SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
R-11SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
O & M
HOUSING DIV.
REVIEWED BY
AS SHOWN
UNITED STATES ARMY GARRISON DAEGU
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
DIRECTORATE OF PUBLIC WORK
HGFEDCBA
T I T L E S H E E T
D - 17 - 24
O, KI TAL
CHON, HYON TAE
DESIGN REVIEW SIGNATURE
ORGANIZATION
USING AGENCY
36TH SIGNAL
MASTER PLN.
ENVIRONMENTAL
NAME SIGNATURE
O&M DIV.
FIRE DEPT.
SAFETY OFFICE
DPTMS(AT/FP)
188TH MP COM.
IND. HYGENIST
HA-00556-5J
UNIT #15746, APO AP 96218-5746
M - 1
R - 1
DRAWING NO.
CHIEF,
DESIGN & TECH. REVIEW Br.
TITLE SHEET
DATE: 25 JUL 17
M - 2
M - 3
M - 45
M - 56
BLDG. NO. T-317 (MSC-K)
REPLACE COOLING TOWER,
PROJECT NO. HA-00556-5J, CAMP CARROLL
BLDG. NO. T-317 (MSC-K)
REPLACE COOLING TOWER,
CAMP CARROLL
M - 67 6 OF 7
M - 78 7 OF 7
MECHANICAL
LEGEND AND ABBREVIATIONS
GENERAL NOTES, US ORIGIN MATERIALS
EQUIPMENT SCHEDULE, SCOPE OF WORK
REMOVE EXISTING COOLING TOWER & PUMP ROOM PLAN
NEW PUMP ROOM ISOMETRIC DIAGRAM
NEW COOLING SYSTEM ISOMETRIC DIAGRAM, SEQUENCE OF OPERATION, PRESSURE SWITCH SCHEDULE
NEW COOLING TOWER & PUMP ROOM PLAN, UNIT HEATER POWER PLAN
SCH
SA
SAN
QTY
R12, R22
RA
RDTR
RPM
RT
PG
PH
POC
POL
PPM
PRV
QT
OA
OAIL
OD
OS&Y
Pa
NTS
BUTTERFLY
CUBIC METER PER HOUR
AIR CONDITION (-ING,-ED)
AIR CONDITION UNIT (S)
AIR COOLED CONDENSING UNIT
CHILLED/HOT WATER RETURN
CHILLED/HOT WATER SUPPLY
REFRIGERANT LIQUID
CAP CAPACITY
CUBIC METER
COMPRESSOR
CONTINUE
CONNECTION
CPRSR
CU M
CONT
CONN
COUNTER CLOCKWISE
COEFFICIENT
CIRCUIT
CAST IRON PIPE
CHILLED WATER
CKT
CMH
COEF
CHW
CCW
CIP
ALARM CHECK VALVEACV
AVG AVERAGE
BAROMETER(-TRIC)
CENTIGRADEC
BARO
AMPERE(AMP, AMPS)
ALUMINUM
APPROX
AMP
AIR COND
AHU
AL
AIR COOLED
ACU
ACLD
ACCU
CHWS
CHWR
CHR
CHS
D
RL
DRAIN
KILOCALORIE PER HOUR
KILOGRAM PER SQ. CENTIMETER
KILOGRAM
THERMAL CONDUCTIVITY
IRON PIPE SIZE
ISOMETRIC
DIAMETER, INSIDE
FACE AREA OR FRESH AIR
EXTERNAL STATIC PRESSURE
EVAPORAT (-E,-ING,-ED,-OR)
ENTERING WATER TEMP
FIRE HOSE CABINET
EXPLOSION PROOF
FHC
FA
ESP
EVAP
EWT
EFF
ENT
EQPT
EP
EFFICIENCY
ENTERING
EQUIPMENT
KG
K
IPS
ISO
ID
NIC
N.O.
NO
MPS
N.C.
