3rd SFG (A) Battalion Operations Facility PN80733 Fort Bragg, NC
Section 27 40 00
SECTION 27 40 00
AUDIO VIDEO SYSTEM
PART 1 – GENERAL
1.1 REFERENCES
The publications listed below form a part of this s pecification to the extent referenced. The publications are referred to within the text by the basic designation only.
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2011; TIA 11-1; Errata 2011; TIA 11-2; TIA 11-3; TIA 11-4)
National Electrical Code
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
ANSI C80.3 (2005) American National Standard for El ectrical Metallic Tubing
(EMT)
TELCOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)
TIA-569 (2012c; Addendum 1 2013; Errata 2013) Comme rcial Building Standard for Telecommunications Pathways a nd Spaces
SPECIFICATONS
01 91 00.00 37 Commissioning
01 78 23 OPERATION AND MAINTENANCE DATA
01 33 00 SUBMITTAL PROCEDURES
27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYST EM
1.2 SYSTEM DESCRIPTION
The Audio Video (AV) system shall utilize the lates t equipment and capabilities. The AV equipment shall be permanently installed on ceilings, walls, within cabinets, lecterns and other furnitur e in each room. The use of mobile carts is NOT allowed. Identical AV equipment shall be used to provide a common platform between rooms.
Provide all associated infrastructure, cabling, con trollers, hardware, software, components, connectors and adapters to pr ovide a complete and fully functional AV system in each room as indicated on t he drawings and described in this specification.
The contractor is responsible to coordinate Governm ent Furnished Government Installed (GFGI) equipment to ensure that all the f unctional requirements of the AV system described in the drawings and specifi cations are met. Equipment and devices not specifically addressed in these doc uments may be required to compensate for features and functions not provided by GFGI equipment. Provide all additional services and equipment to provide a complete and functional system as illustrated in the drawings and described in the specification. The drawings are diagrammatic in nature and field verif ication of exact locations of AV devices shall be made. The contractor shall i ntegrate the lighting controls to the AV system in rooms as indicated wit h preset scenes (lights dim, screen drops, projector powers on, etc.).
The AV systems includes, but is not limited to, the following systems; sound reinforcement, microphones, video displays (project ors, projection screens and flat panel displays/televisions), video annotat ion, lighting control, hard drive recording, touch panel & button panel co ntrol systems, Video Teleconferencing (VTC), and millwork AV furniture t o house AV equipment.
1.2.1 AV INFRASTRUCTURE
All equipment, software applications, and systems s hall be approved by Fort Bragg IT leadership prior to purchase, programming and installation. All AV cabling shall be installed in accordance with TIA-5 68-C.0, TIA-568-C.1, TIA- 568-C.2, TIA/EIA-569-B and TIA/EIA-606 standards an d Division 26 Specification. Any conduit installed as part of thi s specification will follow UL 797 guidelines for installation.
1.3 MINIMAL REQUIRMENTS
Specifications are minimal requirements. If the pro vided system requires enhanced specifications that exceed those specified herein in order to satisfy the specified design, configuration, capabi lity, and performance requirements, then a system with the enhanced speci fications shall be provided at no additional cost to the government.
1.4 CURRENT STATE OF THE ART TECHNOLOGY
The AV system application design and products shall utilize current state of the art technology to provide the enhanced capabili ty and performance specified herein.
1.5 CONTINUOUS DUTY DESIGN
All equipment shall be designed for 24 hour per day , 365 days per year of continuous duty cycle.
1.6 DETAIL DRAWINGS
Submit detail drawings consisting of a complete lis t of equipment and material, including manufacturer's descriptive and technical literature, performance charts and curves, catalog cuts, and in stallation instructions.
Note that the contract drawings show layouts based on typical equipment.
Check the layout based on actual speakers to be ins talled and make the necessary revisions in the detail drawings. Detail drawings shall also contain complete point to point wiring, schematic d iagrams, and other details required to demonstrate that the system has been co ordinated and will properly function as a unit. Drawings shall show pr oposed layout of equipment and apparatuses, and equipment relationship to othe r parts of the work including clearances for maintenance and operation. Contractor
1.7 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for inf ormation only. When used, a designation following the "G" designation identif ies the office that will review the submittal for the government. The follow ing shall be submitted in accordance with Section 01 33 00 SUBMITTAL PROCEDUR ES:
SD-01 Preconstruction Submittals
Qualifications;
AV system contractor, Installer, and Manufacturer q ualifications. Proposed system information.
SD-02 Shop Drawings
Detail Drawings;
As-Built Drawings;
SD-03 Product Data
Material and Equipment;
The manufacturer's product data and specifications, and other information in sufficient detail, and scope to verify that each pr oduct item is in compliance with requirements of the contract docume nts. Include a description of the system operating characteristics and individ ual product data sheets for each item of equipment indicating descriptive a nd technical data, operating temperature limits, heat dissipated, elec trical requirements, dimensions and mounting restrictions. If a product data sheet covers several types or sizes of the product, the sheet shall be m arked to indicate the specific item provided. A letter from the manufactu rer, stating that Fort Bragg will be notified whenever system upgrades and enhancements are available, shall accompany the submittal. Listing o f all hardware, software, cables, and materials products arranged in the orde r of the specification, and model for each item, and a reference to the man ufacturer's product data sheet for the item.
Warranty;
Maintenance Services;
SD-06 Test Reports Acceptance Test Plan;
Acceptance Test Procedure;
Test procedures for the acceptance test. The test p rocedures shall explain in detail, step by step actions and expected results t o demonstrate compliance with the requirements specified. The procedure shal l also explain methods for simulating the necessary conditions of operation to demonstrate system performance.
Acceptance Test Report;
Test reports in booklet form showing all field test s performed to adjust each component and to prove compliance with the specifie d performance criteria, upon completion of testing of the installed system. The reports shall include the manufacturer's model number, and serial number of test equipment used in each test. Each report shall indicate the final pos ition of controls and operating mode of the system.
SD-07 Certificates
Certificates of Compliance;
Copies of current approvals or listings issued be U L, or other nationally recognized testing laboratory for all components.
SD-08 Manufacturer's Instructions
Installation;
SD-10 Operation and Maintenance Data
Operating and Maintenance Manuals;
O&M data in accordance with section 01 78 23 OPERAT ION AND MAINTENANCE DATA, Data Package 5. O&M Manuals available from the manu facturer on a CD shall be submitted in addition to the hard copy manuals. Sub mit addenda to the O&M Manuals from the manufacturer that describe any [ar t of the system application design that is either not covered by, o r deviates from, the O&M Manuals from the manufacturer.
Training Plan;
Description of the training program and materials t o be provided.
Identification and qualification of training instru ctors. Instructional schedules for all classes. The contractor shall sub mit training materials used as part of the specified training programs inc luding all training media, such as video recordings, CDs, and DVDs, that are a vailable from the manufacturer.
1.8 DELIVERY, STORAGE, AND HANDLING
Equipment placed in storage until installation shal l be stored with protection from the weather, humidity and temperatu re variations, dirt and dust, and other contaminants.
1.9 EXTRA MATERIALS
Submit spare part data for each different item of m aterial and equipment specified, after approval of the detail drawings an d not later than 2 months prior to the date of beneficial occupancy. The data shall include a complete list of parts and supplies, with current unit price s and source of supply.
PART 2 – PRODUCTS
2.1 STANDARD PRODUCTS
Provide materials and equipment which are the stand ard products of a manufacturer regularly engaged in the manufacture o f such products, and that essentially duplicate material and equipment that h ave been in satisfactory use at least 2 years. All components used in the sy stem shall be commercial designs that comply with the requirements specified . Submit copies of current approvals or listings issued by UL, or other nation ally recognized testing laboratory for all components. Equipment shall be s upported by a service organization that is within 250 miles of the site.
