W912QR23R0041_Plans-0002.pdf
PDF 3 MB Posted
- Solicitation number
- W912QR23R0041
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXTERIOR FINISHES
CODE MFR/DESCRIPTION
INSULATED METAL PANEL:
MATCH EXISTING, PAINT, COLOR: BASE STANDARD "CONCH SHELL"
STUCCO:
MATCH EXISTING, PAINT, COLOR: BASE STANDARD "CONCH SHELL"
ROOF:
MODIFIED BITUMOUS ROOF, COLOR: WHITE
FASCIA:
COPPER
SOFFITS:
PREFINISHED METAL PANEL, COLOR: BASE STANDARD "CONCH SHELL"
GUTTERS:
COPPER
DOWNSPOUTS:
COPPER
ALUMINUM STOREFRONT SYSTEM - ALUMINUM STOREFRONT:
DOORS:
ALUMINUM, FACTORY FINISH, COLOR: ANODIZED BLACK WITH MATTE
FINISH
DOOR FRAMES:
ALUMINUM, FACTORY FINISHED, COLOR: ANODIZED BLACK WITH MATTE
FINISH
WINDOW FRAMES:
ALUMNIUM, FACTORY FINISHED, COLOR: ANODIZED BLACK WITH MATTE
FINISH
GLAZING:
COLOR: SOLAR GRAY
OVERHEAD DOORS:
INSULATED METAL, STAINLESS STEEL
HANGAR DOORS:
BASE BID MATCH EXISTING, PAINT, COLOR: BASE STANDARD "CONCH
SHELL"
BID OPTION 2 PAINT, COLOR: BASE STANDARD "CONCH SHELL", TRANSLUCENT
PANEL: COLOR: WHITE/WHITE
HANDRAILS AND GUARDRAILS:
GALVANIZED STEEL
EXTERIOR SIGNAGE
BACKGROUND DARK BROWN
LETTERING REFLECTIVE WHITE
LOUVERS:
COLOR: BASE STANDARD "CONCH SHELL"
INTERIOR FINISHES GENERAL SHEET NOTES
CODE MFR/DESCRIPTION
FLOORS:
CPT-CARPET
CPT-1 MILLIKEN / LOW COUNTRY, STYLE: WATERWAY, COLOR: INDIGO
PLANT, SIZE: 9.85" X 39.4",
INSTALLATION: ASHLAR
T-TILE
T-1 DALTILE / PORTFOLIO, COLOR: PF04 DOVE GREY, SIZE: 12" X 24",
INSTALLATION: BRICK, GRT-1
LVT-LUXURY VINYL TILE
LVT-1 EF CONTRACT / PLAYBOOK, COLOR: EFCOB-005 FOSSIL,
SIZE: 7" X 48", INSTALLATION: ASHLAR
SC-SEALED CONCRETE
SC-1 SEALED CONCRETE
RF-RESILIENT FLOORING
RF-1 ROPPE / RAISED DESIGN RUBBER TILE,
STYLE: #992 LOW PROFILE RAISED CIRCULAR DESIGN, COLOR: M123
CHARCOAL
MT-METAL TRANSITION STRIP:
MT-1 SCHLUTER / RENO-U, COLOR: AE SATIN ANODIZED ALUMINUM, SIZE:
5/16"H
RT-RESILIENT TRANSITION STRIP:
RT-1 ROPPE / #42 CUSTOM CARPET EDGING, COLOR: 123
CHARCOAL
WALLS:
P-PAINT
P-1 SHERWIN WILLIAMS / SW7064 PASSIVE
P-2 SHERWIN WILLIAMS / SW7065 ARGOS
P-4 SHERWIN WILLIAMS / SW7674 PEPPERCORN
T-TILE
T-2 DALTILE / CAPE COAST, COLOR: PEDESTAL, SIZE: 12" X 24",
INSTALLATION: BRICK, GRT-1
T-3 DALTILE / COASTAL KEYSTONES, STYLE: 1" HEXAGON MOSAIC,
COLOR: MEDITERRANEAN MIST BLEND CK92, SIZE: 12" X 12",
INSTALLATION: STRAIGHT, GRT-1
T-4 DALTILE / CAPE COAST, COLOR: PEDESTAL, SIZE: 3" X 12",
INSTALLATION: STRAIGHT, GRT-1
TB-TILE COVE BASE
TB-1 DALTILE / PORTFOLIO, COLOR: PF04 DOVE GREY, SIZE: 3" X 12",
INSTALLATION: BRICK, GRT-1
RB-RESILIENT WALL BASE
RB-1 ROPPE / 700 SERIES WALL BASE, STYLE: STANDARD,
COLOR: 123 CHARCOAL
COUNTERTOPS & WINDOW SILLS:
SSM-SOLID SURFACE MATERIAL
SSM-1 CORIAN / RAIN CLOUD
KNEEGUARDS:
PLAM-PLASTIC LAMINATE
PLAM-1 FORMICA / INFINITY DUOTEX 6448-58, MATTE FINISH
PLAM-2 FORMICA / OILED WALNUT 5487-NT, NATURELLE FINISH
SHOWER PANS:
SSM-2 INPRO / SHOWER BASE PAN, COLOR: P9011 BRIGHT WHITE
A. COLORS LISTED ARE FOR COLOR IDENTIFICATION PURPOSES ONLY. THIS
LISTING IS NOT INTENDED TO LIMIT SELECTION OF SAME QUALITY AND
SIMILAR COLORS, TEXTURES AND PATTERNS FROM OTHER MANUFACTURERS.
B. ALL SOLID SURFACE COUNTERTOPS SHALL RECEIVE 4" HIGH INTEGRAL
BACKSPLASH, U.N.O.
C. FOR EXTERIOR MATERIALS, REFERENCE THE IDG EXTERIOR COLOR CHART
CODE MFR/DESCRIPTION
CEILINGS:
GYPSUM
P-3 SHERWIN WILLIAMS / SW7007 CEILING BRIGHT WHITE
ACT-ACOUSTICAL CEILING TILE
ACT-1 ARMSTRONG / OPTIMA SQUARE TEGULAR 3354, COLOR: WHITE,
SIZE: 24" X 24" x 1"
GRID: ARMSTRONG / PRELUDE XL, COLOR: WHITE, SIZE: 15/16"
TP-TOILETPARTITIONS/US-URINAL SCREENS:
TP-1 SCRANTON PRODUCTS / HINY HIDERS, COLOR: CONCRETE,
TEXTURE: ROTARY BRUSHED
US-1 MATCH TP-1
GRT-GROUT
GRT-1 TRUCOLOR RAPID CURE / URETHANE GROUT, COLOR: H144 MISTY
GRAY
DOORS:
WOOD DOORS STAIN TO MATCH WD-1
METAL DOORS MATCH P-4
DOOR FRAMES:
METAL MATCH P-4
WD-WOOD:
WD-1 MINWAX / MW439 WALNUT
FRP-FIBERGLASS REINFORCED PLASTIC
FRP-1 CRANE COMPOSITES / GLASBORD, COLOR: PEARL GRAY 48
WS-WINDOW SHADE:
WS-1 MERMET / E SCREEN, COLOR: 002020 WHITE/LINEN, 3% OPEN
WS-2 MERMET / AVILA TWILIGHT, COLOR: 000002 WHITE, 0% OPEN
SIGNAGE
BACKGROUND: MATCH P-4
LETTERING: MATCH P-3
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
P
BIM 360://Patrick SFB Hangar 750/Patrick AFB Renovate H-750_A-20.rvt
8/2/2023 12:43:14 PM
AF001
F
IN
IS
H
M A
T E
R
IA
L S
L
IS
T
P A
T R
IC
K
S P
A C
E F
O R
C E
B A
S E
F
L O
R
ID
A
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
D R
E M
Y
B B
R A
D D
IC
K
D R
E M
Y
R W
E N
T E
M A
Y
CERTIFIED FINAL SUBMITTAL
R E
N O
V A
T E
H A
N G
A R
F
O R
R
Q W
P R
O J E
C T
N O
S
X H
T -9
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
J U
L Y
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
A
U G
1 2
ARIMS: 200A Disposition: Maintain for 15 yrs after construction.
W
2Q R
R
_P la ns -0
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
LI
C
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
P 2#
LO
U
IS
V
IL
L
E D
IS
T
R
IC
T
D
R . M
A R
T
IN
L U
T H
E R
K
IN
G J
R . P
LA
C
E
LO
U
IS
V
IL
LE
, K
Y
C:\Users\Bryan.Zelinsky\Documents\MP-PAFB B750_v2020_Bryan.Zelinsky.rvt
8/1/2023 9:18:22 AM
M-601
M E
C H
A N
IC
A
L S
C H
E D
U
LE
S
P A
T R
IC
K
S P
A C
E F
O R
C E
B A
S E
, F
LO
R
ID
A
LO
U
IS
V
IL
L
E D
IS
T
R
IC
T
D
R . M
A R
T
IN
L U
T H
E R
K
IN
G J
R . P
LA
C
E
LO
U
IS
V
IL
L E
K
Y
S . B
O R
D E
N
A . H
O P
K
IN
S
B . Z
E
LI
N S
K Y
M A
Y
CERTIFIED FINAL SUBMITTAL
R E
N O
V A
T E
H A
N G
A R
F
O R
R Q
W
P R
O
JE
C T
N O
. S X
H T
0-
AIR HANDLING UNIT SCHEDULE (WATER COILS)
MARK SERVICE
SUPPLY FAN COOLING COIL
VOLTS /
PH / HZ FLA MCA MOCP FILTER
WEIGHT
(LBS) NOTES
AIR
FLOW
(CFM)
E.S.P.
(IN WG)
T.S.P.
(IN WG)
FAN
RPM BHP HP
TOTAL
CAPACITY
(MBH)
SENS.
CAPACITY
(MBH)
SENSIBLE
HEAT
RATIO
E.A.T.
DB/WB
(F)
L.A.T.
DB/WB
(F)
MAX AIR
P.D. (IN
WG)
COIL FACE
VELOCITY
(FPM)
E.W.T.
(F) L.W.T.
(F)
FLOW
RATE
(GPM)
MAX.
W.P.D.
(FT WG)
NO. OF
ROWS
AHU-1 NORTH 4,450 2.00 4.17 1,885 4.32 7.40 180.20 129.52 0.72 78.70 / 65.70 52.26 / 52.09 0.656 446 42.0 54.0 29.92 3.04 6 460/3/60 7.39 9.24 15.0 MERV 13 1,301 SEE NOTES AHU-2 SOUTH 7,250 2.00 3.95 2,266 7.15 7.20 321.10 215.57 0.67 78.60 / 66.00 51.61 / 51.03 0.541 431 42.0 54.0 53.31 12.13 6 460/3/60 7.30 9.13 15.0 MERV 13 1,766 SEE NOTES
1. UNIT SHALL BE PROVIDED WITH VFD
2. PROVIDE (2) SPARE BELTS AND FILTERS WITH UNIT.
3. PROVIDE CONCRETE PAD.
4. UNIT SHALL BE PROVIDED WITH DUAL DIRECT-DRIVE PLENUM FANS (SINGLE VFD), AND (2) SPARE FILTERS.
5. PROVIDE UNIT WITH CONTROLS INTERFACE PACKAGE INCLUDING FAN MOTOR DISCONNECT, TRANSFORMERS, FAN CONTACTORS, AND TERMINAL STRIP FOR FIELD-PROVIDED CONTROLS. INCLUDE THE FOLLOWING END DEVICE OPTIONS: LOW LIMIT PROTECTION, CONDENSATE OVERFLOW SWITCH, FAN STATUS SWITCH, DISCHARGE AIR SENSOR, MIXED AIR SENSOR, RETURN AIR SENSOR, AND RETURN AIR HUMIDITY SENSOR.
