100_Percent_643005_Analytics_Lab_AFRL_Edwards_AFB_Combined_Drawings.pdf
PDF 23 MB Posted
- Attached to
- Analytical Lab AFRL B8523 at Edwards Air Force Base. Federal contract opportunity
- Solicitation number
- W912PL19B0009
About this file
W912PL-19-B-0009 Combined Drawings
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| W912PL19B0009_AbstractofOffers_Construction.pdf | ||
| W912PL19B0009_Amendment0003.pdf | ||
| W912PL19B0009_Amendment0002.pdf | ||
| W912PL19B0009_Amendment0001.pdf | ||
| W912PL19B0009_FIO_SiteVisitSign-InSheet.pdf | ||
| 100_Percent_643005_Analytics_Lab_AFRL_Edwards_AFB_Combined_Specifications.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET ID
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R
IN
G C
O M
M A
N D
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A R
C H
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
T A
S K
O R
D E
R N
O
D
C
B
A
D A
T E
File Name:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
E
F
G
H
I
D e s ig n in g B e tt e r
F u tu re s
F O
R C
O N
S T
R U
C T
IO
N
2 3 4 5 6 7 8 9 10 11 12
TASK ORDER # Q201
CONTRACT NO.: FA8903 - 16 - D - 0014
ISSUE DATE: ISSUE DATE
VOLUME: VOLUME 1
H U
T Z
E L
Q
F A
-1
-D
-0
AIR FORCE CIVIL
ENGINEERING
COMMAND
EDWARDS AIR FORCE BASE, CALIFORNIA
RENOVATIONS FOR ANALYTICS LABORATORY
BUILDING 8523
PROJECT # FSPM 16 1479
100% SUBMITTAL
5/12/2019 6:02:53 PM
G-000
C O
V E
R A
N D
I N
D E
X S
H E
E T
E D
W A
R D
S A
F B
C
A L
IF
O R
N
IA
H A
U C
K -K
A L T
I
H A
U C
K -K
A L T
I
S C
H M
IT
Z
M M
-D D
-Y Y
Y Y
05-16-2019 100% SUBMITTAL
643005_Architectural_Central_2018.rvt
F S
P M
A
N A
L Y
T
IC
S L
A B
O R
A T
O R
Y A
F R
L B
U
IL
D
IN
G
P R
O J E
C T
N O
-1
SHEET INDEXSHEET INDEX
GENERAL
G-000 COVER AND INDEX SHEET
G-001 CODE REVIEW AND GENERAL NOTES
G-002 LIFE SAFETY FLOOR PLAN
STRUCTURAL
S-001 GENERAL NOTES
S-002 SPECIAL INSPECTIONS
S-101 FOUNDATION PLAN
S-102 EQUIPMENT PLATFORM FRAMING PLAN
S-103 ROOF FRAMING PLAN
S-501 SECTIONS AND DETAILS
S-502 SECTIONS AND DETAILS
ARCHITECTURE
A-001 SYMBOLS & ABBREVIATIONS
A-002 OVERALL REFERENCE PLAN
AD101 FIRST FLOOR DEMOLITION PLAN
AD501 EXISTING CONDITIONS PHOTOS
A-101 FIRST FLOOR PLAN
A-102 EQUIPMENT PLATFORMS FLOOR PLANS
A-103 ROOF PLAN
A-111 FIRST FLOOR CEILING PLAN
A-112 EQUIPMENT PLATFORMS CEILING PLAN
A-201 BUILDING ELEVATIONS
A-210 INTERIOR ELEVATIONS AND BUILDING SECTIONS
A-401 ENLARGED RESTROOMS PLANS, ELEVATIONS, AND DETAILS
A-501 PARTITION TYPES AND DETAILS
A-601 DOOR SCHEDULE
A-701 STAIR PLANS AND SECTIONS
INTERIORS
I-001 FINISH SCHEDULE, SPECIFICATIONS AND NOTES
I-101 INTERIOR FINISH PLAN
LOCATION MAP: PROJECT SITE
VICINITY MAP: PROJECT LOCATION
120 FIRE PROTECTION
F-001 LEGEND
F-100 FIRST FLOOR EXISTING FIRE PROTECTION PLAN OVERALL
F-101 FIRST FLOOR FIRE PROTECTION PLAN
F-501 DETAILS
F-502 DETAILS
165 FIRE ALARM
FA001 LEGEND, ABBREVIATIONS, AND GENERAL NOTES
FA101 FIRE ALARM FLOOR PLAN
FA102 EQUIPMENT PLATFORM FIRE ALARM PLAN
FA501 DETAILS
FA502 DETAILS
FA503 DETAILS
FA601 RISER DIAGRAM
FA602 FUNCTIONAL MATRIX
130 PLUMBING
P-001 SYMBOLS AND ABBREVIATIONS
P-002 GENERAL NOTES
PD101 FIRST FLOOR DEMOLITION PLAN
P-101 OVERALL UNDERGROUND PIPING PLAN
P-102 UNDERGROUND PIPING PLANS
P-103 FIRST FLOOR PIPING PLAN
P-104 FIRST FLOOR LAB GAS PIPING PLAN
P-105 ROOF PIPING PLAN
P-401 ENLARGED PLANS
P-501 DETAILS
P-502 DETAILS
P-601 SCHEDULES
P-901 ISOMETRICS
P-902 ISOMETRICS
P-903 ISOMETRICS
P-904 ISOMETRICS
110 LAB PLANNING
Q-001 SYMBOLS AND ABBREVIATIONS
Q-002 LEGENDS
Q-401 ENLARGED LABORATORY FLOOR PLANS
Q-402 ENLARGED LABORATORY FLOOR PLANS
Q-403 LABORATORIES INTERIOR ELEVATIONS
Q-501 DETAILS
Q-601 SCHEDULES
MECHANICAL
M-001 SYMBOLS AND ABBREVIATIONS
M-002 GENERAL NOTES
MD101 FIRST FLOOR DEMOLITION HVAC PLANS
MD102 EQUIPMENT PLATFORM AND ROOF DEMOLITION HVAC PLANS
M-101 FIRST FLOOR HVAC PLANS
M-102 FIRST FLOOR HVAC PLAN - AREA A
M-103 FIRST FLOOR HVAC PLAN - AREA B
M-104 EQUIPMENT PLATFORM HVAC FLOOR PLAN
M-105 ROOF HVAC PLAN
M-106 FIRST FLOOR HVAC PIPING PLANS
M-301 SECTIONS
M-401 ENLARGED PLANS
M-501 DETAILS
M-502 DETAILS
M-503 DETAILS
M-601 SCHEDULES
M-602 SCHEDULES
M-603 DIAGRAMS
M-701 CONTROLS
M-702 CONTROLS
M-703 CONTROLS
M-704 CONTROLS
M-705 CONTROLS
M-706 CONTROLS
M-707 CONTROLS
M-708 CONTROLS
M-709 CONTROLS
M-710 CONTROLS
ELECTRICAL
E-001 SYMBOLS AND ABBREVIATIONS
ED101 FIRST FLOOR DEMOLITION PLANS
E-101 FIRST FLOOR LIGHTING PLANS
E-102 EQUIPMENT PLATFORM LIGHTING PLAN
E-200 OVERALL ELECTRICAL EQUIPMENT PLAN
E-201 FIRST FLOOR POWER PLANS
E-202 EQUIPMENT PLATFORM POWER PLAN
E-301 FIRST FLOOR MECHANICAL EQUIPMENT POWER PLANS
E-302 EQUIPMENT PLATFORM AND ROOF MECHANICAL EQUIPMENT POWER
PLANS
E-601 SCHEDULES
E-602 SCHEDULES
E-801 ELECTRICAL SINGLE-LINE DIAGRAM
TELECOMMUNICATION
T-001 GENERAL NOTES, LEGEND AND ABBREVIATIONS
T-101 FIRST FLOOR TELECOMMUNICATION PLAN
T-501 DETAILS
T-502 DETAILS
T-503 DETAILS
T-504 DETAILS
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R
IN
G C
O M
M A
N D
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A R
C H
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
T A
S K
O R
D E
R N
O
D
C
B
A
D A
T E
File Name:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
E
F
G
H
I
D e s ig n in g B e tt e r
F u tu re s
F O
R C
O N
S T
R U
C T
IO
N
2 3 4 5 6 7 8 9 10 11 12
H U
T Z
E L
F A
-1
-D
-0
Q
5/12/2019 2:47:22 PM
G-001
C O
D E
R E
V
IE
W A
N D
G E
N E
R A
L N
O T
E S
E D
W A
R D
S A
F B
C
A L
IF
O R
N
IA
O S
B E
R G
H A
U C
K -K
A L T
I
S C
H M
IT
Z
M M
-D D
-Y Y
Y Y
05-16-2019 100% SUBMITTAL
643005_Architectural_Central_2018.rvt
F S
P M
A
N A
L Y
T
IC
S L
A B
O R
A T
O R
Y A
F R
L B
U
IL
D
IN
G
P R
O J E
C T
N O
-1
LIFE SAFETY LEGEND
EXIT SIGN
1 HR PARTITION
BUILDING EXIT
TRAVEL DISTANCE
TRAVEL DISTANCE 233 FT
T R
A V
E L D
IS
T
A N
C E
F
T
SHEET ID
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R
IN
G C
O M
M A
N D
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A R
C H
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
T A
S K
O R
D E
R N
O
D
C
B
A
D A
T E
File Name:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
E
F
G
H
I
D e s ig n in g B e tt e r
F u tu re s
F O
R C
O N
S T
R U
C T
IO
N
2 3 4 5 6 7 8 9 10 11 12
KEYPLAN
LAB A
H U
T Z
E L
F A
-1
-D
-0
Q
5/12/2019 2:44:50 PM
G-002
L
IF
E S
A F
E T
Y F
L O
O R
P L A
N
E D
W A
R D
S A
F B
C
A L
IF
O R
N
IA
H A
U C
K -K
A L T
I
H A
U C
K -K
A L T
I
S C
H M
IT
Z
M M
-D D
-Y Y
Y Y
05-16-2019 100% SUBMITTAL
643005_Architectural_Central_2018.rvt
F S
P M
A
N A
L Y
T
IC
S L
A B
O R
A T
O R
Y A
F R
L B
U
IL
D
IN
G
P R
O J E
C T
N O
-1
8' 16' 32'
SCALE: 1/16"=1'-0"
1/16" = 1'-0"G-002
01 FIRST FLOOR LIFE SAFETY PLAN N
STRUCTURAL DESIGN DATA
GOVERNING DESIGN SPECIFICATION
