SCHEDULE OF DRAWINGS

RING NO. REF. NO.REVISION STATUSDWG. NO. SHT. NO.REF. NO.

T - 1

RING NO. DESCRIPTION OF DRAWINGS

TITLE SHEET

DWG. NO. SHT. NO. DESCRIPTION OF DRAWINGS REVISION STATUS

TITLE SHEET

T-1

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

E - 1

E - 2

ELECTRICAL

L - 1 PROJECT LOCATION PLAN2

E - 3

E - 4

REPAIR CBRN PROTECTION SYSTEM

IN VARIOUS BUILDINGS, CRC

CAMP RED CLOUDCHONG, ST

109374

REPAIR CBRN PROTECTION SYSTEM IN VARIOUS BUILDINGS

FEWR NO. 109374, CAMP RED CLOUD

MECHANICAL

M - 1

BLDG S-294, S-292 & S-50, CRC

M - 2

M - 3

M - 4

M - 5

M - 6

M - 7

M - 8

M - 9

M - 10

M - 11

M - 12

M - 13

M - 14

M - 15

M - 16

M - 17

M - 18

M - 19

M - 20

M - 21

M - 22

M - 23

M - 24

M - 25

M - 26

M - 27

M - 28

M - 29

M - 30

M - 31

MECHANICAL MATERIAL INDICATIONS & SYMBOLS AND ABBREVIATIONS

SCOPE OF WORK AND GENERAL NOTES

MECHANICAL EQUIPMENT SCHEDULE

BLAST DOORS FLOOR PLAN(UPPER BUNKER, S-294) AND SPECIFIC NOTES

(BLDG S-294) AND SPECIFIC NOTES

DECON STATION FLOOR PLAN (UPPER BUNKER, S-294)

DECON STATION PARTIAL PLAN-1 & 2(UPPER

PENETRATION WITH NON-METALLIC CONNECTOR AND NOTES

BUNKER, S-294), WALL DUCT

DECON STATION PARTIAL PLAN-3 AND NOTES

DOMESTIC WATER TANK SYSTEM FLOOR AND SECTION PLAN AND NOTES

UPPER BUNKER NBC MAIN CONTROL PANEL-1

UPPER BUNKER NBC MAIN CONTROL PANEL-2

CPS AIR FLOW SYSTEM DIAGRAM (UPPER BUNKER),EXHAUST FAN SYSTEMS

AND AIRLOCK AREA SYSTEM

LADDER DIAGRAM-1(NBC MAIN CONTROLPANEL-1), UPPER BUNKER

LADDER DIAGRAM-2(NBC MAIN CONTROLPANEL-2), UPPER BUNKER

EXISTING MECHANICAL ROOM FLOOR PLAN

NOTES AND BLAST VALVES

(UPPER BUNKER, S-294), SPECIFIC

EXISTING NBC FAN SECTION-1(UPPER BUNKER, S-294)

EXISTING NBC FAN SECTION-2(UPPER BUNKER, S-294)

BLAST DOORS FLOOR PLAN(LOWER BUNKER,

AND SPECIFIC NOTES

S-292), LOW LEVEL FLOOR PLAN

LOWER BUNKER NBC MAIN CONTROL PANEL-1

LOWER BUNKER NBC MAIN CONTROL PANEL-2

CPS AIR FLOW SYSTEM DIAGRAM(LOWER BUNKER) AND EXHAUST FAN

SYSTEM

LADDER DIAGRAM-1(NBC MAIN CONTROLPANEL-1), LOWER BUNKER

LADDER DIAGRAM-2(NBC MAIN CONTROLPANEL-2), LOWER BUNKER

EXISTING MECH RM CEILING LEVEL PLAN

PLAN (LOWER BUNKER, S-292) AND SPECIFIC NOTES

, EXISTING BLAST VALVES UPPER LEVEL

EXISTING MECH RM MCRF FILTER LEVEL

SPECIFIC NOTES

PLAN(LOWER BUNKER, S-292) AND

EXISTING NBC FAN SECTION(LOWER BUNKER, S-292)

EXISTING FLOOR PLAN(BLDG S-50)AND SPECIFIC NOTES

BUNKER(S-50) NBC MAIN CONTROL PANEL

LADDER DIAGRAM-1(NBC MAIN CONTROLPANEL-1), S-50 BUNKER

LADDER DIAGRAM-2(NBC MAIN CONTROLPANEL-2), S-50 BUNKER

BUNKER(S-294,S-292 & S-50) AIR LEAKAGE TEST FLOW CHART

E - 5

E - 6

E - 7

E - 8

E - 9

E - 10

LEGEND, GENERAL NOTES AND SCOPE OF WORKS

INTERCOM SYSTEM DIAGRAM( UPPER BUNKER, S-294 )

EXIST/NEW AIRLOCK SYSTEM CONTROL AND AUXILIARY PLAN,

SYSTEM PLAN( UPPER BUNKER, S-294 )

EXIST/NEW ELECTRICAL DOOR CONTROL

MCC DETAILS & DIAGRAMS, EXIST MCC ( UPPER BUNKER, S-294 )

POWER & CONTROL PLAN (S-294 )

EXIST/NEW FAN & FILTER ASSEMBLY UNIT

SYSTEM PLAN ( LOWER BUNKER, S-292 )

EXIST/NEW ELECTRICAL DOOR CONTOL

( LOWER BUNKER, S-292 )

EXIST/NEW MECHANICAL ROOM PARTIAL POWER PLAN (HIGH LEVEL)

( LOWER BUNKER, S-292 )

MCC DETAILS & DIAGRAMS/EXIST NMCC1

INTERCOM SYSTEM DIAGRAM

EXISTING ELECTRICAL PLAN(BLDG S-50),

HIGH LEVEL( UPPER BUNKER, S-294 )

EXIST/NEW ELECTRICAL ROOM PARTIAL POWER PLAN

UPPER BUNKER PARTIAL & SECTION PLAN

L-1

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

CIVIL

PROJECT LOCATION PLAN

N

GREEN

SAND

S A

N D

FNSH. EL. EL. 68.20

OUT

DOOR

DE

CK

BIK

E R

ACK

FL

EL:

67.0

N

POHANG

UIJONGBU

MAIN GATE

FIRE STATION

GATE #2

NOT TO SCALE

L O C A T I O N M A P

CAMP RED CLOUD

WONJU

MOKPO

TONGYOUNG

SEOUL

TONGDUCHON

CHUNCHON

OSAN

TAEJON

E A S T S E A

BUSAN

WAEGWAN

CHINHAE

TAEGU

MUNSAN

W E S T

S E A

INCHON

KWANGJU

KUNSAN

PYONGTAEK

SCALE:

PROJECT LOCATION PLAN

N/A

S-294

S-50

REPAIR CBRN PROTECTION SYSTEM

IN VARIOUS BUILDINGS, CRC

CAMP RED CLOUDCHONG, ST

109374

S-292

CP RED CLOUD, KOREA

REPAIR CBRN PROTECTION SYSTEM IN VARIOUS BUILDINGS,

FEWR NO. 109374,

THIS PROJECT

M E C H A N I C A L M A T E R I A L I N D I C A T I O N S & S Y M B O L S

NTS

PD

Pa

OS&Y

OXY

OD

OAIL

OA

QT

PRV

PPM

POL

POC

PLMB

PH

PG

RT

RPM

RH

RDTR

RA

R12, R22

QTY

A B B R E V I A T I O N S

SBM

SAN

SA

SCH

FLOWMETER, ORIFICEBUTTERFLY

REFRIGERANT LIQUID

CHILLED WATER SUPPLY

CHILLED WATER RETURN

AIR COOLED CONDENSING UNIT

AIR CONDITION UNIT (S)

APPARATUS DEW POINT

AIR CONDITION (-ING,-ED)

HOT CHILLED WATER RETURN

AMERICAN WIRE GAUGE

PRESSURE, BAROMETRIC

CUBIC METER PER HOUR

HOT/CHILLED WATER SUPPLY

CAPACITYCAP

CONNECTION

CONTINUE

COMPRESSOR

CUBIC METER

CPRSR

CONN

CONT

CU M

CHILLED WATER

CAST IRON PIPE

CIRCUIT

CLASSIFICATION

COOLING LOAD

COEFFICIENT

COUNTER CLOCKWISE

CLASS

CLG LOAD

COEF

CMH

CIP

CCW

CHW

CKT

ACV ALARM CHECK VALVE

AVERAGEAVG

BOILING POINT

CENTIGRADE

BAROMETER(-TRIC)

BRAKE HORSEPOWER

BP

BHP

C

BARO PR

AWG

BARO

ALUMINUM

ALTITUDE

AMBIENT

AIR HANDLING UNIT

AMPERE(AMP, AMPS)

APPROXIMATEAPPROX

ALT

AMB

AMP

AIR COND

ADP

AL

AHU

AIR COOLED

ACCU

ACLD

ACU

CHR

C/HWR

C/HWS

CHS

RL

D

DRAIN

DIAMETER, INSIDE

ISOMETRIC

IRON PIPE SIZE

JOULE

THERMAL CONDUCTIVITY

KILOGRAM

KILOGRAM PER SQ. CENTIMETER (GAUGE)

KILOGRAM PER SQ. CENTIMETER

KILOGRAM PER SQ. CENTIMETER (ABSOLUTE)

KILOCALORIE PER HOUREXPANSION JOINT

EXPLOSION PROOF

FIRE HOSE CABINET

FULL LOAD AMPERES

ENTERING WATER TEMP

EVAPORAT (-E,-ING,-ED,-OR)

EXTERNAL STATIC PRESSURE

FACE AREA OR FRESH AIRFA

FHC

FHY

FLA

FIRE HYDRANT

ESP

EXPJT

EWT

EVAP

EP

EQPT

ENT

EFF

EQUIPMENT

ENTERING

EFFICIENCY

KG/SQ CM

KG/SQ CM A

KG/SQ CM G

KG

KCAL/HR

J

K

ID

ISO

IPS

NO

N.O.

NIC

NPT

MPS

NC

N/A

N.C.

