A02_Drawing_files___58484_ELEC.pdf
PDF 4 MB Posted
- Attached to
- Repair Bldg# 753
- Solicitation number
- W91QVN16R0201
About this file
Drawing files _ 58484 -6
View the file
Other files
| File | Type | Posted |
|---|---|---|
| A21_Submittal_Register___58484.xls | XLS spreadsheet | |
| A21_W91QVN-16-R-0201.docx | DOCX document | |
| A02_Drawing_files___58484___ARCH.pdf | ||
| A02_Drawing_files___58484___MECH.pdf | ||
| A02_Drawing_files___58484___CIVIL.pdf | ||
| A02_Drawing_files___58484___ELEC.pdf | ||
| A02_Drawing_files___58484___TITLE.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES
1.
2.MOUNTING HEIGHTS ABOVE FLOOR SHALL BE AS FOLLOW UNLESS OTHERWISE
NOTED ON THE DRAWING.
LIGHTING FIXTURE SEE LIGHTING FIXTURE SCHEDULE
PANELBOARD SEE SPECIFICATION
SAFETY SWITCH 1524mm TO CENTER OF THE ENCL
RECEPTACLE,TELEPHONE OUTLET 305mm TO CENTER OF THE ENCL
MOTOR CONTROLLER 1524mm TO CENTER OF THE ENCL
1676mm TO CENTER OF THE ENCL
2286mm TO CENTER OF BELL
3.
4.
6.THE SOIL RESISTANCE TO GROUND FOR THE ELECTRICAL AND COMMMUNICATION
SYSTEMS SHALL BE 25 OHMS OR LESS. THE SOIL RESISTANCE TEST SHALL BE
7.
COORDINATED WITH THE CENTRAL FIRE DEPARTMENT SO THAT
THE EQUIPMENT SHOULD BE COMPATIBLE WITH THE MAIN EXISTING
ON CEILINGDETECTOR
1372mm TO CENTER OF STATIONMANUAL PULL STATION
5.
CONDUCTED BY THE CONTRACTOR TO OBTAIN THE REQUIRED SOIL RESISTANCE.
INDICATEDS 2 #12AWG IN 16C
INDICATEDS 3 #12AWG IN 16C
INDICATEDS 4 #12AWG IN 16C
A GREATER NUMBER OF WIRES ARE INDICATED AS FOLLOWS;
1219mm TO CENTER OF THE ENCLWALL SWTICH
CONDUIT UNLESS OTHERWISE INDICATED.
ALL EQUIPMENT CONTROL WIRING SHALL BE #14 AWG. "TW" IN 16C
AND LOCATION OF THE F/A ANTENNA WITH THE CENTRAL FIRE DEPARTMENT
THE CONTRACTOR SHALL SUBMIT THE SHOP DRAWING FOR THE MOUNTING
TO TRANSMIT THE ALARM RADIO SIGNAL WAVE WITHOUT ANY OBSTRUCTION.
DETAIL OF THE F/A ANTENNA, AND COORDINATE THE MOUNTING HEIGHT
F/A EQUIPMENT IN THE CENTRAL FIRE DEPARTMENT.
THE EQUIPMENT SHOULD BE COMPATIBLE WITH THE MAIN EXISTING
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
SCOPE OF WORKS
LEGEND, GENERAL NOTES AND
E-1
1.
SCOPE OF WORK
F/A & MNS EQUIPMENT IN THE CENTRAL FIRE DEPARTMENT.
THE MANUFACTURER AND MODEL OF NEW F/A& MNS EQUIPMENT SHALL BE
F/A &MNS CONTROL
COMBO. SPEAKER & STROBE
3.
2.
6.
12.
13.
14.
5.
4.
A. REPAIR/MAINTENANCE ( K )
10.
11.
8.
9.
REPAIR BLDG NO. S-753
CAMP CASEYTAK, YS
58484
15.
SINGLE POLE TOGGLE SWITCH, 15A-125V
L E G E N D
FLEXIBLE CONDUIT W/CONNECTORS
LIGHTING
WIRING
POWER
INTERIOR
S
SYMBOL DESCRIPTION
DESCRIPTION
DESCRIPTION
T
J
THERMOSTAT (UNDER MECH. ITEM)
JUNCTION BOX
SYMBOL
SYMBOL
F FAN MOTOR (UNDER MECH. ITEM)
SAFETY SWITCH
C CONTROL CIRCUIT
3-WAY SWITCH, 15A-125V
AND GOVERNMENT INSTALLED
GOVERNMENT FURNISHED
GFGI
WEATHERPROOFWP
LA LIGHTNING ARRESTER
EXPLOSIONPROOFEP
DISTRIBUTIONDIST
GROUND FAULT PROTECTIONGFP
A AMPERE
AC ALTERNATING CURRENT
AF/AT AMPERE FRAME/AMPERE TRIP
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BLDG BUILDING
BRKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CONN CONNECTION
CT CURRENT TRANSFORMER
DET(S) DETAIL(S)
DIAG DIAGRAM
DISC DISCONNECT
DWG(S) DRAWING(S)
EA EACH
EM EMERGENCY
ENCL ENCLOSURE
EXST EXISTING
F/A FIRE ALARM
FL FLOOR
FLUOR FLUORESCENT
FXTR FIXTURE
GEN GENERATOR
GND GROUND
HP HORSE POWER
HZ HERTZ
INCAND INCANDESCENT
INSTL INSTALLATION
J-BOX JUNCTION BOX
K KILO
KV KILO VOLT
KVA KILO VOLT AMPERE
LTG LIGHTING
MAG MAGNETIC
MAX MAXIMUM
MIN MINIMUM OR MINUTE
MTG MOUNTING
NO NUMBER
O/H OVER HEAD
PH PHASE
PNLBD PANELBOARD
PRIM PRIMARY
PWR POWER
Q'TY QUANTITY
RCPT RECEPTACLE
REQ'D REQUIRED
SCHED SCHEDULE
SEC SECONDARY
SPEC SPECIFICATION
STD STANDARD
SW SWITCH
TEL TELEPHONE
TYP TYPICAL
U/G UNDERGROUND
V VOLT
VA VOLT AMPERE
W WATT
W/ WITH
XFMR TRANSFORMER
& AND
CABNET TYPE, RATED WATT ON LTG SCHEDULE
LED LIGHTING FIXTURE, WALL MOUNTED OR UNDER
ON LTG SCHEDULE, WET LOCATION
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
FAULT PROTECTED TYPE
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDED
PANELBOARD
3S
HOMERUN CIRCUIT TO PANELBOARD
TYPE OF MTG ON LTG SCHEDULE
EXTERIOR LED LIGHTING FIXTURE, RATED WATT &
TYPE
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING
ABBREVIATION
THE COTNRACTOR SHALL SUBMIT A SHOP DRAWING OF HVAC SYSTEM
IN ACCORDANCE WITH SEQUENCE OF OPERATION INDICATED ON THE
MECHANICAL DRAWINGS.
ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG
WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.
THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR
ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.
CONSOLE AND ASSOCIATED WIRING AND CONDUIT.
SPEAKER (WATTAGE AS REQ'D) DEVICE, LOCAL OPERATING
VISUAL SIGNAL STROBES (15 OR 75 CANDELA), MICROPHONE,
DETECTOR & RELAY MODULE, BUILDING TRANSMITTER, ANTENNA,
NOTIFICATION SYSTEM PANEL, MANUAL PULL STATION, SMOKE
NEW ADDRESSABLE FIRE ALARM CONTROL AND MASS
REPLACE DETERIORATED FIRE ALARM CONTROL SYSTEM WITH
NEW.
W/COVER PLATES AND ASSOCIATED WIRING & CONDUIT WITH
REPLACE EXISTING CATV CABINETS & PULLBOXES, OUTLETS
CEILING.
ALL WIRING SHALL BE CONCEALED ABOVE CEILING WHEN THE ROOM HAS
CATV BEFORE CONSTRUCTION.
CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,
AND GOVERNMENT ACCEPTANCE.
PANELBOARD DOOR, REQUIRED BEFORE FINAL BUILDING INSPECTION
CONTRACTOR SHALL MAKE CIRCUIT CHARTS AND ATTACH THEM TO
FIRE CODE AND SPECIFICATIONS.
OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,
ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS
OR RENOVATION.
CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION
THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING
FIXTURE A MINIMUM DISTANCE OF 458mm.
FIRE ALARM DETECTORS SHALL BE LOCATED TO CLEAR ANY LIGHTING
7.
FMCP
FTR
ANTENNA
AUXILIARY
DESCRIPTION
F
TELEPHONE OUTLET
SYMBOL
CTC CATV SYSTEM CABINET
CATV OUTLET
ADDRESSABLE FA MANUAL PULL STATION
WP
F M
TTB
FIRE ALARM/MASS NOTIFICATION CONTROL PANEL
TELEPHONE TERMINAL BOARD
TV
MOUNTED TYPE
F/A & MASS NOTIFICATION SPEAKER "WP" WALL
STROBES
WALL MOUNTED SPEAKER /COMBO. (FA+MNS)VISUAL
CONNECTION
BUILDING TRANSMITTER UNIT FOR FIRE ALARM
SYSTEM
F FIRE ALARM SYSTEM CIRCUIT
WIRING FOR TELEPHONE LINET
BRANCH CIRCUIT, EXPOSED ON CEILING OR WALL
WIRING CONCEALED IN THE CEILING AND WALL
F/M
8.
WITH NEW.
SYSTEM INCLUDING COMMUNICATION MANHOLE AND ACCESSORIES
REPLACE EXISTING EXTERIOR UNDERGROUND TELECOMMUNICATION
L
PHOTOCELL
LIGHTING SWITCH, SEL SW (H-O-A),
WP
FAULT PROTECTED TYPE, WEATHER PROOF
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDED
TYPE
SINGLE RECEPTACLE, 2P-3W-20A-125V, GROUNDING
TYPE WITH PLUG
SINGLE RECEPTACLE, 3P-4W-30A-125/250V, GROUNDING
TYPE WITH PLUG
SINGLE RECEPTACLE, 3P-4W-50A-125/250V, GROUNDING
L
L
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
W/EMERGENCY BATTERY UNIT
L
W/EMERGENCY UNIT
WIRING TO UPSTAIR OR DOWNSTAIR
TYPE
QUADPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
L
L
SYSTEM WITH ASSOCIATED ACCESSORIES.
REMOVE AND REINSTALL EXISTING CCTV CAMERAS & MONITORING
9.
