| US | Army | Corps | of | Engineers |
| Far | East | District |
| Asbestos | Verification | Survey | Report | for | |
| Building | 1114 | at | Osan | Air | Base |
Prepared by:
Geotechnical and Environmental Engineering Branch, US Army Corps of Engineers District Far East
Unit #15546, APO AP 96205-5546
February 2017
TABLE OF CONTENTS
1. Introduction ········································································ 1
2. Record Review····································································· 2
3. Asbestos Verification Survey ·················································· 2
4. Conclusion ·········································································· 4
Attachments
Attachment A. Asbestos Location Map
Attachment B. Certificate of Asbestos Inspector
Attachment C. Certificate of Laboratory Accreditation
Attachment D. Previous Survey Report
Asbestos Verification Survey for Building 1114 at Osan Air Base
1. Introduction
Geotechnical and Environmental Engineering (G&EE) Branch of Far East District (FED), U.S. Army Corps of Engineers conducted an asbestos verification survey of Building 1114 at Osan Air Base on 23 July 2015. The objective of the asbestos verification survey was to verify the status of detected Asbestos Containing Materials (ACM) in the previous asbestos survey.
The asbestos survey was conducted in general accordance with the requirements of Title 40 of Code of Federal Regulations Part 763 (40 CFR 763) Environmental Protection Agency (EPA)’s Asbestos Hazards Emergency Response Act (AHERA) regulations, 40 CFR 61 Subpart National Emission Standards for Hazardous Air Pollutants (NESHAPS), and 29 CFR 1926.1101 Occupational Safety and Health Administration (OSHA) Occupational Exposure to Asbestos.
The survey was conducted by AHERA-accredited building inspectors. Certificates of asbestos inspector are provided in Attachment B.
Asbestos Building Inspector and Certificate No.
Kim, Kyong-Ho ME67C0EE869B94475 So, Tae-Won MEE5EE223778FA476
The bulk samples were analyzed using Polarized Light Microscopy (PLM) and a stereomicroscope as specified by the EPA Interim Method for the Determination of Asbestos in Bulk Samples (EPA-600/R-93/116). Suspected material that contains greater than one (1) percent asbestos is classified as ACM.
The samples were analyzed by LA Testing located in South Pasadena, CA which is accredited by the National Voluntary Laboratory Accreditation Program (NVLAP) and the American Industrial Hygiene Association (AIHA). NVLAP certificate of LA Testing is provided in Attachment C. The NVLAP-accredited laboratory identification and scope of accreditation are provided below:
NVLAP ID: 200232-0
Scope of Accreditation: Bulk/Air Asbestos Fiber Analysis Address: 520 Mission Street, South Pasadena, CA, 91030, USA.
2. Record Review
Previous survey of building 1114 was conducted by URS in 2001 and the report is provided in Attachment D. Table 1 lists detected ACM description, location and area from Building 1114.
Table 1. List of Detected ACM from Building 1114 in Previous Survey
ACM Description ACM Location ACM Amount
Joint Compound FS #6 and 10 78 SF
12"x12" Brown Floor tile FS #7 140 SF
12"x12" Black Floor Tile FS #11 400 SF
12"x12" Green w/White Flecked Floor Tile FS #13 110 SF
3. Asbestos Verification Survey
3.1 Field Survey
Based on previous survey information, US Army Corp of Engineers FED performed an asbestos verification survey of Building 1114 on 23 July 2015. Verification survey includes:
(1) visual inspection of detected ACM based on previous asbestos survey report; (2) bulk sampling of detected ACM on previous survey report for verification if necessary; and (3) new bulk material was sampled if additional ACM identification is required.
3.2 Survey Results
Table 2 summarizes the results of ACM verification based on visual inspection and table 3 provides photograph for found ACMs. The map for verified ACM is provided in Attachment A.
