This document is a comprehensive bid package for the City of South Lyon, Michigan Wastewater Utility Department's New Generator Installation Project. The project involves installing a new generator at the Wastewater Treatment Plant, with bid documents issued on July 12, 2024, and prepared by HRC Engineers. The scope includes a new 750 kVA generator installation while maintaining the existing 550 kVA diesel generator as an emergency backup system. The project will integrate with the existing control panel and manual transfer switch, with detailed electrical and site plans provided across multiple engineering drawings.
The bid package includes extensive technical specifications, electrical diagrams, site plans, and installation details. The project requires precise electrical and structural work, including generator foundation construction, electrical system modifications, and utility connections. The drawings indicate careful consideration of existing site conditions, underground utilities, and integration with the current wastewater treatment plant infrastructure. The project appears to be funded through municipal infrastructure resources, with detailed specifications for electrical systems, grounding, conduit routing, and equipment mounting. The bid documents provide comprehensive guidance for potential contractors, including specific technical requirements, installation notes, and site-specific considerations for the generator replacement and integration.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Generator addendum No.1.pdf | ||
| specs for new generator project.pdf | ||
| Generator addendum No.1 attachment.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WASTEWATER UTILITY DEPARTMENT
PREPARED UNDER THE SUPERVISION OF:
REGISTERED PROFESSIONAL ENGINEER
HUBBELL, ROTH & CLARK, INC.
SEAL
CITY OF SOUTH LYON, MICHIGAN
MICHAEL J. ROSKELLEY
JOB NO. 20230229
LOCATION MAP
NO SCALE
WASTE WATER TREATMENT PLANT
NEW GENERATOR PROJECT
ISSUED FOR BIDS
JULY 12, 2024
SOUTH LYON CITY COUNCIL CITY ADMINISTRATION
LISA DILG - MAYOR PRO-TEM
JUDY PIEPER - DEPUTY CLERK/TREASURER
RON BEASON - SUPERINTENDENT WATER/WASTEWATER
LISA DEATON - CITY CLERK/TREASURERALEX HANSEN
MARGARET KURTZWEIL
THAD BOGERT
GLENN KIVELL LORI MOSIER
PAUL C. ZELENAK - CITY MANAGER
JOB NO. 20230229
PREPARED BY:
555 HULET DRIVE
BLOOMFIELD HILLS, MI.
P.O. BOX 824
48303 - 0824
PHONE: (248) 454-6300
WEB SITE: www.hrcengr.com
FAX (1st. Floor): (248) 454-6312 FAX (2nd. Floor): (248) 454-6359
N
AutoCAD SHX Text %%uLIST OF DRAWINGS%%u
AutoCAD SHX Text
SHEET NO.
AutoCAD SHX Text %%uSHEET TITLE%%u
AutoCAD SHX Text %%uCIVIL%%u
AutoCAD SHX Text %%uSTRUCTURAL%%u
AutoCAD SHX Text E-1 ELECTRICAL ONE-LINE DIAGRAM ELECTRICAL ONE-LINE DIAGRAM E-2 NOTES, LEGEND, SCHEDULE, AND LOAD CALCULATIONS NOTES, LEGEND, SCHEDULE, AND LOAD CALCULATIONS E-3 ELECTRICAL REMOVAL PLAN SHEET ELECTRICAL REMOVAL PLAN SHEET E-4 ENLARGED GENERATOR ELECTRICAL PLAN SHEET ENLARGED GENERATOR ELECTRICAL PLAN SHEET E-5 ELECTRICAL PROJECT DETAILSELECTRICAL PROJECT DETAILS
AutoCAD SHX Text %%uELECTRICAL%%u
AutoCAD SHX Text V:\202302\20230229\CoverSheet.dwg
AutoCAD SHX Text Uhlianuk, Adam
AutoCAD SHX Text HRC_OLW.ctb
AutoCAD SHX Text
7/12/2024 1:43 PM
AutoCAD SHX Text 2023 Hubbell, Roth & Clark, Inc. All Rights Reserved
AutoCAD SHX Text C
AutoCAD SHX Text
ORIGINAL PLOT SIZE: ANSI FULL BLEED D (22.00 X 34.00 INCHES)
AutoCAD SHX Text
%%UGENERAL
AutoCAD SHX Text
NICHWAGH LAKE
AutoCAD SHX Text
9 MILE RD.
AutoCAD SHX Text
9 MILE RD.
AutoCAD SHX Text
10 MILE RD.
AutoCAD SHX Text
10 MILE RD.
AutoCAD SHX Text
PONTIAC TRAIL
AutoCAD SHX Text
DIXBORO RD
AutoCAD SHX Text
REYNOLD SWEET PKWY
AutoCAD SHX Text SOUTH LYON WASTE WATER TREATMENT PLANT 23500 DIXBORO RD SOUTH LYON, MICHIGAN 48178
AutoCAD SHX Text C-1 EXISTING SITE CONDITIONS EXISTING SITE CONDITIONS C-2 SITE PLAN REMOVAL SHEET SITE PLAN REMOVAL SHEET C-3 CONSTRUCTION SITE PLAN SHEETCONSTRUCTION SITE PLAN SHEET
AutoCAD SHX Text S-1 GENERATOR FOUNDATION PLANS, SECTION, DETAILS AND NOTESGENERATOR FOUNDATION PLANS, SECTION, DETAILS AND NOTES
AutoCAD SHX Text COVER COVER SHEET AND LOCATION MAP COVER SHEET AND LOCATION MAP G-1 GENERAL NOTES, ABBREVIATIONS, AND LEGENDGENERAL NOTES, ABBREVIATIONS, AND LEGEND
APPROVED
CHECKED
DRAWN
DESIGNED
DATE
HRC JOB NO.
DATE
SCALE
ADDITIONS AND/OR REVISIONS
SHEET
NO.
OF
WEB SITE: www.hrcengr.com
CITY OF SOUTH LYON
WASTE WATER
TREATMENT PLANT
NEW GENERATOR
INSTALLATION
PROJECT
48843HOWELL, MI
105 W. GRAND RIVER AVE.
PHONE: (517) 552-9199
GUY
G-V
ET
AutoCAD SHX Text 2023 Hubbell, Roth & Clark, Inc. All Rights Reserved
AutoCAD SHX Text C
AutoCAD SHX Text V:\202302\20230229\E\Sheet\nt02.dwg
AutoCAD SHX Text Uhlianuk, Adam
AutoCAD SHX Text
AutoCAD SHX Text
7/10/2024 3:54 PM
AutoCAD SHX Text 20230229
AutoCAD SHX Text May 2024
AutoCAD SHX Text
ORIGINAL PLOT SIZE: ANSI FULL BLEED D (34.00 X 22.00 INCHES)
AutoCAD SHX Text L.C.
AutoCAD SHX Text D
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text L
AutoCAD SHX Text
CH. BRG.
AutoCAD SHX Text P.C.
AutoCAD SHX Text P.C.C.
AutoCAD SHX Text P.I.
AutoCAD SHX Text P.T.
AutoCAD SHX Text P.O.C.
AutoCAD SHX Text P.R.C.
AutoCAD SHX Text P.V.C.
AutoCAD SHX Text P.V.I.
AutoCAD SHX Text P.V.T.
AutoCAD SHX Text P.O.R.
AutoCAD SHX Text P.O.E.
AutoCAD SHX Text H.C.P.
AutoCAD SHX Text
MSE
AutoCAD SHX Text
ST.
AutoCAD SHX Text
SAN.
AutoCAD SHX Text W.M.
AutoCAD SHX Text R.O.W.
AutoCAD SHX Text T.C.
AutoCAD SHX Text T/C
AutoCAD SHX Text F.J.
AutoCAD SHX Text S.S.L.
AutoCAD SHX Text B.M.
AutoCAD SHX Text P.O.B.
AutoCAD SHX Text C.I.P.
AutoCAD SHX Text C.S.B.
AutoCAD SHX Text
POINT ON CURVE
AutoCAD SHX Text
DEGREE OF CURVATURE
AutoCAD SHX Text
RADIUS
AutoCAD SHX Text
CENTRAL ANGLE
AutoCAD SHX Text
TANGENT
AutoCAD SHX Text
ARC LENGTH
AutoCAD SHX Text
CHORD LENGTH
AutoCAD SHX Text
POINT OF CURVATURE
AutoCAD SHX Text
POINT OF COMPOUND CURVATURE
AutoCAD SHX Text
POINT OF INTERSECTION
AutoCAD SHX Text
POINT OF TANGENCY
AutoCAD SHX Text
POINT OF REVERSE CURVATURE
AutoCAD SHX Text
POINT OF VERTICAL CURVE
AutoCAD SHX Text
POINT OF VERTICAL INTERSECTION
AutoCAD SHX Text
POINT OF VERTICAL TANGENCY
AutoCAD SHX Text
POINT OF ROTATION
AutoCAD SHX Text
POINT OF ENDING
AutoCAD SHX Text
HORIZONTAL CONTROL POINT
AutoCAD SHX Text
BENCH MARK
AutoCAD SHX Text
MECHANICALLY STABILIZED EMBANKMENT
AutoCAD SHX Text
STORM SEWER
AutoCAD SHX Text
SANITARY SEWER
AutoCAD SHX Text
WATERMAIN
AutoCAD SHX Text
RIGHT-OF-WAY
AutoCAD SHX Text
TOP OF CURB
AutoCAD SHX Text
TOP OF DRAINAGE STRUCTURE COVER
AutoCAD SHX Text
HYDRANT FROST JACKET ELEVATION
AutoCAD SHX Text
SLOPE STAKE LINE
AutoCAD SHX Text
CHORD BEARING (LONG CHORD)
AutoCAD SHX Text
POINT OF BEGINNING
AutoCAD SHX Text
COMPACTED IN PLACE
AutoCAD SHX Text
COMPLETE SAND BACKFILL
AutoCAD SHX Text %%uHORIZONTAL CURVES%%U
AutoCAD SHX Text %%uVERTICAL CURVES%%U
AutoCAD SHX Text %%uGENERAL%%U
AutoCAD SHX Text %%uABBREVIATIONS%%U
AutoCAD SHX Text S.H.A.