REMOVE EXISTING PUBLIC ADDRESS SYSTEM INCLUDING SPEAKERS.
UNITS.
CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER
CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10YEARS WARRANTY
ASSOCIATED WIRING & CONDUIT WITH NEW.
RECEPTACLES AND COVER PLATES, CIRCUIT BREAKER, AND
REPLACE EXISTING PANELBOARDS, PANELBOARD FRONT COVERS,
CONDUITS WITH NEW.
SWITCHES, PHOTOCELL, LIGHTING CONTACTOR, WIRES AND
LIGHTS, EXTERIOR LIGHTS, TOGGLE SWITCHES, 3-WAY
REPLACE DETERIORATED EXISTING LIGHTING FIXTURES, EXIT
AND ASSOCIATED WIRING AND CONDUIT WITH NEW.
EQUIPMENT RACK AND ACCESSORIES, OUTLETS W/ COVER PLATES
REPLACE DETERIORATED EXISTING TELEPHONE TERMINAL BOARD,
16.
THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE
WIDTH OF DUCT EXCAVATION.
AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.
TO THEIR ORIGINAL CONDITION AND OPERATION DURING
ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES
THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING
SYSTEM WITH NEW.
BOXES, CONTROL SYSTEM, WIRES AND CONDUITS FOR HVAC
MOTOR STARTERS, MANUAL MOTOR STARTERS, JUNCTION
CONTROL PANEL, COMBINATION MOTOR STARTERS, MAGNETIC
REPLACE DETERIORATED EXISTING SAFETY SWITCHES, MASTER
17.
NO. 756.
CCTV SYSTEM, CAMERAS, WIRING INCLUDING SIGNAL FROM BUILDING
THE CONTRACTOR SHALL BE RESPONSIBLE TO REMOVE/REINSTALL EXISTING
GUARD
SHED
A
B
MH1-16
MH9-7-2
MH1-18
MH1-18-A
MH1-18-B
B
B
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
SEE NOTE 2 BELOW
IN EXIST TELE MANHOLE
PROVIDE NEW SPLICE KIT
(1-12 CORE, SINGLE MODE FIBER OPTIC CABLE)
SCALE :
1/500
EXIST/NEW EXTERIOR TELECOMM DISTRIBUTION PLAN
C
C
C
C
C
C
MH1-18-1
C
EXIST COMM MANHOLE
(TYPICAL)
FOR ABBREVIATION, LEGEND, AND GENERAL NOTES1.
NOTES
2.
SHALL BE INSTALLED ON THE EXISTING MANHOLE
AND TYPE OF SPLICE KITS SHALL BE COORDINATED
THE CONTRACTOR SHALL VERIFY EXISTING3.
UNDERGROUND TELECOMM LINE'S ACTUAL
CONDITION PRIOR TO WORK.
SEE SHEET NO. E-1.
WITH BASE SIGNAL COMPANY.
NEW SPLICE KITS FOR 1-50PAIR, #24AWG TEL CABLE &
1-12 CORE, SINGLE MODE FIBER OPTIC CABLE
(SEE OMA STANDARD DRAWING)/
NEW COMM MANHOLE
COMM RM
P
SINGLE MODE FIBER OPTIC CABLE
REPLACE W/ NEW U/G 1-12 CORE
KITS (1-50PAIR, #24 AWG),
REPLACE W/NEW SPLICE KIT
NEW U/G COMM LINE 2WAY OF 103C
1WAY: 1-50PAIR, #24AWG TEL CABLE IN 4-4" FABRIC INNER DUCT
1WAY: 1-12 CORE, SINGLE MODE FIBER OPTIC CABLE IN 4-4" FABRIC INNER DUCT
1-12 CORE, SINGLE MODE FIBER OPTIC CABLE
REPLACE W/ NEW U/G 1-50 PAIR, #24AWG TEL CABLE &
W/ NEW 4-4" FABRIC INNER DUCTS
"MH9-7-2" TO "MH1-18)
IN EXISTING CONDUIT (TYPICAL FROM
TO NEW COMM MANHOLE)
IN EXISTING CONDUIT (TYPICAL FROM "MH1-18"
NEW TTB
PULL BOX
"WP"
DISTRIBUTION PLAN
EXIST/NEW EXTERIOR TELECOMM
REPAIR BLDG NO. S-753
CAMP CASEYTAK, YS
58484
E-2
SCALE: 1/100
EWC
E W
C
FEC
UP
UP
S/S
STORAGE
VEST
ROOM
ADMIN OFFICE
R.O
106B
T.O
106A
WAIT AREA
STORAGE
106C
STAIR-2
119B
CO
XO
COMM
COMMO SHOP
113A 113B
JAN
MULTI-PURPOSE RM
STORAGE
115 MECH ROOM
C.Q
VEST
STAIR-1
119ALAUNDRY
JAN
CORRIDOR
105A
COMMUNITY
FEC
D
W
W
D
W/D
W/D
DAY RM REF
NBC ROOM
ARMS ROOM
COMM RM
LATRINE
MALE
LATRINE
FEMALE
E W
C
FEC FEC
UP DN
UP DN
REF
STAIR-1
218A
219 CORRIDOR
BED ROOM
201A
BED ROOM
201B
BED ROOM
202A
BED ROOM
202B
BED ROOM
203A
BED ROOM
203B
BED ROOM
204A
BED ROOM
204B
BED ROOM
205A
BED ROOM
205B
BED ROOM
206A
BED ROOM
206B
BED ROOM
207A
BED ROOM
207B
BED ROOM
208A
BED ROOM
208B
STAIR-2
218B
LAUNDRY
BED ROOM
214A
BED ROOM
214B
BED ROOM
213A
BED ROOM
213B
BED ROOM
212A
BED ROOM
212B
BED ROOM
211A
BED ROOM
211B
BED ROOM
210A
BED ROOM
210B
BED ROOM
209A
BED ROOM
209B
JAN
S/S
D
W
W
318A
301A301B302A302B303A303B304A304B305A305B306A306B307A307B308A308B
314A314B313A313B312A312B311A311B310A310B309A309B
318B
401A401B402A402B403A403B404A404B405A405B406A406B407A407B408A408B
414A414B413A413B412A412B411A411B410A410B409A409B
D
W/D
W/D
418B
418A
319419
DAY RM
SCALE: 1/100
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-3
J
J
J
J
J
JJ
J
JJJJ
JJJ
JJ
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
JJJ
J J J
JJ
JJ
J
J
J
J
J
JJ
J
J
J
J
J
JJ
J
JJ
J
J
J
J
JJJJJ
J
J
J
J
J
J
J
J
S
S
S
S
3 S
S S
S
3S
3S3S
S
S
S
S
S
J
JJ
J
J
J
J
J
J
J
J
J J
J E
J
S
S
S S S
S
S
S WP
L
L
LL
LL
JJ
J
L L
L
L
L
L
L
L
LLLLL
L
LLL
L L
L L L L L
LL
L L L
L L L
L
L
L L
L
L
L L
LL L L LL
L
LLLLLLLLLLLLLLL
LL
L
L
L
L
LL
L
LLL
L
LL
LL
L
L L
LL
L L
L
L
L
LLLLLLLLLLLLLLLL
L
L
L
L
L
S SS
S
S
S
S
S3
S S S S
S
S
S
S
S
S
3S 3S
S
S
L
L
J
LIGHTING CIRCUIT
PARKING AREA
RECONNECT EXIST
ORIENTED FACING NORTH
600W, 120V, 1PH
PHOTOELECTRIC
FOR ARMS ROOM
REPLACE W/ NEW WALL MOUNTED LED LIGHT
1ST FLOOR LIGHTING PLAN
2ND, 3RD AND 4TH FLOOR LIGHTING PLAN
PLAN
1ST, 2ND, 3RD AND 4TH FLOOR LIGHTING
MODULE PLAN ON E-8
SEE TYPICAL BEDROOM ELECTRICAL
L
L
L
REPAIR BLDG NO. S-753
CAMP CASEYTAK, YS
58484
OFFICE
OFFICE
ADMIN OFFICE ADMIN OFFICE
L L
L L L
L
L
L
L
LL
L L
L L
S S
CONNECT TO EXISTING LIGHT CIRCUIT
2ND FL ONLY
EXTERIOR LIGHT, TYPE "NS-12"
CONTACTOR
CONNECT TO LIGHTING
CONTACTOR AND WIRING DIAGRAM FOR APPROVAL
CONTRACTOR SHALL PROVIDE SHOP DRAWING FOR LIGHTING
1EA-(H-O-A) SELECTOR SWITCH, NEMA 4X ENCL.
CONTACTS(NO), MECHANICALLY HELD LIGHTING CONTACTOR,
: LIGHTING CONTACTOR, 120V, 60HZ COIL W/2EA-20A,
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-4
DIODE(LED) EXIT LIGHT FIXTURE 1PH, 120V, 4.99W
WALL SURFACE MOUNTED LIGHT EMITTING
NS-7
NS-4a & 4b NS-6a & 6b
WALL MOUNTED FLUORESCENT LIGHT FIXTURE,
1PH, 120V, 1/32W TRIPLE TWIN-TUBE LAMP,
NS-8
100 WALL
NS-9
245mm
254mm
NS-5a & 5b
NS-10
FIXTURE, 1PH, 120V, 45W, WITH CONVERTER & ACCESSORIES
CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)
FIXTURE, 1PH, 120V, 50W, WITH CONVERTER & ACCESSORIES,
CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)
FIXTURE, 1PH, 120V, 18W, WITH CONVERTER & ACCESSORIES,
CEILING SURFACE MOUNTED LIGHT EMITTING DIODE (LED) FIXTURE, 1PH, 120V, 18W, WITH CONVERTER & ACCESSORIES
WALL SURFACE MOUNTED LIGHT EMITTING DIODE (LED)
WET LOCATION SHOWER LIGHT TRIM, UL LISTED POWER UNIT
AS REQUIRED UL LISTED POWER UNIT
W/BUILT-IN PHOTOCELL, WET LOCATION TYPE, UL LISTED
MANUFACTURED BY "SKC LIGHTING" OR APPROVED EQUAL.
MANUFACTURED BY "SKC LIGHTING" OR APPROVED EQUAL.
MANUFACTURED BY "SKC LIGHTING" OR APPROVED EQUAL.
MANUFACTURED BY "SKC LIGHTING" OR APPROVED EQUAL.
MANUFACTURED BY "SKC LIGHTING, CO., LTD"
OR APPROVED EQUAL.