Table 2. Summary of ACM Verification at Building 1114
Material Description
Sample
ID
Location Result
ACM
Amount Physical
Condition Friability Remarks
Joint Compound
Visual Inspection
FS #6 and
No
ACM N/A(1) N/A N/A
Refer to the Note
(2)
12"x12" Brown Floor tile
Visual Inspection FS #7
Not Found N/A N/A N/A Removed
12"x12" Black Floor Tile
Visual Inspection Room #1 ACM 200 SF Good
Non- Friable
12"x12" Green w/White
Flecked Floor Tile
Visual Inspection Room #2 ACM 140 SF N/A N/A
(1)N/A: Not Applicable (2)The joint compound associated with non-ACM gypsum board was not sampled in 2015 survey whereas 2001 survey identified this joint compound as ACM. Based on USFK regulation 201-1 (15- 3.m.1), this wall systems including joint compound is not considered as ACM because wall systems including joint compound are considered combined material and the analytical result of the combined material is expected to be less than one percent of asbestos
Table 3. Photographs for found ACMs at Building 1114
12"x12" Black Floor Tile 12"x12" Green w/White Flecked Floor Tile
4. Conclusion
Visual inspection for detected ACMs based on the previous asbestos survey report was conducted. As a result, vinyl tile was determined as ACM.
The vinyl tile is identified as a non-friable ACM and observed to be in good condition.
Removing the ACMs is not required until a planned building renovation will impact the area or demolition will be performed. However, asbestos fibers become airborne and the risks from asbestos occur when it is disturbed or damaged. The ACM should not be sanded, scraped or abrasively stripped. To avoid disturbing ACM, proper and continuous maintenance activity is required. The ACM can be left in place, but they should be managed in accordance with the Asbestos Management Plan.
Attachment A
Asbestos Location Map
Location Code Material Code
Code Location Code Material Code Material A Attic AT Acoustic Tile PL Plaster B Boiler AS Asphalt Shingle TB Transite Board C Ceiling CK Caulking Material TP Tar Paper D Duct CM Cementitious Material VT Vinyl Tile E Exterior FC Flex Connector F Floor GA Gasket I Interior GB Gypsum Board P Pipe IN Insulation R Roof JC Joint Compound W Wall MA Mastic
Non - Asbestos Containing Material
Sample Location
Asbestos Containing Material
Sample ID
Sample Type
ASBESTOS CONTAINING MATERIAL LEGEND
1A
VTF
U.S. ARMY CORPS OF ENGINEERS
FAR EAST DISTRICT
Surveyed by:
Kim, Kyong-Ho
Drawn By:
Kim, Kyong-Ho
Date:
15 Jun 2016
Project No.:
14-037E
Checked by:
Chon, Son-Chu Building No : 1114
Asbestos Verification Survey Map of Building 1114 at Osan Air Base
12"x12" Black Floor Tile: 200 SF 12"x12" Green w/White Flecked Floor Tile: 140 SF
ARMAMENT SHOP / GUN
MAINTENANCE BAY
ACM (12"x12" Brown Floor Tile) was removed.
ACM (12"x12" Black Floor Tile) was removed.
- The joint compound associated with non-ACM gypsum board was not sampled in 2015 survey whereas 2001 survey identified this joint compound as ACM.
Based on USFK regulation 201-1 (15-3.m.1), this wall systems including joint compound is not considered as ACM because wall systems including joint compound are considered combined material and the analytical result of the combined material is expected to be less than one percent of asbestos.
- No Sample
- Only visual inspection was conducted Room #2
Room #1
Attachment B
Certificate of Asbestos Inspector
Attachment C
Certificate of Laboratory Accreditation
Attachment D
Previous Survey Report
Asbestos Report of Survey Final Report - Volume I
Osan Air Base, Republic of Korea
Prepared for:
51 CES/CEV
Building 426, Unit 2129 Osan AB
Pyongtaek City, South Korea
AFCEE/ERD
3207 North Road
Brooks AFB, Texas 78235-5363
Prepared by:
URS Corporation 8181 East Tufts Avenue
Denver, Colorado 80237
(303) 694-2770
December 2001
USAF Contract No. F41624-97-D8020
Delivery Order No. 0200 and Mod. -01
| 1.Asbestos Verification Survey_1114_Osan |
| 2.Attachment A_Asbestos Map_Cover |
| 3.Attachment A_Asbestos Map-1114 |
| 4.Attachment B_Inspector Certificate_Cover |
| 5.Attachment B_Inspector Certificater |