This document is a set of design drawings and specifications for the construction of two new 48,000 SF, 4-story Collective Training Officers Quarters (CTOQ) buildings at Fort McCoy, Wisconsin. The solicitation number is W912QR24R0003, and the agency is the Department of the Army Corps of Engineers, Louisville District.
The drawings provide detailed specifications for the mechanical, electrical, plumbing, and architectural elements of the buildings, including equipment schedules, panel schedules, and room finish details. Key requirements include a 100-ton air-cooled chiller, fan coil units, ductless split systems, and hot water boilers to provide HVAC for the facility. The electrical systems include a 1200A 480/277V main switchboard, panelboards, and lighting and power distribution. The buildings will have sleeping quarters, laundry facilities, common areas, and support spaces across four floors. Construction is scheduled for FY 2023, with a projected completion date in 2024.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WEDGE-LOCK WELDING
CONNECTOR
STEEL BRACKET ASSY. SECURED
TO WALL (OR WELD TO STEEL PIPE
GUARDRAIL - WHERE OCCURS)
1 1/2" O.D. (MAX.) STEEL PIPE
HANDRAIL WELD TO STEEL
BRACKET
WELD PIPE SECTIONS TOGETHER
WITH A CONTINUOUS WELD, GRIND
SMOOTH, & FILL WITH BODY PUTTY
TO ENSURE INVISIBILITY OF SEAM
3/16" END STEEL PLATE;
WELD & GRIND SMOOTH
WALL, REFER TO PLANS
FOR
PARTITION TYPE
1/2"
CLR.
2 1/4"
R 2 1/2
1/2"
2 1 /2"
12"
TYPICAL ROUND WALL HANDRAIL 1 1/2" O.D. PIPE
F.F.
F.F.
BOTTOM LANDING
TOP LANDING
STAIR3'-
0"
ONE TREAD
1'-0"
6'-0" MAX.
1'-0"
1'-0"
6"
3'- 0"
3'- 0"
PROVIDE CONTINUOUS BACKING
FOR HANDRAIL ATTACHMENT,
TYP.
E15 A-412
Sim
A15 A-412
Sim
3'-0" TO STAIR NOSING
STEEL BRACKET ASSEMBLY WITH
MOUNTING SCREWS & BACKER
PLATE
WALL, REFER TO FLOOR PLAN
CONT. 1 1/2" O.D. STEEL PIPE
HANDRAIL, PAINTED (W2);
WELD TO STEEL BRACKET
ASSEMBLY
NOTE:
AT METAL STUD WALL, PROVIDE 16
GA METAL RUNNER NOTCHED TO
BYPASS METAL STUDS FOR METAL
BACKING.
CLR.
2 1/4"
TUBE STRINGER, PAINTED
TYPICAL
STEEL PAN TREADS WITH
CONCRETE FILL, TYPICAL
1 1/2" O.D. STEEL TUBE HANDRAIL
CONTINUOUS AT INTERNAL RAIL,
PAINTED, TYPICAL.
1 1/2" O.D. STEEL TUBE
GUARDRAIL
SYSTEM, PAINTED, TYPICAL
CLR
2 1/4"
CLR
2 7/8"
3' -0
" 3' -6
" 3' -0
6" METAL STUD WITH (2)
LAYERS 5/8" GYPSUM
BOARD ON BOTH SIDES
UP TO THE METAL DECK
STAIR LANDING
1 1/2" O.D. PIPE TOP RAIL
METAL TOE KICK
1 1/2" O.D. INTERMEDIATE PIPE
RAIL TYP.
1 1/2" O.D. GUARDRAIL PIPE POST
@ 4'-0" MAX. SPACING
NOTE:
1. SUBMIT SHOP DRAWINGS PRIOR TO
FABRICATION.
3' -6
EQ
EQ
EQ
EQ
EQ
2"
M
AX
4"
C
LR
EQ
EQ
1 1/2" O.D. PAINTED STEEL TUBE GUARDRAIL
SYSTEM WITH 1 1/2" O.D. PAINTED (W2)
STEEL HORIZONTAL PICKETS AT 4" O.C. TYP.
WELDED TO POSTS
1 1/2" O.D. STEEL TUBE HANDRAIL,
CONTINUOUS AT INTERNAL RAIL,
PAINTED, TYPICAL. NOTE: EXTEND
HANDRAIL HORIZONTALLY ABOVE
THE LANDING FOR 12" MIN. (AT
WALL BEYOND)
SEE STRUCTURAL DRAWINGS
FOR LANDINGS
TUBE STRINGER, PAINTED (W2),
TYPICAL
3' -6
3' -0
SEE STRUCTURAL DRAWINGS
FOR LANDINGS
TUBE STRINGER, PAINTED
(W4), TYPICAL
1 1/2" O.D. STEEL TUBE HANDRAIL,
CONTINUOUS AT INTERNAL RAIL, PAINTED
(W2), TYPICAL. NOTE: EXTEND HANDRAIL
HORIZONTALLY ABOVE THE LANDING FOR
12" MIN. (AT WALL BEYOND)
1 1/2" O.D. PAINTED STEEL TUBE
GUARDRAIL SYSTEM WITH 1 1/2" O.D.
PAINTED STEEL HORIZONTAL PICKETS AT
4" O.C. TYP. WELDED TO POSTS
3' -6
3' -0
MIN.
1'-0"
4" M
AX
STEEL PAN TREADS WITH CONCRETE
FILL, TYPICAL
TUBE STRINGER, PAINTED (W4),
TYPICAL PROVIDE CLOSURE PLATE
1 1/2" O.D. STEEL TUBE HANDRAIL,
CONTINUOUS AT INTERNAL RAIL,
PAINTED (W2), TYPICAL.
1 1/2" O.D. PAINTED STEEL TUBE
GUARDRAIL SYSTEM WITH 1 1/2" O.D.
PAINTED STEEL HORIZONTAL PICKETS
AT 4" O.C. TYP. WELDED TO POSTS
1ST FLOOR
0"
11"
3' -0
A11 A-412
Sim
" T
O S
TA
IR
N O
SI
N
G
" T
O S
TA
IR
N
O
SI
N
G 1 1/2" O.D. PIPE HANDRAIL
ON BRACKET WELD TO PIPE RAIL
POST
1 1/2" O.D. VERTICAL OR HORIZONTAL
INTERMEDIATE PICKET RAIL (4" MAXIMUM
OPENING)
1 1/2" O.D. PIPE TOP RAILS,
PAINTED
1 1/2" O.D. PIPE,
PAINTED (W2)
CLR
2 1/4"
NOTE:
1. MAXIMUM OPENING IS SUCH THAT
4" SPHERE CANNOT PASS THROUGH.
2. SUBMIT SHOP DRAWINGS PRIOR TO
FABRICATION.
2ND FLOOR
12'-0"
HANDRAIL BEYOND
CONCRETE SLAB ON
METAL DECK, SEE
STRUCT. DWGS
STEEL STRUCTURE,
SEE STRUCT. DWGS
CONTINOUS SLIP TRACK
WITH FIRESTOP MATERIAL
WITH CONTINOUS BEAD OF
SEALANT BOTH SIDES.
2 1/2" METAL STUD
@ 16" O.C.
6" METAL STUD WITH (2)
LAYERS 5/8" GYPSUM
BOARD ON BOTH SIDES
UP TO THE METAL DECK
6" METAL STUD WITH (2)
LAYERS 5/8" GYPSUM
BOARD ON BOTH SIDES
UP TO THE METAL DECK
INTERMEDIATE FLOOR
LANDING PROVIDED BY
STAIR MANUFACTURER
AS PART OF DELEGATED
STAIR DESIGN6" METAL STUD
FRAMING @ 16" O.C.
WITH ( 1 ) LAYER 5/8"
FIRERATED GWB BOTH
SIDES.
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
LO
U
IS
VI
LL
E
D
IS
TR
IC
T
D
R M
AR
TI
N L
U
TH
ER
K
IN
G
J R
P
LA
C E
LO
U
IS
VI
LL
E, K Y
EAST
JA
N
C
ER
TI
FI
ED
F
IN
AL
FT
. M cC O
Y, W
I C
O
LL
EC
TI
VE
T
R
AI
N
IN
G O
FF
IC
ER
S
Q U
AR
TE
R S
(E
AS
T)
PN
FY
, P
VO
LU
M E
0F
C :\U se rs
\h 2e dd ra h\ D oc um en ts
\5
1_
R ev it2
0_ A_
TT
O
Q _h
2e dd ra h.
rv t
4/
/2
9:
:4
AM
A-412
ST
AI
R D
ET
AI
LS
M .J
O H
N
SO
N
B.
AL
LE
N
M .B
AR
R
Y
6" = 1'-0"E15 TYP. WALL HANDRAIL TERMINATION
3/4" = 1'-0"K15 TYPICAL HANDRAIL - MOUNTING
6" = 1'-0"A15 TYPICAL WALL HANDRAIL - MOUNTING
3/4" = 1'-0"E1 STAIR TRANSVERSE SECTION DET .
1" = 1'-0"A1 STAIR GUARDRAIL DET. @ MEZZ (TYP.)
3/4" = 1'-0"A6 STAIR SECTION - LANDING ( TYP. )
3/4" = 1'-0"K11 STAIR SECTION ( TYP. )
3/4" = 1'-0"E11 STAIR SECTION - 1st. FL. ( TYP. )
3" = 1'-0"A11 STAIR HANDRAIL & GUARDRAIL (TYP.)