N/A
MM
MPH
MIN
MAX
NOT IN CONTRACT
NORMALLY OPEN
NUMBER
NORMALLY CLOSED
METERS PER SECOND
METERS PER HOUR
MINIMUM OR MINUTE
NOT APPLICABLE
MILLIMETER
MAXIMUM
HERTZ
HOSE BIBB
HEAD
HORSEPOWER
HOUR(S)
HOT WATER
HOT WATER HEATER
HORIZONTAL
FIBERGLASS REINFORCED PLASTIC
FREQUENCY
FLUSH VALVE
FEED WATER PUMP
FIXTURE
GAGE OR GAUGE
GALVANIZED STEEL
FUEL OIL
FEMALE PIPE THREAD
CIRCULATING WATER PUMPCWP
FRP
DECIBEL OR DRY BULB
DRY BULB TEMPERATURE
ENTERING AIR TEMPERATURE
DRY PIPE VALVE
DIRECT EXPANSION
DO DIESEL OIL
EAT
DPV
DX
DIV
DIAG
DIFF
DB
DBT
DIVISION
DIAMETER
DIAGRAM
DIFFERENCE
DEGREE
HR
HZ
HW
HWH
HORIZ
HB
HD
HP
GA
GALVS
FV
FWP
FXTR
CLOCKWISE OR COLD WATERCW
PLUG VALVE
THREE WAY
FREQ
FO
FPT
GATE, GLOBE
GATE, ANGLE
GLOBE
CONTROL
GATE
M
LPS
LWT
LT
LPH
LPD
LL
LG
LBS
LAT
LAV
L
KWH
KW
LITERS PER SECOND
LITERS PER HOUR
LEAVING WATER TEMPERATURE
METERS
LAUNDRY TRAY
LITERS PER DAY
LIQUID LINE
LEAVING AIR TEMPERATURE
POUNDS
LAVATORY
LENGTH
KILOWATT HOUR
KILOWATT
LITERS
P
STRAINER, BLOW OFF
STRAINER
PUMP (INDICATE USE)
KG/ SM KILOGRAM PER SQ. METER
REFRIGERANT SUCTION
REFRIGERANT DISCHARGE
PIPE TO BE REMOVED
MEDIUM TEMPERATURE HOT WATER RETURN
MEDIUM TEMPERATURE HOT WATER SUPPLY
CONDENSER WATER RETURN
CONDENSER WATER SUPPLY
RS
RD
(NAME)
(NAME)E EXISTING PIPE
HWR
HWS
MTWR
MTWS
CR
CS
PIPING
SANITARY DRAIN
CHECK, SWING
PIPE SLEEVE WITH FIRE STOPPING
VENT THRU ROOF
BFP
PLAN
HOSE BIBB
BALL
ELEV.
PIPE SLEEVE
BACKFLOW PREVENTER
FLOOR DRAIN
FLOOR CLEANOUT
FD
FCO
FLEXIBLE CONNECTOR
ANCHOR, INTERMEDIATE
ANCHOR, MAIN
EXPANSION JOINT
EXPANSION LOOP
EJ
RELIEF
SAFETY
HOSE END DRAIN
LOCK SHIELD
NEEDLE
PRESSURE REDUCING
CONTROL, PNEUMATIC-ELECTRIC
CONTROL, ELECTRIC-PNEUMATIC
CHECK, NON-SLAM
S
R
EP
PE
COLD WATER
VENT
AD FD
QUANTITY
TEMPERATURE DIFFERENCE
TONS OF REFRIGERATION
SCHEDULE
SUPPLY AIR
SANITARY
REFRIGERANT (12, 22, ETC)
RETURN AIR
REVOLUTIONS PER MINUTE
REFRIGERATION TON
RADIATOR
TYP TYPICAL
UNIT HEATER
URINAL
UH
UR
SYMBOL
TEMPERATURE
THICKNESS
TONS
THK
TEMP
SYM
TD
OUTSIDE AIR INTAKE LOUVER
PRESSURE REDUCING VALVE
PHASE (ELECTRIC)
PETROLEUM, OIL AND LUBRICANTS
POINT OF CONNECTION
PARTS PER MILLION
PERCENT/
QUART
PRESSURE GAGE
DIAMETER, OUTSIDE
OUTSIDE SCREW & YOKE
PASCAL
POLE
SPR SPRINKLER
STAINLESS STEEL
SQUARE
STEAM
STANDARD
STEEL
ST
STD
STL
SQ
SST
SPECIFICATION
SQUARE METER
STATIC PRESSURE
SPEC
SP
SM
OUTSIDE AIR
NOT TO SCALE
SECONDSEC
VAV VARIABLE AIR VOLUME
WATER CLOSET
VENTILATION
W/
WT
WC
WD
WITH
WEIGHT
WIDTH
W
WB
VOL
VEL
VENT
VERT
WATT
WET BULB
VOLUME
VELOCITY
VERTICAL
SMOKE DAMPER (PROVIDE ACCESS DOOR)
MANUAL VOLUME DAMPER
VAC
V
VACUUM
VOLT
SPLITTER DAMPER
AD
SD
VD
TEE, SINGLE SWEEP
TEE, OUTLET DOWN
REDUCER, ECCENTRIC (STRAIGHT, DOWN)
REDUCER, ECCENTRIC (STRAIGHT, INVERT)
ELBOW, TURNED DOWN
UNION, FLANGED
UNION, SCREWED
TEE, OUTLET UP
TEE
LATERAL
ELBOW, TURNED UP
