M-1
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
SYMBOLS AND ABBREVIATIONS
heating
ACCU AIR COOLED CONDENSING UNIT
ACLD AIR COOLED
ACU AIR CONDITION UNIT (S)
ACV ALARM CHECK VALVE
ADP APPARATUS DEW POINT
AHU AIR HANDLING UNIT
AIR COND AIR CONDITION (-ING,-ED)
AL ALUMINUM
ALT ALTITUDE
AMB AMBIENT
AMP AMPERE(AMP, AMPS)
APPROX APPROXIMATE
AVG AVERAGE
AWG AMERICAN WIRE GAUGE
BARO BAROMETER(-TRIC)
BARO PR PRESSURE, BAROMETRIC
BHP BRAKE HORSEPOWER
BP BOILING POINT
CAP CAPACITY
CCW COUNTER CLOCKWISE
CHW CHILLED WATER
CIP CAST IRON PIPE
CKT CIRCUIT
CLASS CLASSIFICATION
CLG LOAD COOLING LOAD
COEF COEFFICIENT
CONN CONNECTION
CONT CONTINUE
CPRSR COMPRESSOR
JACKET WATER RETURN
MEDIUM PRESSURE STEAM
MEDIUM PRESSURE CONDENSATE
LOW PRESSURE STEAM
LOW PRESSURE CONDENSATE
BOILER BLOW DOWN
PUMPED CONDENSATE
VACUUM PUMP DISCHARGE
MAKE UP WATER
FUEL OIL DRAIN
FUEL OIL TANK VENT
FUEL OIL GAUGE
FUEL OIL SUPPLY
FUEL OIL RETURN
CONDENSATE WATER SUPPLY
CONDENSATE WATER RETURN
COMPRESSED AIR
VACUUM (AIR)
EXISTING PIPE
PIPE TO BE REMOVED
CONTROL AIR MAIN
REFRIGERANT DISCHARGE
REFRIGERANT SUCTION
REFRIGERANT LIQUID
DRAIN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
HOT/CHILLED WATER SUPPLY
HOT CHILLED WATER RETURN
air conditioning and refrigeration
THREE WAY
PLUG VALVE
GATE, GLOBE
GATE, ANGLE
CONTROL
BUTTERFLY
BALL
AIR LINE
PIPE SLEEVE
BACKFLOW PREVENTER
PITCH OR PIPE, UP(U), DOWN(D)
VENT THRU ROOF
FUNNEL DRAIN, OPEN
SURFACE CLEANOUT
FLOOR CLEANOUT
FLOOR DRAIN
CHEMICAL SUPPLY PIPES
ACID WASTE
GAS
CONDENSATE DRAIN BELOW
CONDENSATE DRAIN ABOVE
SANITARY DRAIN
VENT
HOT WATER RETURN
HOT WATER SUPPLY
COLD WATER
plumbing valves : (for selective actuators)
PIPE SLEEVE WITH FIRE STOPPING
EXPANSION LOOP
EXPANSION JOINT
BALL JOINT
ANCHOR, MAIN
ANCHOR, INTERMEDIATE
ALIGNMENT GUIDE
AIR SEPARATOR
AIR VENT, MANUAL
AIR VENT, AUTOMATIC
SQUARE HEAD BALANCING COCK
SQUARE HEAD BALANCING COCK
SAFETY
RELIEF
QUICK CLOSING, FUSIBLE LINK
QUICK OPENING
PRESSURE REDUCING
NEEDLE
LOCK SHIELD
HOSE END DRAIN
CONTROL, ELECTRIC-PNEUMATIC
CHECK, NON-SLAM
CHECK, SWING
DIAPHRAGM
SOLENOID
MOTOR ELECTRIC
valve actuators
EXPANSION JOINTEXPJT
ENTERING WATER TEMPEWT
EVAPORAT (-E,-ING,-ED,-OR)EVAP
EXTERNAL STATIC PRESSUREESP
EXPLOSION PROOFEP
EQUIPMENTEQPT
ENTERINGENT
EFFICIENCYEFF
EQUIVALENT DIRECT RADIATIONEDR
ECONOMIZERECON
ECCENTRICECC
ENTERING AIR TEMPERATUREEAT
DIRECT EXPANSIONDX
DRY PIPE VALVEDPV
DOUBLE POLE DOUBLE THROWDPDT
DEWPOINT TEMPERATUREDPT
DIESEL OIL
DIVISIONDIV
DIFFERENCEDIFF
DIAGRAMDIAG
DIAMETER
DEGREEDEG or °
DRY BULB TEMPERATUREDBT
DECIBEL OR DRY BULBDB
CIRCULATING WATER PUMPCWP
CLOCKWISE OR COLD WATERCW
COEFFICIENT, VALVE FLOWCv
CU MM
HERTZHZ
HORIZONTALHORIZ
HOT WATER HEATERHWH
HOT WATERHW
HOUR(S)HR
HORSEPOWERHP
MERCURYHG
HEADHD
HOSE BIBBHB
GALVANIZED STEELGALVS
GAGE OR GAUGEGA
FIXTUREFXTR
FEED WATER PUMPFWP
FACE VELOCITYFVEL
FLUSH VALVEFV
FRP
FREQUENCYFREQ
FEMALE PIPE THREADFPT
FUEL OILFO
SUBMERSIBLESBM
SANITARYSAN
SUPPLY AIRSA
REFRIGERATION TONRT
REVOLUTIONS PER MINUTERPM
RELATIVE HUMIDITYRH
RADIATORRDTR
RETURN AIRRA
THERMAL RESISTANCER
QUANTITYQTY
QUARTQT
PERCENT
PRESSURE REDUCING VALVEPRV
PARTS PER MILLIONPPM
POL
POINT OF CONNECTIONPOC
PLUMBINGPLMB
PHASE (ELECTRIC)PH
PRESSURE GAGEPG
PD
POLEP
URINALUR
UNIT HEATERUH
HEAT TRANSFER COEFFICIENTU
TYPICALTYP
THERMOSTATTSTAT
TONS OF REFRIGERATIONTONS
THICKNESSTHK
THERMOMETERTHERM
TEMPERATURETEMP
TEMPERATURE DIFFERENCETD
SYMBOLSYM
SUCTIONSUCT
STORAGESTOR
STEELSTL
STANDARDSTD
STEAMST
SAYBOLT SECONDS UNIVERSALSSU
STAINLESS STEELSST
SAYBOLT SECONDS FUROLSSF
SQUARESQ
SPRINKLERSPR
SPECIFICATIONSPEC
SINGLE POLE DOUBLE THROWSPDT
SM
WATERPROOFWTRPRF
WEIGHTWT
WSHR
WITHW/
WATTHOUR OR WATER HEATERWH
WIDTHWD
WATER-COOLEDWCLD
WATER CLOSETWC
WET BULB TEMPERATUREWBT
WET BULBWB
WATTW
PRESSURE, DYNAMIC(VELOCITY)VP
VOLUMEVOL
VISCOSITYVISC
VERTICALVERT
VENTILATIONVENT
VELOCITYVEL
VARIABLE AIR VOLUMEVAV
LAV LAVATORY
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LG LENGTH
LH LATENT HEAT
LT LAUNDRY TRAY
LWT LEAVING WATER TEMPERATURE
NUMBERNO
NORMALLY OPENN.O.