AutoCAD SHX Text
SCHLEEDE-HAMPTON ASSOCIATES (ROAD & SOIL BORINGS)
AutoCAD SHX Text
WATER MAIN
AutoCAD SHX Text
DECIDUOUS TREE
AutoCAD SHX Text
DECIDUOUS SHRUB
AutoCAD SHX Text
CONIFEROUS TREE
AutoCAD SHX Text
STUMP
AutoCAD SHX Text
STORM MANHOLE & PIPE END
AutoCAD SHX Text
RISER & DOWN SPOUT
AutoCAD SHX Text
PUMP STATION
AutoCAD SHX Text
FIRE HYDRANT
AutoCAD SHX Text
UTILITY POLE
AutoCAD SHX Text
LIGHT POLE
AutoCAD SHX Text
GUY WIRE ANCHOR
AutoCAD SHX Text
UNDERGROUND MARKER
AutoCAD SHX Text
GAS BOX & BLOW OFF
AutoCAD SHX Text
BENCH MARK SYMBOL
AutoCAD SHX Text
GAS VALVE / PIPE END
AutoCAD SHX Text
U.G. CABLE TV
AutoCAD SHX Text
RIGHT-OF-WAY
AutoCAD SHX Text
PROPERTY LINE
AutoCAD SHX Text
ABANDON & REMOVAL SYMBOLS
AutoCAD SHX Text
MH
AutoCAD SHX Text
CB
AutoCAD SHX Text
INL
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ST
AutoCAD SHX Text
SA
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text
ES
AutoCAD SHX Text
%%UITEM
AutoCAD SHX Text
%%UEXISTING
AutoCAD SHX Text
%%USYMBOL
AutoCAD SHX Text
REMOVE CURB & GUTTER
AutoCAD SHX Text
SOIL BORING/PAVEMENT CORE
AutoCAD SHX Text
BUILDING
AutoCAD SHX Text
TRAVERSE LINE & TRAVERSE POINT
AutoCAD SHX Text
WATER STOP BOX & SPRINKLER HEAD
AutoCAD SHX Text
METER PIT
AutoCAD SHX Text
U.G. TELEPHONE
AutoCAD SHX Text
GAS MAIN
AutoCAD SHX Text
STORM SEWER
AutoCAD SHX Text
SANITARY SEWER
AutoCAD SHX Text
STORM UNDERDRAIN
AutoCAD SHX Text
UNSPECIFIED MANHOLE
AutoCAD SHX Text
GATE VALVE, GATE WELL & WELL
AutoCAD SHX Text
MANHOLE, CATCH BASIN, INLET, & END SECTION SYMBOLS
AutoCAD SHX Text
U.G. ELECTRIC
AutoCAD SHX Text
CONIFEROUS SHRUB
AutoCAD SHX Text
DRAINAGE FLOW
AutoCAD SHX Text
U.G. ELEC. & TELE.
AutoCAD SHX Text
%%UPROPOSED
AutoCAD SHX Text %%uLEGEND%%u
AutoCAD SHX Text
FENCE
AutoCAD SHX Text
SLOPE STAKE LINE
AutoCAD SHX Text
DRAINAGE EASEMENT
AutoCAD SHX Text
TEMPORARY GRADING PERMIT
AutoCAD SHX Text
SQUARE/ROUND CATCHBASINS & INLETS IN PAVEMENT
AutoCAD SHX Text
EX. 12" STM. SWR.
AutoCAD SHX Text
EX. 12" SAN. SWR.
AutoCAD SHX Text
EX. 12" D.I. W.M.
AutoCAD SHX Text
EX. 6" S-MP GAS MAIN
AutoCAD SHX Text
COMBINED PROPERTY
AutoCAD SHX Text
EX. 12" CMP
AutoCAD SHX Text
RELOCATE BY OTHERS
AutoCAD SHX Text
ADJUSTMENT
AutoCAD SHX Text
RELOCATE
AutoCAD SHX Text
ADJ
AutoCAD SHX Text
REL
AutoCAD SHX Text
REL B/O
AutoCAD SHX Text
DITCH CENTERLINE
AutoCAD SHX Text S
AutoCAD SHX Text B
AutoCAD SHX Text PRIOR TO WORK ON FACILITIES BELONGING TO OTHER AGENCIES, A MINIMUM OF 72 HOURS NOTICE MUST BE GIVEN IN ORDER TO INSURE PROPER INSPECTION BY THE RESPECTIVE AGENCIES.
AutoCAD SHX Text ALL EXPLORATORY WORK REQUIRED FOR LOCATING EXISTING UTILITIES SHALL NOT BE PAID FOR SEPARATELY.
AutoCAD SHX Text THE CONTRACTOR SHALL LOCATE ALL ACTIVE UNDERGROUND UTILITIES PRIOR TO STARTING WORK, AND SHALL CONDUCT HIS OPERATIONS IN SUCH A MANNER AS TO INSURE THAT THOSE UTILITIES NOT REQUIRING RELOCATION WILL NOT BE DISTURBED.
AutoCAD SHX Text FOR PROTECTION OF UNDERGROUND UTILITIES, THE CONTRACTOR SHALL DIAL 811 OR (800) 482-7171 A MINIMUM OF 3 FULL WORKING DAYS, EXCLUDING SATURDAY, SUNDAY AND HOLIDAYS, PRIOR TO EXCAVATING IN THE VICINITY OF UTILITY LINES. ALL "MISS-DIG" PARTICIPATING MEMBERS WILL THUS BE ROUTINELY NOTIFIED. THIS DOES NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY OF NOTIFYING UTILITY OWNERS WHO MAY NOT BE A PART OF THE "MISS-DIG" ALERT SYSTEM. COORDINATION SHALL ALSO BE CONDUCTED WITH THE CITY TO LOCATE UTILITIES NOT PART OF MISS DIG ALERT SYSTEM 3 DAYS IN ADVANCE OF ANY EXCAVATIONS.
AutoCAD SHX Text THE CONTRACTOR SHALL, BEFORE EACH DAYS WORK, OR WHEN MOVING TO A NEW AREA OF WORK, DETERMINE AND EVALUATE THE LOCATION OF ALL UNDERGROUND FACILITIES IN THE AREA. IF LOCATION STAKES HAVE BEEN MOVED OR DO NOT APPEAR CORRECT, THE CONTRACTOR SHALL NOT EXCAVATE UNTIL ALL UTILITIES HAVE HAD AN OPPORTUNITY TO CHECK OR RE STAKE THEIR LOCATIONS. ANY DELAYS INCURRED DUE TO CHECKING OR RE STAKING OF UTILITIES SHALL NOT BE A BASIS FOR ADDITIONAL COMPENSATION.
AutoCAD SHX Text THE EXISTING UTILITIES LISTED SHOWN ON THESE PLANS REPRESENT THE BEST INFORMATION AVAILABLE AS OBTAINED FROM SURVEYS AND FROM UTILITY RECORD MAPS. THIS INFORMATION DOES NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY TO NOTIFY THE PROPER UTILITIES BEFORE COMMENCING WORK. THE CONTRACTOR IS RESPONSIBLE TO VERIFY ALL EXISTING UTILITIES AND THEIR LOCATIONS AS PART OF THE CONSTRUCTION OF THIS PROJECT.
AutoCAD SHX Text ALL GAS FACILITIES SHALL BE PROTECTED AND SUPPORTED PER DISTRIBUTION STANDARDS AND CONSUMERS ENERGY SPECIFICATIONS.
AutoCAD SHX Text %%uUTILITIES%%U
AutoCAD SHX Text OWNERS OF PUBLIC UTILITIES WILL NOT BE REQUIRED TO MOVE POLES OR STRUCTURES THAT ARE NOT WITHIN GRADING OR STRUCTURE LIMITS IN ORDER TO FACILITATE THE OPERATION OF CONSTRUCTION EQUIPMENT. CONTRACTOR TO COORDINATE WITH UTILITY OWNERS FOR TEMPORARY SUPPORT OR RELOCATION (IF NEEDED) AT HIS EXPENSE. THIS WILL ALSO INCLUDE LIGHT POLES.
AutoCAD SHX Text %%uUTILITY NOTE NO. 1%%U
AutoCAD SHX Text THE UTILITY CONFLICTS INFORMATION PROVIDED HEREIN BY HUBBELL, ROTH & CLARK ("HRC") SHALL NOT BE CONSTRUED AS ANY FORM OF CERTIFICATION, WARRANTY (EXPRESS OR IMPLIED) OR GUARANTEE ON BEHALF OF HRC REGARDING THE ACTUAL LOCATION OF THE UTILITIES IN QUESTION. HRC DOES NOT HAVE ACTUAL KNOWLEDGE OF THE UTILITY LOCATIONS. INSTEAD, THE INFORMATION PROVIDED IS BASED ON INFORMATION OBTAINED FROM OTHERS AND/OR CONSTRUCTION DRAWINGS OF HRC THAT HAVE NOT BEEN VERIFIED TO BE "AS-BUILT" CONDITIONS. THE INFORMATION IS BEING PROVIDED AS A COURTESY, AND SHOULD NOT BE RELIED UPON FOR ACTUAL UTILITY LOCATIONS. PROVIDING THIS INFORMATION SHALL NOT CREATE ANY FORM OF CONTRACTUAL (OR OTHER) RELATIONSHIP BETWEEN HRC AND ANY ENTITY INVOLVED IN THE PROJECT. HRC'S CONTRACT ON THIS PROJECT IS WITH THE OWNER, CITY OF SOUTH LYON WASTE WATER TREATMENT PLANT.
AutoCAD SHX Text THE SOIL EROSION CONTROLS WILL BE MAINTAINED WEEKLY AND AFTER EVERY STORM EVENT BY THE CONTRACTOR. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO MAINTAIN A CLEAN SITE AND CORRECT ANY STORM EVENT EROSIONS AT THEIR OWN EXPENSE TO RETURN SITE BACK TO IT'S ORIGINAL CONDITION OR BETTER.
AutoCAD SHX Text 07-12-24
AutoCAD SHX Text
ISSUED FOR BIDS
AutoCAD SHX Text
GENERAL NOTES,
AutoCAD SHX Text
ABBREVIATIONS AND LEGEND
AutoCAD SHX Text
AS NOTED
AutoCAD SHX Text G-1
AutoCAD SHX Text A.R.U.
AutoCAD SHX Text A.R.U.
AutoCAD SHX Text R.H.W.
R.N.A.
DRAWN
DESIGNED
DATE
HRC JOB NO.
DATE
SCALE
ADDITIONS AND/OR REVISIONS
SHEET
NO.
OF
555 HULET DRIVE
BLOOMFIELD HILLS, MICH.
P.O. BOX 824
48303 - 0824
PHONE: (248) 454-6300
WEB SITE: www.hrcengr.com
FAX (1st. Floor): (248) 454-6312 FAX (2nd. Floor): (248) 454-6359
CITY OF SOUTH LYON
WASTE WATER
TREATMENT PLANT
NEW GENERATOR
INSTALLATION
PROJECT
72 HOURS
BEFORE YOU DIG
(3 WORKING DAYS)
CALL MISS DIG
1-800-482-7171 (TOLL FREE)CALL811.COM or 811
Know what's below.
Call before you dig.
