W912QR24R0003_Plans_Vol2-0003.pdf

PDF 3 MB Posted

Attached to
Fort McCoy, WI - Collective Training Officers Quarters
Solicitation number
W912QR24R0003
Issued by

About this file

This document appears to be a set of plans and drawings for the construction of two new 48,000 SF, 4-story Collective Training Officers Quarters (CTOQ) facilities at Fort McCoy, Wisconsin. The solicitation number is W912QR24R0003. The plans include details on the architectural, structural, mechanical, electrical, and interior finishes for the new buildings. Key details include:

  • Construction of two new 48,000 SF, 4-story CTOQ facilities
  • Architectural, structural, mechanical, electrical, and interior finish details provided
  • Solicitation number W912QR24R0003
  • Located at Fort McCoy, Wisconsin
  • Construction of the new facilities is the main requirement of this federal contract opportunity.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

WEDGE-LOCK WELDING

CONNECTOR

STEEL BRACKET ASSY. SECURED

TO WALL (OR WELD TO STEEL PIPE

GUARDRAIL - WHERE OCCURS)

1 1/2" O.D. (MAX.) STEEL PIPE

HANDRAIL WELD TO STEEL

BRACKET

WELD PIPE SECTIONS TOGETHER

WITH A CONTINUOUS WELD, GRIND

SMOOTH, & FILL WITH BODY PUTTY

TO ENSURE INVISIBILITY OF SEAM

3/16" END STEEL PLATE;

WELD & GRIND SMOOTH

WALL, REFER TO PLANS

FOR

PARTITION TYPE

1/2"

CLR.

2 1/4"

R 2 1/2

1/2"

2 1 /2"

12"

TYPICAL ROUND WALL HANDRAIL 1 1/2" O.D. PIPE

F.F.

F.F.

BOTTOM LANDING

TOP LANDING

STAIR3'-

0"

ONE TREAD

1'-0"

6'-0" MAX.

1'-0"

1'-0"

6"

3'- 0"

3'- 0"

PROVIDE CONTINUOUS BACKING

FOR HANDRAIL ATTACHMENT,

TYP.

E15 A-412

Sim

A15 A-412

Sim

3'-0" TO STAIR NOSING

STEEL BRACKET ASSEMBLY WITH

MOUNTING SCREWS & BACKER

PLATE

WALL, REFER TO FLOOR PLAN

CONT. 1 1/2" O.D. STEEL PIPE

HANDRAIL, PAINTED (W2);

WELD TO STEEL BRACKET

ASSEMBLY

NOTE:

AT METAL STUD WALL, PROVIDE 16

GA METAL RUNNER NOTCHED TO

BYPASS METAL STUDS FOR METAL

BACKING.

CLR.

2 1/4"

TUBE STRINGER, PAINTED

TYPICAL

STEEL PAN TREADS WITH

CONCRETE FILL, TYPICAL

1 1/2" O.D. STEEL TUBE HANDRAIL

CONTINUOUS AT INTERNAL RAIL,

PAINTED, TYPICAL.

1 1/2" O.D. STEEL TUBE

GUARDRAIL

SYSTEM, PAINTED, TYPICAL

CLR

2 1/4"

CLR

2 7/8"

3' -0

" 3' -6

" 3' -0

6" METAL STUD WITH (2)

LAYERS 5/8" GYPSUM

BOARD ON BOTH SIDES

UP TO THE METAL DECK

STAIR LANDING

1 1/2" O.D. PIPE TOP RAIL

METAL TOE KICK

1 1/2" O.D. INTERMEDIATE PIPE

RAIL TYP.

1 1/2" O.D. GUARDRAIL PIPE POST

@ 4'-0" MAX. SPACING

NOTE:

1. SUBMIT SHOP DRAWINGS PRIOR TO

FABRICATION.

3' -6

EQ

EQ

EQ

EQ

EQ

2"

M

AX

4"

C

LR

EQ

EQ

1 1/2" O.D. PAINTED STEEL TUBE GUARDRAIL

SYSTEM WITH 1 1/2" O.D. PAINTED (W2)

STEEL HORIZONTAL PICKETS AT 4" O.C. TYP.

WELDED TO POSTS

1 1/2" O.D. STEEL TUBE HANDRAIL,

CONTINUOUS AT INTERNAL RAIL,

PAINTED, TYPICAL. NOTE: EXTEND

HANDRAIL HORIZONTALLY ABOVE

THE LANDING FOR 12" MIN. (AT

WALL BEYOND)

SEE STRUCTURAL DRAWINGS

FOR LANDINGS

TUBE STRINGER, PAINTED (W2),

TYPICAL

3' -6

3' -0

SEE STRUCTURAL DRAWINGS

FOR LANDINGS

TUBE STRINGER, PAINTED

(W4), TYPICAL

1 1/2" O.D. STEEL TUBE HANDRAIL,

CONTINUOUS AT INTERNAL RAIL, PAINTED

(W2), TYPICAL. NOTE: EXTEND HANDRAIL

HORIZONTALLY ABOVE THE LANDING FOR

12" MIN. (AT WALL BEYOND)

1 1/2" O.D. PAINTED STEEL TUBE

GUARDRAIL SYSTEM WITH 1 1/2" O.D.

PAINTED STEEL HORIZONTAL PICKETS AT

4" O.C. TYP. WELDED TO POSTS

3' -6

3' -0

MIN.

1'-0"

4" M

AX

STEEL PAN TREADS WITH CONCRETE

FILL, TYPICAL

TUBE STRINGER, PAINTED (W4),

TYPICAL PROVIDE CLOSURE PLATE

1 1/2" O.D. STEEL TUBE HANDRAIL,

CONTINUOUS AT INTERNAL RAIL,

PAINTED (W2), TYPICAL.

1 1/2" O.D. PAINTED STEEL TUBE

GUARDRAIL SYSTEM WITH 1 1/2" O.D.

PAINTED STEEL HORIZONTAL PICKETS

AT 4" O.C. TYP. WELDED TO POSTS

1ST FLOOR

0"

11"

3' -0

A11 A-412

Sim

" T

O S

TA

IR

N O

SI

N

G

" T

O S

TA

IR

N

O

SI

N

G 1 1/2" O.D. PIPE HANDRAIL

ON BRACKET WELD TO PIPE RAIL

POST

1 1/2" O.D. VERTICAL OR HORIZONTAL

INTERMEDIATE PICKET RAIL (4" MAXIMUM

OPENING)

1 1/2" O.D. PIPE TOP RAILS,

PAINTED

1 1/2" O.D. PIPE,

PAINTED (W2)

CLR

2 1/4"

NOTE:

1. MAXIMUM OPENING IS SUCH THAT

4" SPHERE CANNOT PASS THROUGH.

2. SUBMIT SHOP DRAWINGS PRIOR TO

FABRICATION.

2ND FLOOR

12'-0"

HANDRAIL BEYOND

CONCRETE SLAB ON

METAL DECK, SEE

STRUCT. DWGS

STEEL STRUCTURE,

SEE STRUCT. DWGS

CONTINOUS SLIP TRACK

WITH FIRESTOP MATERIAL

WITH CONTINOUS BEAD OF

SEALANT BOTH SIDES.

2 1/2" METAL STUD

@ 16" O.C.

6" METAL STUD WITH (2)

LAYERS 5/8" GYPSUM

BOARD ON BOTH SIDES

UP TO THE METAL DECK

6" METAL STUD WITH (2)

LAYERS 5/8" GYPSUM

BOARD ON BOTH SIDES

UP TO THE METAL DECK

2ND FLOOR

12' - 0 1/4"

INTERMEDIATE FLOOR

LANDING PROVIDED BY

STAIR MANUFACTURER

AS PART OF DELEGATED

STAIR DESIGN6" METAL STUD

FRAMING @ 16" O.C.

WITH ( 1 ) LAYER 5/8"

FIRERATED GWB BOTH

SIDES.

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

LO

U

IS

VI

LL

E

D

IS

TR

IC

T

D

R M

AR

TI

N L

U

TH

ER

K

IN

G

J R

P

LA

C E

LO

U

IS

VI

LL

E, K Y

WEST

JA

N

C

ER

TI

FI

ED

F

IN

AL

FT

. M cC O

Y, W

I C

O

LL

EC

TI

VE

T

R

AI

N

IN

G O

FF

IC

ER

S

Q U

AR

TE

R S

(W

ES

T)

PN

F

Y2

2, P

VO

LU

M E

0F

Fi le

P at h:

Pl ot D at e:

C :\U se rs

\h 2e dd ra h\ D oc um en ts

\5

9_

R ev it2

0_ A_

TT

O

Q _h

2e dd ra h.

rv t

4/

/2

9:

:1

AM

A-412

ST

AI

R D

ET

AI

LS

M .J

O H

N

SO

N

B.

AL

LE

N

M .B

AR

R

Y

6" = 1'-0"E15 TYP. WALL HANDRAIL TERMINATION

3/4" = 1'-0"K15 TYPICAL HANDRAIL - MOUNTING

6" = 1'-0"A15 TYPICAL WALL HANDRAIL - MOUNTING

3/4" = 1'-0"E1 STAIR TRANSVERSE SECTION DET .

1" = 1'-0"A1 STAIR GUARDRAIL DET. @ MEZZ (TYP.)