1 1/2" = 1'-0"K1 STAIR WALL DETAIL
1 1/2" = 1'-0"E6 STAIR SECTION - LANDING ( 6" S.S. )
AM
EN
D
M
EN
T
AP
R
11 1
W
2Q R
R
_P la ns _V ol 1-
ARIMS: 200A Disposition: Maintain for 15 yrs after construction.
METAL STUD
METAL STUD
SCREWDRIVER
CAM LOCK
5/8" CEILING
DRYWALL
5/8" CEILING
DRYWALL
PIN HINGE
2 FEET
1 1/4"
5/
8"
1" 1"
3/
4"
SEALANT
HOLLOW
METAL DOOR
FRAME
SEALANT
JAMB
ANCHORS, 3
PER SIDE
(2) 2x12 P.T. WOOD
BLOCKING
AIR SPACE
RIGID
INSULATION
1/2" EXTERIOR
SHEATHING
SPRAY POLYURETHANE
FOAM (SPF)INSULATION,
SEE SHT. A-311.
6" STEEL STUD
@ 16" O.C.
5/8" GYPSUM
BOARD
CORNER BEAD
1/2"x5" LAG BOLT
OPEN BAR BRACKET
STEEL TUBE PER DTL G10 THIS SHEET
VAPOR AIR
BARRIER
UTILITY BRICK 1/3
BOND COURSING WITH
WALL TIES @ 16" O.C.
1' -3
2"
3"
3"
OPEN BAR BRACKET
ATTACHED WITH #10
SELF TAPPING TEK
SCREW INTO WALL
BLOCKING
HHS 1-1/2" x 3" x 3/16" STEEL TUBE WITH 1/2" DIA. x 1" LONG
THREADED BOLT WITH LOCK
WASHER EACH SIDE INTO TAPPED
AND THREADED HOLE IN STEEL
TUBE.
3' -6
3"
1' -6
3"
(3) SELF TAPPING
TEK SCREWS #10
@ 1-1/2" LONG
DOOR
STEEL TUBE
42" A.F.F
TOP
RAILOPEN BAR
BRACKET
1/2" THREADED BOLT
W/LOCK WASHER INTO
TAPPED AND THREADED
HOLE IN HHS.
WALL
NO
EXIT
NO
EXIT
CONTRACTOR TO
PROVIDE 'NO EXIT'
SIGNAGE AS SHOWN
CONTRACTOR TO
PROVIDE 'NO EXIT'
SIGNAGE AS SHOWN
PHOTOGRAPHIC EXAMPLE AS
EXECUTED ON FY19 AND FY20
BARRACKS - PROVIDE SIMILAR
A1 A-301
H
3' -6
7'-4"
KEEP
CLEAR
KEEP
CLEAR
KEEP
CLEAR
KEEP
CLEAR
6" EQ. EQ. 6"
6"
4" SAFETY
YELLOW STRIP
6" SAFETY
YELLOW STRIP
STEEL TUBE PER
DTL G10 THIS SHEET
A-507 A1
G10 A-507
Sim
* POWDER COAT ENTIRE BIKE CANOPY DARK BRONZE, SEE SPECIFICATIONS
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
LO
U
IS
VI
LL
E
D
IS
TR
IC
T
D
R M
AR
TI
N L
U
TH
ER
K
IN
G
J R
P
LA
C E
LO
U
IS
VI
LL
E, K Y
EAST
JA
N
C
ER
TI
FI
ED
F
IN
AL
FT
. M cC O
Y, W
I C
O
LL
EC
TI
VE
T
R
AI
N
IN
G O
FF
IC
ER
S
Q U
AR
TE
R S
(E
AS
T)
PN
FY
, P
VO
LU
M E
0F
C :\U se rs
\h 2e dd ra h\ D oc um en ts
\5
1_
R ev it2
0_ A_
TT
O
Q _h
2e dd ra h.
rv t
4/
/2
:1 6:
A
M
A-507
M
IS
C
EL
LA
N
EO
U
S D
ET
AI
LS
M . J
O H
N
SO
N
B.
A
LL
EN
M . B
AR
R
Y
12" = 1'-0"A10 CEILING ACCESS DOOR - SHOWER/LATRINE/LAUNDRY
3" = 1'-0"A1 MECHANICAL ROOM DOOR JAMB DETAIL
3/4" = 1'-0"G10 EXTERIOR MECH DOOR DETAIL
3/4" = 1'-0"G1 MECHANICAL ROOM FLOOR STRIPING PLAN
N.T.S.E15 BIKE CANOPY
AM
EN
D
M
EN
T
AP
R
W
2Q R
R
_P la ns _V ol 1-
#3/0
#3/0
#6
DM
SPD
65KAGROUND BAR,
IN ENCLOSURE
R
AT
IN
G
P
ER
M
AN
U
FA
C
TU
R
ER
EXTERNAL
GROUND
SYSTEM
BUILDING
STEEL
TMGB ON TER
(RM 125)
BACKBOARD
MAIN
1200AF/1200AT/3P
100% RATED
WITH LSIG
PROTECTION
0A
F/
5A T/
3P
BUILDING MAIN SWITCHBOARD (MSB), 1200A, 480/277V, 65 KAIC, 3 PHASE, WITH FULL NEUTRAL & GROUND BUSES
FUSE
480 V 3O
REFERENCE TABLE
OF RESPONSIBILITY
ON SHEET ES503
FOR TRANSFORMER/
SCC INSTALLATION
SCOPE OF WORK
MSB-MAIN MSB-DIST
FUSED
CUTOUT
MTR-1
0A
F/
5A T/
3P
3 4 5 6
0A
F/
0A T/
3P
PANEL
PL-101
PANEL
PL-102
#6
T-1 112.5 KVA
PANEL
PL-201
#6
T-2 112.5 KVA
PANEL
PL-301
#6
T-3 112.5 KVA
PANEL
PL-401
#6
T-4 112.5 KVA
PANEL
MH-101
0A
F/
5A T/
3P 25 0A
F/
5A T/
3P 80 0A
F/
0A T/
3P
ELEV
CNTLR
EL
EV
AT
O
R
PANEL
PL-103
PANEL
PL-203
PANEL
PL-303
PANEL
PL-403
PANEL
PL-202
PANEL
PL-302
PANEL
PL-402
PANEL
PT-101
PANEL
PT-201
PANEL
PT-301
PANEL
PT-401
GENERAL NOTES
1. THE CONTRACTOR SHALL PROVIDE ALL EQUIPMENT, DEVICES,
APPURTENANCES, ETC. TO COMPLY WITH THE ELECTRICAL
ENERGY METERING REQUIREMENTS OF ASHRAE 90.1,
PARAGRAPH 8.4.3 IN ORDER TO MONITOR, RECORD, & REPORT
EACH OF THE FOLLOWING CATEGORIES INDEPENDENTLY:
A. TOTAL ELECTRICAL ENERGY
B. HVAC SYSTEMS
C. INTERIOR LIGHTING
D. EXTERIOR LIGHTING
E. RECEPTACLE CIRCUITS
2. FAULT CURRENT AMP INTERRUPTING CAPACITIES ARE
MINIMUM. IF STANDARD EQUIPMENT RATING IS GREATER,
PROVIDE STANDARD RATING.
3. PROVIDE FULL LENGTH 100% RATED NEUTRAL BAR AND A
GROUNDING BAR IN EACH SECTION OF THE
SWITCHBOARD/PANELBOARDS. PROVIDE MAIN BONDING
JUMPER IN ACCORDANCE WITH NFPA 70 PARAGRAPH 250.24
(B).
4. SEE SHEETS E-602 THRU E-607 FOR PANEL SCHEDULES.
5. PROVIDE ADDITIONAL SPARES AND SPACES AS SHOWN ON
PANEL SCHEDULES.
6. PROVIDE SURGE PROTECTION FOR EITHER THE CIRCUIT OR
THE PANEL THE CIRCUIT IS CONNECTED TO FOR ALL CIRCUITS
EXITING THE BUILDING SUCH AS BUT NOT LIMITED TO
EXTERIOR LIGHTING, EXTERIOR HVAC EQUIPMENT, AND CATV
EQUIPMENT CIRCUITS. ALSO PROVIDE SURGE PROTECTION
FOR ALL LIGHTING PANELS FEEDING BRANCH CIRCUITS WITH
LED FIXTURES. NOT ALL REQUIRED SURGE PROTECTIVE
DEVICES (SPDS) ARE SHOWN IN PANEL SCHEDULES. SPDS
MAY BE REQUIRED IN ADDITIONAL LOCATIONS BASED ON
FINAL EQUIPMENT INSTALLED AND ITS LOCATION. SURGE
PROTECTIVE DEVICES SHALL BE FED BY A DEDICATED
BREAKER AND INSTALLED EXTERNAL TO PANELBOARDS IN A
SEPARATE ENCLOSURE AND EXTERNAL TO SWITCHBOARD
OR IN A SEPARATE METAL CLAD COMPARTMENT OF THE
SWITCHBOARD.
7. VERIFY AND CHANGE AS NECESSARY THE CIRCUIT BREAKER
RATING, FEEDER, AND CONDUIT SIZES FOR ACTUAL
EQUIPMENT INSTALLED.
8. THE CONTRACTOR SHALL SUBMIT ARC FLASH HAZARD
ANALYSIS BASED ON INSTALLED CONDUIT AND CONDUCTOR
SIZE, TYPE AND LENGTH, EQUIPMENT SIZINGS, RATINGS,
ARRANGEMENTS, AND SETTINGS. SUBMIT AS PART OF
THE FAULT CURRENT AND PROTECTIVE COORDINATION
STUDY ALONG WITH THE SYSTEM MODEL. CONTRACTOR
SHALL PROVIDE ARC FLASH LABELS ON ALL PANELS
INDICATING THE ARC FLASH HAZARD LEVEL BASED ON THE
RESULTS FROM THE ARC FLASH HAZARD ANALYSIS. ADJUST
AIC RATINGS OF EQUIPMENT REQUIRED BASED ON ACTUAL
EQUIPMENT RATINGS.
