TWLR129077a_RIANG_Flight_Sim_Mod-B-3_Final_Drawings.pdf
PDF 5 MB Posted
- Attached to
- Simulator Upgrade Facility Federal contract opportunity
- Solicitation number
- W912LD19R5000
About this file
Drawings for Simulator Upgrade
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| W912LD-19-R-5000-0003.docx | DOCX document | |
| W90FYQ-10-D-0008_RIANG_Flight_Sim_MODS-_Bidder_Inquiries_-6-11_2019.xlsx | XLSX spreadsheet | |
| Simulator_Upgrade_RFis_answered_6-10-19.xlsx | XLSX spreadsheet | |
| W912LD-19-R-5000-0002.docx | DOCX document | |
| W912LD-19-R-5000_Simulator_Upgrade_RFP.docx | DOCX document | |
| TWLR129077a_RIANG_Flight_Sim_Mod-B-3_Final_Specs.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5801 Broadway Extension, Suite 500 Oklahoma City, OK 73118-7436
405.840.2931 | fsb-ae.com
R
IC
HARD S . JOHNSO
N
A
R C H I T E CT
R
EG I ST EREDH O P E
STATE OF
R HOD E I S L A N D
3 9 4 6
H O P E
STATE OF
RHOD E IS L AND
JOHN T. LITTLE
No. 10037
REGISTERED
PROFESSIONAL ENGINEER
ELECTRICAL
H O P E
STATE OF
RHOD E IS L AND
GARY W. JAMES
No. 10167
REGISTERED
PROFESSIONAL ENGINEER
MECHANICAL
RHODE ISLAND
CERTIFICATE OF
AUTHORIZATION
ARC. 0020065-COA
EXP. 12/31/18
RHODE ISLAND
CERTIFICATE OF
AUTHORIZATION
P.E: # 0008029-COA
EXP. 06/30/2020
Rhode Island Air National Guard United States Property & Fiscal Office
Simulator Facility Modifications North Kingstown, RI
TYPE B-3 - FINAL DESIGN SUBMISSION
NOVEMBER 12, 2018
ACT ACOUSTICAL CEILING TILE
ADA AMERICANS WITH DISABILITIES ACT
ADAAG ADA ACCESSIBILITY GUIDELINES
AFF ABOVE FINISH FLOOR
AHU AIR HANDLING UNIT
ALT ALTERNATE
ALUM ALUMINUM
ANSI AMERICAN NATIONAL STANDARDS
INSTITUTE
BO BOTTOM OF
BOT BOTTOM
BRG BEARING
BS BOTH SIDES
BTWN BETWEEN
CAB CABINET
CFMF COLD-FORMED METAL FRAMING
CG CORNER GUARD
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
CORR CORRIDOR
CPT CARPET
CTB CERAMIC TILE BASE
CWT CERAMIC WALL TILE
CTR CENTER
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION
DEPT DEPARTMENT
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DISP DISPENSER
DN DOWN
DR DOOR
DS DOWNSPOUT
DET DETAIL
DWG DRAWING
EA EACH
EIFS EXTERIOR INSULATION &
FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC (OR) ELECTRICAL
ELEV ELEVATOR
EQ EQUAL
EQUIP EQUIPMENT
EW EACH WAY
EXIST EXISTING
EXT EXTERIOR
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FF EL FINISH FLOOR ELEVATION
FG FINISHED GRADE
FLR FLOOR
FLUOR FLUORESCENT
FR FIRE RESISTIVE
FT FOOT (OR) FEET
FURG FURRING
GA GAGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GDR GUARD RAIL
GEN GENERAL
GL GLASS
GRD GRADE
GYP BD GYPSUM BOARD
HM HOLLOW METAL
HORIZ HORIZONTAL
HT HEIGHT
HVAC HEATING, VENTILATING, &
AIR CONDITIONING
ID INSIDE DIAMETER
INSUL INSULATE (OR) INSULATION
INT INTERIOR
JAN JANITOR
K NOT USED
LAM LAMINATE
LAV LAVATORY
LIN LINEAR
LOC LOCATION
LTG LIGHTING
LVR LOUVER
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MIRR MIRROR
MISC MISCELLANEOUS
MO MASONRY OPENING
MTD MOUNTED
MTL METAL
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NOM NOMINAL
NRC NOISE REDUCTION COEFFICIENT
NTS NOT TO SCALE
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED
CONTRACTOR INSTALLED
OFOI OWNER FURNISHED
OWNER INSTALLED
OPH OPPOSITE HAND
ORD OVERFLOW ROOF DRAIN
OVHD OVERHEAD
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PLYWD PLYWOOD
PR PAIR
PRCST PRECAST
PREFAB PREFABRICATED
PT PAINT (INTERIOR)
PVC POLYVINYL CHLORIDE
QTF QUARRY TILE FLOOR
QTB QUARRY TILE BASE
QTY QUANTITY
R RADIUS (OR) RISER
RB RESILIENT BASE
RD ROOF DRAIN
REC RECESSED
REF REFERENCE (OR) REFRIGERATOR
REQD REQUIRED
REV REVISION
RF RESILIENT FLOORING
RM ROOM
RO ROUGH OPENING
SECT SECTION
SF SQUARE FOOT
SHTHG SHEATHING
SIM SIMILAR
SPEC SPECIFICATION(S)
SST STAINLESS STEEL
STC SOUND TRANSMISSION CLASSIFICATION
STD STANDARD
STL STEEL
STRUCT STRUCTURAL (OR) STRUCTURE
T TREAD
T&B TOP AND BOTTOM
TBD TO BE DETERMINED
TD TOWEL DISPENSER
TO TOP OF
TOC TOP OF CONCRETE
TOJ TOP OF JOIST
TOM TOP OF MASONRY
TOS TOP OF STEEL
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WOOD
WH WALL HYDRANT (OR) WATER HEATER
XFMR TRANSFORMER
Y NOT USED
Z NOT USED
ARCHITECTURAL ABBREVIATIONS
GROUND FLOOR PLAN
SCALE:1/8"=1'-0"
A401
A - 101
DRAWING TYPES LEGEND
1 - PLANS (HORIZONTAL VIEWS)
2 - ELEVATIONS (VERTICAL VIEWS)
3 - SECTIONS (SECTIONAL VIEWS)
4 - ENLARGED VIEWS (PLANS, ELEVATIONS OR SECTIONS THAT ARE NOT DETAIL VIEWS)
5 - DETAILS
6 - SCHEDULES & DIAGRAMS
DISCIPLINE TYPE (ARCHITECTURE SHOWN)
DRAWING TYPE (PLAN, ELEVATION, ETC.)
SERIES NUMBER
DETAIL CALLOUT
ENLARGED PLAN OR DETAIL
ON SHEET INDICATED
A201
INTERIOR ELEVATION CALLOUT
ARROWS INDICATE INTERIOR
ELEVATION ON SHEET
INDICATED
STRUCTURAL GRIDS
AS INDICATED ON
DRAWINGS
A
BUILDING SECTION CALLOUT
ARROWS INDICATE BUILDING
SECTION ON SHEET INDICATED
A301
WALL SECTION CALLOUT
ARROW INDICATE WALL SECTION ON
SHEET INDICATED
A302
ROOM NAME
ROOM NAME & NUMBER SYMBOL
REFER TO ROOM FINISH SCHEDULE
ON SHEET AE601
101A
DOOR NUMBER SYMBOL
REFER TO DOOR SCHEDULE
SHEET AE601
PARTITION TYPE SYMBOL
REFER TO PARTITION TYPES
ON SHEET AE602
GLAZING TYPE SYMBOL
REFER TO GLAZING TYPES
ON SHEET AE601
A
AL1
REVISION SYMBOL
REFER TO SHEET BORDER FOR
REVISION HISTORY
ELEVATION DATUM SYMBOL
INDICATES DATUM ELEVATION AS
INDICATED
1 Bottom Text Top Text
DISCIPLINE MODIFIER (ELEMENTS SHOWN)
ARCHITECTURAL ANNOTATION SYMBOLS LEGEND
D3
PLAN DRAWING TITLE
BUILDING SECTION
SCALE:1/8"=1'-0"
ALL OTHER DRAWING TITLES
SOLID BLACK NORTH
ARROW INDICATES
PLAN NORTH FOR EACH
SPECIFIC PLAN. TRUE
NORTH IS INDICATED
WITH DASHED ARROW.
A301
EXTERIOR ELEVATION CALLOUT
ARROW INDICATE ELEVATION ON
SHEET INDICATED
A201
D3
PLAN
NORTH
0 4' 8' 16'
1/8" = 1'-0"
0 4' 8' 16'
1/8" = 1'-0"
Br oa dw ay
Ex ten sio n, Su ite
Ok lah om aC ity ,O
K
8-
5.8
.29
|fs b-ae
.co m
D A
TE
SI
M
UL
AT
OR
FA
CI
LI
TY
M
OD
IF
IC
AT
IO
NS
UN
ITE
DS
TA
TE
SP
RO
PE
RT
Y&
FIS
CA
LO
FF
ICE
,N
OR
TH
KIN
GS
TO
WN
,R I
AI
R
NA
TI
ON
AL
GU
AR
D rd
A
IR
L
IF
T W
IN
G
RH
OD
E
IS
LA
ND
TY
PE
B- 3-
FI
NA
L
DE
SI
GN
SU
BM
IS
SI
ON
DRAWING NO.
TWLR182167
P R
O
JE
C T
TI
TL
E:
S U
B M
IT
TA
L
LE
V E
L:
MAJ. KATHLEEN MAHONEY
PROJECT NO.
BASE ENGINEER:
NOVEMBER 12, 2018
DATE:
DRAWN BY:
S H
EE
T
TI
TL
E
S A F E
TY
B C E
U S E R
F
IR
E
E N V
IR
O
C O O R D
IN
A
TI
O N
S
IG
N A
TU
R E S
S E C U R
IT
Y
C O M M
R E V
IS
IO
N
M A R K
D A
TE
CHECKED BY:
APPROVED BY:DRAWN BY:
R
IC
HARD S . JOHNSO
N
A
R C H I T E CT
R
EG I ST EREDH O P E
STATE OF
R HOD E I S L A N D
3 9 4 6
/5
/2
8:
:2
A
M C
:\U se rs \d ap \D oc um en ts
\M y
R ev it\
0_
A rc h_ dp al m er
FS
H H
P.
