A21 - Island Creek Transformer Supply - AMDT002-DRWGS.pdf
PDF 10 MB Posted
- Attached to
- Island Creek Switchyard Transformer
- Solicitation number
- W912PM26RA006
About this file
These documents are detailed engineering design drawings for transformer switchyard equipment at the Island Creek Pumping Plant, part of the Roanoke River project by the U.S. Army Corps of Engineers. The drawings specify a comprehensive set of requirements for two 5,000 kVA, 115 kV Class II power transformers, including detailed technical specifications for transformer components, control cabinets, temperature monitoring systems, and temporary storage procedures. Key technical details include three-phase delta/grounded wye configuration, ONAN cooling class, nitrogen gas preservation system, fiber-optic temperature monitoring, and specific requirements for bushings, accessories, painting, testing, and environmental protection features. The project is located in Wilmington, North Carolina, with a solicitation number W912PM26RA006 and an issue date of October 2025.
The design drawings provide extensive technical documentation covering transformer tank construction, control cabinet layout, electrical and temperature monitoring schematics, annunciator functional requirements, and site work flowcharts. Specific requirements include detailed specifications for temperature sensors, winding and oil temperature indicators, gas-in-oil monitors, pressure relief devices, grounding systems, and communication interfaces. The drawings also outline a comprehensive process for transformer delivery, temporary storage, site installation, and commissioning, with provisions for government inspection and testing at various stages of the project.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W912PM26RA006
ROANOKE RIVER
WILMINGTON DISTRICT
ISLAND CREEK PUMPING PLANT
TRANSFORMER SWITCHYARD
A N
S I
D
T R
A N
S F
O R
M E
R S
W
IT
C H
Y A
R D
R O
A N
O K
E R
IV
E
R
IS
L
A N
D C
R E
E K
P U
M P
IN
G
P L
A N
T
W
P M
R A
O C
T O
B E
R
W
IL
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
P O
R T
L A
N D
O
R E
G O
N
H Y
D R
O E
L E
C T
R
IC
D E
S
IG
N C
E N
T E
R
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
S
A
W
IN
G N
U M
B E
R
F
IL
E N
A M
E
J O
R D
A N
S F
IN
K
P
.E
V
IC
IN
IT
Y M
A P
P R
O
JE
C T
L O
C A
T
IO
N A
N D
G-001
J .R
O S
E N
T H
A L
S .C
O T
N E
R
P
P
.0
G -0
.d g n
G -0
D .F
IL
E
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
JAMES D. CALNON, P.E.
CHIEF, MECHANICAL/STRUCTURAL BRANCH
JOHN Z. YEN, P.E.
CHIEF, ELECTRICAL BRANCH
JORDAN S. FINK, P.E.
DIRECTOR, HYDROELECTRIC DESIGN CENTER
DATEDATE
DATE
SUBMITTED BY: APPROVED BY:
SUBMITTED BY:
DOCUMENTS WITHIN THE SCOPE OF THEIR EMPLOYMENT AS REQUIRED BY ER 1110-1-8152.
THE INITIALS OR SIGNATURES AND REGISTRATION DESIGNATIONS OF INDIVIDUALS APPEAR ON THESE PROJECT
THIS PROJECT WAS DESIGNED BY THE HYDROELECTRIC DESIGN CENTER OF THE U.S. ARMY CORPS OF ENGINEERS.
of Engineers
US Army Corps
SOLICITATION NO.:
CONTRACT NO.:
ISSUE DATE: OCTOBER 2025
VICINITY MAP LOCATION MAP
SCALE: NTS SCALE: NTS
NN
ISLAND CREEK SITE MAP
SCALE: NTS
N
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
J O
R D
A N
S F
IN
K
P
IN
E X
T O
D R
A W
IN
G
S
G-002
J .R
O S
E N
T H
A L
S .C
O T
N E
R
P
.0
G -0
.d g n
.F
IL
S
A N
S F
O R
M E
R S
W
IT
C H
Y A
R D
R O
A N
O K
E R
IV
E
R
IS
L
A N
D C
R E
E K
P U
M P
IN
G
P L
A N
T
W
P M
R A
O C
T O
B E
R
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
P O
R T
L A
N D
O
R E
G O
N
H Y
D R
O E
L E
C T
R
IC
D E
S
IG
N C
E N
T E
R
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
A
W
IN
G N
U M
B E
R
F
IL
E N
A M
E
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
INDEX TO DRAWINGS
GENERAL
FILE NUMBER
NO.
SHEET
TITLE FILE NUMBER TITLE
REFERENCE
REQ'D
AS-BUILT
INDEX TO REFERENCE DRAWINGS
STRUCTURAL INSTALLS
ELECTRICAL INSTALLS
R D
A N
S F
IN
K
P
.E
S U
M M
A R
Y S
H E
E T
T R
A N
S F
O R
M E
R R
E Q
U
IR
E M
E N
T S
S T
A T
IO
N
T R
A N
S F
O R
M E
R S
G-003
D
F
IL
E R
S .C
O T
N E
R
P
.0
G -0
.d
F
IL
S
A N
S F
O R
M E
R S
W
IT
C H
Y A
R D
R O
A N
O K
E R
IV
E
R
IS
L
A N
D C
R E
E K
P U
M P
IN
G
P L
A N
T
W
P M
R A
O C
T O
B E
R
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
P O
R T
L A
N D
O
R E
G O
N
H Y
D R
O E
L E
C T
R
IC
D E
S
IG
N C
E N
T E
R
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
A
W
IN
G N
U M
B E
R
F
IL
E N
A M
E
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
NAMEPLATE DATA:
TANK AND CONSTRUCTION:
ACCESSORIES:
BUSHINGS:
INSULATING OIL:
SPARE PARTS:
FACTORY ASSEMBLY AND PAINT:
FACTORY ACCEPTANCE TESTS (F.A.T.):
∙ NAPTHENIC BASE - ASTM D 3487 TYPE II; 0.25% - 0.3% BY MASS OF OXIDATION INHIBITOR
(4) COMPLETELY ASSEMBLED AND WITNESSING OF FACTORY ACCEPTANCE TESTS
(3) COMPLETED CORE/COIL ASSEMBLY, BUT PRIOR TO TANKING
(2) AFTER COMPLETION OF WINDINGS BUT PRIOR TO LANDING ON CORE
(1) DESIGN REVIEW MEETING
∙ INSPECTIONS: GOVERNMENT INSPECTIONS PERFORMED DURING
FOR ONE WEEK PRIOR TO OIL FILLING.
∙ INTERIOR PAINT: PRIMER COAT, OIL-RESISTANT FINISH COAT - WHITE. ALLOW TO CURE
SLIP COATING.
STAINLESS STEEL CABINETS, SHALL REMAIN UNPAINTED. COVER TO RECEIVE A NON-
(MUNSELL 5BG 7/0.4 HIGH-GLOSS). CORROSION RESISTANT SURFACES, AND
∙ EXTERIOR PAINT: PRIMER COAT, EPOXY BASE COAT, POLYURETHANE TOP COAT
MATCH-MARKED FOR EASE OF REASSEMBLY.
∙ ASSEMBLY: TRANSFORMERS TO BE FULLY ASSEMBLED, WITH REMOVABLE COMPONENTS
REQUIREMENTS SUMMARY SHEET
ISLAND CREEK PUMPING STATION 115 KV CLASS II POWER TRANSFORMERS
(REFERENCE SPECIFICATION SECTION 48 19 23.04 26)
∙ RADIATORS: HOT-DIP GALVANIZED.
CONSTRUCTION.
ORIENTED STEEL. MAXIMUM DESIGN FLUX DENSITY OF 1.75 TESLA. STEP-LAP
∙ CORE: LAMINATIONS MAXIMUM THICKNESS OF 0.270MM, COLD-ROLLED, GRAIN-
COMPONENTS.
∙ SEISMIC: SEISMIC CALCULATIONS REQUIRED FOR MAIN TANK AND ALL MAJOR
∙ LIFTING EYES: DESIGN LOADS FOR EACH EYE SHALL BE TWO TIMES THE ACTUAL LOAD.
∙ BASE: DESIGNED FOR PAD MOUNTING WITH SEISMIC WELDING TO STEEL PLATES.
ANCHOR POST.
LUG, DBI-SALA MODEL 8517412, DESIGNED FOR USE WITH THE DBI-SALA FALL ARREST
∙ PORTABLE FALL ARREST ANCHOR POST MOUNTING PLATE: UNI-ANCHOR PLATE AND
TEMPERATURE OF 25 DEGREES CELSIUS.
∙ OIL LEVEL MARKING: OPERATING OIL LEVEL MARKING ON THE TANK FOR AN OIL
∙ VALVES: STAINLESS STEEL BALL-TYPE (WITH THE EXCEPTION OF BUTTERFLY VALVES)
SHALL NOT BE USED FOR GASKET GROOVES OF RECTANGULAR CROSS-SECTION.
∙ GASKETS: NITRILE NBR (BUNA-N), DURO 50-60, 25% COMPRESSION. O-RING GASKETS
∙ MAN-HOLE: 24-INCH DIAMETER (MINIMUM TWO)
∙ SFRA TEST SHIPPING BUSHING: 2.5 KV CLASS, 45 KV BIL, 100 AMP
∙ CORE GROUNDS: 2.5 KV CLASS, 45 KV BIL, 100 AMP
BULK-TYPE, LIGHT CONTAMINATION, 125 DEGREES CELSIUS TEMPERATURE RISE RATING
∙ NEUTRAL (X0): 5 KV CLASS, 75 KV BIL, 1,000 AMP, PORCELAIN CONSTRUCTION,
BULK-TYPE, LIGHT CONTAMINATION, 125 DEGREES CELSIUS TEMPERATURE RISE RATING
∙ SECONDARY WINDING (X): 5 KV CLASS, 75 KV BIL, 1,000 AMP, PORCELAIN CONSTRUCTION, RESIN-IMPREGNATED SYNTHETIC (RIS) CONDENSER CORE DESIGN
∙ PRIMARY WINDING (H): 115 KV CLASS, 650 KV BIL, 400 AMP, COMPOSITE EXTERIOR WITH
ENGRAVED BLACK LETTERING.
CONTROL AND POWER CABINETS SHALL BE ANODIZED ALUMINUM OR STAINLESS STEEL WITH
BUSHINGS MADE OF STAINLESS STEEL WITH BLACK LETTERING. DEVICE NAMEPLATES WITHIN THE
NAMEPLATES SHALL BE PROVIDED FOR THE HIGH-VOLTAGE BUSHINGS AND LOW-VOLTAGE
NAMEPLATE FOR SLING LOCATIONS AND LIFT POSITIONS SHALL ALSO BE PROVIDED. EQUIPMENT
VACUUM THE TANK WILL WITHSTAND, AND CALCULATED X/R RATIO. AN ADDITIONAL DIAGRAM
MANUFACTURING DATE, PLANT LOCATION, GOVERNMENT CONTRACT NUMBER, PRESSURE AND
∙ NAMEPLATES: CAST BRONZE OR STAINLESS STEEL; IEEE C57.12.00, TABLE 7, INCLUDING
- FOLD-DOWN MAINTENANCE TRAY ON INSIDE OF CONTROL CABINET DOOR.