UFC 3-301-01 (2015 INTERNATIONAL BUILDING CODE)
RISK CATEGORY
CATEGORY: (IBC 1604.5/ASCE 7-1.5)
MECHANICAL PLATFORM LOADS
LID LIVE LOAD (MECHANICAL EQUIPMENT ROOM):
LID DEAD LOAD:
STEEL DECK + LIGHTWEIGHT CONCRETE:
CEILING & SUPPORT:
MEP ALLOWANCE & COLLATERAL :
TOTAL:
100 PSF
35 PSF
2 PSF
5 PSF
42 PSF
(IBC 1607.12/ASCE 7-4.3.1)
MECHANICAL PLATFORM
SNOW LOAD DESIGN DATA
ROOF SNOW LOAD
A. NOT APPLICABLE AS THE NEW LAB IS AN INTERIOR SPACE SHIELDED FROM SNOW BY
BUILDING 8423
B. STRUCTURE IS NOT DESIGNED TO REMAIN IN PLACE IF SURROUNDING BUILDING IS REMOVED
MECHANICAL PLATFORM/OPEN STRUCTURE
WIND LOAD DESIGN DATA
WIND LOAD:
A. NOT APPLICABLE AS THE NEW LAB IS AN INTERIOR SPACE SHIELDED FROM EXTERNAL
WIND BY BUILDING 8423
B. STRUCTURE IS NOT DESIGNED TO REMAIN IN PLACE IF SURROUNDING BUILDING IS REMOVED
C. INTERIOR WALL AND PARTITION HORIZONTAL LOAD:
MECHANICAL PLATFORM/OPEN STRUCTURE
SEISMIC LOAD DESIGN DATA
EARTHQUAKE DESIGN DATA:
A. SEISMIC IMPORTANCE FACTOR (Ie):
B. SPECTRAL RESPONSE ACCELERATIONS (Ss):
SPECTRAL RESPONSE ACCELERATIONS (S1)
C. SOIL SITE CLASS (PRESUMED):
D. SPECTRAL RESPONSE COEFFICIENT (Sds):
SPECTRAL RESPONSE COEFFICIENT (Sd1):
E. SEISMIC DESIGN CATEGORY:
F. BASIC SEISMIC-FORCE-RESISTING SYSTEMS:
ORDINARY PLAIN MASONRY SHEAR WALLS
G. RESPONSE MOD FACTOR (R) :
H. ANALYSIS PROCEDURE:
I. DESIGN BASE SHEAR:
1.00 1.00g 0.43g
D 0.73g 0.45g
D
1 1/2
ELFP
0.487 x W
(ASCE 7-11.5)
(IBC 1613.3.1/ASCE 7-11.4.1)
(IBC 1613.3.1/ASCE 7-11.4.1)
(IBC 1613.3.2/ASCE 7-11.4.2)
(IBC 1613.3.4/ASCE 7-11.4.4)
(IBC 1613.3.4/ASCE 7-11.4.4)
(IBC 1613.3.5/ASCE 7-11.6)
(ASCE 7-12.2.1)
(ASCE 7-12.2.1)
(ASCE 7-12.8)
(ASCE 7-12.8.1)
II
5 PSF
( + SELF WEIGHT OF
FRAMING MEMBERS)
OPEN STRUCTURE LOADS
LIVE LOAD:
DEAD LOAD:
CEILING & SUPPORT:
MEP ALLOWANCE & COLLATERAL :
TOTAL:
0 PSF
3 PSF
7 PSF
10 PSF
(IBC 1607.12/ASCE 7-4.3.1)
( + SELF WEIGHT OF
FRAMING MEMBERS)
WIND LOAD DESIGN DATA FOR
EXTERIOR BUILDING COMPONENTS
WIND LOADS:
CALCULATED IN ACCORDANCE WITH ASCE 7-10 AND UFC 3-301-01
A. BASIC WIND SPEED:
B. EXPOSURE CATEGORY:
C. ENCLOSURE CLASSIFICATION:
D. INTERNAL PRESSURE COEFFICIENT:
110 MPH
C
ENCLOSED
+/- 0.18
R
L
K
J
X
H
260'-0"
3'-0"
ZONE 2
ZONE 2
Z O
N E
Z O
N E
Z
O N
E
ZONE 3
ZONE 3ZONE 3
ZONE 3
ZONE 2 ZONE 1
ZONE 3
ZONE 3
GROSS COMPONENT AND CLADDING WIND LOAD (PSF)
>5002001005020<10
ZONE
EFFECTIVE
AREA
SQ FT
+16.0 -30.4
+16.0 -29.7
+16.0 -28.6
+16.0 -27.9
+16.0 -27.9
+16.0 -27.9
+16.0 -51.1
+16.0 -45.7
+16.0 -38.5
+16.0 -33.0
+16.0 -33.0
+16.0 -33.0
+16.0 -76.9
+16.0 -63.7
+16.0 -46.2
+16.0 -33.0
+16.0 -33.0
+16.0 -33.0
+27.9 -30.2
+26.6 -29.0
+25.0 -27.3
+23.8 -26.1
+22.5 -24.9
+20.9 -23.2
+27.9 -37.2
+26.6 -34.7
+25.0 -31.4
+23.8 -29.0
+22.5 -26.5
+20.9 -23.2
COMPONENT AND CLADDING TABLE NOTES:
1. WIND DESIGN PRESSURE (COMPONENTS AND CLADDING):
REFER TO DIAGRAM FOR ROOF ZONE 1, 2, AND 3. ZONES 4 AND 5 ARE WALL
ZONES THAT CORRESPOND TO THE LOCATION OF ROOF ZONES 2 AND 3, RESPECTIVELY
WITH THE SAME "a".
2. POSITIVE AND NEGATIVE VALUES REFER TO PRESSURE ACTING TOWARD AND AWAY
FROM THE SURFACE, RESPECTIVELY. THE VALUES INCLUDE EXTERNAL AND INTERNAL
PRESSURE OR SUCTION.
3. NET UPLIFT VALUES INCLUDE THE ALLOWABLE REDUCTIONS DUE TO ROOF DEAD LOAD
(ASCE 7-10 LOAD COMBINATION USING ALLOWABLE STRESS DESIGN 0.6D + 0.6W)
GROSS DEAD LOAD TO BE USED FOR THIS LOAD COMBINATION IS 15 PSF.
4. THE DESIGN WIND PRESSURE SHALL NOT BE LESS THAN A NET PRESSURE OF
16 LB/SQ FT ACTING IN EITHER DIRECTION NORMAL TO THE SURFACE.
SHEET ID
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R
IN
G C
O M
M A
N D
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A R
C H
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
T A
S K
O R
D E
R N
O
D
C
B
A
D A
T E
File Name:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
E
F
G
H
I
D e s ig n in g B e tt e r
F u tu re s
F O
R C
O N
S T
R U
C T
IO
N
2 3 4 5 6 7 8 9 10 11 12
H U
T Z
E L
F A
-1
-D
-0
Q
5/10/2019 11:31:28 AM
S-001
G E
N E
R A
L N
O T
E S
E D
W A
R D
S A
F B
C
A L
IF
O R
N
IA
V E
R S
T
S H
A R
P S
H A
IR
V E
R S
T
M M
-D D
-Y Y
Y Y
643005_Structural_Central_2018.rvt
F S
P M
A
N A
L Y
T
IC
S L
A B
O R
A T
O R
Y A
F R
L B
U
IL
D
IN
G
P R
O J E
C T
N O
-1
GENERAL NOTES
1. THE CONTRACTOR SHALL CONDUCT ALL OPERATIONS IN STRICT ACCORDANCE WITH THE
SAFETY REQUIREMENTS IMPOSED BY THE OWNER AND OSHA. IT IS SOLELY THE
CONTRACTOR'S RESPONSIBILITY TO FOLLOW ALL APPLICABLE SAFETY CODES AND
REGULATIONS GOVERNING THIS WORK. THE CONTRACTOR SHALL REMOVE ALL DEBRIS
FROM THE OWNER'S PROPERTY AND DISCARD ACCORDING TO LOCAL REGULATIONS.
2. THIS STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER IT IS FULLY
COMPLETED. HOWEVER, THE CONTRACTOR IS SOLELY RESPONSIBLE TO DETERMINE THE
ERECTION PROCEDURES AND SEQUENCES REQUIRED TO ENSURE STABILITY OF THE
STRUCTURE AND ITS COMPONENT PARTS DURING CONSTRUCTION. ANY TEMPORARY
BRACING, CONNECTIONS, GUYS, OR TIE-DOWNS THAT MAY BE NECESSARY DURING
ERECTION ARE NOT SHOWN ON STRUCTURAL DRAWINGS. IF APPLIED, THEY SHALL BE
REMOVED AS CONDITIONS PERMIT, AND SHALL REMAIN THE PROPERTY OF THE
CONTRACTOR. THIS CONSTRUCTION STABILITY REQUIREMENT APPLIES CONTINUOUSLY
AND IS NOT LIMITED TO NORMAL WORKING HOURS.
3. ALL TEMPORARY SHORING DRAWINGS SHALL BE PREPARED AND STAMPED BY A LICENSED
ENGINEER.
4. EXISTING UTILITIES AND ALL OTHER OBSTRUCTIONS TO WORK SHALL BE TEMPORARILY
REMOVED AND RE-INSTALLED (INCLUDING NECESSARY MODIFICATIONS) BY THE
CONTRACTOR AFTER COMPLETION OF NEW WORK.
5. DIMENSIONS PERTAINING TO EXISTING CONDITIONS SHALL BE FIELD VERIFIED BY THE
CONTRACTOR PRIOR TO ANY FABRICATION, CONSTRUCTION, OR ERECTION.
6. ALL DETAILS, SECTIONS, AND NOTES PROVIDED ON STRUCTURAL DRAWINGS ARE
INTENDED TO BE TYPICAL FOR SIMILAR SITUATIONS ELSEWHERE, UNLESS SPECIFICALLY
NOTED OTHERWISE. FOR ANY DETAILS AND DIMENSIONS NOT PROVIDED, REFER TO
ARCHITECTURAL DRAWINGS. ALL DIMENSIONS AND ELEVATIONS SHOWN ON STRUCTURAL
DRAWINGS WERE INTENDED TO CONFORM WITH THE INFORMATION PROVIDED ON
ARCHITECTURAL DRAWINGS. THE CONTRACTOR SHALL REPORT ANY DISCREPANCIES TO
THE ARCHITECT OR STRUCTURAL ENGINEER FOR RESOLUTION BEFORE PROCEEDING WITH
ANY ADDITIONAL WORK.
7. OPENING SIZES AND LOCATIONS SHOWN FOR PIPES, DUCTS, ETC. ARE SHOWN FOR
GENERAL INFORMATION ONLY. REFER TO RELATED DRAWINGS (ARCH., MECH., ELECT,
ETC.) FOR OTHER POSSIBLE EQUIPMENT SUPPORTS; WALL, FLOOR AND ROOF OPENINGS;
SLEEVES; AND OTHER EMBEDDED ITEMS NOT SPECIFICALLY INDICATED ON STRUCTURAL
DRAWINGS. COORDINATE ALL REQUIRED DIMENSIONS WITH APPLICABLE TRADE
CONTRACTORS PRIOR TO ANY STEEL FABRICATION OR CONCRETE PLACEMENT. ANY
OPENINGS REQUIRED TO BE LARGER THAN OPENINGS SHOWN SHALL BE VERIFIED PRIOR
TO CONSTRUCTION.
