RFI Q&A – Install Explosion Proof Receptacles (W912JB-19-R-5021)

1) Are exact quantities for explosion proof receptacles going to be posted on fbo?

A. There are 13 devices in the bay which must be made Class 1 explosion proof

2) What is the load schedule and branch circuits for the receptacles?

A. 13 devices in the bay which must be made Class 1 explosion proof, in accordance with technical order 1-1-3., NFPA 70, UFC 4-211-01 and ETL 98-8, and are required to be GFCI protected. 7 of which are 120volt 20amp and 6 which are 220volt single phase. (3wire twist lock).

3) Can you provide any info regarding the to be installed receptacles load requirements such amps,voltage,phase either single or 3 phase requirements?

A. Basis of design receptacle is listed in the statement of work. (meet or exceed the specified Appleton EBR Receptacles with interlocked circuit breaker)