SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
R-11SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
O & M
HOUSING DIV.
REVIEWED BY
AS SHOWN
UNITED STATES ARMY GARRISON DAEGU
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
DIRECTORATE OF PUBLIC WORK
HGFEDCBA
T I T L E S H E E T
D - 17 - 25
O, KI TAL
CHON, HYON TAE
DESIGN REVIEW SIGNATURE
ORGANIZATION
USING AGENCY
36TH SIGNAL
MASTER PLN.
ENVIRONMENTAL
NAME SIGNATURE
O&M DIV.
FIRE DEPT.
SAFETY OFFICE
DPTMS(AT/FP)
188TH MP COM.
IND. HYGENIST
HA-00588-5J
UNIT #15746, APO AP 96218-5746
AE - 1
R - 1
DRAWING NO.
CHIEF,
DESIGN & TECH. REVIEW Br.
TITLE SHEET
DATE: 25 JUL 17
AE - 2
AE - 3
CAMP CARROLL
AE - 45 4 OF 24
AE - 56 5 OF 24
PROJECT NO. HA-00588-5J, CAMP CARROLL
AE - 67 6 OF 24
TEST CELL, BLDG. NO. S-326
RENOVATE TWO(2) ENGINE DYNAMOMETER
TEST CELL, BLDG. NO. S-326
RENOVATE TWO(2) ENGINE DYNAMOMETER
M - 1 9 OF 24
E - 1 18 OF 24
M - 211 10 OF 24
M - 312 11 OF 24
M - 413 12 OF 24
M - 514 13 OF 24
M - 918 17 OF 24
M - 817 16 OF 24
M - 716 15 OF 24
M - 615 14 OF 24
E - 220 19 OF 24
21 20 OF 24
E - 422 21 OF 24
E - 523 22 OF 24
E - 624 23 OF 24
E - 725 24 OF 24
AE - 78 7 OF 24
AE - 89 8 OF 24
ARCHITECTURAL
MECHANICAL
ELECTRICAL
E - 3
EXISTING FLOOR PLAN, BLDG. #326, GENERAL NOTES, NOTE, LEGEND AND CODE REFERENCES
REMOVAL PLAN, BLDG. #326, ENLARGED NEW FLOORPLAN, BLDG. #326, SCOPE OF WORK, KEY PLAN, AND LEGEND
TANK DYNO ROOM SECTION, BLDG. #326, CONTROL ROOM SECTION, BLDG. #326, AND NOTE
INTERIOR FINISH SCHEDULE, DOOR SCHEDULE, DOOR / WINDOW PLAN, AND NOTES
WINDOW SCHEDULE, ACOUSTICAL FIXED WINDOW DETAIL (TYP), AND NOTE
ACOUSTICAL DOOR DETAIL (TYP): HEAD, JAMB, SILL, AND METAL SLIDING DOOR: HEAD, JAMB, SILL
DETAIL (TYP)
CONTRACTION JOINT (TYP), PARTIAL DETAIL (TYP), WALL PARTIAL DETAIL (TYP), AND CEILING PARTIAL
CONCRETE DITCH DETAILS (TYP), CMU WALL OPENING DETAIL, AND CEILING PARTIAL DETAIL (TYP)
LEGEND, ABBREVIATIONS AND GENERAL NOTES
EQUIPMENT SCHEDULE, SCOPE OF WORK, NOTE
REMOVE TANK ENGINE TEST ROOMS, NEW TANK ENGINE TEST ROOMS
NOTES FOR FIRE SPRINKLER SYSTEM, REPLACE SPRINKLER HEAD PLAN
NEW ENGINE DYNAMOMETER TEST CELL SYSTEM
NEW ABOVE THE CEILING OF ENGINE DYNAMOMETER TEST CELL SYSTEM
TEST CELL VENTILATION SYSTEM
COMBUSTION AIR SUPPLY SYSTEM
ENGINE GAS EXHAUST SYSTEM
LEGEND, NOTES AND SCOPE OF WORK
REMOVAL PLAN
LIGHTING PLAN AND FIXTURE DETAIL
POWER PLAN
ELECTRICAL SITE PLAN
PANEL SCHEDULE "DP" AND "MPC"
POWER SINGLE LINE DIAGRAM
AS SHOWN
ARCHITECTURAL
D - 17 - 25HA-00588-5J
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
KIM, CHI SOP
MUN, SON KI
GENERAL NOTES
SCALE : 1 / 200AE 01
US ORIGIN MATERIALS:
US ORIGIN MATERIALS SHALL BE AS INDICATED ON THE DRAWINGS.
AT INTERNET SITE HTTP:// WWW.CCKBID.COM). ALL NON-GENERIC
2004 (ELECTRONIC VERSION OF THIS DOCUMENT CAN BE FOUND
"INSPECTION OF CONSTRUCTION CONTRACTS", DATED FEBRUARY 2,
THE GENERIC SUBMITTAL REGISTER OF IMA-KORO PAMPHLET 420-1
ALL GENERIC US ORIGIN MATERIALS SHALL BE AS OFF-SHORE IN
AE-01
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
MISSION OPERATION.
WORK STAGE BY STAGE WITHOUT ANY INCONVENIENCE TO THE CUSTOMER’S
THE WORK AND GET APPROVAL FROM THE GOVERNMENT AND EXECUTE
THE CONTRACTOR SHALL SUBMIT WORK SCHEDULE PRIOR TO COMMENCING
OR RENOVATION.
CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION
THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFYING ALL EXISTING
CONDITION TO ADJACENT AREAS AS DIRECTED BY THE CONTRACTING OFFICER.
DAMAGES TO EXISTING AREAS CAUSED BYTHIS PROJECT AND TO MATCH
THE CONTRACTOR SHALL BE RESPONSIBLE TO CONSTRUCT OR REPAIR ALL
AND SUBMITTED TO THE CONTRACTING OFFICER FOR APPROVAL.
FIELD BY THE CONTRACTOR ACCORDING TO ACTUAL FIELD CONDITIONS
EXACTLY FIELD CONDITIONS, SUCH DETAILS SHALL BE PREPARED IN THE
SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH
FOR APPROVAL BY THE C.O. OR HIS COR.
CONTRACTOR SHALL SUBMIT MANUFACTURERS INSTALLATION SHOP DRAWINGS
R=15 FACTOR).
INSULATION HEAT RESISTANCE VALUE (ROOF - R=38 FACTOR AND WALL -
APPROVED BY THE C.O. OR HIS COR. BEFORE FABRICATION AND INSTALLATION.
DRAWINGS FOR ALL DOOR AND WINDOW DETAILS AND DRAWING SHALL BE
MANUFACTURER’S INSTRUCTIONS. THE CONTRACTOR SHALL PREPARE SHOP
ALL DOORS AND WINDOWS SHALL BE FABRICATED I.A.W. SPECIFICATIONS AND
WORK.
BE DONE TO INSURE ROUGH-IN WORK IS ACCOMPLISHED PRIOR TO FINISHING
TELEPHONE AND FIRE ALARM SYSTEM COORDINATION OF THIS WORK MUST
THE INSTALLATION AND REPLACEMENT OF MECHANICAL, ELECTRICAL,
CUT, PATCH AND RESTORE WALLS, FLOORS AND CEILING TO MAKE WAY FOR
APPROVED CAULKING MATERIALS RATED FOR THE FIRE WALL.
ALL PENETRATIONS THROUGH FIRE RATED WALLS MUST BE SEALED WITH
PLATE, ETC.)
ROOF THAT DISTURB WATERPROOFING WORK. (ANTENNA, WIRE, SYMBOL, NAME
THE CONTRACTOR SHALL REMOVE & REINSTALL ALL EQUIPMENTS ON THE
MACHINE EQUIPMENTS.
THE CONTRACTOR SHALL PREVENT DUST SCATTERING FOR ACCUPANTS AND
CONTRACT.
ARCHITECTURAL SCOPE OF WORK AT NO ADDITIONAL COST TO THE PROJECT
OF THIS PROJECT. THE DETAILS WILL BE UTILIZED TO ACCOMPLISH THE
INSTALLATION MANAGEMENT COMMANDER, 30 NOVEMBER 2015" FORM AS A PART
DRAWINGS FOR O&MA PROJECTS, KOREA, DEPARTMENT OF THE ARMY
THE ARCHITECTURAL STANDARD DRAWINGS SHOWN IN THE "STANDARD DETAIL
EXISTING FLOOR PLAN, BLDG. #326
CAMP CARROLL
LEGEND AND CODE REFERENCES
GENERAL NOTES, NOTE,
EXISTING FLOOR PLAN, BLDG. #326,
R A
M P
D N
R A
RAMP DN
R A
N
FLOOR: 1
BUILDING: 326
44482mm
145’-11" 123781mm
406’-1" m m m m
120091mm
394’-0"
4724mm
15’-6"
2521mm
8’-3"
7226mm
23’-9"
9512mm
31’-3"
38760mm
127’-2"
4826mm
15’-10"
11176mm
36’-8"
33579mm
110’-2"
5798mm
19’-0" m m m m m m m m m m m m m m m m m m m m m m
7455mm
24’-6"
7226mm
23’-9"
94139mm
308’-10"
4077mm
13’-4" m m m m m m m m
9576mm
31’-5"
6960mm
22’-10"
3226mm
10’-7"
3200mm
10’-6"
3150mm
10’-4"
3200mm
10’-6"
1422mm
4’-8"
2896mm
9’-6"
2946mm
9’-8"
2845mm
9’-4"
2921mm
9’-7"
1492mm
4’-11"
3258mm
10’-8"
3194mm
10’-6"
1638mm
5’-5"
3270mm
10’-9"
1899mm
6’-3"
10217mm
33’-6"
49727mm
163’-2" m m m m m m m m
10154mm
33’-4"
4616mm
15’-2"
4636mm
15’-3"
4616mm
15’-2"
4616mm
15’-2" m m
4997mm
16’-5"
10160mm
33’-4"
4724mm
15’-6" m m m m m m m m m m
42824mm
140’-6"
2978mm
9’-9"
10077mm
33’-1" m m m m m m m m
5645mm
18’-6" m m m m m m
3188mm
10’-6" m m m m m m
7087mm
23’-3"
7163mm
23’-6"
14757mm
48’-5"
4851mm
15’-11" m m
3473mm
11’-5" m m
2870mm
9’-5"
1626mm
5’-4"
1816mm
6’-0" m m
6998mm
23’-0"
4369mm
14’-4"
1194mm
3’-11"
1041mm
3’-5"
9677mm
31’-9"
6445mm
21’-2"
7791mm
25’-7"
20301mm
66’-7"
4724mm
15’-6"
36347mm
119’-3"
3689mm
12’-1" m m m m
3689mm
12’-1"
LEGEND
SINGLE DOOR
DOUBLE DOOR
WINDOW
REMOVE WORK
CMU WALL
CODE REFERENCES
IBC
2009 EDITION
INTERNATIONAL BUILDING CODE
UNIFIED FACILITIES CRITERIAUFC
UNIFIED FACILITIES GUIDE SPECIFICATIONSUFGS
O&MA SPEC
O&MA DRAWINGS
30 NOVEMBER 2015
FOR O&MA PROJECTS, KOREA.