rv t
G-001
SH
EE
T
IN
DE
X, AB
BR
EV
IA
TI
O
NS
SY
M
BO
LS
JMIDAP
DAP JMI
SHEET INDEX
SHEET NUMBER TITLE
GENERAL
G-000 COVER SHEET
G-001 SHEET INDEX, ABBREVIATIONS & SYMBOLS
G-101 CODE COMPLIANCE PLAN
ARCHITECTURAL
AD101 GROUND FLOOR DEMOLITION PLAN
A-101 GROUND FLOOR PLAN
A-102 REFLECTED CEILING PLAN
A-103 DOOR SCHEDULE, DOOR & FRAME TYPES, DETAILS & PARTITION TYPE
A-104 SIGNAGE FLOOR PLAN, SIGNAGE SCHEDULE & DETAILS
FIRE PROTECTION
FX101 FIRE SUPPRESSION PLAN
FA101 FIRE ALARM PLAN
FA601 FIRE ALARM & MASS NOTIFCATION INPUT/OUTPUT MATRIX
PLUMBING
P-101 GROUND FLOOR PLUMBING PLAN
MECHANICAL
MD101 MECHANICAL DEMOLITION
MH101 HVAC PLAN
MP101 PIPING PLAN
M-401 ENLARGED MECHANICAL PLAN
M-501 DETAILS
M-601 FLOW DIAGRAM
M-602 FLOW DIAGRAM
M-701 SCHEDULES AND CONTROLS
ELECTRICAL
E-001 LEGEND AND ABBREVIATIONS
ED101 GROUND FLOOR DEMO PLAN
EP101 GROUND FLOOR POWER PLAN
EP102 POWER DETAILS
ET101 SECURITY AND TELECOMMUNICATIONS PLAN
R
EF
UP
EXISTING STC RATED PARTITION - MINIMUM 45
LIFE SAFETY AND
STC LEGEND
OCCUPANT LOAD NUMBER AT EXIT
COMPONENT
EXIT COMPONENT MAXIMUM OCCUPANT
CAPACITY NUMBER
FIRE EXTINGUISHER
CONTRACTOR FURNISHED / CONTRACTOR
INSTALLED
MAX. TRAVEL DISTANCE TO FIRE EXT. = 50'
STC EXIT ACCESS TRAVEL DISTANCE -
"B" OCCUPANCY IS 300 FT IN
SPRINKLERED BUILDING. TABLE
1016.1 IBC 2009
200'X
DEAD END CORRIDORS -
THE LENGTH IN "B" OCCUPANCY IS
MAX 50 FT. TABLE 1017.3 IBC 200920'X
OCCUPANT LOAD AGGREGATE
ALONG EXIT PATH
OCCUPANT LOAD INTO CORRIDOR
EGRESS PATH
FEC
EXISTING 1-HR RATED PARTITION1-HR
NEW STC RATED PARTITION - MINIMUM 45NEW STC
E E
D.1D.1
DD
CC
BB
A.9A.9
B.1B.1
AA
FEC
FEC
EXISTING BRACKET MOUNTED
MULTI-PURPOSE
FIRE EXTINGUISHER
FEC
RELOCATED SEMI-RECESSED
CABINET MOUNTED MULTI-
PURPOSE FIRE EXTINGUISHER
EXISTING SEMI-RECESSED
CABINET MOUNTED MULTI-
PURPOSE FIRE EXTINGUISHER
TR
AV
EL
D
IS
TA
N C
E
'-1
FE
C
EXISTING SURFACE
CABINET MOUNTED
CLEAN AGENT FIRE
EXTINGUISHER
TRAVEL DISTANCE 83'-9"
2 2
2 2
ST
C
ST
C
STC STC
STC
ST
C
1- H
R
1-HR
ST
C
1- H
R
1- H
R
ST
C
ST
C
1- H
R
ST
C
STC 1-HR STC 1-HR
ST
C
1- H
R
ST
C 1-
H R
ST
C
ST
C
STC
INSTRUCTOR'S
OPEN OFFICE
BREAK
STOR
MENS
305A WOMENS
305B
CBT/CPT
FIRE PROT
BRIEFING
RIOS
LMPTT ROOM
COR OFFICE
ADMIN
SITE MGR
MULTI-PURPOSE
STOR
206A
STOR
206B
COPY
VEST
CORRIDOR
COMPUTER
ROOM
MAINT
OFFICE
DEBRIEFING
MAINT
SUPPORT
SIM MOTION
BAY
ELEC
COMPRESSOR
ROOM
COMM
MECH
1-HR
1-HR
PROVIDE UL SYSTEM C-
AJ-1429 IN TRENCH
BENEATH RATED WALL
1-HR
1- H
R 1-
H R
VEST
FE
C
EXISTING SURFACE
CABINET MOUNTED
CLEAN AGENT FIRE
EXTINGUISHER
STC
ST
C
ST
C
ST
C
NEW STC
N
EW
S
TC
TR
AV
EL
D
IS
TA
N C
E
2' -3
CORRIDOR
TRAVEL DISTANCE 115'-2"
Br oa dw ay
Ex ten sio n, Su ite
Ok lah om aC ity ,O
K
8-
5.8
.29
|fs b-ae
.co m
D A
TE
SI
M
UL
AT
OR
FA
CI
LI
TY
M
OD
IF
IC
AT
IO
NS
UN
ITE
DS
TA
TE
SP
RO
PE
RT
Y&
FIS
CA
LO
FF
ICE
,N
OR
TH
KIN
GS
TO
WN
,R I
AI
R
NA
TI
ON
AL
GU
AR
D rd
A
IR
L
IF
T W
IN
G
RH
OD
E
IS
LA
ND
TY
PE
B- 3-
FI
NA
L
DE
SI
GN
SU
BM
IS
SI
ON
DRAWING NO.
TWLR182167
P R
O
JE
C T
TI
TL
E:
S U
B M
IT
TA
L
LE
V E
L:
MAJ. KATHLEEN MAHONEY
PROJECT NO.
BASE ENGINEER:
NOVEMBER 12, 2018
DATE:
DRAWN BY:
S H
EE
T
TI
TL
E
S A F E
TY
B C E
U S E R
F
IR
E
E N V
IR
O
C O O R D
IN
A
TI
O N
S
IG
N A
TU
R E S
S E C U R
IT
Y
C O M M
R E V
IS
IO
N
M A R K
D A
TE
CHECKED BY:
APPROVED BY:DRAWN BY:
R
IC
HARD S . JOHNSO
N
A
R C H I T E CT
R
EG I ST EREDH O P E
STATE OF
R HOD E I S L A N D
3 9 4 6
/5
/2
8:
:5
A
M C
:\U se rs \d ap \D oc um en ts
\M y
R ev it\
0_
A rc h_ dp al m er
FS
H H
P.
rv t
G-101
CO
DE
CO
M
PL
IA
NC
E
PL
AN
JMIDAP
DAP JMI
SCALE: 3/16" = 1'-0"
1 CODE PLAN 4' 12'8'0
3/16" = 1'-0"
CODE ANALYSIS
1.0 SECTION USE AND OCCUPANCY IBC 2012 CHAP 3
INDIVIDUAL CLASSIFICATION OF OCCUPANCIES:
STORAGE- GROUP S-2 (SECTION 311.3)
BUSINESS- GROUP B (SECTION 304.1)
CODE ANALYSIS BASED ON NONSEPARATED MIXED
USED OCCUPANCY USING THE MOST RESTRICTIVE
OCCUPANCY CLASSIFICATION S-1 (508.3)
1.4 TABLE 1014.3 COMMON PATH EGRESS TRAVEL
FOR STORAGE OCCUPANCY WITH SPRINKLER
SYSTEM 100 FT IS REQUIRED.
ACTUAL MAX. LENGTH IS 38 FT.
1.5 TABLE 1016.2 EXIT ACCESS TRAVEL DISTANCE
FOR STORAGE OCCUPANCY WITH SPRINKLER
SYSTEM 250 FT IS REQUIRED.
ACTUAL MAX. LENGTH IS 122'-3".
1.6 SECTION 1018.4 DEAD ENDS
FOR BUSINESS & STORAGE OCCUPANCIES 50
FT IS MAX. LENGTH.
ACTUAL - NO DEAD END CORRIDORS.
1.1 BUILDING TYPE IIB (TABLE 601) W/ SPRINKLER
SYSTEM 1.7 TABLE 602 FIRE SEPARATION DISTANCE
30 FT MINIMUM IS EXCEEDED. FIRE RATING OF
EXTERIOR WALLS NOT REQUIRED.
1.2 ALLOWABLE HEIGHT (504.2 & TABLE 503) AND
BUILDING AREA (506) FOR NONSEPARATED
OCCUPANCY USING THE MOST RESTRICTIVE
OCCUPANCY CLASSIFICATION S-1
I. ALLOWABLE BUILDING HEIGHT- 75 FT., 3 STORIES
-ACTUAL BUILDING HEIGHT: 63'-1". 1 STORY,
THEREFORE OK
II. ALLOWABLE BUILDING AREA - 17,500 SF
FRONTAGE INCREASE: 0 SF.
-17,500 x 3 = 52,500 SF TOTAL ALLOWABLE AREA
-ACTUAL BUILDING AREA:
10,638 SF, THEREFORE OK.
OCCUPANCY CLASSIFICATION B
I. ALLOWABLE BUILDING HEIGHT- 75 FT., 1 STORIES
-ACTUAL BUILDING HEIGHT: 16'-0". 1 STORY,
THEREFORE OK
II. ALLOWABLE BUILDING AREA - 92,000 SF
FRONTAGE INCREASE: 0 SF.
-92,000 x 2 = 184,000 SF TOTAL ALLOWABLE AREA
-ACTUAL BUILDING AREA:
4,228 SF, THEREFORE OK.
1.4 TABLE 1014.3 COMMON PATH EGRESS TRAVEL
FOR BUSINESS OCCUPANCY WITH SPRINKLER
SYSTEM 100 FT IS REQUIRED.
ACTUAL MAX. LENGTH IS 38 FT.
1.5 TABLE 1016.2 EXIT ACCESS TRAVEL DISTANCE
FOR BUSINESS OCCUPANCY WITH SPRINKLER
SYSTEM 300 FT IS REQUIRED.
ACTUAL MAX. LENGTH IS 100'-7".
BUILDING CODES AND STANDARDS:
• SBC-1 RHODE ISLAND BUILDING CODE,
INCORPORATES IBC 2012 EDITION
• INTERNATIONAL FIRE CODE 2012
• SBC-4 RHODE ISLAND STATE MECHANICAL CODE,
INCORPORATES INTERNATIONAL MECHANICAL CODE
2012 EDITION
• SBC-3 RHODE ISLAND STATE PLUMBING CODE,
INCORPORATES INTERNATIONAL PLUMBING CODE
2012 EDITION
• SBC-5 RHODE ISLAND STATE ELECTRICAL CODE,
INCORPORATES NATIONAL ELECTRIC CODE 2014
• NFPA 101 LIFE SAFETY CODE
• ICC/ANSI A117.1 2012
• DoDM 5200.01, V3
• ADA 2010
• UFC 3-600-01
• ANG ETL 15-01-00
• ICD-705
• ETL 01-18
N
UP
E E
D.1 D.1
DD
CC
BB
A.9A.9
B.1B.1
AA
INSTRUCTOR'S
OPEN OFFICE
VEST
SITE MGR
ADMIN
COR OFFICE
COMPUTER
ROOM
102MULTI-PURPOSE
STOR
206B
COPY
306STOR
206A
BREAK
MENS
305A WOMENS
305B
JAN
FIRE PROT
CBT/CPT
CORRIDOR
MAINT
SUPPORT
MECH
COMM
ELEC
MAINT
OFFICE
SIM MOTION
BAY
STOR
RECYCLE
'-7
1/ 4"
52'-7 1/4"82'-0"
'-8
5/ 8"
1'-4" 17'-0" 14'-8" 17'-0" 1'-4" 7 5/8"7 5/8"
7 5/8" 61'-4" 7 5/8"6'-8"83'-4"
152'-7 1/4"
'-8
18'-0"
VEST
3' -4
3'
-4
3'-4" 2'-8"
VTRATBRIEFING
BRIEFING
LOAD
MASTER
EMM ROOM
CORRIDOR
7 12
DEMOLITION LEGEND
ITEM TO BE DEMOLISHED
ITEM TO REMAIN
NOT IN SCOPE
Br oa dw ay
Ex ten sio n, Su ite
Ok lah om aC ity ,O
K
8-
5.8
.29
|fs b-ae
.co m
D A
TE
SI
M
UL
AT
OR
FA
CI
LI
TY
M
OD
IF
IC
AT
IO
NS
UN
ITE
DS
TA
TE
SP
RO
PE
RT
Y&
FIS
CA
LO
FF
ICE
,N
OR
TH
KIN
GS
TO
WN
,R I
AI
R
NA
TI
ON
AL
GU
AR
D rd
A
IR
L
IF
T W
IN
G
RH
OD
E
IS
LA
ND
TY
PE
B- 3-
FI
NA
L
DE
SI
GN
SU
BM
IS
SI
ON
DRAWING NO.
TWLR182167
P R
O
JE
C T
TI
TL
E:
S U
B M
IT
TA
L
LE
V E
L:
MAJ. KATHLEEN MAHONEY
PROJECT NO.
BASE ENGINEER:
NOVEMBER 12, 2018
DATE:
DRAWN BY:
S H
EE
T
TI
TL
E
S A F E
TY
B C E
U S E R
F
IR
E
E N V
IR
O
C O O R D
IN
A
TI
O N
S
IG
N A
TU
R E S
S E C U R
IT
Y
C O M M
R E V
IS
IO
N
M A R K
D A
TE
CHECKED BY:
APPROVED BY:DRAWN BY:
R
IC
HARD S . JOHNSO
N
A
R C H I T E CT
R
EG I ST EREDH O P E
STATE OF
R HOD E I S L A N D
3 9 4 6
/5
/2
8:
:2
A
M C
:\U se rs \d ap \D oc um en ts
\M y
R ev it\
0_
A rc h_ dp al m er
FS
H H
P.
rv t
AD101
G
RO
UN
D
FL
O
O R
DE
M
O
LI
TI
O
N
PL
AN
JMIDAP
DAP JMI
SCALE: 3/16" = 1'-0"
1 GROUND FLOOR DEMOLITION PLAN
4' 12'8'0
3/16" = 1'-0"
N
SHEET KEYNOTES X
1. DEMOLISH EXISTING WALL & BRACING.
2. DEMOLISH EXISTING DOOR & FRAME.
3. DEMOLISH EXISTING WALL FOR INSTALLATION
OF NEW DOOR. COORDINATE WITH 2 & 3/A-103.
4. DEMOLISH EXISTING CASEWORK.
5. REMOVE EXISTING WELDED WIRE CAGES &
DOORS WITHOUT DAMAGE. COORDINATE WITH
OWNER TO RETAIN OR DISPOSAL.
6. REMOVE SIGNAGE WITHOUT DAMAGE. RETAIN
FOR REINSTALLTION.
7. REMOVE ALL ACOUSTICAL CEILING TILES
WITHOUT DAMAGE. REMOVE EXISTING CEILING
GRID AS REQUIRED FOR INSTALLATION OF NEW
WALL. RETAIN TILES & GRID FOR
REINSTALLATION.
8. REMOVE FIRE EXTINGUISHER, CABINET &
SIGNAGE WITHOUT DAMAGE. RETAIN FOR
REINSTALLATION IN NEW LOCATION.