8. ALL FRAMING MEMBERS PROVIDED FOR MECHANICAL TRADES, ELEVATOR SUPPORT
BEAMS, LINTELS, ROOF OPENINGS, ETC. ARE FOR BIDDING PURPOSES ONLY. THE
CONTRACTOR SHALL SUBMIT MANUFACTURER'S DESIGN DATA FOR THE PROPOSED
EQUIPMENT PRIOR TO STEEL SHOP DRAWING SUBMITTAL, SO STRUCTURAL ENGINEER CAN
VERIFY AND REDESIGN THE SUPPORT FRAMING (IF NECESSARY) TO ACCOMMODATE THE
ACTUAL CONDITION.
9. ALL SPECIAL INSPECTIONS REQUIRED BY THE BUILDING OFFICIAL SHALL BE CONDUCTED IN
ACCORDANCE WITH THE APPLICABLE SECTIONS OF THE GOVERNING BUILDING CODE.
REFER TO THE SPECIAL INSPECTION REQUIREMENTS ON SHEET S.002.
10. REFER TO THE PROJECT SPECIFICATIONS FOR SHOP DRAWINGS AND SUBMITTAL
REQUIREMENTS.
11. SHOP DRAWINGS AND SUBMITTALS PREPARED BY SUPPLIERS AND/OR SUBCONTRACTORS
SHALL BE REVIEWED AND STAMPED BY THE GENERAL CONTRACTOR PRIOR TO
SUBMISSION TO THE STRUCTURAL ENGINEER. ALL DEVIATIONS FROM THE CONTRACT
DOCUMENTS SHALL BE CIRCLED AND NOTED ON THE SHOP DRAWINGS BY THE
CONTRACTOR. THE SCOPE OF THE STRUCTURAL ENGINEER'S REVIEW WILL BE LIMITED TO
CHECKING CONTRACTOR'S GENERAL CONFORMANCE WITH THE CONTRACT DOCUMENTS
AND DESIGN CONCEPT. NO SHOP WORK IS PERMITTED TO COMMENCE UNTIL THE RETURN
OF THE SHOP DRAWINGS BY THE GENERAL CONTRACTOR. DO NOT BEGIN SHOP WORK
UNTIL SHOP DRAWINGS ARE RETURNED WITH ENGINEER’S COMMENTS.
12. USE THE PROJECT SPECIFICATIONS IN CONJUNCTION WITH THE STRUCTURAL DRAWINGS
TO DETERMINE THE COMPLETE PROJECT REQUIREMENTS. ANY DISCREPANCIES OR
CONFLICTS FOUND BETWEEN THE PROJECT SPECIFICATIONS AND THE STRUCTURAL
DRAWINGS SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT OR STRUCTURAL
ENGINEER IMMEDIATELY. THE STRICTEST PROVISION SHALL GOVERN UNLESS THE A/E
DETERMINES OTHERWISE.
CAST-IN-PLACE CONCRETE
ALL CONCRETE WORK SHALL CONFORM TO ALL REQUIREMENTS OF THE CURRENT ACI 301,
"SPECIFICATIONS FOR STRUCTURAL CONCRETE" AND ACI 117 "STANDARD SPECIFICATIONS
FOR TOLERANCES FOR CONCRETE CONSTRUCTION AND MATERIALS" WITH THE
FOLLOWING SUPPLEMENTAL REQUIREMENTS:
1. ALL CONCRETE SHALL BE NORMAL WEIGHT WITH TYPE I OR TYPE II PORTLAND CEMENT
CONFORMING TO ASTM C150 AND AGGREGATES CONFORMING TO ASTM C33.
2. CONCRETE SHALL DEVELOP THE FOLLOWING 28-DAY COMPRESSIVE STRENGTH (F'c):
A. ALL CONCRETE WORK UNLESS NOTED OTHERWISE - 4,000 PSI.
B. CONCRETE SHALLOW SPREAD FOOTINGS - 3,000 PSI
3. GROUT UNDER STEEL COLUMN AND BEAM BEARINGS SHALL BE NON-METALLIC,
NON-SHRINK, NON-GAS FORMING, EXPANSIVE TYPE "SONOGROUT" BY
SONNEBORN/CONTECH, "SEALTIGHT 588" BY W.R. MEADOWS, "EUCO NS" BY THE EUCLID
CHEMICAL COMPANY, OR "MASTERFLOW 928" BY MASTERBUILDERS. GROUT UNDER STEEL
BEARINGS SUPPORTING EQUIPMENT SHALL BE "SIKADUR-42" HIGH STRENGTH POURABLE
EPOXY RESIN GROUT BY THE SIKA CORPORATION. TYPICAL, UNLESS NOTED OTHERWISE.
4. CONCRETE SHALL BE PLACED AT THE SITE WITHIN 90 MINUTES AFTER WATER HAS BEEN
ADDED TO THE CEMENT AND AGGREGATE. ADDITION OF WATER TO THE MIX AT THE
PROJECT SITE WILL NOT BE ALLOWED. ALL WATER MUST BE ADDED AT THE BATCH PLANT.
5. MAXIMUM LENGTH OF WALL POUR BETWEEN CONSTRUCTION JOINTS SHALL NOT EXCEED
60 FEET. JOINTS NOT INDICATED ON STRUCTURAL DRAWINGS ARE NOT PERMITTED
WITHOUT WRITTEN APPROVAL FROM STRUCTURAL ENGINEER.
6. MAXIMUM LENGTH OF SLAB POUR BETWEEN CONSTRUCTION JOINTS SHALL NOT EXCEED
100 FEET, WHILE MAXIMUM AREA OF A SINGLE SLAB POUR SHALL NOT EXCEED 10,000
SQUARE FEET. JOINTS NOT INDICATED ON STRUCTURAL DRAWINGS ARE NOT PERMITTED
WITHOUT WRITTEN APPROVAL FROM STRUCTURAL ENGINEER.
7. CHLORIDE BASED ADMIXTURES ARE PROHIBITED IN ALL REINFORCED CONCRETE. OTHER
ADMIXTURES SHALL CONFORM TO ASTM C494.
8. MAXIMUM SLUMP SHALL BE 4" +/- 1", AS DETERMINED IN ACCORDANCE WITH ASTM C143.
9. AIR ENTRAIN ALL CONCRETE EXPOSED TO WEATHER 6% +/- 1 1/2%.
10. CONCRETE FINISH:
A. INTERIOR FLOOR SLABS - HARD TROWELED FINISH
B. PAVING SLABS/SIDEWALKS - FLOAT/BROOM
11. WHERE INDICATED ON DRAWINGS PROVIDE NO. 15 LB. ASPHALT ROOFING FELT BOND
BREAKER BETWEEN SLABS AND EXISTING CONSTRUCTION.
12. ALL REINFORCING STEEL SHALL BE DEFORMED AND CONFORM TO ASTM A615 GRADE 60,
EXCEPT AS NOTED. WELDED REINFORCING STEEL SHALL BE DEFORMED AND CONFORM
TO ASTM A706 GRADE 60. ALL WELDED WIRE FABRIC SHALL CONFORM TO ASTM A1064,
AND BE FURNISHED IN FLAT SHEETS.
13. CONCRETE COVER ON REINFORCING STEEL SHALL BE PER CURRENT ACI 318 UNLESS
NOTED OTHERWISE.
14. REINFORCEMENT SHALL BE CONTINUOUS ACROSS CONSTRUCTION JOINTS, UNLESS
NOTED OTHERWISE.
15. REINFORCING BARS REQUIRED FOR PROPER SUPPORT OF THE PRINCIPAL REINFORCING
SHALL BE DETAILED AND SUPPLIED BY THE CONTRACTOR WHETHER OR NOT THEY ARE
INDICATED ON THE DRAWINGS.
16. ALL HOOK BARS SHALL HAVE 90 DEGREE ACI STANDARD HOOKS, UNLESS NOTED
OTHERWISE. HOOKS MAY BE ROTATED TO MAINTAIN CLEARANCES. ALL BAR SPLICES AND
LAPS, WHEN NOT SPECIFICALLY DIMENSIONED ON DRAWINGS, SHALL BE PER ACI
STANDARD REQUIREMENTS. CLASS B LAPS SHALL BE USED, UNLESS NOTED OTHERWISE.
17. TOP AND BOTTOM BARS DESIGNATED AS CONTINUOUS IN STRUCTURAL DRAWINGS SHALL
BE LAPPED AS FOLLOWS:
A. TOP BARS NEAR MIDSPAN
B. BOTTOM BARS DIRECTLY OVER SUPPORTS
18. ALL LAP SPLICES, WHEN NOT SPECIFICALLY DIMENSIONED ON DRAWINGS, SHALL BE PER
ACI 318 SECTION 12.2. LAPPING BARS OF TWO DIFFERENT SIZES SHALL BE PER ACI 318
SECTION 12.15.3.
19. PROVIDE HORIZONTAL EXTERIOR CORNER BARS WITH SAME SIZE AND SPACING AS WALL
REINFORCING BARS, UNLESS NOTED OTHERWISE.
20. THE PLACEMENT OF CONDUITS IN CONCRETE SHALL ONLY BE ACCEPTED IN ISOLATED
CASES AND SHALL ADHERE TO THE FOLLOWING:
A. CONDUITS PLACED IN SLAB ON GRADE SHALL BE PLACED DIRECTLY ON THE SUBGRADE
OR VAPOR RETARDER. OUTSIDE DIAMETER OF CONDUIT SHALL NOT EXCEED 1/4 OF SLAB
THICKNESS.
B. ALUMINUM CONDUITS, PIPES, OR SLEEVES ARE NOT PERMITTED.
C. OUTSIDE DIAMETER OF CONDUITS SHALL BE 1" OR LESS WHERE EMBEDDED IN
STRUCTURAL SLABS, AND 1 1/2" OR LESS WHERE EMBEDDED IN BEAMS, WALLS OR
COLUMNS.
D. BUNCHING OF CONDUITS IS NOT PERMITTED. CONDUITS SHALL BE SPACED 3
DIAMETERS OR GREATER ON CENTER. NO CROSSOVERS ARE PERMITTED IN SLABS.
E. MINIMUM CONCRETE COVER ON CONDUITS SHALL BE 1 1/2".
21. ALL INTERIOR FLOOR SLABS SHALL BE FINISHED TO THE FOLLOWING TOLERANCES AND
SHALL BE MEASURED PER ASTM E1155 LATEST EDITION AND SHALL BE MEASURED WITHIN
72 HOURS OF SLAB CONCRETE PLACEMENT:
PER SPECIFICATIONS
22. MAXIMUM WATER CEMENT RATIO FOR SLAB ON GRADE SHALL BE 0.45. CONCRETE SHALL
BE POURED AT THE SITE WITHIN 90 MINUTES AFTER WATER HAS BEEN ADDED TO THE
CEMENT AND AGGREGATE. ADDITION OF WATER TO THE MIX AT THE PROJECT SITE WILL
NOT BE ALLOWED. ALL WATER MUST BE ADDED AT THE BATCH PLANT.
