QUESTIONS AND ANSWERS
W912L2-16-B-2001 – RPR Main Gate (Valencia Gate)
22Jun16
Q1. Keynotes 1, 9, 10, 11, 13, 14, 15, 16, 17, and 18 on Detail 1/g2.0 are not shown on the Keynote
Legend. Please provide the information for the missing Keynotes.
A1.
1. A1. Hinge Post Assembly
2. Hinge End Top Plate Assembly.
3. Not used.
4. Shaft Collar
5. Pillow block
6. Not Used
7. Not Used
8. Not Used
9. Not Used
10. Not Used
11. Latch Post Assembly
12. Manual Latch Pin
13. Cable Eye Cushion
14. Not Used
15. Not Used
16. Not Used
17. Yoke assembly with Tube Clamps
18. Crash Cable Assembly
19. Crash Tube
20. Tape, Red Reflective
Q2. Keynotes 2, 3, 4, and 5 on the Keynote Legend on Detail 1/g2.0 do not appear to correspond to the
Keynotes on the Detail. Is the Keynote Legend correct?
A2. These are General Notes, not keynotes.
Q15. C2.0 note 9 calls to relocate the light pole, please provide a structural detail for the pole base.
A15. See Attached detail.
Q16. Please provide the structural requirements for the CMU columns on the relocated monument sign.
Please include architectural details also.
A16. CMU piers shall be 16”x16” with 4-#5 rebar, one each cell. Provide #2 pencil rod ties at 16” o.c.
vertical. Provide 12” thick x 3’wide x 10’-0” long concrete footing reinforced with 4-#5 x cont.
reinforcing long dimension with #4 cross reinforcing at 24” o.c. perpendicular. Relocate existing marquee sign and support beams. Extend existing power to new sign.
Q34. The Light Pole Detail on Sheet e001 says to “See Structural Details for Additional Information” and to “See Structural Calculations for More Information”. There are no Structural Drawings in the set.
Please provide the missing information.
A34. See attached detail.