2.1.1 IDENTICAL ITEMS
Items of the same classification shall be identical . This requirement includes equipment, modules, assemblies, parts and components.
2.2 SYSTEM FUNCTIONAL REQUIREMENTS
The specifications are minimum requirements. If the provided system requires enhanced specifications that exceed those specified herein in order to satisfy the specified design, configuration, capabi lity and performance requirement, then a system with the enhanced specif ications will be provided.
Substitutions, modifications, or improvements to a system hardware, software are permissible provided that such substitution, mo dification, or improvement will not reduce or degrade the performance or produ ct requirement, nor violate regulatory requirements. No such substituti ons, modifications, or improvements will be made without the written conse nt of the manufacturer and contracting officer. Such consent will not be unrea sonably withheld or delayed.
2.3 SYSTEM MODEL REVISIONS
The system and all product components will be the m anufacturer's latest model, design, version, and quality in production a t time of delivery and installation. Any product hardware or software that becomes available after delivery and installation, and up to the time of sy stem acceptance, will be brought to the attention of the contracting officer upon announcement by the manufacturer, and will be made available to Fort Br agg. If such enhancements customarily are provided at no additional cost, the Government will automatically be entitled to such enhancements. If such enhancements customarily are provided at additional cost, the co ntracting officer has the option to accept or reject such enhancements. Submi t a letter to the contracting officer from the manufacturer guarantee ing that the manufacturer will inform the government of, and make available t o the government, all commercially available enhancements to the system h ardware or software at the then current price. Include the letter with the pro duct data submittal.
2.4 SYSTEM COMPONENTS AND PRODUCTS
2.4.1 90” LED FLAT PANEL DISPLAY – SHARP LC-90LE657 U, OR EQUIVALENT
90” diagonal high definition (1920 X 1080) flat pan el display with edge LED backlight. The flat panel shall include HDMI inputs for video, 15W internal speakers, bi-directional RS-232 and Ethernet for co ntrol system connectivity, 120Hz refresh rate, 600 cd/m2 brightness, and 5,000 :1 contrast ratio. Energy Star rated. Provide a tilting wall mount in the app ropriate load capacity based on size of the display.
2.4.2 60” LED FLAT PANEL DISPLAY – SHARP LC-60LE661 U, OR EQUIVALENT
65” diagonal high definition (1920 X 1080) flat pan el display with direct LED backlight. The flat panel shall include HDMI inputs for video, 10W internal speakers, bi-directional RS-232 for control system connectivity, 60Hz refresh rate, 600 cd/m2 brightness, and 4,000:1 contrast ra tio. Energy Star rated.
Provide a tilting or articulating wall mount in the appropriate load capacity based on size of the display and its intended usage .
2.4.3 70” LED FLAT PANEL DISPLAY – SHARP LC-70LE661 U, OR EQUIVALENT
70” diagonal high definition (1920 X 1080) flat pan el display with direct LED backlight. The flat panel shall include HDMI inputs for video, 15W internal speakers, bi-directional RS-232 and Ethernet for co ntrol system connectivity, 240Hz refresh rate, 550 cd/m2 brightness, and 5,000 :1 contrast ratio. Energy Star rated. Provide a tilting wall mount in the app ropriate load capacity based on size of the display.
2.4.7 SWITCHER – EXTRON DXP 84 HD 4K, OR EQUIVALENT
The presentation switcher shall be a 4 input, HDCP compliant device to support analog and digital sources. The switcher in cludes a scaler, analog to digital conversion, HDMI output, and HDMI audio emb edding. Video inputs include (8) HDMI. One stereo balanced or unbalanced input on captive screw connection and one unbalanced stereo input on 3.5mm connector. On-board EDID management and HDCP encryption technology to ensure consistent compliance, fast switching, and reliable communication between devices.
2.4.8 PRESENTATION MATRIX SWITCHER – EXTRON DTP CRO SSPOINT 108 4K, OR
EQUIVALENT
The presentation matrix switcher shall be a 10 inpu t by 8 output HDCP compliant device with scaling for HDMI and analog s ources. The switcher accepts high resolution signals up to 4K on all inp uts. The switcher includes scaling, analog to digital conversion, twisted pair I/O distribution, and on-board audio DSP. Video inputs include (6) HDMI and (4) twisted pair inputs.
The switcher provides (4) HDMI and (4) independentl y scaled outputs on twisted pair connectors. On-board EDID management a nd HDCP encryption technology to ensure consistent compliance, fast sw itching, and reliable communication between devices. Twisted pair inputs support analog and digital sources from remote transmitters. Twisted pair outp uts require a digital receiver at the display. Twisted pair I/O supports distances up to 100 Meters. The switcher shall include an Ethernet netw ork jack for control system connectivity.
2.4.9 VIDEO TELECONFERNCING (VTC) UNIT – CISCO SX80 , OR EQUIVALENT
The video teleconferencing (VTC) Unit, or codec, sh all be compatible with 1920x1080 resolution, with dual monitor outputs, 5 video inputs (3 HDMI, 1 DVI-I, and 1 CV/S-video), and 3 video outputs (2 HD MI & 1 DVI-I). 8 mic inputs with 48 volt phantom power and AEC, 4 balanc ed line level inputs, and support for embedded audio on HDMI input. The codec shall be installed in an equipment rack. High Definition pan/tilt/zoom camer a shall be mounted on the wall at designated location(s). Control of the syst em shall be by the room’s control system. Provide custom touch panel design a nd programming to initialize and control conferences, control camera pan/tilt/zoom movement, and preset recall. Provide (1) codec for each NIPR, SIPR, & JWIC network as required by the room.
2.4.10 PAN TILT ZOOM (PTZ) HIGH DEFINITION CAMERA – CISCO PRECISION 12X, OR
EQUIVALENT
The PTZ high definition camera shall accept full co mmand set for integration with room control system and CODEC1 (VTC) system. C amera shall feature 1/3-inch CMOS image sensor, 12X optical zoom, 1920 x 10 80p resolution, 43.5 degree vertical field of view and 72 degree horizon tal field of view. Camera control and presets shall be accessible via the con trol system. Provide wall mount or recessed wall box as shown on drawings.
2.4.11 DIGITAL PTZ CAMERA EXTENSION TRANSMITTER – V ADDIO 999-9550-000, OR
EQUIVALENT
The transmitter camera module shall provide long di stance extension of digital HD camera video, RS-232 or HDMI camera cont rol, and camera power via a single CAT5e or CAT6 cable for distances up to 30 0ft. The transmitter also support VISCA control loop and wired & modulated IR signals. HDMI input connector for camera video. Power supplied by head end unit.
2.4.12 DIGITAL PTZ CAMERA EXTENSION RECEIVER – VADD IO 999-9550-000, OR
EQUIVALENT
The receiver head end module shall provide long dis tance extension of digital HD camera video, RS-232 or HDMI camera control, and camera power via a single CAT5e or CAT6 cable for distances up to 300ft. The receiver also support VISCA control loop and wired & modulated IR signals . HDMI output connector for camera video input into CODEC1. The head end un it supplies power to the camera unit CAMTX1.
2.4.13 TWISTED PAIR TRANSMITTER – EXTRON 60-1329-12 , OR EQUIVALENT
Two input Decora ®-style transmitter for distribution of HDMI or anal og video, audio, and control up to 230ft over a shielded CAT5 e or CAT6 cable. The transmitter provides one HDMI input and one VGA inp ut, both with independent analog stereo audio connections. Support for video signals at resolutions up to 1920x1200, including 1080p/60 and 2K is required . The transmitter features analog stereo audio embedding, HDCP-compliance, EDI D Minder ®, auto-switching between inputs, remote power capability, and bidire ctional RS-232 and unidirectional IR pass-through for remote AV device control.
