Building 9310.pdf

PDF 131 KB Posted

Attached to
Replace HVAC Systems LDC Fort Stewart GA
Solicitation number
W912JM25QA020
Issued by

About this file

This document is a two-page architectural plan for Building 9310, detailing demolition and new work for an HVAC system upgrade. The demolition plan involves removing existing ceiling boxes, exposed Romex wiring, 12 incandescent fixtures, and switches, while preserving the existing ½" plywood backing and exterior fire light. The building's interior walls and ceiling will be partially sprayed with open-cell foam insulation.

The new work plan specifies installing a mini-split system with specific Friedrich model components: a 24,000 BTUH, 208/230V inverter (FPHMR24A3A) and an air handler (FPHFW24A3B), mounted at 7'-6" above finished floor. Additional improvements include six 8' weatherproof LED fixtures with new EMT conduit conductors, a double-gang cast box with two 20A switches, and an exterior NEMA 3R disconnect with a GFIC. The inverter will be mounted on an exterior metal rack at 2'-0" above grade, with line sets routed externally and covered with a mill-finished aluminum cover. The work will be powered from the existing 100 AMP main panel.

View the file

Other files

File Type Posted
10324 Inside unit.jpg JPG image
9310 wall to install new HVAC system.jpg JPG image
10324 Inside.jpg JPG image
10324 Fire Alarm Control Panel.pptx PPTX presentation
10324 Outside unit.jpg JPG image
Replace HVAC Units Plenum Box Bldg 10324.pdf PDF
SCOPE OF WORK REPLACE HVAC LDC.docx DOCX document
Solicitation - W912JM25QA020.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EXISTING 100 AMP

MAIN PANEL

REMOVE AND DISPOSE OF EXISTING CEILING

BOXES, EXPOSED ROMEX WIRING AND

INCANDESCENT FIXTURES (TYPICAL 12

FIXTURES)

EXISTING ½” PLYWOOD BACKING TO

REMAIN (FOR NEW MINI-SPLIT UNIT

- 4'’0" X 4'-5")

BUILDING INTERIOR WALLS AND CEILING SPRAYED WITH

OPEN-CELL FOAM INSULATION. REMOVE ONLY PORTIONS

NECESSARY TO ACCOMPLISH REQUIRED WORK.

R O

LL

-U

P D

O O

R

REMOVE EXISTING SWITCHES AND INSTALL

BLANK COVER OVER BOX. SEE NEW WORK PLAN

FOR LOCATION FOR NEW SWITCHES AND BOX

EXISTING EXTERIOR FIRE

LIGHT TO REMAIN

48'-8"

DEMO & EXISTING PLAN

BUILDING NO. 9310

SCALE: ¼” = 1'-0"

GFIGFI

PROVIDE AND INSTALL SIX (6) EACH 8'

WEATHERPROOF LED FIXTURES WITH

NEW CONDUCTORS IN EMT CONDUIT

WITH COMPRESSION FITTINGS. ATTACH

TO EXISTING WOOD JOIST PROVIDE AND INSTALL DOUBLE GANG CAST BOX

(SURFACE MOUNTED) W/TWO 20A SWITCHES

TO EXPOSED DOUBLE STUDS AT APPROX. 2'-8"

RIGHT OF EXISTING SWITCH. NEW DROP IN EMT

TO EXISTING EXTERIOR FIRE LIGHT

EXISTING 100 AMP MAIN PANEL

IN

V

ER

TE

R

A

IR

H A

N D

LE

R

R O

LL

-U

P D

O O

R

PROVIDE AND INSTALL MINI-SPLIT UNIT AND MOUNT ON EXISTING PLYWOOD SURFACE AT 7'-6" AFF. INVERTER TO BE INSTALLED ON EXTERIOR METAL RACK AT 2'-0" ABOVE EXISTING GRADE AND MOUNTED TO EXISTING STRUCTURE. LINE SETS SHALL BE ROUTED IN MOST DIRECT METHOD ON EXTERIOR AND COVERED WITH MILL FINISHED ALUMINUM COVER (ENCLOSING LINE SETS AND CONDENSATE DRAIN). PROVIDE EXTERIOR NEMA 3R DISCONNECT WITH LIQUID FLEX TO INVERTER AND EXTERIOR GFIC WITH PROTECTIVE COVER (FOR SERVICING). FEED FROM EXISTING PANEL. INVERTER TO BE 24,000 BTUH, 208/230V, FRIEDRICH MODEL FPHMR24A3A. AIR HANDLER TO BE FRIEDRICH MODEL FPHFW24A3B (INSTALLED AT 7'-6" AFF TO BOTTOM OF UNIT). BREAKER PROVIDE IN PANEL FOR INVERTER UNIT.

NEW WORK PLAN

BUILDING NO. 9310

SCALE: ¼” = 1'-0"

Building 9310.vsdx
Page-1
Page-2