Pre Bid Questions and Answers
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| W912LR-18-B-5009.pdf | ||
| ACM_in_Base_Bid.pdf | ||
| 3._SOW_-_TVAD182202.pdf | ||
| 2._PWS_TVAD182202.pdf | ||
| W912LR-18-B-5009_Pre-Bid_Conference_Slides.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. In Building #1, indicate that we are going to work on the impacted áreas. Please confirm if only the affected areas will be removed or all the existing sealant will be removed and the entire specification will be worked with section 07 57 13. Please clarify, since roof sealing companies will not be able to give a guarantee if only repairs are made in certain areas. Only isolated/afected areas are requested on SOW.
2. According to the SOW in building # 2, according to the wording indicates that only work will be done on the roof that has the solar systems supports, since the high ceiling is being worked by another contractor and the low and medium roof had no liqueos in the inspection carried out by you. However, during the visit to the field we noticed that the mid-height roofs has affected areas.
Please clarify what works will be part of this proposal in the area of the roofs of building # 2. Present proposal as per Appendix A purple área on high roof only.
3. In the SOW the works inside building # 2, are very general, both in the electrical part, as in the floors and walls, please be more specific so that we all go on equal terms. See page 16 for required área and asume all swthches and receptacles need to be change
4. In the SOW of Building # 2 indicates that we must with the HVAC system, please provide more information and have a map of this area, please submit it. Question not clear. Map i son page 16 of SOW with location of HVAC systems.
5. Please confirm that the works indicated in the SOW of building # 6 will not be part of this proposal, as indicated on the site visit.
Do not include as part of proposal
6. In the SOW in Building # 16 indicate in item # 7 of page # 5 that a 2 "x6" should be installed around the perimeter of the roof, please indicate what is the purpose of this work ?. For the new flashing to be instaled around the building
7. In the SOW in Building # 16, indicate in item # 17 page # 9, that 3 stair treads should be replaced, however in the site visit there were no broken ones, please confirm if this item applies for the proposal or it is eliminated. Include
8. On the site visit we observed the posts of the perimeter, where it was noted that they lacked many lamps, however the poles were installed. Please indicate if any of them should be replaced, or only what is observed in the field such as lamps, brackets, etc. Only what is missing ans if the pole was falling it needs to be replaced or brought to a level ans secure position.
9. In the diesel tank we observed that the angle that supports the grills at their edges are corroded, should be considered the replacement of these grills?. In addition it was observed that the beams perpendicular to these angles are also affected, please indicate if they also have to be replaced? Yes, they need to be replaced
10. Please indicate if the grills in the area of the diesel tank have to be replaced or reused. If they are corroded they need to be replaced.