MAX

MIN

MPH

MM

NOT IN CONTRACT

NATIONAL TAPER PIPE (THREAD)

NUMBER

NORMALLY OPEN

MINIMUM OR MINUTE

METERS PER HOUR

METERS PER SECOND

NORMALLY CLOSED

NOISE CRITERIA

NOT APPLICABLE

MAXIMUM

MILLIMETER R

FEMALE PIPE THREAD

FUEL OIL

GALVANIZED STEEL

GAGE OR GAUGE

FIXTURE

FEED WATER PUMP

FACE VELOCITY

FLUSH VALVE

FREQUENCY

FIBERGLASS REINFORCED PLASTIC

HORIZONTAL

HOT WATER HEATER

HOT WATER

HOUR(S)

HORSEPOWER

MERCURY

HEAD

HOSE BIBB

HERTZ

GRAMS

FRP

CWP CIRCULATING WATER PUMP

DIRECT EXPANSION

DRY PIPE VALVE

EQUIVALENT DIRECT RADIATION

ENTERING AIR TEMPERATURE

DOUBLE POLE DOUBLE THROW

DEWPOINT TEMPERATURE

DRY BULB TEMPERATURE

DECIBEL OR DRY BULB

DIESEL OILDO

ECON

ECC

EAT

EDR

DX

DPV

DPDT

DPT

ECONOMIZER

ECCENTRIC

o

DIFF

DIAG

DIA or

DIV

DBT

DB

DIFFERENCE

DIAGRAM

DIAMETER

DIVISION

DEGREE

HR

HORIZ

HWH

HW

HZ

HP

HG

HD

HB

GALVS

GA

GR

FXTR

FWP

FVEL

FV

CUBIC MILLIMETER

CLOCKWISE OR COLD WATER

COEFFICIENT, VALVE FLOWCv

CU MM

CW

PLUG VALVE

THREE WAY

FPT

FO

FREQ

GATE, ANGLE

GATE, GLOBE

GLOBE

GATE

CONTROL

KJ KILOJOULE

LH

LT

LWT

LPS

M

LL

LPD

LPH

LM

LAV

LAT

LBS

LG

KW

KWH

L

LATENT HEAT

LEAVING WATER TEMPERATURE

LITERS PER HOUR

LITERS PER SECOND

LAUNDRY TRAY

METERS

LIQUID LINE

LITERS PER DAY

LINEAR METER

LEAVING AIR TEMPERATURE

LAVATORY

POUNDS

LENGTH

KILOWATT

KILOWATT HOUR

LITERS

P

FLOWMETER, VENTURI

FLOW SWITCH

PRESSURE SWITCH

PRESSURE GAUGE AND COCK

PUMP (INDICATE USE)

STRAINER

STRAINER, BLOW OFF

KG/SM

KG/SM A

KG/SM G

PS

P

OFM

FS

VFM

KILOGRAM PER SQ. METER

KILOGRAM PER SQ. METER (ABSOLUTE)

KILOGRAM PER SQ. METER (GAUGE)

JACKET WATER RETURN

MEDIUM PRESSURE STEAM

MEDIUM PRESSURE CONDENSATE

LOW PRESSURE STEAM

LOW PRESSURE CONDENSATE

BOILER BLOW DOWN

PUMPED CONDENSATE

JACKET WATER SUPPLY

VACUUM PUMP DISCHARGE

FUEL OIL TANK VENT

CONDENSATE WATER SUPPLY

CONDENSATE WATER RETURN

MEDIUM TEMPERATURE HOT WATER SUPPLY

MEDIUM TEMPERATURE HOT WATER RETURN

LOW TEMPERATURE HOT WATER SUPPLY

LOW TEMPERATURE HOT WATER RETURN

PIPE TO BE REMOVED

REFRIGERANT DISCHARGE

REFRIGERANT SUCTION

LPS

CONTROL AIR MAIN

air conditioning and refrigeration

RD

RS

(NAME)E

(NAME)

M

EXISTING PIPE

COMPRESSED AIR

VACUUM (AIR)

HWR

VAC

A

MTWS

MTWR

HWS

FOD

FUEL OIL DRAIN

FOR

CS

CR

FOV

FOG

FOS

FUEL OIL SUPPLY

FUEL OIL RETURN

FUEL OIL GAUGE

PC

VPD

MU

LPC

BBD

MAKE UP WATER

MPS

MPC

JWR

JWS

heating

PIPING

CHECK, SWINGSANITARY DRAIN

PITCH OR PIPE, UP(U), DOWN(D)

FLOOR SINK (200mm x 200mm)

PIPE SLEEVE WITH FIRE STOPPING

VENT THRU ROOF

BFP

valves : (for selective actuators)

PLAN

HOSE BIBB

AIR LINE

A

BALL

ELEV.

BACKFLOW PREVENTER

PIPE SLEEVE

(NAME)

ACID

200mm x 200mm

SURFACE CLEANOUT

FLOOR CLEANOUT

FLOOR DRAIN

CHEMICAL SUPPLY PIPES

FUNNEL DRAIN, OPEN

FCO

FD

SCO

FLOOR OR GRADE

FLOOR OR GRADE

CONDENSATE DRAIN BELOW

CONDENSATE DRAIN ABOVE

ACID WASTE

GAS

G

CD

CD

AIR VENT, MANUAL

AIR VENT, AUTOMATIC

W/ MEASURING TAP

EXPANSION LOOP

EXPANSION JOINT

BALL JOINT

ANCHOR, MAIN

ANCHOR, INTERMEDIATE

ALIGNMENT GUIDE

AIR SEPARATOR

FLEXIBLE CONNECTOR

SQUARE HEAD BALANCING COCK

EJ

S

MV

AVV

CHECK, NON-SLAM

CONTROL, ELECTRIC-PNEUMATIC

CONTROL, PNEUMATIC-ELECTRIC

QUICK OPENING

PRESSURE REDUCING

NEEDLE

LOCK SHIELD

HOSE END DRAIN

SAFETY

RELIEF

SQUARE HEAD BALANCING COCK

QUICK CLOSING, FUSIBLE LINK

R

S

PE

EP

plumbing

COLD WATER

HOT WATER RETURN

HOT WATER SUPPLY

VENT

MOTOR ELECTRIC

DIAPHRAGM

valves, special duty :

SOLENOID

S valve actuators

M

FDAD

SUCTIONQUANTITY SUCT

TONS OF REFRIGERATION

TEMPERATURE DIFFERENCE

HEAT TRANSFER COEFFICIENT

SANITARY

SUBMERSIBLE

SUPPLY AIR

SCHEDULE

RADIATOR

REFRIGERATION TON

REVOLUTIONS PER MINUTE

RELATIVE HUMIDITY

RETURN AIR

THERMAL RESISTANCE

REFRIGERANT (12, 22, ETC)

TYPICALTYP

URINAL

UNIT HEATER

UR

UH

U

THERMOSTAT

THICKNESS

THERMOMETER

TEMPERATURE

SYMBOL

TSTAT

TONS

THERM

THK

TEMP

TD

SYM

SINGLE POLE DOUBLE THROW

LPH, STANDARD CONDITIONS

LPS, STANDARD CONDITIONS

LPD, STANDARD CONDITIONS

SAYBOLT SECONDS UNIVERSAL

SAYBOLT SECONDS FUROL

SENSIBLE HEATOUTSIDE AIR INTAKE LOUVER SH

PRESSURE DROP OR DIFFERENCE

PRESSURE REDUCING VALVE

PHASE (ELECTRIC)

PERCENT

PARTS PER MILLION

POINT OF CONNECTION

PLUMBING

PETROLEUM, OIL AND LUBRICANTS

QUART

OUTSIDE SCREW & YOKE

DIAMETER, OUTSIDE

PRESSURE GAGE

POLE

PASCAL

OXYGEN

SPRINKLERSPR

STEEL

STANDARD

STEAM

SQUARE

STAINLESS STEEL

STORAGESTOR

STL

STD

ST

SSU

SST

SSF

SQ

SENSIBLE LOAD

STATIC PRESSURE

SQUARE METER

SPECIFICATION

SPDT

SPEC

SM

SP

SLPH

SLPS

SLPD

SL

ALARM CHECK VALVE

SIDEWALL SPRINKLER

PENDENT SPRINKLER

UPRIGHT SPRINKLER

FIRE DEPARTMENT CONNECTION

PRE-ACTION VALVE

NOT TO SCALE

OUTSIDE AIR

(2-WAY SHOWN)

DRY-PIPE VALVE

SECOND

SAFETY FACTOR

SPECIFIC GRAVITYSG

SF

SEC

VARIABLE AIR VOLUMEVAV

VENTILATION

PRESSURE, DYNAMIC(VELOCITY)

WATER-COOLED

WATER CLOSET

WATTHOUR OR WATER HEATER

WET BULB TEMPERATURE

WATERPROOF

WSHR

WCLD

WTRPRF

WH

WT

W/

WD

WC

WBT

WEIGHT

WITH

WASHER

WIDTH

VP

VOL

WB

W

VISC

VERT

VENT

VEL

VOLUME

WET BULB

WATT

VISCOSITY

VERTICAL

VELOCITY

MANUAL VOLUME DAMPER

SMOKE DAMPER (PROVIDE ACCESS DOOR)

PNEUMATIC OPERATED DAMPER

VLV

V

VAC

M

VALVE

VOLT

VACUUM

SPLITTER DAMPER

SD

AD

VD

grilles, registers and diffusers :

SG

SR

600/300

300x150

200mm NCD

FIGURE IS ON TOP

810mm x 400mm dampers

ELBOW, TURNED DOWN

REDUCER, CONCENTRIC

REDUCER, ECCENTRIC (STRAIGHT, INVERT)

REDUCER, ECCENTRIC (STRAIGHT, DOWN)

TEE, OUTLET DOWN

TEE, SINGLE SWEEP

sprinkler

UNION, SCREWED

UNION, FLANGED

TEE, OUTLET UP

TEE

LATERAL

CONNECTION, BOTTOM

CONNECTION, TOP

ELBOW, TURNED UP

BUSHING

CAP

WELDED

FLANGED

SOLDERED

SCREWED BELL AND SPIGOT

SOLVENT CEMENT

SOUND ATTENUATOR

DETECTORS, FIRE AND/OR SMOKE

ELECTRIC MOTOR OPERATED DAMPER

FIRE DAMPER (PROVIDE ACCESS DOOR)