9. SERIES RATED AND PLUG-IN CIRCUIT BREAKERS ARE
PROHIBITED.
10. PROVIDE ARC FLASH WARNING SIGNS ON SWITCHBOARDS,
PANELBOARDS, INDUSTRIAL CONTROL PANELS, METER
SOCKET ENCLOSURES, AND MOTOR CONTROL CENTERS AS
REQUIRED PER NFPA 70 (NEC) ARTICLE 110.16. REFERENCE
NFPA 70 ARTICLE 110.16, NFPA 70E ARTICLE 130.3, AND UFC
3-560-01, ELECTRICAL SAFETY, O & M.
11. PROVIDE ELECTRONIC TRIP BREAKERS WITH LSI SETTINGS
FOR ALL SWITCHBOARD/PANELBOARD BREAKERS SERVING
SUB-PANELS.
12. ELEVATOR CIRCUIT BREAKER DISCONNECT SHALL BE
PROVIDED WITH INTEGRAL SHUNT TRIP AND FIRE ALARM
INTERFACE.
#4
T-5 150 KVA
PANEL
ML-101
PANEL
ML-201
PANEL
ML-401
PANEL
MH-401
1 1 1 1 2 2
SU
BM
ET
ER
IN
G
3P
0A
F/
5A T/
3P
PANEL
PH-101
PANEL
PH-301
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
LO
U
IS
VI
LL
E
D
IS
TR
IC
T
D
R M
AR
TI
N L
U
TH
ER
K
IN
G
J R
P
LA
C E
LO
U
IS
VI
LL
E, K Y
EAST
JA
N
C
ER
TI
FI
ED
F
IN
AL
FT
. M cC O
Y, W
I C
O
LL
EC
TI
VE
T
R
AI
N
IN
G O
FF
IC
ER
S
Q U
AR
TE
R S
EA
ST
PN
FY
, P
VO
LU
M
E
0F
C :\U se rs
\H 2E
D D
LF
A\
D oc um en ts \5
1_ R ev it2
0_
E_
TT
O Q
_H 2E
D D
LF
A.
rv t
4/ 9/
:5
7:
P M
E-601
O N
E-
LI
N E
D
IA
G R
AM
S
AN
D
P
AN
EL
S
C H
ED
U
LE
S
L.
AL
EX
AN
D
ER
L.
AL
EX
AN
D
ER
J.
M
O O
R E
NOT TO SCALE1
ELECTRICAL ONE-LINE DIAGRAM AND
MECHANICAL FEEDER SCHEDULE
KEY NOTES
1 PROVIDE ELECTRONIC MAIN BREAKER WITH METERING
INFORMATION OUTPUT TO THE SUBMETERING SYSTEM
FOR RECEPTACLE LOADS.
2 PROVIDE ELECTRONIC MAIN BREAKER WITH METERING
INFORMATION OUTPUT TO THE SUBMETERING SYSTEM
FOR HVAC/MECHANICAL LOADS.
3 CURRENTLY, FT. MCCOY HAS NO EBCS AND THUS ALL
METERING IS CURRENTLY ONLY REPORTED TO MDMS -
EEDRS THROUGH FT. MCCOY NEC INFRASTRUCTURE AND
TRIDIUM NIAGARA BUILDING POINT OF CONNECTION
(BPOC).
4 IF SOLAR OPTION IS SELECTED, INSTALL/CONNECT SOLAR
PV SYSTEM WITH SUPPLY-SIDE SOURCE CONNECTION
PER NEC 705.11 AND IN ACCORDANCE WITH
EXCEL/WISCONSIN GRID CONNECTION REQUIREMENTS.
CONNECTION TO BE MADE OUTSIDE BUILDING (AT
METER/SCC) AS REQUIRED AND/OR PERMITTED BY XCEL.
REFERENCE SITE PLAN ES101 AND SPECS FOR ARRAY
LOCATION AND REQUIREMENTS.
5 PROVIDE ELECTRONIC MAIN BREAKER WITH METERING
INFORMATION OUTPUT TO THE SUBMETERING SYSTEM
FOR LIGHTING LOADS.
ONE-LINE FEEDER SCHEDULE
Notes Panel Load Voltage Wire Size Conduit
Size
T-1 PL-101 208 V 2 runs of 3-#3/0, 1-#3/0, 1-#3
2 1/2"
T-2 PL-201 208 V 2 runs of 3-#3/0, 1-#3/0, 1-#3
2 1/2"
T-3 PL-301 208 V 2 runs of 3-#3/0, 1-#3/0, 1-#3
2 1/2"
T-4 PL-401 208 V 2 runs of 3-#3/0, 1-#3/0, 1-#3
2 1/2"
ML-101 ML-201 208 V 3-#3, 1-#3, 1-#8 1 1/2"
ML-101 ML-401 208 V 3-#3, 1-#3, 1-#8 1 1/2"
PH-101 PH-301 480 V 3-#6, 1-#6, 1-#10 1 1/2"
PL-101 1st Floor Quarters Receptacle Panel PL-102 208 V 3-#3, 1-#3, 1-#8 1 1/2" PL-101 Telecom Room Panel PT-101 208 V 3-#3, 1-#3, 1-#8 1 1/2" PL-201 2nd Floor Quarters Receptacle Panel PL-202 208 V 3-#3, 1-#3, 1-#8 1 1/2" PL-201 Telecom Room Panel PT-201 208 V 3-#3, 1-#3, 1-#8 1 1/2" PL-301 3rd Floor Quarters Receptacle Panel PL-302 208 V 3-#3, 1-#3, 1-#8 1 1/2" PL-301 Telecom Room Panel PT-301 208 V 3-#3, 1-#3, 1-#8 1 1/2" PL-401 4th Floor Quarters Receptacle Panel PL-402 208 V 3-#3, 1-#3, 1-#8 1 1/2" PL-401 Telecom Room Panel PT-401 208 V 3-#3, 1-#3, 1-#8 1 1/2"
ONE-LINE FEEDER SCHEDULE
Notes Panel Load Voltage Wire Size Conduit
Size
From Service Transformer Secondary
MSB-MAIN Entire TTOQ Building 480 V 4 runs of 3-#350, 1-#350, 1-#3/0
5"
MSB-DIST MH-101 480 V 3 runs of 3-#300, 1-#300, 1-#1/0
3 1/2"
T-5 ML101 208 V 2 runs of 3-#350, 1-#350, 1-#1
3 1/2"
MH-101 T-5 480 V 3-#4/0, 1-#4/0, 1-#4 2 1/2"
MH-101 MH-401 480 V 3-#1, 1-#1, 1-#6 2 1/2"
MSB-DIST T-1 480 V 3-#2/0, 1-#2/0, 1-#6 2 1/2"
MSB-DIST T-2 480 V 3-#2/0, 1-#2/0, 1-#6 2 1/2"
MSB-DIST T-3 480 V 3-#2/0, 1-#2/0, 1-#6 2 1/2"
MSB-DIST PH-101 480 V 3-#4/0, 1-#4/0, 1-#4 2 1/2"
MSB-DIST T-4 480 V 3-#2/0, 1-#2/0, 1-#6 2 1/2"
PL-101 1st Floor Laundry Panel PL-103 208 V 3-#4/0, 1-#4/0, 1-#4 2 1/2" PL-201 2nd Floor Laundry Panel PL-203 208 V 3-#4/0, 1-#4/0, 1-#4 2 1/2" PL-301 3rd Floor Laundry Panel PL-303 208 V 3-#4/0, 1-#4/0, 1-#4 2 1/2" PL-401 4th Floor Laundry Panel PL-403 208 V 3-#4/0, 1-#4/0, 1-#4 2 1/2"
AP
R
AM
EN
D M
EN
T
W
2Q R
R
_P la ns _V ol 1-
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
LO
U
IS
VI
LL
E
D
IS
TR
IC
T
D
R M
AR
TI
N L
U
TH
ER
K
IN
G
J R
P
LA
C E
LO
U
IS
VI
LL
E, K Y
EAST
JA
N
C
ER
TI
FI
ED
F
IN
AL
FT
. M cC O
Y, W
I C
O
LL
EC
TI
VE
T
R
AI
N
IN
G O
FF
IC
ER
S
Q U
AR
TE
R S
EA
ST
PN
FY
, P
VO
LU
M
E
0F
C :\U se rs
\H 2E
D D
LF
A\
D oc um en ts \5
1_ R ev it2
0_
E_
TT
O Q
_H 2E
D D
LF
A.
rv t
4/ 9/
:5
0:
P M
E-602
PA
N
EL
S
C H
ED
U
LE
S
L.
AL
EX
AN
D
ER
L.
AL
EX
AN
D
ER
J.
M
O O
R E
1. PROVIDE COMBINATION-TYPE AFCI PROTECTION FOR BRANCH CIRCUITS SUPPLYING RECEPTACLES IN SLEEPING QUARTERS, HALLWAYS, AND RESTROOMS.