HUMIDISTAT-THERMOSTAT CONTROL.
- PTC RESISTOR DESIGN ENCLOSURE HEATERS WITH INTEGRAL FANS, AND INDUSTRIAL GRADE
- 120 V AC, 20 A HOSPITAL GRADE GFCI RECEPTACLE MOUNTED INSIDE THE CONTROL CABINET.
- 120 V AC, 1,000 LUMEN LED TYPE A19 LAMPS WITH DOOR-ACTUATED SWITCH.
DOOR FOR VIEWING.
PANEL WITHIN CONTROL CABINET, WITH WEATHERPROOF WINDOW PROVIDED IN CABINET
- TRANSFORMER FIBER-OPTIC TEMPERATURE MONITOR (QUALITROL 408), MOUNTED ON SWING
CABINET, WITH WEATHERPROOF WINDOW PROVIDED IN CABINET DOOR FOR VIEWING.
- TWO 10 PT. ANNUNCIATORS (SEL MODEL 2533) MOUNTED ON SWING PANEL WITHIN CONTROL
- LOCKOUT RELAY WITH TRIP COIL MONITORING AND INDICATORS (ELECTROSWITCH SERIES 24)
∙ SPECIAL FEATURES:
- 125 AND 250 V DC CIRCUITS - RATED 125/250 OR 250 V DC, AND 10,000 A INTERRUPTING
- 120 V AC CIRCUITS - RATED 250 V DC AND 120/240 OR 240 V AC, AND 10,000 A INTERRUPTING
∙ MOLDED-CASE CIRCUIT BREAKERS:
120 V AC CIRCUITS - 10 A
- SINGLE-BREAK INDUCTIVE LOAD INTERRUPTING RATING: 125 V DC CIRCUITS - 1.5 A;
- RATED FOR 600 V AC OR 250 V DC
∙ SWITCHES:
120 V AC CIRCUITS - 6.0 A
- SINGLE-CONTACT INDUCTIVE LOAD INTERRUPTING CAPACITY: 125 V DC CIRCUITS - 1.0 A;
- RATED FOR 125 V DC OR 120 V AC; MEETS REQUIREMENTS OF NEMA ICS5; 10 A CONTACTS
∙ AUXILIARY RELAYS:
∙ TERMINAL BLOCKS: 600 V, 30 A MINIMUM, 90 ºC RATED TERMINATIONS.
AND LIQUID-TIGHT HUBS.
APPLIED. OUTLET AND JUNCTION BOXES SHALL BE CAST IRON WITH SCREW-ON IRON ALLOY COVERS
NOT ALLOWED. ALL CONDUIT THREADED JOINTS SHALL HAVE A CONDUCTIVE JOINT COMPOUND
∙ CONDUIT: ALL WIRING TO BE RUN IN CONDUIT. WIRE RUNS THROUGH TANK REINFORCING CHANNELS
∙ WIRING: XLPE
∙ GOVERNMENT-FURNISHED POWER: CONTROL POWER - 125 V DC; ANNUNCIATION POWER - 125 V DC
SOLAR SHIELDING ON TOP, FRONT AND SIDE PANELS OF ENCLOSURES.
WINDOWS FOR VIEWING THE FIBER-OPTIC TEMPERATURE MONITOR AND ANNUNCIATOR.
∙ CABINET MATERIAL: WEATHER-PROOF TYPE 304 STAINLESS STEEL WITH LOCKING PROVISIONS.
CONTROL CABINET:
SURGE ARRESTERS:
∙ (QTY 1): VALVE OF EACH SIZE AND TYPE
∙ (QTY 1): PRESSURE REGULATOR FOR NITROGEN-GAS EQUIPMENT
∙ (QTY 1): FUSE OF EACH TYPE AND RATING
PLATE TO THE TRANSFORMER TEMPERATURE MONITOR FIBER-OPTIC MODULE
∙ (QTY 6): FIBER OPTIC EXTENSION CABLE THAT CONNECTS THE FEED-THROUGH WALL
∙ (QTY 1): OIL TEMPERATURE INDICATOR
∙ (QTY 1): WINDING TEMPERATURE INDICATOR
∙ (QTY 1): LIQUID LEVEL INDICATOR
∙ (QTY 1): RAPID PRESSURE RISE RELAY
∙ (QTY 1): PRESSURE RELIEF DEVICE
∙ (QTY 1): RELAY OF EACH TYPE AND RATING
∙ (QTY 1): COMPLETE GASKET SET
∙ (QTY 1): SET OF GASKETS FOR TRANSFORMER REASSEMBLY
∙ (QTY 2): 15 KV LOW-VOLTAGE / NEUTRAL BUSHING
∙ (QTY 1): 138 KV HIGH-VOLTAGE WINDING BUSHING
TO A TRANSFORMER TANK GOUND PAD
∙ GROUNDING: #4/0 AWG INSULATED GOUNDING CONDUCTORS FROM EACH ARRESTER
∙ RATINGS: 70 KV MCOV; 90 KV DUTY CYCLE
∙ PROVIDED FOR HV BUSHINGS
∙ PORTABLE FALL ARREST SYSTEM ANCHOR POST WITH DAVIT ARM (DBI-SALA MODEL 8516691)
∙ ON-LINE DISSOLVED HYDROGEN AND MOISTURE MONITOR (SERVERON TM1)
∙ RAPID PRESSURE RISE RELAY (QUALITROL 900)
MEASUREMENT (QUALITROL 408)
∙ TRANSFORMER TEMPERATURE MONITOR WITH FIBER-OPTIC WINDING TEMPERATURE
∙ DIRECTED-FLOW PRESSURE RELIEF DEVICE WITH DISCHARGE PIPING (QUALITROL XPRD)
∙ DUAL TANK NITROGEN REGULATOR CABINET WITH ELECTRICAL PACKAGE (ABB INERTAIRE RND2)
∙ WTI AND OTI GAUGES
∙ OIL LEVEL INDICATOR
∙ ANALOG TEMPERATURE GAUGE FUNCTIONAL VERIFICATION
TESTS DURING TRANSFORMER F.A.T.
∙ EACH HIGH-VOLTAGE BUSHING SHALL UNDERGO CAPACITANCE AND POWER FACTOR
∙ ALL ELECTRICAL AND ELECTO-MECHANICAL DEVICES SHALL BE FUNCTIONALLY TESTED
∙ DE-ENERGIZED TAP CHANGER MECHANICAL OPERATIONAL TEST (5 COMPLETE CYCLES)
CONFIGURATION
- ONE SFRA TEST TO BE PERFORMED WITH THE TRANSFORMER IN THE SHIPPING
AND OIL FILLED
- ONE SFRA TEST TO BE PERFORMED WITH THE TRANSFORMER FULLY ASSEMBLED
- CABLE INTEGRITY TEST REQUIRED
∙ SWEEP FREQUENCY RESPONSE ANALYSIS (WITH ELECTRONIC DATA FILES)
∙ LEAKAGE REACTANCE (WITH ELECTRONIC DATA FILES)
500 PC; ONE HOUR LEVEL: 300 PC
∙ INDUCED VOLTAGE TEST ACCEPTANCE CRITERIA: 7,200 CYCLE ENHANCEMENT LEVEL:
∙ AUDIBLE SOUND LEVEL TESTS SHALL BE PERFORMED ON FIRST TRANSFORMER TESTED
∙ LIGHTNING IMPULSE TESTS
∙ TEMPERATURE RISE TESTS SHALL BE PERFORMED ON FIRST TRANSFORMER TESTED
∙ ALL 'ROUTINE' TESTS (IEEE C57.12.00, TABLE 17)
∙ MAXIMUM OIL VOLUME: 3,000 GALLONS
∙ MAXIMUM SOUND LEVEL: 67 DB
∙ OIL PRESERVATION SYSTEM: NITROGEN GAS BLANKETED
∙ TEMPERATURE RISE: 65 ºC
∙ PRIMARY WINDING (H) DETC: 5 TAPS; 2 @ +2.5%, 2 @ -2.5% OF NOMINAL 115 KV TAP
∙ IMPEDANCE: 7.5 % (H-X)
∙ FREQUENCY: 60 HZ
∙ PHASING: THREE-PHASE
∙ BIL LEVELS, KV: 550 (H) / 75 (X) / 75 (X0)
∙ VOLTAGE RATINGS: 115,000 DELTA (H) - 4,160 GRDY (X)
∙ KVA RATING: 5,000
∙ COOLING CLASS: ONAN
∙ TYPE: CLASS II GSU POWER TRANSFORMER
T A
IL
S
P O
R T
L A
N D
O
R E
G O
N
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
W
IL
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
W
IL
M
IN
G T
O N
D
IS
T R
A N
O K
E R
IV
E
R
IS
L
A N
D C
R E
E K
P U
M P
IN
G
P L
A N
T
W
P M
R A
.C
O T
N E
R P
.E
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
H Y
D R
O E
L E
C T
R
IC
D E
S
IG
N C
E N
T E
R
IC
P
.0
S -1
.d g n A
N S
I D
D
F
IL
E R
D
F
IL
E R
S T
A T
IO
N
T R
A N
S F
O R
M E
R S
T R
A N
S F
O R
M E
R F
O U
N D
A T
IO
N
P A
D
S-101
J O
R D
A N
S F
IN
K
P
A N
S F
O R
M E
R S
W
IT
C H
Y A
R D
OUTLINE
TRANSFORMER BASE
DETAIL - TRANSFORMER SEISMIC ANCHORAGE
TRANSFORMER STRUCTURAL BASE
(TYPICAL)
EMBEDDED STEEL MOUNTING PLATE
TRANSFORMER FOUNDATION PAD
TRANSFORMER FOUNDATION PAD
QUENCH ROCK
TRANSFORMER
OIL CONTAINMENT WALL
TRANSFORMER FOUNDATION PAD
(SEE NOTE 4 REGARDING ANCHORAGE)
EMBEDDED STEEL MOUNTING PLATE
ANCHOR STUDS
MOUNTING PLATES
EMBEDDED STEEL
S O
L
IC
IT
A
T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
A
M A
R K
S I Z
E
S U
B M
IT
T
E D
B Y
D A
T E
C O
N T
R A
C T
N O
D R
A W
N B
Y
IS
S
U E
D A
T E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
C H
E C
K E
D B
Y
®of Engineers
US Army Corps ®of Engineers
US Army Corps
D R
A W
IN
G
N O
F
IL
E N
A M
E
TRANSFORMER SEISMIC ANALYSIS REPORT.