N
AutoCAD SHX Text
GM
AutoCAD SHX Text T
AutoCAD SHX Text C/T
AutoCAD SHX Text
SA
AutoCAD SHX Text
SA
AutoCAD SHX Text
SA
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
UN
AutoCAD SHX Text 2023 Hubbell, Roth & Clark, Inc. All Rights Reserved
AutoCAD SHX Text C
AutoCAD SHX Text V:\202302\20230229\C\Sheets\C-1.dwg
AutoCAD SHX Text Uhlianuk, Adam
AutoCAD SHX Text
AutoCAD SHX Text
7/9/2024 10:57 AM
AutoCAD SHX Text 20230229
AutoCAD SHX Text July 2024
AutoCAD SHX Text
ORIGINAL PLOT SIZE: ANSI FULL BLEED D (34.00 X 22.00 INCHES)
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
SITE CONDITIONS
AutoCAD SHX Text 1"=5'-0"
AutoCAD SHX Text C-1
AutoCAD SHX Text A.R.U.
AutoCAD SHX Text A.R.U.
AutoCAD SHX Text M.J.R.
AutoCAD SHX Text R.N.A.
AutoCAD SHX Text 05-24-24
AutoCAD SHX Text
FOR CITY REVIEW
AutoCAD SHX Text 07-12-24
AutoCAD SHX Text
ISSUED FOR BIDS
AutoCAD SHX Text
SCALE: 1" = 20'-0"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
HYD.
AutoCAD SHX Text
STORAGE BUILDING
AutoCAD SHX Text
GARAGE AREA
AutoCAD SHX Text
CONTROL BUILDING
AutoCAD SHX Text
ABANDONED PRIMARY TANKS
AutoCAD SHX Text NOTE: ALL EXISTING UTILITIES SHOWN ON THIS TOPOGRAPHIC SURVEY HAVE BEEN TAKEN FROM VISUAL OBSERVATION AND RECORD MAPPING WHERE AVAILABLE. NO GUARANTEE IS MADE, OR SHOULD BE ASSUMED. AS TO THE COMPLETENESS OR ACCURACY OF THE UTILITIES SHOWN ON THIS DRAWING. PARTIES UTILIZING THIS INFORMATION SHALL FIELD VERIFY. PRIOR TO CONSTRUCTION ALL LOCATIONS AND DEPTHS OR EXISTING UTILITIES (IN CONFLICT WITH PROPOSED IMPROVEMENTS) SHALL BE VERIFIED IN THE FIELD. CALL MISS DIG 3 WORKING DAYS PRIOR TO CONSTRUCTION.
AutoCAD SHX Text
27" SAN
AutoCAD SHX Text
30" SAN
AutoCAD SHX Text
EX. N.G. LINE
AutoCAD SHX Text
EXISTING LEGEND
AutoCAD SHX Text EXISTING FENCE EXISTING SANITARY SEWER LINE EXISTING FIRE MAIN WATER LINE EXISTING STORM SEWER LINE EXISTING STEAM CONDENSATE LINE EXISTING ELECTRICAL SITE POWER EXISTING GAS MAIN LINE EXISTING WATER MAIN LINE EXISTING COLD DOMESTIC WATER EXISTING COMMUNICATIONS LINE EXISTING PIV EXISTING WATER HYDRANT EXISTING LIGHT POLE EXISTING STORM CATCH BASINS EXISTING SANITARY MANHOLE EXISTING GATE VALVE
AutoCAD SHX Text
PIV
SA
DRAWN
DESIGNED
DATE
HRC JOB NO.
DATE
SCALE
ADDITIONS AND/OR REVISIONS
SHEET
NO.
OF
555 HULET DRIVE
BLOOMFIELD HILLS, MICH.
P.O. BOX 824
48303 - 0824
PHONE: (248) 454-6300
WEB SITE: www.hrcengr.com
FAX (1st. Floor): (248) 454-6312 FAX (2nd. Floor): (248) 454-6359
CITY OF SOUTH LYON
WASTE WATER
TREATMENT PLANT
NEW GENERATOR
INSTALLATION
PROJECT
72 HOURS
BEFORE YOU DIG
(3 WORKING DAYS)
CALL MISS DIG
1-800-482-7171 (TOLL FREE)CALL811.COM or 811
Know what's below.
Call before you dig.
N
AutoCAD SHX Text
GM
AutoCAD SHX Text T
AutoCAD SHX Text C/T
AutoCAD SHX Text
SA
AutoCAD SHX Text
SA
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
UN
AutoCAD SHX Text 2023 Hubbell, Roth & Clark, Inc. All Rights Reserved
AutoCAD SHX Text C
AutoCAD SHX Text V:\202302\20230229\C\Sheets\C-2.dwg
AutoCAD SHX Text Uhlianuk, Adam
AutoCAD SHX Text
AutoCAD SHX Text
7/9/2024 10:40 AM
AutoCAD SHX Text 20230229
AutoCAD SHX Text July 2024
AutoCAD SHX Text
ORIGINAL PLOT SIZE: ANSI FULL BLEED D (34.00 X 22.00 INCHES)
AutoCAD SHX Text
SITE PLAN
AutoCAD SHX Text
REMOVAL SHEET
AutoCAD SHX Text 1"=10'-0"
AutoCAD SHX Text C-2
AutoCAD SHX Text A.R.U.
AutoCAD SHX Text A.R.U.
AutoCAD SHX Text M.J.R.
AutoCAD SHX Text R.N.A.
AutoCAD SHX Text 05-24-24
AutoCAD SHX Text
FOR CITY REVIEW
AutoCAD SHX Text 07-12-24
AutoCAD SHX Text
ISSUED FOR BIDS
AutoCAD SHX Text
SCALE: 1" = 10'-0"
AutoCAD SHX Text
AutoCAD SHX Text 2.5
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text NOTE: ALL EXISTING UTILITIES SHOWN ON THIS TOPOGRAPHIC SURVEY HAVE BEEN TAKEN FROM VISUAL OBSERVATION AND RECORD MAPPING WHERE AVAILABLE. NO GUARANTEE IS MADE, OR SHOULD BE ASSUMED. AS TO THE COMPLETENESS OR ACCURACY OF THE UTILITIES SHOWN ON THIS DRAWING. PARTIES UTILIZING THIS INFORMATION SHALL FIELD VERIFY. PRIOR TO CONSTRUCTION ALL LOCATIONS AND DEPTHS OR EXISTING UTILITIES (IN CONFLICT WITH PROPOSED IMPROVEMENTS) SHALL BE VERIFIED IN THE FIELD. CALL MISS DIG 3 WORKING DAYS PRIOR TO CONSTRUCTION.
AutoCAD SHX Text
STORAGE BUILDING
AutoCAD SHX Text
ABANDONED PRIMARY TANKS
AutoCAD SHX Text
CONTROL BUILDING
AutoCAD SHX Text
SCREENING ROOM
AutoCAD SHX Text
HYD.
AutoCAD SHX Text
EX. 6" WTR.MAIN
AutoCAD SHX Text
EX. 12" WTR.MAIN
AutoCAD SHX Text
12" WTR.MAIN
AutoCAD SHX Text
EX. 12" WTR.MAIN
AutoCAD SHX Text
EX. 27" SAN.
AutoCAD SHX Text
EX. 30" SAN.
AutoCAD SHX Text
EX. N.G. LINE
AutoCAD SHX Text
HMA SURFACE REMOVE/EARTH EXCAVATION
AutoCAD SHX Text
EARTH EXVACATION
AutoCAD SHX Text
EX. CONC. S.W.
AutoCAD SHX Text
EXISTING LEGEND
AutoCAD SHX Text EXISTING FENCE EXISTING SANITARY SEWER LINE EXISTING FIRE MAIN WATER LINE EXISTING STORM SEWER LINE EXISTING STEAM CONDENSATE LINE EXISTING ELECTRICAL SITE POWER EXISTING GAS MAIN LINE EXISTING WATER MAIN LINE EXISTING COLD DOMESTIC WATER EXISTING COMMUNICATIONS LINE EXISTING PIV EXISTING WATER HYDRANT EXISTING LIGHT POLE EXISTING STORM CATCH BASINS EXISTING SANITARY MANHOLE EXISTING GATE VALVE
AutoCAD SHX Text
PIV
AutoCAD SHX Text
SA
AutoCAD SHX Text
LEGEND
AutoCAD SHX Text
1. PRIOR TO STARTING ANY EXCAVATIONS THE PRIOR TO STARTING ANY EXCAVATIONS THE CONTRACTOR SHALL COORDINATE WITH THE CITY TO FIELD LOCATE UTILITIES WITHIN THE WORK AREA. 2. THE CONTRACTOR SHALL PROVIDE ALL LABOR, THE CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIALS, AND EQUIPMENT REQUIRED TO COMPLETE THE WORK SHOWN ON THIS SHEET AND TO COMPLETE THE PROJECT. 3. TRENCHING AREAS WITH KNOWN UTILITY TRENCHING AREAS WITH KNOWN UTILITY CROSSINGS OF SIMILAR DEPTH SHALL BE DONE WITH CARE AND SOFT DUG TO LOCATE UTILITY. THE CONTRACTOR SHALL TAKE EVERY PRECAUTION TO NOT DAMAGE EXISTING UTILITIES. 4. CONTRACTOR SHALL COORDINATE WITH OWNER CONTRACTOR SHALL COORDINATE WITH OWNER LOCATION FOR PLACING EARTH EXCAVATION SPOILS. IF SPOILS CANNOT BE STOCK PILED ON SITE THE CONTRACTOR SHALL HAUL AWAY AS DIRECTED BY THE ENGINEER. 5. PAVEMENT REMOVALS SHALL BE SAW CUT PAVEMENT REMOVALS SHALL BE SAW CUT FULL DEPTH WITH A CLEAN EDGE. THE CONTRACTOR SHALL EXTEND THE WIDTH OF PAVEMENT REMOVAL ALONG TRENCHING LINE NO MORE THAN 5' FOR HMA REMOVAL. IF THE EXISTING HMA PAVEMENT ALONG THE EDGE OF TRENCH REMOVAL IS BLOCK CRACKING OR SPALLING THE CONTRACTOR SHALL REMOVE THE BROKEN HMA UNTIL SOLID PAVEMENT IS ENCOUNTERED OR AS DIRECTED BY THE ENGINEER. ADDITIONAL REMOVALS SHALL BE CONSIDERED INCIDENTAL TO THE PROJECT.
GARAGE AREA/ STORAGE
DRAWN
DESIGNED
DATE
HRC JOB NO.
DATE
SCALE
ADDITIONS AND/OR REVISIONS
SHEET
NO.
OF
555 HULET DRIVE
BLOOMFIELD HILLS, MICH.
P.O. BOX 824
48303 - 0824
PHONE: (248) 454-6300
WEB SITE: www.hrcengr.com
FAX (1st. Floor): (248) 454-6312 FAX (2nd. Floor): (248) 454-6359
CITY OF SOUTH LYON
WASTE WATER
TREATMENT PLANT
NEW GENERATOR
INSTALLATION
PROJECT
72 HOURS
BEFORE YOU DIG
(3 WORKING DAYS)
CALL MISS DIG
1-800-482-7171 (TOLL FREE)CALL811.COM or 811
Know what's below.