STANDARD DETAIL DRAWINGS
30 OCTOBER 2015
FOR O&MA PROJECTS, KOREA. REVISION 1
STANDARD TECHNICAL SPECIFICATIONS
UFC 4-010-01
FOR BUILDINGS.
DoD MINIMUM ANTITERRORISM STANDARDS
NOTE
BLDG. #998
131.7 SM (1,417.5 SF)
TEST CELL (#1 & #2) WORK AREA:
CONTROL ROOM
TANK DYNO RM#1 TANK DYNO RM#2
SLIDING DOOR
WORK AREA
ACRYLIC FLUID-APPLIED WATERPROOFINGSECTION 07 14 01
TEST CELLS, BLDG. NO S-326
RENOVATE TWO(2) ENGINE DYNAMOMETER
25 JUL 17
1 24
EXISTING 15mm GWB
EXISTING 100 THK STUD WALL
100 THK INSULATION
12.5mm GWB
25 mm ACOUSTIC TILE
AS SHOWN
ARCHITECTURAL
D - 17 - 25HA-00588-5J
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
KIM, CHI SOP
MUN, SON KI
AE-02
CAMP CARROLL
R A
R A m m m m
7087mm
23’-3"
7163mm
23’-6"
14757mm
48’-5"
TANK DYNO RM#1
CONTROL ROOM
REMOVAL WORK
4 REMOVE EXISTING WALL INSULATION
REMOVE SUSPENDED CEILING SYSTEMS AND SUPPORTS
REMOVE EXISTING CEILING INSULATION
REMOVE EXISTING WALL FINISH WITH FRAME
5 REMOVE EXISTING WALL GWB & ACOUSTICAL TILES
6 REMOVE EXISTING DOOR
8 REMOVE EXISTING WINDOW
REMOVE EXISTING METAL SLIDING DOOR
1 2 4
6 8
1 2 3
4 7
SCOPE OF WORK
A. REPAIR / MAINTENANCE WORK (K)
1 2 3
4 7
SUSPENSION SYSTEM, INSULATION AND NECESSARY ACCESSORIES.
REPLACE EXISTING CEILING SYSTEM WITH NEW INCLUDING
FRAME AND NECESSARY ACCESSORIES.
ACOUSTICAL WALL PANEL INCLUDING INSULATION, METAL
REPLACE EXISTING WALL WITH NEW PERFORATED METAL
AND GWB INCLUDING NECESSARY ACCESSORIES.
REPLACE EXISTING WALL FINISH WITH NEW ACOUSTICAL TILE
INCLUDING METAL FRAME AND NECESSARY ACCESSORIES.
REPLACE EXISTING DOOR WITH NEW ACOUSTICAL DOOR
9 REMOVE EXISTING CONCRETE SLAB
9 9
LEGEND
TRIM, AND NECESSARY ACCESSORIES.
NEW ACOUSTICAL FIXED WINDOW INCLUDING OAK WOOD
REPLACE DETERIORATED EXISTING FIXED WINDOW WITH
DOORS BY MPI.
PAINT ON INTERIOR & EXTERIOR WALLS, FLOOR, AND METAL
1825mm
6’-0"
1800mm
5’-11"
2025mm
6’-8"
1000mm
3’-3"
2025mm
6’-8"
1800mm
5’-11"
1825mm
6’-0"
7200mm
23’-7"
7200mm
23’-7" m m m m m m
7200mm
23’-7"
1600mm
5’-3" 1600mm
5’-3"
7200mm
23’-7"
1600mm
5’-3"
1600mm
5’-3"
550mm
1’-10"
550mm
1’-10"
1000mm
3’-3"
TANK DYNO RM#2
TANK DYNO
RM#2
TANK DYNO
RM#1
Control Room
3 4
7 8
1 2 5
7 8
LEGEND
EXISTING BEAM
EXISTING COLUMN
EXISTING DITCH W/ STEEL PLATE
AIR DUCT
ACOUSTICAL FIXED WINDOW
EXISTING WINDOW
MEATL SLIDING DOOR
SCALE : 1 / 50AE 02
1 REMOVAL PLAN, BLDG. #326
SCALE : 1 / 50AE 02
2 ENLARGED NEW FLOORPLAN, BLDG. #326
CONCRETE SLAB
REMOVE EXISTING
ACOUSTICAL DOOR
EXISTING CMU
100 THK INSULATION
W/ 25X25 SQUARE TUBE
ACOUSTICAL STEEL SHEET
1.6 THK PERFORATED
NECESSARY ACCESSORIES.
METAL RAIL, WEATHER STRIP, MANUAL LOCK SYSTEM AND
REPLACE EXISTING SLIDING DOOR WITH NEW INCLUDING
AE 03
KEY PLAN
R
A
R A
RAMP DN
R A
N
FLOOR: 1
BUILDING: 326
CONTROL ROOM
TANK DYNO RM#1 TANK DYNO RM#2
WORK AREA
(TANK DYNO RM#1 & RM#2)
SCOPE OF WORK, KEY PLAN, AND LEGEND
ENLARGED NEW FLOORPLAN, BLDG. #326,
REMOVAL PLAN, BLDG. #326,
AE 03
Hoist Existing Electric
Hoist Existing Electric
CMU OPENING
10 10
MAKE A MORE BIG SIZE OPENING (1400mm x 1200mm) CMU
CONTRACTION JOINT
AREA FOR MECHANICAL WORK.
SYSTEM INCLUDING NECESSARY ACCESSORIES AT WHOLE ROOF
REPLACE EXISTING ACRYLIC FLUID-APPLIED WATERPROOFING
Oil Line Ditch Oil Line Ditch
OIL LINE DITCH
(1200mm(w)X50mm(d)X70mm(h))
STEEL PLATE
DITCH WITH
830mm
2’-9" m m
2580mm
8’-6"
PLATE, DITCH, EXPANSION JOINT AND NECESSARY ACCESSORIES.
REINFORCING BAR, STEEL BEAM, STEEL ANGLE, STEEL
DYNAMOMETER SYSTEM OF MECHANICAL WORK INCLUDING
REPLACE EXISTING CONCRETE SLAB WITH NEW FOR
11 MAKE A OPENING (450mm x 500mm) CMU. (2800mm FROM FL)
WALL OPENING
m m
TEST CELLS, BLDG. NO S-326
RENOVATE TWO(2) ENGINE DYNAMOMETER
2 24 m m m m
Control Room
Metal Door Acoustical
CMU
Existing
CMU
Existing
2117mm
6’-11"
@ 400mm O.C. (MAX) - TYP 92mm METAL CHANNEL
INSULATION(#60) W/VB
100mm THK MINERAL WOOL
INSULATION(#60) W/VB
100mm THK MINERAL WOOL
12.5mm THK GWB
25mm THK ACOUSTICAL BOARD
RCB
PAINT
EPOXY
(#60) W/VB
WOOL INSULATION
100mm THK MINERAL
12.5mm THK GWB
25mm THK ACOUSTICAL BOARD
AS SHOWN
ARCHITECTURAL
D - 17 - 25HA-00588-5J
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
KIM, CHI SOP
MUN, SON KI
AE-03
CAMP CARROLL
1500mm
4’-11" m m
1800mm
5’-11" m m
1800mm
5’-11" m m m m
1500mm
4’-11"
200mm
8"
830mm
2’-9"
3390mm
11’-1"
200mm
8"
200mm
8"
200mm
8"
2580mm
8’-6"
200mm
8"
2580mm
8’-6"
3390mm
11’-1"
200mm
8"
830mm
2’-9"
200mm
8"
50*50*6 Steel Angle
6T Check Plate
Steel
520mm
1’-8"
13*6, 6T Steel Plate
2450mm
8’-0"
2450mm
8’-0"
520mm
1’-8"
@860 50*50*6
Steel Angle
50*50*6 Steel Angle
6T Check Plate
Steel
13*6, 6T Steel Plate
@860 50*50*6
Steel Angle
Hoist Existing Electric
Beam Existing
Beam Existing
Column Existing
Fixed Window Acoustical
Metal Door Acoustical
Metal Door Acoustical
Fixed Window Acoustical
1 - VAPOR BARRIER
150mm THK CAPILLARY WATER BARRIER
AE 07
Beam Existing
Hoist Existing Electric
Beam Existing
0.5 THK Perforated Painting Plate
AE 07
Insulation (64Kg/cm2)
30*30 Steel Angle
@1000 25*25 Pipe
50 THK Fabric Covered 0.5 THK Perforated Painting Plate Insulation (64Kg/cm2) 50 THK Fabric Covered
AE 07
TANK DYNO
RM#2
TANK DYNO
RM#1
(Same as RM#2)
SCALE : 1 / 25AE 03
1 TANK DYNO ROOM SECTION, BLDG. #326
NOTE
SCALE : 1 / 25AE 03
2 CONTROL ROOM SECTION, BLDG. #326
50mm THK Lean Concrete
OF MANUFACTURE.
