GENERAL NOTES
1.
2.MOUNTING HEIGHTS ABOVE FLOOR SHALL BE AS FOLLOW UNLESS OTHERWISE
NOTED ON THE DRAWING.
LIGHTING FIXTURE SEE LIGHTING FIXTURE SCHEDULE
LOADCENTER SEE SPECIFICATION
SAFETY SWITCH 1524mm TO CENTER OF THE ENCL
305mm TO CENTER OF THE ENCL
3.
4.
6.THE SOIL RESISTANCE TO GROUND FOR THE ELECTRICAL AND COMMMUNICATION
SYSTEMS SHALL BE 25 OHMS OR LESS. THE SOIL RESISTANCE TEST SHALL BE
5.
CONDUCTED BY THE CONTRACTOR TO OBTAIN THE REQUIRED SOIL RESISTANCE.
INDICATEDS 2 #12AWG IN 16C
INDICATEDS 3 #12AWG IN 16C
INDICATEDS 4 #12AWG IN 16C
A GREATER NUMBER OF WIRES ARE INDICATED AS FOLLOWS;
1219mm TO CENTER OF THE ENCLWALL SWTICH
CONDUIT UNLESS OTHERWISE INDICATED.
ALL EQUIPMENT CONTROL WIRING SHALL BE #14 AWG. "TW" IN 16C
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-1
1.
SCOPE OF WORK
3.
2.
12.
13.
4.
A. REPAIR/MAINTENANCE ( K )
10.
11.
8.
9.
SINGLE POLE TOGGLE SWITCH, 15A-125V
L E G E N D
FLEXIBLE CONDUIT W/CONNECTORS
LIGHTING
WIRING
POWER
INTERIOR
S
SYMBOL DESCRIPTION
DESCRIPTION
DESCRIPTION
T
J
THERMOSTAT (UNDER MECH. ITEM)
JUNCTION BOX
SYMBOL
SYMBOL
F FAN MOTOR (UNDER MECH. ITEM)
SAFETY SWITCH
C CONTROL CIRCUIT
3-WAY SWITCH, 15A-125V
AND GOVERNMENT INSTALLED
GOVERNMENT FURNISHED
GFGI
WEATHERPROOFWP
LA LIGHTNING ARRESTER
EXPLOSIONPROOFEP
DISTRIBUTIONDIST
GROUND FAULT PROTECTIONGFP
A AMPERE
AC ALTERNATING CURRENT
AF/AT AMPERE FRAME/AMPERE TRIP
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BLDG BUILDING
BRKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CONN CONNECTION
CT CURRENT TRANSFORMER
DET(S) DETAIL(S)
DIAG DIAGRAM
DISC DISCONNECT
DWG(S) DRAWING(S)
EA EACH
EM EMERGENCY
ENCL ENCLOSURE
EXST EXISTING
F/A FIRE ALARM
FL FLOOR
FLUOR FLUORESCENT
FXTR FIXTURE
GEN GENERATOR
GND GROUND
HP HORSE POWER
HZ HERTZ
INCAND INCANDESCENT
INSTL INSTALLATION
J-BOX JUNCTION BOX
K KILO
KV KILO VOLT
KVA KILO VOLT AMPERE
LTG LIGHTING
MAG MAGNETIC
MAX MAXIMUM
MIN MINIMUM OR MINUTE
MTG MOUNTING
NO NUMBER
O/H OVER HEAD
PH PHASE
PNLBD PANELBOARD
PRIM PRIMARY
PWR POWER
Q'TY QUANTITY
RCPT RECEPTACLE
REQ'D REQUIRED
SCHED SCHEDULE
SEC SECONDARY
SPEC SPECIFICATION
STD STANDARD
SW SWITCH
TEL TELEPHONE
TYP TYPICAL
U/G UNDERGROUND
V VOLT
VA VOLT AMPERE
W WATT
W/ WITH
XFMR TRANSFORMER
& AND
PANELBOARD
3S
HOMERUN CIRCUIT TO PANELBOARD
TYPE OF MTG ON LTG SCHEDULE
EXTERIOR LED LIGHTING FIXTURE, RATED WATT &
TYPE
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING
ABBREVIATION
THE COTNRACTOR SHALL SUBMIT A SHOP DRAWING OF HVAC SYSTEM
IN ACCORDANCE WITH SEQUENCE OF OPERATION INDICATED ON THE
MECHANICAL DRAWINGS.
ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG
WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.
THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR
ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.
CEILING.
ALL WIRING SHALL BE CONCEALED ABOVE CEILING WHEN THE ROOM HAS
CATV BEFORE CONSTRUCTION.
CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,
AND GOVERNMENT ACCEPTANCE.
PANELBOARD DOOR, REQUIRED BEFORE FINAL BUILDING INSPECTION
CONTRACTOR SHALL MAKE CIRCUIT CHARTS AND ATTACH THEM TO
FIRE CODE AND SPECIFICATIONS.
OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,
ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS
OR RENOVATION.
CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION
THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING
BRANCH CIRCUIT, EXPOSED ON CEILING OR WALL
WIRING CONCEALED IN THE CEILING AND WALL
W/EMERGENCY UNIT
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
L
L
ONLY.
UNITS. MANUFACTURER WILL BE RESPONSIBLE FOR SUPPLYING MATERIALS
CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER
CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10YEARS WARRANTY
SWITCHES, WIRES AND CONDUITS WITH NEW.
LIGHTS, EXTERIOR LIGHTS, TOGGLE SWITCHES, 3-WAY
REPLACE DETERIORATED EXISTING LIGHTING FIXTURES, EXIT
OF WORKS
LEGEND, GENERAL NOTES AND SCOPE
THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE
WIDTH OF DUCT EXCAVATION.
AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.
TO THEIR ORIGINAL CONDITION AND OPERATION DURING
ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES
THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING 7.
FAULT PROTECTED TYPE, WEATHER PROOF
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDED "WP"
TYPE OF MTG ON LTG SCHEDULE
EXIT SIGN, LED LIGHTING FIXTURE, RATED WATT &
RECEPTACLE
PLATES AND ASSOCIATED WIRING & CONDUIT WITH NEW.
REPLACE EXISTING LOADCENTER, RECEPTACLES AND COVER
AND CONDUITS FOR HVAC SYSTEM WITH NEW.
MOTOR STARTERS, JUNCTION BOXES, CONTROL SYSTEM, WIRES
REPLACE DETERIORATED EXISTING SAFETY SWTICHES, MANUAL
REPLACE EXISTING EXTERIOR POWER DISTRIBUTION LINE WITH NEW.
REPAIR BUILDING S-400
CP CASEYTAK, YS
111000
C
U
G
SCALE :
1/300
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
EXIST/ NEW EXTERIOR ELECTRICAL DISTRIBUTION PLAN
E-2
NEW 3-AWG#4 IN 54 mm dia C.
EXIST O/H SECONDARY LINE (TYPICAL)
O/H
O
H
O
H
S
S
S
S
EXIST CON'C POLE (TYPICAL)
EXIST O/H COMMUNICATION LINE (TYPICAL)
DISTRIBUTION PLAN
EXIST/NEW EXTERIOR ELECTRICAL
REPAIR BUILDING S-400
CP CASEYTAK, YS
111000
ACCESSORIES INCLUDING ENTRANCE CAP 54mm DIA C.