CEILING SURFACE/PENDANT MOUNTED LIGHT EMITTING DIODE (LED)
FIXTURE, 1PH, 120V, 45W, WITH CONVERTER, ACCESSORIES, UL
LISTED(NS-6a)& EM UNIT(NS-6b), AS REQUIRED AND UL LISTED (NS-5a) & WITH EM UNIT (NS-5b) AS REQUIRED
AS REQUIRED, UL LISTED (NS-4a) & WITH EM UNIT (NS-4b)
MANUFACTURED BY "SKC LIGHTING" OR APPROVED EQUAL.
FIXTURE, 1PH, 120V, 45W, WITH CONVERTER & ACCESSORIES
CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)
AS REQUIRED, UL LISTED (NS-11a) & WITH EM UNIT (NS-11b)
NS-11a & NS-11b NS-12
WALL MOUNTED LIGHT EMITTING DIODE(LED) LIGHT
FIXTURE, 1PH, 120V, 60 WATT, CONVERTER AND ACCESSORIES
UNDERCABINET LED LIGHT FIXTURE
1PH, 120V, 17W, CONVERTER AND ACCESSORIES,
"SKC LIGHTING" OR APPROVED EQUAL.
UL LISTED POWER UNIT, MANUFACTURED BY
WET LOCATIONS TYPE(IP66), UL LISTED POWER,
MANUFACTURED BY "SKC LIGHTING" OR APPROVED EQUAL.
NS-3a & NS-3b
(MAX. INPUT), BATTERY BACK-UP WITH BATTERY CHARGER,
SINGLE FACE(NS-3a) & DOUBLE FACE(NS-3b)
LIGHTING FIXTURE DETAILS
REPAIR BLDG NO. S-753
CAMP CASEYTAK, YS
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-5
MOUNTING METHOD
LIGHTING FIXTURE SCHEDULE
LAMP
TYPENO
ROOM
NAME WATTS
COE STD DET 40-06-04
TYPE
NO
SHT
Q'TY REMARKS MOUNTING METHOD
LIGHTING FIXTURE SCHEDULE
LAMP
TYPENO
ROOM
NAME WATTS
COE STD DET 40-06-04
TYPE
NO
SHT
Q'TY REMARKS
CEILING RECESSED5-
CEILING RECESSED1-
- EXIT LIGHT WALL MOUNTED5NS-3a -
CEILING SURFACE1NS-3b -
DOUBLE FACE
1/4.99
SINGLE FACE,
ABOVE DOOR TOP
WITH ARROW
- EXTERIOR WALL MOUNTED3-1/35
CEILING SURFACE6NS-3a -1/4.99
SINGLE FACE
WITH ARROW
1-
5-
STORAGE103 CEILING RECESSED
COMMUNITY ROOM104 CEILING RECESSED5-
CEILING RECESSED1- W/EM UNIT
ADMIN OFFICE105 CEILING RECESSED7-
CEILING RECESSED1- W/EM UNIT
COMM RM105A CEILING SURFACE1-
WAIT AREA106 CEILING RECESSED1- W/EM UNIT
T.O106A CEILING RECESSED1-
CEILING RECESSED1- W/EM UNIT
R.O106B CEILING RECESSED1-
CEILING RECESSED1- W/EM UNIT
STORAGE106C CEILING SURFACE1-
C.O107 CEILING RECESSED2-
CEILING RECESSED1- W/EM UNIT
X.O108 CEILING RECESSED2-
CEILING RECESSED1- W/EM UNIT
COMM109 CEILING RECESSED2-
CEILING RECESSED1- W/EM UNIT
SUPPLY ROOM110 CEILING RECESSED3-
CEILING RECESSED1-
NBC ROOM111 CEILING RECESSED5-
CEILING RECESSED1-
W/EM UNIT
W/EM UNIT
COMMO SHOP112 CEILING RECESSED2-
MALE113A CEILING RECESSED1-
WALL MOUNTED1-
FEMALE113B CEILING RECESSED1-
WALL MOUNTED1-
JANITOR113 CEILING SURFACE1-
MUIL-PURPOSE114A CEILING RECESSED8-
CEILING RECESSED2-
ROOM
W/EM UNIT
CEILING RECESSED1-
CEILING RECESSED1- W/EM UNIT
STORAGE115
CEILING RECESSED1-C.O116
CEILING RECESSED1-VEST117
CEILING RECESSED1-
W/EM UNIT
LAUNDRY118
1-
1- W/EM UNIT
STAIR-1119A
11-
STAIR-2119B
6- W/EM UNIT
CORRIDOR120
1-
1-
W/EM UNIT
MECH ROOM123 CEILING SURFACE4-
CEILING SURFACE1- W/EM UNIT
BEDROOM201A,B~
DAY RM215 CEILING RECESSED3-
214A,B
CEILING RECESSED1- W/EM UNIT
UNDER CABINET MTD1-
JANITOR216 CEILING SURFACE1-
LAUNDRY217 CEILING RECESSED1-
CEILING RECESSED1- W/EM UNIT
STAIR-1218A CEILING SURFACE2-
STAIR-2218B CEILING SURFACE2-
W/EM UNIT
W/EM UNIT
CORRIDOR219 CEILING RECESSED12-
CEILING RECESSED5- W/EM UNIT
CEILING RECESSED2-
CEILING RECESSED1-DRESS ROOM
BATH ROOM CEILING RECESSED2-
WALL MOUNTED1-
BEDROOM301A,B~
315 CEILING RECESSED3-
314A,B
CEILING RECESSED1- W/EM UNIT
JANITOR316 CEILING SURFACE1-
LAUNDRY317 CEILING RECESSED1-
CEILING RECESSED1- W/EM UNIT
STAIR-1318A CEILING SURFACE2-
STAIR-2318B CEILING SURFACE2-
W/EM UNIT
W/EM UNIT
CORRIDOR319 CEILING RECESSED12-
CEILING RECESSED5- W/EM UNIT
CEILING RECESSED2-
CEILING RECESSED1-DRESS ROOM
BATH ROOM CEILING RECESSED2-
WALL MOUNTED1-
BEDROOM401A,B~
MULTI-PURPOSE415 CEILING RECESSED3-
414A,B
CEILING RECESSED1- W/EM UNIT
JANITOR416 CEILING SURFACE1-
LAUNDRY417 CEILING RECESSED1-
CEILING RECESSED1- W/EM UNIT
STAIR-1418A CEILING SURFACE2-
STAIR-2418B CEILING SURFACE2-
W/EM UNIT
W/EM UNIT
CORRIDOR419 CEILING RECESSED12-
CEILING RECESSED5- W/EM UNIT
CEILING RECESSED2-
CEILING RECESSED1-DRESS ROOM
BATH ROOM CEILING RECESSED2-
WALL MOUNTED1-
ROOM
VEST121
JANITOR122 CEILING SURFACE
CEILING RECESSED1-
W/EM UNIT
WALL MOUNTED7NS-12 -
W/EM UNIT
W/EM UNIT
LED LED50
NS-5a
NS-5b
W/EM UNIT
W/EM UNIT
NS-4b 45 1-
NS-4a 45 - 1
CEILING RECESSED
NS-5a
NS-5b
NS-5a
NS-5b 50
NS-6a 45
NS-5b 50
NS-5a
NS-5b 50
NS-5a
NS-5b 50
NS-6a 45
NS-5a
NS-5b 50
NS-5a
NS-5b 50
NS-5a
NS-5b 50
NS-4a
NS-4b 45
NS-4a
NS-4b 45
NS-4a 45
NS-4b 45 - 1 CEILING RECESSED W/EM UNIT
NS-7 18 -
NS-4a 45
45NS-4b
NS-7 18
NS-4b
NS-7 18
NS-5a
NS-5b 50
NS-4a
NS-4b 45
W/EM UNIT50NS-5b
NS-5b 50
NS-4a
NS-4b 45
- 1 CEILING RECESSED
NS-6b 45
NS-6b 45
W/EM UNIT
NS-11a
NS-11b
CEILING SURFACE
CEILING SURFACE
CEILING RECESSED
CEILING RECESSED
CEILING RECESSED
NS-4a
NS-4b 45
NS-4a
NS-4b
NS-8 17
NS-7 18
NS-5a
NS-5b 50
17NS-10
NS-7 18
NS-4a 45
45NS-4b
W/EM UNIT
NS-6b
NS-6b 45
NS-11a
NS-11b 25
NS-5b 50
NS-7 18
NS-4a 45
45NS-4b
NS-8 17
18NS-7
W/EM UNIT
DAY RM NS-5a
NS-5b 50
17NS-10
NS-7 18
NS-4a 45
45NS-4b
NS-6b
NS-6b 45
NS-11a
NS-11b 25
NS-4a 45
45NS-4b
NS-8 17
18NS-7
NS-5a
NS-5b 50
17NS-10
NS-7 18
NS-4a 45
45NS-4b
NS-6b
NS-6b 45
NS-11a
NS-11b 25
NS-9
1/4.99
- 1
UNDER CABINET MTD
UNDER CABINET MTD
ELECTRICAL
LIGHTING FIXTURE SCHEDULE
LED
FLUOR
REPAIR BLDG NO. S-753
CAMP CASEYTAK, YS
58484
101 ADMIN OFFICE
ADMIN OFFICE NS-5a
NS-5b CEILING RECESSED
CEILING RECESSED
W/EM UNIT
UP
UP
S/S
STORAGE
VEST
ROOM
ADMIN OFFICE
R.O
106B
T.O
106A
WAIT AREA
STORAGE
106C
STAIR-2
119B
CO
XO
COMM
109 110
COMMO SHOP
113A
113B
JAN
MULTI-PURPOSE RM
114 STORAGE
MECH ROOM
C.Q
VEST
STAIR-1
119A
LAUNDRY
JAN
CORRIDOR
105A
COMMUNITY
D
W
W
D
W/D
W/D
DAY RM
REF
NBC ROOM
ARMS ROOM
COMM RM
LATRINE
MALE
LATRINE
FEMALE
UP DN
REF
STAIR-1
218A
219 CORRIDOR
BED ROOM
201A
BED ROOM
201B
BED ROOM
202A
BED ROOM
202B
BED ROOM
203A
BED ROOM
203B
BED ROOM
204A
BED ROOM
204B
BED ROOM