NOT IN CONTRACTNIC
NORMALLY CLOSEDN.C.
NOISE CRITERIANC
NOT APPLICABLEN/A
MAX
WASHER
PETROLEUM, OIL AND LUBRICANTS
PRESSURE DROP OR DIFFERENCE
FIBERGLASS REINFORCED PLASTIC
valves, special duty :
FLEXIBLE CONNECTOR
FLOWMETER, ORIFICE
FLOWMETER, VENTURI
FLOW SWITCH
PRESSURE GAUGE AND COCK
PRESSURE SWITCH
PUMP (INDICATE USE)
STRAINER
STRAINER, BLOW OFF
FIRE DEPARTMENT CONNECTION
PRE-ACTION VALVE
DRY-PIPE VALVE
ALARM CHECK VALVE
SIDEWALL SPRINKLER
PENDENT SPRINKLER
UPRIGHT SPRINKLER
fitting :
THERMOMETER
THERMOSTAT, ELECTRIC
TRAP, ELECTRIC (INDICATE TYPE)
BUSHING
CAP
CONNECTION, BOTTOM
CONNECTION, TOP
ELBOW, 90°
ELBOW, 45°
ELBOW, TURNED UP
ELBOW, TURNED DOWN
REDUCER, CONCENTRIC
REDUCER, ECCENTRIC (STRAIGHT, INVERT)
REDUCER, ECCENTRIC (STRAIGHT, DOWN)
TEE
TEE, OUTLET UP
TEE, OUTLET DOWN
TEE, SINGLE SWEEP
UNION, SCREWED
UNION, FLANGED
DIFFUSER, LINEAR
DUCT SECTION, POSITIVE PRESS., FIRST
DIRECTION OF FLOW
ACCESS DOOR, VERTICAL OR HORIZONTAL
CHANGE OF ELEVATION, RISE(R), DOWN(D)
COWL, (GOOSENECK) AND FLASHING
ACOUSTICAL LINING
FLEXIBLE DUCT
SOUND ATTENUATOR
FLEXIBLE CONNECTION
FIGURE IS ON TOP
FIGURE IS ON TOP
DUCT SECTION, NEGATIVE PRESS., FIRST
R
AD
FC
TRANSITION
TURNING VANES
S DETECTORS, FIRE AND/OR SMOKEF
dampers
BACKDRAFT DAMPER
BDD
S
ELECTRIC MOTOR OPERATED DAMPER
MANUAL VOLUME DAMPER
FD
FIRE DAMPER (PROVIDE ACCESS DOOR)
AD
PNEUMATIC OPERATED DAMPER
SMOKE DAMPER (PROVIDE ACCESS DOOR)
SPLITTER DAMPER
VD
AD
SD
M
SG
SR
SG
SR
EG
ER
RG
RR
UC 13mm
47.2
94.4
DG
TG
grilles, registers and diffusers :
(2-WAY SHOWN)
sprinkler
LATERAL
FLOOR OR GRADE
FLOOR OR GRADE
W/ MEASURING TAP
R
PS
P
FS
VFM
OFM
EJ
S
MV
AVA
S
R
PE
EP
S
M
GLOBE
CONTROL, PNEUMATIC-ELECTRIC
HOSE BIBB
A
PLAN ELEV.
BFP
(NAME)
ACID
G
CD
CD
JWS
JWR
MPS
MPC
LPS
LPC
BBD
PC
VPD
MU
FOD
FOV
FOG
FOS
FOR
CS
CR
MTWS
MTWR
HWS
HWR
A
VAC
(NAME)E
(NAME)
RD
M
RS
RL
D
CHWS
CHWR
CH/HWS
CH/HWR
SCO
FCO
FD
JACKET WATER SUPPLY
FLANGED
PIPING
DUCT WORK
WELDED
SCREWED
SOLVENT CEMENT
BELL AND SPIGOT
VAC VACUUM
LIQUID LINELL
200mm x 200mm
FLOOR SINK (200mm x 200mm)
60°C HOT WATER (60°C)
82.22°C HOT WATER (82.22°C)
810mm x 400mm
810mm x 400mm
810mm x 400mm
200mm NCD
(600mm x 300mmH, 472 LPS)
TRANSFER GRILLE ASSEMBLY
600/300
300x150
DOOR GRILLE (300mmx150mmH)
500/300L
(500mmWx300mmH, 94.4 LPS)
LOUVER, DOOR OR WALL
CUBIC MILLIMETER
C CENTIGRADE
DIA or o
CMH CUBIC METER PER HOUR
CU M CUBIC METER
FA FACE AREA OR FRESH AIR
FHC FIRE HOSE CABINET
FHY FIRE HYDRANT
FLA FULL LOAD AMPERES
GR GRAMS
DIAMETER, INSIDEID
ISOMETRICISO
IRON PIPE SIZEIPS
J JOULE
KG
K THERMAL CONDUCTIVITY
KCAL/HR KILOCALORIE PER HOUR
KILOGRAM
KG/SQ CM KILOGRAM PER SQ. CENTIMETER
KG/SQ CM A KILOGRAM PER SQ. CENTIMETER (ABSOLUTE)
KG/SQ CM G KILOGRAM PER SQ. CENTIMETER (GAUGE)
KW KILOWATT
KWH KILOWATT HOUR
KG/SM KILOGRAM PER SQ. METER
KG/SM A KILOGRAM PER SQ. METER (ABSOLUTE)
KG/SM G KILOGRAM PER SQ. METER (GAGE)
KJ KILOJOULE
L LITERS
Pa PASCAL
OS&Y
OXY OXYGEN
OUTSIDE SCREW & YOKE
OD DIAMETER, OUTSIDE
LPD LITERS PER DAY
LPH LITERS PER HOUR
LPS
LM LINEAR METER
LITERS PER SECOND
LPH, STANDARD CONDITIONSSLPH
LPS, STANDARD CONDITIONSSLPS
SG
SLPD LPD, STANDARD CONDITIONS
SL SENSIBLE LOAD
SH SENSIBLE HEAT
SPECIFIC GRAVITY
VLV VALVE
V VOLT
SF SAFETY FACTOR
SEC SECOND
OAIL OUTSIDE AIR INTAKE LOUVER
OA OUTSIDE AIR
NOT TO SCALENTS
MIN
MPH
M METERS
MAXIMUM
MINIMUM OR MINUTE
METERS PER HOUR
MPS METERS PER SECOND
MM MILLIMETER
NPT NATIONAL TAPER PIPE (THREAD) SCH SCHEDULE