CONNECT TO EXIST SECONDARY LINE WITH NECCESSARY
STORAGE ROOM-2
STORAGE ROOM-1
LLL L
LLL L
LL
L L
X
S
S S
3S
3S
P-1
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-3
WALL MOUNTED ABOVE THE DOOR TOP2NS-3EXIT-
NS-6b 45 1
REMARKSQ'TY
WATTS
MOUNTING METHOD
TYPE
LAMP
NAMENO
ROOM OCE STD DET 40-06-04
LIGHT FIXTURE SCHEDULE
TYPE
LED
G R
O U
N D
F L
O O
R
CEILING RECESSED
2 W/ "EM" UNIT
NS-5 2 WALL MOUNTED ABOVE THE DOOR TOP
W/ "EM" UNIT
NS-4b
NS-4a
NS-6a
4.99
DIODE(LED) EXIT LIGHT FIXTURE 1PH, 120V, 4.99W
WALL SURFACE MOUNTED LIGHT EMITTING
(MAX. INPUT), BATTERY BACK-UP WITH BATTERY CHARGER
NS-3
FIXTURE, 1PH, 120V, 45W, WITH CONVERTER & ACCESSORIES
CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)
NS-5
WALL SURFACE MOUNTED LIGHT EMITTING DIODE (LED)
FIXTURE, 1PH, 120V, 22W, WITH CONVERTER & ACCESSORIES
UL LISTEDPOWER UNIT
W/BUILT-IN PHOTOCELL, WET LOCATION (OUTDOOR) TYPE,
STORAGE ROOM-1
STORAGE ROOM-2
EXTERIOR
SCALE :
GROUND FLOOR LIGHTING PLAN
1/50
NS-4a & NS-4b
AS REQUIRED, UL LISTED (NS-4a), WITH EM UNIT (NS-4b)
NS-6a & 6b
CEILING SURFACE/PENDANT MOUNTED LIGHT EMITTING DIODE (LED)
CEILING PENDENT MOUNTED
LIGHTING FIXTURE SCHEDULE & DETAILS
GROUND FLOOR LIGHTING PLAN,
REPAIR BUILDING S-400
CP CASEYTAK, YS
111000
AS REQUIRED, UL LISTED(NS-6a)& EM UNIT(NS-6b),AND
FIXTURE, 1PH, 120V, 45W, WITH CONVERTER, ACCESSORIES
"P"
OHPU
MP-2
MP-3 MP-8
J
EF-1
S
MP-5
WP
J
T
C
C
P-6
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-4
TOTAL LOAD 13034
LOAD
TOTAL
NEW LOADCENTER "MP" LOAD SCHEDULE
LOAD DESCRIPTION
NO.
CKT
GND
S/N
DIAGRAM
CONNECTION
CIRCUIT BREAKER
PHASE LOAD
A B P AT
SIZE
AF AIC
BA N G
REMARK
MTD TYPE, NEMA 1 ENCL.
1PHASE ,3WIRE, 120/208V,
1 10000100
3#8&1#10(G)
TOTAL DEMAND LOAD ; 11026(VA)
4#2&1#4(G)
3#10&1#10(G)
2#12&1#12(G)
SCALE :
1/50
OHPU
EF-1
(MECH ITEM)
EXHAUST FAN-1/6HP, 1PH, 120VAC
WITH 60A FUSEx3EA, NEMA 3R ENCL.
SAFETY SWITCH, DPST, 240AC, 60A,
S MANUAL MOTOR STARTER, 120VAC, 1HP(MAX.)
"ON-OFF" SWITCH, NEMA 1 ENCL.
GROUNDING TYPE, W/ PLUG
SINGLE RECEPTACLE, 2P-20A-240AC,
T THERMOSTAT (MECH ITEM)
ADDITIONAL LEGEND
"WP"
RCPTS 180VAx4
RCPTS 180VAx4
RCPTS 180VAx4
UNIT, 7.0KW
PACKAGE SYSTEM HEAT PUMP
LED 5Wx2
LIGHTS, LED 45Wx12, 22Wx2, 594 20
EXHAUST FAN-1, 1/6HP 248 248
1000SPARE
SPARE 1000
1 -
SPACE
SPACESPACE
"P"
GROUND FLOOR POWER PLAN
STORAGE ROOM-2
STORAGE ROOM-1
T
C
C
MP-7
60HZ, SN & GND, FLUSH
300 300
180 180
HEAT PUMP INDOOR UNIT
3#8&1#10(G)
2#12&1#12(G)
RCPTS 180VAx2
MAIN 2P-100AF-80AT CIRCUIT BREAKER
6578 6456
3-4 & 1-6(G)
HPU
HPU
HPU
HPU
HPU
7KW, 1PH,, 208VAC (MECH ITEM)
OUTDOOR SPLIT SYSTEM HEAT PUMP UNIT,
0.06KW, 1PH,, 208VAC (MECH ITEM)
INDOOR SPLIT SYSTEM HEAT PUMP UNIT,
LOADCENTER "MP" LOAD SCHEDULE
GROUND FLOOR POWER PLAN, NEW
REPAIR BUILDING S-400
CP CASEYTAK, YS
111000
GROUNDING TYPE (KOREAN RECEPTACLE)
DUPLEX RECEPTACLE, 2P-20A-240AC,
2#8 & 1#10(G) IN 28C
(3/4" dia x10' W/WELDING)
GROUNDING ROD
1-AWG#8 "BC" IN 16mm DIA C.
NEW GROUNDING WIRE,
| 111000_E-1 |