UNIT TRAINING EQUIPMENT SITE ADD/ALT
Copyright 2010 by The American Institute of Architects (AIA)
Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA
SECTION 224233 - WASH FOUNTAINS
Revise this Section by deleting and inserting text to meet Project-specific requirements.
Verify that Section titles referenced in this Section are correct for this Project's Specifications; Section titles may have changed.
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Semicircular wash fountains.
1.2 ACTION SUBMITTALS
A. Product Data: For each type of product.
Retain "LEED Submittals" Paragraph below if applying for LEED certification. See the "LEED Rating System" Article in the Evaluations.
1.3 CLOSEOUT SUBMITTALS
A. Operation and maintenance data.
PART 2 - PRODUCTS
See Editing Instruction No. 1 in the Evaluations for cautions about named manufacturers and products. For an explanation of options and Contractor's product selection procedures, see Section 016000 "Product Requirements."
Do not use the same plumbing fixture designation as is used for a plumbing fixture in another plumbing Section.
Retain "Manufacturers" Subparagraph and list of manufacturers below to require products from manufacturers listed or a comparable product from other manufacturers.
2.1 STAINLESS-STEEL, SEMICIRCULAR WASH FOUNTAINS
Copy "Wash Fountains" Paragraph below and re-edit for each type of semicircular wash fountain required.
Insert letter and number combination to complete drawing designation. Use these designations on Drawings to identify each stainless-steel, semicircular wash fountain.
A. Wash Fountains: On-floor, stainless-steel, semicircular receptor.
Retain "Manufacturers" Subparagraph and list of manufacturers below to require products from manufacturers listed or a comparable product from other manufacturers.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
Retain "Basis-of-Design Product" Subparagraph and list of manufacturers below to identify a specific product or a comparable product from manufacturers listed. Retain option and delete insert note if manufacturer's name and model number are indicated on Drawings.
a. Acorn Engineering Company.
b. Bradley Corporation.
c. Willoughby Industries.
2. Standard: IAPMO IGC 156.
3. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
4. Receptor:
a. Standard: ASME A112.19.3/CSA B45.4 for stainless-steel receptor.
b. Nominal Diameter: 54 inches.
Retain first option in "Height to Rim" Subparagraph below for on-floor receptors, or insert dimension for off-floor receptors for children and elderly/handicapped persons.
c. Height to Rim: 28 inches above floor.
d. Color or Finish: Not applicable.
e. Drain: Grid with NPS 1-1/2 tailpiece.
5. Spray Head:
a. Material: Stainless steel or integral part of receptor back.
b. Number of User Stations: Four.
c. Spray Nozzles: Chrome-plated brass or stainless steel complying with NSF 61 and ASME A112.18.1/CSA B125.1.
Verify option retained in "Control" Subparagraph below is available from listed manufacturers and for type of wash fountain required.
d. Control: Collective, foot-rail actuation with thermostatic mixing valve complying with ASSE 1016 and having check stops; comply with NSF 61.
Retain "Sensor" Subparagraph below if retaining "Individual, hardwired sensor" or "Individual, battery-powered sensor" option in "Control" Subparagraph above.
e. Sensor: ASME A112.18.1/CSA B125.1 and UL 1951.
Verify "Hardwired, sensor actuated" or "Battery powered, sensor actuated" option, if retained in "Liquid-Soap Dispensers" Subparagraph below, is available from listed manufacturers and for type of wash fountain required. Typically, sensor-operated soap dispensers are battery powered; however, they require hardwiring if the nozzles are hardwired.
6. Liquid-Soap Dispensers: Not required.
Retain "Sensor" Subparagraph below if retaining "Hardwired, sensor actuated" or "Battery powered, sensor actuated" option in "Liquid-Soap Dispensers" Subparagraph above.
7. Supply Fittings:
a. Piping: NPS 3/4 copper tubing.
b. Valves: Shutoff valve on each supply.
c. Supply Piping: From top.
8. Waste Fittings:
a. Standard: ASME A112.18.2/CSA B125.2.
b. Trap and Drain Piping: NPS 1-1/2.
c. Vent Piping: NPS 1-1/2 to ceiling.
Retain "Shroud" Subparagraph below if required to conceal vertical supply and vent piping.
Retain "Off-Floor Mounting" Subparagraph below for wall-mounted wash fountains.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Install wash fountains level and plumb according to roughing-in drawings.
B. Set freestanding wash fountains on floor.
C. Install water-supply piping with shutoff valve on each supply to each wash fountain to be connected to domestic-water distribution piping. Use ball valve. Install valves in locations where they can be easily reached for operation. Valves are specified in Section 220523 "General-Duty Valves for Plumbing Piping."
D. Install trap and waste piping on each drain outlet of each wash fountain to be connected to sanitary drainage system.
E. Seal joints between fixtures and walls using sanitary-type, one-part, mildew-resistant, silicone sealant. Match sealant color to fixture color. Comply with sealant requirements specified in Section 079200 "Joint Sealants."
3.2 CONNECTIONS
Coordinate piping installations and specialty arrangements with Drawings and with requirements specified in piping systems. If Drawings are explicit enough, these requirements may be reduced or omitted.
A. Connect wash fountains with water supplies, stops, and risers, and with traps, soil, waste, and vent piping. Use size fittings required to match fixtures.
B. Comply with requirements for water piping specified in Section 221116 "Domestic Water Piping."
C. Comply with requirements for soil and waste drainage piping and vent piping specified in Section 221316 "Sanitary Waste and Vent Piping."
D. Install protective-shielding pipe covers and enclosures on exposed supplies and waste piping of accessible wash fountains. Comply with requirements in Section 220719 "Plumbing Piping Insulation."
3.3 ADJUSTING
A. Operate and adjust wash fountains and controls. Replace damaged and malfunctioning wash fountains, fittings, and controls.
B. Adjust water pressure at faucets to produce proper flow.
3.4 CLEANING AND PROTECTION
A. After installing wash fountains, inspect and repair damaged finishes.
B. Clean wash fountains, faucets, and other fittings with manufacturers' recommended cleaning methods and materials.
C. Provide protective covering for installed wash fountains and fittings.
D. Do not allow use of wash fountains for temporary facilities unless approved in writing by Owner.
END OF SECTION 224233