9. REMOVE WITHOUT DAMAGE ANY CEILING TILE
OR GRID AS REQUIRED FOR INSTALLATION OF
BRIDGE CRANE.
10. DEMOLISH EXISTING CEILING GRID & TILES AS
REQUIRED FOR INSTALLATION OF NEW
OPERABLE PANEL PARTITION. COORDINATE
WITH 9/A-103. REVISE ANY EQUIPMENT IN
REQUIRED INSTALLATION AREA SUCH AS
MECHANICAL DIFFUSERS, LIGHT FIXTURES &
SPRINKLER HEADS. (OPTIONAL LINE ITEM 1)
11. REMOVE WITHOUT DAMAGE THE 30" MONITOR
IN ROOM 102 FOR RELOCATION IN RM 213.
PATCH & REPAIR ANY DAMAGE TO WALL. PAINT
ENTIRE WALL TO MATCH ADJACENT SURFACES.
12. REMOVE EXISTING CORNER GUARD WITHOUT
DAMAGE. RETAIN FOR REINSTALLATION.
GENERAL NOTES
L. AT ALL LOCATIONS WHERE ITEMS ARE CALLED
OUT TO BE REMOVED, THE CONTRACTOR IS TO
PATCH AND REPAIR WALL/FLOOR/CEILINGS AS
REQUIRED TO MATCH ADJACENT SURFACES EVEN
IF NOT SPECIFICALLY CALLED OUT IN DEMO
LEGEND.
M. CONTRACTOR MUST REVIEW ALL SHEETS IN ALL
DISCIPLINES TO LOCATE ALL DEMO ITEMS. NOT
ALL DEMOLITION ITEMS ARE ON THE DEMO
SHEETS. FOR CLARITY SOME DEMO ITEMS ARE IN
DETAILS, SECTIONS, PLANS, ELEVATIONS, ETC.
G. VERIFY AND MAINTAIN THE LOCATION OF EXISTING
POWER, COMMUNICATION AND DATA CABLES SO
AS TO NOT INADVERTENTLY INTERRUPT THE
CONTINUITY OF SERVICE.
H. PATCH ALL FLOOR, WALL AND CEILING
PENETRATIONS RESULTING FROM REMOVAL OR
RE-ROUTING OF NEW OR EXISTING PIPING,
DUCTWORK, CONDUIT, ETC. AS REQUIRED TO
MAINTAIN FIRE SEPARATIONS. FINISH AS
REQUIRED FOR NEW OR EXISTING ADJACENT
SURFACES.
I. CAP ALL DISCONNECTED MECHANICAL PIPING
LINES WITHIN THE WALL OR FLOOR. PATCH AND
FINISH TO MATCH NEW OR EXISTING ADJACENT
SURFACES.
J. ALL CEILING AND WALL MOUNTED ITEMS
INCLUDING BUT NOT LIMITED TO LIGHTS,
SPEAKERS, SMOKE OR THERMAL DETECTORS
SHALL BE REINSTALLED IN THEIR ORIGINAL
LOCATION AND CONDITION UNLESS OTHERWISE
NOTED.
K. MAINTAIN SECURE, WEATHER-TIGHT ENCLOSURE
AT THE EXTERIOR OF THE EXISTING BUILDING
THROUGHOUT THE DEMOLITION/ CONSTRUCTION
PORTION OF THE WORK IN THAT AREA. BUILDING
SECURITY SHALL BE THE RESPONSIBILITY OF THE
GENERAL CONTRACTOR AND COORDINATED WITH
THE OWNER.
A. ALL EXISTING SYSTEMS MUST BE MAINTAINED
THROUGHOUT CONSTRUCTION. COORDINATE
WITH THE OWNER ANY PRE-APPROVED
DISRUPTION AND VERIFICATION OF SERVICE
WITHIN THE EXISTING BUILDING SO AS TO
MINIMIZE THE DISRUPTION OF SERVICE.
B. COORDINATE ALL DEMOLITION PHASING EFFORTS
WITH THE OWNER/ARCHITECT. EVERY EFFORT
SHALL BE MADE TO MINIMIZE THE DISRUPTION OF
OPERATIONS, AND PROVIDE SAFETY FOR THE
OCCUPANTS. EXCESSIVE NOISE OR VIBRATION
SHALL BE PRE-APPROVED AND COORDINATED
WITH THE OWNER.
C. VERIFY ALL EXISTING CONDITIONS AND NOTIFY
THE ARCHITECT/OWNER OF ANY DISCREPANCIES.
D. REMOVE ALL DEMOLITION MATERIALS FROM THE
SITE UNLESS NOTED OTHERWISE. THE OWNER
SHALL RESERVE THE RIGHT TO SALVAGE ANY
MATERIALS. COORDINATE WITH OWNER.
E. PROVIDE PROTECTION FOR ALL EXISTING
BUILDING MATERIALS AND EQUIPMENT FROM
DAMAGE DUE TO ANY DEMOLITION OR
CONSTRUCTION RELATED ACTIVITY PERFORMED
UNDER THIS CONTRACT.
F. REPAIR OR REPLACE ANY WALLS, FLOORS, OR
EQUIPMENT DAMAGED AS A RESULT OF
DEMOLITION OR CONSTRUCTION TO MATCH
EXISTING FINISH AND CONDITION. FILL ALL HOLES,
PATCH OR REPAIR SURFACE PER
MANUFACTURER'S INSTALLATION INSTRUCTIONS
BEFORE INSTALLING NEW FINISHES.
UP
E E
D.1 D.1
DD
CC
BB
A.9A.9
B.1B.1
AA
INSTRUCTOR'S
OPEN OFFICE
VEST
SITE MGR
ADMIN
203 COR OFFICE
LMPTT ROOM
COMPUTER
ROOM
MULTI-PURPOSE
STOR
206B
COPY
306STOR
206A
BREAK
MENS
305A
WOMENS
305B
JAN
FIRE PROT
CBT/CPT
BRIEFING
RIOS
CORRIDOR
DEBRIEFING
MAINT
SUPPORT
MECH
COMM
ELEC
COMPRESSOR
ROOM
MAINT
OFFICE
SIM MOTION
BAY
STOR
RECYCLE
'-7
1/ 4"
52'-7 1/4"82'-0"
'-8
5/ 8"
1'-4" 17'-0" 14'-8" 17'-0" 1'-4" 7 5/8"7 5/8"
7 5/8" 19'-8" 20'-10" 21'-0" 21'-10" 17'-0" 14'-8" 17'-0" 19'-4" 7 5/8"
1' -4
'-0
SIMULATOR EQUIPMENT
MOTION CLEARANCE
CG
152'-7 1/4"
'-8
18'-0"
VEST
210A
214A
101D
D1
D1
312A
2'-8"
3' -4
5'
-0
1' -1
3/
4"
'-8 3/
8"
5/ 8"
2' -0
"2 '-0
'-0
'-1
1" 1'
-9
'-8
5/ 8"
209A
+/- 28'-6" 5'-0"
101A
A-103
A-103
A-103
A-103
SIM
5'-0"
1'-6"
CORRIDOR
CJ CJCJCJCJ
TYP.
+/- 4'-9"
101C
101B
102A
213B213A
211A
212A
214B
103A
311A
ADD CELL LOCKERS
11E1
PLAN LEGEND
BOUNDARY OF OPEN STORAGE
SECRET AREA
NOT IN SCOPE
Br oa dw ay
Ex ten sio n, Su ite
Ok lah om aC ity ,O
K
8-
5.8
.29
|fs b-ae
.co m
D A
TE
SI
M
UL
AT
OR
FA
CI
LI
TY
M
OD
IF
IC
AT
IO
NS
UN
ITE
DS
TA
TE
SP
RO
PE
RT
Y&
FIS
CA
LO
FF
ICE
,N
OR
TH
KIN
GS
TO
WN
,R I
AI
R
NA
TI
ON
AL
GU
AR
D rd
A
IR
L
IF
T W
IN
G
RH
OD
E
IS
LA
ND
TY
PE
B- 3-
FI
NA
L
DE
SI
GN
SU
BM
IS
SI
ON
DRAWING NO.
TWLR182167
P R
O
JE
C T
TI
TL
E:
S U
B M
IT
TA
L
LE
V E
L:
MAJ. KATHLEEN MAHONEY
PROJECT NO.
BASE ENGINEER:
NOVEMBER 12, 2018
DATE:
DRAWN BY:
S H
EE
T
TI
TL
E
S A F E
TY
B C E
U S E R
F
IR
E
E N V
IR
O
C O O R D
IN
A
TI
O N
S
IG
N A
TU
R E S
S E C U R
IT
Y
C O M M
R E V
IS
IO
N
M A R K
D A
TE
CHECKED BY:
APPROVED BY:DRAWN BY:
R
IC
HARD S . JOHNSO
N
A
R C H I T E CT
R
EG I ST EREDH O P E
STATE OF
R HOD E I S L A N D
3 9 4 6
/5
/2
8:
:1
A
M C
:\U se rs \d ap \D oc um en ts
\M y
R ev it\
0_
A rc h_ dp al m er
FS
H H
P.
rv t
A-101
G
RO
UN
D
FL
O
O R
PL
AN
JMIDAP
DAP JMI
SCALE: 3/16" = 1'-0"
1 GROUND FLOOR PLAN
4' 12'8'0
3/16" = 1'-0"
N
SHEET KEYNOTES X
1.
2.
3.
4.
5.
6.
7.
GENERAL NOTES
A. FURNITURE SHOWN IS FOR REFERENCE ONLY.
B. CONTRACTOR TO FIELD VERIFY EXISTING
CONDITIONS AND DIMENSIONS PRIOR TO ANY
FABRICATION OF MATERIAL.
C. ALL PERIMETER FLOOR PLAN DIMENSIONS ARE
NOMINAL EXISTING MASONRY INCLUDING DOOR
OPENINGS UNLESS NOTED OTHERWISE.
ADJUST OPENING TO ACCOUNT FOR DOOR AND
MISC FRAMES TO BE INSTALLED WITHIN EACH
OPENING AS REQUIRED.
D. ALL DIMENSIONS ARE ACTUAL AND ARE TO
FACE OF GWB, FACE OF CONCRETE WALLS,
FACE OF CMU WALLS, FACE OF FRAMES, OR
CENTERLINE OF COLUMNS UNLESS OTHERWISE
NOTED.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
FIELD VERIFY THAT ALL OPENINGS ARE SEALED
AND THE EXISTING WALL CONFORMS TO
PARTITION TYPE D1, STC-50 CONSTRUCTION.
PATCH & REPAIR WHERE DEFICIENCIES OCCUR.
30" VIDEO MONITOR (N.I.C.). REF 5/A-103.
REMOVE EXISTING STEEL GRATING AND INFILL
2'W X 1'-6" DEEP TRENCH WITH STEEL
REINFORCED CONCRETE.
NEW 5" CONCRETE SIDEWALK ON 8" GRAVEL TO
MATCH EXISTING. TIE INTO EXISTING SIDEWALK
& MODULAR CONCRETE UNIT WALL W/ 2% MAX
CROSS SLOPE. ADD NEW MODULAR WALL TO
MATCH EXISTING W/ EXTENTS AS REQUIRED.
CONTRACTOR RESPONSIBLE FOR SITE
DRAINAGE.
EXISTING ACCESS FLOORING TILES TO BE
REPLACED WITH NEW PERFORATED PANELS.
QUANTITIES AND LOCATIONS AS SHOWN ON
MECHANICAL SHEET MH101.
ENSURE THAT ALL OPENINGS AND
PENETRATIONS IN CMU ARE SEALED FOR AN
STC-50 SOUND RATING.
NEW WALL, BASE, FLOOR, DOOR & FRAME
FINISHES ARE TO MATCH ADJACENT EXISTING
FINISHES.
EXISTING CONCRETE SIDEWALK & MODULAR
WALL.
5'-0" X 5'-0" CONCRETE STOOP
NEW EMERGENCY EYEWASH
INSTALL RELOCATED FIRE EXTINGUISHER
CABINET.
VIDEO MONITOR RELOCATED FROM RM 102.
REF 5/A-103. PATCH & REPAIR WALL IN RM 102.
INSTALL NEW STEEL SHEET OVER EXISTING
TRENCH GRATE PER DETAIL 4/A-103.
VERIFY CONDITION OF EXISTING 1-HR UL
SYSTEM C-AJ-1429 IN TRENCH BELOW EXISTING
FIRE RATED WALL. PATCH & REPAIR AS
NECESSARY TO MAINTAIN FIRE RATING.
CONCRETE SLAB EXTENSION. REF. 3/A-103.
INSTALL NEW STC-45 RATED OPERABLE PANEL
PARTITION USING EXISTING SUPPORT BEAM.
COORDINATE WITH 9/A-103. OPTIONAL LINE
ITEM 1.