BY THE SWITCHYARD CONTRACTOR PER THE REQUIREMENTS OF THE
TRANSFORMER WILL BE FIELD WELDED TO THE EMBEDDED STEEL CHANNELS
REQUIREMENTS OF SPECIFICATIONS SECTION 48 20 00.04 26, THE
AFTER ALL TRANSFORMER TESTING HAS BEEN COMPLETED PER THE
4. AFTER POSITIONING OF THE TRANSFORMER ON THE FOUNDATION PAD, AND
SUPERVISOR.
THE PAD IN COORDINATION WITH THE SWITCHYARD CONTRACTOR FIELD
3. MOVE THE TRANSFORMER ONTO THE FOUNDATION PAD, AND POSITION ON
CHANNEL DIMENSIONS.
THAT WILL COINCIDE WITH THE TRANSFORMER STRUCTURAL BASE
2. THE FOUNDATION PAD WILL HAVE EMBEDDED STEEL MOUNTING PLATES
WHICH WILL BE CONSTRUCTED BY OTHERS UNDER SEPARATE CONTRACT.
HOW THE TRANSFORMER WILL BE POSITIONED ON A FOUNDATION PAD,
1. THIS DRAWING IS CONSIDERED 'FOR INFORMATION ONLY' AND INDICATES
O C
T O
B E
R
D2
AND EMBEDDED STEEL MOUNTING PADS
PLAN - TRANSFORMER FOUNDATION PAD
SCALE: 1/4" = 1' - 0"
A1
WITH OIL CONTAINMENT
ELEVATION - TRANSFORMER FOUNDATION PAD
SCALE: 3/8" = 1' - 0"
GENERAL NOTES
(M
X
IM
U M
195" (MAXIMUM)
R D
A N
S F
IN
K
P
.E
S H
E E
T
L A
Y O
U T
A N
D L
IM
IT
IN
G
D
IM
E N
S
IO
N S
S T
A T
IO
N
T R
A N
S F
O R
M E
R S
E-101
D
F
IL
E R
S .C
O T
N E
R
P
.0
E -1
.d
F
IL
S
A N
S F
O R
M E
R S
W
IT
C H
Y A
R D
R O
A N
O K
E R
IV
E
R
IS
L
A N
D C
R E
E K
P U
M P
IN
G
P L
A N
T
W
P M
R A
O C
T O
B E
R
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
P O
R T
L A
N D
O
R E
G O
N
H Y
D R
O E
L E
C T
R
IC
D E
S
IG
N C
E N
T E
R
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
A
W
IN
G N
U M
B E
R
F
IL
E N
A M
E
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
PROTECTIVE COVER
CORE
(#4 AWG)
GROUNDING CABLE
BUSHING
CORE GROUND
TANK COVER
CORE FRAME
(#4 AWG)
GROUNDING CABLE
TANK COVER
IDENTIFICATION (TOP VIEW)
TRANSFORMER TANK SEGMENT
X0
H1 H2 H3
H1 H2 H3
X0
X1
X2
X3
BUSHING SIDE)
(HIGH-VOLTAGE
SEGMENT 3
SEGMENT 2
SEGMENT 1
BUSHING SIDE)
(LOW-VOLTAGE
SEGMENT 4
TRANSFORMER DEVICES
3 3 - COVER
AS DES.
AS DES.
45 AS DES.
AS DES.
15 1
38 AS DES.
AS DES.
COVER
COVER
1,3
1,3
2, COVER
COVER
COVER
3 - COVER
3 - COVER
HIGH-VOLTAGE (H) BUSHING
1.5-INCH UPPER FILTER VALVE
3-INCH VACUUM VALVE
RADIATOR (TYPICAL)
ANALOG TEMPERATURE GAUGES
RADIATOR ISOLATION VALVE
LIFTING EYE (TYPICAL)
SKID-TYPE STRUCTURAL BASE
LOW-VOLTAGE (X) BUSHING
OIL LEVEL INDICATOR
CONTROL CABINET
3-INCH MAIN OIL DRAIN VALVE
1.5-INCH LOWER FILTER VALVE
PRESSURE RELIEF DEVICE WITH DISCHARGE PIPING
MANHOLE ACCESS COVER
FALL ARREST SYSTEM MOUNTING BRACKET
CORE & CORE FRAME GROUND BUSHINGS (SEE FIG. 2)
DUAL TANK NITROGEN REGULATOR CABINET
THERMOWELLS (QTY. 3 - STANDARD, QTY. 2 - HEATED)
GAS-IN-OIL MONITOR
JACKING FACILITIES (TYPICAL)
TRANSFORMER NAMEPLATE LOCATION
LOW-VOLTAGE BUSHING ENCLOSURE (SEE NOTE 5)
5KV CABLE STRAIN RELIEF MOUNTING BRACKET
SURGE ARRESTER
SURGE ARRESTER REMOVABLE MOUNTING BRACKET
LOW-VOLTAGE NEUTRAL (X0) BUSHING
ITEM QTY SEGMENT DEVICE DESCRIPTION EXAMPLE BRAND EXAMPLE MODEL NUMBER
MOSER GLASER
QUALITROL
QUALITROL
QUALITROL
MILWAUKEE VALVE
MILWAUKEE VALVE
MILWAUKEE VALVE
MILWAUKEE VALVE
MILWAUKEE VALVE
MILWAUKEE VALVE
QUALITROL
DBI-SALA
ABB
XPRD
SERIES 104
F20SS, CLASS 150
F20SS, CLASS 150
F20SS, CLASS 150
F20SS, CLASS 150
F20SS, CLASS 150
F20SS, CLASS 150
SERIES 042
8517412
RND2
DURESCA, TYPE DTIOA(S)
L C
H2
H1 H3
X1
X2
X0
X3
129 MILWAUKEE VALVE F20SS, CLASS 1502 1-INCH OIL SAMPLING VALVE
RAPID PRESSURE RISE RELAY
SERVERON TM1
1.5-INCH GAS-IN-OIL MONITOR INTERFACE VALVE
AS DES.
4 LOW-VOLTAGE BUSHING GROUND CONDUCTOR CONDUIT
1.5-INCH RAPID PRESSURE RISE RELAY INTERFACE VALVE
LOW-VOLTAGE BUSHING GROUND CONDUCTOR
BUSHING ENCLOSURE AND INTERNAL LAYOUT.
5. SEE SHEET E-105 FOR THE DETAILED REQUIREMENTS OF THE LOW-VOLTAGE
PER-TRANSFORMER BASIS.
4. THE ITEMS LISTED IN THE TABLE OF TRANSFORMER DEVICES ARE ON A
NOT INTENDED TO INDICATE THE ACTUAL QUANTITY.
3. THE RADIATORS AS DEPICTED INDICATE THE PERMISSIBLE LOCATIONS AND IS
HAVE BEEN INDICATED WITH DASHED OUTLINES.
FOR THE PURPOSES OF DRAWING CLARITY, SOME EQUIPMENT LOCATIONS2.
PROPER INTERCONNECTION TO THE SWITCHYARD EQUIPMENT.
FOR THE MANUFACTURER'S USE IN DESIGNING THE TRANSFORMERS FOR
1. THE TRANSFORMER LAYOUT AND LIMITING DIMENSIONS HAVE BEEN PROVIDED
BUSHING
CORE FRAME
GENERAL NOTES:
H2
PLAN - COVER
SCALE: NTS
L8
FIGURE 1
SCALE: NTS
B2
ELEVATIOIN - SEGMENT 1
SCALE: NTS
D10
FIGURE 2 - CORE & CORE FRAME GROUNDING
SCALE: NTS
A11
DESIGNATION
FIGURE 3 - PHASE RELATION OF TERMINAL
SCALE: NTS
/2
2 3
33 7
9 8
29 26
2 3
(M
X
IM
U M
J O
R D
A N
S F
IN
K
P
.E
S H
E E
T
L A
Y O
U T
A N
D L
IM
IT
IN
G
D
IM
E N
S
IO
N S
S T
A T
IO
N
T R
A N
S F
O R
M E
R S
E-102
D
F
IL
E R
S .C
O T
N E
R
P
.0
E -1
.d
F
IL
S
A N
S F
O R
M E
R S
W
IT
C H
Y A
R D
R O
A N
O K
E R
IV
E
R
IS
L
A N
D C
R E
E K
P U
M P
IN
G
P L
A N
T
W
P M
R A
O C
T O
B E
R
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
P O
R T
L A
N D
O
R E
G O
N
H Y
D R
O E
L E
C T
R
IC
D E
S
IG
N C
E N
T E
R
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
A
W
IN
G N
U M
B E
R
F
IL
E N
A M
E
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R
SH2 H1H3
H H
X0 X1 X2 X3
SEGMENT 1
SEGMENT 2
BUSHING SIDE)
(LOW-VOLTAGE
SEGMENT 4
BUSHING SIDE)
(HIGH-VOLTAGE
SEGMENT 3
TRANSFORMER DEVICES
ITEM QTY SEGMENT DEVICE DESCRIPTION EXAMPLE BRAND EXAMPLE MODEL NUMBER
49 AS DES.
AS DES.
AS DES.
3 3 - COVER
3 - COVER
3 - COVER
COVER
COVER
2, COVER
1,3
1,3
1,3
HIGH-VOLTAGE (H) BUSHING
LOW-VOLTAGE NEUTRAL (X0) BUSHING
LOW-VOLTAGE (X) BUSHING
SURGE ARRESTER
SURGE ARRESTER REMOVABLE MOUNTING BRACKET
CORE & CORE FRAME GROUND BUSHINGS (SEE FIG. 2)
RADIATOR (TYPICAL)
RADIATOR ISOLATION VALVE
DUAL TANK NITROGEN REGULATOR CABINET
CONTROL CABINET
OIL LEVEL INDICATOR
THERMOWELLS (QTY. 3 - STANDARD, QTY. 2 - HEATED)
GAS-IN-OIL MONITOR
3-INCH MAIN OIL DRAIN VALVE
1.5-INCH LOWER FILTER VALVE
1.5-INCH UPPER FILTER VALVE
3-INCH VACUUM VALVE
PRESSURE RELIEF DEVICE WITH DISCHARGE PIPING
DETC HANDWHEEL
LIFTING EYE (TYPICAL)
JACKING FACILITIES (TYPICAL)
SKID-TYPE STRUCTURAL BASE
STRUCTURAL BASE BRACKETS FOR WELDING BASE TO PAD (SHEET S-101)
LOW-VOLTAGE BUSHING ENCLOSURE (SEE NOTE 5)
5KV CABLE STRAIN RELIEF MOUNTING BRACKET
MOSER GLASER DURASEC, TYPE DTOIA(S)
ABB RND2
QUALITROL SERIES 042
QUALITROL 900
MILWAUKEE VALVE
MILWAUKEE VALVE
MILWAUKEE VALVE
MILWAUKEE VALVE
MILWAUKEE VALVE
MILWAUKEE VALVE
QUALITROL
F20SS, CLASS 150
F20SS, CLASS 150
F20SS, CLASS 150
F20SS, CLASS 150
F20SS, CLASS 150
F20SS, CLASS 150
XPRD
29 1 2 MILWAUKEE VALVE F20SS, CLASS 1501-INCH OIL SAMPLING VALVE
RAPID PRESSURE RISE RELAY
SERVERON TM1
1.5-INCH GAS-IN-OIL MONITOR INTERFACE VALVE
1.5-INCH RAPID PRESSURE RISE RELAY INTERFACE VALVE
BUSHING ENCLOSURE AND INTERNAL LAYOUT.
