED
AutoCAD SHX Text
PT
AutoCAD SHX Text
SQUARE FEET OR SQUARE FOOT
AutoCAD SHX Text
SQ FT
AutoCAD SHX Text
SOUTHERN YELLOW PINE
AutoCAD SHX Text
SYP
AutoCAD SHX Text
GALLON
AutoCAD SHX Text
GAL
AutoCAD SHX Text
HOUR
AutoCAD SHX Text
HR
AutoCAD SHX Text
KILN DRIED AFTER TREATMENT
AutoCAD SHX Text
KDAT
AutoCAD SHX Text
LOW POINT
AutoCAD SHX Text
LP
AutoCAD SHX Text
UL
AutoCAD SHX Text
UNDERWRITERS LABORATORIES INC.
AutoCAD SHX Text
KD
AutoCAD SHX Text
KILN DRIED
AutoCAD SHX Text
DENS DECK SHEATHING
AutoCAD SHX Text
2020 FLORIDA BUILDING CODE - BUILDING
AutoCAD SHX Text
BUILDING :
AutoCAD SHX Text Edition :
AutoCAD SHX Text
SEVENTH
AutoCAD SHX Text Edition :
AutoCAD SHX Text
SEVENTH
AutoCAD SHX Text Edition :
AutoCAD SHX Text Edition :
AutoCAD SHX Text Edition :
AutoCAD SHX Text Edition :
AutoCAD SHX Text Edition :
AutoCAD SHX Text
SEVENTH
AutoCAD SHX Text
SEVENTH
AutoCAD SHX Text
SEVENTH
AutoCAD SHX Text
SEVENTH
AutoCAD SHX Text
SEVENTH
AutoCAD SHX Text Edition :
AutoCAD SHX Text
SEVENTH
AutoCAD SHX Text
2020 FLORIDA BUILDING CODE - EXISTING BUILDING
AutoCAD SHX Text
EXISTING :
AutoCAD SHX Text
2020 FLORIDA BUILDING CODE - MECHANICAL
AutoCAD SHX Text
MECHANICAL :
AutoCAD SHX Text
2020 FLORIDA BUILDING CODE - PLUMBING
AutoCAD SHX Text
PLUMBING :
AutoCAD SHX Text
2020 FLORIDA BUILDING CODE - FUEL GAS
AutoCAD SHX Text
FUEL GAS :
AutoCAD SHX Text
2020 FLORIDA BUILDING CODE - ACCESSIBILITY
AutoCAD SHX Text
ACCESSIBILITY :
AutoCAD SHX Text
2020 FLORIDA BUILDING CODE - ENERGY CONSERVATION
AutoCAD SHX Text
ENERGY :
AutoCAD SHX Text
FLORIDA FIRE PREVENTION CODE (2020)
AutoCAD SHX Text
FIRE :
AutoCAD SHX Text
CONSTRUCTION TYPE: TYPE ITYPE I
AutoCAD SHX Text
FIRE SPRINKLERS: YESYES
AutoCAD SHX Text OCCUPANCY: CLASSIFICATION: BUSINESS GROUP - B1CLASSIFICATION: BUSINESS GROUP - B1
AutoCAD SHX Text
STORIES: 11
AutoCAD SHX Text
BUILDING HEIGHT: 24'-5" TO TOP OF RIDGE24'-5" TO TOP OF RIDGE
AutoCAD SHX Text
PROJECT AREA: ROOF AREA - 22,154 SQ. FT.ROOF AREA - 22,154 SQ. FT.
AutoCAD SHX Text
TOTAL AREA - 22,154 SQ. FT.
AutoCAD SHX Text
CONSTRUCTION TYPE: TYPE ITYPE I
AutoCAD SHX Text
FIRE SPRINKLERS: YESYES
AutoCAD SHX Text OCCUPANCY: CLASSIFICATION: BUSINESS GROUP - B1CLASSIFICATION: BUSINESS GROUP - B1
AutoCAD SHX Text
STORIES: 11
AutoCAD SHX Text
BUILDING HEIGHT: 19'-8" TO TOP OF RIDGE19'-8" TO TOP OF RIDGE
AutoCAD SHX Text
PROJECT AREA: ROOF AREA - 4,507 SQ. FT.ROOF AREA - 4,507 SQ. FT.
AutoCAD SHX Text
TOTAL AREA - 4,507 SQ. FT.
GENERAL NOTES:
A. THE CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS IN THE FIELD. THIS
SHALL INCLUDE VERIFYING THE EXACT LOCATIONS, DIMENSIONS AND QUANTITIES
OF ALL EQUIPMENT AND PENETRATIONS WHICH INCLUDES, BUT IS NOT LIMITED TO
VENT PIPES, DRAINS, ELECTRICAL JUNCTION BOXES, CURBS, BASE FLASHING AND
ALL OTHERS PENETRATIONS AND WORK ASSOCIATED WITH THIS PROJECT. THE
CONTRACTOR SHALL NOTIFY THE ARCHITECT, IN WRITING, OF ALL EXISTING
CONDITIONS WHICH ARE IN VARIANCE WITH THE CONDITIONS DOCUMENTED
HEREIN.
B. THE BUILDING MAY BE FULLY OR PARTIALLY OCCUPIED; CONTRACTOR IS SOLELY
RESPONSIBLE FOR ALL MEANS AND METHODS OF CONSTRUCTION AND FOR THE
SAFETY OF ALL PERSONS AT THE PROJECT SITE.
C. CONTRACTOR SHALL PROTECT ALL EXISTING CONSTRUCTION TO REMAIN,
INCLUDING ADJACENT ROOFS, WALLS, LANDSCAPE/VEGETATION, GROUNDS,
EXTERIOR SURFACES AND THE INTERIOR OF THE BUILDING. THIS SHALL INCLUDE,
BUT IS NOT LIMITED TO PAINT, WATER, DUST, DEBRIS AND PHYSICAL DAMAGE. ALL
SURFACES SHALL BE RESTORED TO THEIR PRE-DAMAGE CONDITION BY THE
CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER AND TO THE
SATISFACTION OF THE OWNER AND ARCHITECT.
D. ALL WORK SHALL BE PERFORMED IN STRICT ACCORDANCE WITH ALL
CODES AND AUTHORITIES HAVING JURISDICTION OVER THIS PROJECT.
E. ALL DETAILS INDICATE MINIMUM INSTALLATION REQUIREMENTS. IF THE
MANUFACTURER'S STANDARDS DETAILS ARE MORE STRINGENT, IN THE OPINION
OF THE ARCHITECT, THEY SHALL GOVERN. IF THE DETAILS SHOWN ARE MORE
STRINGENT THAN THE MANUFACTURER'S STANDARD DETAILS, IN THE OPINION OF
THE ARCHITECT, THE DETAILS SHOWN SHALL GOVERN, REGARDLESS OF THE
MANUFACTURER'S WILLINGNESS TO WARRANT / GUARANTY THE LESSER DETAIL.
BY SUBMITTING A BID FOR THIS PROJECT, IT IS UNDERSTOOD THAT THE
CONTRACTOR AND MANUFACTURER AGREE TO WARRANT / GUARANTY THE
DETAILS SHOWN. THE ARCHITECT MAY, BUT IS NOT OBLIGATED TO, ACCEPT ANY
PROPOSED CHANGES TO THE DETAILS SHOWN.
F. THE CONTRACTOR IS TO PROVIDE ALL LABOR AND MATERIAL FOR A COMPLETE
AND WATERTIGHT JOB WHICH IS FULLY WARRANTED / GUARANTEED BY THE
MANUFACTURER AS PROVIDED FOR IN THE CONTRACT DOCUMENTS. ANY DETAILS
OR WORK REQUIRED FOR A COMPLETE JOB, BUT NOT SHOWN OR SPECIFIED BY
THE CONTRACT DOCUMENTS, SHALL BE INSTALLED IN ACCORDANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS AND REQUIREMENTS AT NO ADDITIONAL
COST TO THE OWNER. ANY ADDITIONAL LABOR AND MATERIAL REQUIRED TO MEET
MANUFACTURER'S WARRANTY / GUARANTY REQUIREMENTS, BUT NOT INDICATED
BY THE CONTRACT DOCUMENTS, SHALL BE PROVIDED AT NO ADDITIONAL COST TO
THE OWNER.