STRUCTURAL STEEL
THE FABRICATION AND ERECTION OF STRUCTURAL STEEL SHALL CONFORM TO ALL
REQUIREMENTS OF THE CURRENT AISC 360 "SPECIFICATION FOR STRUCTURAL STEEL
BUILDINGS" AND AISC 303 "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND
BRIDGES" WITH THE FOLLOWING SUPPLEMENTAL REQUIREMENTS:
1. WIDE FLANGE ROLLED STEEL SHAPES SHALL CONFORM TO ASTM A992, Fy=50 KSI, WHILE ALL PLATES, BARS, CHANNELS, AND ANGLES SHALL CONFORM TO ASTM A36, Fy=36 KSI.
HOLLOW STRUCTURAL SECTIONS (HSS) SHALL CONFORM TO ASTM A500, GRADE B, WITH A
MINIMUM YIELD STRESS (Fy) OF 46 KSI FOR SQUARE AND RECTANGULAR SHAPES, AND A MINIMUM YIELD STRESS (Fy) OF 42 KSI FOR ROUND SHAPES.
2. SPLICING OF STRUCTURAL STEEL IS PROHIBITED EXCEPT AS DETAILED.
3. ALL STRUCTURAL STEEL SHALL BE NEW UNLESS NOTED OTHERWISE, AND SHALL BE MADE
FREE OF RUST, SCALE, ETC., AND SHIPPED WITH ONE COAT OF OXIDE PRIMER. ALL STEEL
TO RECEIVE FIREPROOFING SHALL NOT BE PRIME PAINTED, AND ALL STEEL EXPOSED TO
WEATHER OR BELOW GRADE SHALL BE HOT-DIP GALVANIZED, EXCEPT AS NOTED.
4. ALL BOLTS FOR STRUCTURAL STEEL SHALL CONFORM TO ASTM A325X AND SHALL BE 3/4"
DIAMETER MINIMUM UNLESS NOTED OTHERWISE. BOLTS SHALL BE INSTALLED WITH VISUAL
TENSION INDICATORS, ASTM A563 NUTS, AND SHALL HAVE AN ASTM F436 HARDENED STEEL
WASHER UNDER THE TURNED ELEMENT. BOLTS FOR JOISTS AND JOISTS GIRDERS SHALL
BE PER SJI.
5. WELDING SHALL CONFORM TO THE CURRENT AWS D1.1 "STRUCTURAL WELDING
CODE-STEEL", AND WELDING ELECTRODES SHALL BE E70. ALL FIELD WELDS ON
GALVANIZED STEEL SHALL BE TOUCHED UP WITH COLD GALVANIZING COMPOUND.
6. WELDS SHALL BE MADE ONLY BY CERTIFIED WELDERS AND WELDING OPERATORS WHO
HAVE BEEN PREVIOUSLY QUALIFIED BY TESTS AS PRESCRIBED IN THE CURRENT AWS D1.1
"STRUCTURAL WELDING CODE-STEEL". PROOF OF CERTIFICATION SHALL BE SUBMITTED TO
THE OWNER FOR APPROVAL BEFORE ANY WELDING IS PERMITTED TO BEGIN.
7. ANCHOR BOLTS FOR COLUMNS SHALL CONFORM TO ASTM F1554, GRADE AS NOTED ON
DRAWINGS, AND SHALL BE SET BY A TEMPLATE METHOD, OR AN APPROVED EQUIVALENT
METHOD.
8. ALL COLUMN CAP PLATES SHALL BE 5/8" UNLESS NOTED OTHERWISE.
9. ALL VERTICAL BRACING SHALL BE INSTALLED ALONG THE CENTERLINE OF COLUMNS,
UNLESS NOTED OTHERWISE.
10. DESIGN CONNECTIONS FOR THE FULL UNIFORM LOAD CAPACITY OF THE CONTINUOUS
BRACED MEMBER, UNLESS NOTED OTHERWISE.
STEEL JOISTS
1. ALL JOISTS SHALL CONFORM TO THE STEEL JOIST INSTITUTE (SJI) STANDARD
SPECIFICATION, LOAD TABLES AND DETAILS FOR STEEL JOISTS AND JOIST GIRDERS.
2. NO JOISTS SHALL BE CUT OR OTHERWISE MODIFIED WITHOUT THE MANUFACTURER'S
KNOWLEDGE AND WRITTEN APPROVAL.
3. JOIST BRIDGING SHALL BE FURNISHED IN ACCORDANCE WITH SJI STANDARDS EXCEPT
WHERE THESE DRAWINGS DICTATE HEAVIER OR MORE FREQUENT BRIDGING. DESIGN
JOISTS AND GIRDERS FOR THE UPLIFT SHOWN ON THE DESIGN DOCUMENTS.
4. THE TOP AND BOTTOM CHORDS OF THE JOISTS SHALL BE CAPABLE OF SUPPORTING
LIMITED CONCENTRATED LOADS AT ANY POINT WITHOUT ADDITIONAL REINFORCING. THEY
SHALL SUPPORT A CONCENTRATED LIVE LOAD OF 100 POUNDS ON THE BOTTOM CHORD
AND 100 POUNDS ON THE TOP CHORD, NONCONCURRENT WITH THE SPECIFIED UNIFORM
LIVE LOAD. REINFORCE THE JOISTS FOR HEAVIER CONCENTRATED LOADS WHERE
INDICATED ON THE DRAWINGS.
5. LOADS ON JOISTS ARE BASED ON ALLOWABLE STRESS DESIGN.
6. TYPICAL K-SERIES JOIST SEAT DEPTH SHALL BE 2 1/2". TYPICAL LH-SERIES JOIST SEAT
DEPTH SHALL BE 5". TYPICAL UNLESS NOTED OTHERWISE.
7. ALL STEEL JOISTS SHALL BE STORED AND INSTALLED PER SJI RECOMMENDATIONS.
8. DO NOT SUSPEND ANY OBJECT OR LOAD FROM JOIST BRIDGING.
STEEL FLOOR DECK
1. METAL DECK FOR FLOORS SHALL CONFORM TO THE STEEL DECK INSTITUTE DESIGN
MANUAL FOR COMPOSITE DECKS, FORM DECKS AND ROOF DECKS.
2. ALL STEEL FLOOR AND ROOF DECK SHALL BE GALVANIZED G60 AND INSTALLED
CONTINUOUS OVER A MINIMUM OF 3 SPANS, UNLESS NOTED OTHERWISE.
3. DECK WORK SHALL INCLUDE ANY MISCELLANEOUS CLOSURE PIECES, METAL SCREEDS,
CURBS, REINFORCING AROUND OPENINGS, ETC REQUIRED TO COMPLETE THE FLOOR
DECK INSTALLATION. MISCELLANEOUS ITEMS SHALL BE GALVANIZED.
4. FLOOR DECK SHALL BE FASTENED TO ALL SUPPORTS WITH #12 TEK SCREWS WITH A 33/4
PATTERN AND AT 6" O.C. AT ALL EDGES. DECK SIDELAPS SHALL BE FASTENED WITH #10
TEK SCREWS AT MID-POINTS. UNLESS NOTED OTHERWISE, ALL DECK SHALL HAVE A
MINIMUM END LAP OF 3".
5. THE STEEL FLOOR DECK FUNCTIONS AS A STRUCTURAL ELEMENT IN RESISTING LATERAL
LOADS AND PROVIDES OVERALL STABILITY FOR THE BUILDING. THEREFORE, TEMPORARY
CONSTRUCTION BRACING SHALL NOT BE REMOVED UNTIL ALL STEEL DECK IS COMPLETELY
FASTENED IN PLACE.
6. THE STEEL DECK SHALL HAVE THE FOLLOWING MINIMUM PROPERTIES:
1 1/2" x 20 GA. COMPOSITE FLOOR DECK - Ip=0.186 IN4, Sp=0.224 IN3, In=0.222 IN4, Sn=0.231 IN3, Fy=50KSI
ANTI-TERRORISM AND FORCE PROTECTION
1. BUILDING AND COMPONENTS SHALL BE DESIGNED IN ACCORDANCE WITH THE MINIMUM
PROTECTIVE MEASURES AS SPECIFIED BY THE CURRENT DEPARTMENT OF DEFENSE
MINIMUM ANTI-TERRORISM STANDARDS FOR BUILDINGS, UFC 4-010-01.
SUPPORT OF NON-STRUCTURAL COMPONENTS
1. COMPONENT LOADS SHALL BE DISTRIBUTED TO THE STRUCTURE SO THAT THE
COLLATERAL LOAD ALLOWANCES PROVIDED WITH THE STRUCTURAL DESIGN DATA ARE
NEVER EXCEEDED. SUPPORT ANCHORS SHALL HAVE AN ULTIMATE SAFETY FACTOR OF AT
LEAST 4.0.
2. LOADS SUPPORTED FROM BAR JOISTS OR JOIST GIRDERS SHALL BE APPLIED AT A PANEL
POINT. IF LOADS ARE LOCATED OFF A PANEL POINT, REINFORCE THE JOIST/JOIST GIRDER
PER 15/S-501. LOADS SHALL BE APPLIED IN A MANNER WHICH DOES NOT CAUSE TORSION
ABOUT THE LONGITUDINAL AXIS OF THE JOIST OR JOIST GIRDER.
3. COORDINATE AND VERIFY EXACT SIZE AND LOCATION OF MECHANICAL UNITS AND ALL
FRAMED OPENINGS IN FLOORS AND/OR ROOF WITH MECHANICAL DRAWINGS AND
EQUIPMENT SUPPLIER. HVAC CONTRACTOR SHALL PROVIDE ACCURATE DIMENSIONAL
INFORMATION TO STEEL FABRICATOR PRIOR TO FABRICATION OF ALL SUPPORT FRAMES.
4. DO NOT HANG OR OTHERWISE SUPPORT ANY ITEMS DIRECTLY FROM STEEL ROOF DECK.
ROOF CURBS MUST BEAR DIRECTLY ON SUPPORT STEEL WITH SHIMS TO TRANSFER LOADS
THROUGH THE ROOF DECK.
MISCELLANEOUS FRAMING NOTES
1. UNLESS NOTED OTHERWISE ON FRAMING PLANS, FLOOR BEAMS, ROOF BEAMS, AND
JOISTS ARE EVENLY SPACED BETWEEN COLUMN GRID LINES.
2. ALL FRAMING CONNECTIONS SHALL BE COMPLETED PRIOR TO CASTING ELEVATED FLOOR
SLABS. SLABS SHALL BE CAST TO A LEVEL SURFACE AS SHOWN BY A LASER LEVEL. SLAB
THICKNESS INDICATED ON PLANS ARE MINIMUMS, AND SUPPLY ADDITIONAL CONCRETE AS
REQUIRED TO MEET LEVEL TOLERANCES. FINISH SLABS TO REQUIRED TOLERANCES
CONTAINED IN THE PROJECT SPECIFICATIONS.
ADHESIVE FASTENERS
1 EPOXY ADHESIVE SHALL BE EPCON "CERAMIC 6" EPOXY MANUFACTURED BY ITW RAMSET /
RED HEAD. OR HIT RE 500 EPOXY ADHESIVE MANUFACTURED BY THE HILTI COMPANY.