5. SEE SHEET E-105 FOR THE DETAILED REQUIREMENTS OF THE LOW-VOLTAGE
PER-TRANSFORMER BASIS.
4. THE ITEMS LISTED IN THE TABLE OF TRANSFORMER DEVICES ARE ON A
NOT INTENDED TO INDICATE THE ACTUAL QUANTITY.
3. THE RADIATORS AS DEPICTED INDICATE THE PERMISSIBLE LOCATIONS AND IS
HAVE BEEN INDICATED WITH DASHED OUTLINES.
FOR THE PURPOSES OF DRAWING CLARITY, SOME EQUIPMENT LOCATIONS2.
PROPER INTERCONNECTION TO THE SWITCHYARD EQUIPMENT.
FOR THE MANUFACTURER'S USE IN DESIGNING THE TRANSFORMERS FOR
1. THE TRANSFORMER LAYOUT AND LIMITING DIMENSIONS HAVE BEEN PROVIDED
H1
ELEVATION - SEGMENT 4
SCALE: NTS
H8
ELEVATION - SEGMENT 2
SCALE: NTS
A4
ELEVATION - SEGMENT 3
SCALE: NTS
A12
IDENTIFICATION (TOP VIEW)
FIG 1 - TRANSFORMER TANK SEGMENT
GENERAL NOTES:
S
A N
S F
O R
M E
R S
W
IT
C H
Y A
R D
R O
A N
O K
E R
IV
E
R
IS
L
A N
D C
R E
E K
P U
M P
IN
G
P L
A N
T
W
P M
R A
O C
T O
B E
R
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
P O
R T
L A
N D
O
R E
G O
N
H Y
D R
O E
L E
C T
R
IC
D E
S
IG
N C
E N
T E
R
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
A
W
IN
G N
U M
B E
R
F
IL
E N
A M
E
J O
R D
A N
S F
IN
K
P
.E
M O
U N
T
IN
G A
N D
C O
N F
IG
U
R A
T
IO
N
C O
N T
R O
L C
A B
IN
E
T
S T
A T
IO
N
T R
A N
S F
O R
M E
R S
E-103
D
F
IL
E R
S .C
O T
N E
R
P
.0
E -1
.d
F
IL
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
SIDEWALL
TRANSFORMER TANK
(CABINET BACK)
VENTILATOR
ENCLOSURE RAINPROOF
MOUNTS (TYPICAL)
VIBRATION ISOLATION
FRAMEWORK
CABINET MOUNTING
DRIP SHIELD
RAIN AND
GASKET SEAL
DRIP CHANNEL
CABINET DOOR
SOLAR SHIELDING
(SEE DETAIL 'A')
WINDOW SEAL
(INSIDE CABINET DOOR)
COMPUTER TRAY
FOLD-DOWN
(INSIDE CABINET DOOR)
DRAWING POCKET
O&M MANUAL
SEE NOTE 2
LEGEND:
TEMPERED GLASS
RUBBER SEAL
ENCLOSURE PANEL
SECURING STRIP
GROUND WIRE
AND GROUNDING SCREW
WITH A CAPTIVE O-RING GASKET
SHALL BE A MYERS SCRU-TITE
ALL CONDUIT HUB FITTINGS
EQUIPMENT ENCLOSURE
FIBER-OPTIC TEMPERATURE MONITORFTM
LOCKOUT RELAY86T
ANNUNCIATOR30
SHALL HAVE A POCKET SIZED TO HOLD THE O&M MANUAL DRAWINGS.
AND A MEANS FOR LATCHING THE TRAY WHEN STOWED. THE LEFT DOOR
WHICH SECURE THE TRAY IN A HORIZONTAL POSITION WHEN LOWERED,
ON THE INSIDE OF THE DOOR. THE TRAY SHALL INCLUDE FOLDING HINGES
7. THE RIGHT DOOR SHALL HAVE A DROP DOWN LAPTOP TRAY MOUNTED
ISOLATORS.
WHICH IS MOUNTED TO THE TRANSFORMER TANK USING VIBRATION
6. THE CONTROL CABINET SHALL BE MOUNTED TO A FRAME STRUCTURE
APPROXIMATELY 60 INCHES ABOVE THE BASE OF THE TRANSFORMER.
MOUNTED ON THE SWING PANELS SO THAT THE DEVICES ARE
5. THE FIBER-OPTIC TEMPERATURE MONITOR AND ANNUNCIATORS SHALL BE
CONTROL CABINET SHALL ONLY ENTER THROUGH THE BASE.
4. ALL CONDUIT ROUTING FROM THE TRANSFORMER DEVICES TO THE
REMOVABLE PLATE FOR THE PURPOSES OF FIELD FITTING OF CONDUIT.
MAY VARY. THE BASE OF THE CABINET SHALL HAVE A GASKETED
FOR REPRESENTATIVE PURPOSES ONLY. ACTUAL QUANTITIES AND SIZES
3. EXTERNAL CONDUIT CONNECTIONS TO THE PUMPING STATION ARE SHOWN
2. SPACE FOR ARC FLASH LABEL (PROVIDED BY THE GOVERNMENT).
ACCORDANCE WITH UL 508A STANDARD.
IN1. THE TRANSFORMER CONTROL CABINET IS TO BE DESIGNED AND BUILT
CONTROL CABINET
CONDUIT CONNECTIONS
FUTURE EXTERNAL
GENERAL NOTES:
F3
CONTROL CABINET
SCALE: NTS
F10
MOUNTS - SIDE VIEW
DETAIL OF VIBRATION ISOLATION
SCALE: NTS
H16
DOOR SEAL
DETAIL OF TYPICAL CABINET
SCALE: NTS
A2
CONNECTIONS AND GROUNDING
DETAIL OF ENCLOSURE CONDUIT
SCALE: NTS
A9
SEAL - DETAIL A
TYP CLAYTONRITE-TYPE WINDOWS
F
B EC
G
D
B C D E
F
G
5453 55 56
6352 64
59 62
65 67
59 62
59 62
A N
S
A N
S F
O R
M E
R S
W
IT
C H
Y A
R D
R O
A N
O K
E R
IV
E
R
IS
L
A N
D C
R E
E K
P U
M P
IN
G
P L
A N
T
W
P M
R A
O C
T O
B E
R
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
P O
R T
L A
N D
O
R E
G O
N
H Y
D R
O E
L E
C T
R
IC
D E
S
IG
N C
E N
T E
R
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
A
W
IN
G N
U M
B E
R
F
IL
E N
A M
E
J O
R D
A N
S F
IN
K
P
.E
L A
Y O
U T
C O
N T
R O
L C
A B
IN
E
T
S T
A T
IO
N
T R
A N
S F
O R
M E
R S
E-104
D
F
IL
E R
S .C
O T
N E
R
P
.0
E -1
.d
F
IL
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
QUALITROL 408
MOLDED-CASE CIRCUIT BREAKERS
AUXILIARY RELAYS
INTERPOSING RELAY FOR LOCKOUT RELAY GENERAL ELECTRIC
ELECTROSWITCH SERIES 24, MODEL 78PB02E
TERMINAL BLOCKS - CONTROL SIGNAL TYPE
TERMINAL BLOCKS - POWER DISTRIBUTION TYPE
FUSES
FUSE HOLDERS
CABINET HEATER
UNDERVOLTAGE RELAY
RECEPTACLE WITH GROUND FAULT INTERRUPTER HUBBELL GFR8300SGW
MARATHON SERIES 142
TIME MARK
BUSSMAN
BUSSMAN
WAUKESHA PTC2
FAL
C26(XX)
HMA
LPJ
JTN600(XX)
TIME DELAY RELAY AGASTAT SERIES 7000
FIBER-OPTIC TEMPERATURE MONITOR
LOCAL ANNUNCIATOR PANELS (DEVICE 30) SEL 2533
GROUND BUS BAR - -
TRANSFORMER DEVICES - CONTROL CABINET COMPONENTS
HUMIDISTAT / THERMOSTAT (DEVICE 23-1) HAMMOND MFG SKTH012009-C
STATES TYPE NT, CLASS 250
SQUARE D
SQUARE D 8501, TYPE X
LOCKOUT RELAY (DEVICE 86T)
QUALITROL
LEGEND:
LH SIDE PANEL
CABINET LIGHT
(NOTE 3)
OUTLET
RESISTORS
CALIBRATION
ANALOG WTI
DEVICES
RELAYS AND
AUXILIARY
BREAKERS
CIRCUIT
LH BACK PANEL RH BACK PANEL RH SIDE PANEL
HEATER
68 1
AS REQ'D
AS REQ'D
AS REQ'D
AS REQ'D
AS REQ'D
AS REQ'D
AS REQ'D
AS REQ'D
AS REQ'D
ITEM QTY DEVICE DESCRIPTION EXAMPLE BRAND EXAMPLE MODEL NUMBER
HEATER
BLOCKS
TERMINAL
BOTTOM PANEL
DEVICES
ASSOCIATED
FTM
BLOCKS
TERMINAL
BLOCKS
TERMINAL
(FRONT VIEW)
RIGHT SWING PANEL
RAPID PRESSURE RISE SEAL-IN RELAY 909-300-01
WINDING TEMPERATURE INDICATORWTI
FIBER-OPTIC TEMPERATURE MONITORFTM
CONDUIT CONNECTIONS
PLATE FOR EXTERNAL
AND GASKETED BOTTOM
REMOVABLE BOLTED
TRANSFORMER MOUNTED CONDUIT
AREA FOR FACTORY INSTALLATION OF
4. THE REMOVABLE BOTTOM PLATE THICKNESS SHALL BE 10 GAUGE, MINIMUM.
UNOBSTRUCTED.
CABINET, AND ORIENTED SO THAT THE FRONT OF THE OUTLET IS
3. THE GFCI OUTLET SHALL BE ACCESSIBLE ONLY FROM INSIDE THE CONTROL
CONTRACTOR.
PURPOSES ONLY. THE ACTUAL LAYOUT MAY BE MODIFIED BY THE
2. THE CONTROL CABINET LAYOUT AS SHOWN IS FOR ILLUSTRATIVE
ACCORDANCE WITH UL 508A STANDARD.