Call before you dig.
N
AutoCAD SHX Text
GM
AutoCAD SHX Text T
AutoCAD SHX Text
PRIMARY SWITCH + METER
AutoCAD SHX Text
SA
AutoCAD SHX Text
SA
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text
UN
AutoCAD SHX Text 2023 Hubbell, Roth & Clark, Inc. All Rights Reserved
AutoCAD SHX Text C
AutoCAD SHX Text V:\202302\20230229\C\Sheets\C-3.dwg
AutoCAD SHX Text Uhlianuk, Adam
AutoCAD SHX Text
AutoCAD SHX Text
7/10/2024 4:09 PM
AutoCAD SHX Text 20230229
AutoCAD SHX Text July 2024
AutoCAD SHX Text
ORIGINAL PLOT SIZE: ANSI FULL BLEED D (34.00 X 22.00 INCHES)
AutoCAD SHX Text
CONSTRUCTION
AutoCAD SHX Text
SITE PLAN SHEET
AutoCAD SHX Text 1"=10'-0"
AutoCAD SHX Text C-3
AutoCAD SHX Text A.R.U.
AutoCAD SHX Text A.R.U.
AutoCAD SHX Text M.J.R.
AutoCAD SHX Text R.N.A.
AutoCAD SHX Text 05-24-24
AutoCAD SHX Text
FOR CITY REVIEW
AutoCAD SHX Text 07-12-24
AutoCAD SHX Text
ISSUED FOR BIDS
AutoCAD SHX Text
SCALE: 1" = 10'-0"
AutoCAD SHX Text
AutoCAD SHX Text 2.5
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text NOTE: ALL EXISTING UTILITIES SHOWN ON THIS TOPOGRAPHIC SURVEY HAVE BEEN TAKEN FROM VISUAL OBSERVATION AND RECORD MAPPING WHERE AVAILABLE. NO GUARANTEE IS MADE, OR SHOULD BE ASSUMED. AS TO THE COMPLETENESS OR ACCURACY OF THE UTILITIES SHOWN ON THIS DRAWING. PARTIES UTILIZING THIS INFORMATION SHALL FIELD VERIFY. PRIOR TO CONSTRUCTION ALL LOCATIONS AND DEPTHS OR EXISTING UTILITIES (IN CONFLICT WITH PROPOSED IMPROVEMENTS) SHALL BE VERIFIED IN THE FIELD. CALL MISS DIG 3 WORKING DAYS PRIOR TO CONSTRUCTION.
AutoCAD SHX Text
STORAGE BUILDING
AutoCAD SHX Text
ABANDONED PRIMARY TANKS
AutoCAD SHX Text
CONTROL BUILDING
AutoCAD SHX Text
SCREENING ROOM
AutoCAD SHX Text
HYD.
AutoCAD SHX Text
EX. 6" WTR.MAIN
AutoCAD SHX Text
EX. 12" WTR.MAIN
AutoCAD SHX Text
12" WTR.MAIN
AutoCAD SHX Text
EX. 12" WTR.MAIN
AutoCAD SHX Text
EX. 27" SAN.
AutoCAD SHX Text
EX. 30" SAN.
AutoCAD SHX Text
EX. N.G. LINE
AutoCAD SHX Text
GENERATOR STRUCTURAL FOUNDATION PAD
AutoCAD SHX Text
MAINTENANCE STRIP CONCRETE, 6" NON-REINFORCED
AutoCAD SHX Text
EX. CONC. S.W.
AutoCAD SHX Text
EXISTING LEGEND
AutoCAD SHX Text EXISTING FENCE EXISTING SANITARY SEWER LINE EXISTING FIRE MAIN WATER LINE EXISTING STORM SEWER LINE EXISTING STEAM CONDENSATE LINE EXISTING ELECTRICAL SITE POWER EXISTING GAS MAIN LINE EXISTING WATER MAIN LINE EXISTING COLD DOMESTIC WATER EXISTING COMMUNICATIONS LINE EXISTING PIV EXISTING WATER HYDRANT EXISTING LIGHT POLE EXISTING STORM CATCH BASINS EXISTING SANITARY MANHOLE EXISTING GATE VALVE
AutoCAD SHX Text
PIV
AutoCAD SHX Text
SA
AutoCAD SHX Text
LEGEND
AutoCAD SHX Text
GARAGE AREA/ STORAGE
AutoCAD SHX Text
NEW HMA PAVEMENT PATCHING
AutoCAD SHX Text
GREEN SPACE RESTORATION AREA
AutoCAD SHX Text NOTE: A. CONTRACTOR MAY DIRECTIONAL BORE CONDUITS TO GREEN CONTRACTOR MAY DIRECTIONAL BORE CONDUITS TO GREEN SPACE AND OMIT HMA PAVING REQUIREMENTS. EXISTING DRIVEWAY IS BLOCK CRACKING WHICH MAY CAUSE EXTENDED REPAIRS IF OPENED FOR TRENCHING. USE OF HAND PATCH SHALL BE USED TO REPAIR SMALL DAMAGED AREAS AS REQUIRED.
1.5% MAX
DRAWN
DESIGNED
DATE
HRC JOB NO.
DATE
SCALE
ADDITIONS AND/OR REVISIONS
SHEET
NO.
OF
555 HULET DRIVE
BLOOMFIELD HILLS, MICH.
P.O. BOX 824
48303 - 0824
PHONE: (248) 454-6300
WEB SITE: www.hrcengr.com
FAX (1st. Floor): (248) 454-6312 FAX (2nd. Floor): (248) 454-6359
CITY OF SOUTH LYON
WASTE WATER
TREATMENT PLANT
NEW GENERATOR
INSTALLATION
PROJECT
N
N
AutoCAD SHX Text
GENERATOR FOUNDATION
AutoCAD SHX Text
PLANS, SECTION,
AutoCAD SHX Text
DETAILS AND NOTES
AutoCAD SHX Text
AS NOTED
AutoCAD SHX Text S-1
AutoCAD SHX Text
CKC
AutoCAD SHX Text
PMH
AutoCAD SHX Text
RBN
AutoCAD SHX Text
RNA
AutoCAD SHX Text 2023 Hubbell, Roth & Clark, Inc. All Rights Reserved
AutoCAD SHX Text C
AutoCAD SHX Text V:\202302\20230229\S\S01_plot.dwg
AutoCAD SHX Text Haataja, Pamela, M
AutoCAD SHX Text
AutoCAD SHX Text
7/12/2024 8:25 AM
AutoCAD SHX Text 20230229
AutoCAD SHX Text July 2024
AutoCAD SHX Text
ORIGINAL PLOT SIZE: ANSI FULL BLEED D (34.00 X 22.00 INCHES)
AutoCAD SHX Text 07-12-24
AutoCAD SHX Text
ISSUED FOR BIDS
AutoCAD SHX Text
SECTION
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text GENERAL NOTES: 1. VERIFY CONDITIONS AND MEASUREMENTS AT THE SITE & REPORT ANY DISCREPANCIES TO THE OWNER VERIFY CONDITIONS AND MEASUREMENTS AT THE SITE & REPORT ANY DISCREPANCIES TO THE OWNER BEFORE PROCEEDING WITH THE WORK. EXISTING DIMENSIONS AND ELEVATIONS SHOWN WITHIN THESE CONTRACT DOCUMENTS ARE APPROXIMATE AND ARE TO BE FIELD VERIFIED BY THE CONTRACTOR PRIOR TO CONSTRUCTION. 2. EXISTING UTILITIES ARE SHOWN ON THE PLANS FOR THE CONVENIENCE OF THE CONTRACTOR. NO EXISTING UTILITIES ARE SHOWN ON THE PLANS FOR THE CONVENIENCE OF THE CONTRACTOR. NO GUARANTEE CAN BE MADE TO THE COMPLETENESS OR EXACTNESS OF THE LOCATION OF THESE UTILITIES. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO DETERMINE THE EXISTENCE AND LOCATION OF UTILITIES IN THE CONSTRUCTION AREA. THE CONTRACTOR WILL BE HELD RESPONSIBLE FOR ANY DAMAGE TO EXISTING UTILITIES IN THE CONSTRUCTION AREA, AND WILL BE HELD RESPONSIBLE FOR ANY DAMAGE TO EXISTING UTILITIES FROM HIS OPERATION. 3. THE CONTRACTOR SHALL CALL MISS DIG (800-482-7171) A MINIMUM 72 HOURS (3 WORKING DAYS) THE CONTRACTOR SHALL CALL MISS DIG (800-482-7171) A MINIMUM 72 HOURS (3 WORKING DAYS) PRIOR TO THE START OF CONSTRUCTION. 4. THE CONTRACTOR SHALL LOCATE ALL ACTIVE UNDERGROUND UTILITIES PRIOR TO STARTING WORK, AND THE CONTRACTOR SHALL LOCATE ALL ACTIVE UNDERGROUND UTILITIES PRIOR TO STARTING WORK, AND SHALL CONDUCT HIS OPERATIONS IN SUCH A MANNER AS TO ENSURE THAT THOSE UTILITIES NOT REQUIRING RELOCATION WILL NOT BE DISTURBED. 5. THE CONTRACTOR SHALL NOT BURN, CUT, DRILL OR MODIFY STRUCTURAL MEMBERS WITHOUT THE CONTRACTOR SHALL NOT BURN, CUT, DRILL OR MODIFY STRUCTURAL MEMBERS WITHOUT APPROVAL OF THE OWNER. 6. THE CONTRACTOR SHALL PREVENT WATER FROM IMPOSING LOAD ON PORTIONS OF THE WORK PRIOR TO THE CONTRACTOR SHALL PREVENT WATER FROM IMPOSING LOAD ON PORTIONS OF THE WORK PRIOR TO CONCRETE ATTAINING ITS 28 DAY DESIGN STRENGTH. 7. ALL PAVEMENT, SIDEWALKS, DRIVEWAYS, SHOULDERS, LANDSCAPING, DRAINAGE PIPES, ETC., DAMAGED ALL PAVEMENT, SIDEWALKS, DRIVEWAYS, SHOULDERS, LANDSCAPING, DRAINAGE PIPES, ETC., DAMAGED DURING CONSTRUCTION SHALL BE RESTORED BY THE CONTRACTOR AT HIS EXPENSE TO A CONDITION EQUAL TO OR BETTER THAN THAT WHICH EXISTED PRIOR TO CONSTRUCTION. 8. EXISTING MONUMENTS & PROPERTY CORNERS ARE TO BE PRESERVED AND PROTECTED. DISTURBED EXISTING MONUMENTS & PROPERTY CORNERS ARE TO BE PRESERVED AND PROTECTED. DISTURBED SURVEY MARKERS SHALL BE RESTORED AT THE CONTRACTORS EXPENSE. 9. ALL CONSTRUCTION MUST CONFORM TO CURRENT M.I.O.S.H.A. SAFETY STANDARDS. ALL CONSTRUCTION MUST CONFORM TO CURRENT M.I.O.S.H.A. SAFETY STANDARDS. 