G. ALL REFINISHING REQUIREMENTS, SHALL INCLUDE THE FOLLOWING: REMOVE ALL
RUST FROM METAL SURFACES AND APPLY COAT OF RUST INHIBITOR. REPLACE
ALL METAL COMPONENTS WHICH ARE CORRODED THROUGH THE METAL.
PRESSURE CLEAN ALL EXPOSED SURFACES. SECURE ALL LOOSE COMPONENTS
WITH STAINLESS STEEL FASTENERS WHICH EXTEND INTO SOLID SUBSTRATE
BELOW OR BEHIND COMPONENT BEING SECURED. CONCEAL FASTENER HEADS
WITH MATERIAL WHICH MATCHES ADJACENT SURFACES. REPAINT ALL EXPOSED
SURFACES TO MATCH EXISTING FINISHES.
H. LAYDOWN/STORAGE AREA IS LIMITED AND SHALL BE AS APPROVED BY THE
OWNER.
I. PRIOR TO PERFORMING WORK, CONTRACTOR SHALL INSPECT WORK SITE AND
EXISTING CONSTRUCTION FOR POTENTIAL SAFETY HAZARDS. PROVIDE FOR THE
SAFETY AND PROTECTION OF WORKERS AND OCCUPANTS THROUGHOUT COURSE
OF WORK. COMPLY WITH OSHA REQUIREMENTS.
J. BUILDING ACCESS IS RESTRICTED AND ALLOWED ONLY AS REQUIRED TO
ACCOMPLISH CONTRACT WORK. COORDINATE ANY REQUIRED ACCESS WITH THE
OWNER.
K. SITE SHALL BE CLEANED AND SECURED ON A DAILY BASIS AT THE END OF EACH
WORK SHIFT.
L. ALL COMPONENTS AND ASSEMBLIES SHALL MEET OR EXCEED UL STANDARDS FOR
A CLASS A FIRE RATING.
M.THE FINISH OF ALL NEW COMPONENTS OR REPAIRED COMPONENTS SHALL MATCH
ALL CHARACTERISTICS OF THE EXISTING COMPONENTS INCLUDING TEXTURE AND
ALL OTHER QUALITIES.
N. PATCH ALL FINISHES AFFECTED BY THE WORK OF THIS PROJECT AS REQUIRED TO
MATCH ALL CHARACTERISTICS OF EXISTING UNDAMAGED FINISHES.
O. ALL ITEMS IN DRAWINGS ARE NEW UNLESS DEPICTED/NOTED AS "EXISTING".
GENERAL SCOPE OF WORK:
A. SEE SHEET G1.3 FOR DESCRIPTION OF WORK.
BUILDING PROTECTION NOTES:
A. THE BUILDING WILL REMAIN FUNCTIONAL THROUGHOUT THE CONSTRUCTION PERIOD.
CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO CONTENTS AND
OCCUPANTS.
B. THE BUILDING SHALL BE WATERTIGHT AT THE END OF EACH DAYS CONSTRUCTION AND
WHEN INCLEMENT WEATHER THREATENS.
C. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO PROTECT THE
BUILDING, EXTERIOR AND GROUNDS, AND ALL PROMENADE CONCRETE WITHIN THE
PROJECT BOUNDARIES.
D. ANY SURFACES STAINED, MARKED, MARRED, OR DAMAGED BY THE CONTRACTOR SHALL
BE RETURNED TO THE ORIGINAL CONDITION AND TO MATCH ADJACENT SURFACES.
E. THE CONTRACTOR SHALL RETURN THE SITE AND ANY DAMAGED ITEMS OF THE SITE OR
FACILITY TO THE ORIGINAL CONDITION.
F. THE SEQUENCE OF WORK SHALL MINIMIZE CONSTRUCTION TRAFFIC ON THE NEW
WORK.
EXTERIOR RESTORATION NOTES:
A. FOR PURPOSES OF THIS PROJECT, REMOVE SHALL MEAN REMOVE AND DISPOSE OF IN
AN APPROVED AND LEGAL MANNER.
B. CONTRACTOR SHALL VERIFY THE TOTAL NUMBER OF DETAIL CONDITIONS IN THE FIELD
AND PERFORM NEW WORK IN ACCORDANCE WITH THE DETAIL REFERENCED OR THOSE
WHICH ARE SIMILAR. CONTRACTOR SHALL VERIFY ALL CONDITIONS IN THE FIELD.
C. GENERAL DEMOLITION SCOPE: SEE SHEET G1.3.
D. CONTRACTOR SHALL REMOVE ALL DEBRIS FROM CONSTRUCTION SITE AND DISPOSE OF
IN A LEGAL MANNER.
E. DAMAGED OR DETERIORATED WALL SUBSTRATE UNCOVERED DURING DEMOLITION
SHALL BE DOCUMENTED BY THE CONTRACTOR, REPORTED TO THE PROJECT MANAGER
IN WRITING.
F. THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL EXISTING MATERIALS AND
METHODS OF INSTALLATION BEFORE THE START OF WORK. ANY DISCREPANCIES
BETWEEN THE INFORMATION PROVIDED BY THE CONTRACT DOCUMENTS AND
CONDITIONS ENCOUNTERED BY THE CONTRACTOR BEFORE THE START OF WORK SHALL
BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE OWNER. THE CONTRACTOR SHALL
NOT BE ENTITLED TO COMPENSATION FOR ANY ADDITIONAL LABOR OR MATERIALS DUE
TO DIFFERING EXISTING CONDITIONS WHICH ARE NOT BROUGHT TO THE ATTENTION OF
THE OWNER PRIOR TO THE START OF WORK.
G. THE CONTRACTOR SHALL REMOVE ALL EXISTING EXTERIOR CONDUIT, PIPING, LIGHTING
FIXTURES, LIGHTNING PROTECTION SYSTEMS AND ANY OTHER ITEMS WHICH INTERFERE
WITH THE INSTALLATION OF THE NEW EXTERIOR BUILDING ENVELOPE COMPONENTS
AND OR RELATED WORK. ALL SUCH EQUIPMENT AND ITEMS SHALL BE TEMPORARILY
RE-ROUTED AS NECESSARY IF IT IS REQUIRED TO STAY IN SERVICE. ANY ITEMS NOT
REQUIRED TO STAY IN SERVICE SHALL BE PROPERLY STORED BY THE CONTRACTOR AND
REINSTALLED AT THE COMPLETION OF THE WORK. ALL WORK SHALL BE PERFORMED BY
QUALIFIED, LICENSED CRAFTSMEN IN ACCORDANCE WITH ALL APPLICABLE BUILDING
CODES AT NO ADDITIONAL COST TO THE OWNER. ANY EXISTING WORK WHICH DOES
NOT CONFORM TO APPLICABLE CURRENT CODES SHALL BE REPORTED TO THE OWNER
IN WRITING PRIOR TO THE REMOVAL.
H. ALL DEPICTED COMPONENTS ON DRAWINGS ARE NEW UNLESS IDENTIFIED/NOTED AS
"EXISTING".
SPECIFIC NOTES:
1. PERFORMANCE REQUIREMENTS: THE CONTRACTOR SHALL BASE THE BID UPON PROVIDING A
COMPLETE ROOFING REPLACEMENT PROJECT AS REQUIRED TO PROVIDE ASSEMBLIES WHICH WILL
REMAIN WATERTIGHT FOR A MINIMUM PERIOD OF 20 YEARS.
2. EXISTING CONDITIONS VERIFICATION: THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS, INCLUDING BUT NOT LIMITED TO, ROOF AREA SIZES, ROOF SLOPES, EXISTING ROOF MATERIALS AND DETAILS. THE CONTRACTOR SHALL ADVISE THE ARCHITECT OF ANY DISCREPANCIES BETWEEN ACTUAL FIELD CONDITIONS AND THE CONSTRUCTION DOCUMENTS, PRIOR TO SUBMISSION
OF THE BID.
3. COMPLIANCE WITH INDUSTRY STANDARDS: ALL WORK SHALL BE PERFORMED IN
ACCORDANCE WITH THE APPLICABLE DOCUMENT REQUIREMENTS, MANUFACTURER'S
RECOMMENDATIONS, AND OTHER RECOGNIZED INDUSTRY STANDARDS, INCLUDING BUT NOT LIMITED TO, "THE NRCA "ROOFING MANUAL: METAL PANEL AND SPF ROOF SYSTEMS - 2020", "THE NRCA
ROOFING MANUAL: ARCHITECTURAL METAL FLASHING AND CONDENSATION CONTROL AND AIR
LEAKAGE CONTROL - 2018", THE SMACNA "ARCHITECTURAL SHEET METAL MANUAL 7TH EDITION".