1. THE TRANSFORMER CONTROL CABINET IS TO BE DESIGNED AND BUILT IN
K3
CONTROL CABINET TOP VIEW
SCALE: NTS
A2
CONTROL CABINET LAYOUT
14" 7" 14"7" 14" (MINIMUM)14" (MINIMUM)
16" (MINIMUM)
MOUNTING BRACKET
STRAIN RELIEF
5KV CABLE
GROUND CONDUCTOR
LOW-VOLTAGE NEUTRAL BUSHING
GROUND CONDUCTOR
LOW-VOLTAGE NEUTRAL BUSHING
(SEE NOTE 4)
ENTRY CONDUIT
FUTURE 5KV CABLE
EXTENDING TO TANK GROUND PAD
GROUND CONDUCTOR CONDUIT
LOW-VOLTAGE BUSHING
(SEE NOTE 5)
ENCLOSURE DOORS
(X1, X2, X3)
LOW-VOLTAGE BUSHINGS
LOW-VOLTAGE NEUTRAL BUSHING (X0)
MOUNTING BRACKET
STRAIN RELIEF
5KV CABLE
J O
R D
A N
S F
IN
K
P
.E
L A
Y O
U T
L O
W -V
O L
T A
G E
B U
S H
IN
G
E N
C L
O S
U R
E
S T
A T
IO
N
T R
A N
S F
O R
M E
R S
E-105
D
F
IL
E R
S .C
O T
N E
R
P
.0
E -1
.d
F
IL
S
A N
S F
O R
M E
R S
W
IT
C H
Y A
R D
R O
A N
O K
E R
IV
E
R
IS
L
A N
D C
R E
E K
P U
M P
IN
G
P L
A N
T
W
P M
R A
O C
T O
B E
R
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
P O
R T
L A
N D
O
R E
G O
N
H Y
D R
O E
L E
C T
R
IC
D E
S
IG
N C
E N
T E
R
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
A
W
IN
G N
U M
B E
R
F
IL
E N
A M
E
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
BOLTING HARDWARE WITH CAPTIVE NUTS.
OPENING IS TO BE FULLY GASKETED, AND THE DOOR SECURED CLOSED USING
WITHOUT SAGGING OR DEFORMATION WHEN OPENED. EACH ENCLOSURE DOOR
HINGES ON ONE SIDE, CAPABLE OF SUPPORTING THE WEIGHT OF THE DOOR
5. EACH ENCLOSURE DOOR IS TO INCLUDE A MINIMUM OF THREE HEAVY-DUTY
THE ENCLOSURE DIRECTLY BELOW THE X2 BUSHING TERMINAL, AS INDICATED.
ROUTING OF 5KV FEEDER CONDUCTORS. THE 5-INCH CONDUIT WILL ENTER
FUTURE CONNECTION OF A 5-INCH RGS CONDUIT TO BE USED FOR THE
4. THE ENCLOSURE BOTTOM ACCESS PLATE IS TO BE DESIGNED TO ALLOW FOR
DIAMETER.
EXCEEDING A CONDUCTOR BEND RADIUS OF 12-TIMES THE OVERALL CONDUCTOR
CLASS IA 5KV FEEDER CONDUCTORS, SIZE 1000 KCMIL SHIELDED, WHILE NOT
OF THE ENCLOSURE IS SIZED TO ALLOW FOR ROUTING OF THREE TYPE MV-90
3. THE DISTANCE BETWEEN THE STRAIN RELIEF MOUNTING BRACKET AND BOTTOM
INSTALLATION OF 5KV CLASS 2 CABLE TERMINATION STRESS CONES.
THE STRAIN RELIEF MOUNTING BRACKET IS SIZED TO ALLOW FOR THE FUTURE
2. THE DISTANCE BETWEEN THE TERMINALS OF THE LOW-VOLTAGE BUSHINGS AND
LOW-VOLTAGE BUSHING ENCLOSURE HAVE BEEN INDICATED WITH BOLD LINES.
1. FOR THE PURPOSE OF DRAWING CLARITY, THE COMPONENTS WITHIN THE
X0 X1 X2 X3
CL
(S E
E N
O T
E
(S
E E
N O
T E
GENERAL NOTES:
D3
LAYOUT - FRONT VIEW
LOW VOLTAGE BUSHING ENCLOSURE
SCALE: 1 -1/2" = 1' - 0"
D11
SIDE VIEW
LOW VOLTAGE BUSHING ENCLOSURE LAYOUT
SCALE: 1 -1/2" = 1' - 0"
S
A N
S F
O R
M E
R S
W
IT
C H
Y A
R D
R O
A N
O K
E R
IV
E
R
IS
L
A N
D C
R E
E K
P U
M P
IN
G
P L
A N
T
W
P M
R A
O C
T O
B E
R
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
P O
R T
L A
N D
O
R E
G O
N
H Y
D R
O E
L E
C T
R
IC
D E
S
IG
N C
E N
T E
R
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
A
W
IN
G N
U M
B E
R
F
IL
E N
A M
E
J O
R D
A N
S F
IN
K
P
.E
L A
Y O
U T
A N
D D
E T
A
IL
S
T R
A N
S F
O R
M E
R M
O U
N T
E D
D E
V
IC
E S
S T
A T
IO
N
T R
A N
S F
O R
M E
R S
E-106
D
F
IL
E R
S .C
O T
N E
R
P
.0
E -1
.d
F
IL
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
(110 C)
SW. #2
(UNUSED)
SW. #1
(125 C)
SW. #3
(LOW LEVEL)
SW. #1
PRESSURE
LOW
PRESSURE
HIGH
(UNUSED)
SW. #2
(< 200 PSI)
EMPTY CYLINDER
BULB
HEATER
WELL
BULB
HEATER
WELL
(BELOW)
DIAGRAM
SEE CT
TOP OIL THERMOWELLS
(DEVICE 49Q2)
WITH NPT PLUG
THERMOWELL
SPARE HEATED
(WITH NPT PLUG)
THERMOWELL
SPARE
(DEVICE 49WTI)
WINDING TEMPERATURE INDICATOR
(DEVICE 26Q)
OIL TEMPERATURE INDICATOR
(DEVICE 94X)
TRANS. TRIP
(49WTI)
HEATER
THERMOWELL
(SPARE)
HEATER
THERMOWELL
WINDINGS ASSEMBLY
TRANSFORMER CORE AND
CT-X2
49R
49Q1
49Q2
(BELOW)
DIAGRAM
SEE CT
H1 H2 H3
X0
X1
X2
X3
(DEVICE 63PRD)
PRESSURE RELIEF DEVICE
(ALARM)
SW. #1
(TRIP)
SW. #2
(DEVICE 71Q)
OIL LEVEL INDIATOR
TS
(DEVICE 63NR)
NITROGEN PRESSURE REGULATOR
(100C)
SW. #1
ALARM B2
TO DEVICE 30-1
ALARM B1
TO DEVICE 30-1
(WITH NPT PLUG)
THERMOWELL
SPARE
(CRITICAL LOW LEVEL)
SW. #2
ALARM D2
TO DEVICE 30-1
ALARM E1
TO DEVICE 30-1
(DEVICE 94X)
TRANS. TRIP
ALARM E2
TO DEVICE 30-1
ALARM A2
TO DEVICE 30-2
ALARM A1
TO DEVICE 30-2
(DEVICE 26Q)
THERMOWELL
ALARM B2
TO DEVICE 30-2
ALARM C1
TO DEVICE 30-2
ALARM C2
TO DEVICE 30-2
ALARM D1
TO DEVICE 30-2
CABLE
CONNECTOR
CABLE
CONNECTOR
ALARM E1
TO DEVICE 30-2
(DEVICE 63RPR-SIR)
SEAL-IN RELAY
RAPID PRESSURE RISE RELAY
LOCATED IN TRANSFORMER CONTROL CABINET
(DEVICE 94X)
TRANS TRIP
ALARM D2
TO DEVICE 30-2
(DEVICE 95Q)
GAS-IN-OIL MONITOR
SW. #0
ALARM
H2 PPM
SW. #1
ALARM
H2 ROC
SW. #2
ALARM
MOISTURE PPM
SW. #PWR
ALARM
LOSS OF POWER
SW. #SVC
ALARM
SERVICE EVENTS
1 1 J3
423 56 7 89 22 4 56 J4
6 7 8 9 102 3 1 6 4 5 8 9 7
(DEVICE 63RPR)
SENSOR
RAPID PRESSURE RISE RELAY
(63X1)
SW. #1
(63X2)
SW. #2
H1 H3
H2
X1
X2
X3
X0
LOW VOLTAGE BUSHINGSX1,2,3
LOW VOLTAGE NEUTRAL BUSHINGX0
TEST SWITCHTS
SWITCHSW
RESISTANCE TEMPERATURE DETECTORRTD
HIGH VOLTAGE BUSHINGSH1,2,3
CURRENT TRANSFORMERCT
COMMUNICATIONSCOMM
BOURDON TUBE TEMPERATURE SENSINGBULB
GAS-IN-OIL MONITOR95Q
TRIP AUXILIARY RELAY94X
OIL LEVEL INDICATOR71Q
SEAL-IN RELAY -SIR
RAPID PRESSURE RISE RELAY63RPR
PRESSURE RELIEF DEVICE63PRD
NITROGEN PRESSURE REGULATOR63NR
ANALOG WINDING TEMPERATURE INDICATOR49WTI
CALIBRATION RESISTOR49R
HEATED THERMOWELLS49Q1,2
ANNUNCIATOR30
THERMOWELL26Q
ANALOG OIL TEMPERATURE INDICATOR26Q
CONNECTION DETAILS.1. SEE DRAWING E-602 FOR FIBER-OPTIC TEMPERATURE MONITOR
(DEVICE 49Q1)
THERMOWELL
HEATED
GENERAL NOTES:
LEGENDS:
A1
THERMOWELLS
CURRENT TRANSFORMER AND HEATED
SEE NOTE 1
S
A N
S F
O R
M E
R S
W
IT
C H
Y A
R D
R O
A N
O K
E R
IV
E
R
IS
L
A N
D C
R E
E K
P U