205A
BED ROOM
205B
BED ROOM
206A
BED ROOM
206B
BED ROOM
207A
BED ROOM
207B
BED ROOM
208A
BED ROOM
208B
STAIR-2
218B
LAUNDRY
BED ROOM
214A
BED ROOM
214B
BED ROOM
213A
BED ROOM
213B
BED ROOM
212A
BED ROOM
212B
BED ROOM
211A
BED ROOM
211B
BED ROOM
210A
BED ROOM
210B
BED ROOM
209A
BED ROOM
209B
JAN
S/S
W
318A
301A301B302A302B303A303B304A304B305A305B306A306B307A307B308A308B
314A314B313A313B312A312B311A311B310A310B309A309B
318B
401A401B402A402B403A403B404A404B405A405B406A406B407A407B408A408B
414A414B413A413B412A412B411A411B410A410B409A409B
418B
418A
319419
DAY RM
SCALE: 1/100
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-6
J
J
J
+1800
EWC
EWC
F
FCU
F F
FCU
F
FCU
F
FCU
F
FCU
F
FCU
F
FCU
F
FCU
F C
U
TV
TV
S
S
J
S
HJH
F
FCU
F
FCU
J
J
J
EWC
ER
R
RH
F F
FCU
F
TV
TV
S
S
J HJH
EWC
TV
TV
JJJJJ J J
S S
2ND, 3RD & 4TH FLOOR POWER PLAN
1ST FLOOR POWER PLAN
T
T
T
T T
TT
T T
RH
RH
ER
M
R
"P1A"
"P1B"
"P2A" "P3A" "P4A"
"P2B" "P3B" "P4B"
T TC C
P4B-38
T
M D
P
J
J
"L1"
"L2" "L3" "L4"
A/C
+1800
J
J F
L1-1
L1-2
L1-3
L1-4
L1-5
L1-6
L1-7
L2,3,4-7
L2,3,4-6L2,3,4-3
L2,3,4-2
L2,3,4-4
L2,3,4-5
L2,3,4-1
SPARE OF "P1B"
SPARE OF "P2B, P3B,P4B"
SPARE OF "P2B, P3B,P4B"
"P"
TO P4B-40
FROM PANELBOARD "P"
TO LOADCENTER "L1","L2"&"L3"
TO P-5
1/10HP (MECH ITEM)
EXHAUST FAN, 1PH,115V,
ADDITIONAL LEGEND (THIS SHEET ONLY)
GROUNDING TYPE AND COVER FACE PLATE FOR CATV 208VAC SERVICE
2P-3W-20A-250V, GROUNDING TYPE
(LOCATED IN CATV DIST. CABINET)
D
REPLACE EXIST RECEPTACLE20
W/NEW SINGLE RECPTACLE, 2P-3W-20A-125V,
GROUNDING TYPE, PLUG AND COVER FACE
REPLACE EXIST SINGLE RECEPTACLE
W/NEW SINGLE RECPTACLE,
PLATE FOR DRYER, 1PH-120/208V-5KW
FOR ELECTRIC WATER COOLER, 1PH-115V-1/5HP
GROUNDING TYPE AND COVER FACE PLATE
REPLACE EXIST RECEPTACLE
EWC
W/NEW SINGLE RECPTACLE, 2P-3W-20A-125V,
(TYPICAL)
(TYPICAL)
REPLACE NEW SINGLE RECEPTACLE,
FOR CATV 120VAC SERVICE
2P-3W-20A-125V, SURGE SUPPRESSION TYPE
(LOCATED IN CATV DIST. CABINET)
REPLACE NEW DUPLEX RECEPTACLE,
TV
3P-4W-30A-125/250V, TV
S MANUAL MOTOR STARTER
1PH-115V-1HP (MAX.)
(2P-100AF-20AT, 10000AIC)
W/O.L RELAYS, 3-POSITION SEL.
SWITCH (A-O-H) & PILOT LAMPS, NEMA 1 ENCL.
D D
D D
120V, 1KW(MECH ITEM)(TYPICAL)
ELECTRICAL HEATER, 1PH,
2#12 & 1#12(G) IN 16C
PROVIDE NEW WIRING
(TYPICAL)
SAFETY SWITCH, 2PST-240V-30A
A
B
1PH, 120V, 1/2HP
AIR HANDLING UNIT,
LOADCENTER "L2","L3","L4"
TO PANELBOARD "P" FROM
PLATE WITH NEW (TYPICAL)
REPLACE EXIST RECEPTACLE AND COVER
(TYPICAL)
THERMOSTAT (MECH ITEM)
M
MAG.MOTOR STARTER, 2P-120V,
NEMA SIZE "00",
ER
GROUNDING TYPE, PLUG AND COVER FACE
REPLACE EXIST SINGLE RECEPTACLE
W/NEW SINGLE RECPTACLE,
(TYPICAL)
3P-4W-50A-125/250V, PLATE FOR ELECTRIC RANGE
RECONNECT TO EXIST
WIRING(TYPICAL)
FOR WASHER, REF., FAN COIL UNIT, MICROWAVE
M
1PH,115V,1.7FLA (MECH ITEM)
CONDENSATE DRAIN LIFT PUMP,
B
SAFETY SWITCH, 2PST-240V-30A
A
NON-FUSIBLE. NEMA 3R ENCL
NON-FUSIBLE. NEMA 1 ENCL
TO P-6
RECONNECT TO EXIST
WIRING(TYPICAL)
MDP-10
FLOOR ONLY (MECH ITEM)(TYPICAL)
ROOF FAN, 1PH, 120V, 1/15HP @ 4TH
115V, 1.5KW (MECH ITEM)
SPLIT AIR CONDITIONING UNIT, 1PH,
J
1PH,115V, 1/12HP (MECH ITEM)
EXHAUST FAN FOR TOILET,
EF5
EF4 EF4 EF4 EF4 EF4 EF4 EF4
EF3
EF3
EF1
EF1
"MDP" FOR PANELBOARD "P"
WITH NEW CIRCUIT BREAKER (3P-225AF-225AT) IN
EXIST MAIN DIST. PANELBOARD "MDP"/ REPLACE
"P2A", "P2B", "P3A", "P3B","P4A" & "P4B")
WITH NEW (TYPICAL FOR PANELBOARD "P1A", "P1B",
REPLACE EXIST FRONT COVER OF PANELBOARD
1ST, 2ND, 3RD & 4TH FLOOR POWER PLAN
MODULE PLAN ON E-8
SEE TYPICAL BEDROOM ELECTRICAL
TO SPARE OF "P1B"
70mm dia C.
4-3/0 & 1#4(G) IN
IN 36mm C.
3#4& 1#8(G)
IN 28mm C.
3#8& 1#10(G)
IN 22mm C.
3#10& 1#10(G)
W,R,F,M,RH
OVEN, RANGE HOOD
W W
T
TVSST
ALARM SWITCH
FLOOR MOUNTED LATCHING
NEW JUNCTION BOX FOR
( 15 cm ABOVE DOOR )
BALANCED MAGNETIC SWITCH
NEW JUNCTION BOX FOR
J
J
J
J
FOR CONTROL UNIT
NEW JUNCTION BOX
SIGNAL PROCESSOR
ULTRASONIC MOTION SENSOR
NEW JUNCTION BOX FOR
J
SENSOR TRANSCEIVER
ULTRASONIC MOTION
NEW JUNCTION BOX FOR
W/PULLING WIRE (TYPICAL)
EMPTY COPNDUIT 22mm C
TO PNLBD "P1B"
IN 16mmC
1-4PAIR CAT6
NOTE
1.
CONDITION.
FOR J-SIID SYSTEM WIRING TO MEET SITE
RELOCATE WIRING AND JUNCTION BOXES
CONTRACTOR IS RESPONSIBLE TO
120V, 1KW(MECH ITEM)(TYPICAL)
ELECTRICAL HEATER, 1PH,
REPAIR BLDG NO. S-753
CAMP CASEYTAK, YS
58484
OA(��)
EA(��)
RA(��)
SA(��)
F
FCU
F
FCU
F
FCU
F
FCU
F
FCU FCU
F
FCU
F
F
FCU
T
T
T
T
TTT T
C
C
C
C
C
C
C
C
J
360W(MECH ITEM) (TYPICAL OF 8EA)
ENERGY RECOVERY UNIT, 1PH, 208V, 1PH,
J
J
TO SPARE OF "P1B" OR "L1"
SPARE OF "P2B, P3B, P4B OR "L2","L3","L4"SPARE OF "P2B, P3B,P4B"OR "L2","L3","L4"
SPARE OF "P1B OR "L1"
J
OFFICE
OFFICE
F F
T T
F F
C C
C
C
J
L2,4-8
J
FLOOR)
(TYP OF 4EA@2ND&4TH
HEATER,1PH, 208V, 2KW
ELEC. CABINET UNIT
L1,3-8
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-7
1 20 2#12&1#12(G)
13115LOAD CENTER, "L1"
LOAD CENTER, "L2"
LOAD CENTER, "L3"
LOAD CENTER, "L4"
5 6
3PHASE ,4WIRE, 120/208V,
MTD TYPE, NEMA 1 ENCL.
100 100002
18630
REMARK
GNA CB
AICAF
SIZE
ATC PBA
PHASE LOAD
CIRCUIT BREAKER
CONNECTION
DIAGRAM
S/N
GND
CKT
NO.
LOAD DESCRIPTION
TOTAL
LOAD
186302520062460TOTAL LOAD
13 15
1000 1000
SPARE 1000 1000
3 30
SPACE
SPACE
SPACE
PANELBOARD "P" LOAD SCHEDULE 60HZ, SN & GND, FLUSH
6300 6815
13115 6300 6815
13115 6300 6815
13115 6300 6815
UNIT
SPLIT AIR CONDITIONING
PUMP
CONDENSATE DRAIN LIFT
EQUIPMENT RACK(LAN)
TELEPHONE TERMINAL BOARD
FMCP
FMBP#1
FMBP#2
FMBP#3
TVSS
1000 1000
2#12&1#12(G)
SPARE
SPACE
SPACE
SPACESPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
TOTAL DEMAND LOAD ; 50522 (VA)
4-3/0 & 1#4(G) IN
70mm dia C.
3#4&1#8(G)
"L3 &"L4" LOAD SCHEDULE
PANELBOARD "P" & LOAD CENTER "L1","L2",
SPACE
4#10&1#10(G)
MAIN 3P-225AF-225A MAIN
W/LOCK
SPACE SPACE
REPAIR BLDG NO. S-753
CAMP CASEYTAK, YS
58484
TOTAL LOAD 13115
LOAD
TOTAL
LOAD DESCRIPTION
NO.