CONNECTION, TOP
CONNECTION, BOTTOM
BUSHING
CAP
FIRE DAMPER (PROVIDE ACCESS DOOR)
BDD
TURNING VANES
TRANSITION
FLEXIBLE CONNECTION
FLEXIBLE DUCT
FC
DUCT WORK
A B B R E V I A T I O N S
L E G E N D
PG
TM
AAV
FOS
3-WAY VALVE (MOTORIZED)
PRESSURE GAUGE
THERMOMETER
AUTOMATIC AIR VENT
GATE VALVE
CHECK VALVE
FUEL OIL SUPPLY
FLEXIBLE JOINTFJ
& STRAINER
M
CS
SD
SHOWER DRAIN
DEG
DIA or o
CEAT CONDENSER ENTERING AIR TEMP
LCWT LEAVING CHILLED WATER TEMP
FAIL FRESH AIR INTAKE LOUVER
EXPANSION JOINTEXPJT
EXST EXISTING
A / C AIR CONDITIONING
APPROXIMATELY
ARCH ARCHITECTURAL
BLDG BUILDING
CONC CONCRETE
DWG DRAWING
EA EACH
F.C.U. FAN COIL UNIT
MECH MECHANICAL
KCAL/ HR
KG/ SQ CM
HOT WATER SUPPLY
HOT WATER RETURN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
V
DOMESTIC HOT WATER SUPPLY
DOMESTIC HOT WATER RETURN
AAV
ED EXHAUST DUCT
AUTOMATIC AIR VENT
AIR HANDLING UNIT
GROUND LEVELGL
REGISTER, SIDEWALL
SUPPLY AIR GRILLE OR
REGISTER, CEILING
SUPPLY AIR GRILLE OR
(200mm NECK DIAMETER)
CEILING DIFFUSER, ROUND TYPE
REGISTER, CEILING
EXHAUST AIR GRILLE OR
GRILLES, REGISTERS AND DIFFUSERS
SQUARE TYPE
CEILING DIFFUSER,
EG
ER
SG
SR
SG
SR
RG
RR
CD
200mm NCD
COWL, (GOOSENECK) AND FLASHING
(810mm WIDTH x 400mm DEPTH)
DUCT SIZES SHOWN810mm x 400mm
M
ELECTRIC MOTOR OPERATED DAMPER
S
MOTORIZED DAMPER
MD
SUPPLY AIR DUCT RISER
RETURN OR EXHAUST AIR DUCT RISER
SUPPLY AIR DUCT SECTION
RETURN AIR DUCT SECTION
GATE, GLOBE OR BALL VALVE
CHECK VALVE (FLOW)
ANGLE VALVE
STRAINER
DRIP CHECK VALVE
RESTRICTED ORIFICE
FILL CUP
PRESSURE GAUGE
SOLENOID VALVE
ECCENTRIC REDUCER
CONCENTRIC REDUCER
FLEXIBLE PIPE CONNECTION
RELAY
HOSE VALVE
TEST HEADER
SMOKE DAMPER
R
SD
S
: WATER MOTER ALARM GONG
SPRINKLER SYSTEM
: UP-RIGHT TYPE SPRINKLER
: PENDENT TYPE SPRINKLER
: SIDE WALL TYPE SPRINKLER
REMOVAL WORK
RELOCATED WORK
SUPPLY AIR DUCT
RETURN AIR DUCT
EXHAUST AIR DUCT
SA
RA
EA
DEMPERS
VALVES, SPECIAL DUTY
HEATING
AIR CONDITIONING & REFRIGERATION
PLUMBING
VALVES : (for selective actuators)
BACK DRAFT DAMPER
CIRCUIT SETTER
POINT OF CONNECTIONPOC
POR POINT OF REMOVAL
TcH THERMOSTAT HEATING/COOLING
THERMOSTAT OF HEATING
REGISTER, CEILING
RETURN AIR GRILLE OR
Th
REDUCER, CONCENTRIC
NAM, TAE CHIN
H
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
LEGEND AND ABBREVIATIONS
M-1
D - 17 - 24
YI, TONG KI
CAMP CARROLL
G
HA-00556-5J
25 JUL 17
BLDG. NO. T-317 (MSC-K)
REPLACE COOLING TOWER,
1 7
GENERAL NOTES
DUCTWORK SHALL BE PATCHED OR RESTORED TO MATCH THE ADJACENT SURFACE OR AREA.
4. ALL WALL / FLOOR / ROOF OPENINGS RESULTING FROM THE REMOVAL OF PIPING AND
AS DIRECTED BY THE CONTRACTING OFFICER.
EXISTING AREAS CAUSED BY THIS PROJECT AND TO MATCH CONDITION TO ADJACENT AREAS
5. THE CONTRACTOR SHALL BE RESPONSIBLE TO CONSTRUCT OR REPAIR ALL DAMAGES TO
CEILING, ROOF, EQUIPMENT, PIPE, DUCT AND ELECTRICAL ITEMS.
