AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
Reference Solicitation No. W912P8-17-B-0007 New Orleans to Venice hurricane Protection Project, NOV-NF-W-06b.1 Woodpark Floodw alls, Plaquemines Parish, Louisiana. The subject solicitation is amended as follow s:
See continuation page for changes.
1. CONTRACT ID CODE PAGE OF PAGES
J 1 2
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 22-Dec-2016
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W912P8-17-B-0007
X 9B. DATED (SEE ITEM 11)
09-Nov-2016
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
22-Dec-2016
CODE
USACE, CONTRACTING DIVISION
ATTN: HPO CT VICKSBURG
4155 CLAY STREET
VICKSBURG MS 39183-3435
W912P8 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
SECTION 33 11 00
Page 11, paragraph 3.1.1.1. Delete this paragraph in its entirety, and substitute the following therefore: “3.1.1.1 Reserved”.
DRAWINGS
SHEET IDENTIFICATION Nos. S-205 and E-103. Delete these drawings in their entirety and substitute the attached revised SHEET IDENTIFICATION Nos. S-205 and E-103 therefore.
S-205
H S -2 d g n
O
F
S E
C T
IO
N S A
N D D
E T
A
IL
S T
Y P
IC
A L M
O N
O L
IT
H R
E B
A R
-1
-2
R D
R
E V
IS
E D D
E T
A
IL
S
NEW ORLEANS DISTRICT
S O
L
IC
IT
A T
IO
N N
O
F
IL
E N
A M
E
D W
N B
Y
C K
D B
Y
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
D
2 3
C
4 5
A
B
M A
R K
A P
P R
D A
T E
F
IL
E N
U M
B E
R
S
IZ
E
S U
B M
IT
T E
D B
Y
P L
O T S
C A
L E
P L
O T D
A T
E
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
C O
N T
R A
C T N
O
IDENTIFICATION
SHEET
D A
T E
A P
P R
®of Engineers
US Army Corps
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R S
N E
W O
R L E
A N
S D
IS
T R
IC
T
N E
W O
R L E
A N
S L
O U
IS
IA
N A
P L
A Q
U E
M
IN
E S P
A R
IS
H L
O U
IS
IA
N A
A N
S I
D
H -4 -4
X
N O
T E
D
H U
R R
IC
A N
E P
R O
T E
C T
IO
N S
Y S
T E
M
R O
B D
A U
E N
H A
U E
R P .E
A G
W N
O V -N
F -W
-0
B .1 W
O O
D P
A R
K F
L O
O D
W A
L L S
D M
E /S
D C
W
S E
P T
E M
B E
R
O C
T
W P -1
-B -0
S-204
HAIR PIN DETAIL
" = 1'-0"4
3SCALE:
SEE "TYPICAL MONOLITH CROSS SECTIONS" FOR REBAR SPACING.
1. ALL OTHER REBAR OMITTED FOR CLARITY.
NOTE:
STEEL SHEET PILING
1'-6"10"
AS REQ'D.
PILING, ROTATE
STEEL SHEET
EACH PIECE OF
HAIR PIN FOR
ONE NO. 7
SLAB BOTTOM
SLAB TOP
HANDLING HOLE
THROUGH EXISTING
PLACE HAIR PIN
AS POSSIBLE
AS CLOSE TO CENTER
TERMINATE ABOVE PILE
CROSS-SECTION
EQ. SPC.
CROSS-SECTION
TYPICAL REBAR LAYOUT - PI MONOLITHS
N.T.S.
EQ. SPC.
SPACING AS PER SPACING AS PER
CROSS-SECTION
SPACING AS PER
CROSS-SECTION SPACING AS PER
" = 1'-0"2
1SCALE:
18" O.D. PIPE PILES
T-WALL
WATER LINE
12" DUCTILE IRON PIPE
PL 1/2" X 3"
12-INCH WATER LINE PENETRATION DETAIL
PL 1" X 4'-6" X 4'-6" (CRS).
4 3/4" MIN. EMBED, EQUALLY SPACED (CRS).
WITH NUTS AND WASHERS,
4 -3/4" DIA. THREADED RODS INSERTS
PL 1/2" X 2" (CRS) (TYP.)
PIPE SADDLE CLAMP
PROTECTED SIDE FLOOD SIDE
NON-METALLIC GROUT
VOID W/ NON-SHRINK
AFTER SETTING PIPE FILL
OR PRESSURE TREATED LUMBER
4" PIPE SUPPORT REDWOOD
OR PRESSURE TREATED LUMBER
4" PIPE SUPPORT REDWOOD
" = 1'-0"2
1SCALE:
WATER LINE FLOOD SIDE DETAIL
1'-0"
8"
TOP OF SLAB
4 3/4" MIN. EMBED.
3/4" DIA. ANCHOR BOLT (CRS),
PL 1/2" X 2" (CRS)
PIPE SADDLE CLAMP
4 3/4" MIN. EMBED, EQUALLY SPACED (CRS).
WITH NUTS AND WASHERS,
4 -3/4" DIA. THREADED RODS INSERTS
PL 1" X 4'-6" X 4'-6" (CRS).
6 - #6 BARS EQ. SP.
#5 BARS 8" O.C. (TYP.)