BACKDRAFT DAMPER

BDD

S

TRANSITION

TURNING VANES

SF

CHANGE OF ELEVATION, RISE(R), DOWN(D)

DUCT SECTION, NEGATIVE PRESS., FIRST

ACCESS DOOR, VERTICAL OR HORIZONTAL

COWL, (GOOSENECK) AND FLASHING

ACOUSTICAL LINING

FLEXIBLE DUCT

FLEXIBLE CONNECTIONFC

FIGURE IS ON TOP

R

AD

47.2

TG

94.4

UC 13mm

DG

500/300L

DUCT WORK

810mm x 400mm

810mm x 400mm

THERMOSTAT, ELECTRIC

TRAP, ELECTRIC (INDICATE TYPE)

fitting :

R

THERMOMETER

EXHAUST AIR GRILLE OR REGISTER, CEILING

DUCT SECTION, POSITIVE PRESS., FIRST

DIRECTION OF FLOW

SR

DIFFUSER, LINEAR

RETURN AIR GRILLE OR REGISTER, CEILING

CEILING DIFFUSER, SQUARE TYPE

CEILING DIFFUSER, ROUND TYPE (200mm

(600mm x 300mmH, 472 LPS)

UNDERCUT DOOR (13mm, 47.2 LPS)

DOOR GRILLE (300mmx150mmH)

NECK DIAMETER)

TRANSFER GRILLE ASSEMBLY

LOUVER, DOOR OR WALL

(500mmWx300mmH, 94.4 LPS)

RG

RR

SUPPLY AIR GRILLE OR REGISTER, SIDEWALL

EXHAUST AIR GRILLE OR REGISTER, CEILING

SUPPLY AIR GRILLE OR REGISTER, CEILING

ER

SG

EG

FD FIRE DAMPER

VOLUME DAMPERVD

EXHAUST AIREA

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

M-1

MECHANICAL

MECHANICAL MATERIAL INDICATIONS &

SYMBOLS AND ABBREVIATIONS

REPAIR CBRN PROTECTION SYSTEM

IN VARIOUS BUILDINGS, CRC

CAMP RED CLOUDCHONG, ST

109374

5. CONCRETE REMOVAL AND RESTORATION SHALL CONFORM TO SPECIFICATION.

NECESSARY DUCT CONNECTION(S) TO FUNCTION AS ORIGINALLY INTENDED.

12. PRIOR TO INSTALLING NEW HVAC AND PLUMBING PIPING CONTRACTOR MUST

COORDINATE WITH EXISTING DUCTWORK AND PIPING ELEVATION/LOCATION.

IF EXISTING DUCT ELEVATION IS CONFLICTED WITH NEW PIPING INSTALLATION,

REMOVE EXISTING DUCTWORK AND INSTALL NEW DUCTWORK AND MAKE ALL

CONTRACTING OFFICER FOR APPROVAL.

CONTRACTOR ACCORDING TO ACTUAL FIELD CONDITIONS AND SUBMITTED TO THE

FIELD CONDITIONS. SUCH DETAILS SHALL BE PREPARED IN THE FIELD BY THE

11. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACT

SUCH AS ANCHORS, HANGERS/SUPPORT, ETC.

10. ALL HVAC PIPING/DUCTWORK TO BE REMOVED SHALL INCLUDE ALL IT'S ACCESSORIES

9. ANY OPENING RESULT FROM THE REMOVAL WORK THAT'S NOT TO BE RE-USED

SHALL BE PATCHED OR RESTORED TO MATCH ADJACENT SURFACE OR AREA.

PER SPEC.

THIS CONTRACTOR.

AND SHALL BE VERIFIED AT THE JOB SITE.

CORRECTIONS FOR CONTRACTING OFFICER'S APPROVAL.

7. ALL WALL/FLOOR/ROOF OPENINGS RESULTED FROM THE REMOVAL OF PIPING AND

4. ANY PIPES THAT PENETRATE FIRE RATED WALL (EXISTING/ NEW) SHALL BE SEALED

6. NO MECHANICAL WORK CAN BE STARTED WITHOUT AN APPROVED SHOP DRAWINGS.

SHOP DRAWING SHALL NOT BE THE EXACT DUPLICATION OF THE CONTRACT DRAWING.

2. LOCATION AND SIZES OF EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC. APPROXIMATE

OFFICER'S REPRESENTATIVE ATTENTION WITH RECOMMENDATIONS FOR PROPER

IF ANY DISCREPANCY IS DETECTED, IT SHOULD BE BROUGHT TO THE CONTRACTING

THE EXISTING CONDITIONS, EQUIPMENT, FINISHES, ETC., PRIOR TO START OF WORK.

1. THE CONTRACTOR SHALL VISIT THE SITE AND SHALL FAMILIARIZE HIMSELF WITH

THE WORK PERFORMED UNDER THIS CONTRACT SHALL BE REPAIRED OR REPLACED BY

THE EXISTING EQUIPMENT ANY EQUIPMENT, DUCT WORK, PIPING ETC. DAMAGED DUE TO

3. CONNECT TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE

THE REQUIREMENTS OF SEAL CLASS C.

8. ALL SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED

ACCORDING TO SMACNA STATIC PRESSURE CALSS 500PA AND DUCTWORK SHALL MEET

DUCTWORK SHALL BE PATCHED OR RESTORED TO MATCH ADJACENT SURFACE OR AREAS.

SCOPE OF WORK

13.

CHANGES REQUIRED TO MAKE THIS

CONTRACTOR SHALL PROVIDE NECESSARY SHOP DRAWINGS FOR ANY

REQUIREMENT FOR GAS ONLY BURNERS MAY BE JUSTIFIABLE. THE

PACKAGE, PRIOR TO THE START OF CONSTRUCTION, THEREFORE THE

PROVIDE NATURAL GAS ACCESS TO THE BUILDING UNDER THIS DESIGN

CONCURRENT NATURAL GAS CONVERSION PROJECT PACKAGES MAY

HEATING SYSTEMS WITH DPW PRIOR TO THE START OF CONSTRUCTION.

AND OIL) BURNERS FOR HEATING HOT WATER AND DOMESTIC HOT WATER

THE CONTRACTOR SHALL COORDINATE THE USAGE OF DUAL FUEL (GAS

GENERAL NOTES

14.

TO RECOGNIZED COMMERICAL STANDARDS.

INSTALL ALL EQUIPMENT AND MATERIALS IN A FIRST CLASS MANNER CONFORMING

15.

AND OPERATION OF THE EQUIPMENT.

OR CONDITIONS THAT WILL PREVENT THE PROPER INSTALLATION, MAINTENANCE

OF EQUIPMENT AND NOYIFY THE ENGINEER OF ANY INADEQUATE CLEARANCES

REVIEW ALL SPACES WHERE EQUIPMENT IS TO BE INSTALLED PRIOR TO ORDERING

WHILE MEETING THE MANUFACTURER'S RECOMMENDED ACCESS REQUIREMENTS.

ALL EQUIPMENT SHALL BE CAPABLE OF FITTING INTO THE SPACES ALLOCATED

16.

FIRESTOP ALL PENETRATIONS BETWEEN FLOORS.

WITH A UL APPROVED SYSTEM APPROPRIATE FOR THE PENETRATION TYPE AND FIRE RATING,

PROPERLY FIRESTOP ALL PENETRATIONS THROUGH FIRE RATED WALL, FLOORS, OR PARTITIONS

17.

PROVIDE REMOTELY ACTUATED DAMPERS IN AREA WITH GYPBOARD OR CONCEALED CEILINGS.

THAT THE EQUIPMENT CAN BE MAINTAINED ADEQUATELY.

FOR TWO VALVES. COORDINATE THE LOCATION OF ACCESS PANELS TO INSURE

ITEM INDISE DUCTS REQUIRING SERVICING OR INSPECTION 12"x12" ACCESS PANELS

FIRE/SMOKE DAMPERS, DUCT SMOKE DETECTOR, BACKDRAFT DAMPERS AND FOR ANY

PROVIDE ACCESS DOORS IN DUCTS AT ALL AUTOMATIC CONTROL DAMPERS, FIRE DAMPERS,

PROVIDE ACCESS PANELS TO ALL CONCEALED VALVES, DAMPERS, AND EQUIPMENT.

18.

WITH THE CURRENT CITY AND COUNTRY.

SEISMICALLY BRACE ALL EQUIPMENT, PIPING AND DUCTWORK IN ACCORDANCE

19.

OR CONCEALED CEILINGS.

DRAWINGS OR NOT. PROVIDE REMOTELY ACTUATED DAMPERS IN AREAS WITH GYPBOARD

PROVIDE VOLUME DAMPERS ON DUCTWORK BRANCH LINES WHETHER SHOWN ON THE

20.

OR EXTERIOR DUCT INSULATION AS REQUIRED PER SPECIFICATION.

DUCT SIZES SHOWN ARE NET SIZES INSIDE DUCTWORK. MAKE ALLOWANCES FOR INTERIOR

21.

THE FIRE WALL OR FLOOR. FIRE DAMPERS SHALL BE UL LISTED.

WALLS AND FLOORS. FIRE DAMPER RATINGS SHALL BE COMPATIBLE WITH

PROVIDE FIRE DAMPERS AT ALL DUCT PENETRATIONS THROUGH FIRE RATED

22.

TAKE-OFFS FROM SQUARE OR RECTANGULAR MAINS.

TAKE-OFFS FROM THE MAIN DUCT. PROVIDE SPIN-IN TYPE FITTINGS AT ALL ROUND DUCT

30 DEGREES OR USE RADIUS ELBOWS. PROVIDE AIR SPLITTER DAMPERS AT ALL BRANCH

PROVIDE TURNING VANES IN ALL ELBOWS THAT CHANGE AIR DIRECTION MORE THAN

23. PROVIDE VENTS AT ALL HIGH POINTS AND DRAINS AT ALL LOW POINTS OF WATER PIPING.

24.

AND FLOORS.

PROVIDE SLEEVES AND ESCUTCHEONS AT PIPE PENETRATIONS THROUGH CONCRETED WALL

25.

BODIES EXPOSED TO AIR BELOW THE FLOOR.