4. COMPLIANCE WITH FLORIDA BUILDING CODE 2017 (6TH ED): ALL WORK TO MEET OR
EXCEED REQUIREMENTS OF THE FLORIDA BUILDING CODE 2017 (6TH ED).
5. WIND RESISTANCE: ALL ROOFING AND OTHER COMPONENTS SHALL BE INSTALLED TO RESIST ALL FORCES RESULTING FROM AN ULTIMATE DESIGN WIND SPEED OF 150 MPH IN ACCORDANCE WITH ASCE 7-10 AND TO MEET OR EXCEED REQUIREMENTS OF CHAPTER 16, FLORIDA BUILDING CODE 2017 (6TH ED). SUBMIT ENGINEERING CALCULATIONS PREPARED BY A FLORIDA LICENSED STRUCTURAL
ENGINEER TO VERIFY COMPLIANCE WITH THIS REQUIREMENT FOR EACH NEW COMPONENT. SEE
WIND UPLIFT PRESSURE PLAN FOR WIND UPLIFT PRESSURES AND ZONES.
6. TESTING: CONDUCT APPROPRIATE TESTS FOR EACH NEWLY INSTALLED COMPONENT.
7. TYPICAL NOTES, SECTIONS AND DETAILS: NOTES, SECTIONS, AND DETAILS DESCRIBING
REQUIRED WORK AT EACH COMPONENT ARE TYPICAL FOR ALL SIMILAR COMPONENTS AND THE
NOTE, SECTION, OR DETAIL SHALL APPLY AS IF CALLED OUT SEPARATELY AT EACH LOCATION. THE
DETAILS REFLECT A GENERAL DESIGN OF EACH DETAIL. THE CONTRACTOR SHALL MAKE ANY
REQUIRED MODIFICATIONS TO THE GIVEN DETAILS NECESSARY TO MAKE THE DETAIL COMPATIBLE WITH EXISTING CONDITIONS. THE CONTRACTOR SHALL OBTAIN APPROVAL FROM THE ARCHITECT
FOR ALL MODIFIED DETAILS BEFORE THE DETAILS ARE CONSTRUCTED.
8. PATCHING: PATCH ALL EXISTING COMPONENTS THAT ARE AFFECTED BY THE WORK OF THIS
PROJECT WHETHER OR NOT IDENTIFIED BY THE CONSTRUCTION DOCUMENTS TO BE PATCHED.
PATCHING IS DEFINED AS: REPAIRING ALL EXISTING COMPONENTS INCLUDING BUT NOT LIMITED TO
SUBSTRATE MATERIALS, STRUCTURAL COMPONENTS, AND FINISHES IN ACCORDANCE WITH
INDUSTRY STANDARDS. ALL FINISHES SHALL BE PATCHED TO MATCH ALL CHARACTERISTICS OF EXISTING ADJACENT MATERIALS INCLUDING BUT NOT LIMITED TO MATERIAL TYPE, FINISH TEXTURE, AND COLOR OF FINISH.
9. POSITIVE SLOPE: INSTALL NEW SLOPE WHERE DESIGNATED AND WHERE REQUIRED TO ACHIEVE A
POSITIVE ROOF SLOPE THAT DOES NOT POND WATER.
10. MOCKUPS: PREPARE IN-PLACE MOCKUPS OF EACH APPLICATION AND DETAIL. RECEIVE WRITTEN APPROVAL FROM ALL MATERIAL MANUFACTURER'S FOR PRODUCTS INCLUDED IN THE MOCKUP, FROM
THE ARCHITECT, AND FROM THE OWNER PRIOR TO FURTHER APPLICATION OR INSTALLATION.
11. REFERENCE TO "ALL": WHERE SCOPE OF WORK REFERS TO "ALL", THIS IS DEFINED AS ALL SIMILAR
COMPONENTS WHETHER OR NOT THAT REFERENCED COMPONENT IS DEPICTED ON THE DRAWING.
12. NEW COMPONENTS: ALL DEPICTED COMPONENTS ON DRAWINGS ARE NEW UNLESS IDENTIFIED
AS EXISTING.
13. INTERIOR PROTECTION: PRIOR TO DEMOLITION, INSTALL PROTECTION OVER INTERIOR SPACES AS REQUIRED TO PROTECT OCCUPANTS, BUILDING COMPONENTS, AND EQUIPMENT FROM WEATHER
ELEMENTS AND CONSTRUCTION RELATED DEBRIS.
14. WEATHERPROOF ENCLOSURE: APPLY WEATHERPROOF ROOF COVERINGS OVER THE ROOF
AREAS DESIGNATED FOR REPLACEMENT OR REPAIR AS REQUIRED TO PREVENT THE INTRUSION OF
WEATHER ELEMENTS INTO THE BUILDING DURING THE CONSTRUCTION PROCESS.
15. HOUSEKEEPING: THOROUGHLY CLEAN ALL CONSTRUCTION RELATED DEBRIS FROM ALL INTERIOR SURFACES, EXTERIOR SURFACES, AND SITE SURFACES ON A DAILY BASIS. ALL CONSTRUCTION EQUIPMENT, DEBRIS, AND NEW MATERIAL STORED ON THE SITE SHALL BE SECURED TO PREVENT
WIND DISPLACEMENT.
16. SAFETY: PROVIDE ALL NECESSARY MEASURES TO ENSURE SAFETY TO BUILDING OCCUPANTS DURING THE PERIODS WHEN THE BUILDING IS OCCUPIED. PREVENT ACCESS TO THE CONSTRUCTION AREAS AND STAGING AREAS BY SIGNS, FENCES, AND OTHER BARRIERS. INSTALL A TEMPORARY BARRIER OVER THE TOP OF ALL ENTRANCES FOR A DISTANCE OF 10 FEET BEYOND THE ENTRANCE AS
REQUIRED TO PROTECT PEDESTRIANS FROM FALLING DEBRIS.
17. MANUFACTURER'S AND PRODUCTS: MANUFACTURER'S AND PRODUCTS LISTED ARE A BASIS OF DESIGN. FOR ANY OTHER MANUFACTURER'S PRODUCTS, SUBMIT REQUEST FOR CONSIDERATION OF
EACH COMPARABLE PRODUCT DURING THE BIDDING PHASE. ALL COMPARABLE PRODUCTS
APPROVED WILL BE LISTED IN AN ADDENDUM.
18. TRADES: ALL WORK SHALL BE PERFORMED BY CONTRACTORS LICENSED IN THEIR TRADES AND AS REQUIRED BY THE BUILDING DEPARTMENT OFFICIALS. THESE TRADES INCLUDE BUT ARE NOT LIMITED
TO ROOFING CONTRACTORS, GENERAL CONTRACTORS, ELECTRICAL CONTRACTORS, HVAC
CONTRACTORS, PLUMBING CONTRACTORS, AND SEALANT CONTRACTORS.
19. FINAL INSPECTION: THE CONTRACTOR SHALL NOTIFY THE ARCHITECT AFTER ALL WORK HAS
BEEN COMPLETED. A FINAL INSPECTION SHALL BE PERFORMED JOINTLY BY THE ARCHITECT,
COUNTY STAFF, AND BUILDING OFFICIAL, IN ACCORDANCE WITH FLORIDA BUILDING CODE 2017 (6TH
ED) 1512.4.3.3.
SHEET
REVISIONS
NUMBER TYPE DATE:
CONSTRUCTION DOCUMENTS
PLOT:
FAX: (407) 333-4686
3246 LAKEVIEW OAKS DRIVE LONGWOOD, FLORIDA 32779
JAY AMMON ARCHITECT, INC.
(407) 333-1977 E MAIL: JAY@JAYAMMON.COM
CAS / NHR
APPROVED BY:
DRAWN BY:
JPA CONSTRUCTION DOCS
PROJECT NUMBER:
PHASE:
19-066
ENGINEER: FEBRUARY 9, 2021DATE:
ORLANDO, FLORIDA
ORANGE COUNTY - PUBLIC WORKS
ROOFING REPLACEMENT PROJECT
BUILDINGS 2 AND 5
N.T.S. G1.2
GENERAL NOTES
SCOPE OF WORK
THE SCOPE OF WORK INCLUDES, BUT IS NOT LIMITED TO THE
FOLLOWING:
1.0 GENERAL:
1.1 ENGINEERING: CONDUCT PULL TESTS OF THE EXISTING ROOF DECK.
PROVIDE ENGINEERING CALCULATIONS PREPARED BY A FLORIDA LICENSED
STRUCTURAL ENGINEER INCLUDING THE CLIP AND FASTENER SPACING FOR
EACH ROOF WIND ZONE. SUBMIT PULL TEST RESULTS AND THE ENGINEERING
CALCULATIONS TO THE ARCHITECT FOR REVIEW PRIOR TO COMMENCEMENT OF
THE ROOFING INSTALLATION. SEE DRAWINGS FOR WIND PRESSURES.