3/4" = 1'-0"A6 STAIR SECTION - LANDING ( TYP. )

3/4" = 1'-0"K11 STAIR SECTION ( TYP. )

3/4" = 1'-0"E11 STAIR SECTION - 1st. FL. ( TYP. )

3" = 1'-0"A11 STAIR HANDRAIL & GUARDRAIL (TYP.)

1 1/2" = 1'-0"K1 STAIR WALL DETAIL

1 1/2" = 1'-0"E6 STAIR SECTION - LANDING ( 6" S.S. )

AM

EN

D

M

EN

T

AP

R

11 1

W

2Q R

R

_P la ns _V ol 2-

ARIMS: 200A Disposition: Maintain for 15 yrs after construction.

METAL STUD

METAL STUD

SCREWDRIVER

CAM LOCK

5/8" CEILING

DRYWALL

5/8" CEILING

DRYWALL

PIN HINGE

2 FEET

1 1/4"

5/

8"

1" 1"

3/

4"

SEALANT

HOLLOW

METAL DOOR

FRAME

SEALANT

JAMB

ANCHORS, 3

PER SIDE

(2) 2x12 P.T. WOOD

BLOCKING

AIR SPACE

RIGID

INSULATION

1/2" EXTERIOR

SHEATHING

SPRAY

POLYURETHANE

FOAM (SPF)

INSULATION, SEE

SHT. A-311.

6" STEEL STUD

@ 16" O.C.

5/8" GYPSUM

BOARD

CORNER BEAD

1/2"x5" LAG BOLT

OPEN BAR BRACKET

STEEL TUBE PER DTL 18 THIS SHEET

VAPOR AIR

BARRIER

UTILITY BRICK 1/3

BOND COURSING WITH

WALL TIES @ 16" O.C.

1' -3

2"

3"

3"

KEEP

CLEAR

KEEP

CLEAR

4" SAFETY

YELLOW STRIP

G10 A-507

Sim

KEEP

CLEAR

KEEP

CLEAR

6" SAFETY

YELLOW STRIP

A1 A-301

A-507 A1

3' -6

7'-4"

6"

H

EQ EQ

OPEN BAR BRACKET

ATTACHED WITH #10

SELF TAPPING TEK

SCREW INTO WALL

BLOCKING

HHS 1-1/2" x 3" x 3/16" STEEL TUBE WITH 1/2" DIA. x 1" LONG

THREADED BOLT WITH LOCK

WASHER EACH SIDE INTO TAPPED

AND THREADED HOLE IN STEEL

TUBE.

3' -6

3"

1' -6

3"

(3) SELF TAPPING

TEK SCREWS #10

@ 1-1/2" LONG

DOOR

STEEL TUBE

42" A.F.F

TOP

RAILOPEN BAR

BRACKET

1/2" THREADED BOLT

W/LOCK WASHER INTO

TAPPED AND THREADED

HOLE IN HHS.

WALL

NO

EXIT

NO

EXIT

CONTRACTOR TO

PROVIDE 'NO EXIT'

SIGNAGE AS SHOWN

CONTRACTOR TO

PROVIDE 'NO EXIT'

SIGNAGE AS SHOWN

PHOTOGRAPHIC EXAMPLE AS

EXECUTED ON FY19 AND FY20

BARRACKS - PROVIDE SIMILAR

* POWDER COAT ENTIRE BIKE CANOPY DARK BRONZE, SEE SPECIFICATIONS

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

LO

U

IS

VI

LL

E

D

IS

TR

IC

T

D

R M

AR

TI

N L

U

TH

ER

K

IN

G

J R

P

LA

C E

LO

U

IS

VI

LL

E, K Y

WEST

JA

N

C

ER

TI

FI

ED

F

IN

AL

FT

. M cC O

Y, W

I C

O

LL

EC

TI

VE

T

R

AI

N

IN

G O

FF

IC

ER

S

Q U

AR

TE

R S

(W

ES

T)

PN

F

Y2

2, P

VO

LU

M E

0F

Fi le

P at h:

Pl ot D at e:

C :\U se rs

\h 2e dd ra h\ D oc um en ts

\5

9_

R ev it2

0_ A_

TT

O

Q _h

2e dd ra h.

rv t

4/

/2

9:

:4

AM

A-507

M

IS

C

EL

LA

N

EO

U

S D

ET

AI

LS

M .J

O H

N

SO

N

B.

AL

LE

N

M .B

AR

R

Y

12" = 1'-0"A10 CEILING ACCESS DOOR - SHOWER/LATRINE/LAUNDRY

3" = 1'-0"A1 MECHANICAL ROOM DOOR JAMB DETAIL

3/4" = 1'-0"G1 MECHANICAL ROOM FLOOR STRIPING PLAN

3/4" = 1'-0"G10 EXTERIOR MECH DOOR DETAIL

N.T.S.E15 BIKE CANOPY DETAIL

AM

EN

D

M

EN

T

AP

R

W

2Q R

R

_P la ns _V ol 2-

#3/0

#3/0

#6

DM

SPD

65KAGROUND BAR,

IN ENCLOSURE

R

AT

IN

G

P

ER

M

AN

U

FA

C

TU

R

ER

EXTERNAL

GROUND

SYSTEM

BUILDING

STEEL

TMGB ON TER

(RM 125)

BACKBOARD

MAIN

1200AF/1200AT/3P

100% RATED

WITH LSIG

PROTECTION

0A

F/

5A T/

3P

BUILDING MAIN SWITCHBOARD (MSB), 1200A, 480/277V, 3 PHASE, WITH FULL NEUTRAL & GROUND BUSES

FUSE

480 V 3O

REFERENCE TABLE

OF RESPONSIBILITY

ON SHEET ES503

FOR TRANSFORMER/

SCC INSTALLATION

SCOPE OF WORK

MSB-MAIN MSB-DIST

FUSED

CUTOUT

MTR-1

0A

F/

5A T/

3P

3 4 5 6

0A

F/

0A T/

3P

PANEL

PL-101

PANEL

PL-102

#6

T-1 112.5 KVA

PANEL

PL-201

#6

T-2 112.5 KVA

PANEL

PL-301

#6

T-3 112.5 KVA

PANEL

PL-401

#6

T-4 112.5 KVA

PANEL

MH-101

0A

F/

5A T/

3P 25 0A

F/

5A T/

3P 80 0A

F/

0A T/

3P 40 0A

F/

5A T/

3P

ELEV

CNTLR

EL

EV

AT

O

R

PANEL

PL-103

PANEL

PL-203

PANEL

PL-303

PANEL

PL-403

PANEL

PL-202

PANEL

PL-302

PANEL

PL-402

PANEL

PT-101

PANEL

PT-201

PANEL

PT-301

PANEL

PT-401

GENERAL NOTES

1. THE CONTRACTOR SHALL PROVIDE ALL EQUIPMENT, DEVICES,

APPURTENANCES, ETC. TO COMPLY WITH THE ELECTRICAL

ENERGY METERING REQUIREMENTS OF ASHRAE 90.1,

PARAGRAPH 8.4.3 IN ORDER TO MONITOR, RECORD, & REPORT

EACH OF THE FOLLOWING CATEGORIES INDEPENDENTLY:

A. TOTAL ELECTRICAL ENERGY

B. HVAC SYSTEMS

C. INTERIOR LIGHTING

D. EXTERIOR LIGHTING

E. RECEPTACLE CIRCUITS

2. FAULT CURRENT AMP INTERRUPTING CAPACITIES ARE

MINIMUM. IF STANDARD EQUIPMENT RATING IS GREATER,

PROVIDE STANDARD RATING.

3. PROVIDE FULL LENGTH 100% RATED NEUTRAL BAR AND A

GROUNDING BAR IN EACH SECTION OF THE

SWITCHBOARD/PANELBOARDS. PROVIDE MAIN BONDING

JUMPER IN ACCORDANCE WITH NFPA 70 PARAGRAPH 250.24

(B).

4. SEE SHEETS E-602 THRU E-607 FOR PANEL SCHEDULES.

5. PROVIDE ADDITIONAL SPARES AND SPACES AS SHOWN ON

PANEL SCHEDULES.

6. PROVIDE SURGE PROTECTION FOR EITHER THE CIRCUIT OR

THE PANEL THE CIRCUIT IS CONNECTED TO FOR ALL CIRCUITS

EXITING THE BUILDING SUCH AS BUT NOT LIMITED TO

EXTERIOR LIGHTING, EXTERIOR HVAC EQUIPMENT, AND CATV

EQUIPMENT CIRCUITS. ALSO PROVIDE SURGE PROTECTION

FOR ALL LIGHTING PANELS FEEDING BRANCH CIRCUITS WITH

LED FIXTURES. NOT ALL REQUIRED SURGE PROTECTIVE

DEVICES (SPDS) ARE SHOWN IN PANEL SCHEDULES. SPDS

MAY BE REQUIRED IN ADDITIONAL LOCATIONS BASED ON

FINAL EQUIPMENT INSTALLED AND ITS LOCATION. SURGE

PROTECTIVE DEVICES SHALL BE FED BY A DEDICATED

BREAKER AND INSTALLED EXTERNAL TO PANELBOARDS IN A

SEPARATE ENCLOSURE AND EXTERNAL TO SWITCHBOARD

OR IN A SEPARATE METAL CLAD COMPARTMENT OF THE

SWITCHBOARD.

7. VERIFY AND CHANGE AS NECESSARY THE CIRCUIT BREAKER

RATING, FEEDER, AND CONDUIT SIZES FOR ACTUAL

EQUIPMENT INSTALLED.