& DYNAMOMETER SYSTEM BY SPECIFICATION
AND DETAILS FOR THE SURFACE PLATE
A SHOP DRAWINGS OF INSTALLATION,
THE CONTRACTOR SHALL BE SUBMITTED
m m
"3 m m m m
50*50*6 Steel Angle m m m m
AE 07
Joint Expansion
AE 07
300mm THK CONC SLAB
HD16 @ 200mm O.C. EACH WAY
100*100 H Beam
Joint Expansion
@860 50*50*6
Steel Angle m m
2450mm
8’-0"
520mm
1’-8" m m m m m m
Slab Concrete
Slab Concrete
50*50 Pipe @1000
Hole Rate 25% Min
25*25 Pipe @1000
50 THK Insulation w/VB (64Kg/cm2)
50 THK Insulation w/VB (64Kg/cm2) 25*25 Pipe @1000
Hole Rate 25% Min
0.5 THK Metal Sheet
0.5 THK Metal Sheet
TEST CELLS, BLDG. NO S-326
RENOVATE TWO(2) ENGINE DYNAMOMETER
25 JUL 17
3 24
AND NOTE
CONTROL ROOM SECTION, BLDG. #326,
TANK DYNO ROOM SECTION, BLDG. #326,
D - 17 - 25HA-00588-5J
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
KIM, CHI SOP
MUN, SON KI
AE-04
CAMP CARROLL
RCB
MATLMATL
TANK DYNO RM#2
ROOM NAMES
FNSH
FLOOR
COLOR
FF
FNSH
BASE
COLOR COLOR
INTERIOR WALL
MATL FNSH COLORMATL FNSH
CEILING
HGT
REMARKS
RCB-1
FF FF ACST-1 2450
FF 3390RCB RCB-1
RCB RCB-1
INTERIOR FINISH SCHEDULE
TANK DYNO RM#1
CONTROL ROOM
CONC
EXST
CONC
EXST
CONC
EXST
EP-1
GWB/ACST
FF
FF
FF
PMAP-1
PMAP-1
ACST-1
ACOUSTICAL
PANEL
ACOUSTICAL
PANEL
GWB/ACST
ACOUSTICAL
PANEL
ACOUSTICAL
PANEL
FF
FF PMAP-1
PMAP-1
RCB-1
OR APPROVED EQUAL
: RUBBER COVE BASE
COLOR: 54, BLACK-BROWN
ARMSTRONG
BASE MATERIAL/COLOR MISC MATERIAL/COLOR
PT-2
LATEX, SEMI-GLOSS
: PAINT
PT-3 : PAINT
EPOXY, GLOSS
OR APPROVED EQUAL
BENJAMIN MOORE #939
OR APPROVED EQUAL
BENJAMIN MOORE #939
: PAINT
ARCHITECTURAL LATEX/SEMIGLOSS
PT-1
OR APPROVED EQUAL
BENJAMIN MOORE, #939
HIGH PERFORMANCE
: PAINT
SEMI-GLOSS ENAMEL
FOR METAL DOOR & FRAME
OR APPROVED EQUAL
BENJAMIN MOORE
SORREL BROWN #1236
PT-4
WINDOW OAK TRIM & WALL RAIL
OAK (FACTORY NATURAL FINISH)
OR APPROVED EQUAL
ACST-1
PMAP-1
OR APPROVED EQUAL
OR APPROVED EQUAL
EP
EP
EP
EP-1
EP-1
: PERFORATED METAL ACOUSTICAL PANEL
WALL & CEILING MATERIAL & COLOR
: ACOUSTICAL BOARD
TECTUM
25THK, 600 x 2400
EP-1
OR APPROVED EQUAL
MPI 77 SUPERPOXY 200
SAMHWA PAINT
OAK-1 : INTERIOR WOOD SOLID CORE DOOR,
: EPOXY, GLOSS
METAL
FRAME
D5
D2
D4
D3
DOOR
NOS
AD1
METAL
METALA
A
DOOR
DOOR
TYPE
MATERIAL
JAMB
DOOR DIMENSION
21501000
HEIGHT
ROUGH OPENING
WIDTH WIDTH HEIGHT THICK HEAD
SET
NO
HDW
DETAILS
SILL
MEET/MULL
/TRANSOM
DOOR SCHEDULE
GLAZING
UNDER
CUT
REMARKS
METAL 36003100 -- -
TANK DYNO
RM#2
TANK DYNO
RM#1
Control Room
D1 D2
D3
D4D5
W1 W1
W2 W2
FLUSH METAL DOOR A
ACOUSTICAL
WITH METAL FRAME
B METAL SLIDING DOOR
RAL-A86-44
B
B
- -* 3200 * 3700 * 44.5 * 2 * BY DOOR MFR
36003100 * 3200 * 3700 * 44.5
4 5 6
AE AE AE
1 2 3
AE AE AE06
1 2 3
AE AE AE
1 2 3
AE AE AE
4 5 6
AE AE AE
METAL METAL
METAL METAL
* 2 * BY DOOR MFR
* BY DOOR MFR
* BY DOOR MFR
* BY DOOR MFR
* 900 * 2100 * 44.5 * 1
* 1
* 1
21501000 * 900 * 2100 * 44.5
21501000 * 900 * 2100 * 44.5
DOOR STOP L02161
CLOSER DC2000
LOCKSET 4000-1, F04 (LEVER TRIM)
HDW-1
1 1/2PR
HDW-2
Overly Door Company
WEB SITE. - http://door.overly.com
ADDRESS - 574 West Otterman Street Greensburg, PA 15601
ANSI 156.4 Grade 1
OR APPROVED EQUAL
ACOUSTICAL DOOR
Surface Mounted Closer: Corbin/Russwin DC2000, DC3000, DC4000
Saddle Threshold: Reese S105
HINGES OVERLY MCL-1000, NRP
THRESHOLD REESE S105
STEEL ASTRAGALS
CENTER STOP
END STOPPER
1 PR
PAD LOCK, TYPE P01, OPTION B1
HASPS & BOLT (BY MFR)1
ROLLER LATCH (BY MFR)1
SCALE : 1 / 100AE 04
1 DOOR / WINDOW PLAN
MODEL NO. - ACOUSTICAL METAL DOOR #5592175
Full Mortise Cam-Lift Hinge: Overly MCL-1000
Mortise Lock: Corbin / Russwin ML2000, ANSI A156.13 Series 1000 Grade 1
STC-55, UL 10B, UL10C/UBC 7-2
BY ARCH.)
COATED NATURAL COLOR FINISH. ( FINISH TO BE DETERMINED
OR MORE KEYING FOR EXTRA.
THE CONTRACTOR SHALL BE PREPARED TWO (2) EACH
APPROVED BY THE COR. BEFORE APPLICATION.
SINGLE MASTER KEYING SYSTEM DIAGRAM AND SHALL BE
THE CONTRACTOR SHALL BE PREPARE SHOP DRAWINGS FOR
ALL DOOR, WINDOW AND DRAWINGS SHALL BE APPROVED
BY THE CONTRACTING OFFICER BEFORE FABRICATION
AND INSTALLATION
ACCORDANCE WITH NFPA 80 FIRE DOORS AND
ALL WOOD FLUSH DOORS SHALL BE FINISHED FACTORY
FIRE DOORS AND FRAMES SHALL BE INSTALLED IN
1.
2.
3.
4.
5.
6.
7.
8.
FIRE WINDOWS. ASTM. E119.
THE CONTRACTOR SHALL PREPARE SHOP DRAWINGS FOR
ELECTRONIC NETWORKED LOCKSET SHALL BE "SALTO" OR
APPROVED EQUAL
ALL LOCKS EXCEPT ELECTRONIC LOCKSET SHALL BE
INTERCHANGEABLE CORE, "BEST-LOCK" OR APPROVED EQUAL.
ALL DOORS AND WINDOWS SHALL BE FABRICATED IN
ACCORDANCE WITH SPECIFICATIONS, HARDWARE SCHEDULE
AND MANUFACTUES INSTRUCTIONS APPROVED BY THE
CONTRACTOR OFFICER PRIOR TO COMMENCING WORK.
NOTES
06 06
WEB SITE. - http://www.doorengineering.com/
OR APPROVED EQUAL
METAL SLIDING DOOR
DOOR ENGINEERING & MANUFACTURING LLC
MODEL NO. - NTH 2700
ADDRESS - 400 West Cherry Street PO Box 5 Kasota, MN 56050-0005
V A
R
VAR
EWC-1 : EXTERIOR WALL COLOR
OR APPROVED EQUAL
** COLORS SHALL BE SELECTED BY COR & USING AGENCY
TO MATCH EXIST
BENJAMIN MOORE & CO #108
0.5 THK PERFORATED PAINTING PLATE
HOLE RATE 25% MIN
(1000 x 3600 x 0.5)
TEST CELLS, BLDG. NO S-326
RENOVATE TWO(2) ENGINE DYNAMOMETER
25 JUL 17
4 24
DOOR / WINDOW PLAN, AND NOTES
DOOR SCHEDULE,
INTERIOR FINISH SCHEDULE,
D - 17 - 25HA-00588-5J
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
KIM, CHI SOP
MUN, SON KI
AE-05
CAMP CARROLL
REMARKSGLAZING
HEIGHT
MATERIALNOS
WIDTH
A 8401320
TYPE
ALUMINUM
WINDOW SIZE
DESCRIPTION
W1
WINDOW SCHEDULE
WINDOW TYPES
1.
2.
3.
4.
5.
THE CONTRACTOR SHALL PREPARE SHOP DRAWINGS FOR ALL DOORS AND ALUMINUM WINDOWS
AS ACTUAL SIZE, AND DRAWINGS SHALL BE APPROVED BY THE CONTRACTING OFFICER BEFORE
FABRICATION AND INSTALLATION.
WINDOWS IN ALL AREAS WHERE FUNCTIONALLY WARRANTED SHALL BE EQUIPPED WITH HORIZONTAL
MANUFACTURERS LISTED ARE FOR IDENTIFICATION PURPOSES ONLY AND ARE NOT INTENDED TO LIMIT
SELECTIONS OF PRODUCTS. AN EXACT MATCH OF THE MANUFACTURERS FUNCTION, GRADE, COLOR &
QUALITY ARE NOT REQUIRED. BUT CONTRACTOR SHOULD INSTALL HIGH QUALITY AND GRADE PRODUCTS
WITH APPROVAL TO COR.
INSECT SCREEN SHOULD BE EQUIPPED TO ALL EXTERIOR WINDOWS.