6. FACTORY-MOUNTED CONTROL OPTIONS: MIXING SECTION DAMPER ACTUATORS, AIRFLOW MEASURING STATIONS (TRAQ DAMPERS), TEMPERATURE SENSORS, FAN DISCHARGE TEMPERATURE SENSORS, AVERAGING TEMPERATURE SENSORS, LOW-LIMIT SWITCHES, AIRFLOW SWITCHES, DIRTY FILTER SWITCHES, CONDENSATE OVERFLOW SWITCHES, AND CUSTOMER INTERFACE RELAYS.
7. FIELD-MOUNTED CONTROL OPTIONS: CONTROL VALVES, SPACE TEMPERATURE SENSORS, AND OUTDOOR AIR SENSORS.
1. COILS SHALL BE COPPER FIN AND COPPER TUBE TYPE WITH ADDED FACTORY CORROSION PROTECTION COATING, CONSISTING OF ALUMINUM-IMPREGNATED POLYURETHANE AND RATED FOR 10,000 HR SALT SPRAY PER ASTM B117 AND IAW G10 PSFB IFS 45 CES HEATING, VENTILATION & AIR CONDITIONING (HVAC) STANDARDS, G10.5(3). COATING SHALL ALSO BE APPLIED TO INTAKE DAMPER, ACTUATORS, AND CONTROLS TERMINALS.
2. PROVIDE STAINLESS STEEL DUCTING ON UNIT INTAKE.
3. PROVIDE WITH MANUFACTURER'S STANDARD 6" INTEGRAL BASE FRAME.
4. FIELD PROVIDE AN OUTSIDE AIR AND RETURN AIR DEW POINT SENSOR. REFER TO CONTROLS DRAWINGS FOR ADDITIONAL INFORMATION.
5. FACTORY-MOUNTED CONTROL OPTIONS: MIXING SECTION DAMPER ACTUATORS, AIRFLOW MEASURING STATIONS (TRAQ DAMPERS), TEMPERATURE SENSORS, FAN DISCHARGE TEMPERATURE SENSORS, AVERAGING TEMPERATURE SENSORS, LOW-LIMIT SWITCHES, AIRFLOW SWITCHES, DIRTY FILTER SWITCHES, CONDENSATE OVERFLOW SWITCHES, AND CUSTOMER INTERFACE RELAYS.
6. FIELD-MOUNTED CONTROL OPTIONS: CONTROL VALVES, SPACE TEMPERATURE SENSORS, AND OUTDOOR AIR SENSORS.
HOT WATER BOILER SCHEDULE
MARK FUEL
INPUT
(MBH)
OUTPUT
(MBH) EWT (°F) LWT (°F)
FLOW RATE
(GPM)
WATER P.D.
(FT WG)
VENT ELECTRICAL
NOTESQUANTITY SIZE (IN) FLA VOLTS / PH / HZ
B-1 NATURAL GAS 399 376 110 140 25.1 12.5 2 4 2.5 120/1/60 SEE NOTES
B-2 NATURAL GAS 399 376 110 140 25.1 12.5 2 4 2.5 120/1/60 SEE NOTES
1. UNIT TO BE PROVIDED WITH CONDENSATE NEUTRALIZATION KIT.
2. UNIT TO BE PROVIDED WITH CIRCULATION PUMP.
3. UNIT TO BE PROVIDED WITH CONCENTRIC VENT KIT.
4. FACTORY-MOUNTED CONTROL OPTIONS: THERMISTERS, SUPPLY HIGH LIMIT CONTROL, FLUE GAS HIGH LIMIT CONTROL, WATER FLOW SENSOR (LOW WATER FLOW PROTECTION), RELIEF VALVE, ON/OFF SWITCH, FLUE TEMPERATURE SENSOR, LOW WATER CUTOFF CONNECTION, FREEZE PROTECTION, FLUE BLOCKED PROTECTION, BACK FLUE PROTECTION, PRESSURE SENSOR (LOW WATER PRESSURE PROTECTION), AND CONDENSATE BLOCKED DRAIN PROTECTION.
5. FIELD-MOUNTED CONTROL OPTIONS: DIFFERENTIAL PRESSURE SENSOR, PRIMARY AND SECONDARY HW SUPPLY AND RETURN TEMPERATURE SENSORS, AND HYDRAULIC SEPARATOR.
WATER COOLED CHILLER SCHEDULE
MARK
NOMINAL
CAPACITY
(TONS)
EVAPORATOR CONDENSER ELECTRICAL MOTOR STARTER
REFRIGERANT NPLV MANUFACTURER MODEL NOTES
DESIGN FLOW
RATE (GPM) EWT (°F) LWT (°F)
FOULING FACTOR
(HR-SQ FT-DEG
F/BTU)
WATER
P.D. (FT)
FLOW
RATE
(GPM)
E.W.T.
(F)
L.W.T.
(F)
WATER
P.D. (FT
WG) MAX KW VOLTS / PH / HZ MCA MOCP TYPE ENCLOSURE
CH-1 90 178.4 54.0 42.0 0.0001000 13.2 240.0 85.0 95.0 20.3 64.4 460/3/60 108 150 WYE-DELTA - R-134a 0.53 kW/TON TRANE RTWD-90T SEE NOTES
COOLING TOWER SCHEDULE
Mark
NOMINAL
CAPACITY (TONS)
WET BULB DESIGN
TEMP (F)
CONDENSER ELECTRICAL
NOTES
FLOW RATE
(GPM)
E.W.T.
(F) L.W.T. (F)
PUMPING
HEAD (PSI)
FAN MOTOR
HP (PER CELL) VOLTS / PH / HZ
LOCKED ROTOR
CURRENT (A)
CT-1 100 80 240.0 95 85 5.12 7.5 460 / 3 / 60 - SEE NOTES
DEDICATED OUTDOOR AIR UNIT SCHEDULE
MARK LOCATION
SUPPLY
AIR FLOW
(CFM)
SUPPLY
E.S.P.
(IN WG)
SUPPLY
FAN
BHP
SUPPLY
FAN HP
EXHAUST
AIR FLOW
(CFM)
EXHAUST
E.S.P. (IN
WC)
EXHAUST
FAN BHP
EXHAUST
FAN HP
WHEEL PERFORMANCE (N/A) COOLING COIL HEATING COIL
NOTES
COOLING
O.A.
EDB/EWB
(°F)
COOLING
LAT
DB/WB
(°F)
HEATING
O.A.
EDB/EW
B (°F)
HEATING
R.A.
EWB/EDB
(°F)
E.A.T. DB/WB /
L.A.T. DB (F)
TOTAL
COOLING
CAPACITY
(MBH)
CHILLED
WATER
FLOW (GPM)
P.D.
(FT)
FLUID
TEMP
RISE (°F)
E.A.T. DB /
L.A.T. DB (F)
TOTAL
HEATING
CAPACITY
(MBH)
HOT
WATER
FLOW
(GPM)
P.D.
(FT)
FLUID
TEMP
DROP
(°F) DOAS-1 MECH 213 1,350 1.50 1.06 1.5 - - - - - - - - 85.4 / 81.1 / 55 131.5 21.83 2.66 12 43 / 73 43.92 2.93 0.46 30.0 SEE NOTES DOAS-2 MECH 119 3,050 1.50 3.41 5.0 - - - - - - - - 85.4 / 81.1 / 55 297.17 49.34 10.54 12 43 / 73 99.23 6.63 0.14 30.0 SEE NOTES
FAN SCHEDULE
MARK SERVICE AIR FLOW (CFM) S.P. (IN WG) FAN RPM HP VOLTS / PH / HZ TYPE DRIVE LOCATION NOTES
EF-1 153 - HANGAR BAY 11,000 0.75 788 5 460 / 3 / 60 CENTRIFUGAL WALL EXHAUST BELT WALL SEE NOTES 3, 4 EF-2 153 - HANGAR BAY 11,000 0.75 788 5 460 / 3 / 60 CENTRIFUGAL WALL EXHAUST BELT WALL SEE NOTES 3, 4 EF-3 112 - ELEC 400 0.50 1,459 1/10 120 / 1 / 60 CENTRIFUGAL WALL EXHAUST DIRECT WALL SEE NOTES 3, 4 EF-4 148B - PNEUDRAULICS SOLDERING 100 0.25 1,550 1/60 120 / 1 / 60 CENTRIFUGAL WALL EXHAUST DIRECT WALL SEE NOTES 3, 4 EF-5 142 - HAZMAT DISPOSAL & 143 - HAZMAT STOR. 225 0.60 1,550 1/8 120 / 1 / 60 CENTRIFUGAL ROOF EXHAUST DIRECT ROOF SEE NOTES 1, 2, 3 EF-6 123 - AVIONICS SOLDERING 100 0.25 1,550 1/60 120 / 1 / 60 CENTRIFUGAL WALL EXHAUST DIRECT WALL SEE NOTES 3, 4 EF-7 115 - MECH 1,000 0.40 1,096 1/4 120 / 1 / 60 CENTRIFUGAL WALL EXHAUST DIRECT WALL SEE NOTES 3, 4 EF-8 BUILDING EXHAUST 1,150 1.5 1,940 3/4 120 / 1 / 60 CENTRIFUGAL ROOF EXHAUST DIRECT ROOF SEE NOTES 2, 3 EF-9 BUILDING EXHAUST 2,900 1.5 1,418 2 460 / 3 / 60 CENTRIFUGAL WALL EXHAUST DIRECT WALL SEE NOTES 3, 4
1. PROVIDE INTEGRAL 6'-0" TALL STANDS.
2. PROVIDE ALL COMPONENTS AS FIBERGLASS AND STAINLESS STEEL CONSTRUCTION.
3. COOLING TOWER IS A SINGLE CELL TOWER.
4. FACTORY-MOUNTED CONTROL OPTIONS: MECHANICAL MAKE-UP WATER FLOAT VALVE AND FACTORY CALIBRATED ELECTRONIC LIQUID LEVEL SENSOR WITH CONTROLLER.
5. FIELD-MOUNTED CONTROL OPTIONS: CW SUPPLY AND RETURN TEMPERATURE SENSORS AND CW FLOW SENSOR.
FAN COIL UNIT SCHEDULE
MARK SERVICE
SUPPLY FAN COOLING COIL HEATING COIL
MCA MOCP VOLTS / PH / HZ FILTER NOTES
AIR
FLOW
(CFM)
E.S.P.
(IN WG)
T.S.P.
