Additional questions and responses

View the file

Other files for this federal contract opportunity

Other files attached to Bldg 3129 Sq Ops Renovation, newest first.
File Type Posted
W91ZRU-17-B-0001_B3129_Squad_Ops_Reno_Abstract.pdf PDF
W91ZRU-17-B-0001_0001.pdf PDF
W91ZRU-17-B-0001_0002.pdf PDF
Request_for_Information_(Template)_(2).docx DOCX document
Site_Visit_sign_sheet.pdf PDF
W91ZRU-17-B-0001_Final.pdf PDF
COMBINED_SPECIFICATIONS.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

QUESTION 32:

Spec Section 01 49 00 addresses the temporary offices and latrine facilities the contractor is to provide for Gov’t personnel.

1. How many square feet shall be allocated to the 50 personnel? Traditional UFC standards are/were 64 SF per person. Does the furniture layout dictate more or less area per person?

The useable occupied temporary office space (without latrine facility) should be

4,400+ sf to accommodate common areas also.

2. How much area, if any, shall be dedicated to support space such as break room, conference rm, copier area etc?

Approximately 10-20% of space.

3. For the latrine facility, is a two-stall ladies room with one sink acceptable? For the men, two sink vanity with two urinals and two stalls?

Per UFC 3-420-01 and working conditions, Ladies: 3 stall and 2 sink with Gentlemen:

2 stall, 2 urinal, and 2 sink should work.

4. Do the trailers require full connectivity via breezeway or common-wall?

No, but they should be placed to minimize exterior environmental exposure when traversing between temporary office trailers and restroom facility.

QUESTION 33:

What is the size of the desk or cubicle for the temporary facility?

Workstations will be modeled from 6’x3’ desks for layout.

QUESTION 34:

Specification 01 49 00 requires pad lockable doors. Would privacy locks be acceptable?

No, privacy locks are not acceptable for these exterior applications.

QUESTION 35:

Yes.

Specification 01 49 00 requires 3 storage units. Each unit 24’X8’X7’. Would it be acceptable to provide 4 units 20’X8’X7?

File details come from the government source that posted it. Updated .