ALL BLAST WINDOW GLASS SHALL BE PROVIDED BY BLAST WINDOW MFR PER SPEC
ALL EXTERIOR DOOR, GLAZED WINDOW: SEE SEPCIFICATION AND UFC 4-010-01, PAG B-9 & 10, PARA B-3.1
THRU B-3.1.4 ALL EXTERIOR DOOR FRAME AND WINDOW FRAME SHOULD BE CONNECTED TO STRUCTURE
WITH ANCHOR BOLT AND WELDING. CONTRACTOR SHOULD SUBMIT SHOP DRAWING FOR ALL DOOR AND
WINDOW SCHEDULE AND DETAIL DRAWING TO COR FOR APPROVAL.
NOTES
A SLIDING
GLASS
R O
RO
VENETIAN BLINDS. COLOR SHALL BE WHITE OR LIGHT BEIGE TO MAXIMIZE REFLECTANCE AND MINIMIZE
HEAT GAIN AND FIRERATED. EXISTING
AL WINDOW
EXISTING TO REMAIN
R O
RO
B ACOUSTICAL
FIXED WINDOW
B 12001800W2
EXISTING TO REMAIN EXISTING TO REMAIN
1-1/4 IN NOMINAL UL 752 LEVEL I BULLET RESISTANT GLASS
1/4 IN THICK LAMINATED GLASS;
DUAL GLAZED FIXED
BULLET-RESISTANT GLASS
Overly Door Company
WEB SITE. - http://door.overly.com
ADDRESS - 574 West Otterman Street Greensburg, PA 15601
OR APPROVED EQUAL
ACOUSTICAL FIXED WINDOW
UL LEVEL 1 BULLET-RESISTANT
ACOUSTICAL DUAL GLAZED FIXED WINDOW - STC 55
ACOUSTICAL
MODEL NO. - ACOUSTICAL METAL WINDOW #MODEL 559511
METAL * BY WINDOW MFR
STC-55, UL 752 LEVEL 1, ANSI Z97.1, CPAS 16 CFR 1201
ASTM C1036, ASTM C1172, ASTM C1422
NOT TO SCALE
1" [25]1" [25] CLEAR OPENING WIDTH
JAMB OPENING WIDTH
2"
[50]
2"
[50]
OVERALL FRAME WIDTH
1/4" [6] TYPICAL
HORIZONTAL SECTION
AE 05
1 ACOUSTICAL FIXED WINDOW DETAIL (TYP)
JAMB DEPTH
8" [203] MINIMUM
2"
[50]
1" [25]
C L E
A R O
P E
N
IN
G W
ID
T
H
J A
M B O
P E
N
IN
G W
ID
T
H
O V
E R
A L L F
R A
M E W
ID
T
H
1" [25]
2"
[50]
VERTICAL SECTION
AND NOTE
ACOUSTICAL FIXED WINDOW DETAIL (TYP),
WINDOW SCHEDULE,
24" O.C. MAX TYPICAL
MASONRY STRAP ANCHOR
24" O.C. MAX. TYPICAL
SLEEVE ANCHORS
GLASS OR EQUAL
PANE 36 LAMINATED
1/4" [6] ACOUSTA-
UL LEVEL 1 GLASS
GLOBE-AMERADA
1 3/16" [30] NOMINAL
PURGE PORT
FILL ALL VOIDS IN FRAME
TEST CELLS, BLDG. NO S-326
RENOVATE TWO(2) ENGINE DYNAMOMETER
5 24
D - 17 - 25HA-00588-5J
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
KIM, CHI SOP
MUN, SON KI
AE-06
CAMP CARROLL
NOT TO SCALEAE 06
CAM-LIFT HINGES, CAM-LIFT HINGES, & LOCK
DUAL "H" PERIMETER SEALS,
TYPICAL EDGE
DOOR BOTTOM
SUPER "H"
OVERLY
2"
[50] [3]
1/8"
[5]
3/16"
J A
M B O
P E
N
IN
G H
E
IG
H T
F
IN
IS
H E
D D
O O
R H
E
IG
H T
CAM-LIFT HINGE
OVERLY MCL-1000
ACOUSTICAL DOORS
ARE RECOMMENDED FOR USE ON
LOCKS EQUIPPED WITH LEVER HANDLES
2"
[50]
[3]
1/8"
JAMB OPENING WIDTH
FINISHED DOOR WIDTH
[3]
1/8"
2"
[50]
7/8"[22]
[54] 2 1/8"
3"
[76]
[159]
MIN
6 1/4"
SOUND ISOLATOR
SOLID NEOPRENE
VERTICAL SECTION
NOT TO SCALEAE 06
1 ACOUSTICAL DOOR DETAIL (TYP): HEAD ACOUSTICAL DOOR DETAIL (TYP): JAMB
NOT TO SCALEAE 06
1 ACOUSTICAL DOOR DETAIL (TYP): SILL
BEAM
EXISING CONC
TRACK
DOOR
METAL SLIDING
(BY DOOR MFR)
TRACK HANGER
STAY ROLLER
SLAB
EXISING CONC
TROLLEY
(BY DOOR MFR)
(BY DOOR MFR)
(BY DOOR MFR)
DOOR FOR D1~D12
METAL SLIDING
(BY DOOR MFR)
DOOR
METAL SLIDING
(BY DOOR MFR)
WALL
EXISING CMU
STEEL
ASTRAGALS
CENTER
STOP
(BY DOOR MFR)
(BY DOOR MFR)
METAL SLIDING DOOR
1-HR FIRE RATED
(BY DOOR MFR)
FOR D13~D16
R O
R O
RO
m m
O V
E R
L A P m m
102mm
4"
19mm
1" m m
NOT TO SCALEAE 06
NOT TO SCALEAE 06
NOT TO SCALEAE 06
METAL SLIDING DOOR: HEAD, JAMB, SILL
JAMB, SILL, AND
ACOUSTICAL DOOR DETAIL (TYP): HEAD,
METAL SLIDING DOOR (TYP): HEAD METAL SLIDING DOOR (TYP): JAMB METAL SLIDING DOOR (TYP): JAMB
TEST CELLS, BLDG. NO S-326
RENOVATE TWO(2) ENGINE DYNAMOMETER
6 24
D - 17 - 25HA-00588-5J
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
KIM, CHI SOP
MUN, SON KI
AE-07
CAMP CARROLL
76mm
3"
76mm
3" m m
H
H
Joint Expansion
Joint Sealer (TYP)
6.4mm Fiberboard
13mm to 16mm
18mm to 22mm m m
C L
R
AE 07
1 CONTRACTION JOINT (TYP)
SCALE : 1 / 10
m m m m
520mm
1’-8"
(TYP)
3 (TYP)
(TYP)
200mm
8"
STEEL ANCHOR @600 B.S
13mm DIA. x 200mm L.
Steel Plate 13*6, 6T
Steel Angle 50*50*6
Steel Check Plate 6T
@300 Steel Angle 50*50*6
Steel Plate 13*6, 6T
Steel Angle 50*50*6
Anchor @ 300 M10 70mm Set
50 (TYP)
AE 07
SCALE : 1 / 10
320mm
1’-1" m m m m
260mm
10"
50mm
2"
50mm
2"
H-Beam 100*100
HD16 @ 200mm O.C. EACH WAY
(TYP)
HD16*L150 @ 200mm
PARTIAL DETAIL (TYP)
AE 07
SCALE : 1 / 10
PARTIAL DETAIL (TYP)
AE 07
SCALE : 1 / 10
AE 07
SCALE : 1 / 20
CEILING PARTIAL DETAIL (TYP)
WALL PARTIAL DETAIL (TYP)
AE 07
SCALE : 1 / 10
PARTIAL DETAIL (TYP)
0.5 THK Perforated Painting Plate
m m m m
12mm
1/2"
20mm
1" m m
6mm
1/4"
Through 5 DIA Hole
Through 8 DIA Hole
Slab Concrete
Hole Rate 25% Min
1000*3600*0.5
420mm
1’-5"
Existing CMU Anchor @ 600
M10 30mm Set
50 THK Fabric Covered Insulation (64Kg/cm2)
0.5 THK Perforated Painting Plate
50 (TYP)
50*50*4 Steel Angle @1000
Hole Rate 25% Min
1000*3600*0.5
50 THK Insulation W/VB (64Kg/cm2)
0.5 THK Metal Sheet
50 THK Insulation W/VB (64Kg/cm2)
50 THK Fabric Covered Insulation (64Kg/cm2)
0.5 THK Perforated Painting Plate
25 (TYP)
(TYP)
0.5 THK Metal Sheet
Hole Rate 25% Min
1000*3600*0.5
975mm
3’-2"
1000mm
3’-3" m m
12.5mm
12.5mm m m
25mm
1" m m
Slab Concrete
#4 BARS @ 12" OC, EW
TEST CELLS, BLDG. NO S-326
RENOVATE TWO(2) ENGINE DYNAMOMETER
25 JUL 17
7 24
AND CEILING PARTIAL DETAIL (TYP)
WALL PARTIAL DETAIL (TYP),
CONTRACTION JOINT (TYP), PARTIAL DETAIL (TYP),
50*50*4.5 Pipe @1000
25*25*2.3 Pipe @1000 25*25*2.3 Pipe @1000
25*25*2.3 Pipe @1000
Angle 30*30*3
Angle 30*30*3
D - 17 - 25HA-00588-5J
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORKS
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
KIM, CHI SOP
MUN, SON KI
AE-08
CAMP CARROLL
m m m m
520mm
1’-8"
(TYP)
3 (TYP)
(TYP)
200mm
8"
STEEL ANCHOR @600 B.S
13mm DIA. x 200mm L.
Steel Plate 13*6, 6T
Steel Angle 50*50*6
Steel Check Plate 6T
420mm
1’-5"
Slab Concrete
200mm
8"
@ 12" OC, EW
#4 BARS
W.W.F.
MW10(#8)-150X150
@300 Steel Angle 50*50*6
AE 08
SCALE : 1 / 10
CONCRETE DITCH DETAILS (TYP)
A
A
LINTEL
PRECAST CONCRETE
T-BAR
B-BAR STIRRUP
NOTE2
(NOTE1)
GRUOT SOLID
OPENING
200mm 200mm
NOTES :
SOLID TO GREATEST EXTENT POSSIBLE
1. AFTER CUTTING OPENING, GROUT JAMBS
OR LOUVER FRAME
2. DIMENSION AS REQUIRED FOR DOORS, WINDOW,
3. SEE ARCH PLAN FOR DOOR SIZE AND LOCATION
CMU WALL
EXISTING
T-BAR
B-BAR
STIRRUP
40mm CLR
MORTAR
ELEVATION SECTION A-A
LINTEL SCHEDULE
T-BARS B-BARS STIRRUPS
2-HD13 2-HD13 HD10@150 O.C.
m m
AE 08
2 CMU WALL OPENING DETAIL
NOT TO SCALE
SLAB REINFORCING
40mm CLR
VAPOR BARRIER 150mm THK CWB
FORMED JOINT
3.2mm x T / 4 SAWED OR
T
AE 08
NOT TO SCALE
CMU WALL
EXISTING
40mm CLR
W/ SEALANT
10mm THK PEJ
W.W.F.