10. CONTRACTOR SHALL EMPLOY SUCH MEASURES & TAKE SUCH PRECAUTIONS SO AS TO PROTECT FROM CONTRACTOR SHALL EMPLOY SUCH MEASURES & TAKE SUCH PRECAUTIONS SO AS TO PROTECT FROM ANY DAMAGE, ALL ELEMENTS TO REMAIN IN PLACE. 11. CONTRACTOR IS RESPONSIBLE FOR THE DEWATERING OF ALL EXCAVATED AREAS AND TO MAKE HIS CONTRACTOR IS RESPONSIBLE FOR THE DEWATERING OF ALL EXCAVATED AREAS AND TO MAKE HIS OWN DETERMINATION OF WATER LEVELS THAT WILL EXIST DURING CONSTRUCTION. WATER LEVELS ARE SUBJECT TO CHANGE. DEWATERING SHALL NOT BE PAID FOR SEPARATELY. CONTRACTOR IS SOLELY RESPONSIBLE FOR HIS DEWATERING MEANS AND METHODS. 12. CONTRACTOR SHALL PREPARE AND SUBMIT SHOP DRAWINGS FOR THE ENGINEER'S REVIEW, INCLUDING CONTRACTOR SHALL PREPARE AND SUBMIT SHOP DRAWINGS FOR THE ENGINEER'S REVIEW, INCLUDING PRODUCT DATA INFORMATION AND TESTING RESULTS ON ALL PRODUCTS AND MATERIALS TO BE USED. SUBSTITUTIONS FROM THE MATERIALS AND MANUFACTURERS NOTED WITHIN THESE CONTRACT DOCUMENTS IS PERMITTED, PROVIDED THAT THE "OR EQUAL" PRODUCT IS REVIEWED AND ACCEPTED BY THE ENGINEER PRIOR TO INSTALLATION. 13. DENOTES: DENOTES: JWP - JOINT WATERPROOFING ISO JT - ISOLATION JOINT JWP - JOINT WATERPROOFING ISO JT - ISOLATION JOINT ISO JT - ISOLATION JOINT CJ - CONSTRUCTION JOINT 14. FOUNDATION HAS BEEN DESIGNED TO BEAR ON IN-SITU SOILS WITH A NET ALLOWABLE BEARING FOUNDATION HAS BEEN DESIGNED TO BEAR ON IN-SITU SOILS WITH A NET ALLOWABLE BEARING CAPACITY OF 2000 PSF. SHOULD IN-SITU SOIL CAPACITY DIFFER, ENGINEER SHALL BE NOTIFIED IMMEDIATELY AS FOOTING WIDTH MAY NEED TO BE INCREASED. 15. CONTRACTOR TO FURNISH AND INSTALL ANCHORAGES AND HARDWARE PER GENERATOR CONTRACTOR TO FURNISH AND INSTALL ANCHORAGES AND HARDWARE PER GENERATOR MANUFACTURER'S DESIGN SPECIFICATIONS. UNLESS OTHERWISE SPECIFIED BY THE MANUFACTURER, ANCHORS SHALL BE "DRILL & GROUT" AS SPECIFIED IN REINFORCED CONCRETE NOTE 10 WITH A MINIMUM EFFECTIVE EMBEDMENT DEPTH OF 6 INCHES AND A MINIMUM EDGE DISTANCE TO ANCHOR CENTERLINE OF 4 INCHES. REFER TO SPECIFICATION SECTION 16620 FOR SUBMITTAL REQUIREMENTS.. 16. OPENINGS IN FOUNDATION WALL FOR ELECTRICAL CONDUIT SHALL BE FIELD DRILLED. REFERENCE OPENINGS IN FOUNDATION WALL FOR ELECTRICAL CONDUIT SHALL BE FIELD DRILLED. REFERENCE ELECTRICAL DRAWINGS AND COORDINATE WITH ON SITE ENGINEER FOR EXACT SIZE AND LOCATIONS. 17. ALL FOUNDATION ELEMENTS SHALL BE FORMED. CASTING DIRECTLY AGAINST EARTH IS NOT PERMITTED. ALL FOUNDATION ELEMENTS SHALL BE FORMED. CASTING DIRECTLY AGAINST EARTH IS NOT PERMITTED. 18. DO NOT BACKFILL UNTIL CONCRETE HAS ATTAINED AT LEAST 75% OF SPECIFIED 28-DAY COMPRESSIVE DO NOT BACKFILL UNTIL CONCRETE HAS ATTAINED AT LEAST 75% OF SPECIFIED 28-DAY COMPRESSIVE STRENGTH AS DETERMINED BY "FIELD CURED" CYLINDER TESTING.
AutoCAD SHX Text REINFORCED CONCRETE NOTES: 1. CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 4,000 P.S.I. AT 28 DAYS UNLESS CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 4,000 P.S.I. AT 28 DAYS UNLESS OTHERWISE NOTED. FOR MIX DESIGN REQUIREMENTS, REFER TO SPECIFICATION SECTION 03310. 2. STEEL REINFORCEMENT SHALL BE NEW BILLET CONFORMING TO ASTM A615, GRADE 60 AND SHALL BE STEEL REINFORCEMENT SHALL BE NEW BILLET CONFORMING TO ASTM A615, GRADE 60 AND SHALL BE NON EPOXY COATED. REINFORCEMENT STEEL FOR TIES & STIRRUPS SHALL BE NEW BILLET STEEL CONFORMING TO A615, GRADE 60. 3. STEEL REINFORCEMENT SHOP DRAWINGS SHALL BE SUBMITTED AT LEAST TWO WEEKS PRIOR TO STEEL REINFORCEMENT SHOP DRAWINGS SHALL BE SUBMITTED AT LEAST TWO WEEKS PRIOR TO FABRICATION FOR ENGINEER'S APPROVAL. STEEL REINFORCEMENT SHALL BE FABRICATED BY AN MDOT PREQUALIFIED SUPPLIER. 4. REINFORCEMENT SHALL BE DETAILED IN ACCORDANCE WITH LATEST EDITION ACI 318 BUILDING CODE REINFORCEMENT SHALL BE DETAILED IN ACCORDANCE WITH LATEST EDITION ACI 318 BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE AND CONCRETE REINFORCING STEEL INSTITUTE (CRSI), LATEST EDITION, MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES. 5. MINIMUM LAP OF REINFORCEMENT SHALL BE CLASS "B", CASE 2, AS CALLED FOR IN ACI 318, UNLESS MINIMUM LAP OF REINFORCEMENT SHALL BE CLASS "B", CASE 2, AS CALLED FOR IN ACI 318, UNLESS OTHERWISE NOTED. 6. CONCRETE COVER TO REINFORCEMENT : CONCRETE COVER TO REINFORCEMENT : CONCRETE PLACED AGAINST GROUND ......................... 3" CONCRETE PLACED AGAINST GROUND ......................... 3" ALL OTHER (UNLESS OTHERWISE INDICATED) .............. 2" 7. CORNER BARS SHALL BE THE SAME SIZE AND SPACING AS HORIZONTAL REINFORCEMENT UNLESS CORNER BARS SHALL BE THE SAME SIZE AND SPACING AS HORIZONTAL REINFORCEMENT UNLESS OTHERWISE NOTED. PROVIDE LAP SPLICE. PROVIDE HOOKS ON ALL HORIZONTAL BARS MADE DISCONTINUOUS AT WALL OPENINGS. 8. PROVIDE KEYWAYS AT ALL CONSTRUCTION JOINTS (CJ). CONSTRUCTION JOINTS AT THEIR LOCATION AS PROVIDE KEYWAYS AT ALL CONSTRUCTION JOINTS (CJ). CONSTRUCTION JOINTS AT THEIR LOCATION AS SHOWN ARE NOT OPTIONAL. 9. ALL HORIZONTAL RESTEEL SHALL BE CONTINUOUS UNLESS OTHERWISE NOTED. ALL HORIZONTAL RESTEEL SHALL BE CONTINUOUS UNLESS OTHERWISE NOTED. 10. (DRILL & GROUT) - REFERS TO DRILLING INTO EXISTING CONCRETE TO THE SPECIFIED HOLE DIAMETER (DRILL & GROUT) - REFERS TO DRILLING INTO EXISTING CONCRETE TO THE SPECIFIED HOLE DIAMETER AND EMBEDMENT AND ANCHORING THE REINFORCEMENT WITH STRUCTURAL EPOXY ADHESIVE (HIT HY 200 V3 OR HIT HY 500 V3 HIGH STRENGTH INJECTION ADHESIVE SYSTEM BY HILTI CORP. OR APPROVED EQUAL). INSTALL IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATION. THREADED RODS SHALL BE TYPE 304 STAINLESS STEEL HAS RODS WITH MATCHING HARDWARE BY HILTI OR APPROVED EQUAL. 11. ALL EXPOSED CONCRETE CORNERS SHOWN SQUARE ON THE PLANS SHALL BE BEVELED WITH 1/2" ALL EXPOSED CONCRETE CORNERS SHOWN SQUARE ON THE PLANS SHALL BE BEVELED WITH 1/2" TRIANGULAR MOLDINGS EXCEPT AS OTHERWISE NOTED. 12. FIELD CUTTING OF REINFORCEMENT, WHERE NOTED, SHALL BE CUT BY MECHANICAL MEANS. FLAME FIELD CUTTING OF REINFORCEMENT, WHERE NOTED, SHALL BE CUT BY MECHANICAL MEANS. FLAME CUTTING OF REINFORCEMENT IS NOT ACCEPTABLE. 13. ALL EXPOSED CONCRETE SURFACES SHALL RECEIVE PENETRATING WATER REPELLENT SEALER APPLIED ALL EXPOSED CONCRETE SURFACES SHALL RECEIVE PENETRATING WATER REPELLENT SEALER APPLIED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. "MASTER PROTECT H400" BY SIKA/MASTERBUILDERS OR APPROVED EQUAL. 14. JOINT WATERPROOFING (JWP) SHALL BE W.R. MEADOWS "MEL-ROL" WATERPROOFING MEMBRANE OR JOINT WATERPROOFING (JWP) SHALL BE W.R. MEADOWS "MEL-ROL" WATERPROOFING MEMBRANE OR APPROVE EQUAL. CLEAN AND PRIME SURFACES IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS TO REMOVE EXISTING COATINGS AND/OR DEBRIS PRIOR TO WATERPROOFING.
