TIA-607-B September 2011

Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises

ANSI/TIA-607-B-2011

APPROVED: AUGUST 26, 2011

NOTICE

TIA Engineering Standards and Publications are designed to serve the public interest through eliminating misunderstandings between manufacturers and purchasers, facilitating interchangeability and improvement of products, and assisting the purchaser in selecting and obtaining with minimum delay the proper product for their particular need. The existence of such Standards and Publications shall not in any respect preclude any member or non-member of TIA from manufacturing or selling products not conforming to such Standards and Publications. Neither shall the existence of such Standards and Publications preclude their voluntary use by Non-TIA members, either domestically or internationally.

Standards and Publications are adopted by TIA in accordance with the American National Standards Institute (ANSI) patent policy. By such action, TIA does not assume any liability to any patent owner, nor does it assume any obligation whatever to parties adopting the Standard or Publication.

This Standard does not purport to address all safety problems associated with its use or all applicable regulatory requirements. It is the responsibility of the user of this Standard to establish appropriate safety and health practices and to determine the applicability of regulatory limitations before its use.

(From Standard Proposal No. 3-4351-RV2-2, formulated under the cognizance of the TIA TR-42 Telecommunications Cabling Systems, TR-42.16 Subcommittee on Premises Telecommunications Bonding & Grounding).

Published by

©TELECOMMUNICATIONS INDUSTRY ASSOCIATION

Standards and Technology Department 2500 Wilson Boulevard

Arlington, VA 22201 U.S.A.

PRICE: Please refer to current Catalog of

TIA TELECOMMUNICATIONS INDUSTRY ASSOCIATION STANDARDS

AND ENGINEERING PUBLICATIONS

or call IHS, USA and Canada

(1-877-413-5187) International (303-397-2896) or search online at http://www.tiaonline.org/standards/catalog/

All rights reserved Printed in U.S.A.

NOTICE OF COPYRIGHT

This document is copyrighted by the TIA.

Reproduction of these documents either in hard copy or soft copy (including posting on the web) is prohibited without copyright permission. For copyright permission to reproduce portions of this document, please contact the TIA Standards Department or go to the TIA website (www.tiaonline.org) for details on how to request permission. Details are located at:

http://www.tiaonline.org/standards/catalog/info.cfm#copyright or

Telecommunications Industry Association Technology & Standards Department

2500 Wilson Boulevard, Suite 300 Arlington, VA 22201 USA

+1.703.907.7700

Organizations may obtain permission to reproduce a limited number of copies by entering into a license agreement. For information, contact

IHS

15 Inverness Way East

Englewood, CO 80112-5704 or call

USA and Canada (1.800.525.7052) International (303.790.0600)

NOTICE OF DISCLAIMER AND LIMITATION OF LIABILITY

The document to which this Notice is affixed (the “Document”) has been prepared by one or more Engineering Committees or Formulating Groups of the Telecommunications Industry Association (“TIA”). TIA is not the author of the Document contents, but publishes and claims copyright to the Document pursuant to licenses and permission granted by the authors of the contents.

TIA Engineering Committees and Formulating Groups are expected to conduct their affairs in accordance with the TIA Engineering Manual (“Manual”), the current and predecessor versions of which are available at http://www.tiaonline.org/standards/procedures/manuals/TIA’s function is to administer the process, but not the content, of document preparation in accordance with the Manual and, when appropriate, the policies and procedures of the American National Standards Institute (“ANSI”). TIA does not evaluate, test, verify or investigate the information, accuracy, soundness, or credibility of the contents of the Document. In publishing the Document, TIA disclaims any undertaking to perform any duty owed to or for anyone.

If the Document is identified or marked as a project number (PN) document, or as a standards proposal (SP) document, persons or parties reading or in any way interested in the Document are cautioned that: (a) the Document is a proposal;

(b) there is no assurance that the Document will be approved by any Committee of TIA or any other body in its present or any other form; (c) the Document may be amended, modified or changed in the standards development or any editing process.

The use or practice of contents of this Document may involve the use of intellectual property rights (“IPR”), including pending or issued patents, or copyrights, owned by one or more parties. TIA makes no search or investigation for IPR.