M P
IN
G
P L
A N
T
W
P M
R A
O C
T O
B E
R
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
P O
R T
L A
N D
O
R E
G O
N
H Y
D R
O E
L E
C T
R
IC
D E
S
IG
N C
E N
T E
R
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
A
W
IN
G N
U M
B E
R
F
IL
E N
A M
E
J O
R D
A N
S F
IN
K
P
C
N T
R O
L S
C H
E M
A T
IC
S
S T
A T
IO
N
T R
A N
S F
O R
M E
R S
E-601
D
F
IL
E R
S .C
O T
N E
R
P
.0
E -6
.d
F
IL
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
20A
GFCI
OUTLET
P D
B
RECEPTACLE
CABINET
CONTROL
52-3
P D
B
LINE
NEUTRAL
V
A C
-P H
A S
E
H Z
G O
V E
R N
M E
N T
S U
P P
L
IE
D C
O N
T R
O L
P O
W E
R
(DEV. 63NR)
POWER
REGULATOR
PRESSURE
NITROGEN
DS-1
H T
R
LT1 LT2
23-1
NC
DS-2
LIGHTS
CABINET
CONTROL
52-1
HEATER
CABINET
CONTROL
52-2
27-1
H T
R
72-1
P D
B
P D
B
PR
86T
NOTE 4)
(SEE
TRIP COIL MONITORING
LOCKOUT RELAY WITH
86T
HR
R
G
86T
86T
G TB4
B
94X
94X
RESET
POWER
125 VDC
TB1
V
D C
G O
V E
R N
M E
N T
F U
R N
IS
H
E D
C O
N T
R O
L P
O W
E R
120C
FTM
REGULATOR
PRESSURE
NITROGEN
52-5
(DEV. FTM)
POWER
TEMP MONITOR
FIBER-OPTIC
TEMP MONITOR
FIBER-OPTIC
52-6
120C
49T2-H 49T2-X
125C
TB8
TB1
86T-T
TRIP (OUTPUT CONTACT TO POWERHOUSE)
WTI
SEE NOTE 2
DEVICE 30-2, ALARM D2
DEVICE 30-1, ALARM A1
DEVICE 30-1, ALARM A2
COM COM
NC
27-1
(DEV. 95Q)
POWER
MONITOR
GAS-IN-OIL
MONITOR
GAS-IN-OIL
52-4
63RPR-SIR
SEAL-IN RELAY
RAPID PRESSURE RISE
(63X1)
ALARM
(63X2)
TRIP
63X1
63X2
94X
ALARM E1
TO DEVICE 30-2
DEVICE 30-2, ALARM E1
TO 63RPR
TERMINAL BLOCK CONNECTIONTB
RED LEDR
POWER DISTRIBUTION BLOCKPDB
CABINET LIGHTLT
CABINET HEATERHTR
HAND-RESET (DEVICE 86T)HR
GROUND FAULT CIRCUIT INTERRUPTERGFCI
GREEN LEDG
FIBER-OPTIC TEMPERATURE MONITORFTM
CABINET DOOR SWITCHDS
GAS-IN-OIL MONITOR95Q
TRIP AUXILIARY RELAY94X
LOCKOUT RELAY TRIP COIL MONITOR86T-T
TRANSFORMER LOCKOUT RELAY86T
DC MOLDED-CASE CIRCUIT BREAKER72-
SEAL-IN RELAY -SIR
RAPID PRESSURE RISE RELAY63RPR
NITROGEN PRESSURE REGULATOR63NR
PRESSURE RELIEF DEVICE63PRD
AC MOLDED-CASE CIRCUIT BREAKER52-
ANALOG WINDING TEMPERATURE INDICATOR49WT1
WINDING HIGH-TEMPERATURE TRIP CONTACT
FIBER-OPTIC TEMPERATURE MONITOR - LOW-VOLTAGE49T2-X
WINDING HIGH-TEMPERATURE TRIP CONTACT
FIBER-OPTIC TEMPERATURE MONITOR - HIGH-VOLTAGE49T2-H
ANNUNCIATOR30
UNDERVOLTAGE RELAY27
INDUSTRIAL GRADE HUMIDISTAT / THERMOSTAT23
SOLENOID EXCEEDS THE RATING OF THESE DEVICE CONTACTS.
AND FTM OUTPUT RELAY CONTACTS, AS THE BURDEN OF THE LOCKOUT RELAY
THE 86T LOCKOUT RELAY WITHOUT OVERLOADING THE 63RPR SEAL-IN RELAY
3. THE PURPOSE OF THE 94X AUXILIARY RELAY IS TO ALLOW FOR TRIPPING OF
TRIP, SET AT A 5C HIGHER TEMPERATURE.
THE FIBER-OPTIC TEMPERATURE MONITOR WINDING OVER-TEMPERATURE
2. THE ANALOG WINDING TEMPERATURE INDICATOR IS USED AS A BACKUP TO
OF THE CABINET PROVIDED.
1. THE ACTUAL QUANTITY OF HEATERS MAY VARY DEPENDING UPON THE SIZE
63RPR-SIR 94X 86T
86T-T
72-2
(DEV. 30-1)
ANN
(DEV. 30-2)
ANN
H2
120 VAC CONTROL SCHEMATIC
SCALE: NTS
A2
125 VDC CONTROL SCHEMATIC
SCALE: NTS
GENERAL NOTE:
LEGEND:
S
A N
S F
O R
M E
R S
W
IT
C H
Y A
R D
R O
A N
O K
E R
IV
E
R
IS
L
A N
D C
R E
E K
P U
M P
IN
G
P L
A N
T
W
P M
R A
O C
T O
B E
R
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
P O
R T
L A
N D
O
R E
G O
N
H Y
D R
O E
L E
C T
R
IC
D E
S
IG
N C
E N
T E
R
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
A
W
IN
G N
U M
B E
R
F
IL
E N
A M
E
J O
R D
A N
S F
IN
K
P
.E
F U
N C
T
IO
N A
L R
E Q
U
IR
E M
E N
T S
F
IB
E R
O P
T
IC
T E
M P
E R
A T
U R
E M
O N
IT
O
R
S T
A T
IO
N
T R
A N
S F
O R
M E
R S
E-602
D
F
IL
E R
S .C
O T
N E
R
P
.0
E -6
.d
F
IL
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
1 2 3 4 5 6 7 8
ANALOG OUTPUTS
LOW-VOLTAGE WINDINGX
TRANSMITTx
TERMINAL BLOCKTB
RECEIVERx
HIGH-VOLTAGE WINDINGH
BOTTOMBOT
AUXILIARY TRIPPING RELAY94X
FIBER-OPTIC TEMPERATURE MONITOR SYSTEM FAULT74FTM
AC MOLDED-CASE CIRCUIT BREAKER52
WINDING TEMPERATURE49T
ANNUNCIATOR30
OIL TEMPERATURE26Q1
FIBER-OPTIC DESCRIPTION LABEL
CHANNEL 1
CHANNEL 2
CHANNEL 3
CHANNEL 4
CHANNEL 5
CHANNEL 6
CHANNEL 7
CHANNEL 8
HIGH-VOLTAGE WINDING TEMPERATURE, A-PHASE
HIGH-VOLTAGE WINDING TEMPERATURE, B-PHASE
HIGH-VOLTAGE WINDING TEMPERATURE, C-PHASE
TOP OIL TEMPERATURE, RADIATOR OUTLET
LOW-VOLTAGE WINDING TEMPERATURE, A-PHASE
LOW-VOLTAGE WINDING TEMPERATURE, B-PHASE
LOW-VOLTAGE WINDING TEMPERATURE, C-PHASE
BOTTOM OIL TEMPERATURE, RADIATOR INLET
HV-A WINDING TEMP
HV-B WINDING TEMP
HV-C WINDING TEMP
TOP OIL TEMP
LV-A WINDING TEMP
LV-B WINDING TEMP
LV-C WINDING TEMP
BOTTOM OIL TEMP
1 2 3 4 5 6 7 8
INLET)
(RADIATOR
TOP OIL
1 2 3 4 5 6 7 8
AND JUNCTION BOX
FEED THROUGH WALL PLATE
STAINLESS STEEL FIBER-OPTIC
TRANSFORMER TANK
H1 X1 H2 X2 H3 X3
WINDINGS
PHASE A
WINDINGS
PHASE B
WINDINGS
PHASE C
OUTLET)
(RADIATOR
BOTTOM OIL
SEE NOTE 1
1 2 3 4 5 6 7 8
H1 H2 H3
OIL
TOP X1 X2 X3
OIL
BOTTOM
FIBER-OPTIC INPUTS
SERIAL PORT
ALARM (105C)
HIGH TEMP
H WINDING
RELAY 1
TRIP (120C)
HIGH TEMP
H WINDING
RELAY 2
ALARM (105C)
HIGH TEMP
X WINDING
RELAY 3
TRIP (120C)
HIGH TEMP
X WINDING
RELAY 4
ALARM (95C)
HIGH TEMP
TOP OIL
RELAY 5
SPARE
RELAY 6
OUTPUT RELAYS
SPARE
RELAY 7
SPARE
RELAY 8 RELAY
SYSTEM FAULT
74FTM
ALARM B1
TO DEVICE 30-2
ALARM D1
TO DEVICE 30-1TO DEVICE 94X
ALARM C2
TO DEVICE 30-1TO DEVICE 94X
ALARM C1
TO DEVICE 30-1
(FUTURE USE)
SERIAL PORT
GND
TB4
GND Tx+ Tx- Rx+ Rx-
1 2 3 4 5
49T1-H 49T2-H 49T1-X 49T2-X 26Q1
TB2 1 3 2 4 6 5 7 9 8 10 12 11 13 15 14 16 18 17 19 21 20 22 24 23 1TB5 2
GND GND GND GND
1 2TB3 3
H1 H2 H3 OIL
TOP
X1 X2 X3 OIL
BOT
16151413121110987654
120 VAC
INPUT VOLTAGE
1 2TB1 3
GND
NL
(FUTURE USE)
4-20 mA ANALOG OUTPUT
(SEE SHEET E-907)
TO BREAKER 52-6
FIBER-OPTIC TEMPERATURE MONITOR LABELING
ROUTED THROUGH CONDUIT.