NEW LOUVER OPENINGS. COORDINATE WITH
MECHANICAL 1/MH101 & DETAILS 10, 11 & 12/A-
103.
REPAIR CONCRETE SLAB DAMAGE FROM WIRE
CAGE DEMOLITION.
REINSTALL EXISTING CORNER GUARD.
EXTEND TO EXISTING ADJACENT PAVING.
E E
D.1D.1
DD
CC
BB
A.9A.9
B.1B.1
AA
INSTRUCTOR'S
OPEN OFFICE
MENS
305A
WOMENS
305B
JAN
BREAK
RECYCLE
STOR
FIRE PROT
CBT/CPT
BRIEFING
RIOS
DEBRIEFING
MAINT
OFFICE
MAINT
SUPPORT
MECH
COMM
ELEC
COMPRESSOR
ROOM
SIM MOTION
BAY
COMPUTER
ROOM
CORRIDOR
LMPTT ROOM
COR OFFICE
SITE MGR
ADMIN
MULTI-PURPOSE
STOR
206A
STOR
206B
VEST
313 COPY
9'-0"
9'-0"
4 5
CORRIDOR
A-103
49'-9"
PLAN LEGEND
BOUNDARY OF OPEN STORAGE
SECRET AREA
NOT IN SCOPE
TYPICAL CEILING LEGEND
2' x 2' CEILING GRID
GYP BD CEILING
2' x 4' FLUORESCENT FIXTURE -
EMERGENCY
1' x 4' FLUORESCENT FIXTURE
RECESSED DOWNLIGHT
EXIT SIGNS
WALL MTD EXTERIOR LIGHT
SUPPLY AIR DIFFUSERS
RETURN AIR GRILLES1' x 4' FLUORESCENT FIXTURE -
EMERGENCY
2' x 4' FLUORESCENT
FIXTURE
WALL MTD EXTERIOR LIGHT -
EMERGENCY
RECESSED DOWNLIGHT -
EMERGENCY
ACCESS DOORS
Br oa dw ay
Ex ten sio n, Su ite
Ok lah om aC ity ,O
K
8-
5.8
.29
|fs b-ae
.co m
D A
TE
SI
M
UL
AT
OR
FA
CI
LI
TY
M
OD
IF
IC
AT
IO
NS
UN
ITE
DS
TA
TE
SP
RO
PE
RT
Y&
FIS
CA
LO
FF
ICE
,N
OR
TH
KIN
GS
TO
WN
,R I
AI
R
NA
TI
ON
AL
GU
AR
D rd
A
IR
L
IF
T W
IN
G
RH
OD
E
IS
LA
ND
TY
PE
B- 3-
FI
NA
L
DE
SI
GN
SU
BM
IS
SI
ON
DRAWING NO.
TWLR182167
P R
O
JE
C T
TI
TL
E:
S U
B M
IT
TA
L
LE
V E
L:
MAJ. KATHLEEN MAHONEY
PROJECT NO.
BASE ENGINEER:
NOVEMBER 12, 2018
DATE:
DRAWN BY:
S H
EE
T
TI
TL
E
S A F E
TY
B C E
U S E R
F
IR
E
E N V
IR
O
C O O R D
IN
A
TI
O N
S
IG
N A
TU
R E S
S E C U R
IT
Y
C O M M
R E V
IS
IO
N
M A R K
D A
TE
CHECKED BY:
APPROVED BY:DRAWN BY:
R
IC
HARD S . JOHNSO
N
A
R C H I T E CT
R
EG I ST EREDH O P E
STATE OF
R HOD E I S L A N D
3 9 4 6
/5
/2
8:
:3
A
M C
:\U se rs \d ap \D oc um en ts
\M y
R ev it\
0_
A rc h_ dp al m er
FS
H H
P.
rv t
A-102
RE
FL
EC
TE
D
CE
IL
IN
G
PL
AN
JMIDAP
DAP JMI
SCALE: 3/16" = 1'-0"
1 REFLECTED CEILING PLAN
4' 12'8'0
3/16" = 1'-0"
N
SHEET KEYNOTES X
1. PATCH & REPAIR CEILING GRID TO MATCH
EXISTING. REINSTALL UNDAMAGED
ACOUSTICAL CEILING TILES. REPLACE
DAMAGED TILES WITH NEW TILES TO MATCH
EXISTING.
2. ALL CEILINGS OTHER THAN ROOMS 209 & 210
ARE EXISTING TO REMAIN.
3. INSTALL NEW CRANE RAILS ON EXISTING
CRANE RUNWAY BEAMS (TOP OF BEAM 141'-6"
V.I.F.).
4. NEW CRANE BRIDGE
5. NEW HOIST
6. REINSTALL & PATCH/REPAIR ANY CEILING TILES
AND GRID REMOVED AND/OR DAMAGED AS A
RESULT OF BRIDGE CRANE INSTALLATION.
7. INSTALL NEW STC-45 RATED OPERABLE PANEL
PARTITION & GYP BD SOFFIT USING EXISTING
SUPPORT BEAM. PATCH & REPAIR CEILING
GRID & TILES TO MATCH EXISTING ADJACENT
FINISHES. OPTIONAL LINE ITEM 1.
AIR BARRIER
2" RIGID
INSULATION (R-10)
BRICK VENEER
MASONRY JAMB
ANCHORS
MIN (3) PER SIDE
BACKER ROD AND
SEALANT, TYP
HOLLOW METAL FRAME
FILL W/ GROUT
2 1/2"5 1/4"
SELF ADHERED
FLEXIBLE FLASHING
2" RIGID
INSULATION (R-10)
WEEPS @ 16" O.C.
2 1/2"5 1/4"
LOOSE
STEEL LINTEL
HOLLOW METAL FRAME
FILL W/ GROUT
DOOR AS SCHEDULED
AIR BARRIER
BRICK VENEER
BACKER ROD &
SEALANT, TYP
GROUND FLOOR
100'-0"
1/2" EXPANSION
MATERIAL
SEALANT
THRESHOLD
HOLLOW METAL
FRAME BEYOND
DOOR AS SCHEDULED
EXISTING
CONCRETE SLAB
PROVIDE (2) #4
EPOXY GROUTED
DOWELS
ROUGHEN EXISTING
CONCRETE SURFACES
TO 1/4" AMPLITUDE FOR
SLAB EXTENSION
SIDEWALK
SLAB.
REF. PLAN
& DET 7/A-
BRICK LEDGE
EXISTING
PROVIDE (2) #4
D O
O R
H
EI
G H
T
DOOR WIDTH
SFX
STEEL, EXTERIOR
D O
O R
H
EI
G H
T
DOOR WIDTH
WFI
WOOD, INTERIOR
S2 STEEL
D O
O R
H
EI
G H
T 2"
2" 2"DOOR WIDTH
S4 STEEL
D O
O R
H
EI
G H
T 4"
2" 2"DOOR WIDTH
GROUND FLOOR
100'-0"
NEW 14 GA SLIP-RESISTANT DIAMOND
STEEL SHEET, REF. 6/A-103. STEEL
PLATE SIZE TO MATCH INDIVIDUAL
GRATE SECTIONS TO ALLOW FOR
SECTIONS TO BE REMOVED.
TACK WELD NEW
SHEET TO
EXISTING GRATE
FROM BELOW @
4" O.C.E.W.
EXISTING STEEL GRATE,
EMBED SYSTEM &
CONCRETE SLAB
AT EACH SECTION
OF EXISTING
GRATE, CUT
OPENING IN 14 GA
STEEL SHEET FOR
PANEL LIFTING
TOOL INSERTION.
TACK WELD AT
PERIMETER OF
OPENING FROM
BELOW.
LOCATE OPENING
ONE SPACE MIN.
FROM EDGE.
COORDINATE WITH
EXISTING SHELF
ANGLE.
A. ALL SOUND ATTENUATION BATTS
WHERE INDICATED SHALL FILL
THE STUD CAVITY AND SHALL BE
UNFACED, 2.5 PCF - INSTALLED
CONTINUOUS VERTICALLY, CUT
TIGHT TO FIT.
B. DO NOT LOCATE ELECTRICAL
BOXES OPENING TO OPPOSITE
SIDES OF THE WALL WITHIN THE
SAME STUD BAY OF STC
PARTITIONS.
C. PROVIDE ACOUSTICAL SEALANT
AT ALL OPENINGS CUT INTO STC
RATED PARTITIONS.
D. MINERAL WOOL TO BE MIN 4 PCF,
COMPRESS 50% FLUSH WITH
FACES OF WALL.
PARTITION NOTES(2) LAYERS 5/8"
TYPE 'X' GYP. BD.
FINISH FLOOR
DECK
SLOTTED
DEFL. TRACK
CLG. TO
MATCH
EXISTING
STEEL RUNNER
CHANNEL
BASE TO MATCH
EXISTING
100'-0"
FIN. FLOOR
6" 18 GA STUDS
AT 16" O.C.
D1
ICD-705 CONFORMING WALL DESIGN:
GA WP 1052 SYSTEM - MIN. STC 45.
SOUND TEST REFERENCE: NRCC
817-NV. NON-RATED.
PROVIDE UL ASSEMBLY
HW-D-0042 TO DECK
ACOUSTICAL
SEALANT, TYP
5/8" TYPE 'X'
GYP BD
UNFACED
ACOUSTICAL
BATTS
FIRE STOPPING
FINISH
FLOOR
20 GA 3 5/8"
STUDS AT 16"
5/8" TYPE 'X' GYP BD
CLG. TO MATCH
EXISTING
STEEL RUNNER
CHANNEL
NON-RATED PARTITIONE1
BASE TO MATCH
EXISTING
100'-0"
FIN. FLOOR
6"
C
EN
TE
R
O F
M O
N
IT
O R
6' -0
PROVIDE REQUIRED
BLOCKING
FINISH FLOOR
MONITOR
SIZE VARIES
NOTE: CONTRACTOR SHALL COORDINATE SO THAT ALL
POWER, DATA OR COMM J. BOXES INSTALLED BEHIND
MONITORS ARE ACCESSIBLE AND DO NOT INTERFERE
WITH MOUNTING BRACKETS. PATCH & REPAIR EXISTING
WALL FINISH. PAINT ENTIRE WALL TO MATCH ADJACENT
SURFACES.
5" CONC. SIDEWALK
REINFORCE WITH 6X6-10/10
WWF SLOPE
1/8" PER FT.
4" LOAM AND
SEED
8" COMPACTED
GRAVEL BASE
5'-0"
1/2" RADIUS
1/2" RADIUS
4" LOAM AND
SEED
DETAILING & FINISH TO MATCH
EXISTING ADJACENT SURFACES
GROUND FLOOR
100'-0"
TO CMU
112'-8"
E
A-103
A-103
EXISTING WALL
BRICK VENEER ON
CMU CONSTRUCTION
INSULATED STEEL
DOOR/FRAME
PATCH & REPAIR
MASONRY CUT OPENING
CONCRETE
SIDEWALK PER
PLAN. MATCH
EXISTING SIMILAR
CONDITION.
CONCRETE
EXTENSION TO
EXISTING SLAB.
TO CMU
112'-0"
3 5/8" 20 GA MTL STUD
FRAMING @ 16" O.C.
UNFACED ACOUSTIC BATTS
ACOUSTIC CEILING TILE
5/8" TYPE 'X' GYP BD
3 5/8" 20 GA MTL STUDS
@ 16" O.C.
6" 4" 6"
3/8" THREADED ROD
OPERABLE PARTITON HEAD
EXISTING W10X30 STEEL
BEAM
DETAIL IS PART OF OPTIONAL LINE ITEM 1
CONTINUE TO
STRUCTURE ABOVE
PRE-FINISHED LOUVER
BIRD SCREEN
STEEL ANGLE
STEEL PLATE
WEEPS @ 16" O.C.
SELF ADHERED
FLEXIBLE FLASHING
STEEL ANGLE
1/2"
7 5/8"
AIR BARRIER
PRE-FINISHED SILL
PAN W/ FOLDED END
DAMS
1/2"
STEEL ANGLE
SEALANT
BIRD SCREEN
PRE-FINISHED
METAL LOUVER
2" RIGID INSULATION
(R-10)
GROUT SOLID
1/4"
8" CMU
AIR BARRIER
STEEL ANGLE
2" RIGID
INSULATION
(R-10)
PRE-FINISHED
LOUVER
BACKER ROD AND
SEALANT, TYP
BIRD SCREEN
1/ 2"
Br oa dw ay
Ex ten sio n, Su ite
Ok lah om aC ity ,O
K
8-
5.8
.29
|fs b-ae
.co m
D A
TE
SI
M
UL
AT
OR
FA
CI
LI
TY
M
OD
IF
IC
AT
IO
NS
UN
ITE
DS
TA
TE
SP
RO
PE
RT
Y&
FIS
CA
LO
FF
ICE
,N
OR
TH
KIN
GS
TO
WN
,R I
AI
R
NA
TI
ON
AL
GU
AR
D rd
A
IR
L
IF
T W
IN
G
RH
OD
E
IS
LA
ND
TY
PE
B- 3-
FI
NA
L
DE
SI
GN
SU
BM
IS
SI
ON
DRAWING NO.