CKT
GND
S/N
DIAGRAM
CONNECTION
CIRCUIT BREAKER
PHASE LOAD
A B P AT
SIZE
AF AIC
BA N G
REMARK
360 360
1 10000100 2#12&1#12(G)20
EXH FAN-5, 83W
MTD TYPE, NEMA 1 ENCL.
60HZ, SN & GND, FLUSH
1PHASE ,3WIRE, 120/240V,
ELEC RANGE, 6470W
1 20
3#8&1#10(G)
SHUNT-TRIP
3#10&1#10(G)
HOOD FAN 2.0A & REF, 1/4HP
LOADCENTER "L1~L4" LOAD SCHEDULE
RCPTS 180VAx2
COMBINATION WASHER/DRYER
COMBINATION WASHER/DRYER
CATV RCPTS 180VA
CATV RCPTS 360VA 360
180 180
360 360
500 500SPARE
SPARE
SPARE
2#12&1#12(G)
6300 6815
3#4& 1#8(G) IN 36mm C.
TOTAL DEMAND LOAD ; 10784 (VA)
MAIN LUG 100A
ELECTRIC UNIT HEATER 1000 2#12&1#12(G)
1000 1000
12 13
SPARE
SPARE
1000 1000
500 500
UH
J
M J
S
M JMJ
M J
J
J
EF
S
J
TJ
M D
P
ADDITIONAL LEGEND (THIS SHEET ONLY)
W/BUILT-IN CONTROLLER
PILOT LAMPS, NEMA 1 ENCL.
W/O.L RELAYS, 3-POSITION SEL. SW (A-O-H) &
MAGNETIC MOTOR STARTER, 2P-120V, NEMA SIZE "00",A
CONTROL TRANSFORMER & PILOT LAMPS,
W/O.L RELAYS, 3-POSITION SEL. SW (A-O-H),
MAGNETIC MOTOR STARTER, 3P-208V, NEMA SIZE "1",
NEMA 1 ENCL.
C
W/BUILT-IN CONTROLLER
(UNDER MECH. ITEM)
3PH-200V-5HP
H.W.CIRC.PUMP
(UNDER MECH. ITEM)
3PH-200V-7 /2HP
CH.W.CIRC.PUMP
(UNDER MECH. ITEM)
1PH-115V-1/20HP
UNIT HEATER
M-19
(UNDER MECH. ITEM)
1PH-115V-1/4HP
D.H.W.CIRC.PUMP
(UNDER MECH. ITEM)
A
D C
CONTROL TRANSFORMER & PILOT LAMPS,
W/O.L RELAYS, 3-POSITION SEL. SW (A-O-H),
MAGNETIC MOTOR STARTER, 3P-208V, NEMA SIZE "2",
NEMA 1 ENCL.
D
B
3#8 & 1#8(G) IN 27C
3#12 & 1#12(G) IN 21C
(TYPICAL)
(TYPICAL)
CONTROL TRANSFORMER & PILOT LAMPS,
W/O.L RELAYS, 3-POSITION SEL. SW (A-O-H),
NEMA 1 ENCL.
B
(TYPICAL)
1P-115V-1HP (MAX.),
MANUAL MOTOR STARTER,S
NEMA 1 ENCL.
3-POSITION SEL. SW (H-O-A), W/PILOT LAMP (GREEN),
MANUAL MOTOR STARTER, 1P-115V-1HP (MAX.),
S
1/50SCALE:
3#10 & 1#10(G) IN 21C
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-8
D.H.W RECIR. PUMP
3PH-200V-1-1/2HP
1PH-115V-380Wx6EA
1PH-115V-80Wx2EA
EXIST H.W. BOILER
EXIST D.H.W. HEATER
MDP-15
MDP-3
MDP-13
MDP-6
MDP-11
MDP-8
MECH. RM PARTIAL POWER PLAN
PLAN & MECH. RM PARTIAL POWER PLAN
TYPICAL BEDROOM ELECTRICAL MODULE
MDP-12
MDP-14
MCP
MCP
PRIOR TO CONSTRUCTION.
DIAGRAM OF MASTER CONTROL PANEL FOR GOVERNMENT APPROVAL
MASTER CONTROL PANEL, CONTRACTOR SHALL SUBMIT SPEC., AND
REPAIR BLDG NO. S-753
CAMP CASEYTAK, YS
58484
N M
D P
EXIST MAIN DIST. PANELBOARD "NMDP"
EXIST PANELBOARD "MDP"
CHILLER
IN 70mm C.
NEW U/G 2SET OF 4-AWG4/0 & 1-4(G)
240VAC W/ NON-FUSIBLE, NEMA 3R ENCL.
NEW SAFETY SWITCH 3PST-600A,
MAG. MOTOR STARTER, 3P-208V, NEMA SIZE "0",
BED ROOM A BED ROOM B
F
SB
L L
3S
S
S S
S
3S
3S
S
SJ
L
L
L L L
L
J
J J a
J b b b b b b a a a a a
SB
FCUFCU
PLATE W/NEW (TYPICAL)
TV
TV
CATV OUTLET W/"0"dB LOSS FACE
PLATE AND F-81 BARREL TYPE
CONNECTOR (M.H: +300mm AFF)
(TYPICAL)
REPLACE EXIST WALL MTD TYPE LIGHTING
(TYPICAL)
FIXTURE W/ NEW LED LIGHT, TYP "NS-8"
REPLACE EXIST GFCI RECEPTACLE & COVER
PLATE W/NEW (TYPICAL)
L L
REPLACW WITH NEW WALL MTD TYPE
REPLACE EXIST CEILING RECESSED MTD TYPE LIGHTING
(TYPICAL)
FIXTURE W/ NEW LED LIGHT, TYP "NS-4b"
REPLACE EXIST CEILING RECESSED MTD TYPE LIGHTING
(TYPICAL)
FIXTURE W/ NEW LED LIGHT, TYP "NS-4a"
FAN COIL UNIT/1PH, 115V, 1/30HP,
(TYPICAL)
& THERMOSTAT (UNDER MECH. ITEM)
JUCTION BOX
W/NEW (TYPICAL)
REPLACE EXIST 3-WAY LIGHT SWITCH & COVER PLATE
REPLACE EXIST TOGGLE SWITCH & COVER PALTE
(TYPICAL)
FIXTURE W/ NEW LED LIGHT, TYP "NS-7"
REPLACE EXIST CEILING SURFACE MTD TYPE LIGHTING
REPLACE SINGLE RECEPTACLE & COVER
REPLACE EXIST DUPLEX RECEPTACLE & COVER
PLATE W/NEW FOR FAN COIL UNIT (TYPICAL)
REPLACE EXIST SINGLE MODULAR JACK AND
& COVER PALTE W/NEW (TYPICAL)
REPLACE EXIST SMOKE DETECTOR WITH
W/ SOUNDER BASE (TYPICAL)
NEW ADDRESSABLE SMOKE DETECTOR
EXHAUST FAN FOR BATH RM, 1PH, 115V-45W
(UNDER MECH. ITEM)
VISUAL STROBE(FA+MNS) (TYPICAL)
REPLACE EXIST WALL MOUNTED SPEAKER,
T T
THERMOSTAT(MECH ITEM)
TV TV
3S
MODULE-A
W/NEW (TYPICAL)
1/50
TYPICAL BEDROOM ELECTRICAL MODULE PLAN
BED ROOM A BED ROOM B
F
SB
L L
3S
S
S S
S
3S
3S
S
SJ
L
L
L L L
L
J
J J a
J b b b b b b a a a a a
SB
FCUFCU
TV
TV
L L
T T
TV TV
S b
Sb3
3S
MODULE-B
REPLACE SINGLE RECEPTACLE & COVER
PLATE W/NEW FOR FAN COIL UNIT (TYPICAL)
W/NEW (TYPICAL)
REPLACE EXIST 3-WAY LIGHT SWITCH & COVER PLATE
PLATE W/NEW (TYPICAL)
RECEPTACLE & COVER
REPLACE EXIST DUPLEX
REPLACW WITH NEW WALL
MTD TYPE CATV OUTLET W/
"0"dB LOSS FACE PLATE
AND F-81 BARREL TYPE
CONNECTOR (M.H: +300mm
AFF) (TYPICAL)
REPLACE EXIST SINGLE
PALTE W/NEW (TYPICAL)
MODULAR JACK AND COVER
JUCTION BOX
REPLACE EXIST SMOKE DETECTOR WITH
W/ SOUNDER BASE (TYPICAL)
NEW ADDRESSABLE SMOKE DETECTOR
VISUAL STROBE(FA+MNS) (TYPICAL)
REPLACE EXIST WALL MOUNTED SPEAKER,
THERMOSTAT(MECH ITEM)
NOTE
CONTRACTUAL WORK TO MEET SITE CONDITION.
CONTRACTOR SHALL VERIFY EXIST TYPE OF MODULES AND PROVIDE 1.