2. RCPT LOADS ARE FROM 1ST FLOOR LAUNDRY ONLY. LITES INDICATE LOAD FROM CAN LIGHTING ONLY. (TYP)
Total Est. Demand Current: 177 A Total Conn. Current: 243 A
Total Est. Demand: 63797 VA RCPT 30288 VA 20144 VA Total Conn. Load: 87620 VA Receptacle 37400 VA 23700 VA Load Classification Connected Load Estimated Demand Panel Totals
Total Amps: 276 A 222 A 236 A Total Load: 32936 VA 26583 VA 28103 VA
41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42
39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40
37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38
35 SPARE 20 A 1 1000... 0 VA -- -- SPACE 36
33 SPACE -- -- 0 VA 0 VA -- -- SPACE 34
31 SPACE -- -- 0 VA 1000... 1 20 A SPARE 32
29 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 30
27 1st Floor Corridor Rec. 20 A 1 360 VA 1000... 1 20 A SPARE 28 25 1st Floor Corridor/N. Stair Rec. 20 A 1 720 VA 540 VA 1 20 A 1st Floor Corridor Rec./NW Exterior Rec. 26 23 1st Floor Janitor/South Hall Rec. 20 A 1 900 VA 360 VA 1 20 A 1st Floor Stairway Receptacles 24 21 Vestibule/ Company Storage Unswitched Rec. 20 A 1 720 VA 900 VA 1 20 A 1st Floor Company Storage, Switched Rec. 22 19 1st Floor Company Storage Counter Top Rec. 20 A 1 360 VA 720 VA 1 20 A 1st Floor Mechanical Room Receptacles 20 17 1st Floor Company Storage Vending... 20 A 1 180 VA 180 VA 1 20 A 1st Floor Company Storage Refrigerator Rec. 18 15 1st Floor Company Storage Vending... 20 A 1 180 VA 180 VA 1 20 A 1st Floor Company Storage Vending... 16
13 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 14
11 3080... 180 VA 1 20 A Elevator Pit Sump Pump Receptacle 12 9 4220... 720 VA 1 20 A Elevator Pit Receptacles 10
Telecom Room Panel PT-101 100 A 3 4220... 360 VA 1 20 A 1st Floor Electrical Room Receptacles 8
5 9020... 1121... 6 3 7760... 1055... 4
1st Floor Quarters Receptacle Panel PL-102 100 A 3 9200... 1384...
3 225 A 1st Floor Laundry Panel PL-103
CKT Load Name Trip Poles A B C Poles Trip Load Name CKT
Notes:
Enclosure: NEMA 1 MCB Rating: 400 A Mounting: SURFACE Wires: 4 Mains Rating: 400 A
Supply From: T-1 Phases: 3 Mains Type: MAIN CB Location: ELECTRICAL 127 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL
Branch Panel: PL-101
1. PROVIDE COMBINATION-TYPE AFCI PROTECTION FOR BRANCH CIRCUITS SUPPLYING RECEPTACLES IN SLEEPING QUARTERS, HALLWAYS, AND RESTROOMS.
Total Est. Demand Current: 56 A
Total Conn. Current: 72 A Total Est. Demand: 20090 VA Total Conn. Load: 25980 VA
Receptacle 21780 VA 15890 VA Load Classification Connected Load Estimated Demand Panel Totals
Total Amps: 78 A 65 A 77 A Total Load: 9200 VA 7760 VA 9020 VA
41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42
39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40
37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38
35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36
33 SPACE -- -- 0 VA 0 VA -- -- SPACE 34
31 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 32
29 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 30
27 1st Floor Water Fountain 20 A 1 100 VA 100 VA 1 20 A 1st Floor Water Fountain 28 25 Room 121 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 121 Receptacles 26 23 Room 122 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 122 Receptacles 24 21 Room 120 Receptacles 20 A 1 540 VA 1080... 1 20 A Room 119 Receptacles 22 19 NE Exterior/WP Receptacle 20 A 1 180 VA 540 VA 1 20 A Room 120 Receptacles 20 17 Room 116 Receptacles 20 A 1 540 VA 1080... 1 20 A Room 117 Receptacles 18 15 Room 115 Receptacles 20 A 1 1080... 540 VA 1 20 A Room 118 Receptacles 16 13 Room 114 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 114 Receptacles 14 11 Room 112 Receptacles 20 A 1 1080... 1080... 1 20 A Room 113 Receptacles 12 9 Room 110 Receptacles 20 A 1 1080... 1080... 1 20 A Room 111 Receptacles 10 7 Room 108 Receptacles 20 A 1 1080... 1080... 1 20 A Room 109 Receptacles 8 5 Room 106 Receptacles 20 A 1 1080... 1080... 1 20 A Room 107 Receptacles 6 3 Room 104 Receptacles 20 A 1 1080... 1080... 1 20 A Room 105 Receptacles 4 1 Room 102 Receptacles 20 A 1 1080... 1080... 1 20 A Room 103 Receptacles 2
CKT Load Name Trip Poles A B C Poles Trip Load Name CKT
Notes:
Enclosure: NEMA 1 MCB Rating: 100 A Mounting: SURFACE Wires: 4 Mains Rating: 100 A
Supply From: PL-101 Phases: 3 Mains Type: MAIN CB Location: ELECTRICAL 127 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL
Branch Panel: PL-102
RCPT Designates Dryer Load Notes:
Total Est. Demand: 71 A Total Conn.: 99 A
RCPT 30288 VA 66.51% 20144 VA Total Est. Demand: 25470 VA Spare 4800 VA 100.00% 4800 VA Total Conn. Load: 35613 VA Receptacle 540 VA 100.00% 540 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 116 A 88 A 94 A Total Load: 13849 VA 10555 VA 11214 VA
23 SPACE -- -- 0 VA 0 VA -- -- SPACE 24
21 SPACE -- -- 0 VA 0 VA -- -- SPACE 22
19 SPARE 20 A 1 1200... 0 VA -- -- SPACE 20
17 SPARE 20 A 1 1200... 1200... 1 20 A SPARE 18
15 1st Floor Laundry-Washer (RCPT) 20 A 1 1440... 1200... 1 20 A SPARE 16 13 1st Floor Laundry-Washer (RCPT) 20 A 1 1440... 1440... 1 20 A 1st Floor Laundry-Washer (RCPT) 14 11 2500... 1440... 1 20 A 1st Floor Laundry-Washer (RCPT) 12
1st Floor Laundry-Dryer (RCPT) 35 A 2 2500... 540 VA 1 20 A GP Receptacles 10
7 2500... 2500... 8
1st Floor Laundry-Dryer (RCPT) 35 A 2 2500... 2500...
2 35 A 1st Floor Laundry-Dryer (RCPT)
3 2500... 2500... 4
1st Floor Laundry-Dryer (RCPT) 35 A 2 2500... 2500...
2 35 A 1st Floor Laundry-Dryer (RCPT)
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: NEMA 1 MCB Rating: 225 A Mounting: SURFACE Wires: 4 Mains Rating: 225 A
Supply From: PL-101 Phases: 3 Mains Type: MAIN CB Location: Space 130 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL
Branch Panel: PL-103
Notes:
Total Est. Demand: 32 A Total Conn.: 32 A
Total Est. Demand: 11520 VA Spare 4000 VA 100.00% 4000 VA Total Conn. Load: 11520 VA Receptacle 7520 VA 100.00% 7520 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 37 A 37 A 26 A Total Load: 4220 VA 4220 VA 3080 VA
23 SPACE -- -- 0 VA 0 VA -- -- SPACE 24
21 SPACE -- -- 0 VA 0 VA -- -- SPACE 22
19 SPACE -- -- 0 VA 0 VA -- -- SPACE 20
17 SPACE -- -- 0 VA 0 VA -- -- SPACE 18
15 SPACE -- -- 0 VA 0 VA -- -- SPACE 16
13 SPACE -- -- 0 VA 0 VA -- -- SPACE 14
11 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 12
9 2500... 1000... 1 20 A SPARE 10
208V - NEMA L6-20R Receptacle 20 A 2
2500... 1000... 1 20 A SPARE 8
5 NW Receptacles 20 A 1 540 VA 540 VA 1 20 A SE Receptacles 6 3 #2 Rack Receptacle 20 A 1 360 VA 360 VA 1 20 A #2 Rack Receptacle 4 1 #1 Rack Receptacle 20 A 1 360 VA 360 VA 1 20 A #1 Rack Receptacle 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: NEMA 1 MCB Rating: 100 A Mounting: SURFACE Wires: 4 Mains Rating: 100 A
Supply From: PL-101 Phases: 3 Mains Type: MAIN CB Location: TELECOM 125 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL
Branch Panel: PT-101
1 1
1 1
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
AP
R
AM
EN
D M
EN
T
W
2Q R
R
_P la ns _V ol 1-
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
LO
U
IS
VI
LL
E
D
IS
TR
IC
T
D
R M
AR
TI
N L
U
TH
ER
K
IN
G
J R
P
LA
C E
LO
U
IS
VI
LL
E, K Y
EAST
JA
N
C
ER
TI
FI
ED
F
IN
AL
FT
. M cC O
Y, W
I C
O
LL
EC
TI
VE
T
R
AI
N
IN
G O
FF
IC
ER
S
Q U
AR
TE
R S
EA
ST
PN
FY
, P
VO
LU
M
E
0F
C :\U se rs
\H 2E
D D
LF
A\
D oc um en ts \5
1_ R ev it2
0_
E_
TT
O Q
_H 2E
D D
LF
A.
rv t
4/ 9/
:5
0:
P M
E-603
PA
N
EL
S
C H
ED
U
LE
S
L.
AL
EX
AN
D
ER
L.
AL
EX
AN
D
ER
J.
M
O O
R E
1. PROVIDE COMBINATION-TYPE AFCI PROTECTION FOR BRANCH CIRCUITS SUPPLYING RECEPTACLES IN SLEEPING QUARTERS, HALLWAYS, AND RESTROOMS.