8. THE CONTRACTOR SHALL SUBMIT ARC FLASH HAZARD

ANALYSIS BASED ON INSTALLED CONDUIT AND CONDUCTOR

SIZE, TYPE AND LENGTH, EQUIPMENT SIZINGS, RATINGS,

ARRANGEMENTS, AND SETTINGS. SUBMIT AS PART OF

THE FAULT CURRENT AND PROTECTIVE COORDINATION

STUDY ALONG WITH THE SYSTEM MODEL. CONTRACTOR

SHALL PROVIDE ARC FLASH LABELS ON ALL PANELS

INDICATING THE ARC FLASH HAZARD LEVEL BASED ON THE

RESULTS FROM THE ARC FLASH HAZARD ANALYSIS. ADJUST

AIC RATINGS OF EQUIPMENT REQUIRED BASED ON ACTUAL

EQUIPMENT RATINGS.

9. SERIES RATED AND PLUG-IN CIRCUIT BREAKERS ARE

PROHIBITED.

10. PROVIDE ARC FLASH WARNING SIGNS ON SWITCHBOARDS,

PANELBOARDS, INDUSTRIAL CONTROL PANELS, METER

SOCKET ENCLOSURES, AND MOTOR CONTROL CENTERS AS

REQUIRED PER NFPA 70 (NEC) ARTICLE 110.16. REFERENCE

NFPA 70 ARTICLE 110.16, NFPA 70E ARTICLE 130.3, AND UFC

3-560-01, ELECTRICAL SAFETY, O & M.

11. PROVIDE ELECTRONIC TRIP BREAKERS WITH LSI SETTINGS

FOR ALL SWITCHBOARD/PANELBOARD BREAKERS SERVING

SUB-PANELS.

12. ELEVATOR CIRCUIT BREAKER DISCONNECT SHALL BE

PROVIDED WITH INTEGRAL SHUNT TRIP AND FIRE ALARM

INTERFACE.

#6

T-5 112.5 KVA

PANEL

ML-101

PANEL

ML-201

PANEL

ML-401

PANEL

MH-401

PANEL

PH-101

PANEL

PH-301

1 1 1 1 2 32

SU

BM

ET

ER

IN

G

3P

8 US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

Fi le

P at h:

Pl ot D at e:

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

LO

U

IS

VI

LL

E

D

IS

TR

IC

T

D

R M

AR

TI

N L

U

TH

ER

K

IN

G

J R

P

LA

C E

LO

U

IS

VI

LL

E, K Y

WEST

JA

N

C

ER

TI

FI

ED

F

IN

AL

FT

. M cC O

Y, W

I C

O

LL

EC

TI

VE

T

R

AI

N

IN

G O

FF

IC

ER

S

Q U

AR

TE

R S

W

ES

T

PN

F

Y2

2, P

VO

LU

M E

0F

C :\U se rs

\H 2E

D D

JM

9\

D oc um en ts \5

9_ R ev it2

0_

E_

TT

O Q

_H 2E

D D

JM

9.

rv t

3/

/2

2:

:3

PM

E-601

O N

E-

LI

N E

D

IA

G R

AM

S

AN

D

P

AN

EL

S

C H

ED

U

LE

S

J.

M

O O

R E

J.

M

O O

R E

M .L

AW

R

EN

C

E

12" = 1'-0"1

ELECTRICAL ONE-LINE DIAGRAM AND

MECHANICAL FEEDER SCHEDULE

KEY NOTES

1 PROVIDE ELECTRONIC MAIN BREAKER WITH METERING

INFORMATION OUTPUT TO THE SUBMETERING SYSTEM

FOR RECEPTACLE LOADS.

2 PROVIDE ELECTRONIC MAIN BREAKER WITH METERING

INFORMATION OUTPUT TO THE SUBMETERING SYSTEM

FOR HVAC/MECHANICAL LOADS.

3 PROVIDE ELECTRONIC MAIN BREAKER WITH METERING

INFORMATION OUTPUT TO THE SUBMETERING SYSTEM

FOR LIGHTING LOADS.

4 CURRENTLY, FT. MCCOY HAS NO EBCS AND THUS ALL

METERING IS CURRENTLY ONLY REPORTED TO MDMS -

EEDRS THROUGH FT. MCCOY NEC INFRASTRUCTURE AND

TRIDIUM NIAGARA BUILDING POINT OF CONNECTION

(BPOC).

5 IF SOLAR OPTION IS SELECTED, INSTALL/CONNECT SOLAR

PV SYSTEM WITH SUPPLY-SIDE SOURCE CONNECTION

PER NEC 705.11 AND IN ACCORDANCE WITH

EXCEL/WISCONSIN GRID CONNECTION REQUIREMENTS.

CONNECTION TO BE MADE OUTSIDE BUILDING (AT

METER/SCC) AS REQUIRED AND/OR PERMITTED BY XCEL.

REFERENCE SITE PLAN ES101 AND SPECS FOR ARRAY

LOCATION AND REQUIREMENTS.

ONE-LINE FEEDER SCHEDULE

Notes Panel Load Voltage Wire Size Conduit

Size

T-2 PL-201 208 V 2 runs of 3-#3/0, 1-#3/0, 1-#3

2 1/2"

T-3 PL-301 208 V 2 runs of 3-#3/0, 1-#3/0, 1-#3

2 1/2"

T-4 PL-401 208 V 2 runs of 3-#3/0, 1-#3/0, 1-#3

2 1/2"

T-5 ML101 208 V 2 runs of 3-#3/0, 1-#3/0, 1-#3

2 1/2"

ML-101 ML-201 208 V 3-#3, 1-#3, 1-#8 1 1/2"

ML-101 ML-401 208 V 3-#3, 1-#3, 1-#8 1 1/2"

PH-101 PH-301 480 V 3-#6, 1-#6, 1-#10 1 1/2"

PL-101 1st Floor Quarters Receptacle Panel PL-102 208 V 3-#3, 1-#3, 1-#8 1 1/2" PL-101 Telecom Room Panel PT-101 208 V 3-#3, 1-#3, 1-#8 1 1/2" PL-201 2nd Floor Quarters Receptacle Panel PL-202 208 V 3-#3, 1-#3, 1-#8 1 1/2" PL-201 Telecom Room Panel PT-201 208 V 3-#3, 1-#3, 1-#8 1 1/2" PL-301 3rd Floor Quarters Receptacle Panel PL-302 208 V 3-#3, 1-#3, 1-#8 1 1/2" PL-301 Telecom Room Panel PT-301 208 V 3-#3, 1-#3, 1-#8 1 1/2" PL-401 4th Floor Quarters Receptacle Panel PL-402 208 V 3-#3, 1-#3, 1-#8 1 1/2" PL-401 Telecom Room Panel PT-401 208 V 3-#3, 1-#3, 1-#8 1 1/2"

ONE-LINE FEEDER SCHEDULE

Notes Panel Load Voltage Wire Size Conduit

Size

From Service Transformer Secondary

MSB-MAIN Entire TTOQ Building 480 V 4 runs of 3-#350, 1-#350, 1-#3/0

5"

MSB-DIST MH-101 480 V 3 runs of 3-#300, 1-#300, 1-#1/0

3 1/2"

MH-101 T-5 480 V 3-#2/0, 1-#2/0, 1-#6 2 1/2"

MH-101 MH-401 480 V 3-#1, 1-#1, 1-#6 2 1/2"

MSB-DIST T-1 480 V 3-#2/0, 1-#2/0, 1-#6 2 1/2"

MSB-DIST T-2 480 V 3-#2/0, 1-#2/0, 1-#6 2 1/2"

MSB-DIST T-3 480 V 3-#2/0, 1-#2/0, 1-#6 2 1/2"

MSB-DIST PH-101 480 V 3-#4/0, 1-#4/0, 1-#4 2 1/2"

MSB-DIST T-4 480 V 3-#2/0, 1-#2/0, 1-#6 2 1/2"

PL-101 1st Floor Laundry Panel PL-103 208 V 3-#4/0, 1-#4/0, 1-#4 2 1/2" PL-201 2nd Floor Laundry Panel PL-203 208 V 3-#4/0, 1-#4/0, 1-#4 2 1/2" PL-301 3rd Floor Laundry Panel PL-303 208 V 3-#4/0, 1-#4/0, 1-#4 2 1/2" PL-401 4th Floor Laundry Panel PL-403 208 V 3-#4/0, 1-#4/0, 1-#4 2 1/2"

T-1 PL-101 208 V 2 runs of 3-#3/0, 1-#3/0, 1-#3

2 1/2"

AM

EN

D

M

EN

T

AP

R

W

2Q R

R

_P la ns _V ol 2-

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

Fi le

P at h:

Pl ot D at e:

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

LO

U

IS

VI

LL

E

D

IS

TR

IC

T

D

R M

AR

TI

N L

U

TH

ER

K

IN

G

J R

P

LA

C E

LO

U

IS

VI

LL

E, K Y

WEST

JA

N

C

ER

TI

FI

ED

F

IN

AL

FT

. M cC O

Y, W

I C

O

LL

EC

TI

VE

T

R

AI

N

IN

G O

FF

IC

ER

S

Q U

AR

TE

R S

W

ES

T

PN

F

Y2

2, P

VO

LU

M E

0F

C :\U se rs

\H 2E

D D

JM

9\

D oc um en ts \5

9_ R ev it2

0_

E_

TT

O Q

_H 2E

D D

JM

9.

rv t

3/

/2

2:

:4

PM

E-602

PA

N

EL

S

C H

ED

U

LE

S

J.

