This document provides details for a federal construction contract opportunity. The U.S. Army Corps of Engineers Louisville District is seeking proposals for the construction of a new Van Voorhis Elementary School at Fort Knox, Kentucky. The project scope includes building a 100,500 square foot elementary school, demolishing an existing 83,000 square foot school, constructing a playfield, and building a parking lot. The contract will be a firm-fixed-price contract with a value between $25-100 million. Proposals are due for a single-phase selection process that will use a best value tradeoff methodology to evaluate technical, past performance, and price factors. The North American Industry Classification System code for this opportunity is 236220.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation For Replace Van Voorhis Elementary School, Fort Knox, KY
P2: 467721
Design-Bid-Build
Specifications Vol. 2 of 4 (Div. 05-22) Certified Final Design
29 April 2021
W912QR21R0040
ARIMS: 200A
Disposition: Maintain for 15yrs after construction
W912QR21R0040_Specs_Vol2-0000
Replace Van Voorhis Elementary School February 8, 2021 Fort Knox, KY Certified Final Design Submission
PROJECT TABLE OF CONTENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
00 01 07 SEALS PAGE
00 80 00.00 06 SPECIAL PROVISIONS
DIVISION 01 - GENERAL REQUIREMENTS
01 11 00 SUMMARY OF WORK
01 14 00 WORK RESTRICTIONS
01 32 01.00 06 PROJECT SCHEDULE
01 33 00.00 06 SUBMITTAL PROCEDURES
01 33 29.00 06 SUSTAINABILITY REPORTING
01 35 26.00 06 GOVERNMENT SAFETY REQUIREMENTS
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00.15 10 RESIDENT MANAGEMENT SYSTEM CONTRACTOR MODE (RMS CM)
01 45 04.10 06 CONTRACTOR QUALITY CONTROL
01 45 35 SPECIAL INSPECTIONS
01 46 00.10 06 TOTAL BUILDING COMMISSIONING (INDEPENDENT CxA)
01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS
01 57 19.00 06 TEMPORARY ENVIRONMENTAL CONTROLS AND PERMITS
01 74 19 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
01 78 23 OPERATION AND MAINTENANCE DATA
DIVISION 02 - EXISTING CONDITIONS
02 41 00 DEMOLITION
02 42 51 CARPET REMOVAL AND RECLAMATION
02 82 00 ASBESTOS REMEDIATION
02 83 00 LEAD REMEDIATION
02 83 13.00 06 LEAD IN CONSTRUCTION
02 84 16 HANDLING OF LIGHTING BALLASTS AND LAMPS CONTAINING PCBs
AND MERCURY
02 84 33 REMOVAL AND DISPOSAL OF POLYCHLORINATED BIPHENYLS (PCBs)
DIVISION 03 - CONCRETE
03 30 00 CAST-IN-PLACE CONCRETE
DIVISION 04 - MASONRY
04 20 00 UNIT MASONRY
04 72 00 CAST STONE MASONRY
DIVISION 05 - METALS
05 12 00 STRUCTURAL STEEL
05 21 00 STEEL JOIST FRAMING
05 30 00 STEEL DECKS
05 40 00 COLD-FORMED METAL FRAMING
05 50 13 MISCELLANEOUS METAL FABRICATIONS
05 51 00 METAL STAIRS
05 51 33 METAL LADDERS
05 52 00 METAL RAILINGS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 10 00 ROUGH CARPENTRY
PROJECT TABLE OF CONTENTS Page 1
06 41 16.00 10 PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS
06 61 16 SOLID SURFACING FABRICATIONS
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 05 23 PRESSURE TESTING AN AIR BARRIER SYSTEM FOR AIR TIGHTNESS
07 11 13 BITUMINOUS DAMPPROOFING
07 14 00 FLUID-APPLIED WATERPROOFING
07 21 13 BOARD AND BLOCK INSULATION
07 21 16 MINERAL FIBER BLANKET INSULATION
07 22 00 ROOF AND DECK INSULATION
07 27 10.00 10 BUILDING AIR BARRIER SYSTEM
07 42 13 METAL WALL PANELS
07 54 19 POLYVINYL-CHLORIDE ROOFING
07 61 14.00 20 STEEL STANDING SEAM ROOFING
07 62 00 SHEET METAL FLASHING AND TRIM
07 72 00 ROOF ACCESSORIES
07 81 00 SPRAY-APPLIED FIREPROOFING
07 84 00 FIRESTOPPING
07 92 00 JOINT SEALANTS
DIVISION 08 - OPENINGS
08 11 13 HOLLOW METAL DOORS AND FRAMES
08 14 00 WOOD DOORS
08 33 13 COILING COUNTER DOORS
08 34 73 SOUND CONTROL DOOR ASSEMBLIES
08 41 13 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
08 44 00 CURTAIN WALL AND GLAZED ASSEMBLIES
08 60 50 TUBULAR DAYLIGHTING SKYLIGHTS
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 91 00 METAL WALL LOUVERS
DIVISION 09 - FINISHES
09 29 00 GYPSUM BOARD
09 30 10 CERAMIC, QUARRY, AND GLASS TILING
09 35 16 CHEMICAL-RESISTANT QUARRY TILING
09 51 00 ACOUSTICAL CEILINGS
09 62 38 STATIC-CONTROL FLOORING
09 65 00 RESILIENT FLOORING
09 65 66 RESILIENT ATHLETIC FLOORING
09 68 00 CARPETING
09 80 00 ACOUSTICAL METAL WALL PANELS
09 84 20 ACOUSTICAL WALL PANELS
09 90 00 PAINTS AND COATINGS
DIVISION 10 - SPECIALTIES
10 11 00 VISUAL DISPLAY UNITS
10 14 00.10 EXTERIOR SIGNAGE
10 14 00.20 INTERIOR SIGNAGE
10 21 13 TOILET COMPARTMENTS
10 21 23.16 CUBICLE TRACK AND HARDWARE
10 22 39 FOLDING PANEL PARTITIONS
10 26 00 WALL AND DOOR PROTECTION
10 28 13 TOILET ACCESSORIES
10 44 16 FIRE EXTINGUISHERS
PROJECT TABLE OF CONTENTS Page 2
10 51 13 METAL LOCKERS
10 75 00 FLAGPOLES
10 85 00 BUILDING SPECIALTIES
DIVISION 11 - EQUIPMENT
11 05 40 COMMON WORK RESULTS FOR FOODSERVICE EQUIPMENT
11 06 00 STAGE/THEATRICAL EQUIPMENT
11 06 40.13 FOODSERVICE EQUIPMENT SCHEDULE
11 13 19.13 LOADING DOCK LEVELERS
11 30 13 RESIDENTIAL APPLIANCES
11 41 11 REFRIGERATED AND FROZEN FOOD STORAGE EQUIPMENT