1.2 SUBSTRATE PREPARATION: PREPARE, REPAIR, OR REPLACE ALL
SURFACES AS NECESSARY TO COMPLY WITH REQUIREMENTS INCLUDING BUT
NOT LIMITED TO: WIND UPLIFT REQUIREMENTS, MANUFACTURER'S
RECOMMENDATIONS, BUILDING CODE REQUIREMENTS, AND RELEVANT
INDUSTRY STANDARDS. PRIOR TO INSTALLATION OF THE ROOFING ASSEMBLY
SUBMIT A WRITTEN APPROVAL TO THE ARCHITECT, FROM THE MANUFACTURER
OF THE ROOFING ASSEMBLY THAT ALL SUBSTRATES ARE PROPERLY PREPARED
FOR THE INSTALLATION OF THE ASSEMBLY.
1.3 WARRANTY: THE NEW ROOFING ASSEMBLY IS TO BE EXAMINED AND
APPROVED BY THE MANUFACTURER'S OF THE ROOFING ASSEMBLY AND SHALL
RECEIVE A 20 YEAR NDL LABOR AND MATERIAL WARRANTY AGAINST DEFECTS
AND LEAKS. THE CONTRACTOR SHALL SUBMIT A 5 YEAR NDL WARRANTY FOR
ALL WORK AGAINST DEFECTS AND LEAKS UPON COMPLETION OF THE WORK.
ADJUST THE SCOPE OF WORK AS REQUIRED TO OBTAIN THIS WARRANTY. SEE
SPEC. SECTION 07 41 10.
2.0 STANDING SEAM METAL ROOF PANEL ASSEMBLY:
2.1 DEMOLITION: REMOVE ALL EXISTING ROOFING COMPONENTS INCLUDING
BUT NOT LIMITED TO; EXISTING STANDING SEAM METAL ROOF PANELS,
UNDERLAYMENT, METAL FLASHINGS INCLUDING DRIP EDGES, RAKE FLASHINGS
AND ALL RELATED FASTENERS FROM TOP SURFACE OF THE EXISTING COVER
BOARD. REMOVE EXISTING GUTTERS, AND METAL DOWNSPOUTS.
2.2 ROOF DECK PREPARATION: REPLACE ALL EXISTING DETERIORATED ROOF
DECK COMPONENTS AND BASE THE COST OF THE EXISTING COMPONENT
REPLACEMENT ON THE BASE BID QUANTITY INCLUDED IN THE BID FORM UNDER
THE SECTION ENTITLED “UNIT COSTS”. REPLACE THE MATERIALS WITH
MATERIALS MATCHING ALL CHARACTERISTICS INCLUDING MATERIAL AND SIZE
OF THE EXISTING COMPONENTS. INSTALL ONE LAYER OF SELF-ADHERED
UNDERLAYMENT OVER REPLACED MATERIALS.
2.3 COVER BOARD AND INSULATION: INSTALL ONE LAYER OF THE
DESIGNATED THICKNESS OF INSULATION OVER THE EXISTING OR NEW
UNDERLAYMENT. INSTALL ONE LAYER OF COVER BOARD OVER THE
POLYISOCYANURATE INSULATION.
2.4 UNDERLAYMENT: PREPARE ALL ROOF SURFACES TO RECEIVE THE NEW
UNDERLAYMENT AS REQUIRED BY THE UNDERLAYMENT MANUFACTURER.
APPLY PRIMER OVER ALL COVER BOARD SURFACES. APPLY ONE PLY OF HIGH
TEMPERATURE SELF-ADHERED UNDERLAYMENT OVER ALL COVER BOARD
SURFACES AND OVER DESIGNATED ADJACENT SURFACES. APPLY AN
ADDITIONAL UNDERLAYMENT PLY OVER ALL VALLEYS AND OVER ALL PRIMED
METAL FLASHING FLANGES. INSTALL ADDITIONAL PLIES OF SELF-ADHERED
UNDERLAYMENT TO FORM A 10'-0" WIDE STRIP OF DOUBLE LAYER OF
SELF-ADHERED UNDERLAYMENT AT THE PEAK OF THE ARCHED ROOFS.
2.5 METAL ROOF PANELS: INSTALL A 24 GAUGE AZ-50 GALVALUME STEEL
STANDING SEAM ROOF PANELS WITH STIFFENING RIBS USING STAINLESS STEEL
CONCEALED CLIPS FABRICATED WITH THERMALLY MOVABLE COMPONENTS.
SECURE CLIPS THROUGH THE ROOFING ASSEMBLY AND INTO THE EXISTING
STEEL DECK. (SEE SPECIFICATION SECTION 07 41 10).
2.6 METAL FLASHINGS: INSTALL METAL FLASHINGS WITH FULLY WELDED
NON-MOVING SEAMS AND SECURE WITH STAINLESS STEEL FASTENERS AS
REQUIRED TO COMPLY WITH THE DESIGNATED WIND PRESSURES.
2.7 GUTTERS AND DOWNSPOUTS: FABRICATE AND INSTALL SLOPED GUTTERS
AND DOWNSPOUTS. GUTTERS AND DOWNSPOUTS WILL BE PRE-PAINTED WITH
SAFETY PAINT AND PER OWNER'S DIRECTION. INSERT THE DOWNSPOUTS INTO
THE EXISTING STORM LINES AT GRADE WITH NEW SHEET METAL TRANSITIONS.
PROVIDE SQUARE TO ROUND TRANSITIONS TO STORM DRAINS. MATCH THE
EXISTING DOWNSPOUT LOCATIONS.
2.8 PLUMBING VENT FLASHINGS: REMOVE ALL EXISTING PLUMBING AND FLUE
VENT FLASHINGS. EXTEND EXISTING PIPES WHERE REQUIRED TO MAINTAIN AN
8 INCH MINIMUM HEIGHT ABOVE THE NEW FINISHED ROOF SURFACE. INSTALL
PLUMBING VENT METAL FLASHINGS AND STAINLESS STEEL VANDAL-RESISTANT
CAPS.
2.9 VALLEY FLASHING: AT VALLEY FLASHING INSTALL TWO LAYERS OF
SELF-ADHERED UNDERLAYMENT WITH TOP LAYER EXTENDING 12" BEYOND BASE
LAYER ON EACH SIDE, INSTALLED SHINGLE-STYLE. INSTALL 24 GAUGE AZ-50
GALVALUME STEEL VALLEY FLASHING WITH 3" TALL DIVERTER. VALLEY FLASHING
TRANSITIONS TO BE MINIMUM 8" OVERLAP. VALLEY FLASHING TO BE MAXIMUM 4'
IN LENGTH. FULLY SOLDER CAP AT ROOF EDGE. SEE SPECIFICATION SECTION
07 62 00.
2.9A ALTERNATE: INSTALLATION OF A VALLEY DIVERTER: PROVIDE OWNER
WITH AN ALTERNATE PRICE FOR THE INSTALLATION OF AN ELEVATED VALLEY
DIVERTER PER DETAIL B/A5.4.
3.0 LIGHTNING PROTECTION:
3.1 LIGHTNING PROTECTION: REMOVE ALL LIGHTNING PROTECTION
ASSEMBLY COMPONENTS ATTACHED TO THE ROOFING ASSEMBLY, INCLUDING
BUT NOT LIMITED TO, AIR TERMINALS, CONDUCTOR CABLES, ATTACHMENT
COMPONENTS, AND RELATED FASTENERS. REPLACE ALL EXISTING LIGHTNING
PROTECTION WITH NEW COMPONENTS THAT WILL BE COMPATIBLE WITH THE
NEW ROOFING ASSEMBLY. WHERE EXISTING LIGHTNING PROTECTION DOES
NOT EXIST, INSTALL A NEW LIGHTNING PROTECTION ASSEMBLY. TIE-IN THE NEW
LIGHTNING PROTECTION ASSEMBLY COMPONENTS WITH THE EXISTING
LIGHTNING PROTECTION GROUNDING COMPONENTS USING BI-METAL
CONNECTORS WHERE MATERIAL COMPATIBILITY WILL NOT AFFECT THE NEW
ROOFING ASSEMBLY. INSTALL ALL LIGHTNING PROTECTION ASSEMBLIES AND
COMPONENTS BY A QUALIFIED, LICENSED LIGHTNING PROTECTION INSTALLER
WITH A MINIMUM OF 5 YEARS EXPERIENCE IN THE INSTALLATION OF LIGHTNING
PROTECTION SYSTEMS IN ACCORDANCE WITH NFPA-780 AND ALL APPLICABLE
BUILDING CODES. UL MASTER LABEL REQUIRED UPON COMPLETION.