INSTALL PER MANUFACTURER'S RECOMMENDATIONS. SUBSTITUTES MAY BE CONSIDERED;
SUBMIT MANUFACTURER'S DATA PRIOR TO INSTALLATION.
2 THREADED RODS SHALL BE ASTM A36. SIZES AND EMBEDMENT AS INDICATED ON THE
DRAWINGS.
3 CONDUCT JOB-SITE TRAINING OF ALL CONTRACTOR’S PERSONNEL INSTALLING THIS
PRODUCT FOR SAFE AND PROPER INSTALLATION, HANDLING, AND STORAGE OF THE
EPOXY SYSTEM.
4 ANCHORAGE TO CONCRETE: HILTI "HIT-RE 500-SD" EPOXY (ICC ESR-2322). INSTALL PER ICC
REPORT AND MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS (MPII).
SUBSTITUTES COMPLYING WITH ACCEPTANCE CRITERIA AC 308 FOR USE IN CRACKED
CONCRETE MAY BE CONSIDERED; SUBMIT EVALUATION REPORT DEMONSTRATING
COMPLIANCE WITH GOVERNING CODE PRIOR TO INSTALLATION.
A. STEEL THREADED ROD ANCHORS SHALL BE HILTI "HAS-E" STANDARD RODS. SIZE AND
EMBEDMENT SHALL BE AS INDICATED ON DRAWINGS.
5 ANCHORAGE TO SOLID GROUTED CONCRETE MASONRY UNITS: HILTI "HIT HY 150 MAX" (ICC
ESR-1967). INSTALL PER ICC REPORT AND MANUFACTURER'S PRINTED INSTALLATION
INSTRUCTIONS (MPII). SUBSTITUTES COMPLYING WITH ACCEPTANCE CRITERIA AC 58 MAY
BE CONSIDERED; SUBMIT EVALUATION REPORT DEMONSTRATING COMPLIANCE WITH
GOVERNING CODE PRIOR TO INSTALLATION.
A. STEEL THREADED ROD ANCHORS SHALL BE HILTI "HAS-E" RODS. SIZE AND EMBEDMENT
SHALL BE AS INDICATED ON DRAWINGS.
B. FOR TEMPERATURES BETWEEN 40 °F AND -10 °F, USE HILTI HIT-ICE ADHESIVE ANCHORS.
6 CONTRACTOR SHALL VERIFY THAT THE SHELF LIFE OF THE ADHESIVE HAS NOT BEEN
EXCEEDED ON THE DATE OF INSTALLATION.
7 TESTING AND INSPECTION: REFER TO ICC REPORT(S) AND SPECIAL INSPECTION TABLE FOR
TESTING AND INSPECTION REQUIREMENTS.
MECHANICAL FASTENERS
1 EXPANSION ANCHORS SHALL BE THE TYPE, SIZE, AND EMBEDMENT INDICATED ON
DRAWINGS. INSTALL PER MANUFACTURER'S RECOMMENDATIONS AND ICC ESR REPORTS.
SUBSTITUTES MAY BE CONSIDERED; SUBMIT MANUFACTURER'S DATA PRIOR TO
INSTALLATION.
2 ANCHORAGE TO CONCRETE: INSTALL PER ICC REPORT AND MANUFACTURER'S PRINTED
INSTALLATION INSTRUCTIONS (MPII). SUBSTITUTES COMPLYING WITH ACCEPTANCE
CRITERIA AC 193 AND ACI 355.2-07 FOR USE IN CRACKED CONCRETE MAY BE CONSIDERED;
SUBMIT EVALUATION REPORT DEMONSTRATING COMPLIANCE WITH GOVERNING CODE
PRIOR TO INSTALLATION.
3 ANCHORAGE TO CONCRETE MASONRY UNITS: INSTALL PER ICC REPORT AND
MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS (MPII). SUBSTITUTES
COMPLYING WITH ACCEPTANCE CRITERIA AC 01 INCLUDING SEISMIC TESTS MAY BE
CONSIDERED; SUBMIT EVALUATION REPORT DEMONSTRATING COMPLIANCE WITH
GOVERNING CODE PRIOR TO INSTALLATION.
4 TESTING AND INSPECTION: REFER TO ICC REPORT(S) AND SPECIAL INSPECTION TABLE FOR
TESTING AND INSPECTION REQUIREMENTS.
FOUNDATIONS
1. ALL EXCAVATION WORK SHALL PROCEED WITH CAUTION TO AVOID DAMAGE TO UNKNOWN
UNDERGROUND UTILITIES.
2. THE FOUNDATION DESIGN IS BASED UPON THE RECOMMENDATIONS OUTLINED IN THE
GEOTECHNICAL STUDY BY xxxxxxxxx (PROJECT NO. xxxxxxxxxx DATED NOVEMBER xx,20xx).
CONTRACTOR SHALL REVIEW ENTIRE GEOTECHNICAL INVESTIGATION REPORT PRIOR TO
EXCAVATION WORK.
3. ALL EXCAVATION AND FILL SHALL BE PERFORMED ACCORDING TO THE ABOVE
REFERENCED GEOTECHNICAL REPORT.
4. ALL EXCAVATIONS SHALL BE INSPECTED BY A REPRESENTATIVE OF THE GEOTECHNICAL
ENGINEER, OR AN APPROVED GEOTECHNICAL TESTING AGENCY TO VERIFY THE PROPER
BEARING MATERIAL EXISTS PRIOR TO PLACING ENGINEERED FILL, FOUNDATION CONCRETE
AND/OR SLAB ON GRADE. FOUNDATION ELEVATIONS SHOWN ARE FOR BIDDING PURPOSES
ONLY, AND MAY VARY TO SUIT ACTUAL SUBSURFACE SOIL CONDITIONS.
5. SHALLOW SPREAD FOOTINGS BEARING ON NATURAL SOIL OR NEW GRANULAR
ENGINEERED FILL ARE DESIGNED FOR A MAXIMUM SOIL BEARING PRESSURE OF 2,000 PSF.
SHALLOW SPREAD FOOTINGS BEARING ON SLURRY OF INFILLED PIT ARE DESIGNED FOR A
MAXIMUM BEARING CAPACITY OF 5,000 PSF. SOILS UNSUITABLE FOR SUPPORTING
FOUNDATIONS SHALL BE REMOVED AND BACKFILLED TO THE DESIGN BEARING ELEVATION,
AS DIRECTED BY THE GEOTECHNICAL ENGINEER.
6. ALL FOUNDATION BEARING SURFACES SHALL BE UNDISTURBED, LEVEL (WITHIN 1 IN 12),
AND UNLESS NOTED OTHERWISE, ALL FOOTINGS MAY BE POURED NEAT (WITHOUT SIDE
FORMS) WHERE SOIL CONDITIONS PERMIT.
7. ALL COLUMN DOWELS AND ANCHOR BOLTS SHALL BE SET BY A TEMPLATE METHOD PRIOR
TO CONCRETE PLACEMENT.
COMPONENT AND CLADDING DIAGRAM
COMPONENT AND CLADDING
MASONRY
MASONRY WORK SHALL CONFORM TO ALL REQUIREMENTS OF THE CURRENT ACI 530
"BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES" AND ACI 530.1
"SPECIFICATION FOR MASONRY STRUCTURES", WITH THE FOLLOWING SUPPLEMENTAL
REQUIREMENTS:
1. HOLLOW CONCRETE MASONRY UNITS (CMU) SHALL BE TYPE I OR II, MEDIUM WEIGHT, IN
ACCORDANCE WITH ASTM C90. MINIMUM 28-DAY COMPRESSIVE STRENGTH OF UNITS SHALL
BE 1,800 PSI BASED ON THE NET AREA.
2. MORTAR FOR CONCRETE MASONRY SHALL BE TYPE S, IN ACCORDANCE WITH ASTM C270,
AND SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 1800 PSI IN 28 DAYS. ALL UNITS
SHALL BE LAID WITH FULL MORTAR COVERAGE ON HEAD, BED (FACE SHELLS), WEBS, AND
COLLAR JOINTS.
3. ALL MASONRY REINFORCING STEEL SHALL BE DEFORMED AND CONFORM TO ASTM A615
OR A996 GRADE 60. THE MINIMUM LAP FOR SPLICES SHALL BE 48 BAR DIAMETERS.
REINFORCING SHALL BE HELD IN POSITION AT INTERVALS NOT TO EXCEED 192 BAR
DIAMETERS.
4. GROUT SHALL CONFORM TO ASTM C476, "FINE" AND SHALL HAVE A MINIMUM 28-DAY
COMPRESSIVE STRENGTH OF 2,000 PSI AND A SLUMP BETWEEN 8" AND 11". THE LOW-LIFT
METHOD SHALL BE USED TO PLACE GROUT.
5. ALL VERTICAL MASONRY REINFORCING SHALL BE PLACED IN FULLY GROUTED CELLS.
6. DOWELS FROM FOUNDATION INTO MASONRY WALLS SHALL MATCH SIZE AND SPACING OF
WALL VERTICAL BARS, UNLESS NOTED OTHERWISE. DOWELS SHALL BE PROVIDED AND
INSTALLED BY THE FOUNDATION CONTRACTOR, BUT MASONRY CONTRACTOR SHALL
REVIEW THE ACCURACY OF THE DOWEL LAYOUT AND PLACEMENT PRIOR TO THE
PLACEMENT OF FOUNDATION CONCRETE.
7. VERTICAL BARS SHALL BE CONTINUOUS THROUGH BOND BEAMS UNLESS NOTED
OTHERWISE.
8. ALL CMU MASONRY WALLS SHALL BE REINFORCED WITH 9 GAUGE STANDARD TRUSS-TYPE
DURAWALL (OR APPROVED EQUAL), CONFORMING TO ASTM A82, AND CONTINUOUSLY
PLACED IN ALTERNATE HORIZONTAL MORTAR JOINTS (16" OC VERTICALLY). ALL WIRE
REINFORCING SHALL BE HOT-DIPPED GALVANIZED, AND SHALL CONFORM TO ASTM A951.
HORIZONTAL JOINT REINFORCING SHALL ALSO BE PROVIDED AT THE TOP AND BOTTOM OF
WALL OPENINGS, AND SHALL EXTEND NOT LESS THAN 2'-0" PAST THE OPENING.
9. ALL HOLLOW METAL DOOR/WINDOW FRAMES AND STRUCTURAL STEEL JAMB/HEADER TO
BE INSTALLED WITH ADJUSTABLE ANCHORS AND "BUILT INTO" THE CMU. GROUT FRAMES
SOLID AS CMU INSTALLATION PROGRESSES.
10. PROVIDE A VERTICAL CONTROL JOINT AT LOCATIONS INDICATED ON ARCHITECTURAL
ELEVATION SHEETS. BOND BEAM REINFORCING AND GROUT SHALL BE CONTINUOUS AT
MASONRY WALL CONTROL JOINTS.