AutoCAD SHX Text
* FOUNDATION COORDINATION NOTES: DIMENSIONS AND ELEVATIONS SHOWN IN TOP PLAN, SECTIONAL PLAN AND SECTION 1 SHALL BE COORDINATED WITH GENERATOR MANUFACTURER'S REPRESENTATIVE PRIOR TO SUBMITTING SHOP DRAWINGS. DENNIS ROBAK CUMMINS SALES & SERVICE (248) 207-2876 DENNIS.ROBAK@CUMMINS.COM CONTRACTOR SHALL SUBMIT DETAILED GENERATOR SHOP DRAWINGS FOR OWNER/ENGINEER REVIEW AND ACCEPTANCE PRIOR TO THE START OF CONSTRUCTION. CONTRACTOR SHALL CONFIRM DIMENSIONS, ELEVATIONS AND OPENINGS WITH MANUFACTURER'S REPRESENTATIVE FOR SUPPLIED GENERATOR PACKAGE PRIOR TO SUBMITTING FOUNDATION REINFORCEMENT PLAN FOR OWNER REVIEW.
AutoCAD SHX Text 9"
AutoCAD SHX Text 9"
6"
REINF
AutoCAD SHX Text
REINF
AutoCAD SHX Text
BM1
AutoCAD SHX Text
BM2
AutoCAD SHX Text
CONSTRUCTION JOINT
AutoCAD SHX Text
1/2" ISO JT
AutoCAD SHX Text T
AutoCAD SHX Text T/3
AutoCAD SHX Text
NOTE: STOP SHEAR KEY 6" FROM EXPOSED EDGES.
AutoCAD SHX Text 4'-6"
AutoCAD SHX Text 9'-6"
AutoCAD SHX Text 3'-0"
AutoCAD SHX Text 1'-0"
AutoCAD SHX Text 2'-9"
AutoCAD SHX Text 4'-9"
AutoCAD SHX Text #5 @ 12" T&B
AutoCAD SHX Text (4)-#5 T&B
AutoCAD SHX Text 3"
AutoCAD SHX Text
JWP (TYP)
AutoCAD SHX Text
AutoCAD SHX Text
GENERATOR FDN
AutoCAD SHX Text
TOP PLAN
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
SECTIONAL PLAN
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text 9'-6"
AutoCAD SHX Text
AutoCAD SHX Text S-1
AutoCAD SHX Text
AutoCAD SHX Text S-1
AutoCAD SHX Text
FOUNDATION (SYM ABT EXCEPT OPNG)
AutoCAD SHX Text
BM2
AutoCAD SHX Text
BM1
AutoCAD SHX Text
FOUNDATION (SYM ABT EXCEPT OPNG)
AutoCAD SHX Text (2)-#5 x 4'-0" DIAG T&B INNER LAYER (TYP - EA CORNER)
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
- SEE FOUNDATION COORDINATION NOTES
AutoCAD SHX Text
8" TYP, FULL PERIMETER
AutoCAD SHX Text
AutoCAD SHX Text 4'-7"
AutoCAD SHX Text NOTES: 1. FOR CONCRETE MAINTENANCE FOR CONCRETE MAINTENANCE STRIP DETAIL, SEE SHEET E-5. 2. FOR BM1 AND BM2, SEE FOR BM1 AND BM2, SEE DETAILS, THIS SHEET.
AutoCAD SHX Text
FOUNDATION
AutoCAD SHX Text
AutoCAD SHX Text 11'-6"
AutoCAD SHX Text
FOUNDATION (SYM ABT)
AutoCAD SHX Text
AutoCAD SHX Text 9'-6"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FOUNDATION (SYM ABT)
AutoCAD SHX Text S-1
AutoCAD SHX Text
AutoCAD SHX Text
BM1
AutoCAD SHX Text
BM2
AutoCAD SHX Text
TYP REINF SPAN
AutoCAD SHX Text 3'-0"
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SLOPE 1.5% MAX
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text NOTE: GENERATOR SKID NOT SHOWN. FOR DRILL & GROUT OF ANCHORS, SEE REINF CONC NOTE 10.
AutoCAD SHX Text
N. BM2 LOOKING EAST, S. BM2 SIM
AutoCAD SHX Text
DRAWN
DESIGNED
DATE
HRC JOB NO.
DATE
SCALE
ADDITIONS AND/OR REVISIONS
SHEET
NO.
OF
555 HULET DRIVE
BLOOMFIELD HILLS, MICH.
P.O. BOX 824
48303 - 0824
PHONE: (248) 454-6300
WEB SITE: www.hrcengr.com
FAX (1st. Floor): (248) 454-6312 FAX (2nd. Floor): (248) 454-6359
CITY OF SOUTH LYON
WASTE WATER
TREATMENT PLANT
NEW GENERATOR
INSTALLATION
PROJECT
EXISTING 750KVA
TRANSFORMER
AutoCAD SHX Text 2023 Hubbell, Roth & Clark, Inc. All Rights Reserved
AutoCAD SHX Text C
AutoCAD SHX Text V:\202302\20230229\E\Sheet\E01PLOT_Oneline.dwg
AutoCAD SHX Text Uhlianuk, Adam
AutoCAD SHX Text
AutoCAD SHX Text
7/10/2024 10:54 AM
AutoCAD SHX Text 20230229
AutoCAD SHX Text July 2024
AutoCAD SHX Text
ORIGINAL PLOT SIZE: ANSI FULL BLEED D (34.00 X 22.00 INCHES)
AutoCAD SHX Text
REVISED PLANT ONE-LINE DIAGRAM
AutoCAD SHX Text 05-24-24
AutoCAD SHX Text
60% REVIEW SET
AutoCAD SHX Text 07-12-24
AutoCAD SHX Text
ISSUED FOR BIDS
AutoCAD SHX Text
ELECTRICAL
AutoCAD SHX Text
ONE-LINE DIAGRAM
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text E-1
AutoCAD SHX Text A.R.U.
AutoCAD SHX Text A.R.U.
AutoCAD SHX Text M.J.R.
AutoCAD SHX Text R.N.A.
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text 50E
AutoCAD SHX Text K
AutoCAD SHX Text K
AutoCAD SHX Text
DETROIT EDISON METERING
AutoCAD SHX Text
200 AMP LOAD BREAK SWITCH
AutoCAD SHX Text (3)
AutoCAD SHX Text
15 KV INTERMEDIATE CLASS ARRESTERS
AutoCAD SHX Text 3-1/C #2, 15KV, GN & 1-#2 GRD.,3"C. PLUS 1-3" (SPARE CONDUIT) CONFORMS TO DETROIT EDISON CO. SPEC. #501
AutoCAD SHX Text T1
AutoCAD SHX Text
AP
AutoCAD SHX Text
RES
AutoCAD SHX Text 1-#2, 3/4"C.
AutoCAD SHX Text
FUSE
AutoCAD SHX Text W
AutoCAD SHX Text
FUSE
AutoCAD SHX Text
FUSE
AutoCAD SHX Text B
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
60 TD
AutoCAD SHX Text
AutoCAD SHX Text
86 HR
AutoCAD SHX Text
52 CS
AutoCAD SHX Text
52 CS
AutoCAD SHX Text
AutoCAD SHX Text K
AutoCAD SHX Text
AutoCAD SHX Text
FUSE
AutoCAD SHX Text
FUSE
AutoCAD SHX Text 47-2
AutoCAD SHX Text 47-1
AutoCAD SHX Text
800A 800AT
AutoCAD SHX Text 480-120V
AutoCAD SHX Text (2)
AutoCAD SHX Text
(2) 480-120
AutoCAD SHX Text 1600/5 (3)
AutoCAD SHX Text (3)
AutoCAD SHX Text (3)
AutoCAD SHX Text (1)
AutoCAD SHX Text
AP
AutoCAD SHX Text A
AutoCAD SHX Text (1)
AutoCAD SHX Text (1)
AutoCAD SHX Text (1)
AutoCAD SHX Text (1)
AutoCAD SHX Text (1)
AutoCAD SHX Text
1600A,3P. 1600A FU. MAIN SWITCH
AutoCAD SHX Text
EXERCISER
AutoCAD SHX Text 1600A, AutoCAD SHX Text
MB-2
AutoCAD SHX Text
FB-2 800A 600AT 3P.
AutoCAD SHX Text
3 PH., 3W., BUS
AutoCAD SHX Text
MB-1
AutoCAD SHX Text
L.V. SWITCHGEAR
AutoCAD SHX Text SQUARE "D" INDOOR POWER ZONE II DRAW-OUT SWITCHGEAR WITH BREAKER TYPE; DS-416 FOR 1600A FRAME SIZE DS-206 FOR 800A FRAME SIZE
AutoCAD SHX Text M.A.P.
AutoCAD SHX Text M.A.P.
AutoCAD SHX Text 4-20 mA (NOTE-5)
AutoCAD SHX Text 4-20 mA (NOTE-5)
AutoCAD SHX Text
(3) 800/5
AutoCAD SHX Text X
AutoCAD SHX Text
NOTE-4
AutoCAD SHX Text
NOTE-4
AutoCAD SHX Text
EX. 800A., 3P., MANUAL TRANSFER SWITCH WALL MTD. IN ELECTRICAL ROOM
AutoCAD SHX Text
TEMPERATURE INDICATOR
AutoCAD SHX Text
NEW NEMA 3R 100A 240V 1PH DISCONNECT, FUSED AT 100A
AutoCAD SHX Text
NEW 25 KVA 480-240/120V TRANSFORMER GT-1 (Z=5%)
AutoCAD SHX Text
LP-A (22,24), (26)
AutoCAD SHX Text
1200A LSIG
AutoCAD SHX Text
1200A 3P. MAIN BREAKER SET TO 800AT
AutoCAD SHX Text
800A LSIG
AutoCAD SHX Text NOTE: : 1. CONTRACTOR SHALL COORDINATE ALL SWITCHGEAR AND SCADA CONTRACTOR SHALL COORDINATE ALL SWITCHGEAR AND SCADA WORK WITH U.IS.
AutoCAD SHX Text
FB-1 800A, 250AT 3P.
AutoCAD SHX Text
FB-3 800A 150AT 3P.
AutoCAD SHX Text
FB-4 800A 200AT 3P.
AutoCAD SHX Text
FB-5 800A 800AT 3P.
AutoCAD SHX Text
FB-6 800A 800AT 3P.
AutoCAD SHX Text
EX. CONTROL PANEL
EX. MOTOR CONTROL CENTER "MCC-A"
DRAWN
DESIGNED
DATE
HRC JOB NO.
DATE
SCALE
ADDITIONS AND/OR REVISIONS
SHEET
NO.
OF
555 HULET DRIVE
BLOOMFIELD HILLS, MICH.