SHEET
REVISIONS
NUMBER TYPE DATE:
CONSTRUCTION DOCUMENTS
PLOT:
FAX: (407) 333-4686
3246 LAKEVIEW OAKS DRIVE LONGWOOD, FLORIDA 32779
JAY AMMON ARCHITECT, INC.
(407) 333-1977 E MAIL: JAY@JAYAMMON.COM
CAS / NHR
APPROVED BY:
DRAWN BY:
JPA CONSTRUCTION DOCS
PROJECT NUMBER:
PHASE:
19-066
ENGINEER: FEBRUARY 9, 2021DATE:
ORLANDO, FLORIDA
ORANGE COUNTY - PUBLIC WORKS
ROOFING REPLACEMENT PROJECT
BUILDINGS 2 AND 5
N.T.S. G1.3
SCOPE OF WORK
BUILDINGS INCLUDED
IN THE SCOPE OF WORK
TR
UENN
PROPOSED STAGING AREA
(SEE CONSTRUCTION NOTE 2)
BUILDING 2 -
SEE ENLARGED PLANS ON
SHEETS A2.1, A2.1.1 AND A2.1.2
CONSTRUCTION NOTES:
1. CONSTRUCTION LIMITS: LIMITS ARE WITHIN 10 FEET MAXIMUM OF BUILDINGS EXCEPT WHERE OTHERWISE
INDICATED.
2. CONSTRUCTION STAGING AREA: FENCE PERIMETER USING 8'-0" HIGH CHAIN LINK FENCE. COORDINATE IN THE
FIELD WITH REPRESENTATIVE FROM THE OWNER.
3. ACCESSABLE PATH: THE ACCESSABLE PATH MUST BE LEFT UNIMPEDED THROUGHOUT THE CONSTRUCTION.
PROVIDE BARRIERS BETWEEN THE CONSTRUCTION AND THE ACCESSABLE PATH AS NECESSARY TO PROVIDE SAFE
ACCESS.
4. SAFETY PLAN: CONTRACTOR TO SUBMIT SAFETY PLAN WHICH CLEARLY DELINEATES AREAS FOR CONSTRUCTION, SAFETY BARRIERS, EXITS, CONSTRUCTION TRAFFIC DURING VARIOUS PHASES OF THE PROJECT AND WHEN CONDITIONS CHANGE. CONTRACTOR TO CONFORM WITH REQUIREMENTS IN FBC-B, FFPC 1-16.1 AND NFPA 241.
LEGEND
BUILDING 5 -
SEE ENLARGED PLANS ON
SHEETS A2.2, A2.2.1, AND A2.2.2
BUILDING 4 -
NOT IN CONTRACT
SCALE: N.T.S.G1.3
1 SITE PLAN
OVERALL
SCALE: 2G1.3
2 AERIAL VIEW
OVERALL
TR
UENN
BUILDING 2
BUILDING 5
BUILDING 4
N.I.C.
BUILDING -
N.I.C.
BUILDING -
N.I.C.
BUILDING -
N.I.C.
G1.4N.T.S.
OVERALL SITE PLAN
AND AERIAL VIEW
SHEET
REVISIONS
NUMBER TYPE DATE:
CONSTRUCTION DOCUMENTS
PLOT:
FAX: (407) 333-4686
3246 LAKEVIEW OAKS DRIVE LONGWOOD, FLORIDA 32779
JAY AMMON ARCHITECT, INC.
(407) 333-1977 E MAIL: JAY@JAYAMMON.COM
CAS / NHR
APPROVED BY:
DRAWN BY:
JPA CONSTRUCTION DOCS
PROJECT NUMBER:
PHASE:
19-066
ENGINEER: FEBRUARY 9, 2021DATE:
ORLANDO, FLORIDA
ORANGE COUNTY - PUBLIC WORKS
ROOFING REPLACEMENT PROJECT
BUILDINGS 2 AND 5
EXISTING WALL BELOW
A3.1
A3.1
A3.1
A3.1
NEW GUTTER ASSEMBLY
NEW GUTTER ASSEMBLY NEW GUTTER ASSEMBLYEXISTING WALL BELOW
A4.1
A4.1
A4.1
A4.1
A4.1
A4.1
A4.1
A4.1
A A5.2
A A5.2
A A5.2
B A5.1
A A5.4
A A5.4
A A5.1
C A5.2 A
A5.3 A
A5.3
VALLEY VA
LL
EY
A A5.2
A A5.2
A A5.4
B A5.1
B A5.1
A A5.4
A A5.4
A A5.4
B A5.1
B A5.1
A A5.1
A A5.1
C A5.2
C A5.2
10'
10'
DS# 1 DS# 2 DS# 3 DS# 4 DS# 5 DS# 6 DS# 7 DS# 8
DS# 16 DS# 15 DS# 14 DS# 12 DS# 11 DS# 10 DS# 9DS# 13
A4.1
A4.1
A4.1
SHEET
REVISIONS
NUMBER TYPE DATE:
CONSTRUCTION DOCUMENTS
PLOT:
FAX: (407) 333-4686
3246 LAKEVIEW OAKS DRIVE LONGWOOD, FLORIDA 32779
JAY AMMON ARCHITECT, INC.
(407) 333-1977 E MAIL: JAY@JAYAMMON.COM
CAS / NHR
APPROVED BY:
DRAWN BY:
JPA CONSTRUCTION DOCS
PROJECT NUMBER:
PHASE:
19-066
ENGINEER: FEBRUARY 9, 2021DATE:
ORLANDO, FLORIDA
ORANGE COUNTY - PUBLIC WORKS
ROOFING REPLACEMENT PROJECT
BUILDINGS 2 AND 5
A2.13/32" = 1'-0"
BUILDING 2 -
PROPOSED ROOF PLAN
A A5.2
A A5.1
A A5.4
C A5.5
C A5.2
SLOPE
A A5.6
B A5.6
A,B A5.5
X
XX.X
STRUCTURAL
DECK
EXISTING
UNDERLAYMENT
ROOF
FLASHINGS
DRAINAGE
R O
O F
A R
E A
D E
S
IG
N A
TI
O
N
B
LD
G
E
XI
S
TI
N G
1/
2" P
O
LY
ST
YR
EN
E
IN
SU
LA
TI
O N
B O
AR
D
R
-1
E
XI
S
TI
N G
G A
. G A
LV
A
N
IZ
E D
S
TE
E L
D E
C K
O
VE
R S
TE
E
L
JO
IS
TS
EXISTING
INSULATION
EX
IS
TI
N
G B
IT
U
M
IN
O U
S U
N D
ER
LA
YM
EN
T
N
EW
6"
W
ID
E, G
AU
G
E
AZ
-5
G
AL
VA
LU
M E
ST
EE
L
PA
N
EL
P
AN
EL
S.