M

O O

R E

J.

M

O O

R E

M .L

AW

R

EN

C

E

Notes: PROVIDE COMBINATION-TYPE AFCI PROTECTION FOR BRANCH CIRCUITS SUPPLYING RECEPTACLES IN SLEEPING QUARTERS, HALLWAYS, AND RESTROOMS.

Total Est. Demand Current: 177 A Total Conn. Current: 243 A

Total Est. Demand: 63797 VA RCPT 30288 VA 20144 VA Total Conn. Load: 87620 VA Receptacle 37400 VA 23700 VA Load Classification Connected Load Estimated Demand Panel Totals

Total Amps: 276 A 222 A 236 A Total Load: 32936 VA 26583 VA 28103 VA

41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42

39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40

37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38

35 SPARE 20 A 1 1000... 0 VA -- -- SPACE 36

33 SPACE -- -- 0 VA 0 VA -- -- SPACE 34

31 SPACE -- -- 0 VA 1000... 1 20 A SPARE 32

29 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 30

27 1st Floor Corridor Rec. 20 A 1 360 VA 1000... 1 20 A SPARE 28 25 1st Floor Corridor/N. Stair Rec. 20 A 1 720 VA 540 VA 1 20 A 1st Floor Corridor/NE Exterior Rec. 26 23 1st Floor Janitor/South Hall Rec. 20 A 1 900 VA 360 VA 1 20 A 1st Floor Stairway Receptacles 24 21 Vestibule/ Company Storage Unswitched Rec. 20 A 1 720 VA 900 VA 1 20 A 1st Floor Company Storage, Switched Rec. 22 19 1st Floor Company Storage Counter Top Rec. 20 A 1 360 VA 720 VA 1 20 A 1st Floor Mechanical Room Receptacles 20 17 1st Floor Company Storage Vending... 20 A 1 180 VA 180 VA 1 20 A 1st Floor Company Storage Refrigerator Rec. 18 15 1st Floor Company Storage Vending... 20 A 1 180 VA 180 VA 1 20 A 1st Floor Company Storage Vending... 16

13 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 14

11 3080... 180 VA 1 20 A Elevator Pit Sump Pump Receptacle 12 9 4220... 720 VA 1 20 A Elevator Pit Receptacles 10

Telecom Room Panel PT-101 100 A 3 4220... 360 VA 1 20 A 1st Floor Electrical Room Receptacles 8

5 9020... 1121... 6 3 7760... 1055... 4

1st Floor Quarters Receptacle Panel PL-102 100 A 3 9200... 1384...

3 225 A 1st Floor Laundry Panel PL-103

CKT Load Name Trip Poles A B C Poles Trip Load Name CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 400 A Mounting: SURFACE Wires: 4 Mains Rating: 400 A

Supply From: T-1 Phases: 3 Mains Type: MAIN CB Location: ELECTRICAL 127 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: PL-101

Notes: PROVIDE COMBINATION-TYPE AFCI PROTECTION FOR BRANCH CIRCUITS SUPPLYING RECEPTACLES IN SLEEPING QUARTERS, HALLWAYS, AND RESTROOMS.

Total Est. Demand Current: 56 A

Total Conn. Current: 72 A Total Est. Demand: 20090 VA Total Conn. Load: 25980 VA

Receptacle 21780 VA 15890 VA Load Classification Connected Load Estimated Demand Panel Totals

Total Amps: 78 A 65 A 77 A Total Load: 9200 VA 7760 VA 9020 VA

41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42

39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40

37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38

35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36

33 SPACE -- -- 0 VA 0 VA -- -- SPACE 34

31 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 32

29 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 30

27 1st Floor Water Fountain 20 A 1 100 VA 100 VA 1 20 A 1st Floor Water Fountain 28 25 Room 121 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 121 Receptacles 26 23 Room 122 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 122 Receptacles 24 21 Room 120 Receptacles 20 A 1 540 VA 1080... 1 20 A Room 119 Receptacles 22 19 NW Exterior/WP Receptacle 20 A 1 180 VA 540 VA 1 20 A Room 120 Receptacles 20 17 Room 118 Receptacles 20 A 1 540 VA 1080... 1 20 A Room 117 Receptacles 18 15 Room 115 Receptacles 20 A 1 1080... 540 VA 1 20 A Room 118 Receptacles 16 13 Room 114 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 114 Receptacles 14 11 Room 112 Receptacles 20 A 1 1080... 1080... 1 20 A Room 113 Receptacles 12 9 Room 110 Receptacles 20 A 1 1080... 1080... 1 20 A Room 111 Receptacles 10 7 Room 108 Receptacles 20 A 1 1080... 1080... 1 20 A Room 109 Receptacles 8 5 Room 106 Receptacles 20 A 1 1080... 1080... 1 20 A Room 107 Receptacles 6 3 Room 104 Receptacles 20 A 1 1080... 1080... 1 20 A Room 105 Receptacles 4 1 Room 102 Receptacles 20 A 1 1080... 1080... 1 20 A Room 103 Receptacles 2

CKT Load Name Trip Poles A B C Poles Trip Load Name CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 100 A Mounting: SURFACE Wires: 4 Mains Rating: 100 A

Supply From: PL-101 Phases: 3 Mains Type: MAIN CB Location: ELECTRICAL 127 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: PL-102

RCPT Designates Dryer Load Notes:

Total Est. Demand: 71 A Total Conn.: 99 A

RCPT 30288 VA 66.51% 20144 VA Total Est. Demand: 25470 VA Spare 4800 VA 100.00% 4800 VA Total Conn. Load: 35613 VA Receptacle 540 VA 100.00% 540 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 116 A 88 A 94 A Total Load: 13849 VA 10555 VA 11214 VA

23 SPACE -- -- 0 VA 0 VA -- -- SPACE 24

21 SPACE -- -- 0 VA 0 VA -- -- SPACE 22

19 SPARE 20 A 1 1200... 0 VA -- -- SPACE 20

17 SPARE 20 A 1 1200... 1200... 1 20 A SPARE 18

15 1st Floor Laundry-Washer (RCPT) 20 A 1 1440... 1200... 1 20 A SPARE 16 13 1st Floor Laundry-Washer (RCPT) 20 A 1 1440... 1440... 1 20 A 1st Floor Laundry-Washer (RCPT) 14 11 2500... 1440... 1 20 A 1st Floor Laundry-Washer (RCPT) 12

1st Floor Laundry-Dryer (RCPT) 35 A 2 2500... 540 VA 1 20 A GP Receptacles 10

7 2500... 2500... 8

1st Floor Laundry-Dryer (RCPT) 35 A 2 2500... 2500...

2 35 A 1st Floor Laundry-Dryer (RCPT)

3 2500... 2500... 4

1st Floor Laundry-Dryer (RCPT) 35 A 2 2500... 2500...

2 35 A 1st Floor Laundry-Dryer (RCPT)

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 225 A Mounting: SURFACE Wires: 4 Mains Rating: 225 A

Supply From: PL-101 Phases: 3 Mains Type: MAIN CB Location: LAUNDRY 126 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: PL-103

Notes:

Total Est. Demand: 32 A Total Conn.: 32 A

Total Est. Demand: 11520 VA Spare 4000 VA 100.00% 4000 VA Total Conn. Load: 11520 VA Receptacle 7520 VA 100.00% 7520 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 37 A 37 A 26 A Total Load: 4220 VA 4220 VA 3080 VA

23 SPACE -- -- 0 VA 0 VA -- -- SPACE 24

21 SPACE -- -- 0 VA 0 VA -- -- SPACE 22

19 SPACE -- -- 0 VA 0 VA -- -- SPACE 20

17 SPACE -- -- 0 VA 0 VA -- -- SPACE 18

15 SPACE -- -- 0 VA 0 VA -- -- SPACE 16

13 SPACE -- -- 0 VA 0 VA -- -- SPACE 14

11 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 12

9 2500... 1000... 1 20 A SPARE 10

208V - NEMA L6-20R Receptacle 20 A 2

2500... 1000... 1 20 A SPARE 8

5 NE Receptacles 20 A 1 540 VA 540 VA 1 20 A SW Receptacles 6 3 #2 Rack Receptacle 20 A 1 360 VA 360 VA 1 20 A #2 Rack Receptacle 4 1 #1 Rack Receptacle 20 A 1 360 VA 360 VA 1 20 A #1 Rack Receptacle 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 100 A Mounting: SURFACE Wires: 4 Mains Rating: 100 A

Supply From: PL-101 Phases: 3 Mains Type: MAIN CB Location: TELECOM 125 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: PT-101

AM

EN

D

M

EN

T

AP

R

W

2Q R

R

_P la ns _V ol 2-

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

Fi le

P at h:

Pl ot D at e:

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

LO

U

IS

VI

LL

E

D

IS

TR

IC

T

D

R M

AR

TI

N L

U

TH

ER

K

IN

G

J R

P

LA

C E

LO

U

IS

VI

LL

E, K Y

WEST

JA

N

C

ER

TI

FI

ED

F

IN

AL

FT

. M cC O

Y, W

I C

O

LL

EC

TI

VE

T

R

AI

N

IN

G O

FF

IC

ER

S

Q U

AR

TE

R S

W

ES

T

PN

F

Y2

2, P

VO

LU

M E

0F

C :\U se rs

\H 2E

D D

JM

9\

D oc um en ts \5

9_ R ev it2

0_

E_

TT

O Q

_H 2E

D D

JM

9.

rv t

3/

/2

2:

:5

PM

E-603

PA

N

EL

S

C H

ED

U

LE

S

J.