TWLR182167
P R
O
JE
C T
TI
TL
E:
S U
B M
IT
TA
L
LE
V E
L:
MAJ. KATHLEEN MAHONEY
PROJECT NO.
BASE ENGINEER:
NOVEMBER 12, 2018
DATE:
DRAWN BY:
S H
EE
T
TI
TL
E
S A F E
TY
B C E
U S E R
F
IR
E
E N V
IR
O
C O O R D
IN
A
TI
O N
S
IG
N A
TU
R E S
S E C U R
IT
Y
C O M M
R E V
IS
IO
N
M A R K
D A
TE
CHECKED BY:
APPROVED BY:DRAWN BY:
R
IC
HARD S . JOHNSO
N
A
R C H I T E CT
R
EG I ST EREDH O P E
STATE OF
R HOD E I S L A N D
3 9 4 6
/5
/2
8:
:4
A
M C
:\U se rs \d ap \D oc um en ts
\M y
R ev it\
0_
A rc h_ dp al m er
FS
H H
P.
rv t
A-103
DO
O
R
SC
HE
DU
LE
,D
O O
R
FR
AM
E
TY
PE
S, DE
TA
IL
S
PA
RT
IT
IO
N
TY
PE
JMIDAP
DAP JMI
SCALE: 3" = 1'-0"
2 HOLLOW METAL DOOR JAMB
SCALE: 3" = 1'-0"
1 HOLLOW METAL DOOR HEAD
SCALE: 3" = 1'-0"
3 HOLLOW METAL DOOR SILL
3" 9"6"0
3" = 1'-0"
NOTES
1. INSULATED 18 GA. STEEL DOOR, CONFORMING
TO DoDM 5200.01-V3 REQUIREMENTS.
2. REPLACE DOOR W/ LITE WITH SOLID WOOD
CORE DOOR, CONFORMING TO DoDM 5200.01-V3
REQUIREMENTS WITH NO LITE.
3. EGRESS ONLY. NO EXTERIOR DOORWARE.
4. SOLID CORE WOOD DOOR. STC-45.
5. REQUIRED ACCESS CONTROL PER DoDM
5200.01-V3.
6. X10 LOCK REQUIRED. RELOCATE FROM DOOR
101A, IF POSSIBLE. IF NOT, THEN INSTALL NEW.
7. IDS SYSTEM REQUIRED. COORDINATE W/
ELECTRICAL
8. DOOR IS EXISTING TO REMAIN. ADDITIONAL
SECURITY EQUIPMENT ADDED. COORDINATE W/
ELECTRICAL.
DOOR SCHEDULE
MARK
DOOR
FR STC
FRAME
HDW
RSET NOTES
SIZE DOOR
TYPE TYPE MATLWD HGT THK
101A 3'-0" 7'-0" 1 3/4" EXISTING 45 MIN 45 EXISTING HM 8
101B 20'-0" 22'-0" 3/4" EXISTING EXISTING 8
101C 8'-3" 9'-9" 3/4" EXISTING 45 MIN EXISTING 8
101D 3'-0" 7'-0" 1 3/4" SFX 45 S4 HM 1 1, 3, 7
102A 6'-0" 7'-0" 1 3/4" EXISTING 45 MIN 45 EXISTING HM 8
103A 6'-0" 7'-0" 1 3/4" EXISTING 45 MIN 45 EXISTING HM 8
209A 3'-0" 7'-0" 1 3/4" SFX 45 S4 HM 1 1, 3, 7
210A 3'-0" 7'-0" 1 3/4" WFI 45 S2 HM 2 4, 5
211A 3'-0" 7'-0" 1 3/4" EXISTING 45 EXISTING HM 5, 8
212A 3'-0" 7'-0" 1 3/4" EXISTING 45 EXISTING HM 5, 8
213A 3'-0" 7'-0" 1 3/4" EXISTING EXISTING HM 8
213B 3'-0" 7'-0" 1 3/4" EXISTING EXISTING HM 8
214A 3'-0" 7'-0" 1 3/4" SFX 45 S4 HM 1 1, 3, 7
214B 8'-3" 9'-9" 3/4" EXISTING EXISTING 8
311A 3'-0" 7'-0" 1 3/4" EXISTING 45 MIN 45 EXISTING HM 8
312A 3'-0" 7'-0" 1 3/4" WFI 45 S2 HM 3 2, 5, 6, 7
SCALE: 3/8" = 1'-0"
DOOR TYPES
SCALE: 3/8" = 1'-0"
FRAME TYPES
2' 6'4'0
3/8" = 1'-0"
SCALE: 3" = 1'-0"
4 TRENCH COVER DETAIL
SCALE: 3" = 1'-0"
6 PLATE OPENING AT TRENCH COVER
SCALE:NTS
TYPICAL PARTITION TYPE
SCALE: 1/2" = 1'-0"
5 MONITOR MOUNTING HEIGHT
SCALE: 1 1/2" = 1'-0"
7 SIDEWALK DETAIL
6" 1'-6"1'0
1 1/2" = 1'-0"
SCALE: 1/2" = 1'-0"
8 WALL SECTION AT DOOR
0 1' 2' 4'
1/2" = 1'-0"
SCALE: 1 1/2" = 1'-0"
9 OPERABLE PARTITION HEAD
SCALE: 3" = 1'-0"
10 LOUVER HEAD
SCALE: 3" = 1'-0"
11 LOUVER SILL
SCALE: 3" = 1'-0"
12 LOUVER JAMB
UP
1" HIGH PERMANENT TEXT
8"
Conference Room
GRADE 2 BRAILLE
5/8" HIGH PERMANENT TEXT
ON PRINTED PAPER INSERT
1/4" FRAME
NOTE: SEE DETAIL 4/A-104 FOR EXPLODED
ISOMETRIC OF SIGN
2" 6"
8"
7/ 8"
3/4" 3/4"
7/ 8"
7/ 8"
2"
1" HIGH PERMANENT TEXT
8"
Mechanical Room
GRADE 2 BRAILLE
5/8" HIGH PERMANENT TEXT,
TYP.
1/4" FRAME
2" 6"
8"
7/ 8"
3/4" 3/4"
7/ 8"
7/ 8"
2"
8"
4"
EMERGENCY
EXIT ONLY
PERMANENT 5/8" HIGH
TEXT CENTERED AS
SHOWN WITH GRADE
TWO BRAILLE BELOW
5' -0
6"
MOUNT SIGN ON LATCH SIDE OF
DOOR WHERE POSSIBLE.
WHERE REQUIRED MOUNT SIGN
ON HINGE SIDE OF DOOR AT
SAME DISTANCES AS SHOWN.
WHERE REQUIRED MOUNT SIGN
AT SAME HEIGHT AS SHOWN ON
CENTER OF DOOR.
PLASTIC SIGN HEADER ON
NON-GLARE CLEAR ACRYLIC
SIGN COVER. COVER SNAPS
ON SIGN FRAME AND BACK
HIGH IMPACT PLASTIC
FRAME AND BACK W/
PRINTED PAPER INSERT
Conference Room
6"
PERMANENT RAISED
PICTOGRAM
CENTERED IN SIGN
6"
E E
D.1D.1
DD
CC
BB
A.9A.9
B.1B.1
AA
CBT/CPT
FIRE PROT
BRIEFING
RIOS
CORRIDOR
MAINT
OFFICE
DEBRIEFING
MAINT
SUPPORT
COMPUTER
ROOM
SIM MOTION
BAY
A1.03 A1.05
A1.01
A1.06
A1.07
A1.04
A1.08
C2.01
A1.02
A2.02
A2.01
C2.02
C2.03
A1.09
1 1 1
C1.01
TYPICAL SIGN SYMBOL
AREA / LEVEL
SIGN NUMBER
SIGNAGE SYMBOL LEGEND
A0.00
Br oa dw ay
Ex ten sio n, Su ite
Ok lah om aC ity ,O
K
8-
5.8
.29
|fs b-ae
.co m
D A
TE
SI
M
UL
AT
OR
FA
CI
LI
TY
M
OD
IF
IC
AT
IO
NS
UN
ITE
DS
TA
TE
SP
RO
PE
RT
Y&
FIS
CA
LO
FF
ICE
,N
OR
TH
KIN
GS
TO
WN
,R I
AI
R
NA
TI
ON
AL
GU
AR
D rd
A
IR
L
IF
T W
IN
G
RH
OD
E
IS
LA
ND
TY
PE
B- 3-
FI
NA
L
DE
SI
GN
SU
BM
IS
SI
ON
DRAWING NO.
TWLR182167
P R
O
JE
C T
TI
TL
E:
S U
B M
IT
TA
L
LE
V E
L:
MAJ. KATHLEEN MAHONEY
PROJECT NO.
BASE ENGINEER:
NOVEMBER 12, 2018
DATE:
DRAWN BY:
S H
EE
T
TI
TL
E
S A F E
TY
B C E
U S E R
F
IR
E
E N V
IR
O
C O O R D
IN
A
TI
O N
S
IG
N A
TU
R E S
S E C U R
IT
Y
C O M M
R E V
IS
IO
N
M A R K
D A
TE
CHECKED BY:
APPROVED BY:DRAWN BY:
R
IC
HARD S . JOHNSO
N
A
R C H I T E CT
R
EG I ST EREDH O P E
STATE OF
R HOD E I S L A N D
3 9 4 6
/5
/2
8:
:5
A
M C
:\U se rs \d ap \D oc um en ts
\M y
R ev it\
0_
A rc h_ dp al m er
FS
H H
P.
rv t
A-104
SI
G
NA
G
E
FL
O O
R
PL
AN
,S
IG
NA
G E
SC
HE
DU
LE
DE
TA
IL
S
JMIDAP
DAP JMI
SCALE: 3" = 1'-0"
3 SIGN TYPE A1
SCALE: 3" = 1'-0"
5 SIGN TYPE A2
SCALE: 3" = 1'-0"
7 SIGN TYPE C2
SCALE: 1/2" = 1'-0"
2 SIGNAGE MOUNTING HEIGHT
SCALE:NTS
EXPLODED ISOMETRIC
SIGNAGE TYPE A1
GENERAL NOTES
A. SEE SIGNAGE MOUNTING HEIGHT, THIS SHEET
FOR INSTALLATION HEIGHTS OF SIGN TYPES
A1, A2 AND C2.
B. FINISHES OF SIGNS SHALL MATCH EXISTING
BUILDING SIGNAGE OF SIMILAR TYPE.
C. SEE SPECIFICATION DIVISION 10 FOR SIGNAGE
REQUIREMENTS.
D. ALL ROOM NAMES AND NUMBERS SHALL BE
SELECTED BY OWNER. ALL ROOM NAMES &
NUMBERS LISTED ON SIGNAGE SCHEDULES
ARE REFERENCE ONLY.
E. VERIFY ROOM NUMBERS AND WORDING WITH
CONTRACTING OFFICER.
F. INSTALL SIGN TYPE C1 NEXT TO ALL FIRE
EXTINGUISHER CABINETS & WALL BRACKET
MOUNTED EXTINGUISHER AT 5'-0" AFF TO
CENTER OF SIGN.
G. ALL NEW SIGNAGE TO MATCH EXISTING
SIGNAGE OF SIMILAR TYPE.
SCALE: 3" = 1'-0"
6 SIGN TYPE C1
SCALE: 1/4" = 1'-0"
1 SIGNAGE FLOOR PLAN
SIGNAGE SCHEDULE
MARK SIGN TYPE MESSAGE - WORDING REMARKS
A1.01 A1 RIOS REINSTALLED EXISTING SIGN
A1.02 A1 SECURE AREA NEW SIGN
A1.03 A1 CBT/CPT EXISTING SIGNAGE TO REMAIN
A1.04 A1 SIM MOTION BAY EXISTING SIGNAGE TO REMAIN
A1.05 A1 MAINTENANCE OFFICE EXISTING SIGNAGE TO REMAIN
A1.06 A1 DEBRIEFING EXISTING SIGNAGE TO REMAIN
A1.07 A1 BRIEFING EXISTING SIGNAGE TO REMAIN
A1.08 A1 MAINTENANCE SUPPORT EXISTING SIGNAGE TO REMAIN
A1.09 A1 MAINTENANCE OFFICE NEW SIGN
A2.01 A2 MAINTENANCE SUPPORT NEW SIGN MOUNTED ON EXTERIOR
A2.02 A2 SIM MOTION BAY NEW SIGN MOUNTED ON EXTERIOR
C1.01 C1 REINSTALLED EXISTING SIGN
C2.01 C2 EMERGENCY EXIT ONLY EXISTING SIGNAGE TO REMAIN
C2.02 C2 EMERGENCY EXIT ONLY NEW SIGN
C2.03 C2 EMERGENCY EXIT ONLY NEW SIGN
0 2' 4' 8'
1/4" = 1'-0"
0 1' 2' 4'
1/2" = 1'-0"
N
3" 9"6"0
3" = 1'-0"
SHEET KEYNOTES X
1. EXISTING SIGNAGE TO REMAIN.
UP
EE
D.1D.1
DD
CC
B.1B.1
BB
A.9
A.9
AA
OPEN STORAGE SECRET
AREA PERIMETER
OPEN STORAGE SECRET AREA
PERIMETEROPEN STORAGE SECRET AREA
PERIMETER
OUTSIDE SECURE AREA
WALL
ELEVATION
INSIDE SECURE AREA
FIRESTOPPING OR
OTHER SUITABLE
SEALANT
NEOPRENE CONNECTOR (TYP) SIMILAR TO:
THREADED: MASON SAFEFLEX SFU OR EQUAL.