When IPR consisting of patents and published pending patent applications are claimed and called to TIA’s attention, a statement from the holder thereof is requested, all in accordance with the Manual. TIA takes no position with reference to, and disclaims any obligation to investigate or inquire into, the scope or validity of any claims of IPR. TIA will neither be a party to discussions of any licensing terms or conditions, which are instead left to the parties involved, nor will TIA opine or judge whether proposed licensing terms or conditions are reasonable or non-discriminatory. TIA does not warrant or represent that procedures or practices suggested or provided in the Manual have been complied with as respects the Document or its contents.

If the Document contains one or more Normative References to a document published by another organization (“other SSO”) engaged in the formulation, development or publication of standards (whether designated as a standard, specification, recommendation or otherwise), whether such reference consists of mandatory, alternate or optional elements (as defined in the TIA Engineering Manual, 4th edition) then (i) TIA disclaims any duty or obligation to search or investigate the records of any other SSO for IPR or letters of assurance relating to any such Normative Reference; (ii) TIA’s policy of encouragement of voluntary disclosure (see Engineering Manual Section 6.5.1) of Essential Patent(s) and published pending patent applications shall apply; and (iii) Information as to claims of IPR in the records or publications of the other SSO shall not constitute identification to TIA of a claim of Essential Patent(s) or published pending patent applications.

TIA does not enforce or monitor compliance with the contents of the Document. TIA does not certify, inspect, test or otherwise investigate products, designs or services or any claims of compliance with the contents of the Document.

ALL WARRANTIES, EXPRESS OR IMPLIED, ARE DISCLAIMED, INCLUDING WITHOUT LIMITATION, ANY AND ALL WARRANTIES CONCERNING THE ACCURACY OF THE CONTENTS, ITS FITNESS OR APPROPRIATENESS FOR A PARTICULAR PURPOSE OR USE, ITS MERCHANTABILITY AND ITS NONINFRINGEMENT OF ANY THIRD PARTY’S INTELLECTUAL PROPERTY RIGHTS. TIA EXPRESSLY DISCLAIMS ANY AND ALL RESPONSIBILITIES FOR THE ACCURACY OF THE CONTENTS AND MAKES NO REPRESENTATIONS OR WARRANTIES REGARDING THE CONTENT’S COMPLIANCE WITH ANY APPLICABLE STATUTE, RULE OR REGULATION, OR THE SAFETY OR HEALTH EFFECTS OF THE CONTENTS OR ANY PRODUCT OR SERVICE REFERRED TO IN THE DOCUMENT OR

PRODUCED OR RENDERED TO COMPLY WITH THE CONTENTS.

TIA SHALL NOT BE LIABLE FOR ANY AND ALL DAMAGES, DIRECT OR INDIRECT, ARISING FROM OR RELATING TO ANY USE OF THE CONTENTS CONTAINED HEREIN, INCLUDING WITHOUT LIMITATION ANY AND ALL INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES (INCLUDING DAMAGES FOR LOSS OF BUSINESS, LOSS OF PROFITS, LITIGATION, OR THE LIKE), WHETHER BASED UPON BREACH OF CONTRACT, BREACH OF WARRANTY, TORT (INCLUDING NEGLIGENCE), PRODUCT LIABILITY OR OTHERWISE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. THE FOREGOING NEGATION OF DAMAGES IS A FUNDAMENTAL ELEMENT OF THE USE OF THE CONTENTS HEREOF, AND THESE CONTENTS WOULD NOT BE

PUBLISHED BY TIA WITHOUT SUCH LIMITATIONS.