OR PRESSURE TREATED LUMBER
4" X 4'-6" PIPE SUPPORT REDWOOD
WATER LINE
12-INCH DUCTILE IRON PIPE
EL. -1.2
W/STD. HOOKS
#8 @ 10" O.C., NO. 7 BAR @ 12" (TYP.)
#8 @ 10" O.C., NTS
PIPE PENETRATION THRU STEM REINFORING DETAIL
X 3"2
1PL
EL. 16.75
EL. 3.0 TOP OF SLAB
TYPICAL WALL PENETRATION
NTS
X 3"2
1PL
NO. 4 BAR WITH 1' LAP (TYP.)
2'-0"
ALL AROUND
2"x6" KEYWAY
NON-METALLIC GROUT
VOID W/ NON-SHRINK
AFTER SETTING PIPE FILL
12-INCH WATER LINE
NEW ORLEANS DISTRICT
O
L
IC
IT
A T
IO
N N
O
F
IL
E N
A M
E
D W
N B
Y
C K
D B
Y
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
D
2 3
C
4 5
A
B
M A
R K
A P
P R
D A
T E
F
IL
E N
U M
B E
R
S
IZ
E
S U
B M
IT
T E
D B
Y
P L
O T S
C A
L E
P L
O T D
A T
E
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
C O
N T
R A
C T N
O
IDENTIFICATION
SHEET
D A
T E
A P
P R
®of Engineers
US Army Corps
U .S
A R
M Y C
O R
P S O
F E
N G
IN
E E
R
N E
W O
R L E
A N
S D
IS
T R
IC
T
N E
W O
R L E
A N
S L
O U
IS
IA
N A
P L
A Q
U E
M
IN
E S P
A R
IS
H L
O U
IS
IA
N A
A N
S I
D
H -4 -4
X
N O
T E
D
H U
R R
IC
A N
E P
R O
T E
C T
IO
N S
Y S
T E
M
R O
B D
A U
E N
H A
U E
R P .E
A G
W N
O V -N
F -W
-0
B .1 W
O O
D P
A R
K F
L O
O D
W A
L L S
D M
E /S
D C
W
S E
P T
E M
B E
R
O C
T
W P -1
-B -0
SERVICE POLE DETAIL
SCALE: NONE
FINISH GRADE
CONDUIT AND
WEATHERHEAD
MORE THAN 36" APART
AS REQUIRED, BUT NO
CONDUIT STRAPS SPACED
M
METER PAN. COORDINATE WITH ENTERGY.
4 FT. MINIMUM BURIAL
6" NIPPLE
BEYOND WEATHERHEAD.
PROVIDE MINIMUM 3' OF EACH CONDUCTOR
240/120 VOLT, SINGLE PHASE SERVICE.
A RING.
SPACED 10' APART TO FORM
(3) 3/4"x10' COPPER RODS
6' MAX.
STEEL ENCLOSURE
NEMA 4X STAINLESS
SCALE: NONE
STEEL ENCLOSURE
NEMA 4X STAINLESS
SCALE: NONE
2'-0"
FLOODWALL LIGHTING PROFILE
DETAIL THIS SHEET
REFERENCE MOUNTING
SCALE: NONE
MOUNTING DETAIL
ELEVATION
PLAN
T
Y P
1" (TYP.)
TOP OF WALL
3/16
3 1/2" STAINLESS STEEL CONDUIT
PLATE AND CONCRETE
1/8" NEOPRENE PAD BETWEEN
3/8" STAINLESS STEEL PL.
TOP OF WALL
BOLTS (TYP.) (SEE NOTE)
3/8" Ø STAINLESS STEEL
3/4" ELECTRICAL CONDUIT
EL. 3.0
EL. 16.75
PROTECTED SIDE
FLOOD SIDE
FLOOD SIDE
PROTECTED SIDE
2'-0"
EL. 3.0
EL. 16.75
MORE THAN 36" APART
AS REQUIRED, BUT NO
CONDUIT STRAPS SPACED
WITH 2"x2" SQUARE WASHER
1/2" GALVANIZED EYEBOLT
1" RGS
1" RGS
1'-0"
SERVICE HEAD
RAINTIGHT
GOOSENECK WITH
POLE
SERVICE
TO
TO FLOODWALL
WITH 2"x2" SQUARE WASHER
1/2" GALVANIZED EYEBOLT
1" RGS
1" SCHEDULE 80 PVC
UTILITY POLE
TO ENTERGY
24"
RGS CONDUIT ABOVE GRADE
TRANSITION FROM PVC TO
FLOODWALL SERVICE DETAIL (MONOLITH M21)
M30, M35, MPI-4 AND M44
MPI-3, M6, M10, M13, M19, M24,
LIGHTS FIXTURES INSTALLED -
NOTE: THE FOLLOWING MONOLITHS HAVE
NOTE: BOLT EMBEDMENT SHALL BE AT LEAST 2 1/2"
6 AWG
SERVICE GROUND
EMBEDDED IN FLOODWALL
3/4" ELECTRICAL PVC CONDUIT
PHOTOCELL
4XSS ENCLOSURE
30A HEAVY DUTY FDS, FUSED AT 20A IN NEMA
E-103
H E -1
-d g n
E L E
C T
R
IC
A L D
E T
A
IL
S
R
D -1
-2
R E
V
IS
E D D
E T
A
IL