PREVENTION SYSTEM WITH NO ADDITIONAL COST TO THE GOVERNMENT SUCH AS WALLS,
ITEMS TO MAKE WAY FOR THE INSTALLATION AND REPLACEMENT OF MECHANICAL AND FIRE
18. THE CONTRACTOR SHALL BE RESPONSIBLE TO REMOVE AND REINSTALL THE OBSTRUCTED
SPECIFICATIONS.
CONTRACT DRAWINGS SHALL BE SUBMITTED FOR APPROVAL AS REQUIRED BY THE CONTRACT
OF THE ACTUAL PROPOSED CONTROL SYSTEM WHICH MAY DEVIATE FROM THAT SHOWN ON
SYSTEM TO SATISFY ALL FUNCTIONAL REQUIREMENTS SHOWN ON DRAWING. SHOP DRAWINGS
17. THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE AND WORKABLE CONTROL
9. ANY PIPES THAT PENETRATE FIRE RATED WALLS (EXISTING/ NEW) SHALL BE SEALED PER SPEC.
TO ENSURE PROPER OPERATION, AS ORIGINALLY INTENDED.
EQUIPMENT. THE CONTRACTOR SHALL TEST, ADJUST AND BALANCE EQUIPMENT AS REQUIRED
14. THE CONTRACTOR SHALL PROVIDE ALL NECESSARY START-UP AND TESTING OF THE NEW
AND SHALL BE VERIFIED AT THE JOB SITE.
2. LOCATION AND SIZES OF EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC, ARE APPROXIMATE
PRIOR TO COMMENCING CONSTRUCTION FOR APPROVAL.
ACCORDING TO ACTUAL FIELD CONDITIONS AND SUBMITTED TO THE CONTRACTING OFFICER
FIELD CONDITIONS. SUCH DETAILS SHALL BE PREPARED IN THE FIELD BY THE CONTRACTOR
3. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACTLY TO THE
CONTRACTING OFFICER’S APPROVAL.
REPRESENTATIVE ATTENTION WITH RECOMMENDATIONS FOR PROPER CORRECTIONS FOR
IF ANY DISCREPANCY IS DETECTED, IT SHOULD BE BROUGHT TO THE CONTRACTING OFFICER’S
PRIOR TO COMMENCING ANY CONSTRUCTION OR REPAIR.
EQUIPMENT, DUCTWORK, PIPING, DIMENSIONS AND ETC. UNDER THE SUPERVISION OF C.O.R
1. THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFYING ALL EXISTING CONDITION,
A SHOP DRAWING SHALL NOT BE THE EXACT DUPLICATION OF THE CONTRACT DRAWING.
10. NO MECHANICAL WORK CAN BE STARTED WITHOUT AN APPROVED SHOP DRAWING.
THE REQUIREMENTS OF SEAL CLASS C.
TO SMACNA STATIC PRESSURE CONSTRUCTION CLASS 500PA AND DUCTWORK SHALL MEET
7. THE SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED ACCORDING
START OF CONSTRUCTION.
PLAN SHALL BE SUBMITTED TO AND APPROVED BY DPW AND THE USER, PRIOR TO THE
USER TO FULLY UTILIZE THE FACILITY DURING THE CONSTRUCTION PERIOD. THIS PHASING
SHALL PROVIDE A PHASING PLAN FOR CONSTRUCTION COMPLETION ALLOWING FOR THE
FACILITY BE FULLY OPERATIONAL DURING THE CONSTRUCTION PERIOD, THE CONTRACTOR
19. DUE TO THE CRITICAL NATURE OF THE FACILITY FUNCTION, IF IT IS REQUIRED THAT THE
CONTRACTOR.
THE WORK PERFORMED UNDER THIS CONTRACT SHALL BE REPAIRED OR REPLACED BY THIS
THE EXISTING EQUIPMENT, NEW EQUIPMENT, DUCT WORK, PIPING AND ETC. DAMAGES DUE TO
11. CONNECTIONS TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE
FOR APPROVAL.
DESIGN & TECHNICAL REVIEW BRANCH VIA C.O.R. PRIOR TO COMMENCING CONSTRUCTION
12. THE CONTRACTOR SHALL SUBMIT MANUFACTURER’S INSTALLATION SHOP DRAWINGS TO THE
AS INDICATED ON THE DRAWINGS.
INTERNET SITE HTTP:// WWW.CCKBID.COM). ALL NON-GENERIC US ORIGIN MATERIALS SHALL BE
DATED FEBRUARY 2, 2004 (ELECTRONIC VERSION OF THIS DOCUMENT CAN BE FOUND AT
REGISTER OF IMA-KORO PAMPHLET 420-1 "INSPECTION OF CONSTRUCTION CONTRACTS",
ALL GENERIC US ORIGIN MATERIALS SHALL BE AS OFF-SHORE IN THE GENERIC SUBMITTAL
SPECIFICATIONS FOR O & MA PROJECTS, KOREA (REVISION 1 - 20151030)".