MW10(#8)-150X150
VAPOR BARRIER
150mm THK CWB
AE 08
SCALE : 1 / 10
SLAB DETAIL
AND CEILING PARTIAL DETAIL (TYP)
CMU WALL OPENING DETAIL,
CONCRETE DITCH DETAILS (TYP),
CONSTRUCTION JOINT DETAIL
TEST CELLS, BLDG. NO S-326
RENOVATE TWO(2) ENGINE DYNAMOMETER
8 24
SCH
SA
SAN
QTY
R12, R22
RA
RDTR
RPM
RT
PG
PH
POC
POL
PPM
PRV
QT
OA
OAIL
OD
OS&Y
Pa
NTS
BUTTERFLY
CUBIC METER PER HOUR
AIR CONDITION (-ING,-ED)
AIR CONDITION UNIT (S)
AIR COOLED CONDENSING UNIT
CHILLED/HOT WATER RETURN
CHILLED/HOT WATER SUPPLY
REFRIGERANT LIQUID
CAP CAPACITY
CUBIC METER
COMPRESSOR
CONTINUE
CONNECTION
CPRSR
CU M
CONT
CONN
COUNTER CLOCKWISE
COEFFICIENT
CIRCUIT
CAST IRON PIPE
CHILLED WATER
CKT
CMH
COEF
CHW
CCW
CIP
ALARM CHECK VALVEACV
AVG AVERAGE
BAROMETER(-TRIC)
CENTIGRADEC
BARO
AMPERE(AMP, AMPS)
ALUMINUM
APPROX
AMP
AIR COND
AHU
AL
AIR COOLED
ACU
ACLD
ACCU
CHWS
CHWR
CHR
CHS
D
RL
DRAIN
KILOCALORIE PER HOUR
KILOGRAM PER SQ. CENTIMETER
KILOGRAM
THERMAL CONDUCTIVITY
IRON PIPE SIZE
ISOMETRIC
DIAMETER, INSIDE
FACE AREA OR FRESH AIR
EXTERNAL STATIC PRESSURE
EVAPORAT (-E,-ING,-ED,-OR)
ENTERING WATER TEMP
FIRE HOSE CABINET
EXPLOSION PROOF
FHC
FA
ESP
EVAP
EWT
EFF
ENT
EQPT
EP
EFFICIENCY
ENTERING
EQUIPMENT
KG
K
IPS
ISO
ID
NIC
N.O.
NO
MPS
N.C.
N/A
MM
MPH
MIN
MAX
NOT IN CONTRACT
NORMALLY OPEN
NUMBER
NORMALLY CLOSED
METERS PER SECOND
METERS PER HOUR
MINIMUM OR MINUTE
NOT APPLICABLE
MILLIMETER
MAXIMUM
HERTZ
HOSE BIBB
HEAD
HORSEPOWER
HOUR(S)
HOT WATER
HOT WATER HEATER
HORIZONTAL
FIBERGLASS REINFORCED PLASTIC
FREQUENCY
FLUSH VALVE
FEED WATER PUMP
FIXTURE
GAGE OR GAUGE
GALVANIZED STEEL
FUEL OIL
FEMALE PIPE THREAD
CIRCULATING WATER PUMPCWP
FRP
DECIBEL OR DRY BULB
DRY BULB TEMPERATURE
ENTERING AIR TEMPERATURE
DRY PIPE VALVE
DIRECT EXPANSION
DO DIESEL OIL
EAT
DPV
DX
DIV
DIAG
DIFF
DB
DBT
DIVISION
DIAMETER
DIAGRAM
DIFFERENCE
DEGREE
HR
HZ
HW
HWH
HORIZ
HB
HD
HP
GA
GALVS
FV
FWP
FXTR
CLOCKWISE OR COLD WATERCW
PLUG VALVE
THREE WAY
FREQ
FO
FPT
GATE, GLOBE
GATE, ANGLE
GLOBE
CONTROL
GATE
M
LPS
LWT
LT
LPH
LPD
LL
LG
LBS
LAT
LAV
L
KWH
KW
LITERS PER SECOND
LITERS PER HOUR
LEAVING WATER TEMPERATURE
METERS
LAUNDRY TRAY
LITERS PER DAY
LIQUID LINE
LEAVING AIR TEMPERATURE
POUNDS
LAVATORY
LENGTH
KILOWATT HOUR
KILOWATT
LITERS
P
STRAINER, BLOW OFF
STRAINER
PUMP (INDICATE USE)
KG/ SM KILOGRAM PER SQ. METER
REFRIGERANT SUCTION
REFRIGERANT DISCHARGE
PIPE TO BE REMOVED
MEDIUM TEMPERATURE HOT WATER RETURN
MEDIUM TEMPERATURE HOT WATER SUPPLY
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
RS
RD
(NAME)
(NAME)E EXISTING PIPE
HWR
HWS
MTWR
MTWS
CR
CS
PIPING
SANITARY DRAIN
CHECK, SWING
PIPE SLEEVE WITH FIRE STOPPING
VENT THRU ROOF
BFP
PLAN
BALL
ELEV.
PIPE SLEEVE
BACKFLOW PREVENTER
FLOOR DRAIN
FLOOR CLEANOUT
FD
FCO
FLEXIBLE CONNECTOR
ANCHOR, INTERMEDIATE
ANCHOR, MAIN
EXPANSION JOINT
EXPANSION LOOP
EJ
RELIEF
SAFETY
HOSE END DRAIN
LOCK SHIELD
NEEDLE
PRESSURE REDUCING
CONTROL, PNEUMATIC-ELECTRIC
CONTROL, ELECTRIC-PNEUMATIC
CHECK, NON-SLAM
S
R
EP
PE
COLD WATER
VENT
AD FD
QUANTITY
TEMPERATURE DIFFERENCE
TONS OF REFRIGERATION
SCHEDULE
SUPPLY AIR
SANITARY
REFRIGERANT (12, 22, ETC)
RETURN AIR
REVOLUTIONS PER MINUTE
REFRIGERATION TON
RADIATOR
TYP TYPICAL
UNIT HEATER
URINAL
UH
UR
SYMBOL
TEMPERATURE
THICKNESS
TONS
THK
TEMP
SYM
TD
OUTSIDE AIR INTAKE LOUVER
PRESSURE REDUCING VALVE
PHASE (ELECTRIC)
PETROLEUM, OIL AND LUBRICANTS
POINT OF CONNECTION
PARTS PER MILLION
PERCENT/
QUART
PRESSURE GAGE
DIAMETER, OUTSIDE
OUTSIDE SCREW & YOKE
PASCAL
POLE
SPR SPRINKLER
STAINLESS STEEL
SQUARE
STEAM
STANDARD
STEEL
ST
STD
STL
SQ
SST
SPECIFICATION
SQUARE METER
STATIC PRESSURE
SPEC
SP
SM
OUTSIDE AIR
NOT TO SCALE
SECONDSEC
VAV VARIABLE AIR VOLUME
WATER CLOSET
VENTILATION
W/
WT
WC
WD
WITH
WEIGHT
WIDTH
W
WB
VOL
VEL
VENT
VERT
WATT
WET BULB
VOLUME
VELOCITY
VERTICAL
SMOKE DAMPER (PROVIDE ACCESS DOOR)
MANUAL VOLUME DAMPER
VAC
V
VACUUM
VOLT
SPLITTER DAMPER
AD
SD
VD
TEE, SINGLE SWEEP
TEE, OUTLET DOWN
REDUCER, ECCENTRIC (STRAIGHT, DOWN)
REDUCER, ECCENTRIC (STRAIGHT, INVERT)
ELBOW, TURNED DOWN
UNION, FLANGED
UNION, SCREWED
TEE, OUTLET UP
TEE
LATERAL
ELBOW, TURNED UP
CONNECTION, TOP
CONNECTION, BOTTOM
BUSHING
CAP
FIRE DAMPER (PROVIDE ACCESS DOOR)
BDD
TURNING VANES
TRANSITION
FLEXIBLE CONNECTIONFC
DUCT WORK
US ORIGIN MATERIALS:
7.
DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION OR RENOVATION.
3. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACT FIELD
CONDITIONS. SUCH DETAILS SHALL BE PREPARED IN THE FIELD BY THE CONTRACTOR
ACCORDING TO ACTUAL FIELD CONDITIONS AND SUBMITTED TO THE CONTRACTING OFFICER
GENERAL NOTES
4. CONTRACTOR SHALL SUBMIT MANUFACTURERS INSTALLATION SHOP DRAWINGS FOR APPROVAL
BY C.O.R.
8.THE CONTRACTOR SHALL BE RESPONSIBLE TO REMOVE AND REINSTALL THE OBSTRUCTED
ITEMS TO MAKE WAY FOR THE INSTALLATION AND REPLACEMENT OF MECHANICAL AND FIRE
ALARM SYSTEM WITH NO ADDITIONAL COST TO THE GOVERNMENT SUCH AS WALLS, CEILING,
ROOF, EQUIPMENT, PIPE, DUCT AND ELECTRICAL ITEMS.
2. THE CONTRACTOR SHALL BE RESPONSIBLE TO CONSTRUCT OR REPAIR ALL DAMAGES TO
EXISTING AREAS CAUSED BY THIS PROJECT AND TO MATCH CONDITION TO ADJACENT AREAS
AS DIRECTED BY THE CONTRACTOR OFFICER.
6. ALL MECHANICAL SYSTEMS SHALL BE TESTED, ADJUSTED AND BALANCED BY THE CONTRACTOR
STANDARD TECHNICAL SPECIFICATIONS FOR MISCELLANEOUS PROJECTS, KOREA.
THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE AND WORKABLE CONTROL
SYSTEM TO SATISFY ALL FUNCTIONAL REQUIREMENTS SHOWN ON DRAWING. SHOP DRAWINGS
OF THE ACTUAL PROPOSED CONTROL SYSTEM WHICH MAY DEVIATE FROM THAT SHOWN ON
CONTRACT DRAWINGS SHALL BE SUBMITTED FOR APPROVAL AS REQUIRED BY THE CONTRACT
SPECIFICATIONS.
5. THE MECHANICAL STANDARD DRAWINGS SHOWN IN THE "STANDARD DETAIL DRAWINGS
FOR O & MA PROJECTS, KOREA, OCTOBER 1, 2003 DEPARTMENT OF THE ARMY, INSTALLATION
MANAGEMENT AGENCY, KOREA REGION OFFICE" FORM AS A PART OF THIS PROJECT. THE
DETAILS WILL BE UTILIZED TO ACCOMPLISH THE MECHANICAL SCOPE OF WORK AT NO
ADDITIONAL COST TO THE PROJECT CONTRACT.
A B B R E V I A T I O N S
L E G E N D
PG
TM
AAV
FOS
3-WAY VALVE (MOTORIZED)
PRESSURE GAUGE
THERMOMETER
AUTOMATIC AIR VENT
GATE VALVE
CHECK VALVE
FUEL OIL SUPPLY
FLEXIBLE JOINTFJ
& STRAINER
M
CS
SD
SHOWER DRAIN
AS INDICATED ON THE DRAWINGS.
INTERNET SITE HTTP:// WWW.CCKBID.COM). ALL NON-GENERIC US ORIGIN MATERIALS SHALL BE
DATED FEBRUARY 2, 2004 (ELECTRONIC VERSION OF THIS DOCUMENT CAN BE FOUND AT
REGISTER OF IMA-KORO PAMPHLET 420-1 "INSPECTION OF CONSTRUCTION CONTRACTS",
ALL GENERIC US ORIGIN MATERIALS SHALL BE AS OFF-SHORE IN THE GENERIC SUBMITTAL
DEG
DIA or o
CEAT CONDENSER ENTERING AIR TEMP
LCWT LEAVING CHILLED WATER TEMP
FAIL FRESH AIR INTAKE LOUVER
EXPANSION JOINTEXPJT
EXST EXISTING
A / C AIR CONDITIONING
APPROXIMATELY
ARCH ARCHITECTURAL
BLDG BUILDING
CONC CONCRETE
DWG DRAWING
EA EACH
F.C.U. FAN COIL UNIT
MECH MECHANICAL
KCAL/ HR
KG/ SQ CM
HOT WATER SUPPLY
HOT WATER RETURN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
V
DOMESTIC HOT WATER SUPPLY
DOMESTIC HOT WATER RETURN
AAV
ED EXHAUST DUCT
AUTOMATIC AIR VENT
IN STRICT ACCORDANCE WITH APPLICABLE SECTIONS OF DIVISION 15 - MECHANICAL. O & MA
AS SHOWNAS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
DIRECTORATE OF PUBLIC WORK
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
AIR HANDLING UNIT
GROUND LEVELGL
DATE:
REGISTER, SIDEWALL
SUPPLY AIR GRILLE OR
REGISTER, CEILING
SUPPLY AIR GRILLE OR
(200mm NECK DIAMETER)
CEILING DIFFUSER, ROUND TYPE
REGISTER, CEILING
EXHAUST AIR GRILLE OR
GRILLES, REGISTERS AND DIFFUSERS
SQUARE TYPE
CEILING DIFFUSER,
EG
ER
SG
SR
SG
SR
RG
RR
CD
200mm NCD
COWL, (GOOSENECK) AND FLASHING
(810mm WIDTH x 400mm DEPTH)
DUCT SIZES SHOWN810mm x 400mm
M
ELECTRIC MOTOR OPERATED DAMPER
S
MOTORIZED DAMPER
MD
SUPPLY AIR DUCT RISER
RETURN OR EXHAUST AIR DUCT RISER
SUPPLY AIR DUCT SECTION
RETURN AIR DUCT SECTION
GATE, GLOBE OR BALL VALVE
CHECK VALVE (FLOW)
ANGLE VALVE
STRAINER
DRIP CHECK VALVE
RESTRICTED ORIFICE
FILL CUP
PRESSURE GAUGE
SOLENOID VALVE
ECCENTRIC REDUCER
CONCENTRIC REDUCER
FLEXIBLE PIPE CONNECTION
RELAY
HOSE VALVE
TEST HEADER
SMOKE DAMPER
R
SD
S
: WATER MOTER ALARM GONG
SPRINKLER SYSTEM
: UP-RIGHT TYPE SPRINKLER
: PENDENT TYPE SPRINKLER
: SIDE WALL TYPE SPRINKLER
REMOVAL WORK
RELOCATED WORK
SUPPLY AIR DUCT
RETURN AIR DUCT
EXHAUST AIR DUCT
SA
RA
EA
DEMPERS
VALVES, SPECIAL DUTY
HEATING
AIR CONDITIONING & REFRIGERATION
PLUMBING
VALVES : (for selective actuators)
BACK DRAFT DAMPER
CIRCUIT SETTER
1. THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFYING ALL EXISTING CONDITION AND
FOR APPROVAL.
POINT OF CONNECTIONPOC
POR POINT OF REMOVAL
TcH THERMOSTAT HEATING/COOLING
THERMOSTAT OF HEATING
REGISTER, CEILING
RETURN AIR GRILLE OR
Th
REDUCER, CONCENTRIC
FLEXIBLE DUCT
UNITED STATES ARMY GARRISON DAEGU
MECHANICAL
AND GENERAL NOTES
LEGEND, ABBREVIATIONS
D - 17 - 25
M-1
HA-00588-5J
AS SHOWN
25 JUL 17
HOSE BIBB
CAMP CARROLL
Nan, Tae Chin
Yi, Tong Ki
TEST CELL, BLDG. NO. S-326
RENOVATE TWO(2) ENGINE DYNAMOMETER
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNIT #15746, APO AP 96218-5746
DATE:
DIRECTORATE OF PUBLIC WORKS
CBA
D E S C R I P T I O NQ’ TY
NO.
ITEM
EQUIPMENT SCHEDULE
WORK CLASS "K" (REPAIR / MAINTENANCE WORK)
UNITED STATES ARMY GARRISON DAEGU
MECHANICAL
SCOPE OF WORK
EQUIPMENT SCHEDULE, SCOPE OF WORK, NOTE
25 JUL 17
D - 17 - 25
M-2
TYPE
TANK ENGINE DYNAMOMETER TEST CELL SYSTEM
Nan, Tae Chin
Yi, Tong Ki
CAMP CARROLL
HA-00588-5J
POWER INPUT
FAN MOTOR
FAN CAPACITY
HEATING CAPACITY
: 3 KW
: 1/100 HP, 208V, 1 PH, 60HZ
: 350 CFM, 165.2 LPS, 1,600 RPM
: 10,000 BTU/HR
ELECTRIC UNIT HEATER
(CMM)
AIR VOLUME
(mmAq)
STATIC PRESSURE
40 22
(KW)
MOTOR
(V/ O/ Hz/ W)
POWER
480/ 3/ 60/ 3 SIROCCO
SUPPLY FAN
EXHAUST FAN
DRIVE
V - BELT
TYPE
(CMM)
AIR VOLUME
(mmAq)
STATIC PRESSURE
35 22
(KW)
MOTOR
(V/ O/ Hz/ W)
POWER
480/ 3/ 60/ 3 SIROCCO
DRIVE
V - BELT1450
ENGINE EXHAUST GAS FAN
4 1
TYPE
(CMM)
AIR VOLUME
(mmAq)
STATIC PRESSURE
(KW)
MOTOR
(V/ O/ Hz/ W)
POWER
480/ 3/ 60/ 3
DRIVE
260 TURBO150 V - BELT
SUPPLY FAN
TYPE
(CMM)
AIR VOLUME
AIR FOIL FAN
COMBUSTION AIR SUPPLY A. H. U (HORIZONTAL TYPE)
(mmAq)
STATIC PRESS.
(KW)
MOTOR
5.5
LOCATION
ROOF
REMARKS
LOCATION
ROOF
REMARKS
ROOF
LOCATION REMARKS
o
TYPE
DX COIL(REF.)
(Kcal/ hr)
CAPACITY
120,000 o ( C )
EVA. TEMP.
COOLING COIL HEATING COIL
TYPE
ELEC. HEATER10
(Kcal/ hr)
CAPACITY
43,000
(KW)
POWER
(V/ O/ Hz/ W)
POWER
480/ 3/ 60/ 3
REMARKS
DOUBLE ROOF TYPE
TYPE TYPE (V/ O/ Hz/ W)
POWER
480/ 3/ 60/ 3
REMARKS
CONDENSING UNIT
TYPE
4N-20.2 (20HP)
REFRIGERATOR COMPRESSOR
(Kcal/ hr)
CAPACITY
60,000 o ( C )
EVA./ COND. TEMP.
12.5 / 50
CONDENSER
AIR COOLED
TYPE
( m )
SURFACE AREA
(KW/ EA)
FAN MOTOR
0.4 x 3EA
PREPARING FOR A RAINY SEASON
LOW PRESSURE CORRECTION DEVICE,
5 2
1 2
2 2
BRACKET, BUILT-IN CONTROLLER AND STANDARD ACCESSORIES.
MOTOR, THERMAL OVERLOAD PROTECTION, WALL MOUNTED DISCONNECT SWITCH, UNIT MOUNTED THERMOSTAT, WALL MOUNTING
HORIZONTAL DISCHARGE, TOTALLY ENCLOSED, INLET LOUVER, VENTURI AND OUTLET DIFFUSER, CONSIST OF HEATING ELEMENTS, FAN AND
SPRINKLER HEAD
" ORIFICE PENDENT TYPE FUSING POINT OF 175 F - 225 F AND APPROVED U.L. LISTED2
1STANDARD AUTO CLOSED TYPE
7 8
ALSO CONTRACTOR SHALL PERFORM THE WORK AS NOTES FOR FIRE SPRINKLER SYSTEM.