(IN WG)
FAN
RPM BHP HP
TOTAL
CAPACITY
(MBH)
SENS.
CAPACITY
(MBH)
E.A.T.
DB/WB
(F)
L.A.T.
DB/WB
(F) E.W.T.
(F) L.W.T.
(F)
FLOW
RATE
(GPM)
MAX.
W.P.D.
(FT WG)
CAPACITY
(MBH)
E.A.T.
(F) E.W.T.
(F) L.W.T.
(F)
FLOW
RATE
(GPM)
MAX.
W.P.D.
(FT WG)
FCU-1 115 - MECH 390 0.25 0.759 1,134 0.108 1/2 9.93 7.74 78.3 / 58.0 55.0 / 48.3 42.0 52.06 1.97 1.31 9.31 68.0 140.0 97.97 0.44 0.24 9.32 15 115 / 1 / 60 1" THROWAWAY SEE NOTES FCU-2 119 - MECH 320 0.25 0.685 1,016 0.070 1/2 8.15 6.11 78.3 / 58.0 55.0 / 48.3 42.0 60.45 0.88 0.42 7.63 68.0 140.0 120.85 0.80 0.42 9.32 15 115 / 1 / 60 1" THROWAWAY SEE NOTES FCU-3 152 - MECH 300 0.25 0.681 1,002 0.064 1/2 7.64 5.73 78.3 / 58.0 55.0 / 48.3 42 61.44 0.78 0.34 7.16 68.0 140.0 97.07 0.33 0.14 9.32 15 115 / 1 / 60 1" THROWAWAY SEE NOTES FCU-4 101 - LOBBY 300 0.25 0.681 1,002 0.064 1/2 7.64 5.73 78.3 / 58.0 55.0 / 48.3 42 61.44 0.78 0.34 7.16 68.0 140.0 97.07 0.33 0.14 9.32 15 115 / 1 / 60 1" THROWAWAY SEE NOTES
1. FAN TO BE PROVIDED WITH EXPLOSION PROOF MOTOR AND SPARK PROOF CONSTRUCTION (AMCA TYPE B).
2. ROOF FANS SHALL BE PROVIDED WITH NEW ROOF CURB.
3. PROVIDE ROOF/WALL FANS WITH BIRDSCREEN, CURB SEAL, AND EXTERNAL DISCONNECT SWITCH.
4. PROVIDE SIDEWALL FAN WITH LOW-LEAKAGE MOTORIZED DAMPER AND SHORT WALL HOUSING.
1. UNIT SHALL BE SOLE SOURCED AS TRANE.
2. FACTORY-MOUNTED CONTROL OPTIONS: PROVIDE MICROPROCESSOR CONTROL PANEL.
3. FIELD-MOUNTED CONTROL OPTIONS: CHW DIFFERENTIAL PRESSURE SENSOR, CHW SUPPLY AND RETURN TEMPERATURE SENSORS, CHILLED WATER BYPASS VALVE, AND CHW FLOW SENSOR.
1. PROVIDE WALL MOUNTED THERMOSTAT.
2. PROVIDE WITH 2 OR 3-WAY VALVE AS INDICATED ON PIPING PLANS AND HOT WATER RISER DIAGRAMS.
NOTES:
1. COORDINATE POWER REQUIREMENTS FOR ALL POWER TO MECHANICAL EQUIPMENT INCLUDING CONTROL SYSTEM WITH ELECTRICAL CONTRACTOR AND INSURE ALL COSTS ASSOCIATED WITH SUCH ARE INCLUDED IN THE PROJECT BID COST. PROVIDE ELECTRICAL POWER, TRANFORMERS, RELAYS, ETC. AS NECESSARY TO ALL HVAC AND MECHANICAL CONTROLS.
6. PROVIDE UNIT WITH HURRICANE TIE-DOWN STRAPS.
4. PROVIDE CHILLER WITH VFD AND DUAL COMPRESSORS.
R E
V
IS
E D
I N
A C
C O
R D
A N
C E
W
IT
H A
M E
N D
M E
N T
ARIMS: 200A Disposition: Maintain for 15 yrs after construction.
W
2Q R
R
_P la ns -0
1 2 3 4 5 6 7 8
9 10 11 12 13
A
B
C
D
E
F
2 3 G
HP
MDPL
MDPH
T1
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T E
D B
Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T R
A C
T N
O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
P
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
C:\Users\robert.hansley\OneDrive - Tetra Tech, Inc\Documents\E-PAFB B750_v2020_robert.hansley@tetratech.com.rvt
8/3/2023 4:35:13 PM
ED101
S
T F
L O
O R
D E
M O
L
IT
IO
N
P L A
N
P A
T R
IC
K
S P
A C
E F
O R
C E
B A
S E
F L O
R
ID
A
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
J J /R
L H
R L H
R S
R
L D
C
M A
Y
S H
E E
T K
E Y
E D
N O
T E
S
CERTIFIED FINAL SUBMITTAL
R E
N O
V A
T E
H A
N G
A R
F
O R
R
Q W
P R
O J E
C T N
O S
X H
T -9
1/16" = 1'-0"A1
FIRST FLOOR DEMOLITION PLAN
1. DEVICES IN AREAS INDICATED WITH HATCHING OR DASHED LINEWORK
SHALL BE DEMOLISHED. ANY EQUIPMENT SPECIFICALLY NOTED TO REMAIN
SHALL BE RECONNECTED TO NEW ELECTRICAL DISTRIBUTION SYSTEM.
2. NOT ALL ELECTRICAL EQUIPMENT MAY BE SHOWN ON PLANS. REMOVE ALL
60HZ ALTERNATING CURRENT ELECTRICAL EQUIPMENT IN ALL AREAS
WITHIN THE SCOPE, UON.
3. UNLESS SPECIFICALLY NOTED AS EXISTING TO REMAIN ON THE PLANS,
CONTRACTOR SHALL REMOVE ALL WIRING, SWITCHING AND CONTROL
DEVICES ASSOCIATED WITH DEMOLISHED EQUIPMENT, LIGHTING, ETC.
CIRCUITS SHALL BE REMOVED TO SOURCE PANEL IN THEIR ENTIRETY.
4. EXISTING CONDUITS WITHIN MASONRY WALLS AND UNDERGROUND MAY
BE RE-USED WHERE THEY ALIGN FOR AESTHETIC PURPOSES ONLY.
EXISTING ABOVE GROUND, ACCESSIBLE CONDUITS SHALL BE REMOVED IN
THEIR ENTIRETY. CUT CONDUITS FLUSH WITH SURFACE AND REPAIR WALL
OR FLOOR AS NECESSARY. WHERE CONDUITS ARE INTENDED TO BE
RE-USED, CONTRACTOR SHALL TEST CONDUIT TO DETERMINE FEASIBILITY
OF RE-USE AND COORDINATE WITH GOVERNMENT. CONTRACTOR
ASSUMES ALL RISK ASSOCIATED WITH RE-USE AND WILL PROVIDE A
COMPLETE, OPERABLE, AND ACCESSIBLE SYSTEM.
5. MATERIALS BEING REMOVED DURING DEMOLITION, AND NOT INDICATED
FOR RELOCATION AND NOT INDICATED FOR RELOCATION, SHALL BE
PROMPTLY AND COMPLETELY REMOVED FROM THE SITE, UON.
6. CONTRACTOR SHALL EXERCISE CARE IN REMOVAL OF EQUIPMENT. ANY
EQUIPMENT OR CONSTRUCTION INDICATED TO REMAIN THAT BECOMES
DAMAGED DURING CONSTRUCTION SHALL BE REPAIRED OR REPLACED AT
NO ADDITIONAL EXPENSE TO THE GOVERNMENT.
7. REMOVE ALL EQUIPMENT AND CONNECTIONS ON ROOF AND EXTERIOR OF
BUILDING UON.
8. RE-POWER ALL EXISTING ABOVE GROUND LIFTS AND/OR CRANES WITHIN
BUILDING. MAINTAIN EQUIPMENT AND RE-CIRCUIT TO NEW ELECTRICAL
DISTRIBUTION SYSTEMS AS INDICATED ON RENOVATION ELECTRICAL
DRAWINGS.
9. DISCONNECT AND REMOVE EXISTING WIRING, CONDUIT & DISCONNECT
FEEDING HYDRAULIC LIFTS LOCATED THROUGHOUT BULDING.
10. DISCONNECT AND REMOVE EXISTING WIRING, CONDUIT & DISCONNECT
FEEDING CRANE LOCATED IN SECOND FLOOR STORAGE ROOM.
11. MAINTAIN SERVICE TO ALL EXISTING EQUIPMENT AND DEVICES TO REMAIN
AT ALL TIMES, UNLESS ADVANCED WRITTEN PERMISSION IS RECEIVED
FROM THE COR.
12. WHERE MECHANICAL OR PLUMBING EQUIPMENT IS INDICATED FOR
DEMOLITION, REMOVE POWER TO SOURCE AND ASSOCIATED CONTROL
WIRING. SEE MECHANICAL AND PLUMBING DEMOLITION SHEETS FOR
PRECISE LOCATION OF EQUIPMENT.
13. WHERE DEDICATED ELECTRICAL CIRCUITS ARE REMOVED TO SOURCE,
TURN OFF BREAKER AND RE-LABEL AS 'SPARE'.
A
KEY PLAN
B
C
D E
# SHEET KEYED NOTES:
1. DISCONNECT, REMOVE AND STORE EXISTING 400HZ ELECTRICAL
PANEL/CONTROLLER FOR RELOCATION AND RE-INSTALLATION.
2. COMM ROOM 106 SERVES AS A NODE FOR ANCILLARY BUILDINGS.
DISCONNECT AND REMOVE ALL COMMUNICATIONS EQUIPMENT
SERVING THIS BUILDING ONLY. ALL COMMUNICATIONS EQUIPMENT
AND APPURTENANCES SERVING THE ANCILLARY BUILDINGS MUST
REMAIN FULLY OPERATIONAL DURING CONSTRUCTION. RETAIN
EXISTING RECEPTACLES ASSOCIATED WITH THIS EQUIPMENT.
3. COORDINATE POWER OUTAGES AND DEMOLITION OF
RECEPTACLES AND LIGHTING IN THIS AREA WITH COR. REFER TO
NEW WORK FOR INSTALLATION OF POWER AND COMMUNICATION
EQUIPMENT IN ORDER TO MAINTAIN AREA AND MINIMIZE ANY
DOWNTIME.
4. DISCONNECT AND REMOVE EXISTING CONDUIT AND WIRING BACK
TO THE SOURCE PANEL FROM EXISTING CHILLER.
5. DISCONNECT, REMOVE AND STORE EXISTING PUBLIC ADDRESS
SYSTEM (PA) EQUIPEMENT IN A SAFE PLACE FOR
RE-INSTALLATION UNDER NEW WORK. COORDIATE WITH COR
PRIOR TO RE-INSTALLATION. INSPECT WIRING PRIOR TO
INSTALLATION FOR DAMAGE.
6. EXISTING RAMP LIGHTS POWERED FROM MDPL-8,10,12 FEEDER TO
REMAIN.