11. PROVIDE LINTELS OVER OPENINGS IN MASONRY WALLS. SEE SHEET S.501 FOR LINTEL
SIZES AND REFER TO ARCHITECTURAL AND MECHANICAL DRAWINGS (WHEN APPLICABLE)
FOR EXACT NUMBER, LOCATION, AND SIZES OF WALL OPENINGS.
12. SOLID FILL ALL MASONRY POCKETS AND BEARINGS WITH MASONRY AND DRY PACK GROUT.
05-16-2019 100% SUBMITTAL
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R
IN
G C
O M
M A
N D
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A R
C H
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
T A
S K
O R
D E
R N
O
D
C
B
A
D A
T E
File Name:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
E
F
G
H
I
D e s ig n in g B e tt e r
F u tu re s
F O
R C
O N
S T
R U
C T
IO
N
2 3 4 5 6 7 8 9 10 11 12
H U
T Z
E L
F A
-1
-D
-0
Q
5/10/2019 11:31:31 AM
S-002
S P
E C
IA
L I
N S
P E
C T
IO
N
S
E D
W A
R D
S A
F B
C
A L
IF
O R
N
IA
V E
R S
T
S H
A R
P S
H A
IR
V E
R S
T
M M
-D D
-Y Y
Y Y
05-16-2019 100% SUBMITTAL
643005_Structural_Central_2018.rvt
F S
P M
A
N A
L Y
T
IC
S L
A B
O R
A T
O R
Y A
F R
L B
U
IL
D
IN
G
P R
O J E
C T
N O
-1
REQUIRED SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE
TYPE CONTINUOUS PERIODIC
REFERENCED
STANDARD
IBC
REFERENCE
1. STRUCTURAL STEEL
A. INSPECT IN ACCORDANCE WITH THE QUALITY ASSURANCE PLAN
REQUIREMENTS OF AISC 341.
AISC 341 1705.12.1
2. STORAGE RACKS
A. ANCHORAGE OF STORAGE RACKS 8 FEET OR GREATER IN HEIGHT. X 1705.12.7
3. ARCHITECTURAL COMPONENTS
A. ERECTION AND FASTENING OF EXTERIOR CLADDING, INTERIOR AND
EXTERIOR NONBEARING WALLS, AND INTERIOR AND EXTERIOR VENEER
X 1705.12.5
B. ANCHORAGE OF ACCESS FLOORS X 1705.12.5.1
4. PLUMBING, MECHANICAL AND ELECTRICAL COMPONENTS
A. ANCHORAGE OF ELECTRICAL EQUIPMENT FOR EMERGENCY AND
STANDBY POWER SYSTEMS
X 1705.12.6
B. ANCHORAGE OF OTHER ELECTRICAL EQUIPMENT X 1705.12.6
C. INSTALLATION AND ANCHORAGE OF PIPING SYSTEMS INTENDED TO
CARRY HAZARDOUS MATERIALS, AND THEIR ASSOCIATED MECHANICAL
UNITS
X 1705.12.6
D. INSTALLATION AND ANCHORAGE OF HVAC DUCTWORK DESIGNED TO
CARRY HAZARDOUS MATERIALS
X 1705.12.6
E. INSTALLATION AND ANCHORAGE OF VIBRATION ISOLATION SYSTEMS,
WHERE THE CONSTRUCTION DOCUMENTS REQUIRE A NOMINAL
CLEARANCE OF 1/4 INCH OR LESS BETWEEN THE EQUIPMENT SUPPORT
FRAME AND RESTRAINT
X 1705.12.6
5. DESIGNATED SEISMIC SYSTEMS
A. EXAMINE DESIGNATED SEISMIC SYSTEMS REQUIRING SEISMIC
QUALIFICATION IN ACCORDANCE WITH 13.2.2 OF ASCE 7 AND VERIFY THAT
THE LABEL, ANCHORAGE OR MOUNTING CONFORMS TO THE CERTIFICATE
OF COMPLIANCE.
1705.12.4
NOTES
1. "SFRS" REFERS TO "SEISMIC FORCE RESISTING SYSTEM".
REQUIRED SPECIAL INSPECTIONS OF COLD-FORMED STEEL DECK
TYPE CONTINUOUS PERIODIC
REFERENCED
STANDARD
IBC
REFERENCE
1. INSPECTION OR EXECUTION TASKS PRIOR TO DECK PLACEMENT. SD1 QA/QC 1705.2.2
A VERIFY COMPLIANCE OF MATERIALS (DECK AND ALL DECK
ACCESSORIES) WITH CONSTRUCTION DOCUMENTS, INCLUDING
PROFILES, MATERIAL PROPERTIES, AND BASE METAL THICKNESS
X
B DOCUMENT ACCEPTANCE OR REJECTION OF DECK AND DECK
ACCESSORIES.
X
2. INSPECTION OR EXECUTION TASKS AFTER DECK PLACEMENT SD1 QA/QC 1705.2.2
A VERIFY COMPLIANCE OF DECK AND ALL DECK ACCESSORIES
INSTALLATION WITH CONSTRUCTION DOCUMENTS.
X
B VERIFY DECK MATERIALS ARE REPRESENTED BY THE MILL
CERTIFICATIONS THAT COMPLY WITH THE CONSTRUCTION
DOCUMENTS.
X
C DOCUMENT ACCEPTANCE OR REJECTION OF INSTALLATION OF
DECK AND DECK ACCESSORIES.
X
3. INSPECTION OR EXECUTION TASKS PRIOR TO WELDING. SD1 QA/QC 1705.2.2
A WELDING PROCEDURE SPECIFICATIONS (WPS) AVAILABLE. X
B MANUFACTURER CERTIFICATIONS FOR WELDING CONSUMABLE
AVAILABLE.
X
C MATERIAL IDENTIFICATION (TYPE/GRADE). X
D CHECK WELDING EQUIPMENT.. X
4. INSPECTION OR EXECUTION TASKS DURING WELDING. SD1 QA/QC 1705.2.2
A USE OF QUALIFIED WELDERS. X
B CONTROL AND HANDLING OF WELDING CONSUMABLES. X
C ENVIRONMENTAL CONDITIONS (WIND SPEED, MOISTURE,
TEMPERATURE).
X
D WPS FOLLOWED. X
5. INSPECTION OR EXECUTION TASKS AFTER WELDING. SD1 QA/QC 1705.2.2
A VERIFY SIZE AND LOCATION OF WELDS, INCLUDING SUPPORT,
SIDELAP, AND PERIMETER WELDS.
X
B WELDS MEET VISUAL ACCEPTANCE CRITERIA. X
C VERIFY REPAIR ACTIVITIES. X
D DOCUMENT ACCEPTANCE OR REJECTION OF WELDS. X
6. INSPECTION OR EXECUTION TASKS PRIOR TO MECHANICAL
FASTENING.
SD1 QA/QC 1705.2.2
A MANUFACTURER INSTALLATION INSTRUCTIONS AVAILABLE FOR
MECHANICAL FASTENERS.
X
B PROPER TOOLS AVAILABLE FOR FASTENER INSTALLATION. X
C PROPER STORAGE FOR MECHANICAL FASTENERS. X
7. INSPECTION OR EXECUTION TASKS DURING MECHANICAL
FASTENING.
SD1 QA/QC 1705.2.2
A FASTENERS ARE POSITIONED AS REQUIRED. X
B FASTENERS ARE INSTALLED IN ACCORDANCE WITH
MANUFACTURER'S INSTRUCTIONS.
X
8. INSPECTION OR EXECUTION TASKS AFTER MECHANICAL
FASTENING.
SD1 QA/QC 1705.2.2
A CHECK SPACING, TYPE, AND INSTALLATION OF SUPPORT
FASTENERS.
X
B CHECK SPACING, TYPE, AND INSTALLATION OF SIDELAP
FASTENERS.
X
C CHECK SPACING, TYPE, AND INSTALLATION OF PERIMETER
FASTENERS.
X
D VERIFY REPAIR ACTIVITIES. X
E DOCUMENT ACCEPTANCE OR REJECTION OF MECHANICAL
FASTENERS.
X
REQUIRED SPECIAL INSPECTIONS OF CONCRETE CONSTRUCTION
TYPE CONTINUOUS PERIODIC
REFERENCED
STANDARD
IBC
REFERENCE
1. INSPECT REINFORCEMENT AND VERIFY PLACEMENT. X ACI 318 CH.
20, 25.2, 25.3, 26.6.1-26.6.3
1908.4
2. REINFORCING BAR WELDING: AWS D1.4
ACI 318: 26.6.4
A. VERIFY WELDABILITY OF REINFORCING BARS OTHER THAN ASTM A706; X
B. INSPECT SINGLE-PASS FILLET WELDS, MAXIMUM 5/16” X
C. INSPECT ALL OTHER WELDS. X
3. INSPECT ANCHORS CAST IN CONCRETE. X ACI 318: 17.8.2
4. INSPECT ANCHORS POST-INSTALLED IN HARDENED CONCRETE
MEMBERS.
SEE NOTE 1
BELOW
A. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLY
INCLINED ORIENTATIONS TO RESIST SUSTAINED TENSION LOADS.
X ACI 318:
17.8.2.4
B. MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT DEFINED IN 4.A. X ACI 318: 17.8.2
5. VERIFY USE OF REQUIRED DESIGN MIX. X ACI 318: Ch.
19, 26.4.3, 26.4.4
1904.1, 1904.2, 1908.2, 1908.3
6. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR
STRENGTH TESTS, PERFORM SLUMP AND AIR CONTENT TESTS, AND
DETERMINE THE TEMPERATURE OF THE CONCRETE.
X ASTM C172
ASTM C31
ACI 318: 26.4,
26.12
1908.10
7. INSPECT CONCRETE PLACEMENT FOR PROPER APPLICATION
TECHNIQUES.
X ACI 318: 26.5 1908.6,
1908.7, 1908.8
8. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND
TECHNIQUES.
X ACI 318:
26.5.3-26.5.5
1908.9
9. INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS OF THE
CONCRETE MEMBER BEING FORMED.
X ACI 318:
26.11.1.2(b)
SUBMIT CERTIFIED MILL TEST REPORTS FOR REINFORCEMENT. X ACI 318:
21.1.5.2
1705.12.1
NOTES:
1. ESR REPORTS CORRESPONDING TO EACH POST-INSTALLED ANCHOR
PRODUCT SHALL BE REVIEWED FOR SPECIAL INSPECTION
REQUIREMENTS. SUCH REQUIREMENTS SHALL BE COMPLETED IN
ACCORDANCE WITH THESE SPECIAL INSPECTION TABLES.
REQUIRED SPECIAL INSPECTIONS OF OPEN-WEB STEEL JOISTS AND JOIST GIRDERS
TYPE CONTINUOUS PERIODIC
REFERENCED
STANDARD
IBC
REFERENCE
1. INSTALLATION OF OPEN-WEB STEEL JOISTS AND JOIST GIRDERS. 1705.2.3
A. END CONNECTIONS - WELDING OR BOLTED X SJI
SPECIFICATIONS
LISTED IN
SECTION 2207.1.