SP STATIC PRESSURE
SQUARE METER
SOLDERED/BRAZED
M E C H A N I C A L M A T E R I A L I N D I C A T I O N S & S Y M B O L S
A B B R E V I A T I O N S
HOT WATER SUPPLY
MEDIUM TEMPERATURE
HOT WATER RETURN
MEDIUM TEMPERATURE
HOT WATER SUPPLY
LOW TEMPERATURE
HOT WATER RETURN
LOW TEMPERATURE
(810mm WIDTH x 400mm DEPTH)
DUCT SIZES SHOWN
REGISTER, CEILING
EXHAUST AIR GRILLE OR
REGISTER, SIDEWALL
SUPPLY AIR GRILLE OR
REGISTER, CEILING
SUPPLY AIR GRILLE OR
REGISTER, CEILING
RETURN AIR GRILLE OR
(13mm, 47.2 LPS)
UNDERCUT DOOR
(200mm NECK DIAMETER)
CEILING DIFFUSER, ROUND TYPE
SQUARE TYPE
CEILING DIFFUSER,
GATE, NORMALLY CLOSED
REFRIGERANT (134A, 22, ETC)R134A,R22
GATE, NORMALLY OPEN
DFW
MECHANICAL MATERIAL INDICATIONS &
BLDG NO. 257
REPAIR TRANSIENT LIVING QUARTER,
WARRIOR BASECHONG, ST
107389
M-2
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
5. CONCRETE REMOVAL AND RESTORATION SHALL CONFORM TO SPECIFICATION.
NECESSARY DUCT CONNECTION(S) TO FUNCTION AS ORIGINALLY INTENDED.
12. PRIOR TO INSTALLING NEW HVAC AND PLUMBING PIPING CONTRACTOR MUST
COORDINATE WITH EXISTING DUCTWORK AND PIPING ELEVATION/LOCATION.
IF EXISTING DUCT ELEVATION IS CONFLICTED WITH NEW PIPING INSTALLATION,
REMOVE EXISTING DUCTWORK AND INSTALL NEW DUCTWORK AND MAKE ALL
CONTRACTING OFFICER FOR APPROVAL.
CONTRACTOR ACCORDING TO ACTUAL FIELD CONDITIONS AND SUBMITTED TO THE
FIELD CONDITIONS. SUCH DETAILS SHALL BE PREPARED IN THE FIELD BY THE
11. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACT
SUCH AS ANCHORS, HANGERS/SUPPORT, ETC.
10. ALL HVAC PIPING/DUCTWORK TO BE REMOVED SHALL INCLUDE ALL IT'S ACCESSORIES
9. ANY OPENING RESULT FROM THE REMOVAL WORK THAT'S NOT TO BE RE-USED
SHALL BE PATCHED OR RESTORED TO MATCH ADJACENT SURFACE OR AREA.
GENERAL NOTES
PER SPEC.
THIS CONTRACTOR.
AND SHALL BE VERIFIED AT THE JOB SITE.
CORRECTIONS FOR CONTRACTING OFFICER'S APPROVAL.
7. ALL WALL/FLOOR/ROOF OPENINGS RESULTED FROM THE REMOVAL OF PIPING AND
4. ANY PIPES THAT PENETRATE FIRE RATED WALL (EXISTING/ NEW) SHALL BE SEALED
6. NO MECHANICAL WORK CAN BE STARTED WITHOUT AN APPROVED SHOP DRAWINGS.
SHOP DRAWING SHALL NOT BE THE EXACT DUPLICATION OF THE CONTRACT DRAWING.
2. LOCATION AND SIZES OF EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC. APPROXIMATE
OFFICER'S REPRESENTATIVE ATTENTION WITH RECOMMENDATIONS FOR PROPER
IF ANY DISCREPANCY IS DETECTED, IT SHOULD BE BROUGHT TO THE CONTRACTING
THE EXISTING CONDITIONS, EQUIPMENT, FINISHES, ETC., PRIOR TO START OF WORK.
1. THE CONTRACTOR SHALL VISIT THE SITE AND SHALL FAMILIARIZE HIMSELF WITH
THE WORK PERFORMED UNDER THIS CONTRACT SHALL BE REPAIRED OR REPLACED BY
THE EXISTING EQUIPMENT ANY EQUIPMENT, DUCT WORK, PIPING ETC. DAMAGED DUE TO
3. CONNECT TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE
THE REQUIREMENTS OF SEAL CLASS C.
8. ALL SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED
ACCORDING TO SMACNA STATIC PRESSURE CALSS 500PA AND DUCTWORK SHALL MEET
DUCTWORK SHALL BE PATCHED OR RESTORED TO MATCH ADJACENT SURFACE OR AREAS.
SCOPE OF WORK
13.
CHANGES REQUIRED TO MAKE THIS
CONTRACTOR SHALL PROVIDE NECESSARY SHOP DRAWINGS FOR ANY
REQUIREMENT FOR GAS ONLY BURNERS MAY BE JUSTIFIABLE. THE
PACKAGE, PRIOR TO THE START OF CONSTRUCTION, THEREFORE THE
PROVIDE NATURAL GAS ACCESS TO THE BUILDING UNDER THIS DESIGN
CONCURRENT NATURAL GAS CONVERSION PROJECT PACKAGES MAY
HEATING SYSTEMS WITH DPW PRIOR TO THE START OF CONSTRUCTION.