P.O. BOX 824
48303 - 0824
PHONE: (248) 454-6300
WEB SITE: www.hrcengr.com
FAX (1st. Floor): (248) 454-6312 FAX (2nd. Floor): (248) 454-6359
CITY OF SOUTH LYON
WASTE WATER
TREATMENT PLANT
NEW GENERATOR
INSTALLATION
PROJECT
AutoCAD SHX Text 2023 Hubbell, Roth & Clark, Inc. All Rights Reserved
AutoCAD SHX Text C
AutoCAD SHX Text V:\202302\20230229\E\Sheet\E02PLOT_Schedule.dwg
AutoCAD SHX Text Uhlianuk, Adam
AutoCAD SHX Text
AutoCAD SHX Text
7/10/2024 10:55 AM
AutoCAD SHX Text 20230229
AutoCAD SHX Text July 2024
AutoCAD SHX Text
ORIGINAL PLOT SIZE: ANSI FULL BLEED D (34.00 X 22.00 INCHES)
AutoCAD SHX Text 05-24-24
AutoCAD SHX Text
60% REVIEW SET
AutoCAD SHX Text 07-12-24
AutoCAD SHX Text
ISSUED FOR BIDS
AutoCAD SHX Text
NOTES, LEGEND, SCHEDULE,
AutoCAD SHX Text
AND LOAD CALCULATIONS
AutoCAD SHX Text
NO SCALE
AutoCAD SHX Text E-2
AutoCAD SHX Text A.R.U.
AutoCAD SHX Text A.R.U.
AutoCAD SHX Text M.J.R.
AutoCAD SHX Text R.N.A.
AutoCAD SHX Text A-8
AutoCAD SHX Text A-9
AutoCAD SHX Text A-18
AutoCAD SHX Text A-19
AutoCAD SHX Text A-17
AutoCAD SHX Text
INCOMING LINE
AutoCAD SHX Text
SPACE
AutoCAD SHX Text A-4
AutoCAD SHX Text A-3
AutoCAD SHX Text A-2
AutoCAD SHX Text A-1
AutoCAD SHX Text A-11
AutoCAD SHX Text A-15
AutoCAD SHX Text A-14
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
SPACE
AutoCAD SHX Text
SPACE
AutoCAD SHX Text A-13
AutoCAD SHX Text A-12
AutoCAD SHX Text A-10
AutoCAD SHX Text A-7
AutoCAD SHX Text A-6
AutoCAD SHX Text A-5
AutoCAD SHX Text A-21
AutoCAD SHX Text A-20
AutoCAD SHX Text A-22
AutoCAD SHX Text A-23
AutoCAD SHX Text A-29
AutoCAD SHX Text A-16
AutoCAD SHX Text A-24
AutoCAD SHX Text A-25
AutoCAD SHX Text A-26
AutoCAD SHX Text A-27
AutoCAD SHX Text A-28
AutoCAD SHX Text
FRONT ELEVATION MOTOR CONTROL CENTER "MCC-A"
AutoCAD SHX Text
WIRE AND CONDUIT
AutoCAD SHX Text
BREAKER
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text POS. No.
AutoCAD SHX Text
EX. CONTROL MOTOR CENTER "MCC-A" SCHEDULE
AutoCAD SHX Text
DESIG.
AutoCAD SHX Text
* CONN. LOAD
AutoCAD SHX Text
CONN. AMPS.
AutoCAD SHX Text
SWITCH
AutoCAD SHX Text
480V, 3PH., 3 W., 600 AMP. MAIN BUS AND GROUND BUS
AutoCAD SHX Text A-1
AutoCAD SHX Text A-2
AutoCAD SHX Text A-3
AutoCAD SHX Text A-4
AutoCAD SHX Text
TOTAL CONNECTED LOAD
AutoCAD SHX Text
SPARE
AutoCAD SHX Text 20A
AutoCAD SHX Text
SURGE SUPPRESSOR
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
221KVA
AutoCAD SHX Text 266A
AutoCAD SHX Text 30A
AutoCAD SHX Text A-5
AutoCAD SHX Text A-6
AutoCAD SHX Text A-7
AutoCAD SHX Text A-8
AutoCAD SHX Text A-9
AutoCAD SHX Text A-10
AutoCAD SHX Text A-11
AutoCAD SHX Text A-12
AutoCAD SHX Text A-13
AutoCAD SHX Text A-14
AutoCAD SHX Text A-15
AutoCAD SHX Text A-16
AutoCAD SHX Text A-17
AutoCAD SHX Text A-18
AutoCAD SHX Text A-19
AutoCAD SHX Text A-20
AutoCAD SHX Text A-21
AutoCAD SHX Text A-22
AutoCAD SHX Text A-23
AutoCAD SHX Text A-24
AutoCAD SHX Text A-25
AutoCAD SHX Text A-26
AutoCAD SHX Text A-27
AutoCAD SHX Text A-28
AutoCAD SHX Text
NAMEPLATE ENGRAVING
AutoCAD SHX Text
* FUSE
AutoCAD SHX Text
STARTER
AutoCAD SHX Text
SIZE
AutoCAD SHX Text
TYPE
AutoCAD SHX Text
CONTROL DEVISES
AutoCAD SHX Text
AutoCAD SHX Text
FVNR
AutoCAD SHX Text
HOA, PL, ETM
AutoCAD SHX Text
SPARE
AutoCAD SHX Text 50A
AutoCAD SHX Text 100A
AutoCAD SHX Text
HOA, PL, ETM
AutoCAD SHX Text
AutoCAD SHX Text
FVNR
AutoCAD SHX Text
HOIST & CABLE REEL (SCREEN RM)
AutoCAD SHX Text
RAW SEWAGE SAMPLE PUMP
AutoCAD SHX Text
MECHANICAL BAR SCREEN
AutoCAD SHX Text
CONTROL BLDG. SUMP PUMP
AutoCAD SHX Text
CONTROL BLDG. SUMP PUMP
AutoCAD SHX Text
WASH PRESS UNIT
AutoCAD SHX Text
CONTROL BLDG. H & V UNIT
AutoCAD SHX Text
HOT WATER CIRCULATION PUMP
AutoCAD SHX Text
HOT WATER CIRCULATION PUMP
AutoCAD SHX Text
SCREENING RM. H & V UNIT
AutoCAD SHX Text
AIR HANDLING UNIT
AutoCAD SHX Text
CAPACITOR BANK
AutoCAD SHX Text 3 H.P.
AutoCAD SHX Text 4.8
AutoCAD SHX Text
2.1 H.P.
AutoCAD SHX Text 3.3
AutoCAD SHX Text .5 H.P.
AutoCAD SHX Text 1.1
AutoCAD SHX Text 5 H.P.
AutoCAD SHX Text 7.6
AutoCAD SHX Text
NO.1
AutoCAD SHX Text
NO.2
AutoCAD SHX Text 5 H.P.
AutoCAD SHX Text 7.6
AutoCAD SHX Text 5A
AutoCAD SHX Text 30A
AutoCAD SHX Text 5A
AutoCAD SHX Text 30A
AutoCAD SHX Text 20A
AutoCAD SHX Text 30A
AutoCAD SHX Text 15A
AutoCAD SHX Text 30A
AutoCAD SHX Text 15A
AutoCAD SHX Text 30A
AutoCAD SHX Text 20A
AutoCAD SHX Text 30A
AutoCAD SHX Text 30A
AutoCAD SHX Text 60A
AutoCAD SHX Text 5A
AutoCAD SHX Text 30A
AutoCAD SHX Text 5A
AutoCAD SHX Text 30A
AutoCAD SHX Text 5A
AutoCAD SHX Text 30A
AutoCAD SHX Text 8A
AutoCAD SHX Text 30A
AutoCAD SHX Text 50A
AutoCAD SHX Text 60A
AutoCAD SHX Text 5 H.P.
AutoCAD SHX Text 7.6
AutoCAD SHX Text
AHU-2
AutoCAD SHX Text
7.5 H.P.
AutoCAD SHX Text 11.0
AutoCAD SHX Text
CP-1
AutoCAD SHX Text 2 H.P.
AutoCAD SHX Text 3.4
AutoCAD SHX Text
CP-2
AutoCAD SHX Text 2 H.P.
AutoCAD SHX Text 3.4
AutoCAD SHX Text
AHU-4
AutoCAD SHX Text 3 H.P.
AutoCAD SHX Text 4.8
AutoCAD SHX Text
AHU-5
AutoCAD SHX Text 3 H.P.
AutoCAD SHX Text 4.8
AutoCAD SHX Text
NO.1
AutoCAD SHX Text
30KAVR
AutoCAD SHX Text 36.0
AutoCAD SHX Text
AutoCAD SHX Text
MCC LEGEND
AutoCAD SHX Text HORSEPOWERS ARE EST., VERIFY EXACT SIZES WITH EQUIP. FOR STARTER HEATER SIZING, BREAKER SIZING, OR FUSE SIZING
AutoCAD SHX Text
CPT
AutoCAD SHX Text
CR
AutoCAD SHX Text
ETM
AutoCAD SHX Text
FVNR
AutoCAD SHX Text
GFR
AutoCAD SHX Text
HOA
AutoCAD SHX Text
LR
AutoCAD SHX Text
PB
AutoCAD SHX Text
PL
AutoCAD SHX Text
SS
AutoCAD SHX Text
CONTROL POWER TRANSFORMER
AutoCAD SHX Text
CONTROL RELAY
AutoCAD SHX Text
ELAPSED TIME METER
AutoCAD SHX Text
FULL VOLTAGE, NON-REVERSING
AutoCAD SHX Text
GROUND FAULT RELAY
AutoCAD SHX Text
HAND-OFF-AUTO SELECTOR SWITCH
AutoCAD SHX Text
LINE REACTOR
AutoCAD SHX Text
PUSHBUTTON SWITCH
AutoCAD SHX Text
PRESS-TO-TEST INDICATING LIGHT
AutoCAD SHX Text
START AND STOP PUSHBUTTON SWITCHES
AutoCAD SHX Text
SSL
AutoCAD SHX Text
START AND STOP LOCK-OUT PUSHBUTTON SWITCHES
AutoCAD SHX Text
SSR
AutoCAD SHX Text
START AND STOP/RESET PUSHBUTTON SWITCHES
AutoCAD SHX Text
TVSS
AutoCAD SHX Text
TRANSIENT VOLTAGE SURGE SUPPRESSOR
AutoCAD SHX Text
VFD
AutoCAD SHX Text
VARIABLE FREQUENCY CONTROLLER (DRIVE)
AutoCAD SHX Text
GENERATOR RM SERVICE PWR.