B. BRIDGING - HORIZONTAL OR DIAGONAL
1. STANDARD BRIDGING X SJI
SPECIFICATIONS
LISTED IN
SECTION 2207.1.
2. BRIDGING THAT DIFFERS FROM THE SJI SPECIFICATIONS LISTED
IN SECTION 2207.1.
X
REQUIRED SPECIAL INSPECTIONS OF SOILS
TYPE CONTINUOUS PERIODIC
REFERENCED
STANDARD
IBC
REFERENCE
1. VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE ADEQUATE TO
ACHIEVE THE DESIGN BEARING CAPACITY.
X 1705.6
2. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE
REACHED PROPER MATERIAL.
X 1705.6
3. PERFORM CLASSIFICATION AND TESTING OF COMPACTED FILL
MATERIALS.
X 1705.6
4. VERIFY USE OF PROPER MATERIALS, DENSITIES AND LIFT THICKNESSES
DURING PLACEMENT AND COMPACTION OF COMPACTED FILL.
X 1705.6
5. PRIOR TO PLACEMENT OF COMPACTED FILL, INSPECT SUBGRADE AND
VERIFY THAT SITE HAS BEEN PREPARED PROPERLY.
X 1705.6
NOTES:
1. THE PROJECT GEOTECHNICAL REPORT AND THE CONSTRUCTION
DOCUMENTS PREPARED BY THE ENGINEER OF RECORD SHALL BE USED
TO DETERMINE COMPLIANCE.
2. DURING FILL PLACEMENT, THE SPECIAL INSPECTOR SHALL DETERMINE
THAT PROPER MATERIALS AND PROCEDURES ARE USED IN ACCORDANCE
WITH THE PROVISIONS OF THE GEOTECHNICAL REPORT.
SPECIAL INSPECTION GENERAL NOTES
IBC
REFERENCE
1. REPORT REQUIREMENT 1704.2.4
A. APPROVED AGENCIES SHALL KEEP RECORDS OF SPECIAL INSPECTIONS AND TESTS.
B. THE APPROVED AGENCY SHALL SUBMIT REPORTS OF SPECIAL INSPECTIONS AND TESTS TO THE BUILDING
OFFICIAL AND TO THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE.
C. REPORTS SHALL INDICATE THAT WORK INSPECTED OR TESTED WAS OR WAS NOT COMPLETED IN
CONFORMANCE TO APPROVED CONSTRUCTION DOCUMENTS.
D. DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONTRACTOR FOR CORRECTION. IF THEY ARE NOT CORRECTED, THE DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE BUILDING OFFICIAL AND TO THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
PRIOR TO THE COMPLETION OF THAT PHASE OF THE WORK.
E. A FINAL REPORT DOCUMENTING REQUIRED SPECIAL INSPECTIONS AND TESTS, AND CORRECTION OF ANY DISCREPANCIES NOTED IN THE INSPECTIONS OR TESTS, SHALL BE SUBMITTED AT A POINT IN TIME AGREED UPON PRIOR TO THE START OF WORK BY THE OWNER OR THE OWNER’S AUTHORIZED AGENT TO THE
BUILDING OFFICIAL.
F. SPECIAL INSPECTOR OF RECORD SHALL CONFORM TO THE REQUIREMENTS OF UFC 3-301-01 (01 JUNE 2013)
PARAGRAPH 2-2.3.
2. DEFINITIONS 202
A. CONTINUOUS SPECIAL INSPECTION: SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS PRESENT
CONTINUOUSLY WHEN AND WHERE THE WORK TO BE INSPECTED IS BEING PERFORMED.
B. PERIODIC SPECIAL INSPECTION: SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS INTERMITTENTLY
PRESENT WHERE THE WORK TO BE INSPECTED HAS BEEN OR IS BEING PERFORMED.
3. INSPECTION OF FABRICATORS 1704.2.5
A. SPECIAL INSPECTIONS REQUIRED BY THESE SCHEDULES APPLY TO WORK WHETHER COMPLETED ON SITE
OR ELSEWHERE, SUCH AS AT A FABRICATOR'S SHOP.
B. SPECIAL INSPECTOR SHALL VERIFY THAT FABRICATOR MAINTAINS DETAILED FABRICATION AND QUALITY CONTROL PROCEDURES, AND SHALL REVIEW PROCEDURES FOR COMPLETENESS RELATIVE TO THE CODE
REQUIREMENTS FOR FABRICATOR'S SCOPE OF WORK.
1704.2.5.1
C. SPECIAL INSPECTIONS ARE NOT REQUIRED FOR WORK DONE ON THE PREMISES OF A FABRICATOR REGISTERED AND APPROVED BY THE BUILDING OFFICIAL TO PERFORM SUCH WORK WITHOUT SPECIAL INSPECTION. AT COMPLETION OF FABRICATION, THE APPROVED FABRICATOR SHALL SUBMIT A CERTIFICATE OF COMPLIANCE STATING THAT THE WORK WAS PERFORMED IN ACCORDANCE WITH THE CONSTRUCTION
DOCUMENTS.
1704.2.5.1 1704.2.5.2
4. EXCEPTIONS
A. SPECIAL INSPECTIONS AND TESTS ARE NOT REQUIRED FOR CONSTRUCTION OF A MINOR NATURE OR AS WARRANTED BY CONDITIONS IN THE JURISDICTION AS APPROVED BY THE BUILDING OFFICIAL.
1704.2.1
5. STATEMENT OF RESPONSIBILITY
A. EACH CONTRACTOR RESPONSIBLE FOR THE CONSTRUCTION OF A MAIN WIND- OR SEISMIC
FORCE-RESISTING SYSTEM, DESIGNATED SEISMIC SYSTEM OR A WIND- OR SEISMIC FORCE-RESISTING COMPONENT LISTED IN THE STATEMENT OF SPECIAL INSPECTIONS SHALL SUBMIT A WRITTEN STATEMENT OF RESPONSIBILITY TO THE BUILDING OFFICIAL AND THE OWNER OR THE OWNER’S AUTHORIZED AGENT
PRIOR TO THE COMMENCEMENT OF WORK ON THE SYSTEM OR COMPONENT. THE CONTRACTOR’S
STATEMENT OF RESPONSIBILITY SHALL CONTAIN ACKNOWLEDGEMENT OF AWARENESS OF THE SPECIAL
REQUIREMENTS CONTAINED IN THE STATEMENT OF SPECIAL INSPECTIONS.
1704.4
6. REFERENCE STANDARDS
A. THE SPECIAL INSPECTOR SHALL HAVE AVAILABLE ON THE SITE A COPY OF THE STANDARD DOCUMENTS
REFERENCED FOR EACH TASK BEING INSPECTED.
REQUIRED SPECIAL INSPECTIONS OF HOT-ROLLED STRUCTURAL STEEL
TYPE
FOR EACH
LOCATION PERIODIC
REFERENCED
STANDARD
IBC
REFERENCE
1. PRIOR TO WELDING AISC 360 N5.4
A. WELDING PROCEDURE SPECIFICATIONS (WPS'S) ARE AVAILABLE X AWS D1.1 (6.3)
B. MANUFACTURER CERTIFICATIONS FOR CONSUMABLES ARE AVAILABLE X AWS D1.1 (6.2)
C. MATERIAL IDENTIFICATION (PROPER TYPE/GRADE OF ALL MATERIALS AND
CONSUMABLES)
X AWS D1.1 (6.2)
D. WELDER IDENTIFICATION SYSTEM X AISC 360 N5.4
E. FIT-UP OF GROOVE WELDS X AWS D1.1
(5.10, 5.15, 5.18, 5.22, 6.5.2)
F. CONFIGURATION AND FINISH OF ACCESS HOLES X AWS D1.1
(5.17, 6.5.2)
G
FIT-UP OF FILLET WELDS X AWS D1.1
(5.15, 5.18, 5.22.1)
2. DURING WELDING AISC 360 N5.4
A. USE OF QUALIFIED WELDERS X AWS D1.1 (6.4)
B. CONTROL AND HANDLING OF CONSUMABLES (PACKAGING; EXPOSURE
CONTROL)
X AWS D1.1 (5.3,
6.2)
C. NO WELDING OVER CRACKED TACK WELDS X AWS D1.1
(5.18)
D. ENVIRONMENTAL: WIND SPEED, PRECIPITATION, AND TEMPERATURE
WITHIN LIMITS
X AWS D1.1
(5.12.1, 5.12.2)
E. WELDING PROCEDURE SPECIFICATIONS (WPS) ARE FOLLOWED (SETTINGS
ON WELDING EQUIPMENT; TRAVEL SPEED; SELECTED WELDING
MATERIALS; SHIELDING GAS TYPE/FLOW RATE; PREHEAT APPLIED;
INTERPASS TEMPERATURE MAINTAINED, MIN AND MAX; PROPER
POSITION, F/V/H/OH)
X AWS D1.1 (5.5,
5.6, 5.7, 5.21, 6.3.3, 6.5.2)
F. WELDING TECHNIQUES (INTERPASS AND FINAL CLEANING; EACH PASS
WITHIN PROFILE LIMITATIONS AND MEETS QUALITY REQUIREMENTS)
X AWS D1.1
(5.24, 5.30.1, 6.5.2, 6.5.3)
3. AFTER WELDING AISC 360 N5.4
A. WELDS CLEANED X AWS D.1.1
(5.30.1)
B. SIZE, LENGTH, AND LOCATION OF WELDS X AWS D1.1
(6.5.1)
C. WELDS MEET VISUAL ACCEPTANCE CRITERIA (CRACK PROHIBITION;
WELD/BASE METAL FUSION; CRATER CROSS SECTION; WELD PROFILES;
WELD SIZE; UNDERCUT; POROSITY)
X AWS D1.1 (6.1,
6.5.3)
D. ARC STRIKES X AWS D1.1
(5.29)
E. K-AREA: VISUALLY INSPECT FOR CRACKING IN WEB WITHIN 3" OF WELDS
LOCATED IN K-AREA.
X AISC 360 N5.4
F. BACKING AND WELD TABS REMOVED IF REQUIRED X AWS D1.1
(5.10, 5.31)
G
REPAIR ACTIVITIES X AWS D1.1
(5.26, 6.5.3)
H. DOCUMENT ACCEPTANCE OR REJECTION OF WELDED JOINT OR MEMBER X AWS D1.1
(6.5.4, 6.5.5)
4. NON-DESTRUCTIVE TESTING AISC 360 N5.5
A. CJP GROOVE WELDS: ULTRASONIC TESTING X AWS D1.1,
AISC 360 N5.5b
B. CJP GROOVE WELDS: PROVIDE ULTRASONIC TESTING OF 10% OF WELDS X AWS D1.1,
AISC 360
N5.5b,f
C. ACCESS HOLES: TEST THERMALLY CUT SURFACES OF ACCESS HOLES
WITH MAGNETIC PARTICLE OR PENETRANT TESTING. REJECT ANY CRACK
OF ANY SIZE/LOCATION.
