EXHIBIT F
PROPOSAL INQUIRY FORMAT
SOLICITATION W912K6-15-R-0008
NOTE: ALL PRE-PROPOSAL INQUIRIES SHALL BE SUBMITTED VIA EMAIL IN THIS FORMAT!!
EMAIL: 175WG.MSC@ang.af.mil
Date of RFI Response: _19 Aug 2015_
1. We see the requirement for R-value of 24 on the low roof section, is this a average R-value or is this a minimum R-value?
The R-value shall be a minimum average of 24.
2. Can a high density ISO cover board be used instead of the dens deck cover board?
The Government prefers to use the dens deck cover board and will not use the high density ISO cover boards.