15. ALL EQUIPMENT AND MATERIALS SHALL MEET THE REQUIREMENTS OF "STANDARD TECHNICAL
ADDITIONAL COST TO THE PROJECT CONTRACT.
THE DETAILS WILL BE UTILIZED TO ACCOMPLISH THE MECHANICAL SCOPE OF WORK AT NO
O & MA PROJECTS, KOREA (NOVEMBER 30, 2015)" FORM AS A PART OF THIS PROJECT.
16. THE MECHANICAL STANDARD DRAWINGS SHOWN IN THE "STANDARD DETAIL DRAWINGS FOR
REVIEW BRANCH FOR APPROVAL BEFORE COMMENCING THE WORK.
13. THE CONTRACTOR SHALL SUBMIT ALL MATERIAL INFORMATION TO THE DESIGN & TECHNICAL
SUCH AS ANCHORS, HANGERS, SUPPORTS, ETC.
8. ALL PIPES, DRAINS AND DUCTWORK TO BE REMOVED SHALL INCLUDE ALL ITS ACCESSORIES
AS ORIGINALLY INTENDED.
AND INSTALL NEW DUCTWORK AND MAKE ALL NECESSARY DUCT CONNECTION TO FUNCTION
ELEVATION IS CONFLICTED WITH NEW PIPING INSTALLATION, REMOVE THE EXISTING DUCTWORK
& LOCATION PRIOR TO INSTALL NEW HVAC AND PLUMBING PIPING. IF THE EXISTING DUCT
6. THE CONTRACTOR SHALL COORDINATE WITH THE EXISTING DUCTWORK AND PIPING ELEVATION
H
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-2
D - 17 - 24
G
CAMP CARROLL
YI, TONG KI
NAM, TAE CHIN
US ORIGIN MATERIALS:
US ORIGIN MATERIALS
GENERAL NOTES,
YI, TONG KI
NAM, TAE CHIN
25 JUL 17
HA-00556-5J
BLDG. NO. T-317 (MSC-K)
2 7
SCOPE OF WORK
WORK CLASS "K" (REPAIR / MAINTENANCE WORK)
1 1
Q’ TY
NO.
ITEM
D E S C R I P T I O N
3 1 JOCKEY PUMP
FLANGED CONNECTION, ON CAST IRON BASE
IN-LINE CLOSED COUPLED CENTRIFUGAL TYPE, SINGLE STAGE END SUCTION,
PUMP MOTOR
PUMP CAPACITY
: 1 HP, 220 V, 3 PH, 60HZ
: 3 GPM, 184 FT TDH, 1750 RPM
ADJUST PRESSURE RANGE : RELIEF PRESSURE RANGE - 0 TO 75 PSI
03 STAINLESS STEEL TRIM
MAIN VALVE TRIM - CAST BRONZE ASTE B62 WITH
MATERIALS: MAIN VALVE BODY & COVER - CAST IRON ASTM A48
TEMPERATURE RANGE: WATER - TO 180 F MAX
PRESSURE RATING: 125 CLASS - 175 PSI MAX
VALVE SIZE: GLOBE 100 FLANGED
A PILOT CONTROL SYSTEM
IN OPERATION THE VALVE IS ACTUATED BY LINE PRESSURE THROUGH
MODULATING TYPE.
THIS VALVE IS A HYDRAULICALLY-OPERATED, PILOT-CONTROLLED,
MAINTAIN CLOSE PRESSURE LIMITS WITHOUT CAUSING SURGES.
PRESSURE BY BY-PASSING OR RELIEVING EXCESS PRESSURE AND SHALL
THE PRESSURE RELIEF VALVE SHALL MAINTAIN CONSTANT UPSTREAM
PRESSURE RELIEF VALVE (100m)1
PUMP MOTOR
PUMP CAPACITY
FLANGED CONNECTION, ON CAST IRON BASE
FLOOR MOUNTED, CENTRIFUGAL PUMP, SINGLE STAGE END SUCTION,
PUMP MOTOR
PUMP CAPACITY
: 50 HP, 220 V, 3 PH, 60HZ
: 700 GPM, 184 FT TDH, 1750 RPM
FLANGED CONNECTION, ON CAST IRON BASE
FLOOR MOUNTED, CENTRIFUGAL PUMP, SINGLE STAGE END SUCTION,
PUMP MOTOR
PUMP CAPACITY
: 25 HP, 220 V, 3 PH, 60HZ
: 350 GPM, 184 FT TDH, 1750 RPM
FLANGED CONNECTION, ON CAST IRON BASE
FLOOR MOUNTED, CENTRIFUGAL PUMP, SINGLE STAGE END SUCTION,
NO.
ITEM
Q’ TY D E S C R I P T I O N
3 7
H
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-3
D - 17 - 24
G
CAMP CARROLL
YI, TONG KI
NAM, TAE CHIN
SUPPLY PUMP
SUPPLY PUMP
RETURN PUMP
SYSTEM TO DESIGN & TECHNICAL REVIEW BRANCH PRIOR TO CONSTRUCTION.
