GENERAL NOTES

1.

2.MOUNTING HEIGHTS ABOVE FLOOR SHALL BE AS FOLLOW UNLESS OTHERWISE

NOTED ON THE DRAWING.

LIGHTING FIXTURE SEE LIGHTING FIXTURE SCHEDULE

LOADCENTER SEE SPECIFICATION

SAFETY SWITCH 1524mm TO CENTER OF THE ENCL

305mm TO CENTER OF THE ENCL

3.

4.

6.THE SOIL RESISTANCE TO GROUND FOR THE ELECTRICAL AND COMMMUNICATION

SYSTEMS SHALL BE 25 OHMS OR LESS. THE SOIL RESISTANCE TEST SHALL BE

5.

CONDUCTED BY THE CONTRACTOR TO OBTAIN THE REQUIRED SOIL RESISTANCE.

INDICATEDS 2 #12AWG IN 16C

INDICATEDS 3 #12AWG IN 16C

INDICATEDS 4 #12AWG IN 16C

A GREATER NUMBER OF WIRES ARE INDICATED AS FOLLOWS;

1219mm TO CENTER OF THE ENCLWALL SWTICH

CONDUIT UNLESS OTHERWISE INDICATED.

ALL EQUIPMENT CONTROL WIRING SHALL BE #14 AWG. "TW" IN 16C

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-1

1.

SCOPE OF WORK

3.

2.

12.

13.

4.

A. REPAIR/MAINTENANCE ( K )

10.

11.

8.

9.

SINGLE POLE TOGGLE SWITCH, 15A-125V

L E G E N D

FLEXIBLE CONDUIT W/CONNECTORS

LIGHTING

WIRING

POWER

INTERIOR

S

SYMBOL DESCRIPTION

DESCRIPTION

DESCRIPTION

T

J

THERMOSTAT (UNDER MECH. ITEM)

JUNCTION BOX

SYMBOL

SYMBOL

F FAN MOTOR (UNDER MECH. ITEM)

SAFETY SWITCH

C CONTROL CIRCUIT

3-WAY SWITCH, 15A-125V

AND GOVERNMENT INSTALLED

GOVERNMENT FURNISHED

GFGI

WEATHERPROOFWP

LA LIGHTNING ARRESTER

EXPLOSIONPROOFEP

DISTRIBUTIONDIST

GROUND FAULT PROTECTIONGFP

A AMPERE

AC ALTERNATING CURRENT

AF/AT AMPERE FRAME/AMPERE TRIP

AWG AMERICAN WIRE GAUGE

BC BARE COPPER

BLDG BUILDING

BRKR BREAKER

C CONDUIT

CB CIRCUIT BREAKER

CKT CIRCUIT

CONN CONNECTION

CT CURRENT TRANSFORMER

DET(S) DETAIL(S)

DIAG DIAGRAM

DISC DISCONNECT

DWG(S) DRAWING(S)

EA EACH

EM EMERGENCY

ENCL ENCLOSURE

EXST EXISTING

F/A FIRE ALARM

FL FLOOR

FLUOR FLUORESCENT

FXTR FIXTURE

GEN GENERATOR

GND GROUND

HP HORSE POWER

HZ HERTZ

INCAND INCANDESCENT

INSTL INSTALLATION

J-BOX JUNCTION BOX

K KILO

KV KILO VOLT

KVA KILO VOLT AMPERE

LTG LIGHTING

MAG MAGNETIC

MAX MAXIMUM

MIN MINIMUM OR MINUTE

MTG MOUNTING

NO NUMBER

O/H OVER HEAD

PH PHASE

PNLBD PANELBOARD

PRIM PRIMARY

PWR POWER

Q'TY QUANTITY

RCPT RECEPTACLE

REQ'D REQUIRED

SCHED SCHEDULE

SEC SECONDARY

SPEC SPECIFICATION

STD STANDARD

SW SWITCH

TEL TELEPHONE

TYP TYPICAL

U/G UNDERGROUND

V VOLT

VA VOLT AMPERE

W WATT

W/ WITH

XFMR TRANSFORMER

& AND

PANELBOARD

3S

HOMERUN CIRCUIT TO PANELBOARD

TYPE OF MTG ON LTG SCHEDULE

EXTERIOR LED LIGHTING FIXTURE, RATED WATT &

TYPE

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING

ABBREVIATION

THE COTNRACTOR SHALL SUBMIT A SHOP DRAWING OF HVAC SYSTEM

IN ACCORDANCE WITH SEQUENCE OF OPERATION INDICATED ON THE

MECHANICAL DRAWINGS.

ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG

WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.

THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR

ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.

CEILING.

ALL WIRING SHALL BE CONCEALED ABOVE CEILING WHEN THE ROOM HAS

CATV BEFORE CONSTRUCTION.

CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,

AND GOVERNMENT ACCEPTANCE.

PANELBOARD DOOR, REQUIRED BEFORE FINAL BUILDING INSPECTION

CONTRACTOR SHALL MAKE CIRCUIT CHARTS AND ATTACH THEM TO

FIRE CODE AND SPECIFICATIONS.

OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,

ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS

OR RENOVATION.

CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION

THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING

BRANCH CIRCUIT, EXPOSED ON CEILING OR WALL

WIRING CONCEALED IN THE CEILING AND WALL

W/EMERGENCY UNIT

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

L

L

ONLY.

UNITS. MANUFACTURER WILL BE RESPONSIBLE FOR SUPPLYING MATERIALS

CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER

CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10YEARS WARRANTY

SWITCHES, WIRES AND CONDUITS WITH NEW.

LIGHTS, EXTERIOR LIGHTS, TOGGLE SWITCHES, 3-WAY

REPLACE DETERIORATED EXISTING LIGHTING FIXTURES, EXIT

OF WORKS

LEGEND, GENERAL NOTES AND SCOPE

THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE

WIDTH OF DUCT EXCAVATION.

AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.

TO THEIR ORIGINAL CONDITION AND OPERATION DURING

ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES

THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING 7.

FAULT PROTECTED TYPE, WEATHER PROOF

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDED "WP"

TYPE OF MTG ON LTG SCHEDULE

EXIT SIGN, LED LIGHTING FIXTURE, RATED WATT &

RECEPTACLE

PLATES AND ASSOCIATED WIRING & CONDUIT WITH NEW.

REPLACE EXISTING LOADCENTER, RECEPTACLES AND COVER

AND CONDUITS FOR HVAC SYSTEM WITH NEW.

MOTOR STARTERS, JUNCTION BOXES, CONTROL SYSTEM, WIRES

REPLACE DETERIORATED EXISTING SAFETY SWTICHES, MANUAL

REPLACE EXISTING EXTERIOR POWER DISTRIBUTION LINE WITH NEW.

REPAIR BUILDING S-400

CP CASEYTAK, YS

111000

C

U

G

SCALE :

1/300

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

EXIST/ NEW EXTERIOR ELECTRICAL DISTRIBUTION PLAN

E-2

NEW 3-AWG#4 IN 54 mm dia C.

EXIST O/H SECONDARY LINE (TYPICAL)

O/H

O

H

O

H

S

S

S

S

EXIST CON'C POLE (TYPICAL)

EXIST O/H COMMUNICATION LINE (TYPICAL)

DISTRIBUTION PLAN

EXIST/NEW EXTERIOR ELECTRICAL

REPAIR BUILDING S-400

CP CASEYTAK, YS

111000

ACCESSORIES INCLUDING ENTRANCE CAP 54mm DIA C.

CONNECT TO EXIST SECONDARY LINE WITH NECCESSARY

STORAGE ROOM-2

STORAGE ROOM-1

LLL L

LLL L

LL

L L

X

S

S S

3S

3S

P-1

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-3

WALL MOUNTED ABOVE THE DOOR TOP2NS-3EXIT-

NS-6b 45 1

REMARKSQ'TY

WATTS

MOUNTING METHOD

TYPE

LAMP

NAMENO

ROOM OCE STD DET 40-06-04

LIGHT FIXTURE SCHEDULE

TYPE

LED

G R

O U

N D

F L

O O

R

CEILING RECESSED

2 W/ "EM" UNIT

NS-5 2 WALL MOUNTED ABOVE THE DOOR TOP

W/ "EM" UNIT

NS-4b

NS-4a

NS-6a

4.99

DIODE(LED) EXIT LIGHT FIXTURE 1PH, 120V, 4.99W

WALL SURFACE MOUNTED LIGHT EMITTING

(MAX. INPUT), BATTERY BACK-UP WITH BATTERY CHARGER

NS-3

FIXTURE, 1PH, 120V, 45W, WITH CONVERTER & ACCESSORIES

CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)