OR ANY OTHER COLD LIQUID WHICH MAY CREATE CONDENSATION, FROM SINK

INSULATE ALL SEWER PIPING RECEIVING AIR CONDITIONING CONDENSATE DRAINS,

INSTALL CONDENSATE DRAINS AT A MINIMUM SLOPE OF 1 / 4 INCH PER 1 FOOT.

26.

OTHERWISE INDICATED.

MOUNT ALL ROOM THERMOSTATS AT 4'-0" ABOVE FINISHED FLOOR UNLESS

TO SUPPORT THE CONTROL REQUIREMENTS.

PROVIDE STEP DOWN TRANSFORMERS, AUXILARY RELAYS AND WIRING AS NECESSARY

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

M-2

MECHANICAL

SCOPE OF WORK AND GENERAL NOTES

1.

WHERE INTERNAL SPACES ARE SEPERATED BY WALL WITHOUT OPENINGS LARGE

ENOUGH TO ALLOW THE ENTIRE EXTERNAL SHELL TO BE MEASURED AS ONE

VOLUME, EACH SEPERATE VOLUME SHALL BE TESTED TO ENSURE IT PASSES

THE AIR LEAKAGE REQUIREMENT, WHERE LIVING OR OFFICE UNITS ARE

IN CONTACT WITH OTER UNITS ON THE VERTICAL OR HORIZONTAL PLANE THE UNITS

SHALL BE TESTED TO ENSURE THE INDIVIDUAL UNIT PASSES THE AIR LEAKAGE

REQUIREMENT IN SPITE OF THE FACT TO ENSURE THE INDIVIDUAL UNIT PASSES

THE AIR LEAKAGE REQUIREMENT IN SPITE OF THE FACT THAT AREAS OF CONTACT

2. REFERENCE

3. QUALIFIED TESTING AGENCY

1. MINIMUN EXPERIENCE 10 YEARS

2. CERTIFICATION : ABAA & ITC

3. REFER TO "3S KOREA CO., LTD(TEL:02-896-9474) OR APPROVED EQUAL.

AIR LEAKAGE REQUIREMENTS ARE INTENDED TO APPLY FIRSTLY TO EXTERIOR ENVELOPES.

BY FAN PRESSURIZATION

1. ASTM E-779 STANDARD TEST METHOD FOR DETERMINING AIR LEAKAGE RATE

MEASURING AIR LEAKAGE IN BUILDINGS

2. US ARMY CORPS OF ENGINEERS AIR LEAKAGE TEST PROTOCOL FOR

BUILDING ENVELOPS AND AIR BARRIER SYSTEM

3. ASTM C1060 STANDARD PRACTICES FOR AIR LEAKAGE SITE DETECTION IN

REPAIR AND MAINTENANCE WORK(K-WORK)

CBRN TFA PRESSURIZATION SYSTEM

BLDG# S-294(UPPER BUNKER), CRC

1.

2.

3.

4. REPAIR BY REPLACEMENT OF EXISTING DETERIORATED 12"DIA SOFT FLEX DUCT WITH RIGID DUCT(SUS 304).

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED 16"DIA SOFT FLEX DUCT WITH RIGID DUCT(SUS 304).

5.

6. REPAIR BY REPLACEMENT OF EXISTING DETERIORATED SHOCK ISOLATORS FOR NBC FANS(2SETS), DUCT AND ASSOCIATED DUCTWORK WITH NEW.

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED SHOCK ISOLATORS FOR FILTER HOUSING, DUCT AND ASSOCIATED DUCTWORK WITH NEW.7.

8. REPAIR BY REPLACEMENT OF EXISTING DETERIORATED BLAST VALVES(56SETS) WITH NEW.(EXHAUST SIDE)

9. REPAIR AND CLEAN EXISTING DETERIORATED BLAST VALVES(56SETS) INTERNAL PARTS AS NECESSATY.(INTAKE SIDE)

10.

11.

12.

AS INDICATED ON THE DRAWING.

13.

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED AIR FLOW MONITORING STATION(AFMS) AND CONTROLLER AS INDICATED ON THE DRAWING.

14.

REPAIR BY REPLACEMENT OF ALL EXISTING DETERIORATED DP GAUGES AND RE-TIGHTEN PRESSURE LINE FITTINGS ASSOCIATED ACCESSORIES WITH NEW.

15.

16.

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED PLATFORM STL GUARD RAIL INCLUDING PAINTING IN MECH ROOM, UPPER BUNKER(S-294) WITH NEW.

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED GALVANIZED STL GRATING COVER INCLUDING FRAME W/WELDING AS INDICATED ON THE DRAWING.

BLDG# S-292(LOWER BUNKER), CRC

1.

2.

3. REPAIR BY REPLACEMENT OF EXISTING DETERIORATED SHOCK ISOLATORS FOR NBC FANS(2SETS), DUCT AND ASSOCIATED DUCTWORK WITH NEW.

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED SHOCK ISOLATORS FOR FILTER HOUSING, DUCT AND ASSOCIATED DUCTWORK WITH NEW.4.

5.

6. REPAIR AND CLEAN EXISTING DETERIORATED BLAST VALVES(18SETS) FOR CBRN FILTER INTAKE & EXHAUST SIDE WITH NEW.

AS INDICATED ON THE DRAWING.

7.

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED AIR FLOW MONITORING STATION(AFMS) AND CONTROLLER AS INDICATED ON THE DRAWING.8.

BLDG# S-50, CRC

1. REPAIR BY REPLACEMENT OF EXISTING DETERIORATED AIR HANDLING UNIT WITH FAN & FILTER ASSEMBLY(GFCI) ASSOCIATED DUCT WITH NEW.

2. REPAIR BY REPLACEMENT OF EXISTING DETERIORATED CPS MAIN PANEL AND CONTROL WITH NEW.

DO NOT LEAK TO OUTDOORS ON MECH DWG SHEET M-27.

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED NBC FANS(2SETS) WITH VFD, CONTROL ASSOCIATED DUCT AT UPPER BUNKER(S-294) WITH NEW.

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED NBC FANS(2SETS) WITH VFD, CONTROL ASSOCIATED DUCT AT LOWER BUNKER(S-292) WITH NEW.

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED MAIN CONTROL PANEL INCLUDING ACCESSORIES AND WIRING AT UPPER BUNKER(S-294) WITH NEW.

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED MAIN CONTROL PANEL INCLUDING ACCESSORIES AND WIRING AT LOWER BUNKER(S-292) WITH NEW.

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED ELECTRICALLY OPERATED TWO POSITION DAMPERS(EOD, GAS TIGHT DAMPERS)

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED ELECTRICALLY OPERATED TWO POSITION DAMPERS(EOD, GAS TIGHT DAMPER)

17.

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED DUCTWORK ASSOCIATED ACCESSORIES FOR DECON STATION AS INDICATED ON THE DRAWING.

19.AS INDICATED ON THE DRAWING.

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED SOLENOID VALVES(3SETS), WATER LEVEL GAUGE AND WIRING AS INDICATED ON THE DRAWING.

18.

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED DECON STATION'S ACCESSORIES AS INDICATED ON THE DRAWING.

SCOPE OF WORK

BUILDING AIR LEAKAGE TEST(BLDG# S-294, S-292 & S-50)

REPAIR CBRN PROTECTION SYSTEM

IN VARIOUS BUILDINGS, CRC

CAMP RED CLOUDCHONG, ST

109374

27. PROVIDE SHOCK MITIGATION SYSTEM SHALL BE DESIGNED & INSTALLED IN ACCORDANCE

WITH UFC 3-340-01, CH12.

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED SHOCK ISOLATORS FOR FAN AND FILTER ASSEMBLY(2SETS) AND ASSOCIATED DUCTWORK WITH NEW.

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED SEAL & ACCESSORIES FOR BLAST DOORS AND GAS TIGHT DOORS WITH NEW.

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED SEAL & ACCESSORIES FOR BLAST DOORS AND GAS TIGHT DOORS WITH NEW.

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED 2,000 x 2,000 STAINLESS STELL DRAIN PAN WITH 1/2" DRAIN LINE

M-3

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

M E C H A N I C A L E Q U I P M E N T S C H E D U L E

MECHANICAL EQUIPMENT SCHEDULE

SERVICEQ'TYITEM NO R E M A R K S

VOLT/PH/HZ

POWER

RPM

ESP

(INCH)

FAN MOTOR

TYPE (CFM)

AIR CAP

N O T E

INDUSTRIAL PROCESS FAN

BF

1 NBC FAN 16.55,600 252,125 460/3/60

d) EXTENDED LIEF BEARINGS

STUFFING BOX

SHAFT SEAL

EXTENDED LUBRICATION LINES

h) f) g) e)

SHAFT GUARD

BELT GUARD

INLET FLANGE/OUTLET FLANGE

THE FOLLOWING ACCESSORIES :

BF

b) c) a)

& SHALL INCLUDE

1A

BF

INDUSTRIAL PROCESS FAN1

BF

1A

NBC FAN 16.55,600 25 460/3/60 1 STAND-BY2,125

FANS(UPPER BUNKER, S-294)

2A

BF

BF

NBC FAN

Q'TYITEM NO SERVICE

5,600

5,600

INDUSTRIAL PROCESS FAN

INDUSTRIAL PROCESS FAN

2,125

2,125

16.5

16.5

380/3/60

380/3/60

FAN MOTOR

AIR CAP

(CFM)TYPE RPM(INCH)

ESP

(HP)

POWER

R E M A R K S

VOLT/PH/HZ

THE FOLLOWING ACCESSORIES :

EXTENDED LUBRICATION LINESINLET FLANGE/OUTLET FLANGE

BELT GUARD

SHAFT GUARD

EXTENDED LIEF BEARINGS

a) c) b) d)

SHAFT SEAL

STUFFING BOX

e) g) f) h)

& SHALL INCLUDE

BF BF

1A

N O T E

NBC FAN

FANS(LOWER BUNKER, S-292)

AIRFLOW CONTROLLER VARIABLE FREQUENCY CONTROL, VARIABLE FREQUENCY

STARTER INCLUDING AIR MEASURING OR APPROVED EQUAL.

AIRFLOW CONTROLLER VARIABLE FREQUENCY CONTROL, VARIABLE FREQUENCY

STARTER INCLUDING AIR MEASURING OR APPROVED EQUAL.