3. THE CONTRACTOR SHALL SUBMIT DETAILED SHOP DRAWING & SEQUENCE OF OPERATION DRAWING FOR ALL COOLING TOWER CIRCULATING
"KYUNG IN MACHINERY CO., Ltd." MODEL NO. EX-200KLB OR APPROVED EQUAL
"KYUNG IN MACHINERY CO., Ltd." MODEL NO. MEX-500 OR APPROVED EQUAL
COOLING TOWER #1
COOLING TOWER #2
EQUIPMENT SCHEDULE
SCOPE OF WORK
EQUIPMENT SCHEDULE,
YI, TONG KI
NAM, TAE CHIN
25 JUL 17
HA-00556-5J
PRODUCT CERTIFIED BY CTI
ACCESS TO TOP OF TOWER : LADDER
HEIGHT - FOUNDATION TO FAN DECK, mm : 2640
NOMINAL CELL DIMEN. L x W, mm : 2800 x 5270
STRUCTURAL DETAILS
COLD (OUTLET) WATER TEMP. C : 35
HOT (INLET) WATER TEMP. C : 49
CIRCULATING WATER FLOW (Ton/Hr) : 318
MOTOR : 30HP
ELEC. POWER : 208V, 60Hz, 3Ph
TYPE: INDUCED DRAFT, DOUBLE CROSS FLOW
: 50 HP, 220 V, 3 PH, 60HZ
: 1400 GPM, 82 FT TDH, 1750 RPM
BLDG. NO. T-317 (MSC-K)
REPLACE COOLING TOWER,
PRODUCT CERTIFIED BY CTI
ACCESS TO TOP OF TOWER : LADDER
HEIGHT - FOUNDATION TO FAN DECK, mm : 2755
NOMINAL CELL DIMEN. L x W, mm : 2050 x 4070
STRUCTURAL DETAILS
SUPPLY MAKE UP WATER SYSTEM
COLD (OUTLET) WATER TEMP. C : 49
HOT (INLET) WATER TEMP. C : 73
CIRCULATING WATER FLOW (Ton/Hr) : 318
MOTOR : 10HP
ELEC. POWER : 208V, 60Hz, 3Ph
TYPE: INDUCED DRAFT, DOUBLE CROSS FLOW
POWER INPUT
FAN MOTOR
FAN CAPACITY
HEATING CAPACITY
: 3 KW
: 1/100 HP, 208V, 1 PH, 60HZ
: 350 CFM, 165.2 LPS, 1,600 RPM
: 10,000 BTU/HR
ELECTRIC UNIT HEATER
BRACKET, BUILT-IN CONTROLLER AND STANDARD ACCESSORIES.WALL MOUNTING
PROTECTION, WALL MOUNTED DISCONNECT SWITCH, UNIT MOUNTED THERMOSTAT,
DIFFUSER, CONSIST OF HEATING ELEMENTS, FAN AND MOTOR, THERMAL OVERLOAD
HORIZONTAL DISCHARGE, TOTALLY ENCLOSED, INLET LOUVER, VENTURI AND OUTLET
10 2
TO DESIGN & TECHNICAL REVIEW BRANCH.
4. THE CONTRACTOR SHALL PERFORM PERFORMANCE TEST OF NEW ALL COOLING TOWER CIRCULATING SYSTEMS AND SUBMIT TEST REPORT
AND ALL NECESSARY ACCESSORIES & PART.
MAKE UP WATER SYSTEM, ALL PUMPS, ALL CONTROL SYSTEM, ELECTRIC UNIT HEATERS, CONC. PAD, VALVES, FILTERS, PIPING, INSULATION,
1. REPLACE EXISTING DETERIORATED ALL COOLING TOWER CIRCULATING SYSTEMS WITH NEW ONE INCLUDING ALL COOLING TOWERS, ROOM, CIRCULATING PUMP(350 GPM, 184 FT TDH, 1750RPM), PIPING, VALVES AND ALL NECESSARY ACCESSORIES & PART.
