W912PA-16-T-0052
Questions/Anwers – Site Visit – 8 September 2016.
QUESTIONS ANSWER
1. What type of lock has to be installed on the blast resistant doors?
The blast resistant doors have to be equipped with an electric safety lock multi-point type and anti-panic function, compatible with the existing badge reader systems.
2. Are ventilation grills to be installed on metallic doors of electrical substations?
Paragraph "g" in TP-2-02 of specifications shall not be taken into consideration. The installation of ventilation grills are no longer required on metallic doors of electrical substations.
An amendment to the solicitation will be issued.