M

O O

R E

J.

M

O O

R E

M .L

AW

R

EN

C

E

Notes: PROVIDE COMBINATION-TYPE AFCI PROTECTION FOR BRANCH CIRCUITS SUPPLYING RECEPTACLES IN SLEEPING QUARTERS, HALLWAYS, AND RESTROOMS.

Total Est. Demand Current: 171 A

Total Conn. Current: 229 A Total Est. Demand: 61777 VA

RCPT 30288 VA 20144 VA Total Conn. Load: 82382 VA Receptacle 30960 VA 20480 VA Load Classification Connected Load Estimated Demand Panel Totals

Total Amps: 255 A 224 A 212 A Total Load: 30358 VA 26643 VA 25384 VA

41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42

39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40

37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38

35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36

33 SPACE -- -- 0 VA 0 VA -- -- SPACE 34

31 SPACE -- -- 0 VA 0 VA -- -- SPACE 32

29 SPARE 20 A 1 1000... 0 VA -- -- SPACE 30

27 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 28

25 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 26

23 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 24

21 2nd Floor Corridor Rec. 20 A 1 360 VA 540 VA 1 20 A 2nd Floor Corridor/N. Stair Rec. 22 19 2nd Floor Company Storage Vending Rec. 20 A 1 180 VA 360 VA 1 20 A 2nd Floor Corridor Rec. 20 17 2nd Floor Company Storage Vending Rec. 20 A 1 180 VA 180 VA 1 20 A 2nd Floor Company Storage Vending Rec. 18 15 2nd Floor Company Storage Counter Top Rec. 20 A 1 360 VA 180 VA 1 20 A 2nd Floor Company Storage Refrigerator Rec. 16 13 2nd Floor Stairway Receptacles 20 A 1 900 VA 900 VA 1 20 A 2nd Floor Company Storage, Switched Rec. 14 11 1080... 720 VA 1 20 A 2nd Floor Mechanical Room Receptacles 12 9 2720... 1260... 1 20 A 2nd Floor Janitor/Recycle/South Hall Rec. 10

Telecom Room Panel PT-201 100 A 3 2720... 360 VA 1 20 A 2nd Floor Electrical Room Receptacles 8

5 9020... 1121... 6 3 8860... 1037... 4

2nd Floor Quarters Receptacle Panel PL-202 100 A 3 9120... 1384...

3 225 A 2nd Floor Laundry Panel PL-203

CKT Load Name Trip Poles A B C Poles Trip Load Name CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 400 A Mounting: SURFACE Wires: 4 Mains Rating: 400 A

Supply From: T-2 Phases: 3 Mains Type: MAIN CB Location: ELECTRICAL 227 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: PL-201

Notes: PROVIDE COMBINATION-TYPE AFCI PROTECTION FOR BRANCH CIRCUITS SUPPLYING RECEPTACLES IN SLEEPING QUARTERS, HALLWAYS, AND RESTROOMS.

Total Est. Demand Current: 59 A

Total Conn. Current: 75 A Total Est. Demand: 21200 VA Total Conn. Load: 27000 VA

Receptacle 21600 VA 15800 VA Load Classification Connected Load Estimated Demand Panel Totals

Total Amps: 76 A 74 A 75 A Total Load: 9120 VA 8860 VA 9020 VA

41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42

39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40

37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38

35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36

33 SPACE -- -- 0 VA 0 VA -- -- SPACE 34

31 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 32

29 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 30

27 2nd Floor FA/MN Booster Panels 20 A 1 1200... 100 VA 1 20 A 2nd Floor Water Fountain 28 25 Room 221 Receptacles 20 A 1 540 VA 100 VA 1 20 A 2nd Floor Water Fountain 26 23 Room 220 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 221 Receptacles 24 21 Room 219 Receptacles 20 A 1 1080... 540 VA 1 20 A Room 220 Receptacles 22 19 Room 218 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 218 Receptacles 20 17 Room 216 Receptacles 20 A 1 540 VA 1080... 1 20 A Room 217 Receptacles 18 15 Room 215 Receptacles 20 A 1 1080... 540 VA 1 20 A Room 216 Receptacles 16 13 Room 214 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 214 Receptacles 14 11 Room 212 Receptacles 20 A 1 1080... 1080... 1 20 A Room 213 Receptacles 12 9 Room 210 Receptacles 20 A 1 1080... 1080... 1 20 A Room 211 Receptacles 10 7 Room 208 Receptacles 20 A 1 1080... 1080... 1 20 A Room 209 Receptacles 8 5 Room 206 Receptacles 20 A 1 1080... 1080... 1 20 A Room 207 Receptacles 6 3 Room 204 Receptacles 20 A 1 1080... 1080... 1 20 A Room 205 Receptacles 4 1 Room 202 Receptacles 20 A 1 1080... 1080... 1 20 A Room 203 Receptacles 2

CKT Load Name Trip Poles A B C Poles Trip Load Name CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 100 A Mounting: SURFACE Wires: 4 Mains Rating: 100 A

Supply From: PL-201 Phases: 3 Mains Type: MAIN CB Location: ELECTRICAL 127 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: PL-202

RCPT Designates Dryer Load Notes:

Total Est. Demand: 70 A Total Conn.: 98 A

RCPT 30288 VA 66.51% 20144 VA Total Est. Demand: 25290 VA Spare 4800 VA 100.00% 4800 VA Total Conn. Load: 35433 VA Receptacle 360 VA 100.00% 360 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 116 A 86 A 95 A Total Load: 13849 VA 10375 VA 11214 VA

23 SPACE -- -- 0 VA 0 VA -- -- SPACE 24

21 SPACE -- -- 0 VA 0 VA -- -- SPACE 22

19 SPARE 20 A 1 1200... 0 VA -- -- SPACE 20

17 SPARE 20 A 1 1200... 1200... 1 20 A SPARE 18

15 2nd Floor Laundry-Washer (RCPT) 20 A 1 1440... 1200... 1 20 A SPARE 16 13 2nd Floor Laundry-Washer (RCPT) 20 A 1 1440... 1440... 1 20 A 2nd Floor Laundry-Washer (RCPT) 14 11 2500... 1440... 1 20 A 2nd Floor Laundry-Washer (RCPT) 12

2nd Floor Laundry-Dryer (RCPT) 35 A 2 2500... 360 VA 1 20 A GP Receptacles 10

7 2500... 2500... 8

2nd Floor Laundry-Dryer (RCPT) 35 A 2 2500... 2500...

2 35 A 2nd Floor Laundry-Dryer (RCPT)

3 2500... 2500... 4

2nd Floor Laundry-Dryer (RCPT) 35 A 2 2500... 2500...

2 35 A 2nd Floor Laundry-Dryer (RCPT)

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 225 A Mounting: SURFACE Wires: 4 Mains Rating: 225 A

Supply From: PL-201 Phases: 3 Mains Type: MAIN CB Location: LAUNDRY 226 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: PL-203

Notes:

Total Est. Demand: 18 A Total Conn.: 18 A

Total Est. Demand: 6520 VA Spare 4000 VA 100.00% 4000 VA Total Conn. Load: 6520 VA Receptacle 2520 VA 100.00% 2520 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 25 A 25 A 9 A Total Load: 2720 VA 2720 VA 1080 VA

23 SPACE -- -- 0 VA 0 VA -- -- SPACE 24

21 SPACE -- -- 0 VA 0 VA -- -- SPACE 22

19 SPACE -- -- 0 VA 0 VA -- -- SPACE 20

17 SPACE -- -- 0 VA 0 VA -- -- SPACE 18

15 SPACE -- -- 0 VA 0 VA -- -- SPACE 16

13 SPACE -- -- 0 VA 0 VA -- -- SPACE 14

11 SPACE -- -- 0 VA 0 VA -- -- SPACE 12

9 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 10

7 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 8

5 NE Receptacles 20 A 1 540 VA 540 VA 1 20 A SW Receptacles 6 3 #2 Rack Receptacle 20 A 1 360 VA 360 VA 1 20 A #2 Rack Receptacle 4 1 #1 Rack Receptacle 20 A 1 360 VA 360 VA 1 20 A #1 Rack Receptacle 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 100 A Mounting: SURFACE Wires: 4 Mains Rating: 100 A

Supply From: PL-201 Phases: 3 Mains Type: MAIN CB Location: TELECOM 125 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: PT-201

AM

EN

D

M

EN

T

AP

R

1 1

W

2Q R

R

_P la ns _V ol 2-

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

Fi le

P at h:

Pl ot D at e:

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

LO

U

IS

VI

LL

E

D

IS

TR

IC

T

D

R M

AR

TI

N L

U

TH

ER

K

IN

G

J R

P

LA

C E

LO

U

IS

VI

LL

E, K Y

WEST

JA

N

C

ER

TI

FI

ED

F

IN

AL

FT

. M cC O

Y, W

I C

O

LL

EC

TI

VE

T

R

AI

N

IN

G O

FF

IC

ER

S

Q U

AR

TE

R S

W

ES

T

PN

F

Y2

2, P

VO

LU

M E

0F

C :\U se rs

\H 2E

D D

JM

9\

D oc um en ts \5

9_ R ev it2

0_

E_

TT

O Q

_H 2E

D D

JM

9.

rv t

3/

/2

2:

:5

PM

E-604

PA

N

EL

S

C H

ED

U

LE

S

J.