7. DISCONNECT AND REMOVE EXISTING DEMARCATION INCLUDING
WIRING, HANGERS AND CONNECTION NOT SUPPORTING ANY
ANCILLARY BUILDINGS.
0 8' 16' 32'
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
/0
/2
SHEET NOTES:
PLAN NORTH
ARIMS: 200A Disposition: Maintain for 15 yrs after construction.
W
2Q R
R
_P la ns -0
GFI/CH
G F I/ C
H2
24"
24"
J
J
J
GFI
L -2
R
G F I/ C
H
J
24"
24"
G F I/ C
H
24"
J
G F I
G F I/ C
H
G F I/ W
P
G F I/ W
P
G F I/ W
P
G F I/ W
P
G F I
J
J
J
GFI
24"
J
J
J
G F I/ W
P
G F I/ W
P
G F I/ W
P
60"/TV
T V
J
J
4 5 6 732.1.
E
F
3.5 3.9
E.4
E.7
2.9
TL1A
COMM ROOM
BREAK ROOM
PNEUDRAULICS
SOLDERING
ELEVATOR
CONTROL ROOM
MECH
LOBBY
PNEUDRAULICS &
E/E
ELEV
ACCESSORIES
PNEUDRAULICS &
E/E WORKSHOP
L1B-1:1 L1B-1:3
L1B-1:5,7
L1B-1:11,15 L1B-1:13
L1B-1:9
L1B-1:4
L1B-1:6
L1B-1:26
L1B-1:10
L1B-1:16 L1B-1:12
L1B-1:14
L1B-1:20
TL1A:2,4
TL1A:3
TL1A:5
L1B-1:2
L1B-1:8
L1B-1:28
RSFACU
ML1B:28
TD1 MTS
UL RATED MANUAL
TRANSFER SWITCH
WITH PORTABLE
GENERATOR PLUG.
2 3
1 1
TD1
7 8 9 10 11 12 13
F
F.2
F.4
10.7 11.1
EP401
D1
EP401
D4
CT-1
MDPH
LH1B
L1B-2
L1B-1
TL1B
MH1B
H1B
L1B
ML1B
ELEC
COMM. ROOM
FIRE RISER
STAIR
MOF OIC
MOF
MECH
EGRESS
CORRIDOR
MOF MEETING
L1B-1:19
L1B-1:21
L1B-1:17
L1B-1:31
L1B-1:29
L1B-1:25,30
L1B-1:23,34
L1B-1:27
L1B-1:22
MDPL
T1
L1B-1:32
FMCU
ML1B:26
XMIT
ML1B:33
TD2 MTS
UL RATED MANUAL
TRANSFER SWITCH
WITH PORTABLE
GENERATOR PLUG.
2 3
TD2
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T E
D B
Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T R
A C
T N
O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
P
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
C:\Users\robert.hansley\OneDrive - Tetra Tech, Inc\Documents\E-PAFB B750_v2020_robert.hansley@tetratech.com.rvt
8/3/2023 4:35:15 PM
EP101
F
IR
S T F
L O
O R
E L E
C T R
IC
A
L P
O W
E R
P L A
N
A R
E A
A
A R
E A
B
P A
T R
IC
K
S P
A C
E F
O R
C E
B A
S E
F L O
R
ID
A
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
J J /R
L H
R L H
R S
R
L D
C
M A
Y
S H
E E
T K
E Y
E D
N O
T E
S
CERTIFIED FINAL SUBMITTAL
R E
N O
V A
T E
H A
N G
A R
F
O R
R
Q W
P R
O J E
C T N
O S
X H
T -9
1/8" = 1'-0"E1
FIRST FLOOR POWER PLAN - AREA A
1/8" = 1'-0"A1
FIRST FLOOR POWER PLAN - AREA B
1. ALL ELECTRICAL DEVICES INSTALLED OR RELOCATED WITHIN THE
LIMITS OF WORK SHALL BE MOUNTED A MINIMUM OF 18" AFF TO
BOTTOM OF THE DEVICE, UON.
2. ALL WIRING AND EQUIPMENT WITHIN ANY OF THE CLASSIFIED
AREAS SHALL BE RATED AND INSTALLED IN ACCORDANCE WITH
THE APPLICABLE PROVISIONS OF NFPA 70.-002 FOR
CLASSIFICATION OF HAZARDOUS LOCATIONS.
3. REFER TO SHEET E-001 AND E-002 FOR GENERAL ELECTRICAL
NOTES, ABBREVIATIONS AND SYMBOL LEGEND.
4. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR
PROVIDING INFRASTRUCTURE FOR PULLING OF
TELECOMMUNICATION CABLING. SEE T-SERIES SHEETS FOR
CONDUIT AND CABLE TRAY REQUIREMENTS.
5. REFER TO MECHANICAL AND PLUMBING SHEETS FOR PRECISE
LOCATION OF EQUIPMENT.
6. PROVIDE ELECTRICAL CONNECTIONS FOR ALL DIV. 22 AND DIV. 23
EQUIPMENT REQUIRING AC POWER CONNECTIONS.
7. COORDINATE LOCATIONS OF EQUIPMENT SWITCHES AND
STARTERS WITH MECHANICAL CONTRACTOR. LOCATE DEVICES IN
AN ACCESSIBLE LOCATION PER NFPA 70.
A
KEY PLAN
B
C
D E
PLAN NORTH
PLAN NORTH
0 4' 8' 16'
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
/0
/2
GENERAL SHEET NOTES:
0 4' 8' 16'
SHEET KEYED NOTES:
1. MOUNT AT 24" AFF TO AVOID CLASSIFIED SPACE.
2. FURNISH AND INSTALL LAMINATED SIGNAGE ON
MANUAL TRANSFER SWITCH THAT STATES. "PORTABLE
GENERATOR CONNECTION FOR HANGAR DOORS"
3. FURNISH AND INSTALL (CANNON PLUG) OR NFPA 70,
UL-LISTED, CSA-CERTIFIED, DOUBLE-LOCKING, SINGLE
POLE CONNECTORS (CAM-LOK STYLE) AS QUICK
CONNECTION/DISCONNECTION DEVICES FOR
PORTABLE GENERATOR CONNECTIONS OF 600 VOLTS
OR LESS FOR FACILITIES.
ARIMS: 200A Disposition: Maintain for 15 yrs after construction.
W
2Q R
R
_P la ns -0
G F I/
G F I/
G F I/
G F I/
G F I/
G F I/
G F I/
G F I/
G F I/
G F I/
G F I/
J J
JJ
4 5 6 7 8 9 10 11 12 1332.1.
D
E
HANGAR BAY
50KW
400HZ
CONVERTER
CONNECTION
(EX)
50KW
400HZ CONVERTER
L1B:7 L1B:9 L1B:11 L1B:13 L1B:15 L1B:17
L1B:19
LL1D:7LL1D:3LL1D:5LL1D:1
(TYP.)
1(TYP.)
(TYP.)
(TYP.)
100AS/70AF
100AS/70AF
H1B:29,31,33
H1D:13,15,17
(TYP.)
ML1B:30 ML1B:32
ML1B:36ML1B:34
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T E
D B
Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T R
A C
T N
O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
P
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
C:\Users\robert.hansley\OneDrive - Tetra Tech, Inc\Documents\E-PAFB B750_v2020_robert.hansley@tetratech.com.rvt
8/3/2023 4:35:16 PM
EP102
F
IR
S T F
L O
O R
E L E
C T R
IC
A
L P
O W
E R
P L A
N
A R
E A
C
P A
T R
IC
K
S P
A C
E F
O R
C E
B A
S E
F L O
R
ID
A
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
J J /R
L H
R L H
R S
R
L D
C
M A
Y
S H
E E
T K
E Y
E D
N O
T E
S
CERTIFIED FINAL SUBMITTAL
R E
N O
V A
T E
H A
N G
A R
F
O R
R
Q W
P R
O J E
C T N
O S
X H
T -9
3/32" = 1'-0"A1
FIRST FLOOR POWER PLAN - AREA C
1. ALL ELECTRICAL DEVICES INSTALLED OR
RELOCATED WITHIN THE LIMITS OF WORK
SHALL BE MOUNTED A MINIMUM OF 18"
AFF TO BOTTOM OF THE DEVICE, UON.
2. ALL WIRING AND EQUIPMENT WITHIN ANY
OF THE CLASSIFIED AREAS SHALL BE
RATED AND INSTALLED IN ACCORDANCE
WITH THE APPLICABLE PROVISIONS OF
NFPA 70.-002 FOR CLASSIFICATION OF
HAZARDOUS LOCATIONS.
3. REFER TO SHEET E-001 AND E-002 FOR
GENERAL ELECTRICAL NOTES,
ABBREVIATIONS AND SYMBOL LEGEND.
4. ELECTRICAL CONTRACTOR SHALL BE
RESPONSIBLE FOR PROVIDING
INFRASTRUCTURE FOR PULLING OF
TELECOMMUNICATION CABLING. SEE
T-SERIES SHEETS FOR CONDUIT AND
CABLE TRAY REQUIREMENTS.
5. REFER TO MECHANICAL AND PLUMBING
SHEETS FOR PRECISE LOCATION OF
EQUIPMENT.
6. PROVIDE ELECTRICAL CONNECTIONS
FOR ALL DIV. 22 AND DIV. 23 EQUIPMENT
REQUIRING AC POWER CONNECTIONS.
7. COORDINATE LOCATIONS OF EQUIPMENT
SWITCHES AND STARTERS WITH
MECHANICAL CONTRACTOR. LOCATE
DEVICES IN AN ACCESSIBLE LOCATION
PER NFPA 70.
A
KEY PLAN
B
C
D E
PLAN NORTH
0 4' 8' 16'
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
/0
/2
GENERAL SHEET NOTES:
SHEET KEYED NOTES:
1. PROVIDE (2)#10 & (1)#10 GND, 3/4"C
2. EXISTING 400HZ CONVERTER. PROVIDE
A NEW FUSED DISCONNECT AND PIN
AND SLEEVE CONNECTOR AS
REQUIRED TO NEW LOCATION SHOWN.
REFER TO SINGLE LINE DIAGRAM FOR
CIRCUIT AND FEEDER INFORMATION.
COORDINATE WITH COR FOR THE
INSTALLATION OF THE 400HZ SYSTEM
AND APPURTENANCES. COORDINATE
LOCATIONS OF CONNECTORS AND
OUTLETS WITH COR.
3. PROVIDE A NEW FUSED DISCONNECT
AND PIN AND SLEEVE CONNECTOR FOR
400Hz GENERATOR, INCLUDING ALL
CONNECTORS, OUTLETS AND
APPURTENANCES. COORDINATE EXACT
LOCATION WITH COR.
4. WEATHERPROOF BLUE LENS ROTARY
BEACON (NEMA 4). SEE FIRE
PROTECTION SHEETS FOR MORE
DETAILS.
ARIMS: 200A Disposition: Maintain for 15 yrs after construction.
W
2Q R
R
_P la ns -0
SM
SM SM
S M
S M
S M
E E
EE
SM
J
4 5 6 7 8 9 10 11 12 1332.1.