AIRFLOW CONTROLLER VARIABLE FREQUENCY CONTROL, VARIABLE FREQUENCY

STARTER INCLUDING AIR MEASURING OR APPROVED EQUAL.

STARTER INCLUDING AIR MEASURING OR APPROVED EQUAL.

AIRFLOW CONTROLLER VARIABLE FREQUENCY CONTROL, VARIABLE FREQUENCY

EXPERIENCE DESIGNING THESE SYSTEMS IN THE PAST 18 MONTHS.

AND DYNAMIC ANALYSIS FOR SEISMIC AND IN-STRUCTURE SHOCK WITH DEMONSTRABLE

THE ENGINEER SHALL HAVE A MINIMUM OF 5YEARS EXPERIENCE PERFORMING BOTH STATIC

FOR SEISMIC AND IN-STRUCTURE SHOCK LOADING.

OF NON-STRUCTURAL COMPONENTS, INCLUDING EQUIPMENT AND DISTRIBUTION SYSTEMS,

ENGINEERING TO PERFORM ANALYSIS AND DESIGN OF SUPPORT, ANCHORAGE AND BRACING

ENGAGE A REGISTERED PROFESSIONAL ENGINEER SPECIALIZING IN THE FIELD OF STRUCTURAL

PE QUALIFICATION :

PROFESSIONAL ENGINEER.

BASED ON THE SHOCK RESPONSE SPECTRA AND ISOLATION SYSTEM FREQUENCY BY REGISTERED

THE CONSTRUCTION CONTRACTOR TO DESIGN AND FURNISH THE SHOCK ISOLATION SYSTEMS

A1

BF

NBC FAN

DESCRIPTION

MOUNT TYPE

)MFG/MODE(CRITICALITY R E M A R K S

NBC FAN

SHOCK MOUNT SCHEDULE

MCRF

EXISTING CBRN FILTER HOUSING (S-294) CRITICAL

WIRE ROPE ISOLATORS

(IDC M32-XXX-8)

OR APPROVED EQUAL

MAXIMUM ISOLATION

SYSTEM FREQUENCY

8 Hz MINIMUM DAMPING RATIO = 0.1 TO 0.25

CRITICAL

WIRE ROPE ISOLATORS

(IDC M20-XXX-8)

6 Hz

CRITICAL

WIRE ROPE ISOLATORS

(IDC M20-XXX-8)

6 Hz

MINIMUM DAMPING RATIO = 0.1 TO 0.25

MINIMUM DAMPING RATIO = 0.1 TO 0.25

2A

2 NBC FAN

NBC FAN

MCRF

EXISTING CBRN FILTER HOUSING (S-292) CRITICAL

WIRE ROPE ISOLATORS

(IDC M32-XXX-8)

8 Hz MINIMUM DAMPING RATIO = 0.1 TO 0.25

CRITICAL

WIRE ROPE ISOLATORS

(IDC M20-XXX-8)

6 Hz

CRITICAL

WIRE ROPE ISOLATORS

(IDC M20-XXX-8)

6 Hz

MINIMUM DAMPING RATIO = 0.1 TO 0.25

MINIMUM DAMPING RATIO = 0.1 TO 0.25

DUCTWORK EXISTING DUCTWORK CRITICAL

WIRE ROPE ISOLATORS

(IDC M20-XXX-8)

15 Hz MINIMUM DAMPING RATIO = 0.1 TO 0.25

DUCTWORK EXISTING DUCTWORK CRITICAL

WIRE ROPE ISOLATORS

(IDC M20-XXX-8)

15 Hz MINIMUM DAMPING RATIO = 0.1 TO 0.25

BF

BF

BF

NOTES

FFA

(S-294) CRITICAL

WIRE ROPE ISOLATORS

(IDC M20-XXX-8)

8 Hz MINIMUM DAMPING RATIO = 0.1 TO 0.25

ITEM NO

EXISTING FAN AND FILTER ASSEMBLY

VB

VB

S-294 EXHAUST SIDE

Q'TYITEM NO SERVICE

,6002

FUCARE FC-RBV-31-D250

20 / 30300

/EAAIR CAP

)H(CMMODEL )PA(

ESP

S-292 CBRN FILTER INTAKE

BLAST VALVE SCHEDULE

OR APPROVED EQUAL

BLAST DURATION

DESIGN PEAK PRESSURE/

)BAR/MS(

BLAST VALVE BODY

BLADE MATERIAL

STAINLESS STEEL 316

REMARKS

-DOUBLE ACTING

-AUTOMATIC RE-SET

-HIGH CORROSION RESISTANT

NOTES

-BV MOUNTING FRAME (SS316)

VB

12 S-292 EXHAUST SIDE

008,2

,6002

FUCARE FC-RBV-31-D250

OR APPROVED EQUAL

FUCARE FC-RBV-31-D250

OR APPROVED EQUAL

20 / 30 STAINLESS STEEL 316

20 / 30 STAINLESS STEEL 316

PROFESSIONAL ENGINEER EXPERIENCED IN DYNAMIC ANALYSIS AND DESIGN METHODS.

DESIGN AND ANALYSIS CALCULATIONS SHALL BE STAMPED BY A REGISTERED

DEFLECTION, DUCTILITY RATIOS AND SUPPORT ROTATIONS.

DEFLECTIONS; AND DESIGN DEFORMATION LIMITS AND RESPONSE VALUES FOR MAXIMUM

FUNCTION SKETCHES SHOWING EQUIVALENT ULTIMATE RESISTANCE AND ELASTIC

MATERIALS; PLASTIC MOMENT CAPACITIES FOR LOAD-CARRYING MEMBERS; RESISTANCE

LOAD-CARRYING MEMBERS ; MINIMUM YIELD AND TENSILE STRENGTHS FOR STEEL

LAYOUTS AND DIMENSIONS: ELASTIC AND PLASTIC SECTION PROPERTIES FOR ALL

SHETCHES SHOWING THE DESIGN OVERPRESSURE LOADINGS MEMBER CROSS-SECTIONS,

A NARRATIVE DISCUSSION OF THE ANALYSIS TECHNIQUES USED;

VALVE CASTING. WHEN APPLICABLE, ANALYSIS AND CALCULATION SHALL INCLUDE

FRAMING SYSTEMS REQUIRING CHANGES TO ACCOMMODATE THE PROPOSED

DESIGN AND ANALYSIS CALCULATIONS SHOEING CONCRETE OPENING AND

CONTRACTOR DESIGN OF STRUCTURAL SUPPORTS

ELECTRICALLY OPERATED DAMPER

ELECTRICALLY OPERATED DAMPER

AND DUCTWORK

(IDC M20-XXX-8)

CRITICAL

WIRE ROPE ISOLATORS

(IDC M20-XXX-8)

MINIMUM DAMPING RATIO = 0.1 TO 0.25DECON DECON SYSTEM 6 Hz

2.

1.

REFER TO "NSV CO., LTD(TEL:02-598-1988) OR APPROVED EQUAL

1.

2. REFER TO "NSV CO., LTD(TEL:02-598-1988) OR APPROVED EQUAL

REPAIR CBRN PROTECTION SYSTEM

IN VARIOUS BUILDINGS, CRC

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

M-4

SCALE : 1 / 100

M4

TFA AREA

CORR

AIRLOCK

INGRESS-1

INGRESS-2

VAPOR

EGRESS-1

AIRLOCK

EGRESS-2

VAPOR

INGRESS/EGRESS

LIQUID

ASOC INTEL

SUPPLY

ASOC161

EQUIPMENT

RADIO

CORR

129 125

STORAGE

STORAGE

WASHDOWN

STAIR

CLEAN

WASHDOWN

DIRTY

LATRINE

W.

M.LATRINE

SHOSHO

CORRIDOR

143 144

145 148

RECEPTION

STORAGE

STAIR

AIDES AIDES

RADIO MAINT

VAULT

ASOC

CORRIDOR

AG DIST

M. LATRINE

W.

FSE

CG

140138

DCG CS

147146

SCS ROOM

MEETING

BRIEFING

LATRINE

CASIC 3

CASIC 2

C2 CASIC 2/CM & DPROJECT

ROOM 151

SCO

154 155

SSO

FOYER

151A

FOYER

C3 ADMIN

ASOC OPS

C3 DUTY NCO

CORR

C3 PLANS

C6

UPS

111A

BATTERY ROOM

WAR ROOM

PICKUP

MESS DELIVERY

GUARD

CONTROL

US COMM CENTER

MECH ROOM

GENERATOR ROOM (DIRTY)

STAIR

110B

109A

STORAGE

STAIR

109B

110A

HALON

TOXIC FREE AREA

TFA AREA

CORR

AIRLOCK

INGRESS-1

INGRESS-2

VAPOR

EGRESS-1

AIRLOCK

EGRESS-2

VAPOR

INGRESS/EGRESS

LIQUID

ASOC INTEL

SUPPLY

ASOC161

EQUIPMENT

RADIO

CORR

129 125

STORAGE

STORAGE

WASHDOWN

STAIR

CLEAN

WASHDOWN

DIRTY

LATRINE

W.

M.LATRINE

SHOSHO

CORRIDOR

143 144

145 148

RECEPTION

STORAGE

STAIR

AIDES AIDES

RADIO MAINT

VAULT

ASOC

CORRIDOR

AG DIST

M. LATRINE

W.

FSE

CG

140138

DCG CS

147146

SCS ROOM

MEETING

BRIEFING

LATRINE

CASIC 3

CASIC 2

C2 CASIC 2/CM & DPROJECT

ROOM 151

SCO

154 155

SSO

FOYER

151A

FOYER

C3 ADMIN

ASOC OPS

C3 DUTY NCO

CORR

C3 PLANS

C6

UPS

111A

BATTERY ROOM

WAR ROOM

PICKUP

MESS DELIVERY

GUARD

CONTROL

US COMM CENTER

MECH ROOM

GENERATOR ROOM (DIRTY)

STAIR

110B

109A

STORAGE

STAIR

109B

110A

HALON

TOXIC FREE AREA

SEE

- M5

SPECIFIC NOTES

GAS TIGHT DOORS, UPPER BUNKER(S-294) WITH NEW.