M

O O

R E

J.

M

O O

R E

M .L

AW

R

EN

C

E

Notes: PROVIDE COMBINATION-TYPE AFCI PROTECTION FOR BRANCH CIRCUITS SUPPLYING RECEPTACLES IN SLEEPING QUARTERS, HALLWAYS, AND RESTROOMS.

Total Est. Demand Current: 171 A

Total Conn. Current: 229 A Total Est. Demand: 61777 VA

RCPT 30288 VA 20144 VA Total Conn. Load: 82382 VA Receptacle 30960 VA 20480 VA Load Classification Connected Load Estimated Demand Panel Totals

Total Amps: 261 A 215 A 212 A Total Load: 31257 VA 25744 VA 25384 VA

41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42

39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40

37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38

35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36

33 SPACE -- -- 0 VA 0 VA -- -- SPACE 34

31 SPACE -- -- 0 VA 0 VA -- -- SPACE 32

29 SPARE 20 A 1 1000... 0 VA -- -- SPACE 30

27 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 28

25 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 26

23 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 24

21 3rd Floor Corridor Receptacles 20 A 1 360 VA 540 VA 1 20 A 3rd Floor Corridor/N. Stair Rec. 22 19 3rd Floor Company Storage Vending Rec. 20 A 1 180 VA 900 VA 1 20 A 3rd Floor Stairway Receptacles 20 17 3rd Floor Company Storage Vending Rec. 20 A 1 180 VA 180 VA 1 20 A 3rd Floor Company Storage Vending Rec. 18 15 3rd Floor Company Storage Counter Top Rec. 20 A 1 360 VA 180 VA 1 20 A 3rd Floor Company Storage Refrigerator Rec. 16 13 3rd Floor Janitor/Recycle/South Hall Rec. 20 A 1 1260... 900 VA 1 20 A 3rd Floor Company Storage, Switched Rec. 14 11 1080... 720 VA 1 20 A 3rd Floor Mechanical Room Receptacles 12 9 2720... 360 VA 1 20 A 3rd Floor Corridor Receptacles 10

Telecom Room Panel PT-301 100 A 3 2720... 360 VA 1 20 A 3rd Floor Electrical Room Receptacles 8

5 9020... 1121... 6 3 8860... 1037... 4

3rd Floor Quarters Receptacle Panel PL-302 100 A 3 9120... 1384...

3 225 A 3rd Floor Laundry Panel PL-303

CKT Load Name Trip Poles A B C Poles Trip Load Name CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 400 A Mounting: SURFACE Wires: 4 Mains Rating: 400 A

Supply From: T-3 Phases: 3 Mains Type: MAIN CB Location: ELECTRICAL 327 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: PL-301

Notes: PROVIDE COMBINATION-TYPE AFCI PROTECTION FOR BRANCH CIRCUITS SUPPLYING RECEPTACLES IN SLEEPING QUARTERS, HALLWAYS, AND RESTROOMS.

Total Est. Demand Current: 59 A

Total Conn. Current: 75 A Total Est. Demand: 21200 VA Total Conn. Load: 27000 VA

Receptacle 21600 VA 15800 VA Load Classification Connected Load Estimated Demand Panel Totals

Total Amps: 76 A 74 A 75 A Total Load: 9120 VA 8860 VA 9020 VA

41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42

39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40

37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38

35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36

33 SPACE -- -- 0 VA 0 VA -- -- SPACE 34

31 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 32

29 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 30

27 3rd Floor FA/MN Booster Panels 20 A 1 1200... 100 VA 1 20 A 3rd Floor Water Fountain 28 25 Room 321 Receptacles 20 A 1 540 VA 100 VA 1 20 A 3rd Floor Water Fountain 26 23 Room 320 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 321 Receptacles 24 21 Room 319 Receptacles 20 A 1 1080... 540 VA 1 20 A Room 320 Receptacles 22 19 Room 318 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 318 Receptacles 20 17 Room 316 Receptacles 20 A 1 540 VA 1080... 1 20 A Room 317 Receptacles 18 15 Room 315 Receptacles 20 A 1 1080... 540 VA 1 20 A Room 316 Receptacles 16 13 Room 314 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 314 Receptacles 14 11 Room 312 Receptacles 20 A 1 1080... 1080... 1 20 A Room 313 Receptacles 12 9 Room 310 Receptacles 20 A 1 1080... 1080... 1 20 A Room 311 Receptacles 10 7 Room 308 Receptacles 20 A 1 1080... 1080... 1 20 A Room 309 Receptacles 8 5 Room 306 Receptacles 20 A 1 1080... 1080... 1 20 A Room 307 Receptacles 6 3 Room 304 Receptacles 20 A 1 1080... 1080... 1 20 A Room 305 Receptacles 4 1 Room 302 Receptacles 20 A 1 1080... 1080... 1 20 A Room 303 Receptacles 2

CKT Load Name Trip Poles A B C Poles Trip Load Name CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 100 A Mounting: SURFACE Wires: 4 Mains Rating: 100 A

Supply From: PL-301 Phases: 3 Mains Type: MAIN CB Location: ELECTRICAL 327 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: PL-302

RCPT Designates Dryer Load Notes:

Total Est. Demand: 70 A Total Conn.: 98 A

RCPT 30288 VA 66.51% 20144 VA Total Est. Demand: 25290 VA Spare 4800 VA 100.00% 4800 VA Total Conn. Load: 35433 VA Receptacle 360 VA 100.00% 360 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 116 A 86 A 95 A Total Load: 13849 VA 10375 VA 11214 VA

23 SPACE -- -- 0 VA 0 VA -- -- SPACE 24

21 SPACE -- -- 0 VA 0 VA -- -- SPACE 22

19 SPARE 20 A 1 1200... 0 VA -- -- SPACE 20

17 SPARE 20 A 1 1200... 1200... 1 20 A SPARE 18

15 3rd Floor Laundry-Washer (RCPT) 20 A 1 1440... 1200... 1 20 A SPARE 16 13 3rd Floor Laundry-Washer (RCPT) 20 A 1 1440... 1440... 1 20 A 3rd Floor Laundry-Washer (RCPT) 14 11 2500... 1440... 1 20 A 3rd Floor Laundry-Washer (RCPT) 12

3rd Floor Laundry-Dryer (RCPT) 35 A 2 2500... 360 VA 1 20 A GP Receptacles 10

7 2500... 2500... 8

3rd Floor Laundry-Dryer (RCPT) 35 A 2 2500... 2500...

2 35 A 3rd Floor Laundry-Dryer (RCPT)

3 2500... 2500... 4

3rd Floor Laundry-Dryer (RCPT) 35 A 2 2500... 2500...

2 35 A 3rd Floor Laundry-Dryer (RCPT)

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 225 A Mounting: SURFACE Wires: 4 Mains Rating: 225 A

Supply From: PL-301 Phases: 3 Mains Type: MAIN CB Location: LAUNDRY 326 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: PL-303

Notes:

Total Est. Demand: 18 A Total Conn.: 18 A

Total Est. Demand: 6520 VA Spare 4000 VA 100.00% 4000 VA Total Conn. Load: 6520 VA Receptacle 2520 VA 100.00% 2520 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 25 A 25 A 9 A Total Load: 2720 VA 2720 VA 1080 VA

23 SPACE -- -- 0 VA 0 VA -- -- SPACE 24

21 SPACE -- -- 0 VA 0 VA -- -- SPACE 22

19 SPACE -- -- 0 VA 0 VA -- -- SPACE 20

17 SPACE -- -- 0 VA 0 VA -- -- SPACE 18

15 SPACE -- -- 0 VA 0 VA -- -- SPACE 16

13 SPACE -- -- 0 VA 0 VA -- -- SPACE 14

11 SPACE -- -- 0 VA 0 VA -- -- SPACE 12

9 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 10

7 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 8

5 NE Receptacles 20 A 1 540 VA 540 VA 1 20 A SW Receptacles 6 3 #2 Rack Receptacle 20 A 1 360 VA 360 VA 1 20 A #2 Rack Receptacle 4 1 #1 Rack Receptacle 20 A 1 360 VA 360 VA 1 20 A #1 Rack Receptacle 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 100 A Mounting: SURFACE Wires: 4 Mains Rating: 100 A

Supply From: PL-301 Phases: 3 Mains Type: MAIN CB Location: TELECOM 325 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: PT-301

AM

EN

D

M

EN

T

AP

R

1 1

W

2Q R

R

_P la ns _V ol 2-

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

Fi le

P at h:

Pl ot D at e:

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

LO

U

IS

VI

LL

E

D

IS

TR

IC

T

D

R M

AR

TI

N L

U

TH

ER

K

IN

G

J R

P

LA

C E

LO

U

IS

VI

LL

E, K Y

WEST

JA

N

C

ER

TI

FI

ED

F

IN

AL

FT

. M cC O

Y, W

I C

O

LL

EC

TI

VE

T

R

AI

N

IN

G O

FF

IC

ER

S

Q U

AR

TE

R S

W

ES

T

PN

F

Y2

2, P

VO

LU

M E

0F

C :\U se rs

\H 2E

D D

JM

9\

D oc um en ts \5

9_ R ev it2

0_

E_

TT

O Q

_H 2E

D D

JM

9.

rv t

3/

/2

2:

:5

PM

E-605

PA

N

EL

S

C H

ED

U

LE

S

J.