SCALE:
EWC
E W
C
FEC
UP
UP
S/S
STORAGE
VEST
ROOM
ADMIN OFFICE
R.O
106B
T.O
106A
WAIT AREA
STORAGE
106C
STAIR-2
119B
CO
XO
COMM
COMMO SHOP
113A113B
JAN
MULTI-PURPOSE RM
STORAGE
MECH ROOM
C.Q
VEST
STAIR-1
119A
LAUNDRY
JAN
CORRIDOR
105A
COMMUNITY
D
W
W
D
W/D
W/D
DAY RM REF
NBC ROOM
ARMS ROOM
COMM RM
LATRINE
MALE
LATRINE
FEMALE
E W
C
FEC FEC
UP DN
UP DN
REF
STAIR-1
218A
219 CORRIDOR
BED ROOM
201A
BED ROOM
201B
BED ROOM
202A
BED ROOM
202B
BED ROOM
203A
BED ROOM
203B
BED ROOM
204A
BED ROOM
204B
BED ROOM
205A
BED ROOM
205B
BED ROOM
206A
BED ROOM
206B
BED ROOM
207A
BED ROOM
207B
BED ROOM
208A
BED ROOM
208B
STAIR-2
218B
LAUNDRY
BED ROOM
214A
BED ROOM
214B
BED ROOM
213A
BED ROOM
213B
BED ROOM
212A
BED ROOM
212B
BED ROOM
211A
BED ROOM
211B
BED ROOM
210A
BED ROOM
210B
BED ROOM
209A
BED ROOM
209B
JAN
S/S
D
W
W
318A
301A301B302A302B303A303B304A304B305A305B306A306B307A307B308A308B
314A314B313A313B312A312B311A311B310A310B309A309B
318B
401A401B402A402B403A403B404A404B405A405B406A406B407A407B408A408B
414A414B413A413B412A412B411A411B410A410B409A409B
D
W/D
W/D
418B
418A
319419
DAY RM
SCALE:
1/100
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-9
LAN
TTB
DUAL MODULAR JACK
CAT-6, 8-PIN (RJ45 TYPE) OUTLET
FOR "TEL/DATA" (TYPICAL)
W/COVER PLATE & LUG FOR TEL
CAT-6, 8-PIN (RJ45 TYPE) OUTLET
(TYPICAL)
SOLID BOTTOM TYPE CABLE TRAY
ABOVE THE CEILING
(STEEL, 300mmW x 150mm H x LENGTH
AS REQ'D) W/O COVER
WITH SUPPORTER EVERY 3000mm
TO BE TERMINATED AT PATCH
TEL/DATA WIRE IN 27C
2-4PAIR, #24AWG, CAT-6
PANEL VIA CABLE TRAY
(TYPICAL)
(SEE TEL SYSTEM DIAGRAM ON E-10)
TELPHONE TERMINAL BOARD, EQUIPMENT RACK
REPLACE W/ NEW SINGLE MODULAR JACK
(TYPICAL)
TO BE TERMINATED AT MAIN
REPLACE EXISTING SINGLE MODULAR JACK
AND COVER PLATE WITH NEW
P-8
1ST FLOOR LAN/TEL PLAN
2ND, 3RD & 4TH FLOOR TEL PLAN
1ST, 2ND, 3RD & 4TH FLOOR LAN/TEL PLAN
ENTRANCE TELEPHONE CABLE)
AT MECH RM (REMOVE EXISTING
110 TERMINAL BLOCK IN TTC
T T C
REPAIR BLDG NO. S-753
CAMP CASEYTAK, YS
58484
W/FABRIC INNER DUCT IN 54C
1-25PAIR, #24AWG, TEL WIRE
OFFICE
OFFICE
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-10
(TYPICAL)
CABLE SUPPORT
EXOTHERMIC WELDING, LISTED COMPRESSION TWO-
1. THE CONNECTIONS OF THE BONDING CONDUCTOR FOR
TELECOMMUNITIONS TO THE TMGB SHALL UTILIZE
HOLE LUGS, SUITABLE AND EQUIVALENT TWO-HOLE
FINISHED FLOOR AND SHALL BE PLACED WITHIN 75mm
3. ENTRANCE CONDUITS SHALL EXTEND 150mm ABOVE
NOTES:
CROSS CONNECTING
PATCH CORD AS REQ'D
(1-100PAIR) (TYPICAL)
110 TYPE TERMINAL BLOCK
G
PTB
G
1-50PAIR, #24AWG TEL CABLE
NEW TELEPHONE TERMINAL BOARD (TTB)
G
GROUNDING BUSBAR (TMGB)
(100mm(W) x6.4mm(D) x450mmLG)
GROUND WIRE
NEW TELECOMMUNICATION MAIN
CONDUCTOR #6AWG
NOT TO SCALE
RACK TYPE 1-48 PORT
PATCH PANEL "DATA"
STAMP FACING OUT" TO ENSURE THAT THEY CAN BE
"PLYWOOD WILL BE INSTALLED WITH FIRE RATED
4. TEST RESULTS WILL BE PROVIDED IAW THE MOST RECENT
REVISION OF THE ANSI/TIA/EIA-568.
5. LABEL ALL DROPS IAW TIA/EIA-606-A.
6. LABEL ALL GROUNDS IAW I3A.
LUGS ARE PREFERRED.
FIELD VERIFIED.
OF A WALL.
NEW GROUND BONDING
RACK TYPE 1-48 PORT
PATCH PANEL "TEL"
(TYPICAL)
RACK TYPE 1-48 PORT
PATCH PANEL TEL"
PATCH PANEL "DATA"
6 METER (20FEET) SLACK
W/"SC" TYPE CONNECTIONS
HUB (N.I.C)
MODE FIBER OPTIC CABLE
NEW 1-12 STRAND SINGLE
(TYPICAL)
CONN TO NEW MAIN PANEL
GROUNDING SYSTEM
1#6 "BC" IN 27C
SEE NOTE 2 BELOW.
NEW 2WAY OF 103dia CONDUIT
42-4PAIR, CAT-6, #24AWG FOR TEL
1WAY: 42-4PAIR, CAT-6, #24AWG FOR DATA &
1WAY: SPARE W/PULL WIRE
(TYPICAL)
END BLANKS
D
T
PROTECTED TERMINAL BLOCK
(ENTRANCE) (1-50PAIR)
WALL MOUNTED TYPE
SURGE SUPPRESSION TYPE
QUAD-PLEX RECEPTACLE
2P-3W-125V-20A
GROUNDING TYPE WITH
DEDICATED CIRCUIT
D
T
D
T
D
T
D
T
D
T
D
T
105101101 104 105 105 105
ROOM NUMBER
WHICH DEVICE IS LOCATED
(TYPICAL)
1-4PAIR, #24AWG, CAT-6
FOR TEL IN 27C
CONN TO NEW PATCH PANEL
VIA CABLE TRAY
SOLID BOTTOM TYPE CABLE TRAY
ABOVE THE CEILING
(STEEL, 300mmW x 150mm H x LENGTH
AS REQ'D) W/O COVER
WITH SUPPORTER EVERY 3000mm
TO BE TERMINATED AT PATCH
TEL/DATA WIRE IN 27C
2-4PAIR, #24AWG, CAT-6
PANEL VIA CABLE TRAY
(TYPICAL)
1500mmx2400mmx19mmTHK PLYWOODx1EA
D
T
106B
D
T
106B
D
T
D
T
D
T
D
T
D
T
D
T
114 110
D
T
D
T
109 107 107 107 107
DUAL MODULAR JACK
CAT-6, 8-PIN (RJ45 TYPE) OUTLET
FOR "TEL/DATA" (TYPICAL)
SEE SITE PLAN
IN EXIST TTC AT MECH RM.
CONNECT TO MAIN 110 BLCOK
CONDUIT COUPLING
(TYPICAL)
NEW CONDUIT STUB-UP W/SEALING
(150mm AFF) (TYPICAL)
G
G
COMM RM 105A
2. PLYWOOD SHALL BE FIRE-RATED.
EQUIPMENT RACK
84.58"(H)"x24"(W)x34.67"(D)
(100mm(W) x6.4mm(D) x300mmLG)
NEW TELECOMMUNICATION
GROUNDING BUSBAR (TGB)
D
T
D
T
106A
D
T
D
T
D
T
D
T
D
T
D
T
D
T
D
T
D
T
105 105
D
T
106B
D
T
106A
D
T
106A
109 109
D
T
D
T
D
T
D
T
108 108 108 108 108 107
G
D
T
D
T
(TYPE NEMA 5-20R)
POWER RECEPTACLES
P-7 P-8
(TYPICAL)
TELECOMMUNICATION SYSTEM DIAGRAM
TELECOMMUNICATION SYSTEM DIAGRAM
7. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR DETAIL
EQUIPMENT RACK AND TELEPHONE TERMINAL BOARD FOR
GOVENRMENT APPROVAL PRIOR TO CONSTRUCTION.
REPAIR BLDG NO. S-753
CAMP CASEYTAK, YS
58484
G
1-25PAIR, #24AWG TEL CABLE
RACK TYPE 1-48 PORT
RACK TYPE 1-12 PORT
D
T
D
T
102101
D
T
D
T
D
T
102102
D
T
D
T
D
T
D
T
D
T
D
T
D
T
D
T
D
T
EWC
E W
C
UP
UP
S/S
STORAGE
VEST
ROOM
ADMIN OFFICE
R.O
106B
T.O
106A
WAIT AREA
STORAGE
106C
STAIR-2
119B
CO
XO
COMM
109 110 111
COMMO SHOP
113A 113B
JAN
MULTI-PURPOSE RM
STORAGE
MECH ROOM
C.Q
VEST
STAIR-1
119A
LAUNDRY
JAN
CORRIDOR
105A
COMMUNITY
D
W
W
D
W/D
W/D
DAY RM REF
NBC ROOM ARMS ROOM
COMM RM
LATRINE
MALELATRINE
FEMALE
UP DN
UP DN
REF
STAIR-1
218A
219 CORRIDOR
BED ROOM
201A
BED ROOM
201B
BED ROOM
202A
BED ROOM
202B
BED ROOM
203A
BED ROOM
203B
BED ROOM
204A
BED ROOM
204B
BED ROOM
205A
BED ROOM
205B
BED ROOM
206A
BED ROOM
206B
BED ROOM
207A
BED ROOM
207B
BED ROOM
208A
BED ROOM
208B
STAIR-2
218B
LAUNDRY
BED ROOM
214A
BED ROOM
214B
BED ROOM
213A
BED ROOM
213B
BED ROOM
212A
BED ROOM
212B
BED ROOM
211A
BED ROOM
211B
BED ROOM
210A
BED ROOM
210B
BED ROOM
209A
BED ROOM
209B
JAN
S/S
D
W
W
318A
301A301B302A302B303A303B304A304B305A305B306A306B307A307B308A308B
314A314B313A313B312A312B311A311B310A310B309A309B
318B
401A401B402A402B403A403B404A404B405A405B406A406B407A407B408A408B
414A414B413A413B412A412B411A411B410A410B409A409B
D
W/D
W/D
418B
418A
319419
DAY RM
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-11
TVTVTV
TV
TV
TV
TV
T V
T V
T V
T V
T V
T
C T
C
TVTV
SCALE 1/100
1-RG 11/U IN 21C
COAXIAL CABLE
(TYPICAL)
W/8-WAY TAP-OFF AND
PULL BOX (300x300x200D)
LOCKING DEVICE ABOVE CEILING
CATV OUTLET W/"0"dB LOSS FACE
PLATE AND F-81 BARREL TYPE
CONNECTOR (M.H: +300mm AFF)
(TYPICAL)
1-RG 6/U IN 16C
COAXIAL CABLE
(TYPICAL)
W/6-WAY TAP-OFF AND
PULL BOX (300x300x200D)
LOCKING DEVICE ABOVE CEILING SEE DIAGRAM
PROVIDE NEW CATV DIST. CABINET (CTC-1)
NEW WALL MTD TYPE
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TVTV
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
C T
C
6 TV4
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
T V
P
T V
TV
TVTV
TV
TV
TV
W/4-WAY TAP-OFF AND
PULL BOX (300x300x200D)
LOCKING DEVICE ABOVE CEILING
W/6-WAY TAP-OFF AND
PULL BOX (300x300x200D)
LOCKING DEVICE ABOVE CEILING
W/8-WAY TAP-OFF AND
PULL BOX (300x300x200D)
LOCKING DEVICE ABOVE CEILING
(TYPICAL OF 6)
CATV OUTLET W/"0"dB LOSS FACE
NEW WALL MTD TYPE
PLATE AND F-81 BARREL TYPE
CONNECTOR (M.H: +300mm AFF)
(TYPICAL)
1-RG 6/U IN 16C
COAXIAL CABLE
(TYPICAL)
SCALE 1/100
1-RG 11/U IN 21C
COAXIAL CABLE
(TYPICAL)
27C EMPTY CONDUIT
TO " " IN RM. 215CTC
W/PULL WIRE
TO REMAIN
EXIST ENTRANCE CAP & SEC.RACK
T V
TV
REPLACE W/ NEW CATV DIST.