AND OIL) BURNERS FOR HEATING HOT WATER AND DOMESTIC HOT WATER
THE CONTRACTOR SHALL COORDINATE THE USAGE OF DUAL FUEL (GAS
SPRINKLER WORK
REPAIR AND MAINTENANCE WORK
HVAC SYSTEM
1.
2.
1.
2.
3. REPAIR BY REPLACEMENT EXISTING BACK FLOW PREVENTER (BFP) AND PRESSURE REDUCING VALVE (PRV) ASSEMBLY, INCLUDING PIPE
3.
SUPPORTS AND HOSE BIBB WITH NEW.
1. REPAIR BY REPLACEMENT OF EXISTING FIRE PROTECTION SYSTEM WITH NEW WET TYPE SPRINKLER SYSTEM AND ASSOCIATED PIPING WITH NEW.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED ELECTRIC UNIT HEATER WITH NEW.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED ELECTRIC WATER COOLER WITH NEW.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED ALL COLD WATER PIPING WITH NEW.
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED ENERGY RECOVERY VENTILATIONS, DUCTWORK AND DIFFUSERS WITH NEW.
GENERAL NOTES AND SCOPE OF WORK
REPAIR BY REPLACEMENT OF EXISTING DETERIORATED HEATING BOILER, AIR COOLED CONDENSING UNIT, AIR HANDLING UNIT AND DUCT
WITH SPLIT TYPE HEAT PUMP UNITS INCLUDING CONC. PAD.
PLUMBING SYSTEM
BLDG NO. 257
REPAIR TRANSIENT LIVING QUARTER,
M-3
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
M E C H A N I C A L E Q U I P M E N T S C H E D U L E
R E M A R KD E S C R I P T I O NITEM NO QTY.
EWC
ELECTRIC WATER COOLER
MOTOR : 1/5 HP, 115 V, 1 PH, 60 HZ.
FLOOR MOUNTED TYPE, MECHANICALLY
CAPACITY : 8.0 GPH, 80 DEG.F. TO 50 DEG.F.
& COMPRESSOR SHALL CONFORM TO ARISTANDARD 1010.
MECH RM (123)
HORIZONTAL
REMARKS
HP
1/20
VOLT/PH/HZRPMLPS
EAT
1,550256.210
(DEG C)
EWT
(KW)
HEATING
CAPACITY
LPS
82.12.3 0.05
(DEG C)
TYPESERVICE
DISCHARGE TYPE
Q'TYITEM NO
FAN CAPACITY
UH
ELECTRIC UNIT HEATER
HPU
BE INSTALLED AS PER MANUFACTURER RECOMMENDATIONS.
WITH 7 DAY PROGRAMMABLE MOD # PQRCVSL0208V/60Hz/ 300.2 R-410A4-WAY CASSETTE TYPE, Q'TY
COOLING CAP
TYPE
HEATING CAP
ITEM NO
INDOOR SPLIT SYSTEM HEAT PUMP UNIT
(BTU/H ) (BTU/H)
REFRIGERANT
TYPE
FAN CAPACITY
AMPS VOLT/PH/HZ
21,500
POWER
INPUT(W)
SERVICE REMARKS
19,100
AIR CAP
BEDROOM (101, 102, 201
AND 202)
1PH
1. ALL HEAT PUMP UNITS REFRIGERANT PIPING SHALL
2. WALL MOUNTED TEMPERATURE CONTROLLER
DUCT LESS CABINET
(CFM)
3. FOR CASSATTE TYPE UNITS, MFG SHALL PROVIDE AIR DEFLECTOR PLATE
4. BUILT-IN CONDENSATE DRAIN PUMP
5. CASSETTE COVER MODEL PDC-TH1.
6. LG MODEL ARNU183TQC4 OR APPROVED EQUAL
TOTAL
COOLING CAP
(BTU/H)
Q'TY SERVICEITEM NO
TOTAL
HEATING CAP
(BTU/H)
OHPU
POWER SUPPLY
TYPE
TYPE
OUTDOOR HEAT
PUMP UNIT
QTY POWER(A) QTY POWER(A)
COMPRESSOR SUPPLY FAN
VOLT/PH/HZ
TYPE
AIR CAP.
(CFM)
3 3 PROPELLER 17,600
MCA MOP
REFRIGERANT
TYPE
HEATING CAPACITY SHALL BE BASED ON 8 DEG C
208/3/60 R410A
REMARKS
BE INSTALLED AS PER MANUFACTURER RECOMMENDATIONS.
OUTDOOR SPLIT SYSTEM HEAT PUMP UNIT
1ST, 2ND FLOOR HPU
MUILT V TYPE
216,000
POWER
INPUT(W)
14.01
POWER
INPUT(W)
15.87243,000 48.8 25.3
HSS DC SCROLL (B) /19.0
(A)17.0/19.0
4.0/6.0
1. ALL HEAT PUMP UNITS REFRIGERANT PIPING SHALL
2. COOLING CAPACITY SHALL BE BASED ON 35 DEG C
3. SIMILAR TO LG MODEL ARUN216BTE4 OR APPROVED EQUAL
ERV 590 208V/60Hz/1PH470AIR TO AIR HEAT EXCHANGER
CROSS FLOW TYPE
Q'TY TYPE
AIR CAPACITY
ITEM NO VOLT/PH/HZ
ENERGY RECOVERY VENTILATION
REMARKS
(CFM)
POWER INPUT
(W)
SERVICE
3.44
RATED AMPS
(A)
BEDROOM (101, 102, 201
AND 202)
LG MULTI V MODEL ARVU063ZEA2 OR APPROVED EQUAL
AIR COOLED WITH AIR COOLED CONDENSER
MECHANICAL EQUIPMENT SCHEDULE
208/1/60
BLDG NO. 257
REPAIR TRANSIENT LIVING QUARTER,
M-4
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
T T
TH
TC
M
SCALE : 1: 50
BEDROOM
BEDROOM
MECH
RC T
S
M4
EXISTING 1ST FLOOR REMOVAL PLAN
EXST. AIR COOLED CONDENSING UNIT,
CONC. PAD AND PIPING TO BE REMOVED
EXST. ALL DUCT TO BE REMOVED(TYP)
EXST. ALL EQUIPMENTS AND DUCT & HVAC, PLUMBING
AND OIL PIPING TO BE REMOVED IN MECH ROOMEXST. SUMP AND FUEL OIL PIPING
TO BE REMOVED
EXISTING 1ST FLOOR REMOVAL PLAN
BLDG NO. 257
REPAIR TRANSIENT LIVING QUARTER,
M-5
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
BEDROOM
BEDROOM
T
EXST. ALL DUCT TO BE REMOVED(TYP)
SCALE : 1: 50M5
EXISTING 2ND FLOOR REMOVAL PLAN
EXST. SMOKE STACK TO BE REMOVED
EXISTING 2ND FLOOR REMOVAL PLAN
BLDG NO. 257
REPAIR TRANSIENT LIVING QUARTER,
M-6
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
SCALE : 1: 50M6
BEDROOM
BEDROOM
ROOM
MECH
EAOA EAOA
ROUND PAN DIFFUSER
S.A Q : 196 CFM
ø420×ø250 (ND:ø250)
ARVU063ZEA2
ROUND PAN DIFFUSER
R.A Q : 295 CFM
ø420×ø250 (ND:ø250)
ARVU063ZEA2
ROUND PAN DIFFUSER
R.A Q : 295 CFM
ø420×ø250 (ND:ø250)
ARVU063ZEA2
ROUND PAN DIFFUSER
S.A Q : 196 CFM
ø420×ø250 (ND:ø250)
ARVU063ZEA2
R A
S A
E A
O A
R A
S A
E A
O A
ERV
ERV
1ST FLOOR HVAC PLAN(ENERGY RECOVERY VENTILATION)
1.