M

O O

R E

J.

M

O O

R E

M .L

AW

R

EN

C

E

Notes: PROVIDE COMBINATION-TYPE AFCI PROTECTION FOR BRANCH CIRCUITS SUPPLYING RECEPTACLES IN SLEEPING QUARTERS, HALLWAYS, AND RESTROOMS.

Total Est. Demand Current: 171 A

Total Conn. Current: 228 A Total Est. Demand: 61597 VA

RCPT 30288 VA 20144 VA Total Conn. Load: 82022 VA Receptacle 30600 VA 20300 VA Load Classification Connected Load Estimated Demand Panel Totals

Total Amps: 253 A 222 A 212 A Total Load: 30178 VA 26463 VA 25384 VA

41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42

39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40

37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38

35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36

33 SPACE -- -- 0 VA 0 VA -- -- SPACE 34

31 SPACE -- -- 0 VA 0 VA -- -- SPACE 32

29 SPARE 20 A 1 1000... 0 VA -- -- SPACE 30

27 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 28

25 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 26

23 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 24

21 4th Floor Corridor Receptacles 20 A 1 360 VA 360 VA 1 20 A 4th Floor Corridor/N. Stair Rec. 22 19 4th Floor Company Storage Vending Rec. 20 A 1 180 VA 360 VA 1 20 A 4th Floor Corridor Receptacles 20 17 4th Floor Company Storage Vending Rec. 20 A 1 180 VA 180 VA 1 20 A 4th Floor Company Storage Vending Rec. 18 15 4th Floor Company Storage Counter Top Rec. 20 A 1 360 VA 180 VA 1 20 A 4th Floor Company Storage Refrigerator Rec. 16 13 4th Floor Stairway Receptacles 20 A 1 720 VA 900 VA 1 20 A 4th Floor Company Storage, Switched Rec. 14 11 1080... 720 VA 1 20 A 4th Floor Mechanical Room Receptacles 12 9 2720... 1260... 1 20 A 4th Floor Janitor/Recycle/South Hall Rec. 10

Telecom Room Panel PT-401 100 A 3 2720... 360 VA 1 20 A 4th Floor Electrical Room Receptacles 8

5 9020... 1121... 6 3 8860... 1037... 4

4th Floor Quarters Receptacle Panel PL-402 100 A 3 9120... 1384...

3 225 A 4th Floor Laundry Panel PL-403

CKT Load Name Trip Poles A B C Poles Trip Load Name CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 400 A Mounting: SURFACE Wires: 4 Mains Rating: 400 A

Supply From: T-4 Phases: 3 Mains Type: MAIN CB Location: ELECTRICAL 427 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: PL-401

Notes: PROVIDE COMBINATION-TYPE AFCI PROTECTION FOR BRANCH CIRCUITS SUPPLYING RECEPTACLES IN SLEEPING QUARTERS, HALLWAYS, AND RESTROOMS.

Total Est. Demand Current: 59 A

Total Conn. Current: 75 A Total Est. Demand: 21200 VA Total Conn. Load: 27000 VA

Receptacle 21600 VA 15800 VA Load Classification Connected Load Estimated Demand Panel Totals

Total Amps: 76 A 74 A 75 A Total Load: 9120 VA 8860 VA 9020 VA

41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42

39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40

37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38

35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36

33 SPACE -- -- 0 VA 0 VA -- -- SPACE 34

31 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 32

29 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 30

27 4th Floor FA/MN Booster Panels 20 A 1 1200... 100 VA 1 20 A 4th Floor Water Fountain 28 25 Room 421 Receptacles 20 A 1 540 VA 100 VA 1 20 A 4th Floor Water Fountain 26 23 Room 420 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 421 Receptacles 24 21 Room 419 Receptacles 20 A 1 1080... 540 VA 1 20 A Room 420 Receptacles 22 19 Room 418 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 418 Receptacles 20 17 Room 416 Receptacles 20 A 1 540 VA 1080... 1 20 A Room 417 Receptacles 18 15 Room 415 Receptacles 20 A 1 1080... 540 VA 1 20 A Room 416 Receptacles 16 13 Room 414 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 414 Receptacles 14 11 Room 412 Receptacles 20 A 1 1080... 1080... 1 20 A Room 413 Receptacles 12 9 Room 410 Receptacles 20 A 1 1080... 1080... 1 20 A Room 411 Receptacles 10 7 Room 408 Receptacles 20 A 1 1080... 1080... 1 20 A Room 409 Receptacles 8 5 Room 406 Receptacles 20 A 1 1080... 1080... 1 20 A Room 407 Receptacles 6 3 Room 404 Receptacles 20 A 1 1080... 1080... 1 20 A Room 405 Receptacles 4 1 Room 402 Receptacles 20 A 1 1080... 1080... 1 20 A Room 403 Receptacles 2

CKT Load Name Trip Poles A B C Poles Trip Load Name CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 100 A Mounting: SURFACE Wires: 4 Mains Rating: 100 A

Supply From: PL-401 Phases: 3 Mains Type: MAIN CB Location: ELECTRICAL 427 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: PL-402

RCPT Designates Dryer Load Notes:

Total Est. Demand: 70 A Total Conn.: 98 A

RCPT 30288 VA 66.51% 20144 VA Total Est. Demand: 25290 VA Spare 4800 VA 100.00% 4800 VA Total Conn. Load: 35433 VA Receptacle 360 VA 100.00% 360 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 116 A 86 A 95 A Total Load: 13849 VA 10375 VA 11214 VA

23 SPACE -- -- 0 VA 0 VA -- -- SPACE 24

21 SPACE -- -- 0 VA 0 VA -- -- SPACE 22

19 SPARE 20 A 1 1200... 0 VA -- -- SPACE 20

17 SPARE 20 A 1 1200... 1200... 1 20 A SPARE 18

15 4th Floor Laundry-Washer (RCPT) 20 A 1 1440... 1200... 1 20 A SPARE 16 13 4th Floor Laundry-Washer (RCPT) 20 A 1 1440... 1440... 1 20 A 4th Floor Laundry-Washer (RCPT) 14 11 2500... 1440... 1 20 A 4th Floor Laundry-Washer (RCPT) 12

4th Floor Laundry-Dryer (RCPT) 35 A 2 2500... 360 VA 1 20 A GP Receptacles 10

7 2500... 2500... 8

4th Floor Laundry-Dryer (RCPT) 35 A 2 2500... 2500...

2 35 A 4th Floor Laundry-Dryer (RCPT)

3 2500... 2500... 4

4th Floor Laundry-Dryer (RCPT) 35 A 2 2500... 2500...

2 35 A 4th Floor Laundry-Dryer (RCPT)

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 225 A Mounting: SURFACE Wires: 4 Mains Rating: 225 A

Supply From: PL-401 Phases: 3 Mains Type: MAIN CB Location: LAUNDRY 426 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: PL-403

Notes:

Total Est. Demand: 18 A Total Conn.: 18 A

Total Est. Demand: 6520 VA Spare 4000 VA 100.00% 4000 VA Total Conn. Load: 6520 VA Receptacle 2520 VA 100.00% 2520 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 25 A 25 A 9 A Total Load: 2720 VA 2720 VA 1080 VA

23 SPACE -- -- 0 VA 0 VA -- -- SPACE 24

21 SPACE -- -- 0 VA 0 VA -- -- SPACE 22

19 SPACE -- -- 0 VA 0 VA -- -- SPACE 20

17 SPACE -- -- 0 VA 0 VA -- -- SPACE 18

15 SPACE -- -- 0 VA 0 VA -- -- SPACE 16

13 SPACE -- -- 0 VA 0 VA -- -- SPACE 14

11 SPACE -- -- 0 VA 0 VA -- -- SPACE 12

9 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 10

7 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 8

5 NE Receptacles 20 A 1 540 VA 540 VA 1 20 A SW Receptacles 6 3 #2 Rack Receptacle 20 A 1 360 VA 360 VA 1 20 A #2 Rack Receptacle 4 1 #1 Rack Receptacle 20 A 1 360 VA 360 VA 1 20 A #1 Rack Receptacle 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 100 A Mounting: SURFACE Wires: 4 Mains Rating: 100 A

Supply From: PL-401 Phases: 3 Mains Type: MAIN CB Location: TELECOM 425 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: PT-401

AM

EN

D

M

EN

T

AP

R

1 1

W

2Q R

R

_P la ns _V ol 2-

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

D

AT

E M

AR

K

D

ES

C R

IP

TI

O N

Fi le

P at h:

Pl ot D at e:

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

LO

U

IS

VI

LL

E

D

IS

TR

IC

T

D

R M

AR

TI

N L

U

TH

ER

K

IN

G

J R

P

LA

C E

LO

U

IS

VI

LL

E, K Y

WEST

JA

N

C

ER

TI

FI

ED

F

IN

AL

FT

. M cC O

Y, W

I C

O

LL

EC

TI

VE

T

R

AI

N

IN

G O

FF

IC

ER

S

Q U

AR

TE

R S

W

ES

T

PN

F

Y2

2, P

VO

LU

M E

0F

C :\U se rs

\H 2E

D D

JM

9\

D oc um en ts \5

9_ R ev it2

0_

E_

TT

O Q

_H 2E

D D

JM

9.

rv t

3/

/2

2:

:5

PM

E-606

PA

N

EL

S

C H

ED

U

LE

S

J.