D
E
HANGAR BAY
EF-1
EF-2
ML1E:14
ML1E:15
ML1E:12
ML1B:14
ML1B:16
ML1B:18
PROP FAN
CONTROLLER &
SWITCH (EX)
PROP FAN
CONTROLLER &
SWITCH (EX)
PROP FAN
CONTROLLER &
SWITCH (EX)
CRANE
CONTROL
H1B:2,4,6
E 3/60/NF/4X
H1B:8,10,12
EH1B:7,9,11
3/60/NF/4X
ESS-1 ESS-1
ESS-1 ESS-1
L1B:21
L1D:29
F1 F2 F3
F4 F5 F6
F4 F5
F6
F1 F2 F3
3/30/NF/4X
3/30/NF/4X
HANGAR MOTOR #2
HANGAR MOTOR #1
GH-1
GH-2
GH-3
GH-4
WIRING TO
DISCONNECT
SWITCH THROUGH
FLEXIBLE CABLE
<unnamed>
<unnamed>
ML1E:6
ML1E:4
ML1B:10
ML1B:19
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T E
D B
Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T R
A C
T N
O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
P
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
C:\Users\robert.hansley\OneDrive - Tetra Tech, Inc\Documents\E-PAFB B750_v2020_robert.hansley@tetratech.com.rvt
8/3/2023 4:35:18 PM
EP202
F
IR
S T F
L O
O R
M E
C H
A N
IC
A
L P
O W
E R
P L A
N
A R
E A
C
P A
T R
IC
K
S P
A C
E F
O R
C E
B A
S E
F L O
R
ID
A
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
J J /R
L H
R L H
R S
R
L D
C
M A
Y
S H
E E
T K
E Y
E D
N O
T E
S
CERTIFIED FINAL SUBMITTAL
R E
N O
V A
T E
H A
N G
A R
F
O R
R
Q W
P R
O J E
C T N
O S
X H
T -9
3/32" = 1'-0"A1
FIRST FLOOR MECHANICAL POWER PLAN - AREA C
A
KEY PLAN
B
C
D E
0 4' 8' 16'
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
/0
/2
1. SEE SHEET E-001 FOR GENERAL
ELECTRICAL NOTES, ABBREVIATIONS,
AND SYMBOLS LEGEND.
2. PROVIDE ELECTRICAL CONNECTIONS
FOR ALL DIV. 08, DIV. 22 AND DIV. 23
EQUIPMENT REQUIRING AC POWER
CONNECTIONS. SEE ARCHITECTURAL,
MECHANICAL AND PLUMBING SHEETS
FOR PRECISE LOCATION OF
EQUIPMENT.
3. COORDINATE LOCATIONS OF
EQUIPMENT SWITCHES AND STARTERS
WITH MECHANICAL CONTRACTOR.
LOCATE DEVICES IN AN ACCESSIBLE
LOCATION PER NFPA 70.
4. REFER TO M- AND P-SERIES DRAWINGS
FOR ELECTRICAL INFORMATION ON
MECHANICAL AND PLUMBING
EQUIPMENT.
GENERAL SHEET NOTES:
PLAN NORTH
SHEET KEYED NOTES:
1. HANGAR DOOR MOTOR DISCONNECT,
CLASS 1 DIV 2 RATED. POWERED BY
TD1 MTS LOCATED IN MECH 152, SEE
SHEET EP203. REUTILIZE EXISTING BUS
BAR CURRENTLY FEEDING HANGAR
DOOR.
2. HANGAR DOOR MOTOR DISCONNECT,
CLASS 1 DIV 2 RATED. POWERED BY
TD1 MTS LOCATED IN MECH 119, SEE
SHEET A1/EP401. REUTILIZE EXISTING
BUS BAR CURRENTLY FEEDING
HANGAR DOOR.
3. COORDINATE WITH STRUCTURAL
CONTRACTOR AND DRAWINGS FOR
THE REPLACEMENT OF THE WEST
HANGAR DOOR OPERATOR TO BRING IT
TO WORKING CONDITIONS UNDER THE
BASE BID. THIS INCLUDES REPLACING
ALL WIRING AND CONTROLLER AS
REQURED. REFER TO SPECIFICATION
08 34 16.10 HORIZONTAL ROLLING
STEEL DOORS.
ARIMS: 200A Disposition: Maintain for 15 yrs after construction.
W
2Q R
R
_P la ns -0
S M
S M
S M
S M
SM
SM
SM
E
S M
4 5 6 732.1.
B
A
C
B1
A1
A.5
A.0
SUPPORT
SECTION
STORAGE
TRAINING ROOM
SUPPORT
EQUIPMENT
STORAGE
CHECKOUT
COUNTER
AFITS
SUPPORT
SECTION ADMIN.
MECH
HAZMAT STOR.
HAZMAT
DISPOSAL
CONTRACTORS
COMM
ELEC
NURSING
MOTHER'S ROOM
JAN
BREAK ROOM
MEN
STOR
MEN SHOWERS
CORRIDOR
EP401
D8
FCU-3
E
VAV2-01
VAV2-03
VAV2-04
VAV2-02
CU-5
VAV2-10
VAV2-09
VAV2-08
DAH-5
E
ML1E:11
TL1D:9,11
ML1E:13
E
1/30/NF
2/30/NF/4X
ML1E:17,19,21
SUMP
PUMP
(EX)
ESS-1
L1D:31
TL1D
FCF
CONTRACTORS
LL1D
LH1D
L1D-2
L1D-1 L1D
H1D
X1D
M
ML1E:22
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T E
D B
Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T R
A C
T N
O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
P
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
C:\Users\robert.hansley\OneDrive - Tetra Tech, Inc\Documents\E-PAFB B750_v2020_robert.hansley@tetratech.com.rvt
8/3/2023 4:35:20 PM
EP203
F
IR
S T F
L O
O R
M E
C H
A N
IC
A
L P
O W
E R
P L A
N
A R
E A
D
P A
T R
IC
K
S P
A C
E F
O R
C E
B A
S E
F L O
R
ID
A
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
J J /R
L H
R L H
R S
R
L D
C
M A
Y
S H
E E
T K
E Y
E D
N O
T E
S
CERTIFIED FINAL SUBMITTAL
R E
N O
V A
T E
H A
N G
A R
F
O R
R
Q W
P R
O J E
C T N
O S
X H
T -9
1/8" = 1'-0"B1
FIRST FLOOR MECHANICAL POWER PLAN - AREA D
A
KEY PLAN
B
C
D E 0 4' 8' 16'
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
/0
/2
SHEET KEYED NOTES:
1. TO AREA E VAV'S, SEE SHEET EP204.
GENERAL SHEET NOTES:
1. SEE SHEET E-001 FOR GENERAL ELECTRICAL NOTES,
ABBREVIATIONS, AND SYMBOLS LEGEND.
2. PROVIDE ELECTRICAL CONNECTIONS FOR ALL DIV. 08, DIV. 22 AND
DIV. 23 EQUIPMENT REQUIRING AC POWER CONNECTIONS. SEE
ARCHITECTURAL, MECHANICAL AND PLUMBING SHEETS FOR
PRECISE LOCATION OF EQUIPMENT.
3. COORDINATE LOCATIONS OF EQUIPMENT SWITCHES AND
STARTERS WITH MECHANICAL CONTRACTOR. LOCATE DEVICES IN
AN ACCESSIBLE LOCATION PER NFPA 70.
4. REFER TO M- AND P-SERIES DRAWINGS FOR ELECTRICAL
INFORMATION ON MECHANICAL AND PLUMBING EQUIPMENT.
PLAN NORTH
ARIMS: 200A Disposition: Maintain for 15 yrs after construction.
W
2Q R
R
_P la ns -0
L -2
R
SM
E
SM
E
S M
SM
J
C C C
L6-20R
SM
F
MDPH
ELEC
112LH1B
L1B-2
L1B-1
L1B
H1B
T1
MDPL
(EX)
(EX)
(EX)
EXISTING
ELECTRICAL
METER TO REMAIN
COMM. ROOM
TL1B
3TL1B:3
TL1B:2,4TL1B:5
CB-TD1
CB-TD2
F
MECH
MH1B
ML1B
E E
E
E
BCP-1
B-1
BCP-2
B-2
HWP-1
HWP-2
CHWP-2
CHWP-1
GWH-1
CP-1
CH-1
CWP-1
CWP-2
E
E
CU-1
E
FCU-1
TL2B:2,4
MH1B:25,27,29
MH1B:31,33,35
ML1B:8
E
ML1B:5
MH1B:26,28,30
MH1B:13,15,17
MH1B:19,21,23
ML1B:11
3/200/NF1/30/NF
1/30/NF
1/30/NF
3/30/NF
3/30/NF
3/30/NF
3/30/NF
3/30/NF
1/30/NF
3/30/NF
3/30/NF
3/30/NF
1/30/NF
ML1B:2
MH1B:7,9,11
MH1B:1,3,5
2/30/NF/4X
ML1B:20,22,24
ML1B:6
ML1B:21,23,25 E
ML1B:4
1/30/NF/4X
BMS
PANEL
ML1B:7
12 13
C
MECH
MH1E
XM1E
ML1E
EGRESS
CORRIDOR
DOAS-2
AHU-2
GWH-2
CP-2
E
E
E
FCU-2
ML1E:9
E
ML1E:7
MH1E:7,9,11
MH1E:2,4,6
ML1E:8
3/30/NF
1/30/NF
1/30/NF
1/30/NF
3/30/NF
BMS
PANEL
ML1E:2
M M
ML1E:25
ML1E:24
EF-9
E
3/30/NF
MH1E:8,10,12
B
L1D-1
L1D-2
LH1D
LL1D
H1D
X1D
ELEC
L1D
TL1D
COMM
DAH-5
T L D
:2
T L D
:4
T L D
:6
T L D
:8
LH1D:9,11,13,15
LH1D:17,19,21,23
LH1D:1,3,5,7
F
L2B-1
X2B
H2B
L2B-2
DOAS-1
E
3/30/NF
MH1B:2,4,6
L2B-1:28
M
MECH
M
1/30/NF
L2B-2:19
EF-8
1/30/NF
E
L2B-1:22
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T E
D B
Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T R
A C
T N
O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
P
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
C:\Users\robert.hansley\OneDrive - Tetra Tech, Inc\Documents\E-PAFB B750_v2020_robert.hansley@tetratech.com.rvt
8/3/2023 4:35:22 PM
EP401
P A
R T
IA
L F
IR
S
T F
L O
O R
E L E
C T R
IC
A
L P
O W
E R
P L A
N S
P A
T R
IC
K
S P
A C
E F
O R
C E
B A
S E
F L O
R
ID
A
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
J J /R
L H
R L H
R S
R
L D
C
M A
Y
S H
E E
T K
E Y
E D
N O
T E
S
CERTIFIED FINAL SUBMITTAL
R E
N O
V A
T E
H A
N G
A R
F
O R
R
Q W
P R
O J E
C T N
O S
X H
T -9
1/4" = 1'-0"D1
PARTIAL POWER PLAN - AREA B - ELEC. 112
1/4" = 1'-0"D4
PARTIAL POWER PLAN - AREA B - MECH. 115
1/4" = 1'-0"A1
PARTIAL POWER PLAN - AREA E - MECH. 119
1/4" = 1'-0"D8
PARTIAL POWER PLAN - AREA D - ELEC. 138
1/4" = 1'-0"A4
SECOND FLOOR POWER PLAN - AREA A- ELEC. 212
0 2' 4' 8'
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
/0
/2
SHEET KEYED NOTES:
1. TO DAH-1, SEE AREA B SHEET EP205.
2. 480V 3Φ, 60A ENCLOSED CIRCUIT BREAKER. FIELD TAP INCOMING
SERVICE IN MAIN PANEL TO POWER.