NOTES:
CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION
2.
OF DUCT IN FIELD(TYP)
VENTILATION SYSTEM IN MECH. ROOM.
CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR ENERGY RECOVERY
(ENERGY RECOVERY VENTILATION)
1ST FLOOR HVAC PLAN
BLDG NO. 257
REPAIR TRANSIENT LIVING QUARTER,
M-7
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
BEDROOM
BEDROOM
EAOA EAOA
ERV
ROUND PAN DIFFUSER
R.A Q : 196 CFM
ø420×ø250 (ND:ø250)
ARVU063ZEA2
ROUND PAN DIFFUSER
S.A Q : 196 CFM
ø420×ø250 (ND:ø250)
ARVU063ZEA2
ROUND PAN DIFFUSER
R.A Q : 196 CFM
ø420×ø250 (ND:ø250)
ARVU063ZEA2
ROUND PAN DIFFUSER
S.A Q : 196 CFM
ø420×ø250 (ND:ø250)
R A
S A
E A
O A
R A
S A
E A
O A
ERV
SCALE : 1: 50M7
2ND FLOOR HVAC PLAN(ENERGY RECOVERY VENTILATION)
1.
NOTES:
CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION
2.
OF DUCT IN FIELD(TYP)
VENTILATION SYSTEM IN MECH. ROOM.
CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR ENERGY RECOVERY
(ENERGY RECOVERY VENTILATION)
2ND FLOOR HVAC PLAN
BLDG NO. 257
REPAIR TRANSIENT LIVING QUARTER,
M-8
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
BEDROOM
BEDROOM
ROOM
MECH
HPU
HPU
HPU
HPU
HPU
HPU
HPU
HPU
HPU
HPU
OHPU
OHPU
EUH
CONC. PAD
SCALE : 1: 50M8
1ST FLOOR HVAC PLAN(HEAT PUMP)
1.
NOTES:
CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION
2.
OF HEAT PUMP AND PIPING IN FIELD(TYP)
CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR HEAT PUMP AND
PIPING IN MECH. ROOM.
1ST FLOOR HVAC PLAN
(HEAT PUMP)
BLDG NO. 257
REPAIR TRANSIENT LIVING QUARTER,
M-9
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
BEDROOM
BEDROOM
HPU
HPU
HPU
HPU
HPU
HPU
HPU
HPU
HPU
HPU
HPU
HPU
SCALE : 1: 50M9
2ND FLOOR HVAC PLAN(HEAT PUMP)
1.
NOTES:
CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION
2.
OF HEAT PUMP AND PIPING IN FIELD(TYP)
CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR HEAT PUMP AND
PIPING IN MECH. ROOM.
2ND FLOOR HVAC PLAN
(HEAT PUMP)
BLDG NO. 257
REPAIR TRANSIENT LIVING QUARTER,
M-10
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
MECH
MAIN PIPE
50mm SEWER
FIRST FLOOR SECOND FLOOR
POC
WATER PIPE.
25mm DOMESTIC COLD
VALVE TO BE REPLACED
EXIST. BACK-FLOW PREVENTER
ASSEMBLY TO BE REPLACED
EXIST. PRESURE REDUCING 1
M16-
M16-
SCALE : 1: 50
EWC
EWC
CW
CW
M10
PLUMBING PIPING PLANS
1.
NOTES:
CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION
2.
OF CW, SEWER AND VENT PIPING IN FIELD(TYP)
(COLD WATER PIPING, SEWER AND VENT PIPING)
CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PLUMBING PIPING
PRIOR TO COLD, SEWER, VENT PIPING INSTALLATION.
PLUMBING PIPING PLANS AND NOTES
BLDG NO. 257
REPAIR TRANSIENT LIVING QUARTER,
M-11
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
DESCRIPTION OF DRAWINGS
INDEX OF DRAWINGS
F-1
NO.
INDEX OF DRAWINGS & LEGEND & ABBREIVATION
SCALE
NONE
NONE
1/150
DETAILS
<S-257>
<DETAILS>
1/150NEW 2ND FLOOR FIRE PROTECTION CLASSIFICATION PLAN
F-6
F-3
F-4
F-5
F-7
1/50
1/150NEW 1ST FLOOR FIRE PROTECTION PIPING PLAN
NEW 2ND FLOOR FIRE PROTECTION PIPING PLAN
NO.
SHEET
1/150
F-2 NEW 1ST FLOOR FIRE PROTECTION CLASSIFICATION PLAN
NEW MECH ROOM FIRE PROTECTION PIPING PARTIAL PLAN
INDICATING BUTTERFLY
OS & Y
KEY OPERATED
LEGEND & ABBREVIATION
SP MAIN SUPPLY SPRINKLER
UPRIGHT SPRINKLER(K=5.6)
CUTTING POINT
CAP
NON-RISING STEM
TAMPER DETECTION SWITCH
CHECK
WALL MOUNTED TEST HEADER
CONNECTION, TOP
ELBOW, 90
ELBOW, TURNED UP
ELBOW, TURNED DOWN
TEE
TEE, OUTLET UP
TEE, OUTLET DOWN
CONNECTION, BOTTOM
RISER
GATE, NORMALLY CLOSED
GLOBE
DIAPHRAGM
GATE
GATE, NORMALLY OPEN
SWING GATE CHECK
TYPICALTYP.