PLATE JUNCTION BOX AND THE CONTROL CABINET SHALL BE
1. ALL FIBER-OPTIC WIRES BETWEEN THE TANK FEED-THROUGH WALL
G7
(DEVICE FTM)
FIBER-OPTIC TEMPERATURE MONITOR
SCALE: NTS
A1
FIBER-OPTEC SENSOR PLACEMENT
POWER TRANSFORMER TANK AND WINDINGS
SCALE: NTS
S
A N
S F
O R
M E
R S
W
IT
C H
Y A
R D
R O
A N
O K
E R
IV
E
R
IS
L
A N
D C
R E
E K
P U
M P
IN
G
P L
A N
T
W
P M
R A
O C
T O
B E
R
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
P O
R T
L A
N D
O
R E
G O
N
H Y
D R
O E
L E
C T
R
IC
D E
S
IG
N C
E N
T E
R
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
A
W
IN
G N
U M
B E
R
F
IL
E N
A M
E
J O
R D
A N
S F
IN
K
P
.E
S H
E E
T
A N
N U
N C
IA
T
O R
F U
N C
T
IO
N A
L R
E Q
U
IR
E M
E N
T S
S T
A T
IO
N
T R
A N
S F
O R
M E
R S
E-603
D
F
IL
E R
S .C
O T
N E
R
P
.0
E -6
.d
F
IL
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
G1
IN
G2
IN
A1
IN
A2
IN
B1
IN
B2
IN
C1
IN
C2
IN
D1
IN
D2
IN
E1
IN
E2
IN
F1
IN
F2
IN
+1
-2
INPUT
IRIG-B
P R
O G
R A
M M
A B
L E
O P
T O
IS
O
L A
T E
D I
N P
U T
S
1 2
FRONT PANEL ALARM LED
A
B
C
D
E
CONTROLS
FRONT PANEL OPERATOR
SIL ACK RESET TEST
OUT 01
OUT 02
ALARM
OUT 03
OUT 04
OUT 05
OUT 06
OUT 07
OUT 15
THROUGH
OUT 12
P R
O G
R A
M M
A B
L E
O U
T P
U T
C O
N T
A C
T S
1 2 3 4 5
EIA-485
PORT 4A
EIA-232
PORT 4C
T
X
T
X
R
X
R
X
S H
L D
OPTIONAL CARD
EIA-485 OR EIA-232
GND
SUPPLY
POWER
+/H
-/N
GROUND
CHASSIS
PORTS
STANDARD EIA-232
EIA-232
EIA-232
IRIG-B
EIA-232
PORT F (FRONT)
PORT 2 (REAR)
PORT 3 (REAR)
72-2
TRANSFORMER LOCKOUT
86T
LOCKOUT COIL TROUBLE
110C
LOCKOUT
TRANSFORMER
TROUBLE
LOCKOUT COIL
TEMP - GAUGE
TOP OIL HIGH
100C
105C
HV WINDING HIGH TEMP - FIBER
26Q1
(SEE SHEET E-604)
TO DEVICE 30-2
(SEE SHEET E-604)
TO DEVICE 30-2
PRESSURE RELIEF DEVICE
LOW OIL LEVEL - CRITICAL
86T-T
TEMP - GAUGE
WINDING HIGH
X WINDING HIGH TEMP - GAUGE
49 WTI
26 OTI
49T1-H
LV WINDING HIGH TEMP - FIBER
49T1-X
105C
TOP OIL HIGH TEMP - GAUGE
TOP OIL HIGH TEMP - FIBER
LOW OIL LEVEL
95C
TEMP - FIBER
HV HIGH
TEMP - FIBER
LV HIGH
TEMP - FIBER
TOP OIL HIGH
LEVEL
LOW OIL
LEVEL - CRITICAL
LOW OIL
RELIEF DEVICE
PRESSURE
POWER DISTRIBUTION BLOCKPDB
FIBER-OPTIC TEMPERATURE MONITORFTM
LOCKOUT RELAY TRIP COIL MONITOR86T-T
LOCKOUT RELAY (HAND RESET)86T
DC MOLDED-CASE CIRCUIT BREAKER72
OIL LEVEL INDICATOR71Q
PRESSURE RELIEF DEVICE63PR
ANALOG WINDING TEMPERATURE INDICATOR49WTI
WINDING TEMPERATURE (FTM)49T1
ANNUNCIATOR30
OIL TEMPERATURE (FTM)26Q1
ANALOG OIL TEMPERATURE INDICATOR26OTI
71Q-1
71Q-2
63PR-1
OUT 08
OUT 09
OUT 10
OUT 11
(SEE SHEET E-605)
TO CTB2 TERMINAL BLOCK
(SEE SHEET E-601 & E-605)
CONTROL POWER
125 VDC GOVERNMENT FURNISHED
LEGEND:
B3
DEVICE 30-1, 125 VDC ANNUNCIATOR SCHEM
R D
A N
S F
IN
K
P
.E
S H
E E
T
A N
N U
N C
IA
T
O R
F U
N C
T
IO
N A
L R
E Q
U
IR
E M
E N
T S
S T
A T
IO
N
T R
A N
S F
O R
M E
R S
E-604
D
F
IL
E R
S .C
O T
N E
R
P
.0
E -6
.d
F
IL
S
A N
S F
O R
M E
R S
W
IT
C H
Y A
R D
R O
A N
O K
E R
IV
E
R
IS
L
A N
D C
R E
E K
P U
M P
IN
G
P L
A N
T
W
P M
R A
O C
T O
B E
R
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
P O
R T
L A
N D
O
R E
G O
N
H Y
D R
O E
L E
C T
R
IC
D E
S
IG
N C
E N
T E
R
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
A
W
IN
G N
U M
B E
R
F
IL
E N
A M
E
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
G1
IN
G2
IN
A1
IN
A2
IN
B1
IN
B2
IN
C1
IN
C2
IN
D1
IN
D2
IN
E1
IN
E2
IN
F1
IN
F2
IN
+1
-2
INPUT
IRIG-B
P R
O G
R A
M M
A B
L E
O P
T O
IS
O
L A
T E
D I
N P
U T
S
1 2
FRONT PANEL ALARM LED
A
B
C
D
E
CONTROLS
FRONT PANEL OPERATOR
SIL ACK RESET TEST
OUT 01
OUT 02
ALARM
OUT 03
OUT 04
OUT 05
OUT 06
OUT 07
OUT 15
THROUGH
OUT 08
P R
O G
R A
M M
A B
L E
O U
T P
U T
C O
N T
A C
T S
1 2 3 4 5
EIA-485
PORT 4A
EIA-232
PORT 4C
T
X
T
X
R
X
R
X
S H
L D
OPTIONAL CARD
EIA-485 OR EIA-232
GND
SUPPLY
POWER
+/H
-/N
GROUND
CHASSIS
PORTS
STANDARD EIA-232
EIA-232
EIA-232
IRIG-B
EIA-232
PORT F (FRONT)
PORT 2 (REAR)
PORT 3 (REAR)
63NR
(SEE SHEET E-603)
TO DEVICE 30-1
(SEE SHEET E-603)
TO DEVICE 30-1
NITROGEN LOW PRESSURE
NITROGEN EMPTY CYLINDER
63NR
3 2
LOW PRESSURE
NITROGEN
EMPTY CYLINDER
NITROGEN
FTM TROUBLE
74FTM
TROUBLE
TEMP MONITOR
27-1
OUT 08
OUT 09
OUT 10
OUT 11
(SEE SHEET E-605)
TO CTB3 TERMINAL BLOCK
95Q-SW0
J3-3
95Q-SW1
J3-6
GAS MONITOR - H2 ROC
GAS MONITOR - H2 PPM
GAS MONITOR - MOISTURE PPM
GAS MONITOR - SERVICE
GAS MONITOR - LOSS OF POWER
95Q-SW3
95Q-SVC
95Q-PWR
J3-9
J4-3
J4-6
H2 PPM
GAS MONITOR
H2 ROC
GAS MONITOR
MOISTURE PPM
GAS MONITOR
SERVICE EVENT
GAS MONITOR
LOSS OF POWER
GAS MONITOR
RAPID PRESSURE RISE RELAY
RISE RELAY
RAPID PRESSURE
CONTROL POWER
LOSS OF
63RPR-SIR
POWER DISTRIBUTION BLOCKPDB
FIBER-OPTIC TEMPERATURE MONITORFTM
TRANSFORMER GAS-IN-OIL MONITOR95Q
FIBER-OPTIC TEMPERATURE MONITOR STATUS ALARM74FTM
SEAL-IN RELAY -SIR
RAPID PRESSURE RISE RELAY63RPR
NITROGEN PRESSURE REGULATOR SYSTEM63NR
ANNUNCIATOR30
COOLING CONTROL UNDERVOLTAGE RELAY27-1
LOSS OF AC CONTROL POWER
B4
SCHEMATIC
DEVICE 30-2, 125 VDC ANNUNCIATOR
J O
R D
A N
S F
IN
K
P
.E
E X
T E
R N
A L
C O
N N
E C
T
IO
N S
C O
N T
R O
L C
A B
IN
E
T
S T
A T
IO
N
T R
A N
S F
O R
M E
R S
E-605
D
F
IL
E R
S .C
O T
N E
R
P
.0
E -6
.d
F
IL
S
A N
S F
O R
M E
R S
W
IT
C H
Y A
R D
R O
A N
O K
E R
IV
E
R
IS
L
A N
D C
R E
E K
P U
M P
IN
G
P L
A N
T
W
P M
R A
O C
T O
B E
R
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
P O
R T
L A
N D
O
R E
G O
N
H Y
D R
O E
L E
C T
R
IC
D E
S
IG
N C
E N
T E
R
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
A
W
IN
G N
U M
B E
R
F
IL
E N
A M
E
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
TERMINAL BLOCKS - CONTROL SIGNAL TYPE
TERMINAL BLOCKS - POWER DISTRIBUTION TYPE MARATHON SERIES 142
STATES TYPE NT, CLASS 250
TRANS LOCKOUTTRANS LOCKOUT TRIP
(L)
LOCKOUT COIL TROUBLE
TOP OIL HIGH TEMPERATURE - GAUGE
LOW OIL LEVEL - CRITICAL
PRESSURE RELIEF DEVICE
X WINDING HIGH TEMPERATURE - GAUGE
HV WINDING HIGH TEMPERATURE - FIBER
LV WINDING HIGH TEMPERATURE - FIBER
TOP OIL HIGH TEMPERATURE - FIBER
LOW OIL LEVEL
NITROGEN LOW PRESSURE
NITROGEN EMPTY CYLINDER
FTM TROUBLE
GAS MONITOR - H2 ROC
GAS MONITOR - H2 PPM
POWER
120 VAC
PDB1
(N)
POWER
DC CONTROL
PDB2
CONTROL
CTB1
ANNUNCIATION
CTB2
(SEE SHEET E-603)
DEVICE 30-1
TO ANNUNCIATOR
ANNUNCIATION
CTB3
(SEE SHEET E-604)
DEVICE 30-2
TO ANNUNCIATOR
CONTRACT AWARD DURING THE SHOP DRAWING SUBMITTAL REVIEW PROCESS.
4. ANNUNCIATION WIRE NUMBERS TO THE POWER PLANT WILL BE PROVIDED AFTER
DESIGNATIONS, AS INDICATED.
OF EXTERNAL CIRCUITS SHALL CORRESPOND TO THE GOVERNMENT'S
PRACTICE; HOWEVER, WIRE AND CABLE DESIGNATIONS FOR IDENTIFICATION
WIRING DIAGRAMS MAY BE ACCORDING TO THE CONTRACTOR'S STANDARD
3. THE WIRE (TERMINAL POINT) DESIGNATIONS USED ON THE CONTRACTOR'S
TERMINATED ON THE LEFT SIDE OF THE TERMINAL BLOCKS.
2. ALL WIRING FOR EXTERNAL CONNECTIONS TO THE PUMPING STATION SHALL BE
MODIFIED BY THE CONTRACTOR.