3. MOUNT RECEPTACLES IN SPACE A MIN OF 24" AFF TO AVOID
CLASSIFIED SPACE.
4. COORDINATE LOCATION OF EXHAUST FAN WITH MECHANICAL
CONTRACTOR PRIOR TO STARTING WORK.
0 2' 4' 8'
0 2' 4' 8'0 2' 4' 8'0 2' 4' 8'
ARIMS: 200A Disposition: Maintain for 15 yrs after construction.
W
2Q R
R
_P la ns -0
SHEET STEEL JUNCTION BOX
(WITH FLAT COVER WITH KNOCKOUT)
3/4" CONDUIT MINIMUM
CEILING GRID
LAY IN LIGHT FIXTURE
LIGHTING FIXTURE SUPPORT WIRE
ATTACHED TO STRUCTURAL MEMBERS
SO THAT FIXTURE IS SUPPORTED
INDEPENDENT OF CEILING. WIRE TO BE
A MIN. OF #14 GAGE
PRESTRAIGHTENED GALV. ATTACHED @
ALL FOUR CORNERS. (SEE NOTE #1)
1/2" FLEXIBLE CONNECTION TO
FIXTURE (MIN 18" & MAX. 72" LONG)-
ATTACH TO STRUCTURE TO PREVENT
FLEX FROM RESTING ON CEILING
ELECTRICAL CONTRACTOR
SHALL ATTACH FLEX CONDUIT
WITH APPROVED STRAP OR
HANGER.
NOTE:
1. SUPPORT WIRE TO BE INSTALLED IN SUCH A MANNER THAT
WEIGHT OF FIXTURE IS HELD INDEPENDENT OF CLG. GRID
THEREFORE WIRES MUST BE TIGHT WITH NO SLACK.
2. FLEXIBLE CONNECTION FROM FIXTURE TO JUNCTION BOX
MUST BE MIN. 18" & MAX. 72" LONG.
STRAP CONDUIT WITHIN 3' OF
BOX & A MAX OF 10' THERE
AFTER AS PER N.E.C. (TYP)
ELECTRICAL CONTRACTOR
SHALL FURNISH AND INSTALL
HANGER SEPARATE FROM CLG
SYSTEM HANGERS.
CEILING SUPPORT
WIRE
CAT5E. FREE TOPOLOGY & SPLITTER ACCEPTABLE
WITH RJ45 TERMINATIONS. PROVIDE IN 3/4"C WHEN NOT
LOCATED IN CEILING GRID. SUPPORT CABLE ON J-HOOKS
OR CABLE TRAY WHEN ABOVE CEILING GRID.
DUAL TECHNOLOGY PIR & ULTRA SONIC
CEILING MOUNT / CORNER MOUNT
OCCUPANCY/VACANCY SENSORS
DIGITAL ROOM CONTROLLER. PROVIDE AS REQUIRED TO
WORK WITH OCCUPANCY SENSORS INDICATED ON
DRAWINGS. PROGRAM LOAD AS VACANCY SENSOR
(MANUAL ON/AUTOMATIC OFF) FOR LOADS WITH LOW
VOLTAGE WALL SWITCHES INDICATED, OR OCCUPANCY
SENSOR (AUTOMATIC ON/OFF) FOR LOADS WITHOUT LOW
VOLTAGE WALL SWITCHES INDICATED. PROGRAM
STAIRWAYS AND CORRIDOR LOADS TO DIM TO 50% WHEN
VACANT.
DIGITAL LIGHTING CONTROL WALL
SWITCH. QUANTITY AS INDICATED ON
PLANS. COORDINATE DIMMING
SCHEME WITH COR. MIDLEVEL
ILLUMINATION WILL BE 30%-70% OF
THE MAXIMUM ILLUMINATION LEVEL.
LV LV
NEUTRAL-WHT
LIGHTING
LOAD
HOT-BLK PROVIDE UN-SWITCHED HOT
CONDUCTOR TO BATTERY
BACK-UP UNITS AND EXIT SIGNS.
VIO
GRY
CLASS 2 0-10 VOLT
CONTROL WIRING
(DIMMABLE LOADS)
GRY
WHT/BLU
YEL
BLK
RED
WHT
WHT
WHT/BLU
RED
TO FIRE ALARM PANEL NORMALLY
CLOSED DRY CONTACT
BLK
BLU
VIO
EMERGENCY LIGHTING
CONTROL UNIT
EMERGENCY
LOAD
NEUTRAL WHT
HOT BLK
20A
RECEPTACLE
CONTROL BOX
NEUTRAL WHT
HOT BLK
PROGRAM CONTROLS AS VACANCY SENSOR
(MANUAL ON, AUTOMATIC OFF). PROGRAM AT
LEAST 1 DIMMING STEP FOR EACH LIGHTING
LOAD. MIDLEVEL ILLUMINATION WILL BE
30%-70% OF THE MAXIMUM ILLUMINATION
LEVEL.
RED
NEUTRAL WHT
DUAL RELAY
ON/OFF/0-10V DIMMING
ROOM CONTROLLER
LIGHTING LOAD (b)
YEL
VIO
GRY
CLASS 2 0-10 VOLT
CONTROL WIRING
0-10VDC DIMMING
DRIVER REQUIRED.
HOT BLK
EARTH
GROUND
GRN
LMRJ SERIES PRE-TERMINATED CABLES OR CAT 5E
FREE TOPOLOGY & SPLITTER ACCEPTABLE
RJ45
(TYPICAL)
EXIT LIGHT
LIGHTING LOAD (a)
VIO
GRY
3/4"C(2#12, 1#12)
PROVIDE UN-SWITCHED CONDUCTOR TO
BATTERY BACK-UP UNITS AND EXIT SIGNS.
LV2
DUAL TECHNOLOGY
PIR/ULTRA SONIC
CEILING MOUNT / CORNER MOUNT
OCCUPANCY/VACANCY SENSORS
WHT/BLU
BLU
WHT
WHT/BLU
RED
TO FIRE ALARM PANEL NORMALLY
CLOSED DRY CONTACT
BLK
BLK
EMERGENCY LIGHTING
CONTROL UNIT
EMERGENCY
LIGHTING LOADS
VIO
VIO
GRY
NEUTRAL WHT
HOT BLK
20A
RECEPTACLE
CONTROL BOX
NEUTRAL WHT
HOT BLK
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T E
D B
Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T R
A C
T N
O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
P
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
C:\Users\robert.hansley\OneDrive - Tetra Tech, Inc\Documents\E-PAFB B750_v2020_robert.hansley@tetratech.com.rvt
8/3/2023 4:35:10 PM
E-501
E L E
C T R
IC
A
L D
E T A
IL
S
P A
T R
IC
K
S P
A C
E F
O R
C E
B A
S E
F L O
R
ID
A
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
J J /R
L H
R L H
R S
R
L D
C
M A
Y
S H
E E
T K
E Y
E D
N O
T E
S
CERTIFIED FINAL SUBMITTAL
R E
N O
V A
T E
H A
N G
A R
F
O R
R
Q W
P R
O J E
C T N
O S
X H
T -9
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
/0
/2
LIGHTING FIXTURE SCHEDULE
TYPE VOLTAGE WATTS LAMP LUMENS MOUNTING HEIGHT REMARKS Type Comments
A 277V 241 W LED 30000 CEILING PER CEILING HIGH BAY WITH WIDE DISTRIBUTION, SEMI-DIFFUSE ACRYLIC LENS, 80CRI, AND A 4000K
TEMPERATURE
MIN .9/ L90 LLF @ 50, 000 HOURS
AE 277V 241 W LED 30000 CEILING PER CEILING 'A' FIXTURE WITH EMERGENCY BACKUP MIN .9/ L90 LLF @ 50, 000 HOURS
B1 277V 40 W LED 4800 CEILING PER CEILING RECESSED 2x4 WITH A DIMMING CAPABILITY FROM 0-10V, COLOR TEMPERATURE OF 3500K MIN .9/ L90 LLF @ 50, 000 HOURS
B1E 277V 40 W LED 4800 CEILING PER CEILING 'B1' FIXTURE WITH EMERGENCY BACKUP MIN .9/ L90 LLF @ 50, 000 HOURS
B2 277V 32 W LED 4000 CEILING PER CEILING RECESSED 2x4 WITH A DIMMING CAPABILITY FROM 0-10V, COLOR TEMPERATURE OF 3500K MIN .9/ L90 LLF @ 50, 000 HOURS
B2E 277V 32 W LED 4000 CEILING PER CEILING 'B2' FIXTURE WITH EMERGENCY BACKUP MIN .9/ L90 LLF @ 50, 000 HOURS
C 277V 18 W LED 2000 CEILING PER CEILING RECESSED 2x2 WITH A DIMMING CAPABILITY FROM 0-10V, COLOR TEMPERATURE OF 3500K MIN .9/ L90 LLF @ 50, 000 HOURS
CE 277V 18 W LED 2000 CEILING PER CEILING 'C' FIXTURE WITH EMERGENCY BACKUP MIN .9/ L90 LLF @ 50, 000 HOURS
D 277V 11 W LED 1000 CEILING PER CEILING RECESSED 6" CAN DOWNLIGHT WITH A COLOR TEMPERATURE OF 3500K, CLEAR TRIM COLOR, SEMI-SPECULAR, AND DRIVER TO ALLOW A 0-10V DIMMING
MIN .9/ L90 LLF @ 50, 000 HOURS
DE 277V 11 W LED 1000 CEILING PER CEILING 'D' FIXTURE WITH EMERGENCY BACKUP MIN .9/ L90 LLF @ 50, 000 HOURS
F 277V 21 W LED 2000 CEILING PER CEILING 1' x4' LED FIXTURE MIN .9/ L90 LLF @ 50, 000 HOURS