NO
EXST EXISTING
ABBREVIATIONS
MAX MAXIMUM
MIN MINIMUM
DRAIN PIPED NUMBER
DRAWINGDWG
CONN
CONT
CONNECTION
RM ROOM
W/ WITH
W/O WITHOUT
SCH SCHEDULE
ALARM CHECK VALVE
FIRE DEPARTMENT CONNECTION
(2-WAY SHOWN)
AN APPLIANCE WITHIN THE ENCLOSURE AND DEAD ENDS IN THE ENCLOSURE.
OR DUCT SHALL PENETRATE ANY STAIR OR EXIT PASSAGEWAY ENCLOSURE UNLESS IT SERVES
8. ALL PIPING, SANITARY, VENT, WASTE, PLUMBING, OTHER PIPING, POWER OR CONTROL CIRCUTS,
3. PROVIDE EARTHQUAKE PROTECTION (SWAY BRACING), END OF BRANCH LINE AND SEISMIC
BRACING CALCULATION IN ACCORDANCE WITH NFPA 13 REQUIREMENTS; SPRINKLERS
WITH O-RINGS ARE NOT PERMITTED.
4. FIRE PROTECTION PLANS SHOWN ARE USED FOR COST ESTIMATE PURPOSE ONLY.
5. CONTRACTOR SHALL SUBMIT HYDRAULIC CALCULATIONS AS REQUIRED BY NFPA 13 CHAPTER
22-"PLANS AND CALCULATIONS" PRIOR TO SPRINKLER PIPING INSTALLATION. THE
CONTRACTOR SHALL CONFORM TO THE SYMBOLS INDICATED IN NFPA 170 TO DEVELOP THE
AS-BUILT DRAWINGS FOR THIS PROJECT.
6. PROVIDE MINIMUM 1M X 2M SPACE FOR EACH FIRE SPRINKLER RISER FOR INSTALLATION
AND MAINTENANCE. TEST DRAINS ARE NOT TO BE TERMINATED AT WALL SINKS OR FLOOR
DRAINS, BUT MUST TERMINATE TO THE BUILDING EXTERIOR. SPRINKLER RISERS SHALL NOT
7. ALL AUTOMATIC SPRINKLER DRAIN VALVES FOR FIRE DEPARTMENT CONNECTIONS SHALL BE
INSTALLED IN THE HORIZONTAL POSITION.
WATER SUPPLY AND THE SPRINKLER SYSTEM DEMAND.
ENTIRE FACILITY. A MINIMUM 10% SAFETY FACTOR IS REQUIRED BETWEEN THE AVAILABLE
SHOPDRAWINGS. AUTOMATIC SPRINKLER PROTECTION SYSTEM IS REQUIRED TO PROTECT THIS
THE HYDRANT LOCATIONS, FLOW TESTS, AND DATE SHALL BE INDICATED ON THE
ON NFPA 291 REQUIREMENTS AND UTILIZE THIS DATA TO DESIGN THE SPRINKLER SYSTEM.
2. THE CONTRACTOR SHALL CONDUCT WATER SUPPLY HYDRANT TEST FOR THIS PROJECT BASED
LISTED AND FM APPROVED IN ACCORDANCE WITH NFPA 13 AND THE PROJECT SPECIFICATION.
CEILING PANELS, LIGHTING FIXTURES, AND HVAC AIR DEVICES. ALL EQUIPMENT SHALL BE UL
EQUIPMENT LISTINGS. CONTRACTOR SHALL COORDINATE SPRINKLER HEADS LOCATIONS WITH,
SHALL BE IN ACCORDANCE WITH APPLICABLE CODES, MANUFACTURER'S RECOMMENDATIONS, AND
INSTALLATION. THE EQUIPMENT SHOWN ARE SUGGESTED LOCATIONS HOWEVER FINAL LAYOUT
NFPA 13 AND SPECIFICATION REQUIREMENTS AND SUBMIT FOR APPROVAL PRIOR TO
CONTRACTOR SHALL SUBMIT A COMPLETE FIRE SPRINKLER SYSTEM SHOPDRAWINGS BASED ON
PERFORMANCE BASED WHICH MEANS CONCEPTUAL REQUIREMENT ONLY. THE SPRINKLER
TO FULLY PROTECT THIS FACILITY. THE FIRE SPRINKLER SYSTEM SHOWN THESE DRAWING IS
1. THE CONTRACTOR SHALL PROVIDE AND INSTALL AN AUTOMATIC WET PIPE SPRINKLER SYSTEM
AUTOMATIC FIRE SUPPRESSION(S) GENERAL NOTES:
INDEX OF DRAWING, LEGEND &
SUPPRESSION GENERAL NOTES
ABBREVIATION AND AUTOMATIC FIRE
BLDG NO. 257
REPAIR TRANSIENT LIVING QUARTER,
M-12
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
BEDROOM
BEDROOM
MECH
150 150 150 150 150 150 150 150
UPRIGHT TYPE SPRINKLER HEAD
15mm QUICK RESPONSE
UPRIGHT TYPE SPRINKLER HEAD
20mm QUICK RESPONSE
SEE
T
S P (W
SCALE : 1: 50M12
1ST FLOOR FIRE PROTECTION PIPING PLAN
1ST FLOOR FIRE PROTECTION PIPING PLAN
M15-
SEE
M15-
SEE
M14-
H-SHAPE 125x125x6.5x9
1.
NOTES:
2.
CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR H-SHAPE TO SUPPORTED
SPRINKLER PIPING.
THE H-SHAPE SHALL BE INSTALLED RIGHT ABOVE THE SPRINKLER PIPING.