2.4.14 TWISTED PAIR RECEIVER – EXTRON 60-1271-13, O R EQUIVALENT
The digital twisted pair receiver works with AVTX1 to send HDMI, audio, and bidirectional RS-232 and IR signals up to 230 feet over a shielded CAT5e or CAT6 cable. It supports video signals at resolution s up to 4K. The receiver is HDCP-compliant, and supports EDID and HDCP trans mission. An HDMI video output is provided. A balanced or unbalanced stereo audio output is provided via captive screw connector.
2.4.15 ENTERPRISE IPTV SET TOP BOX – V-BRICK 8000-0 188, OR EQUIVALENT
Multi-format video decoder for display of campus IP TV distribution. The set top box shall be located at designated display devi ces. The appliance decodes H.264, Windows Media, MPEG2, and MPEG 4 part 2 form ats. The appliance provides digital and analog video outputs and a ste reo audio output.
2.4.16 TOUCH PANEL – CRESTRON TSW-752, OR EQUIVALEN T
Provide custom touch panel design and programming t o control all audio visual functionality including: video projector power, CA TV tuner channel up/down, projection screen up/down (where applicable), video source selection, video and audio conferencing and dialing, volume up/down, system power distribution on/off, PTZ camera control and preset recalls, room separation and combining (where applicable). When rooms are combined, video is to be displayed on all projection screens to facilitate shorter viewing di stances for audience. A fire alarm connection shall be monitored in all mee ting and conference spaces and when triggered by the fire alarm, will result i n powering off all AV displays and muting all AV sound reinforcement syst ems.
Touch panels shall be TFT active color matrix LCD w ith a 7” diagonal screen, and 800 X 480 resolution. Panel shall feature 300 c d/m2 brightness, 350:1 contrast ratio, edge-lit LED illumination, and (5) projected capacitive touch pushbuttons. Available finishes are black and white . Provide appropriate lectern, table, or wall mounting accessory as requi red.
2.4.17 CONTROL SYSTEM PROCESSOR – CRESTRON CP3, OR EQUIVALENT
Centralized control of AV functionality in each spa ce shall be provided by an integrated control system processor. The processor shall feature standards based 10/100 Ethernet for secure high speed network connectivity. The onboard web server shall provide the foundation for advance d system programming offering secure IP based remote control. The proces sor shall support various control protocol connectivity and feature an on-boa rd processor for custom programming for operation with remote color touch p anels, button panels, and switches as required. Control ports include relay, bi-directional RS-232, versiport, IR, proprietary control system manufactu rer protocol, and LAN.
2.4.18 ROOM USE STATUS PANEL – CRESTRON TSW-730, OR EQUIVALENT
A wall mounted 7” LCD color display will be wall mo unted outside most rooms.
These panels will display the occupancy, security s tatus, and availability of the room. Side mount color LED status indicators (R ed and Green) designate room availability. Panels are compatible with Micro soft Exchange and other scheduling applications. The front panel displays a scrolling calendar view of the upcoming schedule and allows local schedulin g. Touch panels shall be TFT active color matrix LCD with a 7” diagonal scre en, and 800 X 480 resolution. Panel shall feature 300 cd/m2 brightnes s, 350:1 contrast ratio, edge-lit LED illumination, and (5) projected capaci tive touch pushbuttons for menu navigation. Available finishes are black and w hite. Provide appropriate wall mounting accessory as required.
2.4.19 DIGITAL AUDIO SIGNAL PROCESSOR 1 – EXTRON 60 -1179-01, OR EQUIVALENT
The DSP provides extensive audio processing includi ng but not limited to:
routing and mixing, room optimization, equalization , filtering, dynamics, and delay as well as control, monitoring and diagnostic tools. The DSP should include 48 volt phantom power, a minimum of six bal anced or unbalanced mic/line inputs, and a minimum of four balanced or unbalanced line level outputs. All features configured through device spe cific system design software.
2.4.20 NETWORK ETHERNET SWITCH – NETGEAR GS516TP, O R EQUIVALENT
16 port fast Ethernet unmanaged network switch. The switch features 16 auto sensing 10/100 RJ-45 ports, and PoE on 8 ports AND 2 SFP Gigabit fiber ports.
2.4.21 SINGLE CHANNEL POWER AMPLIFIER 1 – EXTRON 60 -580-01, OR EQUIVALENT
Single channel power amplifiers shall drive 70 volt load as appropriate for system. Amplifier shall be ENERY STAR rated, utiliz e Class D design, Amplifier shall be capable of withstanding 10 dB in put overload, output overload, and output short or open circuit in any c ombination indefinitely without causing component damage. Front and rear pa nel LED indicator of protection circuit. All inputs via 5-pole captive s crew connector. All outputs via 2-pole captive screw connector. Output power shall be 200 Watt or as shown on the drawings, 20-20,000 Hz at 0.1 perce nt THD+N.
2.4.22 DUAL CHANNEL POWER AMPLIFIER 2 – EXTRON 60-1 245-01, OR EQUIVALENT
Dual channel power amplifiers shall drive (2) 70 vo lt loads as appropriate for system. Amplifier shall be ENERY STAR rated, ut ilize Class D design, Amplifier shall be capable of withstanding 10 dB in put overload, output overload, and output short or open circuit in any c ombination indefinitely without causing component damage. Front and rear pa nel LED indicator of protection circuit. All inputs via 5-pole captive s crew connector. All outputs via 2-pole captive screw connector. Output power shall be 200 Watts per channel or as shown on the drawings, 20-20,000 Hz at 0.1 percent THD+N, all channels operating.
2.4.23 GOOSENECK MICROPHONE – SHURE MX412/C, OR EQU IVALENT
Miniature electret condenser microphones shall be p rovided for video conferencing and speech reinforcement, and shall be mounted on lecterns.
Single element, cardioid directional patterns for h igh sensitivity applications. 12” flexible, fully adjustable goosen eck. 50 Hz to 17 KHz frequency response, 180 Ohms output impedance, and 22 to 52 Vdc phantom power. Shock mount with vibration isolation.
2.4.24 TABLETOP MICROPHONE –SHURE MX396/C-TRI, OR E QUIVALENT
Condenser microphone shall be provided for video co nferencing and speech reinforcement, and shall be placed on the conferenc e. Single element cardioid directional patterns for high sensitivity applicati ons. The mic features immunity from RF interference, optimization for voi ce recognition, and high output for distance micing. 60 – 10 KHz frequency r esponse, 150 Ohms output impedance, and 18 – 52 Vdc phantom power. The mic i s supplied with 48” of adjustable cable.
2.4.25 OVERHEAD MOUNTED (CEILING) LOUDSPEAKER – TAN NOY CVS6, OR EQUIVALENT
Two-way, high power, high sensitivity loudspeaker w ith separate or coaxially mounted 6” woofer and ¾” tweeter drivers. The louds peaker will have an attached multi-tap 70 volt line matching transforme r, back box, and white grille. The grille will be at least 20 percent open . Supply with hardware suitable for recessed ceiling mounting. Minimum per formance requirement:
Frequency response: 79-21,000 Hz -100 dB. Nominal i mpedance: 6 ohms. Axial sensitivity: 91dB, 60W power handling
2.4.26 RACK MOUNT POWER DISTRIBUTION – PWR1
EIA compliant 19” Rackmount power strip with a 15 a mp power capacity, differential and common mode surge and spike protec tion and EMI filtering.