11 42 00 FOOD PREPARATION EQUIPMENT
11 44 00 FOOD COOKING EQUIPMENT
11 46 00 FOOD DISPENSING EQUIPMENT
11 47 00 ICE MACHINES
11 48 00 CLEANING AND DISPOSAL EQUIPMENT
11 66 23 GYMNASIUM EQUIPMENT
11 66 53 GYMNASIUM DIVIDERS
11 68 13 PLAYGROUND EQUIPMENT
DIVISION 12 - FURNISHINGS
12 24 13 ROLLER WINDOW SHADES
12 48 13 ENTRANCE FLOOR MATS AND FRAMES
12 93 00 SITE FURNISHINGS
DIVISION 13 - SPECIAL CONSTRUCTION
13 48 00 SEISMIC BRACING FOR MISCELLANEOUS EQUIPMENT
DIVISION 14 - CONVEYING EQUIPMENT
14 24 23 HYDRAULIC PASSENGER ELEVATORS
DIVISION 21 - FIRE SUPPRESSION
21 12 00 STANDPIPE SYSTEMS
21 13 13.00 10 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION
21 23 00.00 20 WET CHEMICAL FIRE EXTINGUISHING FOR KITCHEN CABINET
DIVISION 22 - PLUMBING
22 00 00 PLUMBING, GENERAL PURPOSE
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 00 00 AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS
23 05 48.00 40 VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND
EQUIPMENT
23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS
23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC
23 09 13 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC
23 09 23.02 BACNET DIRECT DIGITAL CONTROL FOR HVAC AND OTHER BUILDING
CONTROL SYSTEMS
23 11 25 FACILITY GAS PIPING
23 21 23 HYDRONIC PUMPS
23 23 00 REFRIGERANT PIPING
PROJECT TABLE OF CONTENTS Page 3
23 25 00 CHEMICAL TREATMENT OF WATER FOR MECHANICAL SYSTEMS
23 52 00 HEATING BOILERS
23 63 00.00 10 COLD STORAGE REFRIGERATION SYSTEMS
23 64 26 CHILLED, CHILLED-HOT, AND CONDENSER WATER PIPING SYSTEMS
23 81 00 DECENTRALIZED UNITARY HVAC EQUIPMENT
23 81 47 WATER-LOOP AND GROUND-LOOP HEAT PUMP SYSTEMS
DIVISION 25 - INTEGRATED AUTOMATION
25 05 11.21 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS FIRE
LIFE SAFETY
25 05 11.23 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS UTILITY
MONITORING CONTROL SYSTEM (UMCS) TO INCLUDE HVAC AND
LIGHTING CONTROL SYSTEMS
DIVISION 26 - ELECTRICAL
26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS
26 05 48.00 10 SEISMIC PROTECTION FOR ELECTRICAL EQUIPMENT
26 20 00 INTERIOR DISTRIBUTION SYSTEM
26 24 13 SWITCHBOARDS
26 28 01.00 10 COORDINATED POWER SYSTEM PROTECTION
26 29 23 ADJUSTABLE SPEED DRIVE (ASD) SYSTEMS UNDER 600 VOLTS
26 41 00 LIGHTNING PROTECTION SYSTEM
26 51 00 INTERIOR LIGHTING
26 56 00 EXTERIOR LIGHTING
DIVISION 27 - COMMUNICATIONS
27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM
27 51 23.10 INTEGRATED INTERCOM, PUBLIC ADDRESS AND MASTER CLOCK SYSTEM
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 05 13 CONDUCTORS AND CABLES FOR ELECTRONIC SECURITY
28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM
DIVISION 31 - EARTHWORK
31 00 00.00 06 EARTHWORK
31 11 00 CLEARING AND GRUBBING
31 21 13 RADON MITIGATION
31 63 29 DRILLED CONCRETE PIERS AND SHAFTS
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 05 33 LANDSCAPE ESTABLISHMENT
32 11 23 AGGREGATE BASE COURSES
32 11 23.23 BASE COURSE DRAINAGE LAYERS
32 12 13 BITUMINOUS TACK AND PRIME COATS
32 12 16.16 ROAD-MIX ASPHALT PAVING
32 13 13.06 PORTLAND CEMENT CONCRETE PAVEMENT FOR ROADS AND SITE
FACILITIES
32 13 73.19 COMPRESSION CONCRETE PAVING JOINT SEALANT
32 16 19 CONCRETE CURBS, GUTTERS AND SIDEWALKS
32 17 23 PAVEMENT MARKINGS
32 18 16.13 PLAYGROUND PROTECTIVE SURFACING
32 31 13 CHAIN LINK FENCES AND GATES
32 92 19 SEEDING
PROJECT TABLE OF CONTENTS Page 4
32 92 23 SODDING
32 93 00 EXTERIOR PLANTS
DIVISION 33 - UTILITIES
33 11 00 WATER UTILITY DISTRIBUTION PIPING
33 11 23 NATURAL GAS PIPING
33 30 00 SANITARY SEWERAGE
33 40 00 STORM DRAINAGE UTILITIES
33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION
33 82 00 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS Page 5
THIS PAGE INTENTIONALLY LEFT BLANK
PROJECT TABLE OF CONTENTS Page 6
SECTION 05 12 00
STRUCTURAL STEEL
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
AISC 207 (2016; R 2017) Certification Standard for Steel Fabrication and Erection, and Manufacturing of Metal Components
AISC 303 (2016) Code of Standard Practice for Steel Buildings and Bridges
AISC 325 (2017) Steel Construction Manual
AISC 326 (2009) Detailing for Steel Construction
AISC 360 (2016) Specification for Structural Steel Buildings
AISC DESIGN GUIDE 10 (1997) Erection Bracing of Low-Rise Structural Steel Buildings
AMERICAN SOCIETY FOR NONDESTRUCTIVE TESTING (ASNT)
ANSI/ASNT CP-189 (2016) ASNT Standard for Qualification and Certification of Nondestructive Testing Personnel (ANSI/ASNT CP-105-2006)
AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)
ASME B46.1 (2009) Surface Texture, Surface Roughness, Waviness and Lay
AMERICAN WELDING SOCIETY (AWS)
AWS A2.4 (2012) Standard Symbols for Welding, Brazing and Nondestructive Examination
AWS D1.1/D1.1M (2015; Errata 1 2015; Errata 2 2016) Structural Welding Code - Steel
AWS QC1 (2016) Specification for AWS Certification of Welding Inspectors
ASTM INTERNATIONAL (ASTM)
ASTM A6/A6M (2017a) Standard Specification for General Requirements for Rolled Structural Steel
SECTION 05 12 00 Page 1
Bars, Plates, Shapes, and Sheet Piling
ASTM A29/A29M (2016) Standard Specification for General Requirements for Steel Bars, Carbon and Alloy, Hot-Wrought
ASTM A36/A36M (2014) Standard Specification for Carbon Structural Steel
ASTM A53/A53M (2018) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless
ASTM A123/A123M (2017) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A500/A500M (2018) Standard Specification for Cold-Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes
ASTM A563 (2015) Standard Specification for Carbon and Alloy Steel Nuts
ASTM A780/A780M (2009; R 2015) Standard Practice for Repair of Damaged and Uncoated Areas of Hot-Dip Galvanized Coatings
ASTM A992/A992M (2011; R 2015) Standard Specification for Structural Steel Shapes
ASTM B695 (2004; R 2016) Standard Specification for Coatings of Zinc Mechanically Deposited on Iron and Steel
ASTM C827/C827M (2016) Standard Test Method for Change in Height at Early Ages of Cylindrical Specimens of Cementitious Mixtures
ASTM C1107/C1107M (2017) Standard Specification for Packaged Dry, Hydraulic-Cement Grout (Nonshrink)
ASTM F436/F436M (2016) Standard Specification for Hardened Steel Washers Inch and Metric Dimensions
ASTM F844 (2007a; R 2013) Washers, Steel, Plain (Flat), Unhardened for General Use
ASTM F959/F959M (2017a) Standard Specification for Compressible-Washer-Type Direct Tension Indicators for Use with Structural Fasteners, Inch and Metric Series
ASTM F1136/F1136M (2011) Standard Specification for Zinc/Aluminum Corrosion Protective Coatings for Fasteners
ASTM F1554 (2018) Standard Specification for Anchor
SECTION 05 12 00 Page 2
Bolts, Steel, 36, 55, and 105-ksi Yield Strength
ASTM F2329/F2329M (2015) Standard Specification for Zinc Coating, Hot-Dip, Requirements for Application to Carbon and Alloy Steel Bolts, Screws, Washers, Nuts, and Special Threaded Fasteners
ASTM F2833 (2011; R 2017) Standard Specification for Corrosion Protective Fastener Coatings with Zinc Rich Base Coat and Aluminum Organic/Inorganic Type
ASTM F3125/F3125M (2015a) Standard Specification for High Strength Structural Bolts, Steel and Alloy Steel, Heat Treated, 120 ksi (830 MPa) and 150 ksi (1040 MPa) Minimum Tensile Strength, Inch and Metric Dimensions
U.S. GREEN BUILDING COUNCIL (USGBC)
LEED NC (2009) Leadership in Energy and Environmental Design(tm) New Construction Rating System
SOCIETY FOR PROTECTIVE COATINGS (SSPC)
SSPC PA 1 (2016) Shop, Field, and Maintenance Coating of Metals
SSPC Paint 20 (2002; E 2004) Zinc-Rich Primers (Type I, Inorganic, and Type II, Organic)
SSPC Paint 29 (2002; E 2004) Zinc Dust Sacrificial Primer, Performance-Based
SSPC SP 3 (1982; E 2004) Power Tool Cleaning
SSPC SP 6/NACE No.3 (2007) Commercial Blast Cleaning
U.S. DEPARTMENT OF DEFENSE (DOD)
UFC 3-301-01 (2019) Structural Engineering
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR Part 1926, Subpart R Steel Erection
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance with Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SECTION 05 12 00 Page 3
SD-01 Preconstruction Submittals
Erection and Erection Bracing Drawings; G
SD-02 Shop Drawings
Fabrication Drawings Including Details of Connections; G
SD-03 Product Data
Shop Primer
Welding Electrodes and Rods
Direct Tension Indicator Washers
Non-Shrink Grout
Tension Control Bolts
Recycled Content for Structural Steel; S
Recycled Content for Structural Steel Tubing; S
Recycled Content for Steel Pipe; S
SD-05 Design Data
Design Calculations for Steel Connections; G, Shoring and Temporary Bracing; G SD-06 Test Reports
Class B Coating
Bolts, Nuts, and Washers
Weld Inspection Reports
Direct Tension Indicator Washer Inspection Reports
Bolt Testing Reports
SD-07 Certificates
Steel
Bolts, Nuts, and Washers
Galvanizing
AISC Structural Steel Fabricator Quality Certification
AISC Structural Steel Erector Quality Certification
Welding Procedures and Qualifications
Welding Electrodes and Rods
Certified Welding Inspector
SECTION 05 12 00 Page 4
NDT Technician
Welding Procedure Specifications (WPS)
1.3 LEED REQUIREMENTS
In accordance to LEED NC:
Building Product Disclosure and Optimization – Environmental Product Declarations – MR Credit 2, Option 1:
a) Submit product EPD; refer to Division 013329 and the LEED BD+C v4 Reference Guide for full requirements. The EPD must conform to one of the disclosure types listed in below, in descending order of preference:
1. Product-specific Type III EPD (i.e., conforms to ISO 14025, 14040, 14044, and EN 15804 or ISO 21930 and has at least a cradle to gate scope).
2. Industry-wide (generic) EPD (i.e., conforms to ISO 14025, 14040, 14044, and EN 15804 or ISO 21930 and has at least a cradle to gate scope).
3. A publicly available, critically reviewed life-cycle assessment conforming to ISO 14044 (i.e., has at least a cradle to gate scope).
b) Provide LEED Submittal Cover Sheet in accordance with Section 013329.
Building Product Disclosure and Optimization, Sourcing of Raw Materials:
Option 2, Leadership Extraction Practices
a) Submit description of salvaged, refurbished or reused products.
b) Submit manufacturer’s data sheet or statement of pre-consumer and post-consumer recycled content. Indicate the percentage of the dollar value of the recycled content compared to the total dollar value of the product or assembly containing the product
c) Permanently installed, non-recycled wood and wood-based materials should be certified in accordance with Forest Stewardship Council Guidelines. This includes wood permanently installed in the project wood products. Submit all FSC product certification information including required Chain-of-Custody certificates and invoices tracking FSC purchase. Refer to Division 013329 and the LEED BD+C v4 Reference Guide for full requirements.
d) Provide LEED Submittal Cover Sheet in accordance with Section 013329.
Low-Emitting Materials – Exterior applied products (Healthcare and Schools Projects only):
a) For all exterior-applied adhesives, sealants, coatings, roofing, and waterproofing materials applied on site, meet the VOC limits of
SECTION 05 12 00 Page 5
California Air Resources Board (CARB) 2007 Suggested Control Measure (SCM) for Architectural Coatings, and South Coast Air Quality Management District (SCAQMD), Rule 1168, effective July 1, 2005. Refer to Division 013329 and the LEED BD+C v4.1 Reference Guide for full emissions requirements.
b) Two materials are prohibited and do not count toward total percentage compliance: hot-mopped asphalt for roofing, and coal tar sealants for parking lots and other paved surfaces.
c) Provide LEED Submittal Cover Sheet in accordance with Section 013329.
1.4 AISC QUALITY CERTIFICATION
Work must be fabricated by an AISC Certified Structural Steel Fabricator, in accordance with AISC 207 , Category BU. Submit AISC Structural Steel Fabricator quality certification.
Work must be erected by an AISC Structural Steel Certified Erector, in accordance with AISC 207 , Category CSE. Submit AISC Structural Steel erector quality certification.
1.5 QUALITY ASSURANCE
1.5.1 Preconstruction Submittals
1.5.1.1 Erection and Erection Bracing Drawings
Submit for record purposes. Indicate the sequence of erection, temporary shoring and bracing. The erection drawings must conform to AISC 303 .
1.5.2 Fabrication Drawing Requirements
Submit fabrication drawings for approval prior to fabrication. Prepare in accordance with AISC 303 , AISC 326 and AISC 325 . Fabrication drawings must not be reproductions of contract drawings. Sign and seal fabrication drawings by a registered professional engineer where components are part of a delegated design. Include complete information for the fabrication and erection of the structure's components, including the location, type, and size of bolts, welds, member sizes and lengths, connection details, blocks, copes, and cuts. Use AWS A2.4 standard welding symbols. Shoring and temporary bracing must be designed and sealed by a registered professional engineer and submitted for record purposes, with calculations, as part of the drawings. Clearly highlight any deviations from the details shown on the contract drawings highlighted on the fabrication drawings. Where such deviations impact strength or serviceability, deviations shall be submitted to the COR for approval.Explain the reasons for any deviations from the contract drawings.
1.5.3 Delegated Connection Design
Design structural steel connections indicated in the contract documents per AISC 303 , Option 3, using the connection loads indicated. Submit design calculations for steel connections signed and sealed by a registered professional engineer.
SECTION 05 12 00 Page 6
1.5.4 Certifications
1.5.4.1 Welding Procedures and Qualifications
Prior to welding, submit certification for each welder stating the type of welding and positions qualified for, the code and procedure qualified under, date qualified, and the firm and individual certifying the qualification tests. If the qualification date of the welder or welding operator is more than 6 months old, the welding operator's qualification certificate must be accompanied by a current certificate by the welder attesting to the fact that he has been engaged in welding since the date of certification, with no break in welding service greater than 6 months.
Conform to all requirements specified in AWS D1.1/D1.1M
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
Provide the structural steel system, including either shop primer or galvanizing as dictated by the contract documents, complete and ready for use. Provide structural steel systems including design, materials, installation, workmanship, fabrication, assembly, erection, inspection, quality control, and testing in accordance with AISC 303 , AISC 360 , ,and UFC 3-301-01 except as modified in this contract.
2.2 STEEL
Steel products should contain a minimum of 85 percent recycled content, or highest content available among options. Preference should be to products with components that are both extracted and manufactured within 100 miles of the project site, if available. Provide product documentation from supplier with regional materials information. Information must include location of material manufacturer and points of extraction, harvest or recovery for each material. Include statement indicating distance to project location, cost for each regional material and fraction by weight that is considered regional.
a) Submit manufacturer's data sheet or statement of pre-consumer and post-consumer recycled content. Indicated the percentage of the dollar value of the recycled content compared to the total dollar value of the product or assembly containing the product.
b) Provide Industry-wide (generic) Environmental, Product Declaration (EPD) with product submittals; if other EPD types are available, provide in addition to the industry-wide EPD.
c) Provide LEED Submittal Cover Sheet in accordance with Section 013329.
d) LEED Submittals shall be submitted and reviewed concurrently with product data submittal and samples.
2.2.1 Structural Steel
Wide flange and WT shapes, ASTM A992/A992M . Angles, Channels and Plates, minimum ASTM A36/A36M.
SECTION 05 12 00 Page 7
2.2.2 Structural Steel Tubing
ASTM A500/A500M , Grade C.
2.2.3 Steel Pipe
ASTM A53/A53M, Type E or S, Grade B, weight class as indicated.
2.3 BOLTS, NUTS, AND WASHERS
Submit the certified manufacturer's mill reports which clearly show the applicable ASTM mechanical and chemical requirements together with the actual test results for the supplied fasteners.
2.3.1 High-Strength Bolts
High strength bolts and nuts must be shipped together in the same shipping container. Fasteners indicated to be galvanized shall be tested by the supplier to show that the galvanized nut with the supplied lubricant provided may be rotated from the snug tight condition well in excess of the rotation required for pretensioned installation without stripping.
The supplier shall supply nuts that have been lubricated and tested with the supplied bolts.
2.3.1.1 Bolts
ASTM F3125/F3125M , Grade A325M A325, Type 1 3 Heavy Hex Head Style, plain finish. A hot dip zinc coating shall be provided when the underlying member is galvanized.
2.3.1.2 Nuts
ASTM A563, Grade and Style as specified in the applicable ASTM bolt standard. A hot dip zinc coating shall be provided when the underlying member is galvanized.
2.3.1.3 Direct Tension Indicator Washers
ASTM F959/F959M . Provide ASTM B695, Class 55, Type 1 galvanizing where components are used in contact with galvanized members. Submit product data for direct tension indicator washers.
2.3.1.4 Washers
ASTM F436/F436M , plain carbon steel. A hot-dip zinc coating shall be provided when the underlying member is galvanized.
2.3.2 Tension Control Bolts
ASTM F3125/F3125M , Grade F1852, Type 1, twistoff style assemblies consisting of steel structural bolts with splined ends, heavy-hex carbon steel nuts, and hardened carbon steel washers. Assembly finish must be plain except that when the underlying member is galvanized the finish must be a mechanically deposited zinc coating. Submit product data for tension control bolts.
SECTION 05 12 00 Page 8
2.3.3 Foundation Anchorage
2.3.3.1 Anchor Rods
ASTM F1554 Gr 55, Class 1A with supplement S1.
2.3.3.2 Anchor Nuts
ASTM A563, Grade A, hex style.
2.3.3.3 Anchor Washers
ASTM F844.
2.3.3.4 Anchor Plate Washers
ASTM A36/A36M.
2.4 STRUCTURAL STEEL ACCESSORIES
2.4.1 Welding Electrodes and Rods
AWS D1.1/D1.1M . Submit product data for welding electrodes and rods.
2.4.2 Non-Shrink Grout
ASTM C1107/C1107M , with no ASTM C827/C827M shrinkage. Grout must be nonmetallic. Submit product data for non-shrink grout.
2.4.3 Welded Shear Stud Connectors
ASTM A29/A29M, Grades 1010 through 1020. AWS D1.1/D1.1M , Table 7.1, Type B.
2.5 GALVANIZING
ASTM F2329/F2329M , ASTM F1136/F1136M , ASTM F2833 or ASTM B695 for threaded parts or ASTM A123/A123M for structural steel members, as applicable, unless specified otherwise galvanize after fabrication where practicable.
2.6 FABRICATION
Fabrication must be in accordance with the applicable provisions of AISC 325 . Fabrication and assembly must be done in the shop to the greatest extent possible. Punch, subpunch and ream, or drill bolt holes perpendicular to the surface of the member.
Compression joints depending on contact bearing must have a surface roughness not in excess of 500 micro inch as determined by ASME B46.1 , and ends must be square within the tolerances for milled ends specified in
ASTM A6/A6M.
Shop splices of members between field splices will be permitted only where indicated on the Contract Drawings. Splices not indicated require the approval of the Contracting Officer.
2.6.1 Markings
Prior to erection, identify members by a painted erection mark.
SECTION 05 12 00 Page 9
Connecting parts assembled in the shop for reaming holes in field connections must be match marked with scratch and notch marks. Do not locate erection markings on areas to be welded. Do not locate match markings in areas that will decrease member strength or cause stress concentrations.
2.6.2 Shop Primer
SSPC Paint 20 or SSPC Paint 29 , (zinc rich primer). Shop prime structural steel, except as modified herein, in accordance with SSPC PA 1 . Do not prime steel surfaces embedded in concrete, galvanized surfaces, surfaces to receive sprayed-on fireproofing, surfaces to receive epoxy coatings, or surfaces within 0.5 inch of the toe of the welds prior to welding (except surfaces on which metal decking and shear studs are to be welded). If flash rusting occurs, re-clean the surface prior to application of primer. Apply primer to a minimum dry film thickness of
2.0 mil. Submit shop primer product data.
Prime slip critical surfaces with a Class B coating in accordance with AISC 325 . Submit test report for Class B coating.
Prior to assembly, prime surfaces which will be concealed or inaccessible after assembly. Do not apply primer in foggy or rainy weather; when the ambient temperature is below 45 degrees F or over 95 degrees F; or when the primer may be exposed to temperatures below 40 degrees F within 48 hours after application, unless approved otherwise by the Contracting Officer. Repair damaged primed surfaces with an additional coat of primer.
2.6.2.1 Cleaning
SSPC SP 6/NACE No.3 , except steel exposed in spaces above ceilings, attic spaces, furred spaces, and chases that will be hidden to view in finished construction may be cleaned to SSPC SP 3 when recommended by the shop primer manufacturer. Maintain steel surfaces free from rust, dirt, oil, grease, and other contaminants through final assembly.
2.6.3 Fireproofing and Epoxy Coated Surfaces
Clean and prepare surfaces to receive sprayed-on fireproofing or epoxy coatings in accordance with the manufacturer's recommendations, and as specified in Section 07 81 00 SPRAY-APPLIED FIREPROOFING.
2.6.4 Surface Finishes
ASME B46.1 maximum surface roughness of 125 for pin, pinholes, and sliding bearings, unless indicated otherwise.
2.7 DRAINAGE HOLES
Drill adequate drainage holes to eliminate water traps. Hole diameter must be 1/2 inch and location indicated on the detail drawings. Hole size and locations must not affect the structural integrity.
PART 3 EXECUTION
3.1 ERECTION
a. Erection of structural steel, except as indicated in item b. below, must be in accordance with the applicable provisions of AISC 325 , SECTION 05 12 00 Page 10
AISC 303 and 29 CFR Part 1926, Subpart R .
b. For low-rise structural steel buildings (60 feet tall or less and a maximum of 2 stories), erect the structure in accordance with
AISC DESIGN GUIDE 10 .
After final positioning of steel members, provide full bearing under base plates and bearing plates using nonshrink non-metallic grout. Place nonshrink non-metallic grout in accordance with the manufacturer's instructions.
3.1.1 STORAGE
Store the material out of contact with the ground in such manner and location as to minimize deterioration.
3.2 CONNECTIONS
Except as modified in this section, design connections indicated in accordance with AISC 360 . Build connections into existing work. Do not tighten anchor bolts set in concrete with impact torque wrenches. Holes must not be cut or enlarged by burning. Bolts, nuts, and washers must be clean of dirt and rust, and lubricated immediately prior to installation.
3.2.1 High-Strength Bolts
Provide direct tension indicator washers in all ASTM F3125/F3125M , Grade A325 and Grade A490 bolted connections. Bolts must be installed in connection holes and initially brought to a snug tight fit. After the initial tightening procedure, fully tension bolts, progressing from the most rigid part of a connection to the free edges.
Fastener components shall be protected from dirt and moisture in closed containers at the site of the installation. Fastener components that are not incorporated into the work shall be returned to protected storage at the end of the work shift.
3.2.1.1 Installation of Direct Tension Indicator Washers (DTIW)
Where possible, install the DTIW under the bolt head and tighten the nut.
If the DTIW is installed adjacent to the turned element, provide a flat washer between the DTIW and nut when the nut is turned for tightening, and between the DTIW and bolt head when the bolt head is turned for tightening. In addition to the LIW, provide flat washers under both the bolt head and nut when ASTM F3125/F3125M , Grade A490 bolts are used.
3.2.2 Tension Control Bolts
Bolts must be installed in connection holes and initially brought to a snug tight fit. After the initial tightening procedure, fully tension bolts, progressing from the most rigid part of a connection to the free edges.
3.3 GAS CUTTING
Use of gas-cutting torch in the field for correcting fabrication errors is not permitted on any member in the structural framing.
SECTION 05 12 00 Page 11
3.4 WELDING
Welding must be in accordance with AWS D1.1/D1.1M Provide AWS D1.1/D1.1M qualified welders, welding operators, and tackers.
Develop and submit the Welding Procedure Specifications (WPS) for all welding, including welding done using prequalified procedures. Submit for approval all WPS, whether prequalified or qualified by testing.
3.4.1 Removal of Temporary Welds, Run-Off Plates, and Backing Strips
Remove backing strips from bottom flange of moment connections, backgouge the root pass to sound weld metal and reinforce with a 5/16 inch fillet weld minimum.
3.5 SHOP PRIMER REPAIR
Repair shop primer in accordance with the paint manufacturer's recommendation for surfaces damaged by handling, transporting, cutting, welding, or bolting.
3.6 GALVANIZING REPAIR
Repair damage to galvanized coatings using ASTM A780/A780M zinc rich paint for galvanizing damaged by handling, transporting, cutting, welding, or bolting. Do not heat surfaces to which repair paint has been applied.
3.7 FIELD QUALITY CONTROL
Perform field tests, and provide labor, equipment, and incidentals required for testing. Notify the Contracting Officer in writing of defective welds, bolts, nuts, and washers within 7 working days of the date of the inspection.
3.7.1 Welds
3.7.1.1 Visual Inspection
AWS D1.1/D1.1M . Furnish the services of AWS-certified welding inspectors for fabrication and erection inspection and testing and verification inspections. A Certified Welding Inspector must perform visual inspection on 100 percent of all welds. Document this inspection in the Visual Weld Inspection Log. Submit certificates indicating that certified welding inspectors meet the requirements of AWS QC1.
Inspect proper preparation, size, gaging location, and acceptability of all welds; identification marking; operation and current characteristics of welding sets in use.
3.7.1.2 Nondestructive Testing
Nondestructive testing must be in accordance with AWS D1.1/D1.1M .
Ultrasonic testing must be performed in accordance with Table 6.2 of AWS D1.1/D1.1M . Test locations must be selected by the Contracting Officer.
All personnel performing NDT must be certified in accordance with ANSI/ASNT CP-189 in the method of testing being performed. Submit certificates showing compliance with ANSI/ASNT CP-189 for all NDT technicians. If more than 20percent of welds made by a welder contain defects identified by testing, then all groove welds made by that welder
SECTION 05 12 00 Page 12 must be tested by ultrasonic testing, and all fillet welds made by that welder must be inspected by magnetic particle testing (MT) or dye penetrant testing (PT) as approved by the Contracting Officer. When groove welds made by an individual welder are required to be tested, magnetic particle or dye penetrant testing may be used only in areas inaccessible to ultrasonic testing. Retest all repaired areas. Submit weld inspection reports.
Testing frequency: Provide the following types and number of tests:
Test Type Number of Tests
Ultrasonic 50 percent of CJP Welds
Magnetic Particle 50 percent of PJP and Fillet Welds
Dye Penetrant 50 percent of PJP and Fillet Welds
3.7.2 Direct Tension Indicator Washers
3.7.2.1 Direct Tension Indicator Washer Compression
Test direct tension indicator washers in place to verify that they have been compressed sufficiently to provide the 0.015 inch gap, as required by ASTM F959/F959M . Submit direct tension indicator washer inspection reports.
3.7.3 High-Strength Bolts
3.7.3.1 Testing Bolt, Nut, and Washer Assemblies
Test a minimum of 3 bolt, nut, and washer assemblies from each mill certificate batch in a tension measuring device at the job site prior to the beginning of bolting start-up. Demonstrate that the bolts and nuts, when used together, can develop tension not less than the provisions specified in AISC 360 , depending on bolt size and grade. The bolt tension must be developed by tightening the nut. A representative of the manufacturer or supplier must be present to ensure that the fasteners are properly used, and to demonstrate that the fastener assemblies supplied satisfy the specified requirements. Submit bolt testing reports.
3.7.3.2 Inspection
Inspection procedures must be in accordance with AISC 360 . Confirm and report to the Contracting Officer that the materials meet the project specification and that they are properly stored. Confirm that the faying surfaces have been properly prepared before the connections are assembled. Observe the specified job site testing and calibration, and confirm that the procedure to be used provides the required tension.
Monitor the work to ensure the testing procedures are routinely followed on joints that are specified to be fully tensioned.
Inspect calibration of torque wrenches for high-strength bolts.
3.7.3.3 Testing
The Government has the option to perform nondestructive tests on 5 percent of the installed bolts to verify compliance with pre-load bolt tension requirements. Provide the required access for the Government to perform
SECTION 05 12 00 Page 13 the tests. The nondestructive testing will be done in-place using an ultrasonic measuring device or any other device capable of determining in-place pre-load bolt tension. The test locations must be selected by the Contracting Officer. If more than 10 percent of the bolts tested contain defects identified by testing, then all bolts used from the batch from which the tested bolts were taken, must be tested at the Contractor's expense. Retest new bolts after installation at the Contractor's expense.
3.7.4 Inspection and Testing of Steel Stud Welding
Perform verification inspection and testing of steel stud welding conforming to the requirements of AWS D1.1/D1.1M , Stud Welding Clause.
The Contracting Officer will serve as the verification inspector. Bend test studs that do not show a full 360 degree weld flash or have been repaired by welding as required by AWS D1.1/D1.1M , Stud Welding Clause.
Studs that crack under testing in the weld, base metal or shank will be rejected and replaced by the Contractor at no additional cost.
-- End of Section --
SECTION 05 12 00 Page 14
SECTION 05 21 00
STEEL JOIST FRAMING
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2015; Errata 1 2015; Errata 2 2016) Structural Welding Code - Steel
ASTM INTERNATIONAL (ASTM)
ASTM A36/A36M (2014) Standard Specification for Carbon Structural Steel
INTERNATIONAL CODE COUNCIL (ICC)
ICC IBC (2018) International Building Code
U.S. GREEN BUILDING COUNCIL (USGBC)
LEED NC (2009) Leadership in Energy and Environmental Design(tm) New Construction Rating System
SOCIETY FOR PROTECTIVE COATINGS (SSPC)
SSPC PA 1 (2016) Shop, Field, and Maintenance Coating of Metals
SSPC Paint 15 (1999; E 2004) Steel Joist Shop Primer
SSPC SP 2 (1982; E 2000; E 2004) Hand Tool Cleaning
STEEL JOIST INSTITUTE (SJI)
SJI LOAD TABLES (2010; Errata 1 2011; Errata 2 2012) 42nd Edition Catalog of Standard Specifications Load Tables and Weight Tables for Steel Joists and Joist Girders
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1926 Safety and Health Regulations for Construction
29 CFR 1926.757 Steel Erection; Open Web Steel Joists
SECTION 05 21 00 Page 1
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-01 Preconstruction Submittals
Welder Qualification
SD-02 Shop Drawings
Steel Joist Framing; G
SD-03 Product Data
Recycled Content Of Steel Products; S
SD-05 Design Data
Design Calculations; G
Blast Report; G
Blast Design Calculation; G
SD-06 Test Reports
Erection Inspection Welding Inspections
SD-07 Certificates
Certification of Compliance Blast Consultant Qualifications; G
1.3 LEED REQUIREMENTS
In accordance to LEED NC:
Building Product Disclosure and Optimization – Environmental Product Declarations – MR Credit 2, Option 1:
a) Submit product EPD; refer to Division 013329 and the LEED BD+C v4 Reference Guide for full requirements. The EPD must conform to one of the disclosure types listed in below, in descending order of preference:
1. Product-specific Type III EPD (i.e., conforms to ISO 14025, 14040, 14044, and EN 15804 or ISO 21930 and has at least a cradle to gate scope).
2. Industry-wide (generic) EPD (i.e., conforms to ISO 14025, 14040, 14044, and EN 15804 or ISO 21930 and has at least a cradle to gate scope).
SECTION 05 21 00 Page 2
3. A publicly available, critically reviewed life-cycle assessment conforming to ISO 14044 (i.e., has at least a cradle to gate scope).
b) Provide LEED Submittal Cover Sheet in accordance with Section 013329.
Building Product Disclosure and Optimization, Sourcing of Raw Materials:
Option 2, Leadership Extraction Practices
a) Submit description of salvaged, refurbished or reused products.
b) Submit manufacturer’s data sheet or statement of pre-consumer and post-consumer recycled content. Indicate the percentage of the dollar value of the recycled content compared to the total dollar value of the product or assembly containing the product
c) Permanently installed, non-recycled wood and wood-based materials should be certified in accordance with Forest Stewardship Council Guidelines. This includes wood permanently installed in the project wood products. Submit all FSC product certification information including required Chain-of-Custody certificates and invoices tracking FSC purchase. Refer to Division 013329 and the LEED BD+C v4 Reference Guide for full requirements.
d) Provide LEED Submittal Cover Sheet in accordance with Section 013329.
Low-Emitting Materials – Exterior applied products (Healthcare and Schools Projects only):
a) For all exterior-applied adhesives, sealants, coatings, roofing, and waterproofing materials applied on site, meet the VOC limits of California Air Resources Board (CARB) 2007 Suggested Control Measure (SCM) for Architectural Coatings, and South Coast Air Quality Management District (SCAQMD), Rule 1168, effective July 1, 2005. Refer to Division 013329 and the LEED BD+C v4.1 Reference Guide for full emissions requirements.
b) Two materials are prohibited and do not count toward total percentage compliance: hot-mopped asphalt for roofing, and coal tar sealants for parking lots and other paved surfaces.
c) Provide LEED Submittal Cover Sheet in accordance with Section 013329.
1.4 QUALITY ASSURANCE
Perform all work in compliance with the requirements set forth in
29 CFR 1926 .
1.4.1 Drawing Requirements
Submit drawings of steel joist framing including fabrication, specifications for shop painting, and identification markings of joists.
Show joist type and size, layout in plan, all applicable loads, deflection criteria, and erection details including methods of anchoring, framing at openings, type, size, and location and connections for and spacing of
SECTION 05 21 00 Page 3 bridging, requirements for field welding, and details of accessories as applicable. Show profiles for nonstandard joist configurations.
1.4.2 Certification of Compliance
Prior to construction commencement, submit certification for welder qualification, in compliance with AWS D1.1/D1.1M , welding operation, and tacker, stating the type of welding and positions qualified for, the code b and procedure qualified under, date qualified, and the firm and individual certifying the qualification tests. Submit certification of compliance for the following:
a. Steel Joist Institute Member Fabricator
b. 29 CFR 1926
c. 29 CFR 1926.757
d. Statement from steel joist manufacturer, that work was performed in accordance with approved construction documents and with SJI standard specifications, in accordance with ICC IBC Section 1704.2.5.2.
1.4.3 Blast Consultant Qualifications
Blast engineering consultant performing blast calculations shall be a licensed professional engineer, with formal training in Structural dynamics. Consultant shall have a minimum of 5 years of experience in providing qualified blast engineering services similar in design to that required for this project. "Qualified blast engineering services" is defined as "a minimum of three projects of similar value and scope that meet the satisfaction of the Owner and whose work has resulted in construction with a record of successful in-service performance for a period of at least 5 years". All requirements shall be addressed in submittal provided to the Contracting Officer for review and approval.
1.5 BLAST PERFORMANCE CRITERIA
1.5.1 Blast Design Criteria
Provide steel roof joist framing that are designed for compliance with requirements indicated. Each framing type shall be verified through analysis to meet the following performance requirements.
1.5.1.1 Design Blast Loads
The design blast load is a dynamic load to be used with an inelastic dynamic structural analysis method of the steel roof joist framing members.
a. Linearly decaying load function with peak pressure and impulse.
As indicated on the drawings.
b. Negative phase effects shall not be considered.
c. Rebound resistance shall be 50 percent.
A positive peak pressure is applied to the steel roof joist framing members in the downward direction. A negative peak pressure is applied to the steel roof joist framing members in the upward or uplift direction.
SECTION 05 21 00 Page 4
1.5.1.2 Analysis
Blast design of steel roof joist framing shall be performed using inelastic dynamic structural analysis methods.
1.5.1.3 Single Degree of Freedom Structural Response Limits
Response limits based on a Low Level of Protection (LLOP).
1.5.1.3.1 Flexural Response - Downward
Rotation of the steel roof joist framing members over the full length shall not exceed 3 degrees at the design blast loading.
Flexural response limits for downward loading are based on the assumption that deformation occurs by tensile yielding in the bottom chord. Top chords may need additional bracing to prevent buckling.
1.5.1.3.2 Flexural Response - Upward
Ductility ratio of the steel roof joist framing members shall not exceed
1.5 at the design blast loading.
Additional anchors may be needed to prevent pull-out failures. Bottom chords may need additional bracing to prevent lateral buckling.
1.5.1.3.3 Shear Response
Ductility ratio of the steel roof joist framing members shall not exceed
0.8 at the design blast loading.
Shear response limits apply if member capacity is limited by the capacity of the web members, or web connections, or support connections. Shear response ductility ratio is equal to the peak shear force divided by the shear capacity.
1.5.1.4 Static and Dynamic Increase Factors
A dynamic increase factor (DIF) of 1.19 may be applied to the yield stress for steel members to account for strain rate effects. In addition to the
DIF, a static increase factor (SIF) of 1.05 may also be applied to yield stress for steel members.
1.5.2 Blast Report
Submit blast report, including a summary narrative, structural design sketches, and Blast Design Calculations for all steel roof joist framing showing compliance with blast performance requirements for review and approval.
The blast report shall be prepared and submitted by a qualified blast engineering consultant as defined in the paragraph entitled "Blast Consultant Qualifications" of this specification. The blast report shall be signed and sealed by a registered professional engineer.
1.5.3 Blast Analyses Standards
All building components requiring blast resistance for the project must
SECTION 05 21 00 Page 5 meet requirements of Department of Defense (DoD) facilities and shall be designed using established methods and approaches for determining dynamic loads and dynamic structural response.
1.6 DELIVERY, STORAGE, AND HANDLING
Handle, transport, and store joists in a manner to prevent damage affecting their structural integrity. Verify piece count of all joist products upon delivery and inspect all joists products for damage. Report any damage to the joist supplier. Store all items off the ground in a well-drained location protected from the weather and easily accessible for inspection and handling. Store joists with top chord down and with joists in a vertical position. Store deep joists horizontally if they were shipped on their sides.
PART 2 PRODUCTS
2.1 SYSTEM DESCRIPTION
Designate steel joists on the drawings in accordance with the standard designations of the Steel Joist Institute. Joists of other standard designations or joists with properties other than those shown may be substituted for the joists designated provided the structural properties are equal to or greater than those of the joists shown and provided all other specified requirements are met.
2.2 STEEL JOISTS
Provide steel joists conforming to SJI LOAD TABLES . Design joists designated K, KCS, LH and DLH to support the loads given in the applicable standard load tables of SJI LOAD TABLES . Submit design calculations for special steel joists,,net uplift loads, non-SJI standard details, and field splices. Include cover letter signed and sealed by the joist manufacturer's registered design professional.
2.2.1 Steel Joist Camber
Camber joists according to SJI LOAD TABLES
2.2.2 Special Steel Joists
Provide special joists and connections capable of withstanding the design loads indicated with a live-load deflection less than L/360 for roof joists.
2.2.3 Steel Joist Substitutes and Outriggers
Provide joist substitutes and outriggers conforming to SJI LOAD TABLES with steel angle or channel members.
2.3 RECYCLED CONTENT
Provide products with an average Recycled Content Of Steel Products of postconsumer recycled content plus one half of preconsumer recycled content not less than 25 percent.
Steel products should contain a minimum of 85 percent recycled content, or highest content available among options. Preference should be to products with components that are both extracted and manufactured within 100 miles
SECTION 05 21 00 Page 6 of the project site, if available. Provide product documentation from supplier with regional materials information. Information must include location of material manufacturer and points of extraction, harvest or recovery for each material. Include statement indicating distance to project location, cost for each regional material and fraction by weight that is considered regional.
a) Submit manufacturer's data sheet or statement of pre-consumer and post-consumer recycled content. Indicated the percentage of the dollar value of the recycled content compared to the total dollar value of the product or assembly containing the product.
b) Provide Industry-wide (generic) Environmental, Product Declaration (EPD) with product submittals; if other EPD types are available, provide in addition to the industry-wide EPD.
c) Provide LEED Submittal Cover Sheet in accordance with Section 013329.
d) LEED Submittals shall be submitted and reviewed concurrently with product data submittal and samples.
2.4 ACCESSORIES AND FITTINGS
2.4.1 Bridging
Provide bridging of material, size, and type required by SJI LOAD TABLES for type of joist, chord size, spacing and span. Furnish additional erection bridging if required for stability.
2.4.2 Bearing Plates
Fabricate steel bearing plates from ASTM A36/A36M steel of size and thickness indicated.
2.4.3 Ceiling Extensions
Furnish ceiling extensions, either bottom-chord elements or a separate extension unit of enough strength to support ceiling construction. Extend ends to within 1/2 inch of finished wall surface unless otherwise indicated.
2.5 SHOP PAINTING
SSPC Paint 15 . Shop prime joists, except as modified herein, in accordance with SSPC PA 1 . Clean joists in accordance with SSPC SP 2 before priming. Do not prime joists to receive sprayed-on fireproofing.
If flash rusting occurs, re-clean the surface prior to application of primer. For joists which require finish painting under Section 09 90 00 PAINTS AND COATINGS, the primer paint must be compatible with the finish paint.
PART 3 EXECUTION
3.1 ERECTION
Install joists in conformance with SJI LOAD TABLES for the joist series indicated, and the requirements of 29 CFR 1926 and 29 CFR 1926.757 .
Handle and set joists avoiding damage to the members. Place the "tag
SECTION 05 21 00 Page 7 end" of joists as shown on the joist's placement plans. Ensure that square-end joists are erected right side up. Distribute temporary loads so that joist capacity is not exceeded.