FLANGED: MASONFLEX SFEJ OR EQUAL.
Br oa dw ay
Ex ten sio n, Su ite
Ok lah om aC ity ,O
K
8-
5.8
.29
|fs b-ae
.co m
D A
TE
SI
M
UL
AT
OR
FA
CI
LI
TY
M
OD
IF
IC
AT
IO
NS
UN
ITE
DS
TA
TE
SP
RO
PE
RT
Y&
FIS
CA
LO
FF
ICE
,N
OR
TH
KIN
GS
TO
WN
,R I
AI
R
NA
TI
ON
AL
GU
AR
D rd
A
IR
L
IF
T W
IN
G
RH
OD
E
IS
LA
ND
TY
PE
B- 3-
FI
NA
L
DE
SI
GN
SU
BM
IS
SI
ON
DRAWING NO.
TWLR182167
P R
O
JE
C T
TI
TL
E:
S U
B M
IT
TA
L
LE
V E
L:
MAJ. KATHLEEN MAHONEY
PROJECT NO.
BASE ENGINEER:
NOVEMBER 12, 2018
DATE:
DRAWN BY:
S H
EE
T
TI
TL
E
S A F E
TY
B C E
U S E R
F
IR
E
E N V
IR
O
C O O R D
IN
A
TI
O N
S
IG
N A
TU
R E S
S E C U R
IT
Y
C O M M
R E V
IS
IO
N
M A R K
D A
TE
CHECKED BY:
APPROVED BY:DRAWN BY:
HO P E
STATE OF
RHODE IS L AND
GARY W. JAMES
No. 10167
REGISTERED
PROFESSIONAL ENGINEER
MECHANICAL
/5
/2
9:
:2
A
M H
:\P R
J\
\0
3- B
IM
\0
7-
FP
\7
_F
P.
rv t
FX101
FI
RE
SU
PP
RE
SS
IO
N
PL
AN
LFOJME
JME LFO
SCALE: 1/8" = 1'-0"
1 FIRE SUPPRESSION PLAN
GENERAL NOTES
SECURE AREA ROOM SCHEDULE
NUMBER NAME NOTE
101 SIM MOTION BAY
102 COMPUTER ROOM
103 COMPRESSOR ROOM
205 MULTI-PURPOSE 1
209 CORRIDOR 1
210 RIOS 1
211 BRIEFING
212 DEBRIEFING
213 MAINT OFFICE
214 MAINT SUPPORT
311 COMM
A. EXISTING SPRINKLER SYSTEM PIPING
PENETRATING SECURE PERIMETER PARTITION
SHALL BE PROVIDED WITH NON-CONDUCTIVE,
FLEXIBLE CONNECTION INSIDE THE SECURE
PERIMETER ADJACENT TO PENETRATION IN
ACCORDANCE WITH DETAIL 2/FX101.
B. PENETRATIONS SHOWN BASED ON ASBUILT
INFORMATION AND MAY NOT BE INDICATIVE OF
ACTUAL FIELD CONDITIONS. CONTRACTOR SHALL
VERIFY SIZE, QUANTITY, AND LOCATION OF ALL
SPRINKLER SYSTEM PIPING PENETRATIONS
THROUGH SECURE PERIMETER.
C. ALL MODIFICATIONS TO SPRINKLER SYSTEM PIPING
SHALL BE COMPLETED IN ACCORDANCE WITH THE
REQUIREMENTS OF UFC 3-600-01 AND NFPA 13.
SHEET KEYNOTES
1. 4" SPRINKLER SYSTEM PIPING PENETRATING
SECURE PERIMETER AT THIS LOCATION.
2. 2.5" SPRINKLER SYSTEM PIPING PENETRATING
SECURE PERIMETER AT THIS LOCATION.
3. 2" SPRINKLER SYSTEM PIPING PENETRATING
SECURE PERIMETER AT THIS LOCATION.
4. 1.5" SPRINKLER SYSTEM PIPING PENETRATING
SECURE PERIMETER AT THIS LOCATION.
5. 1.25" SPRINKLER SYSTEM PIPING PENETRATING
SECURE PERIMETER AT THIS LOCATION.
SCALE:NTS
2 SECURE AREA PENETRATION DETAIL
0 4' 8' 16'
1/8" = 1'-0"
NOTES:
1. RECONFIGURE SPRINKLER LAYOUT TO ACCOMMODATE
NEW PARTION OR OPERABLE PARTITION
CONFIGURATION.
1 2 3 4 5 6 7 8 9
E
D.1
D
C
B.1
B
A.9
A
OPEN STORAGE SECRET
AREA PERIMETEROPEN STORAGE SECRET
AREA PERIMETER 3
EXISTING FACP/ACU
OPEN STORAGE SECRET
AREA PERIMETER
FIRE ALARM AND MASS NOTIFICATION LEGEND
DESCRIPTIONSYMBOL
MONITOR MODULE
CONTROL MODULE; XX INDICATES
ASSOCIATED UNIT OR DEVICE
END OF LINE RESISTOR
FIRE ALARM CONTROL PANEL
TRANSIENT VOLTAGE SURGE
SUPPRESSOR
DESCRIPTIONSYMBOL
FIRE ALARM MANUAL PULL STATION
CEILING MOUNTED FIRE ALARM STROBE, CLEAR
LENS, MARKED FIRE, XX INDICATES CANDELA RATING
WALL MOUNTED FIRE ALARM STROBE, CLEAR LENS,
MARKED FIRE, XX INDICATES CANDELA RATING
FIRE ALARM/MASS NOTIFICATION SPEAKER
PHOTOELECTRIC SMOKE DETECTOR
CEILING MOUNTED MASS NOTIFICATION STROBE, AMBER
LENS, MARKED ALERT, XX INDICATES CANDELA RATING WATER FLOW SWITCH
TAMPER (SUPERVISORY) SWITCH
RELAY MODULE
P
M
TVSS
XX
XX
SMOKE DETECTOR FOR DUCT; XX
INDICATES ASSOCIATED UNIT
XX
XX MASS NOTIFICATION STROBE - WALL
MOUNTED, XX INDICATES CANDELA RATING
FIRE DEPARTMENT KEY BOXKB
STARTER/DISCONNECT
LOCAL OPERATING CONSOLELOC
XXXX
MONACO RADIO ANTENNA
WALL MOUNTED FIRE ALARM/MASS NOTIFICATION
SPEAKER, WP INDICATES WEATHER PROOFWP
ASPIRATING SMOKE DETECTOR
MASS NOTIFICATION AUTONOMOUS
CONTROL UNIT
FIRE ALARM/MASS NOTIFICATION
TRANSCEIVER
Br oa dw ay
Ex ten sio n, Su ite
Ok lah om aC ity ,O
K
8-
5.8
.29
|fs b-ae
.co m
D A
TE
SI
M
UL
AT
OR
FA
CI
LI
TY
M
OD
IF
IC
AT
IO
NS
UN
ITE
DS
TA
TE
SP
RO
PE
RT
Y&
FIS
CA
LO
FF
ICE
,N
OR
TH
KIN
GS
TO
WN
,R I
AI
R
NA
TI
ON
AL
GU
AR
D rd
A
IR
L
IF
T W
IN
G
RH
OD
E
IS
LA
ND
TY
PE
B- 3-
FI
NA
L
DE
SI
GN
SU
BM
IS
SI
ON
DRAWING NO.
TWLR182167
P R
O
JE
C T
TI
TL
E:
S U
B M
IT
TA
L
LE
V E
L:
MAJ. KATHLEEN MAHONEY
PROJECT NO.
BASE ENGINEER:
NOVEMBER 12, 2018
DATE:
DRAWN BY:
S H
EE
T
TI
TL
E
S A F E
TY
B C E
U S E R
F
IR
E
E N V
IR
O
C O O R D
IN
A
TI
O N
S
IG
N A
TU
R E S
S E C U R
IT
Y
C O M M
R E V
IS
IO
N
M A R K
D A
TE
CHECKED BY:
APPROVED BY:DRAWN BY:
HO P E
STATE OF
RHODE IS L AND
GARY W. JAMES
No. 10167
REGISTERED
PROFESSIONAL ENGINEER
MECHANICAL
/5
/2
9:
:3
A
M H
:\P R
J\
\0
3- B
IM
\0
7-
FP
\7
_F
P.
rv t
FA101
FI
RE
AL
AR
M
PL
AN
LFOJME
JME LFO
SCALE: 1/8" = 1'-0"
1 FIRE ALARM & MASS NOTIFICATION PLAN
SECURE AREA ROOM SCHEDULE.
NUMBER NAME
101 SIM MOTION BAY
102 COMPUTER ROOM
103 COMPRESSOR ROOM
205 MULTI-PURPOSE
209 CORRIDOR
210 RIOS
211 BRIEFING
212 DEBRIEFING
213 MAINT OFFICE
214 MAINT SUPPORT
311 COMM
GENERAL NOTES
A. FIRE ALARM EQUIPMENT AND DEVICES SHOWN ARE
EXISTING UNLESS NOTED OTHERWISE.
B. NEWLY PROVIDED DEVICES SHALL BE
INCORPORATED INTO THE EXISTING FIRE ALARM &
MASS NOTIFICATION SYSTEM. FIRE ALARM & MASS
NOTIFICATION SYSTEM INPUT/OUTPUT FUNCTIONS
SHALL BE MODIFIED AS REQUIRED TO
ACCOMMODATE NEW FUNCTIONS. REFER TO
1/FA601.
C. FIRE ALARM EQUIPMENT AND DEVICES SHOWN
BASED ON ORIGINAL DESIGN DRAWINGS AND MAY
NOT BE INDICATIVE OF ACTUAL FIELD CONDITIONS.
CONTRACTOR SHALL FIELD VERIFY ALL
CONDITIONS AS REQUIRED.
D. PROVIDE FIRE ALARM MONITOR MODULES FOR
EACH ASPIRATING SMOKE DETECTORS AS
REQUIRED TO ANNUNCIATE LOW DETECTION
THRESHOLD, HIGH DETETCTION THRESHOLD, AND
TROUBLE CONDITIONS TO THE FIRE ALARM
SYSTEM.
E. ALL MODIFCATIONS TO THE EXISTING FIRE ALARM &
MASS NOTIFICATION SYSTEM SHALL BE
COMPLETED IN ACCORDANCE WITH UFC 3-600-01,
NFPA 70, AND NFPA 72.
SHEET KEYNOTES
1. AIR SAMPLING SMOKE DETECTOR FOR COMPUTER
ROOM SUBFLOOR, SAMPLING PORTS INSTALLED
BELOW RAISED FLOOR, AND ASSOCIATED FIRE
ALARM MONITOR MODULES FOR HIGH LEVEL
ALARM, LOW LEVEL ALARM, AND TROUBLE
CONDITION.
2. AIR SAMPLING SMOKE DETECTOR FOR COMPUTER
ROOM OCCUPIED SPACE, SAMPLING PORTS
INSTALLED AT CEILING LEVEL, AND ASSOCIATED
FIRE ALARM MONITOR MODULES FOR HIGH LEVEL
ALARM, LOW LEVEL ALARM, AND TROUBLE
CONDITION.
3. AIR SAMPLING SMOKE DETECTOR FOR SIM MOTION
BAY, SAMPLING PORTS INSTALLED AT CEILING
LEVEL, AND ASSOCIATED FIRE ALARM MONITOR
MODULES FOR HIGH LEVEL ALARM, LOW LEVEL
ALARM, AND TROUBLE CONDITION.
4. AIR SAMPLING SMOKE DETECTOR FOR COMM
ROOM, SAMPLING PORTS INSTALLED AT CEILING
LEVEL, AND ASSOCIATED FIRE ALARM MONITOR
MODULES FOR HIGH LEVEL ALARM, LOW LEVEL
ALARM, AND TROUBLE CONDITION.