FE 277V 21 W LED 2000 CEILING PER CEILING 1' x 4' LED FIXTURE WITH EMERGENCY BACKUP MIN .9/ L90 LLF @ 50, 000 HOURS
G1 277V 25 W LED 3000 PENDANT 12'-0" 48" PENDANT STRIP LIGHT WITH A SNAP ON FROSTED DIFFUSER, 80CRI, COLOR TEMPERATURE OF
4000K, AND WHITE PAINT FINISH
MIN .9/ L90 LLF @ 50, 000 HOURS
G1E 277V 25 W LED 3000 PENDANT 12'-0" 'G1' FIXTURE WITH EMERGENCY BACKUP MIN .9/ L90 LLF @ 50, 000 HOURS
G2 277V 34 W LED 5000 PENDANT 12'-0" 48" PENDANT STRIP LIGHT WITH A SNAP ON FROSTED DIFFUSER, 80CRI, COLOR TEMPERATURE OF
4000K, AND WHITE PAINT FINISH
MIN .9/ L90 LLF @ 50, 000 HOURS
G2E 277V 34 W LED 5000 PENDANT 12'-0" MIN .9/ L90 LLF @ 50, 000 HOURS
H 277V 15 W LED 600 WALL/CEILIN
G
10'-0" OR
CEILING
VAPORTIGHT GENERAL PURPOSE FIXTURE WITH A COLOR TEMPERATURE OF 4000K, AND A GREY
FINISH
MIN .9/ L90 LLF @ 50, 000 HOURS
J 277V 25 W LED 3000 WALL 10'-0" LOW PROFILE WRAPAROUND WITH A CURVED, RIBBED LENS, A DRIVER THAT ALLOWS A DIMMING FROM 0-10V, 82CRI, 3500K COLOR TEMPERATURE, AND A STANDARD PRE-PAINT WHITE FINISH
MIN .9/ L90 LLF @ 50, 000 HOURS
JE 277V 25 W LED 3000 WALL 10'-0" 'J' FIXTURE WITH EMERGENCY BACKUP MIN .9/ L90 LLF @ 50, 000 HOURS
K 277V 33 W LED 4357 WALL 10'-0" 4FT LINEAR WALL MOUNTED FIXTURE MIN .9/ L90 LLF @ 50, 000 HOURS
W1 277V 27 W LED 2400 WALL 10'-0" EXTERNAL WALL PACK WITH EMERGENCY BACKUP, AN AMBER (1000k) SEA TURTLE SAFE LIGHT, TYPE II OPTICS, BUTTON PHOTOCELL, AND DARK BRONZE MATTE TEXTURED FINISH
MIN .9/ L90 LLF @ 50, 000 HOURS
W2 277V 80 W LED 3600 WALL 10'-0" EXTERNAL WALL PACK WITH EMERGENCY BACKUP, AN AMBER (1000k) SEA TURTLE SAFE LIGHT, TYPE II OPTICS, BUTTON PHOTOCELL, AND DARK BRONZE MATTE TEXTURED FINISH
MIN .9/ L90 LLF @ 50, 000 HOURS
X 277V 5 W LED 5 WALL/CEILIN
G
10'-0" OR
CEILING
STENCIL FACE TYPE, WHITE HOUSING COLOR, RED LETTER COLOR, SELF-DIAGNOSTIC EXIT SIGN
WITH EMERGENCY BACKUP
MIN .9/ L90 LLF @ 50, 000 HOURS
Y 277V 5 W LED 5 WALL/CEILIN
G
10'-0" OR
CEILING
EXPLOSION PROOF, STEEL SEAL GASKETED ENCLOSURE. MIN .9/ L90 LLF @ 50, 000 HOURS
NTSE1
LAY-IN MOUNTED LIGHT DETAIL
NTSA1
LIGHT & PLUG TYPICAL CONTROLS DETAIL
NTSA6
LIGHT & PLUG CLASSROOM CONTROLS DETAIL
ALL LIGHTING FIXTURES MUST COMPLY WITH DLC / ENERGY STAR EFFICIENCY REQUIREMENTS.*
ARIMS: 200A Disposition: Maintain for 15 yrs after construction.
W
2Q R
R
_P la ns -0
EXISTING TO REMAIN
PANEL MDPH
1200 AF
1200 AT
600AF
400AT
200AF
150AT
600AF
400AT
1200A, 480V, 3PH, 4W, 60HZ
400AF
400AT
H1B
RM 112
80AT 40AT
400A, 480V, 3PH, 4W, 60HZ
100AT 100AT
150A
MCB
ML1B
(RM115)
400AF
400AT
MH1B
RM 115
150AT 20AT
400A, 480V, 3PH, 4W, 60HZ
20AT
CHILLER
CH-1
COOLING
TOWER
CT-1
AHU-1
20AT
CHWP-1
30AT
HWP-1
400AF
400AT
L1B
RM 112
150AT 125AT
400A, 208V, 3PH, 4W, 60HZ
100AT
150A L1B-1
125A L1B-2
100A
TL1B
400HZ
SYSTEM
NORTH
(TO REMAIN)
CRANE
60AT
SPARE
100A
MCB
LH1B
X2B
75 KVA
480- 208/120V
225A
MCB
L2B-1
225A
MCB
H2B
25AT
600AF
400AT
600AF
600AT
H1D
RM 139
200AT80AT
400A, 480V, 3PH, 4W, 60HZ
100AT 100AT
SPARE
X1D
150 KVA
480- 208/120V
400AF
400AT
L1D
RM 139
150AT 125AT
400A, 208V, 3PH, 4W, 60HZ
100AT 100AT
150A L1D-1
125A L1D-2
100A
TL1D
NEW
400HZ
SYSTEM
SOUTH
100AT 60AT
SPARE
100A
MCB
LH1D
100AT
SPARE
100A
LL1D
150A
MCB
ML1E
(RM119)
200AF
200AT
MH1E
RM 119
15AT
225A, 480V, 3PH, 4W, 60HZ
25AT
AHU-2 EF-2
70AT 50AT
XM1E
45 KVA
480- 208/120V
15AT 15AT
SPARE
200AT
MECH
LOAD
EF-1
15AT
COMP
N
G
SERVICE TRANSFORMER
13.2KV-480/277V
UTILITY
100A
MCB
TL2B
30AT
SPD
SPD
SPD
SPD
30AT
SPD
600AF
400AT
T1
500 KVA
480-208/120V
1200AF
1200AT
EXISTING
TO REMAIN
MDPL
RM 112
1200A, 208V, 3PH, 4W, 60HZ
400AF
400AT
NEW
200AF
150AT
600AF
400AT
600AF
400AT
TO
EXISTING
RAMP
LIGHTS
SPARE
E
E
15 11 15
8 2 2 2 4 4 2
11 8 8
2 5 4
10 9 8 8
10 9 8
8 85 10
15AT15AT
DOAS-1
SF-1
2 2
SPARE
20AT
CHWP-2
30AT
HWP-2
15AT
CWP-1
15AT
CWP-2
DOAS-2
SF-1
8 8
EF-9
100AT
100A
TL1A
ELEVATOR
100A
TL2E
100AT
100A
MCB
L2B-2
SPD
EXISTING
TD1
15 KVA
480-208/120V
TD2
15 KVA
480-208/120V
30A 3Φ
ENCLOSED CB
30A 3Φ
ENCLOSED CB
HANGAR DOOR
CONTROLLER
60A 3Φ
ENCLOSED CB
PORTABLE
GENERATOR
CONNECTION
PORTABLE
GENERATOR
CONNECTION
30A 3Φ
ENCLOSED
CB
30A 3Φ
ENCLOSED CB
CB-TD1
30A, 3Φ
ENCLOSED CB
CB-TD2
30A, 3Φ
ENCLOSED CB
TD1 MTS
30A 3Φ
TD2 MTS
30A 3Φ
4 4
4 4
4 4 4
4 4
400AF
400AT
HYDRAULIC
TEST STAND
HANGAR DOOR
CONTROLLER
30A
NF
NEMA 7
30A
NF
NEMA 7
750 KVA
CABLE SCHEDULE
KEY # SETS WIRE CONDUIT AMPS@60
1 1 2#12 & #12G 3/4" 20
2 1 3#12 & #12G 3/4" 20
3 1 2#10 & #10G 3/4" 30
4 1 3#10 & #10G 1" 30
5 1 3#4 & #8G 1-1/4" 70
6 1 3#2 & #8G 1-1/2" 95
7 1 3#1/0 & #6G 2" 125
8 1 4#1/0 & #6G 2" 125
9 1 4#2/0 & #6G 2" 145
10 1 4#3/0 & #6G 2" 165
11 1 4#250KCMIL & #4G 2-1/2" 215
12 1 3#300KCMIL & #4G 2-1/2" 240
13 1 4#300KCMIL & #4G 2-1/2" 240
14 2 4#250KCMIL & #4G 2-1/2" 430
15 2 4#500KCMIL & #4G 4" 640
16 1 4#4 & #10G 1-1/4" 60
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T E
D B
Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T R
A C
T N
O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
P
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
C:\Users\robert.hansley\OneDrive - Tetra Tech, Inc\Documents\E-PAFB B750_v2020_robert.hansley@tetratech.com.rvt
8/3/2023 4:35:11 PM
E-601
E L E
C T R
IC
A
L S
IN
G
L E
L
IN
E D
IA
G
R A
M
N E
W W
O R
K
P A
T R
IC
K
S P
A C
E F
O R
C E
B A
S E
F L O
R
ID
A
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
J J /R
L H
R L H
R S
R
L D
C
M A
Y
S H
E E
T K
E Y
E D
N O
T E
S
CERTIFIED FINAL SUBMITTAL
R E
N O
V A
T E
H A
N G
A R
F
O R
R
Q W
P R
O J E
C T N
O S
X H
T -9
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
/0
/2
NTSA1
ELECTRICAL SINGLE LINE DIAGRAM
NTSE7
CABLE SCHEDULE
SHEET KEYED NOTES:
ARIMS: 200A Disposition: Maintain for 15 yrs after construction.