BLDG NO. 257
REPAIR TRANSIENT LIVING QUARTER,
M-13
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
BEDROOM
BEDROOM
UPRIGHT TYPE SPRINKLER HEAD
15mm QUICK RESPONSE
SP
(W
T
150 150 150
150 150 150 150
150 150 150 150 150 150 150
25 25
SCALE : 1: 50M13
2ND FLOOR FIRE PROTECTION PIPING PLAN
2ND FLOOR FIRE PROTECTION PIPING PLAN
BLDG NO. 257
REPAIR TRANSIENT LIVING QUARTER,
M-14
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
(5.6)
115K-FACTOR OF
SPRINKLER NOZZLE
MIN. 2.4 M (8 FT)
MAX. 4.6 M (15 FT)
MECH ROOMBED ROOM
OCCUPANCY
HC-2 HAZARD
ORDINARY TEMPERATURE RATING
(57°C-77°C / 135°F-170°F)
OCCUPANCY
HC-1 HAZARD
60 MIN.
140 SM (1500 SF)
950 LPM (250 GPM)
QUICK RESPONSE
4.1 LPM/SM (0.10 GPM/SF)
WET SPRINKLER
INTERMEDIATE TEMPERATURE RATING
(79°C-107°C / 175°F-220°F)
60 MIN.
MIN. 1.8 M (6 FT)
230 SM (2500 SF)
MAX. 4.6 M (15 FT)
950 LPM (250 GPM)
12.07 SM (130 SF)
QUICK RESPONSE
8.2 LPM/SM (0.20 GPM/SF)
WET SPRINKLER
- RESIDUAL FLOW : 3112 LPM (822 GPM)
- WATER FLOW TEST DATE : MAR. 11. 2016
- RESIDUAL PRESSURE : 2.28 BAR (33 PSI)
WATER SUPPLY INFORMATION*
APPLICATION AREA
DESIGN AREA
HOSE STREAM
DURATION OF SUPPLY
DESIGN DENSITY
FIRE PROTECTION REQUIREMENTS
HAZARD
DESCRIPTION
SPRINKLER TEMPERATURE
RATING*
MAX. & MIN. SPACE OF
BETWEEN SPRINKLERS
MAX. COVERAGE PER
SPRINKLER TYPE
SPRINKLER
TYPE OF SYSTEM
(8.0)
- STATIC PRESSURE : 2.62 BAR (38 PSI)
THIS DWG.
KEY PLAN
REFER TO PARA 4-2.3.1, UFC 3-600-01(1. MAR. 2013, CHANGE 3)**
20.90 SM (225 SF)
N.O
N.O
N .C
N .O
BACKFLOW PREVENTER
ALARM CHECK VALVE
HOSE HEADER CONNECTION
FIRE DEPARTMENT CONNECTION
OS&Y GATE VALVE
CHECK VALVE
MECH
N.O.N.O.
TEST HOSE HEADER
FIRE DEPARTMENT CONNECTION
SPARE SPRINKLER HEAD CABINET
150mm ALARM CHECK VALVE
BACKFLOW PREVENTER
100mm CHECK VALVE
100mm GATE VALVE
(WITH TAMPER SWITCH)
150mm GATE VALVE
(WITH TAMPER SWITCH)
FROM WATER SUPPLY
SCALE : 1: 50M14
MECH ROOM FIRE PROTECTION PIPING PARTIAL PLAN
- M14
MECH ROOM FIRE PROTECTION PIPING ISOMETRIC DIAGRAM
NOT TO SCALE
MECH ROOM FIRE PROTECTION PIPING
PARTIAL PLAN & ISOMETRIC DIAGRAM
AND FIRE PROTECTION REQUIREMENTS
BLDG NO. 257
REPAIR TRANSIENT LIVING QUARTER,
M-15
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
F-7
SEE
CONC. THRUST BLOCKTIE-ROD
GL.
SERVICE MAIN
FROM FIRE
FLOOR SLEEVE
DUCTILE IRON FLANGE
DROP INSIDE OF
AND SPIGOT PIECE
TIE-ROD SHALL
PIPE SLEEVE FL.
SEALANT
STEEL PIPE
AG
UG
DIMENSION TABLE FOR THRUST BLOCK
SIZE
PIPE
1,500 PSF (7,324 KG/M2)
SOIL BEARING PRESSURE
TYPE I
TYPE
CB
A
DEPTH
THRUST BLOCK
PIPE TRENCH WALL
PIPE
THRUST BLOCK
TRENCH
EXCAVATION
AT THRUST
BLOCK
ENTERING OR LEAVING THE SUBJECT BUILDING.
THIS DETAIL SHALL BE UTILIZED WHERE FIRE MAIN SERVICE LINES ARE
NOTES
1.
THE BURIAL DEPTH OF THE INCOMING FIRE PROTECTION WATER PIPE LINE AT A MIN. 1.4m.2.
CLEVIS HANGER
SUPPORT NUT
PIPE
LOCKING NUT
HANGER ROD
HEAVY DUTY
ROD DIA
HANGER ROD
FOR INCLINED PIPE
TYPE 3 PIPE CLAMP
BRANCH PIPE
METAL DECK
PURLIN
ANGLE
(SLOPE CEILING)
ROD DIA
FL.
25mm GLOBE VALVE
SPLASH BLOCK
GL.
PRESSURE GAUGE
SIGHT GLASS
EXTERIOR WALL
A P P
R O
X m m
(N O
T
O V E
R m m
PIPE SUPPORT
(RISER CLAMP)
1. CORROSION-RESISTANT ORIFICE GIVING FLOW EQUIVALENT
NOTE
TO THE SMALLEST SPRINKLER ORIFICE IN THE SYSTEM
RESISTANT OUTLET
SMOOTH BORE CORROSION
REMOTE BRANCH LINE
25mm PIPE FROM END OF
WITH ORIFICE GIVING FLOW
EQUIVALENT TO ONE SPRINKLER
BOLT & NUT
PIPE
HOUSING
FLUSH SEAL GASKET
BOLT & NUT
COUPLING HOUSING
THE GASKET OF RIGID COUPLING AND FLEXIBLE COUPLING SHALL BE THE FLUSH TYPE IN ACCORDANCE
NOTE
P
IP
E
SEALANT #2
BACK UP MATERIAL
(CLOSED CELL
FLEXIBLE FOAM
RUBBER OR PLASTIC)
C
SLEEVE
FIN. FLOOR
WATERPROOFING SLEEVE
FLASHING
20KG/SQ. METER
OR 450 GMS COPPER
TEST HEADER FOR BACKFLOW
PREVENTER FLOW TEST
PRESSURE GAUGE(2-REQUIRED)
DESCRIPTION
WATER MOTOR ALARM GONG
TAMPER SWITCH
MAIN DRAIN VALVE
RETARDING CHAMBER
OS&Y GATE VALVE
PRESSURE SWITCH
FIRE DEPARTMENT CONNECTION
W/TAMPER SWITCH
LOCAL ALARM SHUTOFF VALVE
AUTO BALL DRIP VALVE
WATER MOTOR ALARM DRAIN
CHECK VALVE
DOUBLE CHECK TYPE BACKFLOW
PREVENTER
15 STRAINER
ITEM
MAIN DRAIN5
PRESSURE RELIEF VALVE
N.O.