2. LOADS ARE FROM 1ST FLOOR LAUNDRY ONLY. LITES INDICATE LOAD FROM CAN LIGHTING ONLY. (TYP)
Total Est. Demand Current: 171 A Total Conn. Current: 229 A
Total Est. Demand: 61777 VA RCPT 30288 VA 20144 VA Total Conn. Load: 82382 VA Receptacle 30960 VA 20480 VA Load Classification Connected Load Estimated Demand Panel Totals
Total Amps: 255 A 224 A 212 A Total Load: 30358 VA 26643 VA 25384 VA
41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42
39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40
37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38
35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36
33 SPACE -- -- 0 VA 0 VA -- -- SPACE 34
31 SPACE -- -- 0 VA 0 VA -- -- SPACE 32
29 SPARE 20 A 1 1000... 0 VA -- -- SPACE 30
27 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 28
25 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 26
23 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 24
21 2nd Floor Corridor Rec. 20 A 1 360 VA 540 VA 1 20 A 2nd Floor Corridor/N. Stair Rec. 22 19 2nd Floor Company Storage Vending Rec. 20 A 1 180 VA 360 VA 1 20 A 2nd Floor Corridor Rec. 20 17 2nd Floor Company Storage Vending Rec. 20 A 1 180 VA 180 VA 1 20 A 2nd Floor Company Storage Vending Rec. 18 15 2nd Floor Company Storage Counter Top Rec. 20 A 1 360 VA 180 VA 1 20 A 2nd Floor Company Storage Refrigerator Rec. 16 13 2nd Floor Stairway Receptacles 20 A 1 900 VA 900 VA 1 20 A 2nd Floor Company Storage, Switched Rec. 14 11 1080... 720 VA 1 20 A 2nd Floor Mechanical Room Receptacles 12 9 2720... 1260... 1 20 A 2nd Floor Janitor/Recycle/South Hall Rec. 10
Telecom Room Panel PT-201 100 A 3 2720... 360 VA 1 20 A 2nd Floor Electrical Room Receptacles 8
5 9020... 1121... 6 3 8860... 1037... 4
2nd Floor Quarters Receptacle Panel PL-202 100 A 3 9120... 1384...
3 225 A 2nd Floor Laundry Panel PL-203
CKT Load Name Trip Poles A B C Poles Trip Load Name CKT
Notes:
Enclosure: NEMA 1 MCB Rating: 400 A Mounting: SURFACE Wires: 4 Mains Rating: 400 A
Supply From: T-2 Phases: 3 Mains Type: MAIN CB Location: ELECTRICAL 227 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL
Branch Panel: PL-201
1. PROVIDE COMBINATION-TYPE AFCI PROTECTION FOR BRANCH CIRCUITS SUPPLYING RECEPTACLES IN SLEEPING QUARTERS, HALLWAYS, AND RESTROOMS.
2. 10A BOOSTER PANELS ARE STANDARD AT FT. MCCOY. 600VA PER PANEL - ESTIMATING UP TO (2) PER FLOOR.
Total Est. Demand Current: 59 A Total Conn. Current: 75 A
Total Est. Demand: 21200 VA Total Conn. Load: 27000 VA
Receptacle 21600 VA 15800 VA Load Classification Connected Load Estimated Demand Panel Totals
Total Amps: 76 A 74 A 75 A Total Load: 9120 VA 8860 VA 9020 VA
41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42
39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40
37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38
35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36
33 SPACE -- -- 0 VA 0 VA -- -- SPACE 34
31 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 32
29 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 30
27 2nd Floor FA/MN Booster Panels (Note 1) 20 A 1 1200... 100 VA 1 20 A 2nd Floor Water Fountain 28 25 Room 221 Receptacles 20 A 1 540 VA 100 VA 1 20 A 2nd Floor Water Fountain 26 23 Room 220 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 221 Receptacles 24 21 Room 219 Receptacles 20 A 1 1080... 540 VA 1 20 A Room 220 Receptacles 22 19 Room 218 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 218 Receptacles 20 17 Room 216 Receptacles 20 A 1 540 VA 1080... 1 20 A Room 217 Receptacles 18 15 Room 215 Receptacles 20 A 1 1080... 540 VA 1 20 A Room 216 Receptacles 16 13 Room 214 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 214 Receptacles 14 11 Room 212 Receptacles 20 A 1 1080... 1080... 1 20 A Room 213 Receptacles 12 9 Room 210 Receptacles 20 A 1 1080... 1080... 1 20 A Room 211 Receptacles 10 7 Room 208 Receptacles 20 A 1 1080... 1080... 1 20 A Room 209 Receptacles 8 5 Room 206 Receptacles 20 A 1 1080... 1080... 1 20 A Room 207 Receptacles 6 3 Room 204 Receptacles 20 A 1 1080... 1080... 1 20 A Room 205 Receptacles 4 1 Room 202 Receptacles 20 A 1 1080... 1080... 1 20 A Room 203 Receptacles 2
CKT Load Name Trip Poles A B C Poles Trip Load Name CKT
Notes:
Enclosure: NEMA 1 MCB Rating: 100 A Mounting: SURFACE Wires: 4 Mains Rating: 100 A
Supply From: PL-201 Phases: 3 Mains Type: MAIN CB Location: ELECTRICAL 227 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL
Branch Panel: PL-202
RCPT Designates Dryer Load Notes:
Total Est. Demand: 70 A Total Conn.: 98 A
RCPT 30288 VA 66.51% 20144 VA Total Est. Demand: 25290 VA Spare 4800 VA 100.00% 4800 VA Total Conn. Load: 35433 VA Receptacle 360 VA 100.00% 360 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 116 A 86 A 95 A Total Load: 13849 VA 10375 VA 11214 VA
23 SPACE -- -- 0 VA 0 VA -- -- SPACE 24
21 SPACE -- -- 0 VA 0 VA -- -- SPACE 22
19 SPARE 20 A 1 1200... 0 VA -- -- SPACE 20
17 SPARE 20 A 1 1200... 1200... 1 20 A SPARE 18
15 2nd Floor Laundry-Washer (RCPT) 20 A 1 1440... 1200... 1 20 A SPARE 16 13 2nd Floor Laundry-Washer (RCPT) 20 A 1 1440... 1440... 1 20 A 2nd Floor Laundry-Washer (RCPT) 14 11 2500... 1440... 1 20 A 2nd Floor Laundry-Washer (RCPT) 12
2nd Floor Laundry-Dryer (RCPT) 35 A 2 2500... 360 VA 1 20 A GP Receptacles 10
7 2500... 2500... 8
2nd Floor Laundry-Dryer (RCPT) 35 A 2 2500... 2500...
2 35 A 2nd Floor Laundry-Dryer (RCPT)
3 2500... 2500... 4
2nd Floor Laundry-Dryer (RCPT) 35 A 2 2500... 2500...
2 35 A 2nd Floor Laundry-Dryer (RCPT)
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: NEMA 1 MCB Rating: 225 A Mounting: SURFACE Wires: 4 Mains Rating: 225 A
Supply From: PL-201 Phases: 3 Mains Type: MAIN CB Location: LAUNDRY 226 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL
Branch Panel: PL-203
Notes:
Total Est. Demand: 18 A Total Conn.: 18 A
Total Est. Demand: 6520 VA Spare 4000 VA 100.00% 4000 VA Total Conn. Load: 6520 VA Receptacle 2520 VA 100.00% 2520 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 25 A 25 A 9 A Total Load: 2720 VA 2720 VA 1080 VA
23 SPACE -- -- 0 VA 0 VA -- -- SPACE 24
21 SPACE -- -- 0 VA 0 VA -- -- SPACE 22
19 SPACE -- -- 0 VA 0 VA -- -- SPACE 20
17 SPACE -- -- 0 VA 0 VA -- -- SPACE 18
15 SPACE -- -- 0 VA 0 VA -- -- SPACE 16
13 SPACE -- -- 0 VA 0 VA -- -- SPACE 14
11 SPACE -- -- 0 VA 0 VA -- -- SPACE 12
9 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 10
7 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 8
5 NW Receptacles 20 A 1 540 VA 540 VA 1 20 A SE Receptacles 6 3 #2 Rack Receptacle 20 A 1 360 VA 360 VA 1 20 A #2 Rack Receptacle 4 1 #1 Rack Receptacle 20 A 1 360 VA 360 VA 1 20 A #1 Rack Receptacle 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: NEMA 1 MCB Rating: 100 A Mounting: SURFACE Wires: 4 Mains Rating: 100 A
Supply From: PL-201 Phases: 3 Mains Type: MAIN CB Location: TELECOM 225 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL
Branch Panel: PT-201
1 1
AP
R
AM
EN
D M
EN
T
W
2Q R
R
_P la ns _V ol 1-
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
LO
U
IS
VI
LL
E
D
IS
TR
IC
T
D
R M
AR
TI
N L
U
TH
ER
K
IN
G
J R
P
LA
C E
LO
U
IS
VI
LL
E, K Y
EAST
JA
N
C
ER
TI
FI
ED
F
IN
AL
FT
. M cC O
Y, W
I C
O
LL
EC
TI
VE
T
R
AI
N
IN
G O
FF
IC
ER
S
Q U
AR
TE
R S
EA
ST
PN
FY
, P
VO
LU
M
E
0F
C :\U se rs
\H 2E
D D
LF
A\
D oc um en ts \5
1_ R ev it2
0_
E_
TT
O Q
_H 2E
D D
LF
A.
rv t
4/ 9/
:5
0:
P M
E-604
PA
N
EL
S
C H
ED
U
LE
S
L.