Rack mount power strip shall have enhanced surge pr otection with no surge diversion to ground. Rack mount power strip shall o perate on 120 volt AC/60Hz current. Rackmount power strip shall include 9' 4/3 power cord with NEMA 5- 15P plug, 8 rear outlets, 1 front outlet, and 15 am p circuit breaker located on the power strip’s rear. Rackmount power strip sh all occupy one rack space and be constructed of 18-gauge phosphate pre-treate d steel with a black powder finish
2.4.27 PORTABLE EQUIPMENT RACK – MIDDLE ATLANTIC RF R-2824BR, OR EQUIVALENT
EIA compliant 19” mobile furniture equipment rack. Useable height shall be 24 rack spaces. The rack shall come equipped with one pair of adjustable steel rack rails with tapped 10-32 mounting holes in univ ersal EIA spacing, black e-coat finish and numbered rack spaces. The rack sh all have bolt through 4” height casters, shall be constructed of melamine an d have a Black Cascade finish. A locking and latching IR friendly tempered glass front door and locking and latching melamine rear door shall be in cluded.
2.4.28 CREDENZA – MIDDLE ATLANTIC IC5-FF31-3, OR EQ UIVALENT
Credenzas shall be EIA Compliant 19” A/V Credenza R acks. Credenza Rack shall be 3 bay configurations. Overall dimensions shall b e shown on drawings.
Usable height shall be 14 rack spaces per bay. Rack frames shall ship fully assembled and be constructed of steel. Total weight capacity of the frame only shall be 800 lbs. Each rack bay shall come equ ipped with 2 pairs of 11-gauge steel rack rail tapped with 10-32 mounting ho les in universal EIA spacing, black e-coat finish and numbered rack spac es. Credenza rack shall have one 50 CFM thermostatically controlled proport ional speed blower per bay. Exhaust air shall exit the front of the creden za for unrestricted air flow. Thermostatically controlled fans shall be pow ered on at 87°F and turn off at 85°F. Credenza rack shall require vent panel and have venting on the top and bottom of the face of the rack. Credenza ra ck shall include two adjustable side mounted horizontal lacing bars for enhanced cable management.
Credenza rack shall have a steel rear access panel. Credenza rack shall be finished in a durable black powder coat. Top, sides , and front doors shall ship separately from rack frame. Top shall be const ructed of 1-1/8” OR 1” thick triple refined MDF or Particle Board, sides s hall be constructed of ¾” OR 1” thick triple refined MDF or particle board, f ront doors shall be constructed of 3/4” thick triple refined MDF. Front doors shall be solid or plexi. Top, sides, and front doors shall match the architectural finishes in each space. Credenza rack shall include 4 fine floo r casters.
2.4.29 SPEAKER CABLE
Cables will be of the gauge required depending upon the cable run length. In no case will cable be used which is smaller than 18 AWG. Insulation on the cable will be a plenum rated jacket.
2.4.30 CATEGORY CABLE
All video distribution requires a minimum shielded CAT5E cable. AV control and AV networking cable requires a minimum CAT5E ca ble. All category cable will be plenum rated.
2.4.31 MICROPHONE / AUDIO LINE LEVEL / CONTROL CABL E
All audio distribution requires 1 22 AWG shielded t wisted pair with a drain wire. Cable shall be plenum rated.
2.4.32 POWER LINE SURGE PROTECTION
Major components of the system such as power amplif iers, mixer-preamplifiers, and tuners, will have a device, whether internal or external, which provides protection against voltage spikes and current surge s originating from commercial power sources. Fuses will not be used fo r surge protection. The surge protector shall be rated for a maximum let th ru voltage of 350 volts AC (line to neutral) and 350 volt AC (neutral to groun d). Surge protection device will be UL listed and labeled as having been tested in accordance with
UL 1449.
PART 3 - EXECUTION
3.1 EXAMINATION
After becoming familiar with the details of the wor k and working conditions, verify dimensions in the field, and advise the cont racting officer of any discrepancies before performing the work.
3.2 INSTALLATION
Equipment shall be installed and specified, and in accordance with the manufacturer's recommendations except where otherwi se indicated.
3.2.1 EQUIPMENT RACKS
Racks shall be mounted to the wall. Items of the sa me function shall be grouped together, either vertically or side by side . Controls shall be symmetrically arranged. Audio and video input and i nterconnections shall be made with approved shielded cable and plug connecto rs; output connections may be screw terminal type. All connections to power su pplies shall utilize standard male plug and female receptacle connectors with the female receptacle being the source side of the connection. Inputs, outputs, interconnections, test points, and relays shall be accessible at the rear of the equipment rack for maintenance and testing. Eac h item shall be removable from the rack without disturbing other items or pan els so that the entire front of the rack is occupied by panels.
3.2.2 WIRING
Install wiring in electric metallic tubing as speci fied in section 26 20 00 INTERIOR DISTRIBUTION SYSTEM. Wiring for microphone , grounding, line level, speaker, and power cables shall be isolated from ea ch other by physical isolation and metallic shielding. Shielding shall b e terminated at only one end.
3.3 GROUNDING
All grounding practices shall comply with NFPA 70. Equipment shall be grounded to the serving panel board ground bus thro ugh a green grounding conductor. Metallic conduits serving the equipment shall be isolated on the equipment end with a isolating bushing to prevent n oise from being transferred to the circuit. Equipment racks shall b e grounded to the panel board ground bus utilizing a #8 conductor. Groundin g conductor shall be terminated to the rack using connector suitable for that purpose.
3.4 TRAINING
Conduct a training course for the operating and mai ntenance staff as designated by the contracting officer. The training course will be given at the installation during normal working hours for a total of 16 hours and shall start after the system is functionally comple te but prior to final acceptance tests. The field instructions shall cove r all of the items contained in the approved operating and maintenance manuals, as well as demonstrations of routine maintenance operations. N otify the contracting officer at least 14 days prior to the start of the training course.
3.5 ACCEPTANCE TESTS
3.5.1 GENERAL REQUIREMENTS
After installation has been completed, the Contract or shall conduct acceptance tests, utilizing the approved test proce dures, to demonstrate that equipment operates in accordance with specification requirements. The acceptance tests shall include originating and rece iving messages at specified stations, at proper volumes levels, witho ut cross talk or noise from other links or non-designated units. Each syst em operating mode shall be demonstrated to perform as required by operation of each individual system component under normal and simulated normal system conditions.
3.5.2 TESTING PROCEDURES
Measure system acoustical performance using a sound level meter set for "slow" meter damping except as otherwise noted, and flat response with random incidence at height of 4 to 5 feet. All interior fi nishes and furnishings shall be in place, and system gain shall be adjuste d to provide levels or 70 to 80 dB and at least 10 dB above background noise at the measuring location for these tests, except as otherwise noted. Include the following tests and adjustments.
3.5.3 FREQUENCY RESPONSE
a. Measure loudspeaker frequency response with all con trol equalization set for flat response, using 1/3 octave bands of pi nk noise centered on ANSI preferred frequencies, or broadband calibrated pink noise measured in 1/3 octave bands using a calibrated real time an alyzer.
b. Adjust equalization to provide average system respo nse within +-6 dB of a response (0 dB) which is flat from 100-2500 Hz an d slopes uniformly from 0 dB at 2500 Hz to -5 dB at 10,000 Hz.
3.5.4 UNIFORMATY OF COVERAGE
a. Use 4000 Hz octave band of random noise as test sig nal output to loudspeakers.
b. Lateral Uniformity: +-8 dB at all positions equidis tant from front of room.
c. Front to back Uniformity: Decreasing linearly withi n +-2 dB from 0 dB at front of room to -8 dB at rear as measured on th e room center line.
d. The audio system shall be capable of full spectrum audio coverage throughout the student seating area with no greater variance than +-3 dB infrequency response from 250 Hz to 16,000 Hz. S PL level measurements shall vary no more than 6 dB throughou t the student seating area when walk test using a pink noise gene rator.
e. Refer to NFPA for current CIS measurement technique s and standards related to testing. NFPA standards and requirements for systems are not applicable to this project. The NFPA documentation is intended as standard reference for performing the CIS test as i t relates to providing a performance metric for the audio system . This audio system is not to be considered a part of any mass notifica tion system.
f. Based on the throw distance, loudspeaker frequency response, power handling capability and coverage patterns, the syst em will be sufficient for the specified performance metrics. T he final construction of the room may cause acoustic anomali es prohibiting the system from meeting the CIS score of .7 due to high er than expected reverberation times post build. If the room constru ction is proven to cause the CIS specification to be exceeded, the per formance metrics may be modified to provide the best possible solution f or the owner.