M

O O

R E

J.

M

O O

R E

M .L

AW

R

EN

C

E

Notes:

Total Est. Demand: 540 A Lighting 429 VA 125.00% 536 VA Total Conn.: 540 A Spare 90745 VA 100.00% 90745 VA Total Est. Demand: 449047 VA Other 0 VA 0.00% 0 VA Total Conn. Load: 448943 VA

HVAC 364922 VA 100.00% 364922 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 540 A

Total Conn. Load: 448943 VA

20 SPACE -- -- -- 0 VA --

19 SPACE -- -- -- 0 VA --

18 SPACE -- -- -- 0 VA --

17 SPACE -- -- -- 0 VA --

16 SPACE -- -- -- 0 VA --

15 SPACE -- -- -- 0 VA --

14 SPACE -- -- -- 0 VA --

13 SPACE -- -- -- 0 VA --

12 SPACE -- -- -- 0 VA --

11 SPARE 3 -- 50 A 33225 VA

10 SPARE 3 -- 20 A 13300 VA

9 SPARE 3 -- 20 A 13300 VA

8 DOAS-1 3 50 A 45 A 36082 VA

7 HWP-2 3 20 A 20 A 11431 VA Estimating 7.5hp Motor 6 HWP-1 3 20 A 20 A 11431 VA Estimating 7.5hp Motor 5 CWP-2 3 20 A 20 A 14550 VA Estimating 10hp Motor 4 CWP-1 3 20 A 20 A 14550 VA Estimating 10hp Motor 3 100 Ton Air Cooled Scroll Chiller ACC-1 3 400 A 225 A 172928 VA Based On Chiller MCA

2 MH-401 3 250 A 125 A 54670 VA

1 T-5 3 250 A 175 A 78428 VA

CKT Circuit Description # of Poles Frame Size Trip Rating Load Remarks

Notes:

Enclosure: NEMA 1 MCB Rating: 800 A Mounting: SURFACE Wires: 4 Mains Rating: 800 A

Supply From: MSB-DIST Phases: 3 Mains Type: MCB Location: Volts: 480/277 Wye A.I.C. Rating: 22kA SYMMETRICAL

Switchboard: MH-101

Notes:

Total Est. Demand Current: 218 A Receptacle 180 VA 100.00% 180 VA Total Conn. Current: 218 A Other 0 VA 0.00% 0 VA Total Est. Demand: 78533 VA Lighting 429 VA 125.00% 536 VA Total Conn. Load: 78428 VA

HVAC 64127 VA 100.00% 64127 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 233 A 233 A 197 A Total Load: 27405 VA 27407 VA 23633 VA

53 SPACE -- -- 0 VA 0 VA -- -- SPACE 54

51 SPACE -- -- 0 VA 0 VA -- -- SPACE 52

49 SPACE -- -- 0 VA 0 VA -- -- SPACE 50

47 SPACE -- -- 0 VA 0 VA -- -- SPACE 48

45 SPACE -- -- 0 VA 0 VA -- -- SPACE 46

43 SPACE -- -- 0 VA 0 VA -- -- SPACE 44

41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42

39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40

37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38

35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36

33 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 34

31 SPARE 20 A 1 1000 VA 1000... 1 20 A SPARE 32

29 SPARE 20 A 1 1000... 1920 VA 1 20 A FA/MN Equipment in Mechanical 128 30 27 Boiler 2 20 A 1 720 VA 623 VA 1 20 A Elevator Controller, Outlet and Hoistway Lights 28 25 Boiler 1 20 A 1 720 VA 1976... 26

23 1976... 1976 VA

2 25 A DSS-9 4th Floor Electrical Room

DSS-8 3rd Floor Electrical Room 25 A 2

1976... 1976... 22

19 1976 VA 1976...

2 25 A DSS-7 2nd Floor Electrical Room

DSS-6 1st Floor Electrical Room 25 A 2

1976... 1144 VA 18

15 1144... 1144...

2 25 A DSS-5 4th Floor Telecom Room

DSS-4 3rd Floor Telecom Room 25 A 2

1144 VA 1144... 14

11 1144... 1144 VA

2 25 A DSS-3 2nd Floor Telecom Room

DSS-2 1st Floor Telecom Room 25 A 2

1144... 1144... 10

7 GF-1 20 A 1 660 VA 1144...

2 25 A DSS-1 Elevator Equipment Room

5 5806... 5806 VA 6

3 7910... 7815... 4

ML-201 100 A 3

7421 VA 7421...

3 100 A ML-401

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 400 A Mounting: SURFACE Wires: 4 Mains Rating: 400 A

Supply From: T-5 Phases: 3 Mains Type: MAIN CB Location: Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: ML-101

Notes:

Total Est. Demand Current: 59 A

Total Conn. Current: 59 A Total Est. Demand: 21110 VA Total Conn. Load: 21110 VA

HVAC 17438 VA 17438 VA

Load Classification Connected Load Estimated Demand Panel Totals

Total Amps: 64 A 68 A 48 A Total Load: 7421 VA 7910 VA 5806 VA

41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42

39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40

37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38

35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36

33 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 34

31 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 32

29 RCP-1, 1st Floor Mechanical Room 20 A 1 65 VA 65 VA 1 20 A RCP-2, 2nd Floor Mechanical Room 30 27 2nd Floor Quarters, FCU-218/220 15 A 1 660 VA 660 VA 1 15 A 2nd Floor Quarters, FCU-219/221 28 25 2nd Floor Quarters, FCU-214/216 15 A 1 660 VA 660 VA 1 15 A 2nd Floor Quarters, FCU-215/217 26 23 2nd Floor Quarters, FCU-210/212 15 A 1 660 VA 660 VA 1 15 A 2nd Floor Quarters, FCU-211/213 24 21 2nd Floor Quarters, FCU-206/208 15 A 1 660 VA 660 VA 1 15 A 2nd Floor Quarters, FCU-207/209 22 19 2nd Floor Quarters, FCU-202/204 15 A 1 660 VA 660 VA 1 15 A 2nd Floor Quarters, FCU-203/205 20 17 2nd Floor Stair Heaters (CH) 20 A 1 192 VA 1524... 1 15 A 2nd Floor Corridor, Laundry, Comm. Area FCU 18 15 UH-2 Mech. Room Unit Heater 20 A 1 240 VA 50 VA 1 20 A VAV-2, 2nd Floor Laundry 16 13 1st Floor Quarters, FCU-118/120 15 A 1 660 VA 660 VA 1 15 A 1st Floor Quarters, FCU-119/121 14 11 1st Floor Quarters, FCU-114/116 15 A 1 660 VA 660 VA 1 15 A 1st Floor Quarters, FCU-115/117 12 9 1st Floor Quarters, FCU-110/112 15 A 1 660 VA 660 VA 1 15 A 1st Floor Quarters, FCU-111/113 10 7 1st Floor Quarters, FCU-106/108 15 A 1 660 VA 660 VA 1 15 A 1st Floor Quarters, FCU-107/109 8 5 1st Floor Quarters, FCU-102/104 15 A 1 660 VA 660 VA 1 15 A 1st Floor Quarters, FCU-103/105 6 3 1st Floor Stair Heaters (CH) 20 A 1 288 VA 1524... 1 15 A 1st Floor Corridor, Laundry, Comm. Area FCU 4 1 UH-1 Mech. Room Unit Heater 20 A 1 240 VA 50 VA 1 20 A VAV-1, 1st Floor Laundry 2

CKT Load Name Trip Poles A B C Poles Trip Load Name CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 100 A Mounting: SURFACE Wires: 4 Mains Rating: 225 A

Supply From: ML-101 Phases: 3 Mains Type: MCB Location: ELECTRICAL 127 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL

Branch Panel: ML-201

Notes:

Total Est. Demand Current: 58 A

Total Conn. Current: 58 A Total Est. Demand: 21014 VA Total Conn. Load: 21014 VA

HVAC 17342 VA 17342 VA

Load Classification Connected Load Estimated Demand Panel Totals

Total Amps: 64 A 67 A 48 A Total Load: 7421 VA 7815 VA 5806 VA

41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42

39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40

37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38

35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36

33 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 34

31 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 32

29 RCP-3, 3rd Floor Mechanical Room 20 A 1 65 VA 65 VA 1 20 A RCP-4, 4th Floor Mechanical Room 30 27 4th Floor Quarters, FCU-418/420 15 A 1 660 VA 660 VA 1 15 A 4th Floor Quarters, FCU-419/421 28 25 4th Floor Quarters, FCU-414/416 15 A 1 660 VA 660 VA 1 15 A 4th Floor Quarters, FCU-415/417 26 23 4th Floor Quarters, FCU-410/412 15 A 1 660 VA 660 VA 1 15 A 4th Floor Quarters, FCU-411/413 24 21 4th Floor Quarters, FCU-406/408 15 A 1 660 VA 660 VA 1 15 A 4th Floor Quarters, FCU-407/409 22 19 4th Floor Quarters, FCU-402/404 15 A 1 660 VA 660 VA 1 15 A 4th Floor Quarters, FCU-403/405 20 17 4th Floor Stair Heaters (CH) 20 A 1 192 VA 1524...