B A
S
IS
O F
D E
S
IG
N "D
O U
B
LE
L O
C K
ZE
E
-L O
C K
C U
R
VE
D " M
AN
U
FA
C
TU
RE
D B
Y
BE
RR
ID
G E
M
AN
U
FA
C
TU
RI
N
G C
O M
PA
N
Y
NE
W
G
AU
GE
P
RE
-P
AI
NT
ED
S
TE
EL
G
UT
TE
RS
A
ND
G
AU
GE
P
RE
PA
IN
TE
D
ST
EE
L D
OW
NS
PO
UT
S
NEW METAL
PANELS
D A5.5
E
XI
S
TI
N G
/2
" C O
VE
R
B O
A R
D
EXISTING
COVERBOARD
N E
W M
IN
. R
-1
PO
LY
IS
O
C
YA
N U
R
AT
E
IN
SU
LA
TI
O
N B
O
AR
D
IN
S
TA
LL
E
D
IN
M U
LT
IP
LE
L
A
YE
R S
NEW
INSULATION
N E
W
/2 " C
O
VE
R B
O A
R D
NEW
COVERBOARD
NEW
UNDERLAYMENT
N E
W H
IG
H
-T E
M P
E R
A
TU
R E
S E
LF
-A
D H
E R
E D
U N
D E
R
LA
YM
E
N T
N E
W P
R E
-P A
IN
TE
D G
A
LV
A
LU
M E
S
TE
E L
FL
A
S H
IN
G
S
PROPOSED ROOFING ASSEMBLY -
STANDING SEAM METAL ROOFING - BUILDING 2
DS#
LEGEND
SYMBOL DESCRIPTION DETAIL
SCOPE OF
WORK ITEM
ROOF EDGE WITH GUTTER &
DOWNSPOUTS
2.7
PLUMBING VENT 2.8
BUILDING LINE BELOW
ADDITIONAL SELF ADHERED
UNDERLAYMENT AT RIDGE TOP
2.4
ROOFING ASSEMBLY - TYPE 1
STANDING SEAM METAL ROOF
PANELS
1.O & 2.0
LIGHTNING PROTECTION AIR
TERMINALS
3.0
FLUE VENT 2.8
METAL ROOF PANEL SLOPE
DOWNSPOUT DESIGNATION
DETAIL/WALL SECTION
DESIGNATION
ELEVATION DESIGNATION
NEW CONSTRUCTION NOTES
1. GUTTERS AND DOWNSPOUTS: INSTALL NEW GUTTERS AND NEW DOWNSPOUTS IN
SAME LOCATIONS AS WHERE THEY WERE REMOVED. INSTALL GUTTER EXPANSION JOINTS
CENTERED IN BETWEEN DOWNSPOUT LOCATIONS, NO MORE THAN 50 FEET APART IN
LONG, STRAIGHT RUNS AND NO MORE THAN 25 FEET FROM ANY FIXED CORNER. SEE
DETAILS ON SHEET A5.7.
2. ONE-PIECE TRANSITION FLASHINGS: INSTALL NEW ONE-PIECE TRANSITION
FLASHINGS WITH ALL ADHERED NON-MOVING JOINTS. PREPARE IN-PLACE MOCKUP FOR
OWNER AND A/E APPROVAL.
NN
TRUE / PLAN
NORTH
SCALE: 3/32" = 1'-0"A2.1
1 PROPOSED ROOF PLAN
BUILDING 2 -
KEY PLAN
N
BUILDING 2
SCOPE OF WORK
THE SCOPE OF WORK INCLUDES, BUT IS NOT LIMITED TO THE
FOLLOWING:
1.0 GENERAL:
1.1 ENGINEERING: CONDUCT PULL TESTS OF THE EXISTING ROOF DECK.
PROVIDE ENGINEERING CALCULATIONS PREPARED BY A FLORIDA LICENSED
STRUCTURAL ENGINEER INCLUDING THE CLIP AND FASTENER SPACING FOR
EACH ROOF WIND ZONE. SUBMIT PULL TEST RESULTS AND THE ENGINEERING
CALCULATIONS TO THE ARCHITECT FOR REVIEW PRIOR TO COMMENCEMENT OF
THE ROOFING INSTALLATION. SEE DRAWINGS FOR WIND PRESSURES.
1.2 SUBSTRATE PREPARATION: PREPARE, REPAIR, OR REPLACE ALL
SURFACES AS NECESSARY TO COMPLY WITH REQUIREMENTS INCLUDING BUT
NOT LIMITED TO: WIND UPLIFT REQUIREMENTS, MANUFACTURER'S
RECOMMENDATIONS, BUILDING CODE REQUIREMENTS, AND RELEVANT
INDUSTRY STANDARDS. PRIOR TO INSTALLATION OF THE ROOFING ASSEMBLY
SUBMIT A WRITTEN APPROVAL TO THE ARCHITECT, FROM THE MANUFACTURER
OF THE ROOFING ASSEMBLY THAT ALL SUBSTRATES ARE PROPERLY PREPARED
FOR THE INSTALLATION OF THE ASSEMBLY.
1.3 WARRANTY: THE NEW ROOFING ASSEMBLY IS TO BE EXAMINED AND
APPROVED BY THE MANUFACTURER'S OF THE ROOFING ASSEMBLY AND SHALL
RECEIVE A 20 YEAR NDL LABOR AND MATERIAL WARRANTY AGAINST DEFECTS
AND LEAKS. THE CONTRACTOR SHALL SUBMIT A 5 YEAR NDL WARRANTY FOR
ALL WORK AGAINST DEFECTS AND LEAKS UPON COMPLETION OF THE WORK.
ADJUST THE SCOPE OF WORK AS REQUIRED TO OBTAIN THIS WARRANTY. SEE
SPEC. SECTION 07 41 10.
2.0 STANDING SEAM METAL ROOF PANEL ASSEMBLY:
2.1 DEMOLITION: REMOVE ALL EXISTING ROOFING COMPONENTS INCLUDING
BUT NOT LIMITED TO; EXISTING STANDING SEAM METAL ROOF PANELS,
UNDERLAYMENT, METAL FLASHINGS INCLUDING DRIP EDGES, RAKE FLASHINGS
AND ALL RELATED FASTENERS FROM TOP SURFACE OF THE EXISTING COVER
BOARD. REMOVE EXISTING GUTTERS, AND METAL DOWNSPOUTS.
2.2 ROOF DECK PREPARATION: REPLACE ALL EXISTING DETERIORATED ROOF
DECK COMPONENTS AND BASE THE COST OF THE EXISTING COMPONENT
REPLACEMENT ON THE BASE BID QUANTITY INCLUDED IN THE BID FORM UNDER
THE SECTION ENTITLED “UNIT COSTS”. REPLACE THE MATERIALS WITH
MATERIALS MATCHING ALL CHARACTERISTICS INCLUDING MATERIAL AND SIZE
OF THE EXISTING COMPONENTS. INSTALL ONE LAYER OF SELF-ADHERED
UNDERLAYMENT OVER REPLACED MATERIALS.
2.3 COVER BOARD AND INSULATION: INSTALL ONE LAYER OF THE
DESIGNATED THICKNESS OF INSULATION OVER THE EXISTING OR NEW
UNDERLAYMENT. INSTALL ONE LAYER OF COVER BOARD OVER THE
POLYISOCYANURATE INSULATION.
2.4 UNDERLAYMENT: PREPARE ALL ROOF SURFACES TO RECEIVE THE NEW
UNDERLAYMENT AS REQUIRED BY THE UNDERLAYMENT MANUFACTURER.
APPLY PRIMER OVER ALL COVER BOARD SURFACES. APPLY ONE PLY OF HIGH
TEMPERATURE SELF-ADHERED UNDERLAYMENT OVER ALL COVER BOARD
SURFACES AND OVER DESIGNATED ADJACENT SURFACES. APPLY AN
ADDITIONAL UNDERLAYMENT PLY OVER ALL VALLEYS AND OVER ALL PRIMED
METAL FLASHING FLANGES. INSTALL ADDITIONAL PLIES OF SELF-ADHERED
UNDERLAYMENT TO FORM A 10'-0" WIDE STRIP OF DOUBLE LAYER OF
SELF-ADHERED UNDERLAYMENT AT THE PEAK OF THE ARCHED ROOFS.
2.5 METAL ROOF PANELS: INSTALL A 24 GAUGE AZ-50 GALVALUME STEEL
STANDING SEAM ROOF PANELS WITH STIFFENING RIBS USING STAINLESS STEEL
CONCEALED CLIPS FABRICATED WITH THERMALLY MOVABLE COMPONENTS.
SECURE CLIPS THROUGH THE ROOFING ASSEMBLY AND INTO THE EXISTING
STEEL DECK. (SEE SPECIFICATION SECTION 07 41 10).
2.6 METAL FLASHINGS: INSTALL METAL FLASHINGS WITH FULLY WELDED
NON-MOVING SEAMS AND SECURE WITH STAINLESS STEEL FASTENERS AS
REQUIRED TO COMPLY WITH THE DESIGNATED WIND PRESSURES.
2.7 GUTTERS AND DOWNSPOUTS: FABRICATE AND INSTALL SLOPED GUTTERS
AND DOWNSPOUTS. GUTTERS AND DOWNSPOUTS WILL BE PRE-PAINTED WITH
SAFETY PAINT AND PER OWNER'S DIRECTION. INSERT THE DOWNSPOUTS INTO
THE EXISTING STORM LINES AT GRADE WITH NEW SHEET METAL TRANSITIONS.