5. AIR SAMPLING SMOKE DETECTOR FOR COMPUTER
ROOM SIMULATOR EQUIPMENT, PROVIDED BY
SIMULATOR MANUFACTURER. CONTRACT TO
PROVIDE ASSOCIATED FIRE ALARM MONITOR
MODULES FOR HIGH LEVEL ALARM, LOW LEVEL
ALARM, AND TROUBLE CONDITION.
6. FIRE ALARM CONTROL MODULE FOR INTERFACE TO
SECURITY SYSTEM CONTROL PANEL.
7. FIRE ALARM MANUAL PULL STATION ADJACENT TO
NEW DOOR.
8. FIRE ALARM MONITOR MODULE FOR EMERGENCY
EYEWASH STATION FLOW SWITCH.
9. RELOCATE EXISTING MONACO TRANSCEIVER
OMNIDIRECTIONAL ANTENNA ADJACENT TO FIRE
PROTECTION ROOM EXTERIOR TO BUILDING
CORNER AT GRIDLINE 1 & GRIDLINE E. WALL MOUNT
ANTENNA MOUNT KIT WITH ANTENNA AFFIXED TO 1"
MAST. ELEVATE ANTENNA 3 FEET ABOVE TOP OF
EVE. RUN ANTENNA CABLE IN 1" C. UP MAST AND
CONNECT TO ANTENNA. BOD WINEGARD PIPE
MOUNT KIT MODEL DS 3000. REUSE ANTENNA
LIGHTNING ARRESTOR KIT.
0 4' 8' 16'
1/8" = 1'-0"
ANNUNCIATION AT
LOCAL PANELS
TRANSMIT SIGNALS TO FIRE
DEPARTMENT/CENTRAL STATION
AUXILIARY
FUNCTIONS
NOTIFICATION
SIGNALS
A U
D
IO
-V
IS
U A
L
FI
R E
A
LA
R M
IN
D
IC
A
TI
O
N B
Y P
O
IN
T A
U D
IO
-V
IS
U
A L
TR
O
U B
LE
IN
D
IC
A
TI
O N
B Y
P O
IN
T
A U
D
IO
-V
IS
U A
LS
U
P E
R V
IS
O
R Y
IN
D
IC
A
TI
O
N B
Y P
O
IN
T
C O
M M
O N
TR
O
U B
LE
S
IG
N
A L
P E
R B
U
IL
D
IN
G
C O
M M
O N
S U
P E
R V
IS
O
R Y
S
IG
N A
L P
E R
B U
IL
D
IN
G
C O
M M
O N
FI
R
E A
LA
R
M P
E R
B U
IL
D
IN
G
SP
R
IN
KL
ER
W
AT
ER
FL
O
W
FA
C
IL
IT
Y
FI
R E
E V
A C
U A
TI
O
N A
U D
IO
-V
IS
U
A L
S
IG
N A
L
O V
E R
R
ID
E
FA
C
IL
IT
Y
FI
R
E E
V A
C U
A
TI
O N
V
IS
U A
L S
IG
N
A L
D U
R
IN
G M
A S
S N
O
TI
FI
C
A
TI
O N
A N
N O
U N
C E
M E
N T
A B C D E F G H I J
SYSTEM OUTPUTS
SYSTEM INPUTS
FIRE ALARMS
MANUAL FIRE ALARM PULL STATIONS
SPOT-TYPE SMOKE DETECTORS
DUCT SMOKE DETECTORS
WATERFLOW SWITCH-WET PIPE SPRINKLER SYSTEM WP-1
SUPERVISORY SIGNALS
VALVE TAMPER SWITCH
VALVE TAMPER SWITCH COVER
TROUBLE CONDITIONS
LOW BATTERY VOLTAGE
CIRCUIT FAULT
SUPERVISED COMPONENT FAILURE/TROUBLE
AC POWER FAILURE
MASS NOTIFICATION SYSTEM
MASS NOTIFICATION MIC/TAPED MESSAGE OUTPUT
LOC AHU SHUT DOWN SWITCH
X
X
X X X
X
X
X
X
X
X X
X
XXX
X
X
X
X
X
X
X
FI
R
E P
U M
P R
U N
N
IN
G
M A
S S
N O
TI
FI
C A
TI
O
N S
Y S
TE
M
O P
E R
A
TI
O N
S H
U T
D O
W N
A S
S O
C
IA
TE
D
H V
A C
U N
IT
FA
C
IL
IT
Y M
A S
S N
O
TI
FI
C
A
TI
O N
A U
D
IO
-V
IS
U A
L S
IG
N
A L
K L M N O P Q R S T
FI
R
E P
U M
P
LO
SS
O
F P
H
AS
E
FI
R
E P
U M
P P
H A
S E
R E
V E
R S
A L
U
FI
R
E
PU
M P
LO
S
S O
F
PO
W
ER
FIRE PUMP SET
FIRE PUMP MOTOR RUNNING
FIRE PUMP LOSS OF PHASE
FIRE PUMP PHASE REVERSAL
FIRE PUMP LOSS OF 480V POWER
X
X
X
X
X
X
X
X
X
X
X X
X
X
X
TR
A
IN
IN
G S
Y S
TE
M
P O
W E
R S
O U
R C
E S
H U
TD
O
W N
ASPIRATING SMOKE DETECTION - HIGH LEVEL DETECTION THRESHOLD X5
ASPIRATING SMOKE DETECTION - LOW LEVEL DETECTION THRESHOLD9
X X X
X
LO
C
A L
A
LA
R M
FO
R
TR
A
IN
IN
G S
Y S
TE
M
O P
E R
A
TO
R S
X
WATERFLOW SWITCH-WET PIPE SPRINKLER SYSTEM WP-2 X X
X
X X X
A C
TI
V
A
TE
FI
R
E A
LA
R
M /S
E C
U R
IT
Y
S Y
S
TE
M
IN
E R
FA
C
E R
E
LA
Y C
O N
TR
O
L M
O D
U
LE
X
X
X
X
X
NOTE: INPUT/OUTPUT MATRIX INDICATIVE OF ALL FUNCTIONS OF EXISTING FIRE ALARM/MASS NOTIFICATION SYSTEM. SYSTEM FUNCTIONALITY LISTED IS INCLUSIVE OF FUNCTIONS NOT NECESSARILY INCLUDED IN THIS SCOPE OF WORK. VERIFY AND MAINTAIN PREVIOUS FUNCTION WHILE ADDING NEW FUNCTIONS REQUIRED BY THIS SCOPE.
EMERGENCY EYEWASH OPERATION X X
16 ASPIRATING SMOKE DETECTION - TROUBLE XX
Br oa dw ay
Ex ten sio n, Su ite
Ok lah om aC ity ,O
K
8-
5.8
.29
|fs b-ae
.co m
D A
TE
SI
M
UL
AT
OR
FA
CI
LI
TY
M
OD
IF
IC
AT
IO
NS
UN
ITE
DS
TA
TE
SP
RO
PE
RT
Y&
FIS
CA
LO
FF
ICE
,N
OR
TH
KIN
GS
TO
WN
,R I
AI
R
NA
TI
ON
AL
GU
AR
D rd
A
IR
L
IF
T W
IN
G
RH
OD
E
IS
LA
ND
TY
PE
B- 3-
FI
NA
L
DE
SI
GN
SU
BM
IS
SI
ON
DRAWING NO.
TWLR182167
P R
O
JE
C T
TI
TL
E:
S U
B M
IT
TA
L
LE
V E
L:
MAJ. KATHLEEN MAHONEY
PROJECT NO.
BASE ENGINEER:
NOVEMBER 12, 2018
DATE:
DRAWN BY:
S H
EE
T
TI
TL
E
S A F E
TY
B C E
U S E R
F
IR
E
E N V
IR
O
C O O R D
IN
A
TI
O N
S
IG
N A
TU
R E S
S E C U R
IT
Y
C O M M
R E V
IS
IO
N
M A R K
D A
TE
CHECKED BY:
APPROVED BY:DRAWN BY:
HO P E
STATE OF
RHODE IS L AND
GARY W. JAMES
No. 10167
REGISTERED
PROFESSIONAL ENGINEER
MECHANICAL
/5
/2
9:
:3
A
M H
:\P R
J\
\0
3- B
IM
\0
7-
FP
\7
_F
P.
rv t
FA601
FI
RE
AL
AR
M
M
AS
S
NO
TI
FC
AT
IO
N
IN
PU
T/
O
UT
PU
T
M
AT
RI
X
LFOJME
JME LFO
SCALE:NTS
1 FIRE ALARM & MASS NOTIFICATION INPUT/OUTPUT MATRIX
INSTRUCTOR'S
OPEN OFFICE
MULTI-PURPOSE
ADMIN
SITE MGR
COR OFFICE
LMPTT ROOM
COMPUTER
ROOM
SIM MOTION
BAY
COMPRESSOR
ROOM
ELEC
COMM
MECH
MAINT
SUPPORT
DEBRIEFING
MAINT
OFFICE
CORRIDOR
BRIEFING
RIOS
FIRE PROT
CBT/CPT
WOMENS
305B
MENS
305A
COPY
STOR
206B
STOR
206A
BREAK
JAN
A
E
A.9
1 8 9
B.1
2 3 4 5
D.1
B
D
6 7
C
B
BA
COORDINATE LOCATION
AND TERMINATION OF
BREATHING AIR DROP
WITH FLIGHT SIMULATOR
EQUIPMENT PROVIDER
DEMO EXISTING BREATHING
AIR PIPING AND REPLACE
WITH NEW 1/4" STAINLESS
STEEL.
EXISTING 3/4"
COLD WATER
4 4
EXISTING 3/4"
COLD WATER
3/4"
3/4"
1 1/2"
DRAIN
AFF
FLOOR
UNION, TYPICAL
1. BREATHING AIR PIPING SHALL BE
SUBMITTED UNDER SPECIFICATION
NUMBER 226113. THE SYSTEM
PROVIDED WILL BE A TURNKEY
SOLUTION WHICH INCLUDES ALL
PIPING AND COMPONENTS AS
INDICATED BY DETAIL 2/M-501. THE
SYSTEM SHALL PROVIDE GRADE E
QUALITY BREATHING AIR TO THE
SIMULATOR. STAINLESS STEEL PIPING
PROVIDED DOWNSTREAM OF THE
REGULATOR SHALL BE RATED FOR
GRADE E BREATHING AIR AND A
MINIMUM OF 500 PSIG. FITTINGS SHALL
BE SWAGELOK OR APPROVED EQUAL.
2. ROUTE ALL DRAIN LINES TO NEAREST
FLOOR DRAIN AND DISCHARGE THRU
AIR GAP.
3. COORDINATE LOCATION OF
EQUIPMENT WITH EXISTING FLOOR
DRAINS, CLEANOUTS, ETC.
BA
PACKAGED BREATHING
AIR SYSTEM, SET TO
CYCLE BETWEEN 3000
AND 4000 PSIG
NEW 1/4" STAINLESS STEEL BREATHING AIR PIPING, VALVE AND CAP INSIDE
COMPRESSOR ROOM FOR FUTURE COMPRESSED AIR SYSTEM. REFER TO 1/P-101
FOR CONTINUATION.
BA
P
BA
ISOLATION VALVE, TYPICAL
CGA-347 VALVE (TYPICAL OF 2)
UN ISO 4500 PSIG STORAGE CYLINDER,
SECURE TO WALL WITH WALL MOUNT
TRACK AND CYLINDER CLAMPS
0-7500 PSIG, 2 1/2" GAUGE FACE (INPUT/STORAGE PRESSURE)
FULLY ADJUSTABLE REGULATOR
(SET TO 300 PSIG)
NOTES:
P
1/4"
0-600 PSIG, 2 1/2" GAUGE FACE (REGULATED PRESSURE)
BALANCE OF PIPING, AIR COMPRESSOR, AND ALL ASSOCIATED VALVES AND
EQUIPMENT TO BE INSTALLED AT LATER DATE BY OWNER.
FLOOR
UNION (TYP)
Y-STRAINER (100 MESH)
80°F
BRADLEY MODEL S19224B WALL MOUNT EYEWASH WITH STAINLESS STEEL BOWL
ROUTE 1 1/2" DRAIN TO FLOOR DRAIN IN ROOM 103, REFER TO PLAN
KELTECH HL SERIES TANKLESS
WATER HEATER, 480V 3 PHASE
18 KW WITH NEMA-1 ENCLOSURE
AND Y-STRAINER
BRADLEY S19-2000 THERMOSTATIC MIXING
VALVE WITH COLD WATER BYPASS, DIAL
THERMOMETER AND WALL MOUNTING
BRACKET, SET TO 75° F
C W
REFER TO PLAN
3/4"
1. COORDINATE LOCATION OF EQUIPMENT
WITH STRUCTURAL BRACING.
3/4"
NOTES:
BRADLEY S19-324E EMERGENCY
SIGNALING SYSTEM, CONNECT
TO EMCS. EYEWASH OPERATION
SHALL SHALL BE MONITORED BY
FIRE ALARM SYSTEM, REFER TO
FA101.