W
2Q R
R
_P la ns -0
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T E
D B
Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T R
A C
T N
O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
File Path:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
P
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
C:\Users\robert.hansley\OneDrive - Tetra Tech, Inc\Documents\E-PAFB B750_v2020_robert.hansley@tetratech.com.rvt
8/3/2023 4:35:12 PM
E-606
E L E
C T R
IC
A
L P
A N
E L S
C H
E D
U L E
S
P A
T R
IC
K
S P
A C
E F
O R
C E
B A
S E
F L O
R
ID
A
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
J J /R
L H
R L H
R S
R
L D
C
M A
Y
S H
E E
T K
E Y
E D
N O
T E
S
CERTIFIED FINAL SUBMITTAL
R E
N O
V A
T E
H A
N G
A R
F
O R
R
Q W
P R
O J E
C T N
O S
X H
T -9
TOTAL EST. DEMAND... 123 A
TOTAL CONNECTED... 123 A
Receptacle 360 VA 100.00% 360 VA TOTAL ESTIMATED DEMAND: 44206 VA
Motor 36015 VA 100.00% 36015 VA TOTAL CONNECTED LOAD: 44206 VA
Mechanical Equipment 7831 VA 100.00% 7831 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
LEGEND:
TOTAL AMPS: 120 A 124 A 125 A
TOTAL LOAD: 14425 VA 14827 VA 14954 VA
41 SPARE 20 A 1 0 0 -- -- -- 42
39 SPARE 20 A 1 0 0 -- -- -- 40
37 SPARE 20 A 1 0 0 3 30 A SPD 38
35 SPARE 20 A 1 0 0 1 20 A SPARE 36
33 SPARE 20 A 1 0 0 1 20 A SPARE 34
31 SPARE 20 A 1 0 0 1 20 A SPARE 32
29 SPARE 20 A 1 0 0 1 20 A SPARE 30
27 SPARE 20 A 1 0 0 1 20 A SPARE 28
25 MOD ROOM 118 20 A 1 0.5 0 1 20 A SPARE 26
23 EF-5 15 A 1 0.13 0.5 1 20 A MOD ROOM 119 24
21 -- -- -- 4.8 0.5 1 20 A MOD ROOM 144 22
19 -- -- -- 4.8 7.21 -- -- -- 20
17 EXISTING SUMP PUMP 40 A 3 4.8 7.21 -- -- -- 18
15 PROP FAN 20 A 1 0.02 7.21 3 20 A LIFT STATION (EX) 16
13 VAV2-01 - VAV2-12 20 A 1 0.3 0.02 1 20 A PROP FAN 14
11 FCU-3 15 A 1 1.18 0.02 1 20 A PROP FAN 12
9 FCU-2 15 A 1 1.18 0.13 1 20 A VAV2-13 - VAV2-17 10
7 CP-2 20 A 1 0.24 0.5 1 20 A GWH-2 8
5 EF-6 15 A 1 0.13 1 1 20 A GH-4 6
3 SPARE 20 A 1 0 1 1 20 A GH-3 4
1 MECH 119 & CORRIDOR 118 RECEPTACLES 20 A 1 0.36 0.5 1 20 A BMS PANEL 2
CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT
MOUNTING: Surface WIRES: 4 MAINS RATING: 150 A
SUPPLY FROM: XM1E PHASES: 3 MAINS TYPE: 150 A MCB
LOCATION: MECH 119 VOLTS: 208Y/120V A.I.C. RATING: 10KAIC
Branch Panel: ML1E
TOTAL EST. DEMAND... 74 A
TOTAL CONNECTED... 108 A
TOTAL ESTIMATED DEMAND: 26763 VA
Receptacle 34405 VA 64.53% 22203 VA TOTAL CONNECTED LOAD: 38965 VA
Mechanical Equipment 4560 VA 100.00% 4560 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
LEGEND:
TOTAL AMPS: 107 A 116 A 103 A
TOTAL LOAD: 12785 VA 13880 VA 12300 VA
41 SPARE 20 A 1 0 0 -- -- -- 42
39 SPARE 20 A 1 0 0 -- -- -- 40
37 SPARE 20 A 1 0 0 3 30 A SPD 38
35 SPARE 20 A 1 0 0 1 20 A SPARE 36
33 SPARE 20 A 1 0 0 1 20 A SPARE 34
31 SPARE 20 A 1 0 0 1 20 A SPARE 32
29 SPARE 20 A 1 0 0 1 20 A SPARE 30
27 DEPUTY COMMANDER 202 RECEPTACLES 20 A 1 0.72 1 1 20 A GH-1 28
25 COMMANDER 201 RECEPTACLES 20 A 1 0.72 0.18 1 20 A COMMANDER SUITE 205 COPIER 26
23 CORRIDOR 216 & AHU213 RECEPTACLES 20 A 1 1.08 0.54 1 20 A CSS 210 DESK RECEPTACLES 24
21 COMMAND SUITE 205 COFFEE MAKER 20 A 1 1 1.26 1 20 A EF-8 22
19 COMMAND SUITE 205 MICROWAVE 20 A 1 0.8 0.72 1 20 A CSS 210 RECEPTACLES 20
17 COMMAND SUITE 205 DISHWASHER 20 A 1 1.2 1 1 20 A CSS 210 CUBICLES 18
15 COMMAND SUITE 205 COUNTER... 20 A 1 0.18 0.5 1 20 A CSS 210 DESKS 16
13 COMMAND SUITE 205 RECEPTACLES 20 A 1 0.72 1 1 20 A CSS 210 DESKS 14
11 COMMAND SUITE 205 CUBICLE 20 A 1 1 1.08 1 20 A CONFERENCE ROOM 209 RECEPTACLES 12
9 COMMAND SUITE 205 CUBICLE 20 A 1 1 0.72 1 20 A CONFERENCE ROOM 209 FLOOR... 10
7 COMMAND SUITE 205 CUBICLE 20 A 1 1 0.4 1 20 A CONFERENCE ROOM 209 TV RECEPTACLE 8
5 -- -- -- 0.36 6.04 -- -- -- 6
3 -- -- -- 1.26 6.24 -- -- -- 4
1 PANEL TL2B 100 A 3 1.26 5.99 3 100 A PANEL L2B-2 2
CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT
MOUNTING: Surface WIRES: 4 MAINS RATING: 225 A
SUPPLY FROM: X2B PHASES: 3 MAINS TYPE: 225 A MCB
LOCATION: MECH 213 VOLTS: 208Y/120V A.I.C. RATING: 10KAIC
Branch Panel: L2B-1
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
/0
/2
TOTAL EST. DEMAND... 56 A
TOTAL CONNECTED... 56 A
TOTAL ESTIMATED DEMAND: 20309 VA
Receptacle 6500 VA 100.00% 6500 VA TOTAL CONNECTED LOAD: 20309 VA
Mechanical Equipment 13809 VA 100.00% 13809 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
LEGEND:
TOTAL AMPS: 57 A 69 A 47 A
TOTAL LOAD: 6623 VA 8106 VA 5581 VA
41 SPARE 20 A 1 0 0 -- -- -- 42
39 SPARE 20 A 1 0 0 -- -- -- 40
37 SPARE 20 A 1 0 0 3 30 A SPD 38
35 SPARE 20 A 1 0 0.5 1 20 A BLUE LENS ROTARY BEACON 36
33 XMIT 20 A 1 1.5 0.5 1 20 A BLUE LENS ROTARY BEACON 34
31 0.5 1 20 A BLUE LENS ROTARY BEACON 32
29 0.5 1 20 A BLUE LENS ROTARY BEACON 30
27 1.5 1 20 A RSFACU 28
25 -- -- -- 0.3 1.5 1 20 A FMCU 26
23 -- -- -- 0.3 0.3 -- -- -- 24
21 BCP-2 15 A 3 0.3 0.3 -- -- -- 22
19 GH-1 20 A 1 1 0.3 3 15 A BCP-1 20
17 MOD ROOM 112 & 115 20 A 1 1 0.02 1 20 A PROP FAN 18
15 -- -- -- 0.9 0.02 1 20 A PROP FAN 16
13 CU-6 15 A 2 0.9 0.02 1 20 A PROP FAN 14
11 GWH-1 20 A 1 0.5 1.92 1 20 A SP-1 12
9 FCU-4 15 A 1 1.18 1 1 20 A GH-2 10
7 BMS PANEL 20 A 1 0.5 1.18 1 15 A FCU-1 8
5 CP-1 20 A 1 0.24 0.3 1 20 A B-2 6
3 VAV1-06 - VAV1-12 20 A 1 0.18 0.73 1 15 A EF-7 4
1 VAV1-01 - VAV1-05 20 A 1 0.13 0.3 1 20 A B-1 2
CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT
MOUNTING: Surface WIRES: 4 MAINS RATING: 150 A
SUPPLY FROM: MDPL PHASES: 3 MAINS TYPE: 150 A MCB
LOCATION: MECH 115 VOLTS: 208Y/120V A.I.C. RATING: 10KAIC
Branch Panel: ML1B
TOTAL EST. DEMAND... 40 A
TOTAL CONNECTED... 51 A
TOTAL ESTIMATED DEMAND: 14383 VA
Receptacle 17765 VA 78.15% 13883 VA TOTAL CONNECTED LOAD: 18265 VA
Mechanical Equipment 500 VA 100.00% 500 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS
LEGEND:
TOTAL AMPS: 50 A 52 A 50 A
TOTAL LOAD: 5985 VA 6240 VA 6040 VA
41 SPACE -- -- 0 0 -- -- SPACE 42
39 SPACE -- -- 0 0 -- -- SPACE 40
37 SPACE -- -- 0 0 -- -- SPACE 38
35 SPACE -- -- 0 0 -- -- SPACE 36
33 SPACE -- -- 0 0 -- -- SPACE 34
31 SPACE -- -- 0 0 -- -- SPACE 32
29 SPARE 20 A 1 0 0 1 20 A SPARE 30
27 SPARE 20 A 1 0 0 1 20 A SPARE 28
25 SPARE 20 A 1 0 0 1 20 A SPARE 26
23 SPARE 20 A 1 0 0 1 20 A SPARE 24
21 SPARE 20 A 1 0 1.08 1 20 A MXG MEETING 222 RECEPTACLES 22
19 MOD ROOM 213 20 A 1 0.5 0.4 1 20 A MXG MEETING 222 TV 20
17 WOMENS SINKS, TOILETS, & RECEPTACLES 20 A 1 1.26 0.72 1 20 A GROUP SUPERINTENDENT 221 RECEPTACLES 18
15 QUALITY ASSURANCE 226 FLOOR... 20 A 1 0.72 1 1 20 A MXG OFFICES 220 CUBICLES 16
13 QUALITY ASSURANCE 226 TV 20 A 1 0.4 0.91 1 20 A CORRIDOR 216 RECEPTACLES 14
11 QUALITY ASSURANCE 226 RECEPTACLES 20 A 1 1.26 0.8 1 20 A BREAK ROOM 218 MICROWAVE 12
9 QUALITY ASSURANCE 226 CUBICLES 20 A 1 1 1.08 1 20 A MENS SINKS, TOILETS, & RECEPTACLES 10
7 QUALITY ASSURANCE 226 CUBICLES 20 A 1 1 1.2 1 20 A BREAK ROOM 218 REFRIGERATOR 8
5 QUALITY ASSURANCE 226 CUBICLES 20 A 1 1 1 1 20 A BREAK ROOM 218 COFFEE MAKER 6
3 QUALITY ASSURANCE 226 CUBICLES 20 A 1 1 0.36 1 20 A BREAK ROOM 218 COUNTER RECEPTACLES 4
1 QUALITY ASSURANCE 226 DESKS 20 A 1 0.5 1.08 1 20 A BREAK ROOM 218 & MXG OFFICES 220 REC 2
CKT CIRCUIT DESCRIPTION TRIP POLES A B C POLES TRIP CIRCUIT DESCRIPTION CKT
MOUNTING: Surface WIRES: 4 MAINS RATING: 100 A
SUPPLY FROM: L2B-1 PHASES: 3 MAINS TYPE: MLO
LOCATION: MECH 213 VOLTS: 208Y/120V A.I.C. RATING: 10KAIC
Branch Panel: L2B-2
ARIMS: 200A Disposition: Maintain for 15 yrs after construction.
W
2Q R
R
_P la ns -0
TELECOMMUNICATIONS SYMBOLS ABBREVIATIONS
AFF ABOVE FINISHED FLOOR TO CENTERLINE
AFG ABOVE FINISHED GRADE TO CENTERLINE
AWG AMERICAN WIRE GAUGE
C CONDUIT
C/B CIRCUIT BREAKER
CAT CATEGORY
CH COUNTER HEIGHT
CKT CIRCUIT
C…
This is the start of the file's text. The full file is on GovTribe.