2. REPLACE DETERIORATED WET TYPE FIRE SPRINKLER HEAD WITH NEW INCLUDING ALL NECESSARY ACCESSORIES AND PARTS
"HO YOUNG ENGINEERING CO., LTD." OR APPROVED EQUAL
VIBRATION ISOLATION FUNCTION, OUTSIDE INSTALLATION
VIBRATION ISOLATION FUNCTION, OUTSIDE INSTALLATION
& TECHNICAL REVIEW BRANCH.
4. THE CONTRACTOR SHALL PERFORM PERFORMANCE TEST OF NEW TANK ENGINE DYNAMOMETER TEST CELL SYSTEM AND SUBMIT TEST REPORT TO DESIGN
300 C HEAT RESISTING PAINT
VIBRATION ISOLATION FUNCTION, OUTSIDE INSTALLATION,
(SEMI-HERMETIC)
RECIPRO.
DCS-250
TEST CELL, BLDG. NO. S-326
RENOVATE TWO(2) ENGINE DYNAMOMETER
SHEET OF10
ELECTRIC UNIT HEATER, HOSE BIBB, PIPING, VALVES, INSULATION AND ALL NECESSARY ACCESSORIES.
INCLUDING SUPPLY FAN, EXHAUST FAN, ENGINE EXHAUST GAS FAN, COMBUSTION AIR SUPPLY A. H. U, CONDENSING UNIT, ENGINE SURFACE PLATE,
1. REPLACE EXISTING DETERIORATED TANK ENGINE DYNAMOMETER TEST CELL WITH NEW TANK ENGINE DYNAMOMETER TEST CELL SYSTEM
SYSTEM TO DESIGN & TECHNICAL REVIEW BRANCH PRIOR TO CONSTRUCTION.
ALSO THE CONTRACTOR SHALL SUBMIT DETAILED SHOP DRAWING & SEQUENCE OF OPERATION DRAWING OF NEW TANK ENGINE DYNAMOMETER TEST CELL
3. THE NEW TANK ENGINE DYNAMOMETER TEST CELL SYSTEM NEED TO BE INSTALLED COMPATIBLE WITH NEW TANK ENGINE DYNAMOMETER TEST EQUIPMENT
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNIT #15746, APO AP 96218-5746
DATE:
DIRECTORATE OF PUBLIC WORKS
UNITED STATES ARMY GARRISON DAEGU
MECHANICAL
Yi, TongKi
25 JUL 17
D - 17 - 25
M-3
SCALE : 1 / 100
NEW TANK ENGINE TEST ROOMS
CBA
- M3
P-2
Nan, Tae Chin
CAMP CARROLL
HA-00588-5J
SCALE : 1 / 200- M3
P-1
CUT & CAP
REMOVE EXISTING UNIT HEATER (TYP. OF 2EA)
TEST CELL SYSTEM (TYP. OF 2SET)
REMOVE ALL TANK ENGINE DYNAMOMETER
WITH WATER PIPING
REMOVE EXISTING HOSE BIBB (TYP. OF 3EA)
REMOVE TANK ENGINE TEST ROOMS
NEW TANK ENGINE TEST ROOMS
REMOVE TANK ENGINE TEST ROOMS,
PUMP ROOM
REMOVE EXISTING FUEL OIL PIPING
IN NEW ENGINE DYNAMOMETER TEST SELL
WITH WATER PIPING & INSULATION
NEW 3/4" HOSE BIBB (TYP. OF 3EA)
TEST CELL SYSTEM (TYP. OF 2EA)
NEW ENGINE DYNAMOMETER
ELECTRIC UNIT HEATER (TYP. OF 2EA)6
POC
POC
POC
POC
RM #2
TANK DYNO
RM #1
TANK DYNO
REMAIN EXISTING FUEL OIL STORAGE TANK
CUT & CAP (TYP. OF 2EA)
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
UNIT #15746, APO AP 96218-5746
DATE:
DIRECTORATE OF PUBLIC WORKS
UNITED STATES ARMY GARRISON DAEGU
MECHANICAL
Yi, TongKi
25 JUL 17
D - 17 - 25
M-4
CBA
Nan, Tae Chin
CAMP CARROLL
HA-00588-5J
SCALE : 1 / 200- M4
P-1
PUMP ROOM 25
SPRINKLER HEAD (TYP. OF 8EA)
5. FIRE PROTECTION SYSTEM SHALL COMPLY WITH UFC 3-600-1.
NFPA 13 AND 13R.
6. AUTO SPRINKLER SYSTEM SHALL BE DESIGNED AND INSTALLED IN ACCORDANCE WITH
PREVENTION OFFICE TO COORDINATE INSPECTION OF MATERIAL.
PRIOR TO INSTALLATION TO VERIFY COMPLIANCE WITH STANDARDS. CONTACT FIRE
12. ALL EQUIPMENT AND PIPING MUST BE INSPECTED BY THE FIRE PREVENTION OFFICE
NEEDED LOCATIONS.
14. ENSURE TO INSTALL LABELED ACCESS DOORS FOR ALL THE TEST AND MAINTENANCE
NFPA 13 AND 13R.
11. SWAY BRACING FOR SPRINKLER PIPING SHALL BE PROVIDED IN ACCORDANCE WITH
NOTES FOR FIRE SPRINKLER SYSTEM:
OFFICE FOR APPROVAL PRIOR TO CONSTRUCTION.
DESIGN ANALYSIS TO DESIGN & TECHNICAL REVIEW BRANCH AND FIRE PREVENTION
CONSTRUCTION. THE CONTRACTOR SHALL SUBMIT DETAILED SHOP DRAWINGS AND
MEET WITH APPLICABLE CODES AND REGULATIONS TO COMPLETE SUBJECT PROJECT
COST CAUSED FROM NOT SHOWN OR/AND INDICATED IN THE CONCEPTUAL DRAWINGS TO
IGCE PURPOSE ONLY. THE CONTRACTOR IS RESPONSIBLE FOR ALL OTHER ADDITIONAL
1. THE FIRE SPRINKLER SYSTEM ROUTING AND PIPE SIZES SHOWN ARE CONCEPTUAL FOR
AND EQUIPMENT LISTS.
SHALL BE IN ACCORDANCE WITH APPLICABLE CODES, MANUFACTURER’S RECOMMENDATIONS
2. ALL EQUIPMENT SHOWN IN SUGGESTED LOCATIONS, FINAL QUANTITY AND LAYOUT
3. COORDINATE EQUIPMENT LOCATIONS WITH LIGHTING AND HVAC SYSTEMS.
USED PROVIDED IT MEETS UL OR/AND FM REQUIREMENTS).
4. ALL EQUIPMENT TO BE UL LISTED OR FM APPROVED (LOCAL EQUIPMENT MAYBE
FIRE PREVENTION OFFICE PRIOR TO IMPLEMENTATION.
PLAN, THE CHANGE SHALL BE APPROVED TO DESIGN & TECHNICAL REVIEW BRANCH AND
7. IF FIELD CONDITIONS NECESSITATE SIGNIFICANT CHANGE FROM APPROVED
VERIFICATION.
FAILURE TO DO THIS WILL REQUIRE THE CONTRACTOR TO RE-EXPOSE THE PIPING FOR
PIPE THAT SUPPLIES THE AUTOMATIC FIRE EXTINGUISHING SYSTEM / STANDPIPE SYSTEM.
8. THE FIRE INSPECTOR SHALL PERFORM A VISUAL INSPECTION OF ALL UNDERGROUND
SPRINKLER HEAD IN THE SYSTEM.
RISER WILL RESULT IN FLUSHING THE ABOVEGROUND SPRINKLER SYSTEM THROUGH EVERY
SYSTEM. FAILURE TO FLUSH UNDERGROUND FIRE LINE PRIOR TO "STACKING" THE SPRINKLER
GROUND PIPES WHICH SUPPLY THE AUTOMATIC FIRE-EXTINGUISHING SYSTEM/ STANDPIPE
9. THE FIRE INSPECTOR MUST WITNESS A HYDROSTATIC TEST AND FLUSH OF ALL UNDER-
POSITION.
INSPECTOR TEST VALVES AND/OR MAIN DRAIN. FULLY LABEL ALL VALVES AND NORMAL
13. ENSURE ALL PIPING IS SLOPED TO ALLOW 100 PERCENT DRAINING OF SYSTEM FROM
ETC. FAILURE TO INSPECTION WILL RESULT IN RESCHEDULING INSPECTION.
SPRINKLER PIPE, NAIL PLATES IF REQUIRED, LOCATION OF FIRE DEPARTMENT CONNECTIONS, CLIPS IF REQUIRED, PLACEMENT & TYPE OF SPRINKLER HEADS, FIRE CAULKING AROUND
10. AT THE TIME OF THE TEST, THE INSPECTOR SHALL CHECK PIPE SIZE, PIPE HANGERS, SURGE
REPLACE SPRINKLER HEAD PLAN
REPLACE SPRINKLER HEAD PLAN
NOTES FOR FIRE SPRINKLER SYSTEM,
TEST CELL, BLDG. NO. S-326
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNIT #15746, APO AP 96218-5746
DATE:
DIRECTORATE OF PUBLIC WORKS
UNITED STATES ARMY GARRISON DAEGU
MECHANICAL
Yi, TongKi
25 JUL 17
D - 17 - 25
M-5
CBA
Nan, Tae Chin
CAMP CARROLL
HA-00588-5J
SCALE : 1 / 50- M5
P-1 NEW ENGINE DYNAMOMETER TEST CELL SYSTEM
FUEL OIL PIPING 15 mm WITH 4EA AAV
(TYP.)
HOOD - 2850x2850
SILENCER (TYP.)
ENGINE EXHAUST PIPE (TYP.)
RM #1
TANK DYNO
DUCT 1400x1200 (TYP.)
FLEXIBLE DUCT D300 (TYP.)
CONNECT EXISTING COMP. AIR LINE (TYP.)
DOOR
GL
100mm (TYP.)
BURIAL GROUND
F O
S
FOS FOS
CONTROL RM.
& CASING (TYP.)
DUCT 400 x 400 W/ INSULATION
FUEL OIL PIPE 15A
COMP. AIR LINE 15A
OIL TANK
EXISTING FUEL
RM #2
TANK DYNO
NEW ENGINE DYNAMOMETER TEST CELL SYSTEM
STEEL PLATE (TYP.)