AL
EX
AN
D
ER
L.
AL
EX
AN
D
ER
J.
M
O O
R E
1. PROVIDE COMBINATION-TYPE AFCI PROTECTION FOR BRANCH CIRCUITS SUPPLYING RECEPTACLES IN SLEEPING QUARTERS, HALLWAYS, AND RESTROOMS.
2. RCPT LOADS ARE FROM 3RD FLOOR LAUNDRY ONLY.
Total Est. Demand Current: 171 A Total Conn. Current: 229 A
Total Est. Demand: 61777 VA RCPT 30288 VA 20144 VA Total Conn. Load: 82382 VA Receptacle 30960 VA 20480 VA Load Classification Connected Load Estimated Demand Panel Totals
Total Amps: 261 A 215 A 212 A Total Load: 31257 VA 25744 VA 25384 VA
41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42
39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40
37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38
35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36
33 SPACE -- -- 0 VA 0 VA -- -- SPACE 34
31 SPACE -- -- 0 VA 0 VA -- -- SPACE 32
29 SPARE 20 A 1 1000... 0 VA -- -- SPACE 30
27 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 28
25 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 26
23 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 24
21 3rd Floor Corridor Receptacles 20 A 1 360 VA 540 VA 1 20 A 3rd Floor Corridor/N. Stair Rec. 22 19 3rd Floor Company Storage Vending Rec. 20 A 1 180 VA 900 VA 1 20 A 3rd Floor Stairway Receptacles 20 17 3rd Floor Company Storage Vending Rec. 20 A 1 180 VA 180 VA 1 20 A 3rd Floor Company Storage Vending Rec. 18 15 3rd Floor Company Storage Counter Top Rec. 20 A 1 360 VA 180 VA 1 20 A 3rd Floor Company Storage Refrigerator Rec. 16 13 3rd Floor Janitor/Recycle/South Hall Rec. 20 A 1 1260... 900 VA 1 20 A 3rd Floor Company Storage, Switched Rec. 14 11 1080... 720 VA 1 20 A 3rd Floor Mechanical Room Receptacles 12 9 2720... 360 VA 1 20 A 3rd Floor Corridor Receptacles 10
Telecom Room Panel PT-301 100 A 3 2720... 360 VA 1 20 A 3rd Floor Electrical Room Receptacles 8
5 9020... 1121... 6 3 8860... 1037... 4
3rd Floor Quarters Receptacle Panel PL-302 100 A 3 9120... 1384...
3 225 A 3rd Floor Laundry Panel PL-303
CKT Load Name Trip Poles A B C Poles Trip Load Name CKT
Notes:
Enclosure: NEMA 1 MCB Rating: 400 A Mounting: SURFACE Wires: 4 Mains Rating: 400 A
Supply From: T-3 Phases: 3 Mains Type: MAIN CB Location: ELECTRICAL 327 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL
Branch Panel: PL-301
1. PROVIDE COMBINATION-TYPE AFCI PROTECTION FOR BRANCH CIRCUITS SUPPLYING RECEPTACLES IN SLEEPING QUARTERS, HALLWAYS, AND RESTROOMS.
2. 10A BOOSTER PANELS ARE STANDARD AT FT. MCCOY. 600VA PER PANEL - ESTIMATING UP TO (2) PER FLOOR.
Total Est. Demand Current: 59 A Total Conn. Current: 75 A
Total Est. Demand: 21200 VA Total Conn. Load: 27000 VA
Receptacle 21600 VA 15800 VA Load Classification Connected Load Estimated Demand Panel Totals
Total Amps: 76 A 74 A 75 A Total Load: 9120 VA 8860 VA 9020 VA
41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42
39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40
37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38
35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36
33 SPACE -- -- 0 VA 0 VA -- -- SPACE 34
31 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 32
29 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 30
27 3rd Floor FA/MN Booster Panels (Note 1) 20 A 1 1200... 100 VA 1 20 A 3rd Floor Water Fountain 28 25 Room 321 Receptacles 20 A 1 540 VA 100 VA 1 20 A 3rd Floor Water Fountain 26 23 Room 320 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 321 Receptacles 24 21 Room 319 Receptacles 20 A 1 1080... 540 VA 1 20 A Room 320 Receptacles 22 19 Room 318 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 318 Receptacles 20 17 Room 316 Receptacles 20 A 1 540 VA 1080... 1 20 A Room 317 Receptacles 18 15 Room 315 Receptacles 20 A 1 1080... 540 VA 1 20 A Room 316 Receptacles 16 13 Room 314 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 314 Receptacles 14 11 Room 312 Receptacles 20 A 1 1080... 1080... 1 20 A Room 313 Receptacles 12 9 Room 310 Receptacles 20 A 1 1080... 1080... 1 20 A Room 311 Receptacles 10 7 Room 308 Receptacles 20 A 1 1080... 1080... 1 20 A Room 309 Receptacles 8 5 Room 306 Receptacles 20 A 1 1080... 1080... 1 20 A Room 307 Receptacles 6 3 Room 304 Receptacles 20 A 1 1080... 1080... 1 20 A Room 305 Receptacles 4 1 Room 302 Receptacles 20 A 1 1080... 1080... 1 20 A Room 303 Receptacles 2
CKT Load Name Trip Poles A B C Poles Trip Load Name CKT
Notes:
Enclosure: NEMA 1 MCB Rating: 100 A Mounting: SURFACE Wires: 4 Mains Rating: 100 A
Supply From: PL-301 Phases: 3 Mains Type: MAIN CB Location: ELECTRICAL 327 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL
Branch Panel: PL-302
RCPT Designates Dryer Load Notes:
Total Est. Demand: 70 A Total Conn.: 98 A
RCPT 30288 VA 66.51% 20144 VA Total Est. Demand: 25290 VA Spare 4800 VA 100.00% 4800 VA Total Conn. Load: 35433 VA Receptacle 360 VA 100.00% 360 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 116 A 86 A 95 A Total Load: 13849 VA 10375 VA 11214 VA
23 SPACE -- -- 0 VA 0 VA -- -- SPACE 24
21 SPACE -- -- 0 VA 0 VA -- -- SPACE 22
19 SPARE 20 A 1 1200... 0 VA -- -- SPACE 20
17 SPARE 20 A 1 1200... 1200... 1 20 A SPARE 18
15 3rd Floor Laundry-Washer (RCPT) 20 A 1 1440... 1200... 1 20 A SPARE 16 13 3rd Floor Laundry-Washer (RCPT) 20 A 1 1440... 1440... 1 20 A 3rd Floor Laundry-Washer (RCPT) 14 11 2500... 1440... 1 20 A 3rd Floor Laundry-Washer (RCPT) 12
3rd Floor Laundry-Dryer (RCPT) 35 A 2 2500... 360 VA 1 20 A GP Receptacles 10
7 2500... 2500... 8
3rd Floor Laundry-Dryer (RCPT) 35 A 2 2500... 2500...
2 35 A 3rd Floor Laundry-Dryer (RCPT)
3 2500... 2500... 4
3rd Floor Laundry-Dryer (RCPT) 35 A 2 2500... 2500...
2 35 A 3rd Floor Laundry-Dryer (RCPT)
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: NEMA 1 MCB Rating: 225 A Mounting: SURFACE Wires: 4 Mains Rating: 225 A
Supply From: PL-301 Phases: 3 Mains Type: MAIN CB Location: LAUNDRY 326 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL
Branch Panel: PL-303
Notes:
Total Est. Demand: 18 A Total Conn.: 18 A
Total Est. Demand: 6520 VA Spare 4000 VA 100.00% 4000 VA Total Conn. Load: 6520 VA Receptacle 2520 VA 100.00% 2520 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 25 A 25 A 9 A Total Load: 2720 VA 2720 VA 1080 VA
23 SPACE -- -- 0 VA 0 VA -- -- SPACE 24
21 SPACE -- -- 0 VA 0 VA -- -- SPACE 22
19 SPACE -- -- 0 VA 0 VA -- -- SPACE 20
17 SPACE -- -- 0 VA 0 VA -- -- SPACE 18
15 SPACE -- -- 0 VA 0 VA -- -- SPACE 16
13 SPACE -- -- 0 VA 0 VA -- -- SPACE 14
11 SPACE -- -- 0 VA 0 VA -- -- SPACE 12
9 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 10
7 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 8
5 NW Receptacles 20 A 1 540 VA 540 VA 1 20 A SE Receptacles 6 3 #2 Rack Receptacle 20 A 1 360 VA 360 VA 1 20 A #2 Rack Receptacle 4 1 #1 Rack Receptacle 20 A 1 360 VA 360 VA 1 20 A #1 Rack Receptacle 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: NEMA 1 MCB Rating: 100 A Mounting: SURFACE Wires: 4 Mains Rating: 100 A
Supply From: PL-301 Phases: 3 Mains Type: MAIN CB Location: TELECOM 325 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL
Branch Panel: PT-301
1 1
AP
R
AM
EN
D M
EN
T
W
2Q R
R
_P la ns _V ol 1-
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
LO
U
IS
VI
LL
E
D
IS
TR
IC
T
D
R M
AR
TI
N L
U
TH
ER
K
IN
G
J R
P
LA
C E
LO
U
IS
VI
LL
E, K Y
EAST
JA
N
C
ER
TI
FI
ED
F
IN
AL
FT
. M cC O
Y, W
I C
O
LL
EC
TI
VE
T
R
AI
N
IN
G O
FF
IC
ER
S
Q U
AR
TE
R S
EA
ST
PN
FY
, P
VO
LU
M
E
0F
C :\U se rs
\H 2E
D D
LF
A\
D oc um en ts \5
1_ R ev it2
0_
E_
TT
O Q
_H 2E
D D
LF
A.
rv t
4/ 9/
:5
0:
P M
E-605
PA
N
EL
S
C H
ED
U
LE
S
L.