MECHANICAL

RE-SEAL AND REPAIR ACCESSARIES FOR EXISTING DETERIORATED BLAST DOORS AND

BLAST DOOR-1

BLAST DOOR-1

BLAST DOOR-2

BLAST DOOR-2

BLAST DOOR-3

BLAST DOOR-3

BLAST DOORS FLOOR PLAN ( UPPER BUNKER, S-294 )

S-294) AND SPECIFIC NOTES

BLAST DOORS FLOOR PLAN(UPPER BUNKER,

SCALE : 1 / 50

BLAST DOORS UPPER LEVEL FLOOR PLAN

M4

BLAST DOOR-4

BLAST DOOR-4

BLAST DOOR-5 BLAST DOOR-6

BLAST DOOR-6

BLAST DOOR-5

BLAST DOOR-7 BLAST DOOR-8 BLAST DOOR-9

(UPPER)

(LOWER)

BLAST DOOR-7(UPPER & LOWER)

BLAST DOOR-7(UPPER & LOWER)

BLAST DOOR-7

(UPPER & LOWER)

(UPPER & LOWER)

BLAST DOOR-7

BLAST DOOR-8BLAST DOOR-9

REPAIR CBRN PROTECTION SYSTEM

IN VARIOUS BUILDINGS, CRC

CAMP RED CLOUDCHONG, ST

109374

NOTES:

REFER TO "NSV CO., LTD(TEL:02-598-1988) OR APPROVED EQUAL3.

CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION OF BLAST DOORS IN FIELD(TYP)1.

CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR BLAST DOORS.2.

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

M-5

INGRESS/EGRESS

LIQUID

SECURITY

OFFICE

TFA AREA

INGRESS-1

AIRLOCK

AIRLOCK

INGRESS-2

EGRESS-2

AIRLOCK

AIRLOCK

EGRESS-1

INGRESS/EGRESS

LIQUID

SECURITY

OFFICE

TFA AREA

M F

S A

S A

F M

TT

TT

AIRLOCK

INGRESS-1

AIRLOCK

INGRESS-2

INGRESS/EGRESS

LIQUID

TFA AREA

SIZE=24"x24"

GRILLE

SUPPLY EGGCRATE

TT

FILTER AND FAN ASSEMBLY-580

TO INLET SIDE OF FILTER AND FAN ASSEMBLY-580

REPLACE 12" DIA SOFT FLEX. DUCT

WITH RIGID DUCT(SUS 304).

REPLACE EXISTING 16" DIA FLEX DUCT WITH

RIGID DUCT(SUS 304)(TYPICAL)

SPECIFIC NOTES

REPLACE EXISTING DETERIORATED 16" DIA FLEX DUCT WITH RIGID DUCT(SUS 304).

1 UPPER BUNKER PARTIAL PLAN ( BLDG S-294 )

SCALE : 1 / 50

UPPER BUNKER SECTION PLAN ( BLDG S-294 )

SCALE : 1 / 50

MECHANICAL

(BLDG S-294) AND SPECIFIC NOTES

M5

M5

FFA(E)

REPLACE EXISTING DETERIORATED UPPER BUNKER(S-294) NBC MAIN CONTROL PANEL WITH NEW.

REPLACE EXISTING DETERIORATED LOWER BUNKER(S-292) NBC MAIN CONTROL PANEL WITH NEW.

REPLACE EXISTING DETERIORATED 12" DIA SOFT FLEX DUCT WITH RIGID DUCT(SUS 304).

REPLACE EXISTING DETERIORATED SHOCK ISOLATORS FOR FAN AND FILTER ASSEMBLY WITH NEW(TYPICAL).

FFA(E)

NOTES:

CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION OF DUCT IN FIELD(TYP)1.

CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR DUCT.2.

REPAIR CBRN PROTECTION SYSTEM

IN VARIOUS BUILDINGS, CRC

CAMP RED CLOUDCHONG, ST

109374

UPPER BUNKER PARTIAL & SECTION PLAN

6 REPLACE EXISTING DETERIORATED WALL REGISTER WITH NEW.

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

SCALE : 1 / 100

TFA AREA

CORR

AIRLOCK

INGRESS-1

INGRESS-2

VAPOR

EGRESS-1

AIRLOCK

EGRESS-2

VAPOR

INGRESS/EGRESS

LIQUID

ASOC INTEL

SUPPLY

ASOC161

EQUIPMENT

RADIO

CORR

129 125

STORAGE

STORAGE

WASHDOWN

STAIR

CLEAN

WASHDOWN

DIRTY

LATRINE

W.

M.LATRINE

SHOSHO

CORRIDOR

143 144

145 148

RECEPTION

STORAGE

STAIR

AIDES AIDES

RADIO MAINT

VAULT

ASOC

CORRIDOR

AG DIST

M. LATRINE

W.

FSE

CG

140138

DCG CS

147146

SCS ROOM

MEETING

BRIEFING

LATRINE

CASIC 3

CASIC 2

C2 CASIC 2/CM & DPROJECT

ROOM 151

SCO

154 155

SSO

FOYER

151A

FOYER

C3 ADMIN

ASOC OPS

C3 DUTY NCO

CORR

C3 PLANS

C6

UPS

111A

BATTERY ROOM

WAR ROOM

PICKUP

MESS DELIVERY

GUARD

CONTROL

US COMM CENTER

MECH ROOM

GENERATOR ROOM (DIRTY)

STAIR

110B

109A

STORAGE

STAIR

109B

110A

HALON

TOXIC FREE AREA

TFA AREA

CORR

AIRLOCK

INGRESS-1

INGRESS-2

VAPOR

EGRESS-1

AIRLOCK

EGRESS-2

VAPOR

INGRESS/EGRESS

LIQUID

ASOC INTEL

SUPPLY

ASOC161

EQUIPMENT

RADIO

CORR

129 125

STORAGE

STORAGE

WASHDOWN

STAIR

CLEAN

WASHDOWN

DIRTY

LATRINE

W.

M.LATRINE

SHOSHO

CORRIDOR

143 144

145 148

RECEPTION

STORAGE

STAIR

AIDES AIDES

RADIO MAINT

VAULT

ASOC

CORRIDOR

AG DIST

M. LATRINE

W.

FSE

CG

140138

DCG CS

147146

SCS ROOM

MEETING

BRIEFING

LATRINE

CASIC 3

CASIC 2

C2 CASIC 2/CM & DPROJECT

ROOM 151

SCO

154 155

SSO

FOYER

151A

FOYER

C3 ADMIN

ASOC OPS

C3 DUTY NCO

CORR

C3 PLANS

C6

UPS

111A

BATTERY ROOM

WAR ROOM

PICKUP

MESS DELIVERY

GUARD

CONTROL

US COMM CENTER

MECH ROOM

GENERATOR ROOM (DIRTY)

STAIR

110B

109A

STORAGE

STAIR

109B

110A

HALON

TOXIC FREE AREA

SEE

MECHANICAL

M6

M7

M-6

DECON STATION FLOOR PLAN ( UPPER BUNKER, S-294 )

DECON STATION FLOOR PLAN

(UPPER BUNKER, S-294)

- M8

REPAIR CBRN PROTECTION SYSTEM

IN VARIOUS BUILDINGS, CRC

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICALMECHANICAL

M F

F M

M F

16"ø

12"ø

14"ø

500 CFM

16"x16"

6"x24"

24"x10"

FFA-1000

ISOLATOR

CABLE

M20-xxx

IDC

SCALE : 1 / 100

M7

- M7

SPECIFIC NOTES

NONE TO SCALE

DUCTWORK

(WHERE REQUIRED)

DUCT INSULATION

SIDES OF WALL OR FLOOR

FOUR SIDES OF SLEEVE & BOTH

FLOOR. PROVIDE ANGLES ON ALL

SECURE ANGLES TO WALL OR

WELDS AT 150 O.C. DO NOT

TO 18 GA SLEEVES WITH 15

50x50x6 SHALL BE SECURED

RETAINING ANGLES SHALL BE

CONNECTOR

NON-METALLIC

FM APPROVED - M7

- M7

NONE TO SCALE

WALL DUCT PENETRATION WITH NON-METALLIC CONNECTOR

SECURITY

OFFICE

TFA AREA

INGRESS-1

AIRLOCK

AIRLOCK

INGRESS-2

EGRESS-2

AIRLOCK

AIRLOCK

EGRESS-1

INGRESS/EGRESS

LIQUID

SECURITY

OFFICE

TFA AREA

S A

S A

TT

TT

FFA(E)

FFA(E)

MECH ROOM

GENERATOR ROOM (DIRTY)

STAIR

110B

109A

STORAGE

110A

HALON

SEE

REPLACE EXISTING DETERIORATED FAN & FILTER ASSEMBLY(GFCI) WITH SHOCK ISOLATORS.

REPLACE EXISTING DETERIORATED DUCTWORK(SUS304) ASSOCIATED ACCESSORIES.

DECON STATION PARTIAL PLAN-1 ( UPPER BUNKER, S-294 )

DECON STATION PARTIAL PLAN-2

DECON STATION PARTIAL PLAN-1 & 2(UPPER

BUNKER, S-294), WALL DUCT PENETRATION

WITH NON-METALLIC CONNECTOR AND NOTES

M-7

16"ø

REPAIR CBRN PROTECTION SYSTEM

IN VARIOUS BUILDINGS, CRC

CAMP RED CLOUDCHONG, ST

109374

NOTES:

CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION OF F & F ASSEMBLY 1.

AND DUCT IN FIELD(TYP)

CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR F & F ASEMBLY AND DUCT.2.

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICALMECHANICAL

SCALE : 1 / 100

M8

M-8

92 92 153 264

TUNNEL

45°

DD

F

F

A B C

EE

DECON STATION PARTIAL PLAN-3 ( UPPER BUNKER, S-294 )

GRAB ROD

SCALE 1 : 8

DETAIL A

SCALE 1 : 4

DETAIL B

SCALE 1 : 4

DETAIL C

TRIM

DECKING

DIAMOND TREAD

DECKING

DIAMOND TREAD

ANGLE

SCALE 1 : 4

SECTION E-E

ANGLE

TRIM

DECKING

DIAMOND TREAD

DECKING

DIAMOND TREAD

SCALE 1 : 10

SECTION D-D

FLAT BAR

ANGLED

DECKING

DIAMOND TREAD

(2 PLACES)

ANGLED FLAT BAR

GRATING

TRIM

FLAT BAR

ANGLED

TRIM

GRATING TRIM

SCALE 1 : 5

SECTION F-F

TRIM

ANGLE

DECKING

DIAMOND TREAD

(2 PLACES)

BOOTWASH

LOCKER

DECON STATION PARTIAL PLAN-3

AND NOTES

SPECIFIC NOTES

REPLACE EXISTING DETERIORATED INTERCOM(8SETS) WIT NEW.

