02 July 2018
ADDENDUM N. 0001 TO THE SCOPE OF WORK/PERFORMANCE WORK
SCHEDULE OF PROJECT ES-00272-7P, Repair water system bldg. 5893, S&M Area -
DMC
1. SCOPE OF WORK, Phase 1 (Design) Description Paragraph Architectural/Structural works:
After the sentence “A new prefabricated room to house all the new water treatment equipment, guaranteeing the necessary maintenance space” add the following: “The new technical room shall have dimensions no less than 240x300x240 (h) cm.. It will consist of a galvanized steel supporting structure. The walls and the cover will be in modular panels of galvanized steel type self-supporting sandwich thermally insulated with polyurethane resin, minimum thickness
50 mm. PVC floor. The windows will be aluminum, with glasses and external protection bars.
The access door will have dimensions not less than 120x210 cm. The room will be equipped with an exterior type IP55 electrical system, inclusive of general lighting and LED type emergency lighting. It will be provided of 4 P40 service outlets. It will be provided with a panel dedicated to the equipment in the technical room. Each piece of equipment must be provided with a dedicated switch. It will be equipped with suitable support structures for the installed equipment.”
PAOLO SERRAGLINI, PE
Chief, Engineering Services Branch
| 2018-07-03T15:17:43+0200 | |
| SERRAGLINI.PAOLO.1465880569 |