6 17
N.O.
N .O
MAX.
610MM
PIPE SUPPORT
MAX.
610MM
TO SPRINKLER MAIN
GL.
FL.
TO DRAIN
4-WAY BRACING
PER NFPA 13
N .O
FLEXIBLE COUPLING
4N .C
MIN.
300MM
AG
UG
S A
M E
S
F .D .C m m m m (M
IM
.4
M A
X .1
S A
IN
D R
A
IN
(M A
X m m
S A
A
IN
S A
A
IN
ALARM CHECK VALVE
PIPE SLEEVE
SEALANT
NOTE
IF SURGE RESTRAINERS ARE NOT USED, ROD SHALL EXTEND TO THE PIPE.
W/TAMPER SWITCH
FEED MAIN
WATER FLOW SWITCH
150(MIN.)600(MIN.)
PRESSURE GAUGE
OS & Y VALVE
50mm m m
TEST VALVE
SIGHT GLASS
DRAIN
SECTION
VALVE
m m
UNION
4-WAY BRACING
PER NFPA 13
CORROSION-RESISTANT ORIFICE GIVING FLOW EQUIVALENT
NOTE
W/ORIFICE
SEE THE NOTE
TO THE SMALLEST SPRINKLER ORIFICE IN THE SYSTEM.
BRACE PIPE
SCH. 40, 1 IN.
UNIVERSAL SWIVEL SWAY
BRACE ATTACHMENT
SWAY BRACE ATTACHMENT
W/LEAF SPRING
M
IN
. 1
" BRACE PIPE
SCH. 40
LONGITUDINAL "IN-LINE"
SWAY BRACE ATTACHMENT
UNIVERSAL SWIVEL SWAY
BRACE ATTACHMENT
PLAN SYMBOL
TO MAIN RISER
UNIVERSAL SWIVEL SWAY
BRACE ATTACHMENT
BRACE PIPE
SCH. 40, 1 IN.
SWAY BRACE ATTACHMENT
W/LEAF SPRING
M
IN. 1"
CONCRETE FASTNER
PLAN SYMBOL
PERPENDICULAR TO MAIN PIPE
MAIN
A
PARALLEL TO MAIN PIPE
PLAN SYMBOLMAIN
B
9.5 mm(3/8 in.)
END OF BRANCH LINE
SURGE RESTRAINER
ADJUSTABLE RING
HANGER
HANGER ROD
9.5 mm(3/8 in.)
RESTRAINT ROD
(THREADED AT BOTH ENDS)
SWIVEL ATTACHMENT
(THREADED AT BOTH ENDS)
L/R 400
HANGER ROD
9.5 mm(3/8 in.)
(THREADED AT BOTH ENDS)
9.5 mm(3/8 in.)
RESTRAINT ROD
(THREADED AT BOTH ENDS)
=L/R 400
ADJUSTABLE RING
HANGER
ADJUSTABLE RING
HANGER MAX.
150mm
BEAM CLAMP
BAR JOIST
BEAM CLAMP
STRAP
RETAINING
NOT TO SCALEM15
MAIN RISER DETAIL
- NOT TO SCALEM15
2 MAIN RISER CONNECTION
- NOT TO SCALEM15
3 WITH WATERPROOFING
PIPE SLEEVE-THRU FLOOR
- NOT TO SCALEM15
4 SWAY BRACE
- NOT TO SCALEM15
5 FLOOR CONTROL VALVE
- NOT TO SCALEM15
6 CLEVIS HANGER & PIPE CLAMP
- NOT TO SCALEM15
7 BRANCH LINE RESTRAINT
- NOT TO SCALEM15
8 ON WET SPRINKLER SYSTEM
SYSTEM TEST CONNECTION
- NOT TO SCALEM15
9 FLEXIBLE COUPLING
DETAILS-1
BLDG NO. 257
REPAIR TRANSIENT LIVING QUARTER,
PIPE HANGER
BACK-FLOW PREVENTER
REDUCED PRESSURE
STRAINER
(TYP OF 3)
GATE VALVE
GLOBE VALVE
UNION (TYP)
CW TO SYSTEM
PET COCK (TYP OF 2)
REDUCING TEE (TYP)
REDUCER
(TYP OF 2)
GAUGE
PRESSURE
VALVE
REDUCING
PRESSURE
(TYP OF 2)
TAPPING
GAUGE
M-16
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
NOT TO SCALE
BACKFLOW PREVENTER & PRESSURE REDUCING STATION
M16 - NOT TO SCALEM16
ACTUAL EQUIPMENT SIZE6" 6"
CONC. PAD DETAIL
EXST CONC FLOOR
1/ 2" THK EXPANSION JOINT ( TYP )
CROSS WAY ( TOP & BOTTOM )
#4 STL BAR @ 10" OC
CONC PAD
"B" "B"
S E C T I O N "B" - "B"
P L A N
A C
T U
A L
E
Q U
IP
M E
N T
S
IZ
E
ACTUAL EQUIPMENT SIZE
6"
6"
6" 6"
EQUIPMENT UNIT
TEE DRAINGE PATTERN
AS REQ'D
PIPE SLEEVE
NOTE : WATER COOLER SHELL BE STATIONARY
WATER COOLER
ELECTRIC
BUBBLER
P-TRAP
- NOT TO SCALEM16
3 ELECTRIC WATER COOLER
DETAILS-2
BLDG NO. 257
REPAIR TRANSIENT LIVING QUARTER,
| Bldg# S-257,WB-M1 |
| Bldg# S-257,WB-M2 |
| Bldg# S-257,WB-M3 |
| Bldg# S-257,WB-M4 |
| Bldg# S-257,WB-M5 |
| Bldg# S-257,WB-M6 |
| Bldg# S-257,WB-M7 |
| Bldg# S-257,WB-M8 |
| Bldg# S-257,WB-M9 |
| Bldg# S-257,WB-M10 |
| Bldg# S-257,WB-M11 |
| Bldg# S-257,WB-M12 |
| Bldg# S-257,WB-M13 |
| Bldg# S-257,WB-M14 |
| Bldg# S-257,WB-M15 |
| Bldg# S-257,WB-M16 |
File details come from the government source that posted it. Updated .