1 1 1

1 1

REPLACE EXISTING DETERIORATED HOSE REEL(2SETS) WITH NEW.

3 REPLACE EXISTING DETERIORATED TRASH CAN(8SETS) WITH NEW.

3 3

3 3

4 REPLACE EXISTING DETERIORATED SCISSOR TRAY(4SETS) WITH NEW.

5 REPLACE EXISTING DETERIORATED GRAB ROD(2SETS) WITH NEW.

6 REPLACE EXISTING DETERIORATED STOOL(2SETS) WITH NEW.

7 REPLACE EXISTING DETERIORATED STATION LOCATORS(3SETS) WITH NEW.

8 REPLACE EXISTING DETERIORATED LOCKER WITH NEW.

REPLACE EXISTING DETERIORATED BOOTWASH(2SETS), DIAMOND TREND DECKING AND GRATING WITH NEW.

REPAIR CBRN PROTECTION SYSTEM

IN VARIOUS BUILDINGS, CRC

CAMP RED CLOUDCHONG, ST

109374

NOTES:

CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION OF DECON STATION IN FIELD(TYP)1.

CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR DECON STATION.2.

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICALMECHANICAL

SCALE : 1 / 100

M9

TANK CELL B

STAIR

INDUSTRIAL WATER INDUSTRIAL WATER

TANK CELL C

INDUSTRIAL WATER

TANK CELL D

INDUSTRIAL WATER

TANK CELL A

DOMESTIC WATER

TANK CELL A

DOMESTIC WATER

TANK CELL B

PUMP ROOM

M

M

M

M

M

FROM WATER PLANT

SUPPLY WATER MAIN

UP TO BUNKER

N.C.

N.C.

N.O.

WATER LEVEL GUAGE

N.C.

N.C.

TO CPS PANEL

TO CPS PANEL

TO CPS PANEL

TO CPS PANEL

V-1

V-2

V-3

DOMESTIC WATER VALVE CONTROL

VALVE NO. NORMAL MODE CW MODE

V-1 OPEN CLOSE

V-2 CLOSE OPEN

V-3 CLOSE CLOSE

SPECIFIC NOTES

ROOM

CORR

KEY PLAN

SCALE: NONE

DOMESTIC WATER

TANK CELL BTANK CELL A

DOMESTIC WATER

ROOM

PUMP

WATER LEVEL GUAGE

SCALE : 1 / 100M9

TO CPS PANEL

REPLACE EXISTING DETERIORATED 2,000 x 2,000 STAINLESS STEEL DRAIN PAN(20MM LIP) WITH 1/2" DRAIN LINE ELBOW DOWN(50MM)

REPLACE EXISTING DETERIORATED SOLENOIDE VALVES(3SETS) AND WIRING TO CPS PANEL.

REPLACE EXISTING DETERIORATED WATER LEVEL GAUGE AND WIRING TO CPS PANEL.

M-9

DOMESTIC WATER TANK SYSTEM FLOOR PLAN ( UPPER BUNKER, S-294 )

DOMESTIC WATER TANK SYSTEM SECTION PLAN ( UPPER BUNKER, S-294 )

DOMESTIC WATER TANK SYSTEM FLOOR AND

SECTION PLAN AND NOTES

REPAIR CBRN PROTECTION SYSTEM

IN VARIOUS BUILDINGS, CRC

CAMP RED CLOUDCHONG, ST

109374

NOTES:

CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION OF WATER PIPING LINE IN FIELD(TYP)1.

CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR WATER PIPING LINE.2.

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

NOT TO SCALE

UPPER BUNKER NBC MAIN CONTROL PANEL-1

MECHANICAL

UPPER BUNKER NBC MAIN CONTROL PANEL-1

1.

NOTES

REPAIR BY REPLACEMENT OF EXISTING DETERIORATED MAIN CONTROL PLANEL INCLUDING ALL ACCESSORIES AND WIRING,

2. REFER TO "UNISYS ENGINEERING CO., LTD(TEL:02-2113-1661~2) OR APPROVED EQUAL

3. CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION OF CONTROL PANEL AND VARIOUS DEVICES IN FIELD(TYP)

4. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR CONTROL PANEL AND WIRING.

M-10

M10

REPAIR CBRN PROTECTION SYSTEM

IN VARIOUS BUILDINGS, CRC

CAMP RED CLOUDCHONG, ST

109374

AS INDICATED ON THE DRAWING(DWG SHEET M-11,M-12,M-13 & M-14)

16 08 0

DOOR STATUS/LEGEND

SYMBOL FOR

DOOR CLOSED

(AIRLOCK)

DOOR OPEN

DOOR OPEN

DOOR UNLOCK

DOOR NO.

PROCESSING

EGRESS

PROCESSING

INGRESS

AHU FAN

DESIGNATION

STATUS

OPERATIONAL

PROBLEM

MOTOR

AHU-1

AHU-2

AHU-3

NBC SUPPLY AIR FAN

DESIGNATION

STATUS

OPERATIONAL

PROBLEM

MOTOR

NOT CLOSED

DAMPER

NOT CLOSED

DAMPER

BF-1

BF-1A

FILTER SYSTEMS

DESIGNATION HOUR METER

HEPA FILTERS

CHANGE

CHANGE PREFILTERS

MAIN FILTER UNITS

UNITS

AIRLOCK FILTER

EXHAUST FANS IN CW MODE

DESIGNATION FAN OFF FAN NOT OFF

(PROBLEM)

NOT CLOSED

DAMPER

EF-1

EF-2

EF-3

AIR LOCK FILTER UNITS

DESIGNATION

STATUS

OPERATIONAL

(INGRESS AIRLOCK)

FU-1

(EGRESS AIRLOCK)

FU-2

(DECON STATION)

FU-3

(DECON STATION)

FU-4

DOMESTIC WATER VALVE

DESIGNATION

STATUS

OPERATIONAL

EV-1

EV-2

EV-3

TFA PRESSURE

( P= "W.G)

MODE SWITCH

NORMAL C/W

UPPER BUNKER NBC MAIN CONTROL PANEL

C/W -NORMAL TFA LOW PRESS

PROBLEM

PRIMARY BF-1A

BACKUP BF-1

EMERGENCY

OFFBACKUP BF-1A

PRIMARY BF-1

MCRF FILTERED

AIRFLOW METER FOR

BF-1 / BF-1A

NORMAL

( CFM) ( CFM)

C/W MODE

NBC AIR FLOW SYSTEM DIAGRAM

NBC MAIN CONTROL

PANEL(LOWER BUNKER)

AIRLOCK #2

INGRESS

HATCH CLEAN PUMP

ACCESS FLOOR

ROOM BELOW

AIRLOCK PRESSURE

(INCHES, WG)

NBC MAIN CONTROL

PANEL(UPPER BUNKER)

AIRLOCK #1

INGRESS

AIRLOCK #1

EGRESS

FLOWRATE, EGRESS

AIRFLOW(CFM)

EGRESS

AIRLOCK #2

AIRFLOW(CFM)

FLOWRATE, INGRESS

TFA BOUNDARY

EXHAUST FAN SYSTEMS

(N.O.)

D-3M

EA

(N.O.)

EA

(CLOSES DURING C/W MODE)

MOTORIZED DAMPER(TYP OF 3)

LOW LEAKAGE

D-1

(N.O.)

EA

M

D-2M

EA

SHALL BE SHUT-OFF

HALON AREA EXHAUST FAN

EF

DPS

EA

DPS

DIFF PRESS SWITCH

GENERATOR ROOM

SHALL BE SHUT-OFF

TOILET AREA EXHAUST FAN

EF

EA

EF

EA

EA

OPERATES CONTINUOUSLY

EF

BATTERY ROOM EXHAUST FAN

DIRTY MECH RM

AREAS

E

A

(TYPICAL)

FROM MECH ROOM

O.A.

TFA BOUNDARY WALL

TFA BOUNDARY WALL

MAGNAHELICS GAGE

BUTTERFLY DAMPER(TYP)

DWYER MODEL 2000-0

DEVICE(TYP.)

AIR MEASURING

S .A

MCRF

SA DUCT

3015 OR EQUAL

DWYER MODEL 1910-20

DIFF PRESS SWITCH

MIN. ONE DUCT

SA DUCT

S .A

DIAMETER

DPS

S .A

DPS

DPS/GAUGE

(TYP OF 2)

DWYER MODEL CPS. RM.

TOXIC AREA

DWYER MODEL 3003(TYP)

DPS/GAUGE

M M

NBC FAN

BF

PF

PREFILTER

BF NBC FAN

1A (STANDBY)

(TYP)

VARIABLE FREQUENCY DRIVE STARTER

VARIABLE FREQUENCY CONTROL

(11,530 CFM)

S.A.

(6,950 CFM)

(1,4430 CFM)

R.A.

S.A.

(9,100 CFM)

R.A.

S.A.

(2,650 CFM)

(2,100 CFM)

R.A.

O.A.

H C

AHU

(550 CFM)CC

O.A.

(2,150 CFM)

CC

AHU

AHU

O.A.

H C

(2,900 CFM)

CC

O.A.

H C

(SEE NOTE)

(TYP OF 4)

AIR MEASURING DEVICE

PFPREFILTER

VFD VFD

FAN MOTOR(TYP)

W

DC POWER "ON" FLASHER BUZZER SILENCE SWITCH

DOORS

TFA BOUNDARY

BUZZER SILENCE SWITCH

TFA BOUNDARY ALARM

E F

D

B C

A

(CONTROL ROOM)

YOU ARE HERE

OA

Y

B

G

Y

DOOR MONITORING

AIRFLOW CONTROLLER

P S

FU-1

AIRLOCK AREA / DECON STATION SYSTEM

FU-2

P S

M F

EGRESS

AIR LOCK1

M F

EGRESS

AIR LOCK2

AIR LOCK1

INGRESS INGRESS

AIR LOCK2

DPS

SEE DETAIL "B"

SWITCH/GAUGE

HEPA FILTER DIFF PRESS

MODEL # HP5027-30

DIFF PRESS SWITCH HONEY WELL

H

L

BMC FANS SELECTION SWITCH

MCRF PRIMARY / BACKUP

PF-1 PF-2

ROOM

EF-3 CPS

D-3

ROOM

EF-2 CPS

D-2

D-1

D-4

D-5

TFA BOUNDARY

C/W MODE START-UP INSTRUCTIONS : UPON AUTHORIZATION / COMMAND TO BUTTON-UP :

(IN CONTROL PANEL STORAGE BOX) FOR TROUBLESHOOTING PROCEDURE.