AutoCAD SHX Text
LP-GEN
AutoCAD SHX Text
10 KVA
AutoCAD SHX Text 21.0
AutoCAD SHX Text 25A
AutoCAD SHX Text 30A
AutoCAD SHX Text 4A
AutoCAD SHX Text 30A
AutoCAD SHX Text 30A
AutoCAD SHX Text
100 VA
AutoCAD SHX Text .21
AutoCAD SHX Text
LAB. VACUUM PUMP
AutoCAD SHX Text
1.5 HP
AutoCAD SHX Text 2.6
AutoCAD SHX Text 4A
AutoCAD SHX Text 30A
AutoCAD SHX Text 5A
AutoCAD SHX Text 30A
AutoCAD SHX Text
LAB. VACUUM PRIMER
AutoCAD SHX Text
2 HP+ 2 HP
AutoCAD SHX Text 6.8
AutoCAD SHX Text
EXHAUST FAN GENERATOR RM.
AutoCAD SHX Text
EF-8
AutoCAD SHX Text
3 HP
AutoCAD SHX Text 4.8
AutoCAD SHX Text 8A
AutoCAD SHX Text 60A
AutoCAD SHX Text
CAPACITY BANK
AutoCAD SHX Text
NO.2
AutoCAD SHX Text
30KVAR
AutoCAD SHX Text 36.0
AutoCAD SHX Text 50A
AutoCAD SHX Text 60A
AutoCAD SHX Text
RAW SEWAGE PUMP NO.1 VFD
AutoCAD SHX Text
RAW SEWAGE PUMP NO.2 VFD
AutoCAD SHX Text
RAW SEWAGE PUMP NO.3 VFD
AutoCAD SHX Text
RAW SEWAGE PUMP NO.4 VFD
AutoCAD SHX Text
RAW SEWAGE PUMP NO.5 VFD
AutoCAD SHX Text
25 HP
AutoCAD SHX Text 34.0
AutoCAD SHX Text
25 HP
AutoCAD SHX Text 34.0
AutoCAD SHX Text
25 HP
AutoCAD SHX Text 34.0
AutoCAD SHX Text
10 HP
AutoCAD SHX Text 14.0
AutoCAD SHX Text
25 HP
AutoCAD SHX Text 34.0
AutoCAD SHX Text 50A, 3P
AutoCAD SHX Text 50A, 3P
AutoCAD SHX Text 50A, 3P
AutoCAD SHX Text 50A, 3P
AutoCAD SHX Text 20A, 3P
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
SS, PL, GFR
AutoCAD SHX Text
AutoCAD SHX Text
FVNR
AutoCAD SHX Text
3-#12 + #12 GRD. & 6-#14, 3/4"C.
AutoCAD SHX Text
3-#12 + #12 GRD., 3/4"C.
AutoCAD SHX Text
3-#12 + #12 GRD. & 9-#14, 3/4"C.
AutoCAD SHX Text
3-#12 + #12 GRD. & 4-#14, 3/4"C.
AutoCAD SHX Text
3-#12 + #12 GRD., 3/4"C.
AutoCAD SHX Text
3-#12 + #12 GRD., 3/4"C.
AutoCAD SHX Text
3-#8 + #10 GRD., 1"C.
AutoCAD SHX Text
3-#12 + #12 GRD. & 2-#14, 3/4"C.
AutoCAD SHX Text
AutoCAD SHX Text
FVNR
AutoCAD SHX Text
HOA, PL
AutoCAD SHX Text
3-#12 + #12 GRD. & 2-#14, 3/4"C.
AutoCAD SHX Text
AutoCAD SHX Text
FVNR
AutoCAD SHX Text
HOA, PL
AutoCAD SHX Text
3-#12 + #12 GRD., 3/4"C.
AutoCAD SHX Text
3-#12 + #12 GRD., 3/4"C.
AutoCAD SHX Text
3-#8 + #10 GRD., 1"C.
AutoCAD SHX Text
3-#12 + #12 GRD., 3/4"C.
AutoCAD SHX Text
AutoCAD SHX Text
FVNR
AutoCAD SHX Text
HOA, PL, ETM
AutoCAD SHX Text
CPT, 3 CR (ALT)
AutoCAD SHX Text
AutoCAD SHX Text
FVNR
AutoCAD SHX Text
HOA, PL
AutoCAD SHX Text
3-#12 + #12 GRD., 3/4"C.
AutoCAD SHX Text
3-#12 + #12GRD., 3/4"C.
AutoCAD SHX Text
3-#12 + #12 GRD. & 2-#14, 3/4"C.
AutoCAD SHX Text
AutoCAD SHX Text
FVNR
AutoCAD SHX Text
HOA, PL, ETM
AutoCAD SHX Text
3-#8 + #10 GRD., 1"C.
AutoCAD SHX Text
3-#6 + #8 GRD., 1-1/4"C.
AutoCAD SHX Text
3-#6 + #8 GRD., 1-1/4"C.
AutoCAD SHX Text
3-#6 + #8 GRD., 1-1/4"C.
AutoCAD SHX Text
3-#12 + #12 GRD., 3/4"C.
AutoCAD SHX Text
3-#6 + #8 GRD., 1-1/4"C.
AutoCAD SHX Text A-29
AutoCAD SHX Text
GT-1 TRANS.
AutoCAD SHX Text 70A
AutoCAD SHX Text 100A
AutoCAD SHX Text 70A, 2P
AutoCAD SHX Text
3-#4 + #8 GRD., 1"C.
AutoCAD SHX Text
AutoCAD SHX Text
SPARE
AutoCAD SHX Text 50A
AutoCAD SHX Text 100A
AutoCAD SHX Text
HOA, PL, ETM
AutoCAD SHX Text
AutoCAD SHX Text
FVNR
AutoCAD SHX Text
GENERAL NOTES:
AutoCAD SHX Text
1. THE CONTRACTOR SHALL VISIT THE JOB SITE AND THE CONTRACTOR SHALL VISIT THE JOB SITE AND THOROUGHLY CHECK THE FIELD CONDITIONS AND EXISTING ELECTRICAL INSTALLATION AND UTILITIES (ELECTRICAL AND TELEPHONE) PRIOR TO SUBMITTING A BID. 2. OTHER PROJECTS ARE, OR MAY BE, UNDER CONSTRUCTION AT OTHER PROJECTS ARE, OR MAY BE, UNDER CONSTRUCTION AT THIS SITE, AND THIS CONTRACTOR SHALL COORDINATE WITH THEM SO AS NOT TO DELAY THEIR SCHEDULES OR IMPEDE THEIR WORK. 3. ALL ELECTRICAL WORK SHALL COMPLY WITH THE N.E.C. ALL ELECTRICAL WORK SHALL COMPLY WITH THE N.E.C. AND THE CITY'S LOCAL CODES, ORDINANCES, REGULATIONS, AND MIOSHA. 4. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, LICENSES, INSPECTIONS, APPROVALS AND FEES REQUIRED AND ENSURE THAT THE ENTIRE INSTALLATION CONFORMS TO CODES AND REGULATIONS REQUIRED BY AUTHORITY OR AGENCY HAVING JURISDICTION OVER THE INSTALLATION, ALTERATION OR CONSTRUCTION OF WORK INCLUDED. ALL FEES SHALL BE INCLUDED IN THE BASE PROPOSAL. 5. COORDINATE ALL UNDERGROUND WORK WITH THE CITY OR COORDINATE ALL UNDERGROUND WORK WITH THE CITY OR MISS DIG, NEW AND EXISTING, UNDERGROUND UTILITIES PRIOR TO EXCAVATIONS OR INSTALLATIONS. 6. ALL POWER WIRING 120 VOLTS AND GREATER SHALL BE ALL POWER WIRING 120 VOLTS AND GREATER SHALL BE INSTALLED IN CONDUIT AND SHALL BE NEW. UNLESS NOTED OTHERWISE, RIGID GALVANIZED STEEL SHALL BE USED WHERE CONDUIT IS EXPOSED OUTSIDE. EMT CONDUIT SHALL BE USED IN BUILDING INTERIORS. 7. ALL DIRECT BURIED CONDUITS SHALL BE RIGID GALVANIZED ALL DIRECT BURIED CONDUITS SHALL BE RIGID GALVANIZED OR P.V.C. SCH. 40. 8. ALL DIRECT BURIED CONDUITS SHALL BE 24" BELOW ALL DIRECT BURIED CONDUITS SHALL BE 24" BELOW GRADE (MIN,) AND SHALL SLOPE A MINIMUM 3" PER 100' TO MANHOLES, HANDHOLES, CABLE VAULTS, OR OTHER STRUCTURES. 9. ALL EXPOSED CONDUIT SHALL BE RIGID GALVANIZED STEEL, ALL EXPOSED CONDUIT SHALL BE RIGID GALVANIZED STEEL, INSTALLED WITH WATERTIGHT CONDUIT FITTINGS. EXPANSION FITTINGS SHALL BE PROVIDED AT ALL TRANSITIONS FROM UNDERGROUND TO EXPOSED CONDUIT. 10. ALL UNDERGROUND CONDUITS AND/OR DUCTS IN DUCT ALL UNDERGROUND CONDUITS AND/OR DUCTS IN DUCT BANKS SHALL BE P.V.C. EXCEPT WHERE ENTERING MANHOLES, HANDHOLES, BUILDINGS, LIGHT POLE BASES, AND TRANSFORMER PADS. UNDERGROUND CONDUITS AND/OR DUCTS SHALL BE RIGID GALVANIZED STEEL WITHIN 5' OF THE STRUCTURE. ALL CONDUITS AND/OR DUCTS UNDER BUILDINGS SHALL BE RIGID GALVANIZED STEEL. 11. ALL EMPTY CONDUITS SHALL BE PROVIDED WITH A 1/4" ALL EMPTY CONDUITS SHALL BE PROVIDED WITH A 1/4" DIA. POLYPROPYLENE FISHLINE. 12. ALL CONDUITS SHALL BE ROUTED TO AVOID OPENINGS IN ALL CONDUITS SHALL BE ROUTED TO AVOID OPENINGS IN FLOORS, ROOFS, AND WALLS. LADDERS UP WALLS SHALL NOT BE CROSSED BY EXPOSED CONDUIT RUNS. PROVIDE THE MINIMUM CLEAR SPACE REQUIRED BY ALL GOVERNING CODES BETWEEN HANDRAILS AND ALL ELECTRICAL ENCLOSURES AND RACEWAYS, WHICH IN NO CASE SHALL BE LESS THAN 1 1/2" CLEAR. 13. ALL ELECTRICAL FLOOR MOUNTED EQUIPMENT SUCH AS ALL ELECTRICAL FLOOR MOUNTED EQUIPMENT SUCH AS MOTORS, CONTROL PANELS AND METALLIC SUPPORT RACKS SHALL HAVE A MIMIMUM #2 BARE COPPER GROUND CONDUCTOR BETWEEN THE MOTOR, FRAME, ENCLOSURE, OR SUPPORT LEG AND THE BUILDING GROUND SYSTEM. 14.