NS-5

WALL SURFACE MOUNTED LIGHT EMITTING DIODE (LED)

FIXTURE, 1PH, 120V, 22W, WITH CONVERTER & ACCESSORIES

UL LISTEDPOWER UNIT

W/BUILT-IN PHOTOCELL, WET LOCATION (OUTDOOR) TYPE,

STORAGE ROOM-1

STORAGE ROOM-2

EXTERIOR

SCALE :

GROUND FLOOR LIGHTING PLAN

1/50

NS-4a & NS-4b

AS REQUIRED, UL LISTED (NS-4a), WITH EM UNIT (NS-4b)

NS-6a & 6b

CEILING SURFACE/PENDANT MOUNTED LIGHT EMITTING DIODE (LED)

CEILING PENDENT MOUNTED

LIGHTING FIXTURE SCHEDULE & DETAILS

GROUND FLOOR LIGHTING PLAN,

REPAIR BUILDING S-400

CP CASEYTAK, YS

111000

AS REQUIRED, UL LISTED(NS-6a)& EM UNIT(NS-6b),AND

FIXTURE, 1PH, 120V, 45W, WITH CONVERTER, ACCESSORIES

"P"

OHPU

MP-2

MP-3 MP-8

J

EF-1

S

MP-5

WP

J

T

C

C

P-6

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-4

TOTAL LOAD 13034

LOAD

TOTAL

NEW LOADCENTER "MP" LOAD SCHEDULE

LOAD DESCRIPTION

NO.

CKT

GND

S/N

DIAGRAM

CONNECTION

CIRCUIT BREAKER

PHASE LOAD

A B P AT

SIZE

AF AIC

BA N G

REMARK

MTD TYPE, NEMA 1 ENCL.

1PHASE ,3WIRE, 120/208V,

1 10000100

3#8&1#10(G)

TOTAL DEMAND LOAD ; 11026(VA)

4#2&1#4(G)

3#10&1#10(G)

2#12&1#12(G)

SCALE :

1/50

OHPU

EF-1

(MECH ITEM)

EXHAUST FAN-1/6HP, 1PH, 120VAC

WITH 60A FUSEx3EA, NEMA 3R ENCL.

SAFETY SWITCH, DPST, 240AC, 60A,

S MANUAL MOTOR STARTER, 120VAC, 1HP(MAX.)

"ON-OFF" SWITCH, NEMA 1 ENCL.

GROUNDING TYPE, W/ PLUG

SINGLE RECEPTACLE, 2P-20A-240AC,

T THERMOSTAT (MECH ITEM)

ADDITIONAL LEGEND

"WP"

RCPTS 180VAx4

RCPTS 180VAx4

RCPTS 180VAx4

UNIT, 7.0KW

PACKAGE SYSTEM HEAT PUMP

LED 5Wx2

LIGHTS, LED 45Wx12, 22Wx2, 594 20

EXHAUST FAN-1, 1/6HP 248 248

1000SPARE

SPARE 1000

1 -

SPACE

SPACESPACE

"P"

GROUND FLOOR POWER PLAN

STORAGE ROOM-2

STORAGE ROOM-1

T

C

C

MP-7

60HZ, SN & GND, FLUSH

300 300

180 180

HEAT PUMP INDOOR UNIT

3#8&1#10(G)

2#12&1#12(G)

RCPTS 180VAx2

MAIN 2P-100AF-80AT CIRCUIT BREAKER

6578 6456

3-4 & 1-6(G)

HPU

HPU

HPU

HPU

HPU

7KW, 1PH,, 208VAC (MECH ITEM)

OUTDOOR SPLIT SYSTEM HEAT PUMP UNIT,

0.06KW, 1PH,, 208VAC (MECH ITEM)

INDOOR SPLIT SYSTEM HEAT PUMP UNIT,

LOADCENTER "MP" LOAD SCHEDULE

GROUND FLOOR POWER PLAN, NEW

REPAIR BUILDING S-400

CP CASEYTAK, YS

111000

GROUNDING TYPE (KOREAN RECEPTACLE)

DUPLEX RECEPTACLE, 2P-20A-240AC,

2#8 & 1#10(G) IN 28C

(3/4" dia x10' W/WELDING)

GROUNDING ROD

1-AWG#8 "BC" IN 16mm DIA C.

NEW GROUNDING WIRE,

111000_E-1
111000_E-2
111000_E-3
111000_E-4