5. IF ANY STATUS INDICATORS FOR PRESSURES, FILTER UNIT OPERATION ARE RED, CONSULT OPERATOR'S MANUAL

4. CHECK READINESS AND CONDITION OF DECON SUPPLIES AND EQUIPMENT IN THE TFA.

3. REAL WORLD CONTINGENCY : SET HOLDING TANKS SWITCH TO C/W MODE.

2. CLOSE AND SECURE ALL TFA BOUNDARY DOORS AS INDICATED BY DOOR SIGNAGE.

THE CPS PROVIDES CBR PROTECTION BY INCREASING THE OVER PRESSURE AND ACTIVATES THE TFA.

1. TURN "C/W MODE-NORMAL MODE" SWITCH TO "C/W" POSITION IN THE CW MODE,

M M

D-4 D-5

EOD

EOD

(AMD-1)

TO CONTROL

PANEL

DURING C/W MODE

DURING C/W MODE

SHALL REMAIN OPERATING

UNDER C/W MODE

NORMAL VENTILATION FAN

DOMESTIC WATER SYSTEM DIAGRAM

M

FULL ALARM

FULL

ALARM

HIGH LEVEL

TO CONTROL PANEL

CONTROL SWITCH

LIQUID LEVEL

BOOSTER PUMP(TYP)

NORMAL MODE DOMESTIC WATER SUPPLY

FROM BASE WATER SYSTEM

(EV-1) N.O.

ELECTRIC KNIFE GATE

VALVE

(EV-2)

N.C.

(EV-3)N.C.

%100

10001000

EOD

M

D-6 M

D-7

PS

FU-4

MF

PS

FU-3

MF

DECON STATION

D-6

D-7

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

MECHANICAL

NOT TO SCALE

UPPER BUNKER NBC MAIN CONTROL PANEL-2

UPPER BUNKER NBC MAIN CONTROL PANEL-2

M-11

M11

REPAIR CBRN PROTECTION SYSTEM

IN VARIOUS BUILDINGS, CRC

CAMP RED CLOUDCHONG, ST

109374

5.2 TFA DIFFERENTIAL PRESSURE GAGE SHALL MEASURE TFA

TYPE DIAPHRAGM OPERATED WITH SWITCHING BY PHOTOCELL

RELAY WITH MANUAL RESET FOR LOW TFA PRESSURE INDICATION,

ACTUATED CIRCUITS AND TWO DPDT RELAYS, AND LOW LATCHING

DWYER MODEL 3001 OR APPROVED EQUAL.

AND ATMOPHERIC AND SHALL BE PHOTOHELIC

OPERATING RANGE 0.0 TO 1.0 INCHES W.G[249Pa]. TWO PHOTOCELL

CONTROLLED RELAYS WITH GAGE AND SWITCH SET POINT INDICATORS,

SEQUENCE OF CONTROL:

THE TOXIC FREE AREA(TFA) AHU'S

OPERATE CONTINUOUSLY DURING ALL MODES OF OPERATION.

ARE LOCKED OUT FROM OPERATION AND RESSPECTIVE

CW MODE: THE NBC FANS RUN WHEN ASSOCIATED

NORMAL MODE: THE NBC FANS RUN WHEN

DIFF PRESS SWITCH MAKES CONTACT. BUILDING EXHAUST FANS

LOW LEARAGE MOTORIZED DAMPER CLOSE.

FAN'S OPERATIONAL STATUS(PILOT LIGHT GREEN)

PREFILTER DIFFERENTIAL PRESSURE SWITCH/GAGE SHALL

INDICATE PREFILTER FILTER DIRTY STATUS(PILOT LIGHT RED).

INDICATE HEPA FILTER DIRTY STATUS(PILOT LIGHT RED).

MCRF DIFFERENTIAL PRESSURE SWITCH/GAGE SHALL

AND FAN "NOT-OFF" PROBLEM (PILOT LIGHT RED).

TFA DIFFERENTIAL PRESSURE SWITCH/GAGE SHALL INDICATE TFA

ALARM WILL SOUND IF ANY OF THE TFA BOUNDRY DOORS ARE OPENED.

HOUR METER SHALL PROVIDE RUNNING TIME AND NUMBER

HOUR METER/COUNTER 2EACH SHALL BE PROVIDED

INDICATION STATUS, OPEN (RED) & CLOSED (GREEN)

COUNTS. THIS WOULD BE REPRESENTATIVE OF ALL FILTER UNITS

TYPE TO REGISTER 99999.99 HOURS AND 9999999 NUMBER OF

ENERGIZED INDICATING THAT THE FACILITY IS AT MINIMUM PRESSURE

CHECKING AIRFLOW METERS AND THE STATUS OF FILTER UNITS/DAMPERS.

AND THEREFORE THE FACILITY USER SHALL INITIATE TROUBLE SHOOTING

PILOT LIGHT RED. LOW PRESSURE FLASHER LIGHT AND BUZZER ARE

OF RUNNING COUNTS. HOUR METER/COUNTER SHALL BE NONRESET

AT THIS TIME THE FACILITY SHALL BE SECURED TO PREVENT IN AND

BUILDING DESIGNATED DOORS SHALL BE PROVIDED WITH RESPECTIVE DOOR

NBC FAN MOTOR OVERLOAD CONTACT SHALL INDICATE FAN MOTOR PROBLEM

(PILOT LIGHT RED). ADDITIONALLY DISCHARGE PRESSURE SWITCH SHALL INDICATE

BUILDING EXHAUST FAN(S) SHALL INDICATE FAN "OFF" (PILOT LIGHT GREEN)

THE AIRFLOW SHALL BE CONTROLLED UNDER BOTH MODES, THE C/W MODE

CAPACITY IS EQUAL TO 5,600 CFM AND THE NOMAL MODE CAPACITY IS EQUAL TO

5,600 CFM. RESPECTIVE SINGLE LOOP AIRLOW CONTROLLERS SHALL CONTROL

THE OPERATING FAN UNIT TO CONTROL THE VFD TO MAINTAIN THE

SET "CW MODE-NORMAL MODE" SELECTOR SWITCH TO THE DESIRED MODE

ARE ALLOWED TO OPERATE UNDER THEIR RESPECTIVE CONTROL FUNCTIONS.

ASSOCIATED DIFF PRESS SWITCH MAKES CONTACT. BUILDING EXHAUST FANS

STANDBY FAN SHALL BE ACTIVATED AUTOMATICALLY. THE SYSTEM SHALL

WHILE THE OTHER FAN IS ON STANDBY. IF THE OPERATING FAN FAILS, THE

EITHER PRIMARY FAN OR BACKUP FAN POSITION, ALLOWS ONE FAN TO OPERATE

SET "PRIMARY (BF-1) FAN - BACKUP (BF-1A) FAN" SELECTOR SWITCH TO

RESPECTIVE TFA LOW LEAKAGE DAMPER SHALL INDICATE DAMPER NOT CLOSED

PRESSURES AND INDICATE LOW TFA PRESSURES AT 0.15"WG[37.36Pa], THE COLLECTIVE PROTECTION SYSTEM(CPS) SHALL PROVIDE CHEMICAL, BIOLOGICAL AND

RADIOLOGICAL (NBC) PROTECTION FOR THIS FACILITY. MULTI CELL RADIAL FLOW (MCRF)

FILTER UNIT (1 EACH, 5,600-CFM CAPACITY UNIT) IS USED FOR THE BUILDING FILTRATION

SYSTEM DURING NORMAL AND C/W MODE OPERATIONS. THE FILTER UNIT HOUSING SHALL BE

FACTORY CONSTRUCTED EITHER IN KOREA OR THE U.S.A. AND

THE M56A1 FILTERS FOR MCRF WILL BE FURNISHED BY AND PROVIDED AND INSTALLED

BY CONTRACTOR. THE NBC FANS (1-STANDBY) ARE SIZED TO PRESSURIZE

THE PROTECTED ENVELOPE TO 0.3-INCH WG. THE FILTRATION SYSTEM IS

INSTALLED IN THE CPS ROOM CONSIDERED AS DIRTY MECHANICAL ROOM.

DURING THE C/W OPERATING MODE, ONE NBC FAN (SECOND ON STANDBY FOR

AUTO CHANGEOVER) OPERATES TO DRAW OUTSIDE AIR THROUGH PRE-FILTER UNITS AND PUSH

THROUGH THE MCRF FILTER UNIT AND THE ASSOCIATED DUCTED SYSTEM THROUGH

DURING THE NORMAL OPERATING MODE, ONE NBC FAN (SECOND ON STANDBY FOR

AUTO CHANGEOVER) OPERATES TO DRAW OUTSIDE AIR THROUGH PRE-FILTER UNITS AND PUSH

THROUGH THE MCRF FILTER UNIT AND ASSOCIATED DUCTED SYSTEM THRU THE AHU'S.

OUT PROCESSING.

5.1

5.0

4.8

4.8.1

INSTRUMENTS : SCHEDULE

DOOR MONITORING SYSTEM :

RUN PERIODS.

4.5

4.4

4.3

4.6

3.2

4.0

3.1

MONITORING STATUS:

4.2

4.1

PROBLEM, PILOT LIGHT RED.

2.0

2.1

NBC FANS SETUP:

REQUIRED AIRFLOW CAPACITIES.

OF OPERATION.

3.0 SYSTEM OPERATION:

1.3

1.2

1.4

1.1

SYSTEM SETUP:1.0

FFA-1000 UNITS SHALL OPERATE.

ELECTRONIC AIRFLOW METER SHALL INDICATED THE…