CONDENSING UNIT W/ CONC. PAD (TYP. OF 2EA)
W/ CONC. PAD
COMBUSTION AIR SUPPLY A. H. U
THROUGH THE DOOR (TYP.)
BEND WHEN THE OIL PIPE PASSES
FRL UNIT (TYP.)
REMOTE CONTROL PANEL(TOUCH SCREEN TYPE)
MCC PANEL #1 MCC PANEL #2
TEST CELL, BLDG. NO. S-326
RENOVATE TWO(2) ENGINE DYNAMOMETER
SHEET OF
ENGINE SURFACE PLATE SIZE 2,400 x 4,000
MORE THAN AIR SUPPLY 6BAR
AIR SPRING INSULATOR - 4SET
L-50x50x6t L-50x50x6t
ENGINE SURFACE PLATE60x60x2.9t OR ANGLE
PLAT BAR - W20x6t
ROUND BAR 8o LUG 10o
STEEL PLATE 3.2t
PIT COVER CHECK PLATE 6t
PLAT BAR - W30x6t
ENGINE SURFACE PLATE SIZE 2,400 x 4,000
30 (PLAT BAR)
DUCT 1500 x 1500 (TYP.)
NEW ENGINE SURFACE PLATE DETAIL
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNIT #15746, APO AP 96218-5746
DATE:
DIRECTORATE OF PUBLIC WORKS
UNITED STATES ARMY GARRISON DAEGU
MECHANICAL
Yi, TongKi
25 JUL 17
D - 17 - 25
M-6
CBA
Nan, Tae Chin
CAMP CARROLL
HA-00588-5J
SCALE : 1 / 50- M6
P-1 NEW ABOVE THE CEILING OF ENGINE DYNAMOMETER TEST CELL SYSTEM
DUCT 1600x1600
DUCT 1500x1500
SUPPLY FAN SUPPORTER
TUBULAR DILATATION D500 (TYP.)
1 SUPPLY FAN (TYP. OF 2EA)
EXHAUST FAN (TYP. OF 2EA)2
3 ENGINE EXHAUST GAS FAN (TYP. OF 2EA)
DYNAMOMETER TEST CELL SYSTEM
NEW ABOVE THE CEILING OF ENGINE
TEST CELL, BLDG. NO. S-326
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNIT #15746, APO AP 96218-5746
DATE:
DIRECTORATE OF PUBLIC WORKS
UNITED STATES ARMY GARRISON DAEGU
MECHANICAL
Yi, TongKi
25 JUL 17
D - 17 - 25
M-7
CBA
Nan, Tae Chin
CAMP CARROLL
HA-00588-5J
M
M
M
ENGINE
HC
DYNAMO
M
ENGINE
HC
DYNAMO
1 SUPPLY FAN
FLOW DURING WINTER SEASON
AUTOMATIC CONTROL OF AIR
O. A
INV INV INV INV
O. AE. A E. A
2 EXHAUST FAN 2 EXHAUST FAN 1 SUPPLY FAN
FLOW DURING WINTER SEASON
AUTOMATIC CONTROL OF AIR
FLOW DURING WINTER SEASON
AUTOMATIC CONTROL OF AIR
FLOW DURING WINTER SEASON
AUTOMATIC CONTROL OF AIR
- M7
P-1 TEST CELL VENTILATION SYSTEM
NOT TO SCALE
TANK DYNO RM #1 TANK DYNO RM #2
TEST CELL VENTILATION SYSTEM
TEST CELL, BLDG. NO. S-326
RENOVATE TWO(2) ENGINE DYNAMOMETER
INVERTER INVERTER INVERTER INVERTER
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNIT #15746, APO AP 96218-5746
DATE:
DIRECTORATE OF PUBLIC WORKS
UNITED STATES ARMY GARRISON DAEGU
MECHANICAL
Yi, TongKi
25 JUL 17
D - 17 - 25
M-8
CBA
Nan, Tae Chin
CAMP CARROLL
HA-00588-5J
- M8
P-1 COMBUSTION AIR SUPPLY SYSTEM
NOT TO SCALE
F C
P
S
C
S
MM
ENGINE
HC
DYNAMO
ENGINE
HC
DYNAMO
CONDENSING UNIT
COMBUSTION AIR SUPPLY A. H. U 4
5 CONDENSING UNIT5
150 CMM
DRAIN
LESS THAN 30 C
o
C
M M
C
M M
TANK DYNO RM #1 TANK DYNO RM #2
INSULATION 20T
COMBUSTION AIR SUPPLY SYSTEM
TEST CELL, BLDG. NO. S-326
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNIT #15746, APO AP 96218-5746
DATE:
DIRECTORATE OF PUBLIC WORKS
UNITED STATES ARMY GARRISON DAEGU
MECHANICAL
Yi, TongKi
25 JUL 17
D - 17 - 25
M-9
CBA
Nan, Tae Chin
CAMP CARROLL
HA-00588-5J
- M9
P-1
NOT TO SCALE
C
M M
C
M M
ENGINE
HC
DYNAMO
ENGINE
HC
DYNAMO
3 ENGINE EXHAUST GAS FAN 3 ENGINE EXHAUST GAS FAN
ENGINE GAS EXHAUST SYSTEM
TANK DYNO RM #1 TANK DYNO RM #2
SILENCER (TYP.)
(TYP.)
C. W INSULATION
ENGINE GAS EXHAUST SYSTEM
TEST CELL, BLDG. NO. S-326
AND THE COLOR OF TOGGLE SWITCHES AND RECEPTACLE SHALL BE GRAY.
ALL COVER PLATES OF RECEPTACLES AND SWITCHES SHALL BE STAINLESS STEEL METALLIC ONES
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
ELECTRICAL
KIM, CK
E-1AS SHOWN
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISION DAEGU
DIRECTORATE OF PUBLIC WORK
UNIT #15746, APO AP 96218-5746
DATE:
N O T E S
3.
2.
4. MOUNTING HEIGHTS ARE AS BELOW. MEASUREMENT IS TO CENTER OF OUTLET.
WIRES IS INDICATED AS FOLLOW;
AND ONE (1)-#12AWG GROUND WIRE IN 16mm CONDUIT. A GREATER NUMBER OF
ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES TWO (2)-#12AWG WIRES
3-#12AWG WIRES AND 1-#12AWG GROUND WIRE IN 16mm CONDUIT.
4-#12AWG WIRES AND 1-#12AWG GROUND WIRE IN 16mm CONDUIT.
FIRE ALARM CONTROL PANEL----------------------------5’-0" ABOVE FLOOR
MANUAL PULL STATION----------------------------------4’-6" ABOVE FLOOR
FIRE ALARM BELL---------------------------------------7’-0" ABOVE FLOOR
LIGHTING FIXTURE--------------------SEE LIGHTING FIXTURE SCHEDULE
TOGGLE SWITCH-----------------------1220mm TO CENTER OF THE OUTLET
RECEPTACLE---------------------------460mm TO CENTER OUTLET
PANELBOARD, CIRCUIT BREAKER------------------------SEE SPECIFICATION
CAULKING MATERIAL SHALL BE VERIFIED BY F&ES OFFICE PRIOR TO CONSTRUCTION.
BOTH SIDE OF FIRE WALLS, FIRE-PARTITIONS AND FIRE-RATED PIPE CHASE WALLS.
ALL PIPE PENETRATIONS SHALL BE SEALED WITH FIRE RATED CAULKING MATERIAL ON
1.
SPECIFICATIONS FOR O&MA PROJECTS, AND SPECIFICATIONS.
ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE, FIRE CODE, TECHNICAL STANDARD
ALL ELECTRICAL WORK SHALL CONFORM TO THE LATEST REQUIREMENTS OF THE NATIONAL
CONDUIT WHICH IS TO BE BONDED TO THE MAIN GROUNDING SYSTEM AT BOTH ENDS.
GROUNDING WIRE SHALL BE GREEN INSULATED COPPER WIRE IN RIGID GALVANIZED STEEL
ALL WIRING SHALL BE CONCEALED ABOVE THE CEILING WHEN THE ROOM HAS A CEILING.
US ORIGIN MATERIAL:
ALL NON-GENERIC US ORIGIN MATERIALS SHALL BE AS INDICATED ON THE DRAWINGS.
INTERNET SITE http// 147.242.150.235/03%20headquarters/dbo/eps-page/trd-mission-R&D.html).
DATED FEBRURY 2, 2004 (ELECTRONIC VERSION OF THIS DOCUMENT CAN BE FOUND AT
REGISTER OF IMA-KORO PAMPHLET 420-1 "INSPECTION OF CONSTRUCTION CONTRACTS
ALL GENERIC US ORIGIN MATERIALS SHALL BE IDENTIFY AS OFF-SHORE IN THE GENERIC SUBMITAL
MAGNETIC MOTOR STARTER
RECEPTACLE, DUPLEX, 2P-3W-20A-250V, GRD’G, KOREAN TYPE.
L E G E N D
NEWEXSTREMOVE
RECEPTACLE, DUPLEX, 2P-3W-20A-125V, GRD’G TYPE.
S
PANELBOARD OR LOAD CENTER
GROUND-FAULT CIRCUIT-INTERRUPTING TYPE.
RECEPTACLE, DUPLEX, 2P-3W-20A-125V,
SS
J
JUNCTION BOX
+ WIRING CONCEALED IN UNDERGROUND
HOMERUN CIRCUIT TO PANELBOARD OR ENCLOSURE
WIRING CONCEALED IN CEILINGS AND WALL
WIRING EXPOSED ON CEILINGS AND WALL
1.6
1.6M ABOVE FLOOR
///// C C CONTROL CIRCUITC
TOGGLE SWITCH, 1P-20A-120/277V.
SCOPE OF WORK
CAMP CARROLL
SHEET OF
HA-00588-5J
1.
5.
6.
7.
EXIT LIGHT, SINGLE FACE, WALL MOUNT TYPE
A. REPAIR/MAINTENANCE
25 JUL 17
WITH 2/28W, T-8 LAMPS & ELECTRONIC BALLAST.
FLUORESCENT LIGHTING FIXTURE 1’ X 4’, 120VAC,
T-8 LAMPS & ELECTRONIC BALLAST AND EMERGENCY UNIT.
W2/ 28FLUORESCENT LIGHTING FIXTURE 1’ X 4’, 120VAC, WITH
SIN, YS
WITH…