However, should the CIS specification be deemed to be below .5, the contractor shall examine other speaker systems whic h offer pattern control to 250 Hz to increase the CIS value and cou nteract high reverberation times and room anomalies.
-- End of Section --
TR
X M
C J
M S
N
IP
R S
S
IP
R
X X X
X X X
S
SIPR
S
NIPR
TSP
AV
M
X X X
M
AUDIO VISUAL SYMBOLS
VIDEO MONITOR CONNECTED TO
PRESENTATION SYSTEM
J-BOX FOR FUTURE VIDEO TELECONFERENCING
CAMERA, CONDUIT AND BACKBOX ONLY, NO CABLING
NIPR COMMUNICATIONS OUTLET
SIPR COMMUNICATIONS OUTLET
OVERHEAD SPEAKER
CEILING HANGING MICROPHONE
TOUCH PANEL CONTROL
VIDEO TELECONFERENCING SYSTEM
TELECOMUNICATIONS RACK
AUDIO VISUAL INPUTS AND CONTROLLER
SIPR
NIPR
AV
TSP
VTC
ROOM STATUS MONITORRSM
AUDIO VISUAL NOTES
1. ALL TELECOMMUNICATIONS OUTLETS ARE
SHOWN FOR COORDINATION PURPOSES ONLY.
REFER TO TELECOM PLANS FOR OUTLET
REQUIREMENTS.
2. PROGRAMMING ON TOUCHSCREEN CONTROL
DEVICES SHALL BE COORDINATED WITH THE
GOVERNMENT.
TABLE TOP AV CONNECTIVITY BOX. REFER TO AV DETAILSCB
VEST.
E101
VAULT
E108
VAULT
F108
SECURE STORAGE
E109
MAINTENANCE
READINESS
E104
ASC READINESS
F106
ASC READINESS
F106
UNIT STORAGE
F109
SECURE STORAGE
F107
NBC STOR
F110
COMM EQUIP
STORAGE
F111
OUTSIDE STORAGE
F116
OUTSIDE STORAGE
F117
SUSTAINMENT &
DISTRIBUTION
READINESS
D106
VEST.
F101
CORRIDOR
F103
SNIPER CLASSROOM
F102
COMMITTEE ROOM
F115
VEST.
F114
COMMITTEE ROOM
F113
STORAGE
F112
ELEC CLOSET
F106A
EXTERIOR COVERED
WALKWAY
G159
AV702
J
AV710
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
D
A R
L
IN
G T
O N
A V
E N
U E
W
IL
M
IN
G T
O N
N
C
C H
E C
K E
D B
Y
US Army Corps of Engineers ®
D
C
B
A
C A
T E
G O
R Y
C O
D E
A N
S I D
E
F
G
2 3 4 5 6 7 8 9 10
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
F O
R O
F F
IC
IA
L U
S E
O N
L Y
F
O U
O
CORRECTED FINAL
C:\Users\taggese\Documents\FY16PN80773BOF_CTE_R15_taggese.rvt
5/18/2016 4:56:19 PM
/1
/2 s o l
-3
W H
N -1
-D
-0
P H
IE
B
IN
G
S T
A G
G E
A p p ro v e r
AV114
F
IR
S T
F L O
O R
A U
D
IO
V
IS
U A
L P
L A
N
P A
R T
D
E X
P F
E D
E R
A L I N
C
N
M
IC
H
IG
A
N A
V E
S
U
IT
E
C H
IC
A
G O
I L
C O
D E
R
C
H I-
-A
F O
R T
B R
A G
G N
O R
T H
C A
R O
L
IN
A R
D S
F G
A
B
A T
T A
L
IO
N O
P E
R A
T
IO
N S
F A
C
IL
IT
Y
P N
C h e c k e r
KEY PLAN
PART A PART B PART C PART D
PART E
GENERAL NOTES
LEGEND
TRUE NORTHPLAN NORTH
164 8268
SCALE: 1/8"=1'-0"
KEYNOTE LEGEND
Key Value Keynote Text
01 AUDIO VISUAL INPUTS AND CONTROLLER AT
INSTRUCTOR PODIUM. REFER TO DETAIL 1/AV501.
01 FLOOR AV - PART D1
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E
M
C J
M S
N
IP
R S
S
IP
R
UP
TSP
M
M
V T
C
X
X
X
X
X
X
X
X
X
X
X
X
TSP
TSP
X X
XX
RSM
RSM
VTC M
J
VTC
CBCB
CBCB
CBCB
CBCB
CB
CB
CB
CB
M
M
X
X
TR
M
TR
TR
AUDIO VISUAL SYMBOLS
VIDEO MONITOR CONNECTED TO
PRESENTATION SYSTEM
J-BOX FOR FUTURE VIDEO TELECONFERENCING
CAMERA, CONDUIT AND BACKBOX ONLY, NO CABLING
NIPR COMMUNICATIONS OUTLET
SIPR COMMUNICATIONS OUTLET
OVERHEAD SPEAKER
CEILING HANGING MICROPHONE
TOUCH PANEL CONTROL
VIDEO TELECONFERENCING SYSTEM
TELECOMUNICATIONS RACK
AUDIO VISUAL INPUTS AND CONTROLLER
SIPR
NIPR
AV
TSP
VTC
ROOM STATUS MONITORRSM
AUDIO VISUAL NOTES
1. ALL TELECOMMUNICATIONS OUTLETS ARE
SHOWN FOR COORDINATION PURPOSES ONLY.
REFER TO TELECOM PLANS FOR OUTLET
REQUIREMENTS.
2. PROGRAMMING ON TOUCHSCREEN CONTROL
DEVICES SHALL BE COORDINATED WITH THE
GOVERNMENT.