1. THE LAYOUT SHOWN IS FOR ILLUSTRATIVE PURPOSES ONLY, AND MAY BETERMINAL BLOCKS FOR EXTERNAL CONNECTIONS TO PUMPING STATION
TRANSFORMER DEVICES
ITEM QTY DEVICE DESCRIPTION EXAMPLE BRAND EXAMPLE MODEL NUMBER
AS REQ'D
AS REQ'D
GAS MONITOR - MOISTURE PPM
GAS MONITOR - SERVICE
GAS MONITOR - LOSS OF POWER
RAPID PRESSURE RISE RELAY
POWER DISTRIBUTION BLOCKPDB
CONTROL TERMINAL BLOCKCTB
ANNUNCIATOR30
SEE SHEET E-601
125 VDC CONTROL POWER
SEE SHEET E-601
120 VAC CONTROL POWER
LOSS OF AC CONTROL POWER
ANN DEVICE 30-1 TROUBLE ANN DEVICE 30-2 TROUBLE
CONNECTIONS
FUTURE EXTERNAL
CONNECTIONS
FUTURE EXTERNAL
CONNECTIONS
FUTURE EXTERNAL
CONNECTIONS
FUTURE EXTERNAL
CONNECTIONS
FUTURE EXTERNAL
D3
FOR EXTERNAL CONNECTIONS
TERMINAL BLOCKS
CONTROL CABINET
SCALE: NTS
UNIT 1
BUILDING
PAINT STORAGE
RAILS
TRANSFERWAY
TRANSFORMER
20"-0 3/8" HIGH
15'-0" WIDE X
ROLL-UP DOOR
PART OF RAIL SPUR
ARE NO LONGER
POWERHOUSE
RAILS INTO
CART
TRANSFER
RAILS FOR
HATCH
SEE DETAIL "A"
HATCH
10'-0"
20'-6"
24'-10"
16'-4"
2'-3"
CART
TRANSFER
RAILS FOR
DOOR
FOLDING
EL 243.0
ROOM
OPERATOR'S
TO
TRANSFERWAY
TO TRANSFORMER
FOLDING DOOR
AND WOOD BERMS
INSTALL OIL CONTAINMENT
FOR BOTH TRANSFORMERS.
TEMPORARY STORAGE LOCATION
J O
R D
A N
S F
IN
K
P
.E
S H
E E
T
O
P T
IO
N
A L
T E
M P
O R
A R
Y S
T O
R A
G E
R E
Q U
IR
E
M E
N T
S
S T
A T
IO
N
T R
A N
S F
O R
M E
R S
E-801
D .F
IL
E
R /C
.P O
B A
N Z
S .C
O T
N E
R
P
.0
E -8
.d
.F
IL
E
R /C
.P O
B A
Z
S
A N
F O
R M
E R
S U
P P
L Y
P O
W E
R H
O U
S E
R O
A N
O K
E R
IV
E
R
IS
L
A N
D C
R E
E K
P U
M P
IN
G
P L
A N
T
W
P M
R A
O C
T O
B E
R
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
P O
R T
L A
N D
O
R E
G O
N
H Y
D R
O E
L E
C T
R
IC
D E
S
IG
N C
E N
T E
R
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
A
W
IN
G N
U M
B E
R
F
IL
E N
A M
E
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
EL 240.0
A
A
D2
STORAGE AT JOHN H. KERR POWERHOUSE
LOCATION FOR TEMPORARY TRANSFORMER
SCALE: 1/16" = 1'-0"
H12
DETAIL "A"
SCALE: 1/4" = 1'-0"
A11
VIEW A-A FOLDING DOOR ELEVATION
SCALE: 1/4" = 1'-0"
GROUND PAD
TRANSFORMER TANK
COORDINATED WITH THE C.O.R.
CONDUCTORS SHALL BE
CONNECTION OF THE GROUNDING
RAISE CABLE OVER BERM)
WITH STRUT HARDWARE TO
(EATON B-LINE DB SERIES
CABLE SUPPORT
BERM WITH GROUND MAT
ONE-PIECE OIL CONTAINMENT
(SEE NOTE 2)
(QTY. 2 PER TRANSFORMER)
12" x 4' x 20' HARDWOOD TIMBER MATS
(SEE NOTE 2)
(QTY. 2 PER TRANSFORMER)
12" x 4' x 20' HARDWOOD TIMBER MATS
BERM WITH GROUND MAT
ONE-PIECE OIL CONTAINMENT
J O
R D
A N
S F
IN
K
P
.E
S H
E E
T
O
P T
IO
N
A L
T E
M P
O R
A R
Y S
T O
R A
G E
R E
Q U
IR
E
M E
N T
S
S T
A T
IO
N
T R
A N
S F
O R
M E
R S
E-802
D
F
IL
E R
S .C
O T
N E
R
P
.0
E -8
.d
F
IL
S
A N
S F
O R
M E
R S
W
IT
C H
Y A
R D
R O
A N
O K
E R
IV
E
R
IS
L
A N
D C
R E
E K
P U
M P
IN
G
P L
A N
T
W
P M
R A
O C
T O
B E
R
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
P O
R T
L A
N D
O
R E
G O
N
H Y
D R
O E
L E
C T
R
IC
D E
S
IG
N C
E N
T E
R
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
A
W
IN
G N
U M
B E
R
F
IL
E N
A M
E
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
RING TERMINAL COMPRESSION FITTINGS.
GROUNDING PAD, USING #8 AWG GROUNDING CONDUCTORS AND
THE X0 NEUTRAL BUSHING, WHICH IS GROUNDED TO THE TANK
TRANSFORMERS DURING SHIPMENT ARE TO BE GROUNDED TO
3. ALL LOW-VOLTAGE BUSHINGS REMAINING INSTALLED ON THE
DRAWING E-801, AND AS INDICATED BY THE COR.
HARDWOOD TIMBER MATS IN THE LOCATION AS SHOWN ON
STORAGE IN THEIR SHIPPING CONFIGURATION, AND PLACED ON
2. THE TRANSFORMERS ARE TO BE PLACED INTO TEMPORARY
REQUIREMENTS OF SPECIFICATIONS SECTION 48 20 01.04 26.
STORAGE, ALL STORAGE CONDITIONS MUST MEET THE
FOR PLACEMENT OF THE TRANSFORMERS INTO TEMPORARY
1. IF THE GOVERNMENT EXERCISES THE OPTIONAL BID ITEM
X0
X0
X1
X2
X3
J4
PLAN VIEW
TRANSFORMER TEMPORARY STORAGE CONNECTION
SCALE: NTS
A5
ELEVATION VIEW (SEGMENT 1 SIDE)
TRANSFORMER TEMPORARY STORAGE CONNECTION
GENERAL NOTES
R D
A N
S F
IN
K
P
IT
E W
O R
K F
L O
W C
H A
R T
S T
A T
IO
N
T R
A N
S F
O R
M E
R S
E-803
D
F
IL
E R
S .C
O T
N E
R
P
.0
E -8
.d
F
IL
S
A N
S F
O R
M E
R S
W
IT
C H
Y A
R D
R O
A N
O K
E R
IV
E
R
IS
L
A N
D C
R E
E K
P U
M P
IN
G
P L
A N
T
W
P M
R A
O C
T O
B E
R
M
IN
G T
O N
N
O R
T H
C A
R O
L
IN
A
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
P O
R T
L A
N D
O
R E
G O
N
H Y
D R
O E
L E
C T
R
IC
D E
S
IG
N C
E N
T E
R
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
A
W
IN
G N
U M
B E
R
F
IL
E N
A M
E
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
A
B
C
D
E
F
G
H
J
K
L
M
N
P
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
IS
S
U E
D A
T E
S I Z
E
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
SHEET ID
®of Engineers
US Army Corps
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
DELIVERY
TRANSFORMERS'
BERMS
AND CONTAINMENT
PROVIDE CRIBBING
STORAGE LOCATION
AT TEMPORARY
OFF-LOAD TRANSFORMERS
CRATES
ACCESSORY
OFF-LOAD
CLEANING
TRANSFORMER
PERFORM
PERFORM TESTS
SYSTEM AND
ESTABLISH NITROGEN
FOUNDATION PADS
AT NEW SWITCHYARD
OFF-LOAD TRANSFORMERS
YES
NO
READY?
FOUNDATION PADS
ARE THE
READY?
FOUNDATION PADS
ARE THE YES
NO
HEATERS AND GROUNDS
CONNECTIONS FOR
PROVIDE WIRING AND
HEATERS AND GROUNDS
CONNECTIONS TO
REMOVE WIRING AND
CRIBBING
BERM AND
REMOVE CONTAINMENT
SWITCHYARD
FOR MOVEMENT TO NEW
LOAD ACCESSORY CRATES
ISLAND CREEK PUMP STATION
NEW SWITCHYARD AT
ACCESSORY CRATES TO
MOVE TRANSFORMERS AND
SWITCHYARD
MOVEMENT TO NEW
HEAVY HAUL TRUCKS FOR
LOAD TRANSFORMERS ON
SWITCHYARD
CRATES AT NEW
OFF-LOAD ACCESSORY
TOUCH-UP PAINTING.
TRANSFORMER CLEANING AND
PARTIAL OIL-FILLING, FIELD TESTING,
PERFORM TRANSFORMER REASSEMBLY,
SERVICES
COMMISSIONING
PERFORM
PAD IS READY
YEAR OR UNTIL FOUNDATION
TEMPORARY STORAGE FOR ONE
KEEP TRANSFORMERS IN
(SEE SHEET E-802)
(SEE SHEET E-801)
AT JH KERR POWERHOUSE
TO STORAGE LOCATION
AND ACCESSORY CRATES
DELIVER TRANSFORMERS
INSPECTIONS
SITE DELIVERY
PERFORM TRANSFORMER
INSPECTIONS
SITE DELIVERY
PERFORM TRANSFORMER
ISLAND CREEK PUMP STATION
TO NEW SWITCHYARD AT
AND ACCESSORY CRATES
DELIVER TRANSFORMERS
(SEE SHEET S-101)
A1
(OPTIONAL CLIN 0009)
SECTION 48 20 01.04 26
TRANSFORMER TEMPORARY STORAGE
SCALE: NTS
N2
(CLIN 0003)
ASSSEMBLY, SECTION 48 20 00.04 26
TRANSFORMER SHIPMENT, HAULING AND SITE
| 001-Untitled |
| 002-Untitled |
| 003-Untitled |
| 004-Untitled |
| 005-Untitled |
| 006-Untitled |
| 007-Untitled |
| 008-Untitled |
| 009-Untitled |
| 010-Untitled |
| 011-Untitled |
| 012-Untitled |
| 013-Untitled |
| 014-Untitled |
| 015-Untitled |
| 016-Untitled |
| 017-Untitled |
| 018-Untitled |
| 2025-11-06T14:53:21-0800 | |
| CASPER.TERESA.1513254853 |
| 2025-11-06T15:12:41-0800 | |
| DIBLASI.VINCENT.JOHN.1236867877 |
| 2025-11-07T08:38:29-0800 | |
| DEMEAUX.SHARON.E.1231649014 |
File details come from the government source that posted it. Updated .