REPAIR_TRANSFORMER_RFI'S_1.pdf
PDF 283 KB Posted
- Attached to
- Repair Transformers Federal contract opportunity
- Solicitation number
- W912JB-19-B-5009
About this file
RFI's 1st Addition
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Bid_Opening_Abstract_Trans_2.pdf | ||
| Bid_Sign_In_Sheet.pdf | ||
| Bid_Opening_Abstract.pdf | ||
| W912JB-19-B-5009_Solicitation_Amendment_0002.pdf | ||
| Site_Visit_Minutes_Transformer_2nd_Site_Visit.pdf | ||
| 2nd_Sign_In_Sheet.pdf | ||
| Sign_In_Sheet.pdf | ||
| Site_Visit_Minutes_Transformer.pdf | ||
| W912JB-19-B-5009_Solicitation_Amendment_0001.pdf | ||
| Presolicitation_Announcement_Repair_Transformers.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
W912JB-19-B-5009
REPAIR ELECTRICAL TRANSFORMERS
RFI’S 1st Addition
1. Drawings do not indicate this, but does any of the sites require low profile equipment?
None known
2. Will the work at the individual sites be one at a time, in a certain order, or expected to be done concurrently?
Awarded contractor will provide the Government a schedule 3064 how they are to perform the work, secure areas will need escorts.
3. Will we be held responsible to repair or replace fencing? And if so, is there a required fencing to be used, or replace with the same?
Follow drawings and specs for fence and slab demolition.
4. Do any of the sites have means to connect a generator currently?
Follow Plans and specs for Generator Connections.
3.11 INTERRUPTION OF SERVICE AND ADDITIONAL REQUIREMENT
A. Perform any interruption of service at a time approved in advance by the Owner’s Engineer so as not to interfere with the present building operations. Contractor shall notify the Owner’s
Engineer of the electrical systems involved, area affected and duration of outage.
B. Some areas may not be shut down except for temporary and new service tie-ins. Coordinate all
Shutdowns with the Owner’s Representative. If any service serving this area is severed or
Disconnected unintentionally, the Contractor shall immediately notify the Owner’s
Representative and work continuously until the service is restored. While the documents show
Some service connections, it is the Contractor’s responsibility, prior to bid, to thoroughly
Investigate this area and have a complete understanding of all the systems serving the area