TABLE TOP AV CONNECTIVITY BOX. REFER TO AV DETAILSCB
STORAGE
G121
SPO WARRANT
G120
SPO OFFICER
G119
SPO OPEN OFFICE
G118
SGM
G113
CONFERENCE
G114
STORAGE
G115 MEN'S
G123
WOMEN'S
G122
S-4 OFFICER
G127
SHOWERS
G125
SHOWERS
G124
S-4 OPEN OFFICE
G129
OFFICE
G135
ESS ROOM
G136
CENTRAL FILES
G134
MAIN NIPR
G132MAIN SIPR
G131
STORAGE
G133
DISTRIBUTION
G137
COMSEC FACILITY
G141
BREAK RM
G143
ELEV EQUIP
G142
CORRIDOR
G112
S-6 OPEN OFFICE
G140
STORAGE
G138
S-6 OFFICER
G139
ELEC
G144
STAIR
G145
VESTIBULE
G101
LOBBY
G102
SDO
G103
S-3 PLANS & OPS
G111
SGM
G109
CLOSET
G108
S-3 OFFICER
G107
S-3 STORAGE
G106
CENTRAL FILES
G105
S-3 CONFERENCE
G104
JANITOR
G126
CONFERENCE
G128
S-2 OFFICER
G110
J
J
J J
J
AV702
1 04
AV702
J
AV702
AV710
AV710
AV710
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
D
A R
L
IN
G T
O N
A V
E N
U E
W
IL
M
IN
G T
O N
N
C
C H
E C
K E
D B
Y
US Army Corps of Engineers ®
D
C
B
A
C A
T E
G O
R Y
C O
D E
A N
S I D
E
F
G
2 3 4 5 6 7 8 9 10
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
F O
R O
F F
IC
IA
L U
S E
O N
L Y
F
O U
O
CORRECTED FINAL
C:\Users\taggese\Documents\FY16PN80773BOF_CTE_R15_taggese.rvt
5/18/2016 4:56:20 PM
/1
/2 s o l
-3
W H
N -1
-D
-0
P H
IE
B
IN
G
S T
A G
G E
A p p ro v e r
AV115
F
IR
S T
F L O
O R
A U
D
IO
V
IS
U A
L P
L A
N
P A
R T
E
E X
P F
E D
E R
A L I N
C
N
M
IC
H
IG
A
N A
V E
S
U
IT
E
C H
IC
A
G O
I L
C O
D E
R
C
H I-
-A
F O
R T
B R
A G
G N
O R
T H
C A
R O
L
IN
A R
D S
F G
A
B
A T
T A
L
IO
N O
P E
R A
T
IO
N S
F A
C
IL
IT
Y
P N
C h e c k e r
KEY PLAN
PART A PART B PART C PART D
PART E
GENERAL NOTES
LEGEND
TRUE NORTHPLAN NORTH
164 8268
SCALE: 1/8"=1'-0"
01 FLOOR AV - PART E1
KEYNOTE LEGEND
Key Value Keynote Text
04 AUDIO/VISUAL EQUIPMENT MOUNTED WITHIN
LECTERNS.
M A
R K
D E
S C
R
IP
T
IO
N D
A
M
C J
M S
N
IP
R S
S
IP
R
FD
FD
X
X
X
X
X
X
TSP
M J
V T
C
M
RSM
CB
CBCB
CB
TR
AUDIO VISUAL SYMBOLS
VIDEO MONITOR CONNECTED TO
PRESENTATION SYSTEM
J-BOX FOR FUTURE VIDEO TELECONFERENCING
CAMERA, CONDUIT AND BACKBOX ONLY, NO CABLING
NIPR COMMUNICATIONS OUTLET
SIPR COMMUNICATIONS OUTLET
OVERHEAD SPEAKER
CEILING HANGING MICROPHONE
TOUCH PANEL CONTROL
VIDEO TELECONFERENCING SYSTEM
TELECOMUNICATIONS RACK
AUDIO VISUAL INPUTS AND CONTROLLER
SIPR
NIPR
AV
TSP
VTC
ROOM STATUS MONITORRSM
AUDIO VISUAL NOTES
1. ALL TELECOMMUNICATIONS OUTLETS ARE
SHOWN FOR COORDINATION PURPOSES ONLY.
REFER TO TELECOM PLANS FOR OUTLET
REQUIREMENTS.
2. PROGRAMMING ON TOUCHSCREEN CONTROL
DEVICES SHALL BE COORDINATED WITH THE
GOVERNMENT.
TABLE TOP AV CONNECTIVITY BOX. REFER TO AV DETAILSCB
PLTN OFFICE
A209
STOR.
A210
PLATOON OFFICE
A211
PLTN OFFICE
A212
PLATOON OFFICE
A213
1ST SGT
A214
STORAGE
A215
CO
A216
PLATOON OFFICE
A230
XO
A220
PLTN OFFICE
A221
PLTN OFFICE
A224
PLTN OFFICE
A226
STORAGE
A225
STAIR
A218
TRAINING
A219
STOR
A217
TISC OPEN OFFICE
A208
VEST.
A206
PLATOON OFFICE
A207
STORAGE
A205
PLTN OFFICE
A204
PLATOON OFFICE
A203
CONFERENCE
A202
VEST.
A201
PLTN OFFICE
A228
SIGNAL DETACHMENT
OPEN OFFICE
A229
VEST.
A234 NIPR
A233
SIPR
A232
CENTRAL FILES
A231
J J
AV702
AV710
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
D
A R
L
IN
G T
O N
A V
E N
U E
W
IL
M
IN
G T
O N
N
C
C H
E C
K E
D B
Y
US Army Corps of Engineers ®
D
C
B
A
C A
T E
G O
R Y
C O
D E
A N
S I D
E
F
G
2 3 4 5 6 7 8 9 10
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
F O
R O
F F
IC
IA
L U
S E
O N
L Y
F
O U
O
CORRECTED FINAL
C:\Users\taggese\Documents\FY16PN80773BOF_CTE_R15_taggese.rvt
5/18/2016 4:56:22 PM
/1
/2 s o l
-3
W H
N -1
-D
-0
P H
IE
B
IN
G
S T
A G
G E
A p p ro v e r
AV121
S E
C O
N D
F L O
O R
A U
D
IO
V
IS
U A
L P
L A
N
P A
R T
A
E X
P F
E D
E R
A L I N
C
N
M
IC
H
IG
A
N A
V E
S
U
IT
E
C H
IC
A
G O
I L
C O
D E
R
C
H I-
-A
F O
R T
B R
A G
G N
O R
T H
C A
R O
L
IN
A R
D S
F G
A
B
A T
T A
L
IO
N O
P E
R A
T
IO
N S
F A
C
IL
IT
Y
P N
C h e c k e r
KEY PLAN
PART A PART B PART C PART D
PART E
GENERAL NOTES
LEGEND
TRUE NORTHPLAN NORTH
164 8268
SCALE: 1/8"=1'-0"
02 FLOOR AV - PART A1
KEYNOTE LEGEND
Key Value Keynote Text
04 AUDIO/VISUAL EQUIPMENT MOUNTED WITHIN
LECTERNS.
M A
R K
D E
S C
R
IP
T
IO
N D
A
M
C J
M S
N
IP
R S
S
IP
R
FD
FD
FD
FD
TSP TSP
M M
J
V T
C
J
V T
C
X
X
X
X
X
X
X
X
X
X
X
X
RSM
RSM
M M
CB
CBCB
CB
CB
CBCB
CB
TR TR
AUDIO VISUAL SYMBOLS
VIDEO MONITOR CONNECTED TO
PRESENTATION SYSTEM
J-BOX FOR FUTURE VIDEO TELECONFERENCING
CAMERA, CONDUIT AND BACKBOX ONLY, NO CABLING
NIPR COMMUNICATIONS OUTLET
SIPR COMMUNICATIONS OUTLET
OVERHEAD SPEAKER
CEILING HANGING MICROPHONE
TOUCH PANEL CONTROL
VIDEO TELECONFERENCING SYSTEM
TELECOMUNICATIONS RACK
AUDIO VISUAL INPUTS AND CONTROLLER
SIPR
NIPR
AV
TSP
VTC
ROOM STATUS MONITORRSM
AUDIO VISUAL NOTES
1. ALL TELECOMMUNICATIONS OUTLETS ARE
SHOWN FOR COORDINATION PURPOSES ONLY.
REFER TO TELECOM PLANS FOR OUTLET
REQUIREMENTS.
2. PROGRAMMING ON TOUCHSCREEN CONTROL
DEVICES SHALL BE COORDINATED WITH THE
GOVERNMENT.
TABLE TOP AV CONNECTIVITY BOX. REFER TO AV DETAILSCB
VESTIBULE
G224
CONFERENCE
C214
PLTN OFFICE
C213
PLTN OFFICE
C212
TRAINING
C211
XO
C210
CO
C209
STOR.
C208
1SGT
C207
HHC & CHEMICAL
DETACHMENT OPEN
OFFICE
C202
STAIR
C206
STOR.
C203
CO
B209
XO
B211
PLTN OFFICE
B212
PLTN OFFICE
B213
PLTN OFFICE
B214
VEST.
B215
TRAINING
B207
1SGT
B210
MI OPEN OFFICE
B203
STORAGE
B217
VEST.
B201
STORAGE
B202
STAIR
B206
STOR.
B208
CORRIDOR
G230
CONFERENCE
B216
AV702
J J J J
AV702
AV710
AV710
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
D
A R
L
IN
G T
O N
A V
E N
U E
W
IL
M
IN
G T
O N
N
C
C H
E C
K E
D B
Y
US Army Corps of Engineers ®
D
C
B
A
C A
T E
G O
R Y
C O
D E
A N
S I D
E
F
G
2 3 4 5 6 7 8 9 10
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
F O
R O
F F
IC
IA
L U
S E
O N
L Y
F
O U
O
CORRECTED FINAL
C:\Users\taggese\Documents\FY16PN80773BOF_CTE_R15_taggese.rvt
5/18/2016 4:56:23 PM
/1
/2 s o l
-3
W H
N -1
-D
-0
P H
IE
B
IN
G
S T
A G
G E
A p p ro v e r
AV122
S E
C O
N D
F L O
O R
A U
D
IO
V
IS
U A
L P
L A
N
P A
R T
B
E X
P F
E D
E R
A L I N
C
N
M
IC
H
IG
A
N A
V E
S
U
IT
E
C H
IC
A
G O
I L
C O
D E
R
C
H I-
-A
F O
R T
B R
A G
G N
O R
T H
C A
R O
L
IN
A R
D S
F G
A
B
A T
T A
L
IO
N O
P E
R A
T
IO
N S
F A
C
IL
IT
Y
P N
C h e c k e r
KEY PLAN
PART A PART B PART C PART D
PART E
GENERAL NOTES
LEGEND
TRUE NORTHPLAN NORTH
164 8268
SCALE: 1/8"=1'-0"
02 FLOOR AV - PART B1
KEYNOTE LEGEND
Key Value Keynote Text
01 AUDIO VISUAL INPUTS AND CONTROLLER AT
INSTRUCTOR PODIUM. REFER TO DETAIL 1/AV501.
04 AUDIO/VISUAL EQUIPMENT MOUNTED WITHIN
LECTERNS.
M A
R K
D E
S C
R
IP
T
IO
N D
A
M
C J
M S
N
IP
R S
S
IP
R
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD
FD FD
TSP
M J
VTC
X X
X X
X X
M
R S
M
CB CB
CB CB
TR TR
AUDIO VISUAL SYMBOLS
VIDEO MONITOR CONNECTED TO
PRESENTATION SYSTEM
J-BOX FOR FUTURE VIDEO TELECONFERENCING
CAMERA, CONDUIT AND BACKBOX ONLY, NO CABLING
NIPR COMMUNICATIONS OUTLET
SIPR COMMUNICATIONS OUTLET
OVERHEAD SPEAKER
CEILING HANGING MICROPHONE
TOUCH PANEL CONTROL
VIDEO TELECONFERENCING SYSTEM
TELECOMUNICATIONS RACK
AUDIO VISUAL INPUTS AND CONTROLLER
SIPR
NIPR
AV
TSP
VTC
ROOM STATUS MONITORRSM
AUDIO VISUAL NOTES
1. ALL TELECOMMUNICATIONS OUTLETS ARE
SHOWN FOR COORDINATION PURPOSES ONLY.
REFER TO TELECOM PLANS FOR OUTLET
REQUIREMENTS.
2. PROGRAMMING ON TOUCHSCREEN CONTROL
DEVICES SHALL BE COORDINATED WITH THE
GOVERNMENT.
TABLE TOP AV CONNECTIVITY BOX. REFER TO AV DETAILSCB
VESTIBULE
G231
CORRIDOR
G230
SUSTAINMENT &
DISTRIBUTION OPEN
OFFICE
D217
SIPR
D218
NIPR
D219
VEST.
D220
STORAGE
D221
VEST.
D201
CORRIDOR
D209
STAIR
D208
ELEC
D207
TRAINING
D216
1SGT
D215
STOR.
D214CO
D213
XO
D212
PLTN OFFICE
D211
PLTN OFFICE
D210
PLTN OFFICE
D203
CONFERENCE
D202
CENTRALIZED
MECHANICAL ROOM
G248
SHOWERS
G255
MEN'S
G254
CORRIDOR
G253
RECYCLING
G250
BREAKROOM
G252
WOMEN'S
G249
SHOWERS
G246
ELECTRIC
G247
JANITOR
G251
J
J
AV601
AV710
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
D
A R
L
IN
G T
O N
A V
E N
U E
W
IL
M
IN
G T
O N
N
C
C H
E C
K E
D B
Y
US Army Corps of Engineers ®
D
C
B
A
C A
T E
G O
R Y
C O
D E
A N
S I D
E
F
G
2 3 4 5 6 7 8 9 10
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
F O
R O
F F
IC
IA
L U
S E
O N
L Y
F
O U
O
CORRECTED FINAL
C:\Users\taggese\Documents\FY16PN80773BOF_CTE_R15_taggese.rvt
5/18/2016 4:56:25 PM
/1
/2 s o l
-3
W H
N -1
-D
-0
P H
IE
B
IN
G
S T
A G
G E
A p p ro v e r
AV123
S E
C O
N D
F L O
O R
A U
D
IO
V
IS
U A
L P
L A
N
P A
R T
C
E X
P F
E D
E R
A L I N
C
N
M
IC
H
IG
A
N A
V E
S
U
IT
E
C H
IC
A
G O
I L
C O
D E
R
C
H I-
-A
F O
R T
B R
A G
G N
O R
T H
C A
R O
L
IN
A R
D S
F G
A
B
A T
T A
L
IO
N O
P E
R A
T
IO
N S
F A
C
IL
IT
Y
P N
C h e c k e r
KEY PLAN
PART A PART B PART C PART D
PART E
GENERAL NOTES
LEGEND
TRUE NORTHPLAN NORTH
164 8268
SCALE: 1/8"=1'-0"
02 FLOOR AV - PART C1
KEYNOTE LEGEND
Key Value Keynote Text
04 AUDIO/VISUAL EQUIPMENT MOUNTED WITHIN
LECTERNS.
M A
R K
D E
S C
R
IP
T
IO
N D
A
M
C J
M S
N
IP
R S
S
IP
R
FD
FD
FD
FD
AV TSP
M
M
J
VTC
J
VTC
X X
X X
X X
XX X
XX X
XX X
AV
TSP
AV
TSP
XX X
XX X
XX X
X X
X X
X X
S N
IP
R
S S
IP
R
M
M
R S
M
RSM
CB CB
CB CB
CB CB
CBCB
M M
M M
TR
TR
AUDIO VISUAL SYMBOLS
VIDEO MONITOR CONNECTED TO
PRESENTATION SYSTEM
J-BOX FOR FUTURE VIDEO TELECONFERENCING
CAMERA, CONDUIT AND BACKBOX ONLY, NO CABLING
NIPR COMMUNICATIONS OUTLET
SIPR COMMUNICATIONS OUTLET
OVERHEAD SPEAKER
CEILING HANGING MICROPHONE
TOUCH PANEL CONTROL
VIDEO TELECONFERENCING SYSTEM
TELECOMUNICATIONS RACK
AUDIO VISUAL INPUTS AND CONTROLLER
SIPR
NIPR
AV
TSP
VTC
ROOM STATUS MONITORRSM
AUDIO VISUAL NOTES
1. ALL TELECOMMUNICATIONS OUTLETS ARE
SHOWN FOR COORDINATION PURPOSES ONLY.
REFER TO TELECOM PLANS FOR OUTLET
REQUIREMENTS.
2. PROGRAMMING ON TOUCHSCREEN CONTROL
DEVICES SHALL BE COORDINATED WITH THE
GOVERNMENT.