AL
EX
AN
D
ER
L.
AL
EX
AN
D
ER
J.
M
O O
R E
1. PROVIDE COMBINATION-TYPE AFCI PROTECTION FOR BRANCH CIRCUITS SUPPLYING RECEPTACLES IN SLEEPING QUARTERS, HALLWAYS, AND RESTROOMS.
2. RCPT LOADS ARE FROM 4TH FLOOR LAUNDRY ONLY.
Total Est. Demand Current: 171 A Total Conn. Current: 228 A
Total Est. Demand: 61597 VA RCPT 30288 VA 20144 VA Total Conn. Load: 82022 VA Receptacle 30600 VA 20300 VA Load Classification Connected Load Estimated Demand Panel Totals
Total Amps: 253 A 222 A 212 A Total Load: 30178 VA 26463 VA 25384 VA
41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42
39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40
37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38
35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36
33 SPACE -- -- 0 VA 0 VA -- -- SPACE 34
31 SPACE -- -- 0 VA 0 VA -- -- SPACE 32
29 SPARE 20 A 1 1000... 0 VA -- -- SPACE 30
27 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 28
25 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 26
23 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 24
21 4th Floor Corridor Receptacles 20 A 1 360 VA 360 VA 1 20 A 4th Floor Corridor/N. Stair Rec. 22 19 4th Floor Company Storage Vending Rec. 20 A 1 180 VA 360 VA 1 20 A 4th Floor Corridor Receptacles 20 17 4th Floor Company Storage Vending Rec. 20 A 1 180 VA 180 VA 1 20 A 4th Floor Company Storage Vending Rec. 18 15 4th Floor Company Storage Counter Top Rec. 20 A 1 360 VA 180 VA 1 20 A 4th Floor Company Storage Refrigerator Rec. 16 13 4th Floor Stairway Receptacles 20 A 1 720 VA 900 VA 1 20 A 4th Floor Company Storage, Switched Rec. 14 11 1080... 720 VA 1 20 A 4th Floor Mechanical Room Receptacles 12 9 2720... 1260... 1 20 A 4th Floor Janitor/Recycle/South Hall Rec. 10
Telecom Room Panel PT-401 100 A 3 2720... 360 VA 1 20 A 4th Floor Electrical Room Receptacles 8
5 9020... 1121... 6 3 8860... 1037... 4
4th Floor Quarters Receptacle Panel PL-402 100 A 3 9120... 1384...
3 225 A 4th Floor Laundry Panel PL-403
CKT Load Name Trip Poles A B C Poles Trip Load Name CKT
Notes:
Enclosure: NEMA 1 MCB Rating: 400 A Mounting: SURFACE Wires: 4 Mains Rating: 400 A
Supply From: T-4 Phases: 3 Mains Type: MAIN CB Location: ELECTRICAL 427 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL
Branch Panel: PL-401
1. PROVIDE COMBINATION-TYPE AFCI PROTECTION FOR BRANCH CIRCUITS SUPPLYING RECEPTACLES IN SLEEPING QUARTERS, HALLWAYS, AND RESTROOMS.
2. 10A BOOSTER PANELS ARE STANDARD AT FT. MCCOY. 600VA PER PANEL - ESTIMATING UP TO (2) PER FLOOR.
Total Est. Demand Current: 59 A Total Conn. Current: 75 A
Total Est. Demand: 21200 VA Total Conn. Load: 27000 VA
Receptacle 21600 VA 15800 VA Load Classification Connected Load Estimated Demand Panel Totals
Total Amps: 76 A 74 A 75 A Total Load: 9120 VA 8860 VA 9020 VA
41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42
39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40
37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38
35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36
33 SPACE -- -- 0 VA 0 VA -- -- SPACE 34
31 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 32
29 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 30
27 4th Floor FA/MN Booster Panels (Note 1) 20 A 1 1200... 100 VA 1 20 A 4th Floor Water Fountain 28 25 Room 421 Receptacles 20 A 1 540 VA 100 VA 1 20 A 4th Floor Water Fountain 26 23 Room 420 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 421 Receptacles 24 21 Room 419 Receptacles 20 A 1 1080... 540 VA 1 20 A Room 420 Receptacles 22 19 Room 418 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 418 Receptacles 20 17 Room 416 Receptacles 20 A 1 540 VA 1080... 1 20 A Room 417 Receptacles 18 15 Room 415 Receptacles 20 A 1 1080... 540 VA 1 20 A Room 416 Receptacles 16 13 Room 414 Receptacles 20 A 1 540 VA 540 VA 1 20 A Room 414 Receptacles 14 11 Room 412 Receptacles 20 A 1 1080... 1080... 1 20 A Room 413 Receptacles 12 9 Room 410 Receptacles 20 A 1 1080... 1080... 1 20 A Room 411 Receptacles 10 7 Room 408 Receptacles 20 A 1 1080... 1080... 1 20 A Room 409 Receptacles 8 5 Room 406 Receptacles 20 A 1 1080... 1080... 1 20 A Room 407 Receptacles 6 3 Room 404 Receptacles 20 A 1 1080... 1080... 1 20 A Room 405 Receptacles 4 1 Room 402 Receptacles 20 A 1 1080... 1080... 1 20 A Room 403 Receptacles 2
CKT Load Name Trip Poles A B C Poles Trip Load Name CKT
Notes:
Enclosure: NEMA 1 MCB Rating: 100 A Mounting: SURFACE Wires: 4 Mains Rating: 100 A
Supply From: PL-401 Phases: 3 Mains Type: MAIN CB Location: ELECTRICAL 427 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL
Branch Panel: PL-402
RCPT Designates Dryer Load Notes:
Total Est. Demand: 70 A Total Conn.: 98 A
RCPT 30288 VA 66.51% 20144 VA Total Est. Demand: 25290 VA Spare 4800 VA 100.00% 4800 VA Total Conn. Load: 35433 VA Receptacle 360 VA 100.00% 360 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 116 A 86 A 95 A Total Load: 13849 VA 10375 VA 11214 VA
23 SPACE -- -- 0 VA 0 VA -- -- SPACE 24
21 SPACE -- -- 0 VA 0 VA -- -- SPACE 22
19 SPARE 20 A 1 1200... 0 VA -- -- SPACE 20
17 SPARE 20 A 1 1200... 1200... 1 20 A SPARE 18
15 4th Floor Laundry-Washer (RCPT) 20 A 1 1440... 1200... 1 20 A SPARE 16 13 4th Floor Laundry-Washer (RCPT) 20 A 1 1440... 1440... 1 20 A 4th Floor Laundry-Washer (RCPT) 14 11 2500... 1440... 1 20 A 4th Floor Laundry-Washer (RCPT) 12
4th Floor Laundry-Dryer (RCPT) 35 A 2 2500... 360 VA 1 20 A GP Receptacles 10
7 2500... 2500... 8
4th Floor Laundry-Dryer (RCPT) 35 A 2 2500... 2500...
2 35 A 4th Floor Laundry-Dryer (RCPT)
3 2500... 2500... 4
4th Floor Laundry-Dryer (RCPT) 35 A 2 2500... 2500...
2 35 A 4th Floor Laundry-Dryer (RCPT)
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: NEMA 1 MCB Rating: 225 A Mounting: SURFACE Wires: 4 Mains Rating: 225 A
Supply From: PL-401 Phases: 3 Mains Type: MAIN CB Location: LAUNDRY 426 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL
Branch Panel: PL-403
Notes:
Total Est. Demand: 18 A Total Conn.: 18 A
Total Est. Demand: 6520 VA Spare 4000 VA 100.00% 4000 VA Total Conn. Load: 6520 VA Receptacle 2520 VA 100.00% 2520 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 25 A 25 A 9 A Total Load: 2720 VA 2720 VA 1080 VA
23 SPACE -- -- 0 VA 0 VA -- -- SPACE 24
21 SPACE -- -- 0 VA 0 VA -- -- SPACE 22
19 SPACE -- -- 0 VA 0 VA -- -- SPACE 20
17 SPACE -- -- 0 VA 0 VA -- -- SPACE 18
15 SPACE -- -- 0 VA 0 VA -- -- SPACE 16
13 SPACE -- -- 0 VA 0 VA -- -- SPACE 14
11 SPACE -- -- 0 VA 0 VA -- -- SPACE 12
9 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 10
7 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 8
5 NW Receptacles 20 A 1 540 VA 540 VA 1 20 A SE Receptacles 6 3 #2 Rack Receptacle 20 A 1 360 VA 360 VA 1 20 A #2 Rack Receptacle 4 1 #1 Rack Receptacle 20 A 1 360 VA 360 VA 1 20 A #1 Rack Receptacle 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: NEMA 1 MCB Rating: 100 A Mounting: SURFACE Wires: 4 Mains Rating: 100 A
Supply From: PL-401 Phases: 3 Mains Type: MAIN CB Location: TELECOM 425 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL
Branch Panel: PT-401
1 1
AP
R
AM
EN
D M
EN
T
W
2Q R
R
_P la ns _V ol 1-
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
LO
U
IS
VI
LL
E
D
IS
TR
IC
T
D
R M
AR
TI
N L
U
TH
ER
K
IN
G
J R
P
LA
C E
LO
U
IS
VI
LL
E, K Y
EAST
JA
N
C
ER
TI
FI
ED
F
IN
AL
FT
. M cC O
Y, W
I C
O
LL
EC
TI
VE
T
R
AI
N
IN
G O
FF
IC
ER
S
Q U
AR
TE
R S
EA
ST
PN
FY
, P
VO
LU
M
E
0F
C :\U se rs
\H 2E
D D
LF
A\
D oc um en ts \5
1_ R ev it2
0_
E_
TT
O Q
_H 2E
D D
LF
A.
rv t
4/ 9/
:5
0:
P M
E-606
PA
N
EL
S
C H
ED
U
LE
S
L.