CABINET (CTC-2) SEE DIAGRAM
1ST FL CATV PLAN
2ND ,3RD AND 4TH FL CATV PLAN
1ST, 2ND ,3RD AND 4TH FLOOR CATV PLAN
REPAIR BLDG NO. S-753
CAMP CASEYTAK, YS
58484
OFFICE
OFFICE
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-12
3F
4F
2F
1F
AMP
2 4
ROOF
2 AMP
AMP
AMP
TV
106B
TV
TVTV
TV
TV
TVTV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TVTV
TV
211210
TV
TV
TV
TV
TV
TVTV
TV
TV
TV
TV
TV
TV
TVTV
TV
202203
TV
TV
TV
TV
TV
TVTV
TV
204205
TV
TV
TV
TV
TV
TVTV
TV
206207
TV
TV
TV
TV
TV
TVTV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TVTV
TV
311310
TV
TV
TV
TV
TV
TVTV
TV
TV
TV
TV
TV
TV
TVTV
TV
302303
TV
TV
TV
TV
TV
TVTV
TV
304305
TV
TV
TV
TV
TV
TVTV
TV
306307
TV
TV
TV
TV
TV
TVTV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TV
TVTV
TV
411410
TV
TV
TV
TV
TV
TVTV
TV
TV
TV
TV
TV
TV
TVTV
TV
402403
TV
TV
TV
TV
TV
TVTV
TV
404405
TV
TV
TV
TV
TV
TVTV
TV
406407
TV
TV
TV
TV
TV
TVTV
TV
G
G G
G G
RG 6/U IN 16C
COAXIAL CABLE
(TYPICAL)
DEVICE IS LOCATED
ROOM NUMBER WHICH
(TYPICAL)
CATV OUTLET W/"0"dB LOSS FACE
NEW WALL MTD TYPE
PLATE AND F-81 BARREL TYPE
CONNECTOR (M.H: +300mm AFF)
(TYPICAL)
SURGE SUPPRESSION TYPE
DUPLEX RECEPTACLE
(2P-3W-15A-125V)
FOR AMPLIFIER
(TYPICAL)
(TYPICAL)
1#6 "BC" IN 21C
(TYPICAL)
GROUNDING TERMINAL BLOCK
W/8-WAY TAP-OFF AND
PULL BOX (300x300x200D)
LOCKING DEVICE ABOVE CEILING
(TYPICAL)
W/4-WAY TAP-OFF AND
PULL BOX (300x300x200D)
LOCKING DEVICE ABOVE CEILING
(TYPICAL)
W/6-WAY TAP-OFF AND
PULL BOX (300x300x200D)
LOCKING DEVICE ABOVE CEILING
(TYPICAL)
2#12 & 1#12(G) IN 16C
RG 11/U IN 21C
COAXIAL CABLE
(TYPICAL)
GROUND ROD, COPPER CLAD STEEL,
19mm dia x 3000mm LONG
WITH WELDING CONNECTION AND
CONN. TO BLDG ELECTRODE
GROUNDING SYSTEM
#6 "BC"
EXIST ENTRANCE CAP & SEC. RACK
TO REMAIN
PROVIDE NEW 27C EMPTY CONDUIT
W/PULL WIRE
TV
TV
TV
TVTV
TV
TV
TV
TVTV
TV
2#12 & 1#12(G) IN 16C
2#12 & 1#12(G) IN 16C
1PH-208V
2#12 & 1#12(G) IN 16C
CATV DISTRIBUTION CABINET (CTC-2)
(762mm(W)x610mm(H)x254mm(D), BACKBOARD LINE EXTENDER
WITH 610x610 W/19THK PLYWOOD
AMPLIFIERS, 4-WAY SPLITTER-1EA,
RECEPTACLE, AIR VENTS AND
LOCKING DEVICE NEMA 1 ENCL
2-WAY SPLITTER-1EA,
CATV DISTRIBUTION CABINET (CTC-1)
(762mm(W)x610mm(H)x254mm(D), BACKBOARD LINE EXTENDER
WITH 610x610 W/19THK PLYWOOD
AMPLIFIERS, 2-WAY SPLITTER-1EA,
RECEPTACLE, AIR VENTS AND
LOCKING DEVICE NEMA 1 ENCL
CATV DISTRIBUTION CABINET (CTC-3)
(762mm(W)x610mm(H)x254mm(D), BACKBOARD LINE EXTENDER
WITH 610x610 W/19THK PLYWOOD
AMPLIFIERS, 2-WAY SPLITTER-1EA,
RECEPTACLE, AIR VENTS AND
LOCKING DEVICE NEMA 1 ENCL
CATV DISTRIBUTION CABINET (CTC-4)
(762mm(W)x610mm(H)x254mm(D), BACKBOARD LINE EXTENDER
WITH 610x610 W/19THK PLYWOOD
AMPLIFIERS, 2-WAY SPLITTER-1EA,
RECEPTACLE, AIR VENTS AND
LOCKING DEVICE NEMA 1 ENCL
CATV SYSTEM DIAGRAM
NOT TO SCALE
TO LOADCENTER "L1", CKT NO. "L1-5"
1PH-208V
2#12 & 1#12(G) IN 16C
TO LOADCENTER "L1", CKT NO. "L1-4"
TO LOADCENTER "L2", CKT NO. "L2-4"
TO LOADCENTER "L2", CKT
NO. "L2-5" 1PH-208V
TO LOADCENTER "L3", CKT NO. "L3-4"
TO LOADCENTER "L3", CKT
NO. "L3-5" 1PH-208V
TO LOADCENTER "L4", CKT
NO. "L4-5" 1PH-208V
TO LOADCENTER "L4", CKT NO. "L4-4"
CATV SYSTEM DIAGRAM
REPAIR BLDG NO. S-753
CAMP CASEYTAK, YS
EWC
FEC
UP
UP
S/S
STORAGE
VEST
121ROOM
ADMIN OFFICE
R.O
106B
T.O
106A
WAIT AREA
STORAGE
106C
STAIR-2
119B
CO
XO
COMM
109 110 111
COMMO SHOP
113A 113B
JAN
MULTI-PURPOSE RM
STORAGE
MECH ROOM
C.Q
VEST
STAIR-1
119A
LAUNDRY
JAN
CORRIDOR
105A
COMMUNITY
D
W
W
D
W/D
W/D
DAY RM REF
NBC ROOM ARMS ROOM
COMM RM
LATRINE
MALE
LATRINE
FEMALE
E W
C
FEC FEC
UP DN
UP DN
STAIR-1
218A
CORRIDOR
BED ROOM
201A
BED ROOM
201B
BED ROOM
202A
BED ROOM
202B
BED ROOM
203A
BED ROOM
203B
BED ROOM
204A
BED ROOM
204B
BED ROOM
205A
BED ROOM
205B
BED ROOM
206A
BED ROOM
206B
BED ROOM
207A
BED ROOM
207B
BED ROOM
208A
BED ROOM
208B
STAIR-2
218B
LAUNDRY
BED ROOM
214A
BED ROOM
214B
BED ROOM
213A
BED ROOM
213B
BED ROOM
212A
BED ROOM
212B
BED ROOM
211A211B 210A
210B
BED ROOM
209A
BED ROOM
209B
JAN
S/S
D
W
W
318A
301A301B302A302B303A303B304A304B305A305B306A306B307A307B308A308B
314A
314B313A313B312A312B311A311B 310A
310B309A309B
318B
401A401B402A402B403A403B404A404B405A405B406A406B407A407B408A408B
414A
414B413A413B412A412B411A411B 410A
410B409A409B
D
W/D
W/D
418B
418A
319419
DAY RM
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-13
ADDRESSABLE FIRE ALARM
F M
C P
F T
R
FF
F
F
F F
F
F
F
FF
F
F
F
F
F F
F F
F
F
F
F
F
AS REQ'D. PROGRAMMABLE MODULE
RELAYS, POWER MODULE AS REQ'D,
LCD ANNUNCIATOR, SYNCHRONIZATION
CONTROL MODULE, BATTERY,
BATTERY CHARGER, NEMA 1 ENCL
SURFACE MOUNTED BUILDING TRANSMITTER
W/BATTERY & BATTERY CHARGER
NEMA 1ENCL
1/100SCALE:
ADDRESSABLE FIRE ALARM
MANUAL PULL STATION
(TYPICAL)
SMOKE DETECTOR
(TYPICAL)
S P
R
J J
C
F
F
F F
F F
F
F
F
FF
F
FFFFFFFFFFFF
FF
F
F F
F
F F
F
F
F F
F F
F
F
F
F
F
F
F
SB
SH SH
F
F
SB SBSB
FF
SBSB
F
SBSB
F
SBSB
F
SBSH
F
SBSB
F
SBSB
FFFFFF
F
SH SH
F
SH SH
F
SB SH
F
SB SB
F
SB SB
1/100SCALE:
SURFACE MOUNTED BOOSTER PANEL
1PH, 120VAC INPUT, 5A(MAX)@24VDC, OUTPUT
W/CLASS "A" AS REQ'D W/SLC MODULE
AS REQ'D POWER MODULE AS REQ'D
CONFIGURATION PROGRAMMABLE RELAYS.