SYSTEM SHALL CONTAIN THE COOLING COIL(73,700 Kcal/h) WITH CONDENSING UNIT(85Kw, 208V, 3PH, 60Hz) FOR WATER TANK UNDER PUMP
2. THE CONTRACTOR SHALL PROVIDE A TEMPORARY COOLING SYSTEM DURING THE CONSTRUCTION PERIOD ALSO TEMPORARY COOLING
4 7
H
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-4
D - 17 - 24
G
CAMP CARROLL
YI, TONG KI
NAM, TAE CHIN
P-1 M-4
SCALE : 1 / 100
REMOVE EXISTING COOLING TOWER & PUMP ROOM PLAN
TK
TK
TK
S326
TK
NPN
W
S
W
S
D
D
D
N
W
ROOM
PUMP
TOWER & PUMP ROOM PLAN
REMOVE EXISTING COOLING
YI, TONG KI
NAM, TAE CHIN
25 JUL 17
HA-00556-5J
& ALL ASSOCIATED PART
REMOVE EXITING COOLING TOWER
& ALL ASSOCIATED PART
REMOVE EXITING COOLING TOWER
W/ ALL PIPING, VALVE & ALL ASSOCIATED PART
REMOVE EXITING ALL PUMP
BLDG. NO. T-317 (MSC-K)
SCALE : 1 / 200- M5
P-1
5 7
H
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-5
D - 17 - 24
G
CAMP CARROLL
YI, TONG KI
NAM, TAE CHIN
RETURN LINE
COOLING WATER
SUPPLY LINE
COOLING WATER
POC
POC
NEW COOLING TOWER & PUMP ROOM PLAN
3 JOCKEY PUMP
9 PRESSURE RELIEF VALVE
MCC PANEL
SUPPLY PUMP CONC. PAD
SUPPLY PUMP CONC. PAD 4
RETURN PUMP W/ CONC. PAD 7
COOLING TOWER #2
COOLING TOWER #1
YI, TONG KI
NAM, TAE CHIN
25 JUL 17
HA-00556-5J
RETURN WATER LINE
REMAIN EXISTING UNDERGROUND
SUPPLY WATER LINE
REMAIN EXISTING UNDERGROUND
MOTORIZED VALVE & FILTER
M
BLDG. NO. T-317 (MSC-K)
REPLACE COOLING TOWER,
ELECTRIC UNIT HEATER (TYP. OF 2EA)10
3KW, 208V, 1PH, 60Hz (TYP. OF 2EA)
ELECTRIC UNIT HEATER
NEMA 1 ENCL. (TYP. OF 2EA)
SAFETY SWITCH 2PST-250V-30A NOT FUSIBLE
SCALE : 1 / 50- M5
P-2
ON EXISTING PANEL "1"
2EA 2P-100AF-20AT AND 2EA 1P-100AF-20AT
INSTALL BRANCH CIRCUIT BREAKER
P1
P1
2-#12 "THW", 1-#12 AWG(G) IN 16mmC
UNIT HEATER POWER PLAN
UNIT HEATER POWER PLAN
NEW COOLING TOWER & PUMP ROOM PLAN,
6 7
H
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
SHEET OF
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
MECHANICAL
M-6
D - 17 - 24
G
CAMP CARROLL
YI, TONG KI
NAM, TAE CHIN
(TY
P.
OF
2E
A) x 1
R
EDUCER
(TY
P.
OF
2E A)
FO
OT
VAL
VE
W
/ ST
RAIN
ER
RE
TU
RN
PUMP
RE
TU
RN
PUMP
JO
CKE
Y
PUMP
SUP
PL
Y
PUMP
SUP
PL
Y
PUMP
SUP
PL
Y
PUMP
(TY
P.
OF
2E
A)
CHEC
K
VAL
VE
FL
EXIB
LE
C
ONN.
(TY
P.)
PR
ES
SURE
R
EL
IEF
V
AL
VE
(1
m) 25
CHEC
K
VAL
VE
250 x 150 REDUCER x 2
COOLIN
G
WAT
ER
H
EADER
(TY
P.)25
GAT
E
VAL
VE
COOLIN
G
WAT
ER
R
ET
URN
LIN
E
STRAINER (TYP.)
150 VERTICAL BASKET
x
R
EDUCER
150 X 125 REDUCER (TYP.)
150 GATE VALVE (TYP.)
FL
EXIB
LE
C
ONN.(
TY
P.)
RE
TU
RN
LIN
E
SUP
PL
Y
LIN
E
I-1 M-6-
NOT TO SCALE
NEW PUMP ROOM ISOMETRIC DIAGRAM
G
AT
E
VAL
VE
C
HEC
K
VAL
VE
G
AT
E
VAL
VE
x
R
EDUCER
(T
YP
NEW PUMP ROOM ISOMETRIC DIAGRAM
YI, TONG KI
NAM, TAE CHIN
25 JUL 17
HA-00556-5J
BLDG. NO. T-317 (MSC-K)
REMAIN EXISTING WATER TANK
WATER LINE
50 EXISTING MAKE-UP
REMAIN EXISTING WATER TANK
POC
PLC PANEL
CONTROL LINE
W/ 150m x 100m 2EA REDUCER
100m PRESSURE RELIEF VALVE SET @ 70 PSI
FOR COOLING WATER RETURN PUMP
RE - ARRANGEMENT LEVEL LENGTH
LIQUID LEVEL CONTROLLER
REMAIN EXISTING WATER TANK
FOOT VALVE & PIPING
COOLING WATER HEADER
LOW WATER CUT-OFF SWITCH
LIQUID LEVEL CONTROLLER
TEMPERATURE CONTROLLER
POC
TEMPERATURE CONTROLLER
RETURN LINE TO COOLING WATER HEADER
RETURN LINE TO PUMP RM. WATER TANK
SUPPLY LINE TO ENGINE TEST CELL
REMAIN UNDERGROUND RETURN LINE TO COOLING TOWER
TOWER #2
COOLING
SEQUENCE OF OPERATION
PRESSURE SWITCH SCHEDULE
SWITCH NO.