PROVIDE SQUARE TO ROUND TRANSITIONS TO STORM DRAINS. MATCH THE
EXISTING DOWNSPOUT LOCATIONS.
2.8 PLUMBING VENT FLASHINGS: REMOVE ALL EXISTING PLUMBING AND FLUE
VENT FLASHINGS. EXTEND EXISTING PIPES WHERE REQUIRED TO MAINTAIN AN
8 INCH MINIMUM HEIGHT ABOVE THE NEW FINISHED ROOF SURFACE. INSTALL
PLUMBING VENT METAL FLASHINGS AND STAINLESS STEEL VANDAL-RESISTANT
CAPS.
2.9 VALLEY FLASHING: AT VALLEY FLASHING INSTALL TWO LAYERS OF
SELF-ADHERED UNDERLAYMENT WITH TOP LAYER EXTENDING 12" BEYOND BASE
LAYER ON EACH SIDE, INSTALLED SHINGLE-STYLE. INSTALL 24 GAUGE AZ-50
GALVALUME STEEL VALLEY FLASHING WITH 3" TALL DIVERTER. VALLEY FLASHING
TRANSITIONS TO BE MINIMUM 8" OVERLAP. VALLEY FLASHING TO BE MAXIMUM 4'
IN LENGTH. FULLY SOLDER CAP AT ROOF EDGE. SEE SPECIFICATION SECTION
07 62 00.
2.9A ALTERNATE: INSTALLATION OF A VALLEY DIVERTER: PROVIDE OWNER
WITH AN ALTERNATE PRICE FOR THE INSTALLATION OF AN ELEVATED VALLEY
DIVERTER PER DETAIL B/A5.4.
3.0 LIGHTNING PROTECTION:
3.1 LIGHTNING PROTECTION: REMOVE ALL LIGHTNING PROTECTION
ASSEMBLY COMPONENTS ATTACHED TO THE ROOFING ASSEMBLY, INCLUDING
BUT NOT LIMITED TO, AIR TERMINALS, CONDUCTOR CABLES, ATTACHMENT
COMPONENTS, AND RELATED FASTENERS. REPLACE ALL EXISTING LIGHTNING
PROTECTION WITH NEW COMPONENTS THAT WILL BE COMPATIBLE WITH THE
NEW ROOFING ASSEMBLY. WHERE EXISTING LIGHTNING PROTECTION DOES
NOT EXIST, INSTALL A NEW LIGHTNING PROTECTION ASSEMBLY. TIE-IN THE NEW
LIGHTNING PROTECTION ASSEMBLY COMPONENTS WITH THE EXISTING
LIGHTNING PROTECTION GROUNDING COMPONENTS USING BI-METAL
CONNECTORS WHERE MATERIAL COMPATIBILITY WILL NOT AFFECT THE NEW
ROOFING ASSEMBLY. INSTALL ALL LIGHTNING PROTECTION ASSEMBLIES AND
COMPONENTS BY A QUALIFIED, LICENSED LIGHTNING PROTECTION INSTALLER
WITH A MINIMUM OF 5 YEARS EXPERIENCE IN THE INSTALLATION OF LIGHTNING
PROTECTION SYSTEMS IN ACCORDANCE WITH NFPA-780 AND ALL APPLICABLE
BUILDING CODES. UL MASTER LABEL REQUIRED UPON COMPLETION.
AutoCAD SHX Text
XX.X
X
10'
10'
10'
10'
2'
2'2'
2 33
3 3
2 2
2'2'
10'
10'
20'-3"
40'-6"
20'-3"
7'-9" 15'-6" 7'-9"
T/METAL EDGE
13'-10" AFF
T/CURVED RIDGE
23'-10" AFF
T/CURVED RIDGE
20'-2" AFF
T/CURVED RIDGE
23'-10" AFF
T/METAL EDGE
13'-10" AFF
T/METAL EDGE
13'-10" AFF
T/METAL EDGE
13'-10" AFF
SHEET
REVISIONS
NUMBER TYPE DATE:
CONSTRUCTION DOCUMENTS
PLOT:
FAX: (407) 333-4686
3246 LAKEVIEW OAKS DRIVE LONGWOOD, FLORIDA 32779
JAY AMMON ARCHITECT, INC.
(407) 333-1977 E MAIL: JAY@JAYAMMON.COM
CAS / NHR
APPROVED BY:
DRAWN BY:
JPA CONSTRUCTION DOCS
PROJECT NUMBER:
PHASE:
19-066
ENGINEER: FEBRUARY 9, 2021DATE:
ORLANDO, FLORIDA
ORANGE COUNTY - PUBLIC WORKS
ROOFING REPLACEMENT PROJECT
BUILDINGS 2 AND 5
A2.1.13/32" = 1'-0"
BUILDING 2 -
WIND UPLIFT PRESSURE ROOF PLANKEY PLAN
N
BUILDING 2
NN
TRUE / PLAN
NORTH
SCALE: 3/32" = 1'-0"A2.1.1
1 WIND UPLIFT PRESSURE ROOF PLAN
BUILDING 2 -
AutoCAD SHX Text ASCE 7-16, Vult=150 mph, Vasd= 116 mph wind, category III
AutoCAD SHX Text Exposure "C", Kd = 0.85, h = 25 ft., ENCLOSED BUILDING: GCpi = %%P 0.18.
AutoCAD SHX Text
%%UWIND DESIGN FOR ROOFING COMPONENTS AND CLADDING:
AutoCAD SHX Text
WIND UPLIFT PRESSURES SHOWN ARE GROSS PRESSURES FOR
AutoCAD SHX Text
CORNER ZONE, EDGE ZONE, AND FIELD ZONE FOR
AutoCAD SHX Text
ROOF COMPONENTS AND CLADDING (C & C).
AutoCAD SHX Text
%%UWIND UPLIFT PRESSURE LEGEND:
AutoCAD SHX Text
ZONE 2' - ARCH ZONE
AutoCAD SHX Text
ZONE 2 - EDGE ZONE
AutoCAD SHX Text
ZONE 1 - FIELD ZONE
AutoCAD SHX Text
-71.00 PSF
AutoCAD SHX Text
-33.38 PSF
AutoCAD SHX Text
-30.20 PSF
AutoCAD SHX Text
ASCE 7-16
AutoCAD SHX Text
AREA %%U<%%U 10 SF.
AutoCAD SHX Text
WIND HAS BEEN CHECKED FOR AN ENCLOSED STRUCTURE AT EACH
AutoCAD SHX Text
ROOF SLOPE AND HIGHEST WIND PRESSURES ARE SHOWN FOR EACH AREA.
AutoCAD SHX Text
ROOF C & C
AutoCAD SHX Text
DESIGN PRESSURES
AutoCAD SHX Text
ZONE 3 - CORNER ZONE
AutoCAD SHX Text CODES: FLORIDA BUILDING CODE 2020 (7TH ED) AND ASCE 7-16 FLORIDA BUILDING CODE 2020 (7TH ED) AND ASCE 7-16 'A' DIMENSION = 10'
AutoCAD SHX Text
-71.00 PSF
ALL PRESSURES ARE ALLOWABLE STRESS DESIGN (ASD). DEPTH OF PERIMETER AND CORNER ZONES FROM ROOF EDGE - 'a' DIMENSION IS 10 FEET
VALLEY
SLOPE SLOPE
S
LO
P E
DS# 1 DS# 2 DS# 3 DS# 4 DS# 6 DS# 7 DS# 8
DS# 16 DS# 15 DS# 14 DS# 12 DS# 11 DS# 10 DS# 9DS# 13
S
LO
P E
S
LO
P E
S
LO
P E
S
LO
P E
S
LO
P E
S
LO
P E
S
LO
P E
GEJ GEJ GEJ GEJGEJGEJ
GEJ GEJ GEJGEJGEJGEJ GEJ
DS# 5
NN
TRUE / PLAN
NORTH
A
ROOF DRAINAGE CALCULATION
SHEET
REVISIONS
NUMBER TYPE DATE:
CONSTRUCTION DOCUMENTS
PLOT:
FAX: (407) 333-4686
3246 LAKEVIEW OAKS DRIVE LONGWOOD, FLORIDA 32779
JAY AMMON ARCHITECT, INC.