Br oa dw ay
Ex ten sio n, Su ite
Ok lah om aC ity ,O
K
8-
5.8
.29
|fs b-ae
.co m
D A
TE
SI
M
UL
AT
OR
FA
CI
LI
TY
M
OD
IF
IC
AT
IO
NS
UN
ITE
DS
TA
TE
SP
RO
PE
RT
Y&
FIS
CA
LO
FF
ICE
,N
OR
TH
KIN
GS
TO
WN
,R I
AI
R
NA
TI
ON
AL
GU
AR
D rd
A
IR
L
IF
T W
IN
G
RH
OD
E
IS
LA
ND
TY
PE
B- 3-
FI
NA
L
DE
SI
GN
SU
BM
IS
SI
ON
DRAWING NO.
TWLR182167
P R
O
JE
C T
TI
TL
E:
S U
B M
IT
TA
L
LE
V E
L:
MAJ. KATHLEEN MAHONEY
PROJECT NO.
BASE ENGINEER:
NOVEMBER 12, 2018
DATE:
DRAWN BY:
S H
EE
T
TI
TL
E
S A F E
TY
B C E
U S E R
F
IR
E
E N V
IR
O
C O O R D
IN
A
TI
O N
S
IG
N A
TU
R E S
S E C U R
IT
Y
C O M M
R E V
IS
IO
N
M A R K
D A
TE
CHECKED BY:
APPROVED BY:DRAWN BY:
HO P E
STATE OF
RHODE IS L AND
GARY W. JAMES
No. 10167
REGISTERED
PROFESSIONAL ENGINEER
MECHANICAL
/2
/2
3:
:3
PM
H :\P
R J\
\0 3-
B
IM
\0 6-
Pl bg
\7
_P lb g.
rv t
P-101
G
RO
UN
D
FL
O
O R
PL
UM
BI
NG
PL
AN
RRSWBB
WBB RRS
SCALE: 3/16" = 1'-0"
1 GROUND FLOOR PLUMBING PLAN
N
SHEET KEYNOTES
1. PACKAGED BREATHING AIR COMPRESSOR SYSTEM,
BAUER MODEL NUMBER mVT8-E3. 5000 PSIG, 8.4
CFM CHARGING RATE, THREE STAGE
COMPRESSOR, 7.5 HP 3 PHASE/460 VOLT MOTOR
WITH STARTER. PLC BASED CONTROLLER WITH
PROGRAMMABLE PARAMETERS TO CUSTOM SET
OPERATION FOR IDEAL SITUATION, P2 SECURUS
ELECTRONIC MOISTURE MONITORING SYSTEM
PROCESSES 67,000 CUBIC FEET OF AIR BETWEEN
CARTRIDGE CHANGES, AUTOMATIC CONDENSATE
DRAIN WITH COLLECTION RESERVOIR, HIGH
TEMPERATURE AND LOW OIL PRESSURE SWITCH
WITH FAULT NOTIFICATION AND SHUTDOWN, UL
LISTED ELECTRICAL ASSEMBLY WITH NEMA 4
ENCLOSURE, PRESSURE SWITCH FOR AUTOMATIC
START/STOP CONTROL, EMERGENCY STOP
BUTTON. PROVIDE OPTIONAL CO MONITOR. REFER
TO 2 / P-101.
2. VALVE AND CAP NEW BREATHING AIR PIPING
INSIDE COMPRESSOR ROOM. REFER TO 2 / P-101
FOR PIPING AT BREATHING AIR SYSTEM.
3. EXTEND 3/4" COLD WATER THROUGH BALL VALVE
TO HUMIDIFIER CONNECTION ON MECHANICAL UNIT.
4. DEMO EXISTING COLD WATER SERVING
MECHANICAL UNITS WHICH ARE BEING RELOCATED.
5. STORAGE CYLINDER SECURED TO WALL.
6. DISCHARGE DRAIN FROM EYEWASH TO FLOOR
DRAIN THROUGH AIR GAP.
7. EMERGENCY EYEWASH, REFER TO 3 / P-101.
8. THERMOSTATIC MIXING VALVE, REFER TO 3 / P-101.
9. TANKLESS WATER HEATER, REFER TO 3 / P-101.
SCALE:NTS
2 BREATHING AIR PIPING SCHEMATIC
SCALE:NTS
3 EMERGENCY EYEWASH PIPING SCHEMATIC
4' 12'8'0
3/16" = 1'-0"
EE
D.1D.1
DD
CC
B.1B.1
ELEC
EMM ROOM
1 1
VTRAT
BRIEFING
BRIEFING
MAINT OFFICE
SIM MOTION BAY
COMM
MECH
MAINT SUPPORT
COMPUTER ROOM
CRAC-04CRAC-03
B ro ad wa y E xte ns ion
, S uit e 5
Ok lah om a C ity , O
K
8-
5.8
.29
| f sb -a e.c om
D A
TE
SI
M
UL
AT
OR
F
AC
IL
IT
Y
M
OD
IF
IC
AT
IO
NS
UN
ITE
D S
TA
TE
S P
RO
PE
RT
Y &
FIS
CA
L O
FF
ICE
, N
OR
TH
KI
NG
ST
OW
N, RI
AI
R
NA
TI
ON
AL
G
UA
RD
rd
A
IR
L
IF
T W
IN
G
RH
OD
E
IS
LA
ND
TY
PE
B -3
FI
NA
L
DE
SI
GN
S
UB
M
IS
SI
ON
DRAWING NO.
TWLR182167
P R
O
JE
C T
TI
TL
E
S U
B M
IT
TA
L
LE
V E
L:
MAJ. KATHLEEN MAHONEY
PROJECT NO.
BASE ENGINEER:
NOVEMBER 12, 2018
DATE:
DRAWN BY:
S H
EE
T
TI
TL
E
S A F E
TY
B C E
U S E R
F
IR
E
E N V
IR
O
C O O R D
IN
A
TI
O N
S
IG
N A
TU
R E S
S E C U R
IT
Y
C O M M
R E V
IS
IO
N
M A R K
D A
TE
CHECKED BY:
APPROVED BY:DRAWN BY:
HO P E
STATE OF
RHODE IS L AND
GARY W. JAMES
No. 10167
REGISTERED
PROFESSIONAL ENGINEER
MECHANICAL
/5
/2
9:
:1
A
M H
:\P R
J\
\0
3- B
IM
\0
5- M ec h\
0_ M ec h.
rv t
MD101
M
EC
HA
NI
CA
L
DE
M
O
LI
TI
O
N
KJWRRS
RRS RRS
SCALE: 3/16" = 1'-0"
1 MECHANICAL DEMOLITION PLAN
GENERAL NOTES
1. CONTRACTOR SHALL FIELD VERIFY EXISTING
CONDITIONS PRIOR TO STARTING WORK.
SHEET KEYNOTES
1. REMOVE AND RELOCATE EXISTING CRAC UNIT
TO LOCATIONS SHOWN ON MH101. DISCONNECT
POWER, DRAINAGE AND CHILLED WATER.
2. CAP EXISTING PIPING WHERE REMOVED AND
REINSULATE AS REQUIRED.
3. DEMOLISH EXISTING PIPING AND INSULATION AS
REQUIRED TO ACCOMODATE NEW FLEXIBLE
CONNECTION.
4. DEMOLISH EXISTING DUCTWORK AS INDICATED
TO ACCOMODATE NEW SECURE DUCT
PENETRATION.
5. REMOVE AND RELOCATE EXISTING VAV BOX TO
LOCATION SHOWN ON MH101.
6. REMOVE AND RELOCATED EXISTING HUMIDIFER
DISPSERSION GRID TO LOCATION INDICATED ON
MH101.
7. DEMOLISH EXISTING FIRE DAMPER AND
DUCTWORK AS INDICATED
8. REMOVE AND RELOCATE EXISTING RETURN AIR
GRILLE WHERE LOCATED ON MH101.
9. DEMOLISH EXISTING DUCTWORK AS INDICATED.
N
T
EE
D.1D.1
DD
CC
B.1B.1
BB
A.9A.9
AA
M-401
22"x20" 24"x24"
22"x20"22"x20"
8"x8"
24"x24"
22"x20"
FD
FD
FD
FD
AD
AD
AD
AD
8"ø
30"x30"
46"x20"
24"x24"
6"x10"
TYP.
BRIEFING
RIOS
210CBT/CPT
DEBRIEFING
MAINT
OFFICE
COMPUTER
ROOM
SIM MOTION
BAY
COMPRESSOR
ROOM
ELEC
COMM
MECH
MAINT
SUPPORT
A-6
A-6
B-2
FCU-01
12"x14"
12"x14"
L-11
16"x16"
L-12
B-2
400 CFM
B ro ad wa y E xte ns ion
, S uit e 5
Ok lah om a C ity , O
K
8-
5.8
.29
| f sb -a e.c om
D A
TE
SI
M
UL
AT
OR
F
AC
IL
IT
Y
M
OD
IF
IC
AT
IO
NS
UN
ITE
D S
TA
TE
S P
RO
PE
RT
Y &
FIS
CA
L O
FF
ICE
, N
OR
TH
KI
NG
ST
OW
N, RI
AI
R
NA
TI
ON
AL
G
UA
RD
rd
A
IR
L
IF
T W
IN
G
RH
OD
E
IS
LA
ND
TY
PE
B -3
FI
NA
L
DE
SI
GN
S
UB
M
IS
SI
ON
DRAWING NO.
TWLR182167
P R
O
JE
C T
TI
TL
E
S U
B M
IT
TA
L
LE
V E
L:
MAJ. KATHLEEN MAHONEY
PROJECT NO.
BASE ENGINEER:
NOVEMBER 12, 2018
DATE:
DRAWN BY:
S H
EE
T
TI
TL
E
S A F E
TY
B C E
U S E R
F
IR
E
E N V
IR
O
C O O R D
IN
A
TI
O N
S
IG
N A
TU
R E S
S E C U R
IT
Y
C O M M
R E V
IS
IO
N
M A R K
D A
TE
CHECKED BY:
APPROVED BY:DRAWN BY:
HO P E
STATE OF
RHODE IS L AND
GARY W. JAMES
No. 10167
REGISTERED
PROFESSIONAL ENGINEER
MECHANICAL
/5
/2
9:
:1
A
M H
:\P R
J\
\0
3- B
IM
\0
5- M ec h\
0_ M ec h.
rv t
MH101
HV
AC
P
LA
N
KJWRRS
RRS RRS
SCALE: 3/16" = 1'-0"
1 HVAC PLAN
GENERAL NOTES
1. CONTRACTOR SHALL FIELD VERIFY EXISTING
CONDITIONS PRIOR TO STARTING WORK.
SHEET KEYNOTES
1. PROVIDE DUCT PENETRATION DETAIL FOR
SECURE AREA IN ACCORDANCE WITH DETAIL 2,
M-501.
2. PROVIDE DUCT PENETRATION DETAIL FOR
SECURE AREA IN ACCORDANCE WITH DETAIL 3,
M-501.
3. PROVIDE DUCT PENETRATION DETAIL FOR
SECURE AREA IN ACCORDANCE WITH DETAIL 4,
M-501.
4. PROVIDE DUCT PENETRATION DETAIL FOR
SECURE AREA IN ACCORDANCE WITH DETAIL 5,
M-501.
5. PROVIDE DUCT PENETRATION DETAIL FOR
SECURE AREA IN ACCORDANCE WITH DETAIL 6,
M-501.
6. RELOCATED HUMIDIFIER DISPERSION GRID.
7. RELOCATED RETURN GRILLE, BALANCE TO
AIRFLOW INDICATED.
8. RELOCATED VAV BOX. REBALANCE VAV BOX
FOR 135 CFM MAXIMUM FLOW AND 90 CFM
MINIMUM AND HEATING FLOW.
9. 16 PERFORATED FLOOR TILES FOR RAISED
FLOOR. COORDINATE LOCATIONS WITH FLIGHT
SIMULATOR PROVIDER. SELECTION BASED ON
TATE PERF 800 AIR FLOW PANEL WITH 560 CFM
AT 0.07" W.C. PRESSURE DROP. IF ALTERNATE
MANUFACTURER PROVIDED, LIMIT PRESSURE
DROP TO SAME AS DESIGN AND PROVIDE MORE
PERFORATED FLOOR TILES AS REQUIRED.
10. BALANCE EXISTING VAV BOX TO 200 CFM
MAXIMUM FLOW AND 90 CFM MINIMUM AND
HEATING FLOW.
11. INSTALL FAN COIL UNIT IN ACCORDANCE WITH
DETAIL 7, M-501.
12. OPPOSED BLADE CONTROL DAMPER.
N
SDSD
T
T
EE
D.1D.1
DD
CC
B.1B.1
BB
A.9A.9
AA
1 1/2"
3/4"
HWR
3/4"
HWS
DEBRIEFING
BRIEFING
RIOS
CORR…
This is the start of the file's text. The full file is on GovTribe.