AL
EX
AN
D
ER
L.
AL
EX
AN
D
ER
J.
M
O O
R E
CONTINUOUS load class is for reserved furture EV charging stations.
Notes:
SPECIFIC LOADS 1119 VA 100.00% 1119 VA Total Est. Demand: 534 A Lighting 429 VA 125.00% 536 VA Total Conn.: 534 A Spare 85985 VA 100.00% 85985 VA Total Est. Demand: 444360 VA Other 0 VA 0.00% 0 VA Total Conn. Load: 444256 VA
HVAC 363563 VA 100.00% 363563 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 534 A
Total Conn. Load: 444256 VA
20 SPACE -- -- -- 0 VA --
19 SPACE -- -- -- 0 VA --
18 SPACE -- -- -- 0 VA --
17 SPACE -- -- -- 0 VA --
16 SPACE -- -- -- 0 VA --
15 SPACE -- -- -- 0 VA --
14 SPACE -- -- -- 0 VA --
13 SPACE -- -- -- 0 VA --
12 SPACE -- -- -- 0 VA --
11 SPARE 3 -- 50 A 33225 VA
10 SPARE 3 -- 20 A 13300 VA
9 SPARE 3 -- 20 A 13300 VA
8 DOAS-1 3 50 A 45 A 36082 VA
7 HWP-2 3 20 A 20 A 11431 VA Estimating 7.5hp Motor 6 HWP-1 3 20 A 20 A 11431 VA Estimating 7.5hp Motor 5 CWP-2 3 20 A 20 A 14550 VA Estimating 10hp Motor 4 CWP-1 3 20 A 20 A 14550 VA Estimating 10hp Motor 3 100 Ton Air Cooled Scroll Chiller ACC-1 3 400 A 225 A 172928 VA Based On Chiller MCA
2 MH-401 3 250 A 125 A 54670 VA
1 T-5 3 400 A 225 A 73762 VA
CKT Circuit Description # of Poles Frame Size Trip Rating Load Remarks
Notes:
Enclosure: NEMA 1 MCB Rating: 800 A Mounting: SURFACE Wires: 4 Mains Rating: 800 A
Supply From: MSB-DIST Phases: 3 Mains Type: MCB Location: Volts: 480/277 Wye A.I.C. Rating: 22,000 AMPS SYMMETRICAL
Switchboard: MH-101
CONTINUOUS load class is for reserved furture EV charging stations.
Notes:
SPECIFIC LOADS 1119 VA 100.00% 1119 VA Total Est. Demand Current: 205 A Receptacle 180 VA 100.00% 180 VA Total Conn. Current: 205 A Other 0 VA 0.00% 0 VA Total Est. Demand: 73866 VA Lighting 429 VA 125.00% 536 VA Total Conn. Load: 73762 VA
HVAC 62768 VA 100.00% 62768 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 220 A 217 A 186 A Total Load: 25935 VA 25520 VA 22319 VA
53 SPACE -- -- 0 VA 0 VA -- -- SPACE 54
51 SPACE -- -- 0 VA 0 VA -- -- SPACE 52
49 SPACE -- -- 0 VA 0 VA -- -- SPACE 50
47 SPACE -- -- 0 VA 0 VA -- -- SPACE 48
45 SPACE -- -- 0 VA 0 VA -- -- SPACE 46
43 SPACE -- -- 0 VA 0 VA -- -- SPACE 44
41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42
39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40
37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38
35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36
33 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 34
31 SPARE 20 A 1 0 VA 0 VA 1 20 A SPARE 32
29 SPARE 20 A 1 0 VA 1920 VA 1 20 A FA/MN Equipment in Mechanical 128 30 27 Boiler 2 20 A 1 720 VA 623 VA 1 20 A Elevator Controller, Outlet and Hoistway Lights 28 25 Boiler 1 20 A 1 720 VA 1976... 26
23 1976... 1976 VA
2 25 A DSS-9 4th Floor Electrical Room
DSS-8 3rd Floor Electrical Room 25 A 2
1976... 1976... 22
19 1976 VA 1976...
2 25 A DSS-7 2nd Floor Electrical Room
DSS-6 1st Floor Electrical Room 25 A 2
1976... 1144 VA 18
15 1144... 1144...
2 25 A DSS-5 4th Floor Telecom Room
DSS-4 3rd Floor Telecom Room 25 A 2
1144 VA 1144... 14
11 1144... 1144 VA
2 25 A DSS-3 2nd Floor Telecom Room
DSS-2 1st Floor Telecom Room 25 A 2
1144... 1144... 10
7 GF-1 20 A 1 660 VA 1144...
2 25 A DSS-1 Elevator Equipment Room
5 5806... 5410 VA 6
3 7910... 7803... 4
ML-201 100 A 3
7421 VA 7815...
3 100 A ML-401
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: NEMA 1 MCB Rating: 600 A Mounting: SURFACE Wires: 4 Mains Rating: 600 A
Supply From: T-5 Phases: 3 Mains Type: MAIN CB Location: Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL
Branch Panel: ML-101
Notes:
Total Est. Demand Current: 59 A
Total Conn. Current: 59 A Total Est. Demand: 21110 VA
SPECIFIC LOADS 230 VA 230 VA Total Conn. Load: 21110 VA
HVAC 17208 VA 17208 VA
Load Classification Connected Load Estimated Demand Panel Totals
Total Amps: 64 A 68 A 48 A Total Load: 7421 VA 7910 VA 5806 VA
41 SPACE -- -- 0 VA 0 VA -- -- SPACE 42
39 SPACE -- -- 0 VA 0 VA -- -- SPACE 40
37 SPACE -- -- 0 VA 0 VA -- -- SPACE 38
35 SPACE -- -- 0 VA 0 VA -- -- SPACE 36
33 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 34
31 SPARE 20 A 1 1000... 1000... 1 20 A SPARE 32
29 RCP-1, 1st Floor Mechanical Room 20 A 1 65 VA 65 VA 1 20 A RCP-2, 2nd Floor Mechanical Room 30 27 2nd Floor Quarters, FCU-218/220 15 A 1 660 VA 660 VA 1 15 A 2nd Floor Quarters, FCU-219/221 28 25 2nd Floor Quarters, FCU-214/216 15 A 1 660 VA 660 VA 1 15 A 2nd Floor Quarters, FCU-215/217 26 23 2nd Floor Quarters, FCU-210/212 15 A 1 660 VA 660 VA 1 15 A 2nd Floor Quarters, FCU-211/213 24 21 2nd Floor Quarters, FCU-206/208 15 A 1 660 VA 660 VA 1 15 A 2nd Floor Quarters, FCU-207/209 22 19 2nd Floor Quarters, FCU-202/204 15 A 1 660 VA 660 VA 1 15 A 2nd Floor Quarters, FCU-203/205 20 17 2nd Floor Stair Heaters (CH) 20 A 1 192 VA 1524... 1 15 A 2nd Floor Corridor, Laundry, Comm. Area FCU 18 15 UH-2 Mech. Room Unit Heater 20 A 1 240 VA 50 VA 1 20 A VAV-2, 2nd Floor Laundry 16 13 1st Floor Quarters, FCU-118/120 15 A 1 660 VA 660 VA 1 15 A 1st Floor Quarters, FCU-119/121 14 11 1st Floor Quarters, FCU-114/116 15 A 1 660 VA 660 VA 1 15 A 1st Floor Quarters, FCU-115/117 12 9 1st Floor Quarters, FCU-110/112 15 A 1 660 VA 660 VA 1 15 A 1st Floor Quarters, FCU-111/113 10 7 1st Floor Quarters, FCU-106/108 15 A 1 660 VA 660 VA 1 15 A 1st Floor Quarters, FCU-107/109 8 5 1st Floor Quarters, FCU-102/104 15 A 1 660 VA 660 VA 1 15 A 1st Floor Quarters, FCU-103/105 6 3 1st Floor Stair Heaters (CH) 20 A 1 288 VA 1524... 1 15 A 1st Floor Corridor, Laundry, Comm. Area FCU 4 1 UH-1 Mech. Room Unit Heater 20 A 1 240 VA 50 VA 1 20 A VAV-1, 1st Floor Laundry 2
CKT Load Name Trip Poles A B C Poles Trip Load Name CKT
Notes:
Enclosure: NEMA 1 MCB Rating: 100 A Mounting: SURFACE Wires: 4 Mains Rating: 225 A
Supply From: ML-101 Phases: 3 Mains Type: MCB Location: ELECTRICAL 227 Volts: 120/208 Wye A.I.C. Rating: 10,000 AMPS SYMMETRICAL
Branch Panel: ML-201
Notes:
Total Est. Demand Current: 58 A
Total Conn. Current: 58 A Total Est. Demand: 20999 VA
SPECIFIC LOADS 230 VA 230 VA Total Conn. Load: 20999 VA
HVAC 16872 VA 16872 VA
Load Classification Connected Load Estimated Demand Panel Totals
Total Amps: 68 A 68 A 45 A Total Load: 7815 VA 7803 VA 5410 VA
41 SPACE -- -- 0…