(407) 333-1977 E MAIL: JAY@JAYAMMON.COM
CAS / NHR
APPROVED BY:
DRAWN BY:
JPA CONSTRUCTION DOCS
PROJECT NUMBER:
PHASE:
19-066
ENGINEER: FEBRUARY 9, 2021DATE:
ORLANDO, FLORIDA
ORANGE COUNTY - PUBLIC WORKS
ROOFING REPLACEMENT PROJECT
BUILDINGS 2 AND 5
A2.1.23/32" = 1'-0"
BUILDING 2 -
PROPOSED ROOF DRAINAGE PLAN
SCALE: 3/32" = 1'-0"A2.1.2
1 PROPOSED ROOF DRAINAGE PLAN
BUILDING 2 -
KEY PLAN
N
BUILDING 2
SLOPE
DS#
LEGEND
SYMBOL DESCRIPTION
NEW ROOF EDGE PERIMETER.
(SEE SCOPE OF WORK ITEM 2.6)
NEW GUTTER WITH
DOWNSPOUTS.
(SEE SCOPE OF WORK ITEM 2.7)
EXISTING BUILDING LINE BELOW
NEW VALLEY
DOWNSPOUT DESIGNATION
METAL ROOF PANEL SLOPE
GUTTER SLOPE
GUTTER EXPANSION JOINT
(SEE DETAIL B/A5.7)
SPECIFIC NOTE LOCATION
NEW CONSTRUCTION NOTES
1. GUTTERS AND DOWNSPOUTS: INSTALL NEW GUTTERS AND NEW DOWNSPOUTS IN
SAME LOCATIONS AS WHERE THEY WERE REMOVED. INSTALL GUTTER EXPANSION JOINTS
CENTERED IN BETWEEN DOWNSPOUT LOCATIONS, NO MORE THAN 50 FEET APART IN
LONG, STRAIGHT RUNS AND NO MORE THAN 25 FEET FROM ANY FIXED CORNER. SEE
DETAILS ON SHEET A5.7.
2. ONE-PIECE TRANSITION FLASHING: INSTALL NEW ONE-PIECE TRANSITION FLASHING
WITH ALL ADHERED NON-MOVING JOINTS. PREPARE IN-PLACE MOCKUP FOR OWNER AND
A/E APPROVAL.
GEJ
EXISTING WALL BELOW
NEW GUTTER ASSEMBLY
NEW GUTTER
ASSEMBLY
A3.2
A3.2
A3.2
A3.2
VALLEY
VALL
EY
EXISTING WALL BELOW
EXISTING BOLLARD
BELOW
10'
10'
10'
NEW GUTTER ASSEMBLY
EXISTING BOLLARD
BELOW
A4.1
B A5.1
A4.1
A A5.4
A4.1
A A5.2
B A5.1
A4.1
A4.1
B A5.1
A A5.2
A A5.2
A4.1
A A5.2
A A5.4
A4.1
A A5.2
B A5.1
A4.1
A4.1
B A5.1
A A5.1
A A5.1
C A5.2
C A5.2
C A5.2
DS# 8
DS# 1 DS# 2
DS# 3
DS# 4
DS# 5
DS# 7
DS# 6
EXISTING
WALL BELOW
A2.23/32" = 1'-0"
BUILDING 5 -
PROPOSED ROOF PLAN
SHEET
REVISIONS
NUMBER TYPE DATE:
CONSTRUCTION DOCUMENTS
PLOT:
FAX: (407) 333-4686
3246 LAKEVIEW OAKS DRIVE LONGWOOD, FLORIDA 32779
JAY AMMON ARCHITECT, INC.
(407) 333-1977 E MAIL: JAY@JAYAMMON.COM
CAS / NHR
APPROVED BY:
DRAWN BY:
JPA CONSTRUCTION DOCS
PROJECT NUMBER:
PHASE:
19-066
ENGINEER: FEBRUARY 9, 2021DATE:
ORLANDO, FLORIDA
ORANGE COUNTY - PUBLIC WORKS
ROOFING REPLACEMENT PROJECT
BUILDINGS 2 AND 5
PROPOSED ROOFING ASSEMBLY -
STANDING SEAM METAL ROOFING - BUILDING 5
SCALE: 3/32" = 1'-0"A2.2
1 PROPOSED ROOF PLAN
BUILDING 5 -
KEY PLAN
N
BUILDING 5
NN
TRUE / PLAN
NORTH
STRUCTURAL
DECK
EXISTING
UNDERLAYMENT
ROOF
FLASHINGS
DRAINAGE
R O
O F
A R
E A
D E
S
IG
N A
TI
O
N
B
LD
G
E
XI
S
TI
N G
1/
2" P
O
LY
ST
YR
EN
E
IN
SU
LA
TI
O N
B O
AR
D
R
-1
E
XI
S
TI
N G
G A
. G A
LV
A
N
IZ
E D
S
TE
E L
D E
C K
O
VE
R S
TE
E
L
JO
IS
TS
EXISTING
INSULATION
EX
IS
TI
N
G B
IT
U
M
IN
O U
S U
N D
ER
LA
YM
EN
T
NEW METAL
PANELS
E
XI
S
TI
N G
/2
" C O
VE
R
B O
A R
D
EXISTING
COVERBOARD
N E
W M
IN
. R
-1
PO
LY
IS
O
C
YA
N U
R
AT
E
IN
SU
LA
TI
O
N B
O
AR
D
IN
S
TA
LL
E
D
IN
M U
LT
IP
LE
L
A
YE
R S
NEW
INSULATION
N E
W
/2 " C
O
VE
R B
O A
R D
NEW
COVERBOARD
NEW
UNDERLAYMENT
N E
W H
IG
H
-T E
M P
E R
A
TU
R E
S E
LF
-A
D H
E R
E D
U N
D E
R
LA
YM
E
N T
A A5.2
A A5.1
A A5.4
C A5.5
C A5.2
SLOPE
A A5.6
B A5.6
A,B A5.5
X
XX.X
D A5.5
DS#
LEGEND
SYMBOL DESCRIPTION DETAIL
SCOPE OF
WORK ITEM
ROOF EDGE WITH GUTTER &
DOWNSPOUTS
2.7
PLUMBING VENT 2.8
BUILDING LINE BELOW
ADDITIONAL SELF ADHERED
UNDERLAYMENT AT RIDGE TOP
2.4
ROOFING ASSEMBLY - TYPE 1
STANDING SEAM METAL ROOF
PANELS
1.O & 2.0
LIGHTNING PROTECTION AIR
TERMINALS
3.0
FLUE VENT 2.8
METAL ROOF PANEL SLOPE
DOWNSPOUT DESIGNATION
DETAIL/WALL SECTION
DESIGNATION
ELEVATION DESIGNATION
NEW CONSTRUCTION NOTES
1. GUTTERS AND DOWNSPOUTS: INSTALL NEW GUTTERS AND NEW DOWNSPOUTS IN
SAME LOCATIONS AS WHERE THEY WERE REMOVED. INSTALL GUTTER EXPANSION JOINTS
CENTERED IN BETWEEN DOWNSPOUT LOCATIONS, NO MORE THAN 50 FEET APART IN
LONG, STRAIGHT RUNS AND NO MORE THAN 25 FEET FROM ANY FIXED CORNER. SEE
DETAILS ON SHEET A5.7.
2. ONE-PIECE TRANSITION FLASHINGS: INSTALL NEW ONE-PIECE TRANSITION
FLASHINGS WITH ALL ADHERED NON-MOVING JOINTS. PREPARE IN-PLACE MOCKUP FOR
OWNER AND A/E APPROVAL.
SCOPE OF WORK
THE SCOPE OF WORK INCLUDES, BUT IS NOT LIMITED TO THE
FOLLOWING:
1.0 GENERAL:
1.1 ENGINEERING: CONDUCT PULL TESTS OF THE EXISTING ROOF DECK.
PROVIDE ENGINEERING CALCULATIONS PREPARED BY A FLORIDA LICENSED
STRUCTURAL ENGINEER INCLUDING THE CLIP AND FASTENER SPACING FOR
EACH ROOF WIND ZONE. SUBMIT PULL TEST RESULTS AND THE ENGINEERING
CALCULATIONS TO THE ARCHITECT FOR REVIEW PRIOR TO COMMENCEMENT OF
THE ROOFING INSTALLATION. SEE DRAWINGS FOR WIND PRESSURES.
1.2 SUBSTRATE PREPARATION: PREPARE, REPAIR, OR REPLACE ALL
SURFACES AS NECESSARY TO COMPLY WITH REQUIREMENTS INCLUDING BUT
N…