PRESSURE
USAGE
FOR ALARMPS-A
PS-1
PS-2
PS-3
PS-4
PRESSURE RANGE SETTING POINT
10 TO 150 PSI 40 +2 PSI
66 +2 PSI
62 +2 PSI
80 +2 PSI
72 +2 PSI
10 TO 150 PSI
10 TO 150 PSI
10 TO 150 PSI
10 TO 150 PSI
FOR JOCKEY PUMP
o o o o
E N
G
IN
E
T E S T
C
E L L
FOR SUPPLY PUMP
FOR SUPPLY PUMP
FOR SUPPLY PUMP6
7 8
P-1 M-7-
NOT TO SCALE
NEW COOLING SYSTEM ISOMETRIC DIAGRAM
MOTORIZED VALVE & FILTER
M
REMAIN EXISTING PIPING & GATE VALVES
4 5 6
4 5 6
TOWER #1
COOLING
CAMP CARROLL
MECHANICAL
PRESSURE SWITCH SCHEDULE
SEQUENCE OF OPERATION,
NEW COOLING SYSTEM ISOMETRIC DIAGRAM,
YI, TONG KI
NAM, TAE CHIN
25 JUL 17
HA-00556-5J
(TYP OF 4EA)
PRESSURE SWITCH
THE TEMPERATURE CONTROLLER.
THE BLOWER FAN RUNS AT LOW SPEED (900 RPM) AND 26 C THE BLOWER FAN STOPS BY
9. WHEN THE BASIN WATER TEMPERATURE OF THE COOLING TOWER #2 REACHES 30 C,
BY THE TEMPERATURE CONTROLLER.
THE BLOWER FAN RUNS AT LOW SPEED (900 RPM) AND 38 C THE BLOWER FAN STOPS
8. WHEN THE BASIN WATER TEMPERATURE OF THE COOLING TOWER #1 REACHES 43 C,
THE COOLING TOWER #1 AND #2.
7. THE COOLING WATER RETURN PUMPS AND WILL ENERGIZED THE BLOWERS OF
IN THE COOLING TOWER #2.
6. MOTORIZED VALVE IN THE VALVE BOX SHALL BE CYCLED BY THE LIQUID LEVEL CONTROLLER
CONTROLLED BY THE LIQUID LEVEL CONTROLLER IN PUMP ROOM.
5. THE COOLING WATER RETURN PUMPS (DUTY) AND (STAND-BY) SHALL BE
THE LOW WATER CUT-OFF SHALL DE-ENERGIZE PUMPS .
4. IF THE WATER LEVEL OF THE COOLING WATER SUPPLY HEADER DROPS BELOW CENTER LINE OF HEADER, THE COOLING WATER SUPPLY PIPING PRESSURE AS SCHEDULED.
3. START OR STOP THE COOLING WATER SUPPLY PUMP TO MAINTAIN
THE COOLING WATER SUPPLY PIPING PRESSURE, THE PRESSURE SWITCH AS SCHEDULED.
2. THE JOCKEY PUMP SHALL BE BY THE PRESSURE SWITCH PS-1 TO MAINTAIN
SET AT MINIMUM 60 PSI.
THE COOLING WATER SUPPLY LINE PRESSURE SHALL BE MAINTAINED BY THE PRESSURE RELIEF VALVE
1. FOR PROPER OPERATION OF ENGINE TEST DYNAMOMETER,
M
M
CUT-OFF SWITCH
LOW WATER
PS-4 PS-3 PS-2 PS-1 PS-A
BLDG. NO. T-317 (MSC-K)
REPLACE COOLING TOWER,
7 7
HGF
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
EDCBA
AS SHOWN
DATE:
M-7
D - 17 - 24
SHEET OF
SYSTEM
& WATER LEVEL CONTROL
MAKE-UP WATER SYSTEM
DOUBLE CHECK VALVE,
WITH ALUMINUM JACKET
ALL ABOVE GROUND PIPING INSULATION(40T)
WITH ALUMINUM JACKET
ALL ABOVE GROUND PIPING INSULATION(40T)
| HA-00556-5J_T01 |
| HA-00556-5J_M01 |
| HA-00556-5J_M02 |
| HA-00556-5J_M03 |
| HA-00556-5J_M04 |
| HA-00556-5J_M05 |
| HA-00556-5J_M06 |
| HA-00556-5J_M07 |