TABLE TOP AV CONNECTIVITY BOX. REFER TO AV DETAILSCB
TTC COMMITTEE
F202
VEST.
F201
CORRIDOR
F204
AD CLASSROOM
F220
COMMITTEE ROOM
F221
VEST.
F223
STORAGE
F224
CONFERENCE
F222
CORRIDOR
F215
STOR.
F219
STAIR
F216
ASC OPEN OFFICE
F208
TRAINING
F209
XO
F212
CO
F211
1SGT
F210
STORAGE
F205
COMMITTEE
F206
COMMITTEE
F207
CO
E209
1SGT
E208
STOR.
E207
MAINTENANCE OPEN
OFFICE
E206
XO
E210
TRAINING
E211
PLTN OFFICE
E212
STAIR
E205
CONFERENCE
E202
VEST.
E201
PLTN OFFICE
E213
TTC CLASSROOM
F203
J
J
AV702
AV702
J
J
AV702
J
J
AV702
AV710
AV710
AV710
AV710
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
D
A R
L
IN
G T
O N
A V
E N
U E
W
IL
M
IN
G T
O N
N
C
C H
E C
K E
D B
Y
US Army Corps of Engineers ®
D
C
B
A
C A
T E
G O
R Y
C O
D E
A N
S I D
E
F
G
2 3 4 5 6 7 8 9 10
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
F O
R O
F F
IC
IA
L U
S E
O N
L Y
F
O U
O
CORRECTED FINAL
C:\Users\taggese\Documents\FY16PN80773BOF_CTE_R15_taggese.rvt
5/18/2016 4:56:27 PM
/1
/2 s o l
-3
W H
N -1
-D
-0
P H
IE
B
IN
G
S T
A G
G E
A p p ro v e r
AV124
S E
C O
N D
F L O
O R
A U
D
IO
V
IS
U A
L P
L A
N
P A
R T
D
E X
P F
E D
E R
A L I N
C
N
M
IC
H
IG
A
N A
V E
S
U
IT
E
C H
IC
A
G O
I L
C O
D E
R
C
H I-
-A
F O
R T
B R
A G
G N
O R
T H
C A
R O
L
IN
A R
D S
F G
A
B
A T
T A
L
IO
N O
P E
R A
T
IO
N S
F A
C
IL
IT
Y
P N
C h e c k e r
KEY PLAN
PART A PART B PART C PART D
PART E
GENERAL NOTES
LEGEND
TRUE NORTHPLAN NORTH
164 8268
SCALE: 1/8"=1'-0"
02 FLOOR AV - PART D1
KEYNOTE LEGEND
Key Value Keynote Text
01 AUDIO VISUAL INPUTS AND CONTROLLER AT
INSTRUCTOR PODIUM. REFER TO DETAIL 1/AV501.
04 AUDIO/VISUAL EQUIPMENT MOUNTED WITHIN
LECTERNS.
M A
R K
D E
S C
R
IP
T
IO
N D
A
M
C J
M S
N
IP
R S
S
IP
R
DN
FD
FD
FD
FD
TSP
M
TR
MM
S
NIPR
S
NIPR
S
SIPR
S
SIPR
X XX
X XX
X XX
X XX
X XX
X XX
TSP
AV
TSP
AV
S N
IP
R
S S
IP
R
X XX
X XX
M V
T C
R S
M
CB
CB CB
CB
TR
M M
AUDIO VISUAL SYMBOLS
VIDEO MONITOR CONNECTED TO
PRESENTATION SYSTEM
J-BOX FOR FUTURE VIDEO TELECONFERENCING
CAMERA, CONDUIT AND BACKBOX ONLY, NO CABLING
NIPR COMMUNICATIONS OUTLET
SIPR COMMUNICATIONS OUTLET
OVERHEAD SPEAKER
CEILING HANGING MICROPHONE
TOUCH PANEL CONTROL
VIDEO TELECONFERENCING SYSTEM
TELECOMUNICATIONS RACK
AUDIO VISUAL INPUTS AND CONTROLLER
SIPR
NIPR
AV
TSP
VTC
ROOM STATUS MONITORRSM
AUDIO VISUAL NOTES
1. ALL TELECOMMUNICATIONS OUTLETS ARE
SHOWN FOR COORDINATION PURPOSES ONLY.
REFER TO TELECOM PLANS FOR OUTLET
REQUIREMENTS.
2. PROGRAMMING ON TOUCHSCREEN CONTROL
DEVICES SHALL BE COORDINATED WITH THE
GOVERNMENT.
TABLE TOP AV CONNECTIVITY BOX. REFER TO AV DETAILSCB
S-1 OPEN OFFICE
G242
STORAGE
G241
HR SGT
G240
S1-OFFICER
G239
CENTRAL FILES
G238
MEN'S
G236
WOMEN'S
G235
NIPR
G233
SIPR
G234
CLASSROOM 01
G225
CLASSROOM 02
G229
JAG OFFICE
G222
BJA
G221
CHAPLAIN
G220
OPEN OFFICE
G219
LACT.
G218
STOR.
G217BN SURGEON
G216
CONSULT
G215
MEDICAL OPEN
OFFICE
G214
CONFERENCE
G213
BREAK
G211
STOR
G212 TOILET
G210
ADMIN/ RECEPTION
G203
STORAGE
G204
CORRIDOR
G209
XO
G208
REINLISTMENT
G205
CSM
G206
CO
G207
UPPER LOBBY
G201
STAIR
G243
STOR
G202
ELEC
G245
CORRIDOR
G227
FAMILY READINESS
G244
01 01 J J
AV710
AV710
AV703
AV703
J J
AV702
AV703
AV703
AV710
AV710
SHEET ID
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
W
IL
M
IN
G T
O N
D
IS
T R
IC
T
D
A R
L
IN
G T
O N
A V
E N
U E
W
IL
M
IN
G T
O N
N
C
C H
E C
K E
D B
Y
US Army Corps of Engineers ®
D
C
B
A
C A
T E
G O
R Y
C O
D E
A N
S I D
E
F
G
2 3 4 5 6 7 8 9 10
FOR OFFICIAL USE ONLY (FOUO)
FOR OFFICIAL USE ONLY (FOUO)
F O
R O
F F
IC
IA
L U
S E
O N
L Y
F
O U
O
CORRECTED FINAL
C:\Users\taggese\Documents\FY16PN80773BOF_CTE_R15_taggese.rvt
5/18/2016 4:56:28 PM
/1
/2 s o l
-3
W H
N -1
-D
-0
P H
IE
B
IN
G
S T
A G
G E
A p p ro v e r
AV125
S E
C O
N D
F L O
O R
A U
D
IO
V
IS
U A
L P
L A
N
P A
R T
E
E X
P F
E D
E R
A L I N
C
N
M
IC
H
IG
A
N A
V E
S
U
IT
E
C H
IC
A
G O
I L
C O
D E
R
C
H I-
-A
F O
R T
B R
A G
G N
O R
T H
C A
R O
L
IN
A R
D S
F G
A
B
A T
T A
L
IO
N O
P E
R A
T
IO
N S
F A
C
IL
IT
Y
P N
C h e c k e r
KEY PLAN
PART A PART B PART C PART D
PART E
GENERAL NOTES
LEGEND
TRUE NORTHPLAN NORTH
164 8268
SCALE: 1/8"=1'-0"
KEYNOTE LEGEND
Key Value Keynote Text
01 AUDIO VISUAL INPUTS AND CONTROLLER AT
INSTRUCTOR PODIUM. REFER TO DETAIL 1/AV501.
04 AUDIO/VISUAL EQUIPMENT MOUNTED WITHIN
LECTERNS.
02 FLOOR AV -…