GROUND LOOP ISOLATION ANS TRANSIENT
PROTECTION etc. NEMA 1 ENCL
CONN TO SHUNT TRIP CIRCUIT
RELAY W/ADDRESSABLE MODULE
FIRE SUPPRESSION PANEL
W/ADDRESSABLE MODULE
(UNDER MECH. ITEM)
FOR ELEC RANGE
ADDRESSABLE FIRE ALARM
MANUAL PULL STATION
(TYPICAL)
F F F
F M
B P
J
PS TS
J
TS
J
TS
J
TS
J
LOC
LOC
J
FS
S
PJ
J
C
WALL MOUNTED SPEAKER (WATTAGE AS REQ'D)
/COMBO. (FA+MNS) VISUAL STROBES
(CANDELA AS REQ'D) (TYPICAL)
WALL MOUNTED SPEAKER (WATTAGE AS REQ'D)
/COMBO. (FA+MNS) VISUAL STROBES
(CANDELA AS REQ'D) (TYPICAL)
LOCAL OPERATING CONSOLE
SURFACE MOUNTED ADDRESSABLE COMBINED FIRE ALARM
CONTROL AND MASS NOTIFICATION SYSTEM PANEL, W/24VDC
BULIT-IN ADDRESSABLE POINTS MODULES
BED ROOMBED ROOM
BED ROOM
(TYPICAL)
LOCAL OPERATING CONSOLE
(TYPICAL)
D
J
DS
R
J
CO
W P
F M
W P
F M
WP
F M
F
TS
JJ
FS
R
CONN TO SHUNT TRIP CIRCUIT
FOR ELEC RANGE
BREAKER L1-3 IN LOADCENTER "L1"
WALL MOUNTED SPEAKER (WATTAGE AS REQ'D)
,COMBO. (FA+MNS), "WP" (TYPICAL)
1ST FL FIRE ALARM AND MASS NOTIFICATION SYSTEM PLAN
2ND, 3RD & 4TH FL FIRE AND MASS NOTIFICATION SYSTEM PLAN
AND MASS NOTIFICATION SYSTEM PLAN
1ST, 2ND, 3RD & 4TH FLOOR FIRE ALARM
LOADCENTER "L2","L3" &"L4"
BREAKER L2-3,L3-3 & L4-3 IN
REPAIR BLDG NO. S-753
CAMP CASEYTAK, YS
58484
SMOKE W/SOUNDER BASE (TYPICAL)
ADDRESSABLE COMBINED PHOTOELECTRIC
OFFICE
OFFICE
F F
F
F
F F
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
2#12 IN 16C(FOR POWER)
12#14 IN 21C(FOR SIGNAL)
(TYPICAL)
SEE NOTE 2. BELOW
FOR NO & SIZE OF WIRE
WHICH DEVICE IS LOCATED
(TYPICAL)
ROOM NUMBER
SG
6#14 IN 16C
BOOSTER PANEL#1 (FMBP)
BATTERY CHARGER, POWER MODULE PANEL(AS REQ'D)
SYNCHRONIZATION CONTROL MODULE, DIGITAL VOICE
FIRE ALARM/MASS NOTIFICATION CONTROL PANEL,
24VDC, BUILT-IN ADDRESSABLE POINTS MODULES
AS REQUIRED, PROGRAMMABLE MODULE & RELAYS,
POWER MODULE AS REQ.D LCD ANNUNCIATOR,
123120101 117
EXT 120120 109 110 113B
NOT TO SCALE
(TYPICAL)
BATTERY & BATTERY CHARGER, etc. NEMA 1 ENCL
GROUND LOOP ISOLATION AND TRANSIENT PROTECTION
BOOSTER PANEL, 1PH, 120VAC INPUT, 6A(MAX)
@24VDC OUTPUT W/CLASS"A" AS REQ'D WITH
SLC MODULE AS REQ'D, POWER MODULE PANEL (AS REQ'D)
AMPLIFIER(AS REQ'D) CONFIGURATION PROGRAMMABLE RELAYS,
MANUAL PULL STATION
(TYPICAL)
W/MOUNTING BRACKET
LIGHTNING ARRESTER
OMNI-DIRECTION TYPE
W/CONNECTORS IN 16C
COAXIAL CABLE
GROUND CONDUCTOR
#6 "BC" IN 21C
W/WEATHER-PROOF ENCLOSURE
WITH WELDING CONNECTION
GROUND ROD, COPPER CLAD
STEEL, 19mmdia x 3000mmLG
BUILDING
TRANSMITTER
G ~
GROUND ROD, COPPER CLAD
#6, "BC" IN 21C
GROUNDING SYSTEM
CONN TO BLDG ELECTRODE
STEEL, 19mmdiax3000mmLG
WITH WELDING CONNECTION AND
2#12 & 1#12(G) IN 16C
G
SG
CONTROL PANEL (FMCP)
COMBINED FIRE ALARM/
ROOF
3rd FLOOR
1st FLOOR
EXT
113A
111107
120 106104
SURFACE MOUNTED COMBINED ADDRESSABLE
MODULE, POWER SUPPLY, MICROPHONE, BATTERY,
AND AMPLIFIER(AS REQ'D), NEMA 1 ENCL
MASS NOTIFICATION
FIRE ALARM/MASS NOTIFICATION
15.
"FIRE" AND W/CLEAR LENS.
1.
"ALERT" IN RED LETTER AND W/AMBER LENS.
SAFE PATH FACILITY COMMUNICATIONS OR APPROVED EQUAL.
STROBES FOR FIRE ALARM SHALL BE MARKED
STROBES FOR MASS NOTIFICATION SHALL BE MARKED
FOR ABBREVIATION, LEGEND, AND GENERAL NOTES
MASS NOTIFICATION SYSTEM SHALL BE SIMILAR TO WHEELOCK10.
5) EMERGENCY WEATHER CONDITIONS APPROPRIATE FOR THE LOCAL AREA
4) EVACUATION OF THE BUILDING USING EXITS OTHER THAN THE NORMAL MAIN ENTRANCE/EXIT
2) INTRUDER/HOSTILE PERSON SIGHTED WITHIN/AROUND THE BUILDING
1) BOMB THREAT OR ACTUAL BOMB WITHIN/AROUND THE BUILDING
ARE IN ENGLISH AND HANGUL AT LEAST FOR THE FOLLOWING ITEMS.
THE MASS NOTIFICATION SYSTEM SHALL BE ENSURED THAT PRERECORDED MESSAGES
WITH THE MANUFACTURER'S LISTED INSTALLATION REQUIREMENTS AND WIRE COUNT.
SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION DEVICE LOCATIONS IN ACCORDANCE
THE APPLICABLE CODE, SPECIFICATIONS AND MANUFACTURER'S EQUIPMENT LISTING.
IS THE MINIMUM REQUIRED AND THE FINAL QUANTITY SHALL BE IN ACCORDANCE WITH
THE MASS NOTIFICATION SYSTEM IS CONCEPTUAL. THE NUMBER OF DEVICES SHOWN19.
3) OCCUPANTS DIRECTED TO TAKE COVER WITHIN THE BUILDING
6) "ALL CLEAR" MESSAGE
PER DRAFT UFC 4-021-01.
18.
21.
20.
14. ADDITIONAL RELAY IS PROVIDED AS REQUIRED.
SYNCHRONIZED. AUDIBLE APPLIANCES SHALL PROVIDE THE
SPECIFICATION SECTION 28.31.64.00.31(FA) AND NFPA 72.
APPROVED.
ARCHITECTURAL FEATURES.
LOCATIONS IN ACCORDANCE WITH THE MANUFACTURER'S
IN ACCORDANCE WITH THE APPLICABLE CODE, SPECIFICATIONS
THE MINIMUM REQUIRED AND THE FINAL QUANTITY SHALL BE
AND READY TO USE. THE NUMBER OF DEVICES SHOWN IS
BE PROVIDED WITH CLASS "A" MODULES
HORIZONTAL AND 305mm VERTICALLY.
TRANSMITTER AND ANTENNA.
PANEL COVER.
BREAKER AND/OR DISCONNECT SWITCH.
FOR THE FIRE ALARM AND DETECTION SYSTEM.
AUDIBILITY CALCULATION, WIRE SIZE, NO. OF WIRES
NOTES:
SHALL BE RESPONSIBLE FOR PROVIDING FIRE ALARM
THE FIRE ALARM/MASS NOTIFICATION SYSTEM CONTRACTOR
FIRE ALARM CIRCUIT SHALL BE IDENTIFIED BY A RED LETTER
"FIRE ALARM CIRCUIT" ON THE DEDICATED POWER CIRCUIT
CIRCUIT SHALL BE INDICATED ON THE FIRE ALARM CONTROL
THE POWER CIRCUIT NUMBER DEDICATED TO FIRE ALARM4.
3.
2.
COAXIAL CABLE SHALL BE ONE PIECE BETWEEN BUILDING5.
SYSTEM SHALL BE SEPARATED BY A MINIMUM OF 1220mm
INCOMING AND OUTGOING CLASS "A" RACEWAY OF FA6.
7. ALL CLASS "A" EXCEPTIONS IN NFPA 72, 6.4.2.2.2 ARE
PROHIBITED FOR ALL IDC, NAC AND SLC.
ALL TAMPER SWITCHES, FLOW SWITCHES, PRESSURE
SWITCHES AND NON-ADDRESSABLE INITIATION DEVICES SHALL
COORDINATE THE EXACT DEVICE LOCATIONS WITH ELECTRICAL
AND MECHANICAL SYSTEM EQUIPMENT AND BUILDING
ALL DEVICES AND EQUIPMENT SHALL BE UL LISTED OR FM
ALL AUDIBLE APPLIANCES WITHIN THE BUILDING AND ALL
VISUAL APPLIANCES WITHIN THE SAME ROOM SHALL BE
STANDARD TEMPORAL PATTERN, NFPA 72.
SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH
9.
11.
12.
13.
SHALL COMPLETE THE DESIGN AND INSTALL THE SYSTEM
8.
LISTED INSTALLATION REQUIREMENTS AND WIRE COUNT.
SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION DEVICE
AND MANUFACTURER'S EQUIPMENT LISTING.
COMPLETE THE DESIGN AND INSTALL THE SYSTEM COMPLETE
THE FIRE ALARM SYSTEM IS CONCEPTUAL. THE CONTRACTOR
ALSO CONDUITS SHALL BE RUN AWAY AT LEAST 900mm
(3-FEET) FROM HVAC, HOT & COLD WATER PIPING.
SURFACE MOUNTED BUILDING
F
DS
D
F
WP
F M
WP
F M
215219214A212A
210B 207B 207A 206A
203B202B202A201A
205A
204A
205B
203A
206B
201B
211B
213A 214B
210A…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .