Questions and Answers
Q. Noted that all existing Annunciation devices in the Building are 10” Bells, are these to be changed to Horn/Strobe and Bells?
A. Yes, change to horn/strobe (no bell)
Q. Are new Wire Pathways required to be in Light Wall Conduit or is Fire MC Cable sufficient?
A. Light Wall Conduit
Q. Are Existing Duct Detectors required to be replaced or only monitored? SOW does not mention anything regarding Duct Detectors.
A. Replace
Q. SOW requests 4 CO Detectors, 1-Inside and outside each Boiler room, Only 1 Boiler Room at the building, are the other 2 CO detectors required? And if so please provide locations
A. Only 1 CO detector is required inside the boiler room.