X AISC 360 N5.5c
D. WELDED JOINTS SUBJECTED TO FATIGUE LOADING X AISC 360 N5.5d
5. BEFORE HIGH-STRENGTH BOLTING (PRETENSIONED AND SLIP-CRITICAL)
THIS INSPECTION DOES NOT APPLY TO SNUG-TIGHT JOINTS
A. MANUFACTURER CERTIFICATION FOR FASTENERS IS AVAILABLE X AISC 360 N5.6
B. FASTENERS MARKED IN ACCORDANCE WITH ASTM X AISC 360 N5.6
C. PROPER FASTENERS SELECTED FOR THE JOINT DETAIL X AISC 360 N5.6
D. PROPER BOLTING PROCEDURE SELECTED FOR THE JOINT DETAIL X AISC 360 N5.6
E. CONNECTING ELEMENTS, INCLUDING FAYING SURFACE CONDITION AND
HOLE PREP, MEET REQUIREMENTS
X AISC 360 N5.6
F. PRE-INSTALLATION VERIFICATION TESTING BY INSTALLER OBSERVED AND
DOCUMENTED FOR FASTENER ASSEMBLIES AND METHODS USED
X AISC 360 N5.6
G
PROPER STORAGE FOR BOLTS, NUTS, WASHERS, AND OTHER FASTENER
COMPONENTS
X AISC 360 N5.6
6. DURING HIGH STRENGTH BOLTING (PRETENSIONED AND SLIP-CRITICAL)
THIS INSPECTION DOES NOT APPLY TO SNUG-TIGHT JOINTS
THIS INSPECTION MAY BE PERFORMED AFTER-THE-FACT IF CONDITIONS
OF AISC N5.6 (2) ARE MET.
A. FASTENER ASSEMBLIES, OF SUITABLE CONDITION, PLACED IN ALL HOLES
AND WASHERS POSITIONED AS REQUIRED
X AISC 360 N5.6
B. JOINTS SNUG-TIGHT PRIOR TO PRETENSIONING X AISC 360 N5.6
C. FASTENER COMPONENT NOT TURNED BY WRENCH IS PREVENTED FROM
ROTATING
X AISC 360 N5.6
D. FASTENERS PRETENSIONED PER RCSC SPECIFICATION X AISC 360 N5.6
7. AFTER HIGH-STRENGTH BOLTING
A. DOCUMENT ACCEPTANCE OR REJECTION OF BOLTED CONNECTION X AISC 360 N5.6
NOTES:
1. SPECIAL INSPECTIONS ARE NOT REQUIRED FOR STEEL WORK OF A MINOR
NATURE.
2. SPECIAL INSPECTORS SHALL COMPLETE ALL TASKS ASSIGNED TO
"QUALITY ASSURANCE"/"QA" IN AISC 360 CHAPTER N.
3. SPECIAL INSPECTIONS ARE NOT REQUIRED FOR WORK COMPLETED IN
THE SHOP BY AN AISC CERTIFIED FABRICATOR. THIS DOES NOT RELIEVE
THE FABRICTOR FROM INSPECTIONS REQUIRED BY THE AISC
CERTIFICATION PROGRAM, NOR FROM AISC 360 "QUALITY CONTROL"
INSPECTIONS.
1704.2.5
4. FOR FULLER EXPLANATION OF WELDING STANDARDS FOR INSPECTION,
REFER TO COMMENTARY OF AISC 360.
REQUIRED SPECIAL INSPECTIONS OF MASONRY CONSTRUCTION - LEVEL B
TYPE
CONTINUOU
S PERIODIC
ACI 530
REFERENCE
ACI 530.1
REFERENCE
1. VERIFICATION OF SLUMP FLOW X 1.5B.1.b.3
2. VERIFICATION OF f'm PRIOR TO CONSTRUCTION EXCEPT WHERE
SPECIFICALLY EXEMPTED BY ACI 530/530.1.
X 1.4B
3. VERIFY COMPLIANCE WITH THE REVIEWED SUBMITTALS AND THE
REQUIRED INSPECTION PROVISIONS OF THE CONSTRUCTION
DOCUMENTS.
X 1.5
4. AS MASONRY CONSTRUCTION BEGINS, THE FOLLOWING SHALL BE
VERIFIED TO ENSURE COMPLIANCE:
A. PROPORTIONS OF SITE-PREPARED MORTAR X 2.1, 2.6A
B. CONSTRUCTION OF MORTAR JOINTS X 3.3B
C. LOCATION OF REINFORCEMENT AND CONNECTORS X 3.4, 3.6A
5. PRIOR TO GROUTING, VERIFY THE FOLLOWING TO ENSURE COMPLIANCE:
A. GROUT SPACE X 3.2D, 3.2F
B. GRADE, TYPE, AND SIZE OF REINFORCEMENT AND ANCHOR BOLTS X 1.16 2.4, 3.4
C. PLACEMENT OF REINFORCEMENT AND CONNECTORS X 1.16 3.2E, 3.4,
3.6A
D. PROPORTIONS OF SITE-PREPARED GROUT X 2.6B,
2.4G.1.b
E. CONSTRUCTION OF MORTAR JOINTS X 3.3B
6. VERIFY DURING CONSTRUCTION:
A. SIZE AND LOCATION OF STRUCTURAL ELEMENTS X 3.3F
B. TYPE, SIZE AND LOCATION OF ANCHORS, INCLUDING OTHER DETAILS OF
ANCHORAGE OF MASONRY TO STRUCTURAL MEMBERS, FRAMES OR
OTHER CONSTRUCTION.
X 1.16.4.3, 1.17.1
C. WELDING OF REINFORCING BARS X 2.1.7.7.2,
3.3.3.4.C, 8.3.3.4.B
D. PREPARATION, CONSTRUCTION AND PROTECTION OF MASONRY DURING
COLD WEATHER (TEMPERATURE BELOW 40 DEG F) OR HOT WEATHER
(TEMPERATURE ABOVE 90 DEG F)
X 1.8C, 1.8D
7. PREPARATION OF ANY REQUIRED GROUT SPECIMENS, MORTAR
SPECIMENS, AND/OR PRISMS SHALL BE OBSERVED.
X 1.4B.2.A.3, 1.4B.2.B.3, 1.4B.2.C.3, 1.4B.3, 1.4B.4
NOTES:
1. SPECIAL INSPECTIONS ARE NOT REQUIRED FOR MASONRY WORK OF A
MINOR NATURE.
2. QUALIFICATIONS OF WELDERS MUST BE VERIFIED PRIOR TO THE START
OF THE WORK.
DW DW
B L F+34
BL60F
3 4 5 6 7 83.5 4.5 5.5 6.5
L
K
MM
J
G
H
3.6
6.4
K.8 K.8
K.2 K.2
5.8
20'-0" 20'-0" 20'-0" 20'-0" 20'-0" 20'-0" 20'-0" 20'-0" 20'-0"
12'-9" 7'-3" 19'-3" 9"
F01
F01
F02
F02
F06
F06
F40
F40 F7055
F7055 F45
F45
F03
F03
F03F04
3.2
10'-0"
K.7 2
S-501
S-501
S-501
EXISTING SLAB
CONTROL JOINTS
EXISTING EMBEDED
STEEL BEAM
10'-1 1/2"
F05 F05 F05 F05 F05 F05 F05 F05 F05
F05F05F05F05F05F05F05F05
20'-0"
S-501
A.
B.
C.
REFER TO SHEETS S-001 AND S-002 FOR GENERAL NOTES AND SPECIAL
INSPECTIONS.
REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS NOT SHOWN.
EXISTING CONDITIONS SHOWN ARE BASED ON A COMBINATION OF EXISTING
DRAWINGS AND FIELD MEASUREMENTS. EXISTING CONDITIONS TO BE VERIFIED
BY GENERAL CONTRACTOR PRIOR TO FABRICATION OR CONSTRUCTION.
REPORT ANY DISCREPANCIES TO ENGINEER.
SHEET ID
A
IR
F O
R C
E C
IV
IL
E N
G
IN
E E
R
IN
G C
O M
M A
N D
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A R
C H
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
T A
S K
O R
D E
R N
O
D
C
B
A
D A
T E
File Name:
Plot Date:
M A
R K
D E
S C
R
IP
T
IO
N
E
F
G
H
I
D e s ig n in g B e tt e r
F u tu re s
F O
R C
O N
S T
R U
C T
IO
N
2 3 4 5 6 7 8 9 10 11 12
KEYPLAN
LAB A
H U
T Z
E L
F A
-1
-D
-0
Q
5/10/2019 11:31:36 AM
S-101
F O
U N
D A
T
IO
N P
L A
N
E D
W A
R D
S A
F B
C
A L
IF
O R
N
IA
V E
R S
T
S H
A R
P S
H A
IR
V E
R S
T
M M
-D D
-Y Y
Y Y
05-16-2019 100% SUBMITTAL
643005_Structural_Central_2018.rvt
F S
P M
A
N A
L Y
T
IC
S L
A B
O R
A T
O R
Y A
F R
L B
U
IL
D
IN
G
P R
O J E
C T
N O
-1
1/8" = 1'-0"S-101
01 FOUNDATION PLAN
GENERAL NOTES
N
16'4' 8'
SCALE: 1/8"=1'-0"
DRAWING NOTES
F01 SAWCUT EXISTING 8" THICK SLAB. EXCAVATE 12" OF SLURRY FILL.
CAST NEW FOOTING -8" BELOW FINISH FLOOR. POUR BACK 8"
CONCRETE FLOOR OVER NEW FOOTING.
F02 SAWCUT EXISTING 6" THICK SLAB. EXCAVATE AND CAST NEW FOOTING
-8" BELOW FINISH FLOOR. POUR BACK 8" CONCRETE FLOOR OVER NEW
FOOTING.
F03 EXISTING 6" SLAB ON GRADE.
F04 PER EDWARDS AIR FORCE BASE; LIMITS OF INFILLED PIT. INFILL
CONSISTS OF 22'± OF SLURRY MIX CAPPED WITH AN 8" THICK SLAB
WITH (2) LAYERS OF REINFORCING.
F05 REMOVE STEEL PLATE. INFILL TRENCH WITH LOW DENSITY CONCRETE
FILL TO AND ELEVATION OF 8" BELOW FINISH FLOOR. CAP WITH 8"
CONCRETE. FINISH WITH SMOOTH TROWEL.
F06 SAWCUT EXISTING 6" THICK SLAB. EXCAVATE AND REMOVE EXISTING
FOOTING. CAST NEW FOOTING -8" BELOW FINISH FLOOR. POUR BACK 8"
CONCRETE FLOOR OVER NEW FOOTING.
COLUMN FOOTING SCHEDULE
MARK
DIMENSIONS REINFORCING
REMARKSWIDTH LENGTH DEPTH
TRANSVERSE LONGITUDINAL
QUANTITY SIZE QUANTITY SIZE
F40 4' - 0" 4' - 0" 1' - 0" 6 #4 6 #4
F45 4' - 6" 4' - 6" 1' - 0" 6 #4 6 #4
F7055 5' - 6" 7'…