ANSI/TIA-607-B

i

Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises

Table of Contents

1 SCOPE

2 Normative references

3 DEFINITIONS

3.1 General

3.2 Definition of terms

3.3 Abbreviations and acronyms

3.4 Units of measure

4 REGULATORY

4.1 National requirements

4.2 Local code requirements

5 OVERVIEW OF TELECOMMUNICATIONS BONDING AND GROUNDING SYSTEMS

5.1 General

5.2 Overview of the telecommunications bonding and grounding infrastructure

5.2.1 General

5.2.2 Telecommunications main grounding busbar (TMGB)

5.2.3 Bonding conductor for telecommunications (BCT)

5.2.4 Telecommunications bonding backbone (TBB)

5.2.5 Telecommunications grounding busbar (TGB)

5.2.6 Grounding equalizer (GE)

6 TELECOMMUNICATIONS BONDING AND GROUNDING COMPONENTS

6.1 General

6.2 Busbars

6.2.1 Telecommunications main grounding busbar (TMGB)

6.2.2 Telecommunications grounding busbar (TGB)

6.3 Conductors

6.3.1 General

6.3.2 Sizing the telecommunications bonding backbone (TBB)

6.3.3 Sizing the bonding conductor for telecommunications (BCT)

6.3.4 Sizing the grounding equalizer (GE)

6.4 Connectors

6.5 Identification

6.5.1 Conductors

6.5.2 Labels

7 DESIGN REQUIREMENTS

7.1 General

7.1.1 Telecommunications entrance facility (TEF)

7.1.2 Distributors (see ANSI/TIA-568-C.0)

7.1.3 Computer rooms

7.1.4 Cabinets and racks

7.1.5 Cable ladders, cable runways, conduits, pipes, and building steel

7.2 Telecommunications main grounding busbar (TMGB)

7.2.1 General

7.2.2 Bonds to the TMGB

7.2.3 Connections to the TMGB

7.3 Telecommunications grounding busbar (TGB)

7.3.1 General

7.3.2 Bonds to the TGB

7.3.3 Connections to the TGB

ii

7.4 Conductors

7.4.1 General

7.4.2 Bonding conductor for telecommunications (BCT)

7.4.3 Telecommunications bonding backbone (TBB)

7.4.4 Grounding equalizer (GE)

7.4.5 Coupled bonding conductor (CBC)

7.4.6 Bonding conductors for connections to the mesh-BN or RGB

7.4.7 Telecommunications equipment bonding conductor (TEBC)

7.4.7.1 General

7.4.7.2 Separation

7.5 Bonding equipment cabinets/equipment racks to the TEBC

7.6 Structural bonding of equipment cabinets/equipment racks

7.7 Supplementary bonding networks

7.7.1 Mesh-BN

7.7.2 Mesh-IBN

7.7.3 Bonding conductor for connections to the supplementary bonding network

7.8 Administration

8 PERFORMANCE AND TEST REQUIREMENTS

8.1 Two-point ground/continuity testing

ANNEX A (INFORMATIVE) GROUNDING ELECTRODES

A.1 General A.2 Ground rods A.3 Electrolytic ground rods A.4 Ground plate electrodes A.5 Wire mesh A.6 Concrete encased electrode A.7 Ground ring electrodes A.8 Ground radial electrodes A.9 Enhanced grounding materials A.10 Grounding conductors

ANNEX B (INFORMATIVE) TOWERS AND ANTENNAS

B.1 General B.2 Grounding electrode system B.2.1 External grounding B.2.2 Grounding busbars B.2.3 Bonding connections B.2.4 Grounding systems B.2.4.1 Type 1 sites B.2.4.2 Type 2 sites B.2.5 Tower grounding B.2.5.1 Guyed metallic towers B.2.5.2 Self-supporting metallic towers B.2.5.3 Wooden structures (poles) B.2.6 Building/shelter and outdoor cabinet grounding B.2.7 Rooftop sites grounding system B.2.7.1 Down conductors B.2.7.2 Roof conductors B.2.8 Transmission line grounding at antenna locations B.2.9 Ancillary objects requiring bonding and grounding B.2.9.1 Fence grounding B.2.9.2 Generators B.2.9.3 Satellite dishes B.2.10 Internal bonding and grounding B.2.10.1 Components iii

B.2.10.2 Installation B.2.10.3 Bonding to the external ground electrode system

ANNEX C (INFORMATIVE) TELECOMMUNICATIONS ELECTRICAL PROTECTION

ANNEX D (INFORMATIVE) ELECTRICAL PROTECTION FOR OPERATOR-TYPE EQUIPMENT

POSITIONS

ANNEX E (INFORMATIVE) CROSS REFERENCE OF TERMS

ANNEX F (INFORMATIVE) REFERENCES

List of Figures

Figure 1 – Relationship between TIA cabling standards ........................................................................ v Figure 2 – Illustrative example of a larger building Figure 3 – Illustrative example of a smaller building Figure 4 – Typical TMGB Figure 5 – Typical TGB Figure 6 – Label for bonding and grounding conductors Figure 7 – Example of three methods to bond equipment and racks to ground Figure 8 – Bonding to the service equipment (power) ground Figure 9 – Example TEBC to rack bonding conductor connection Figure 10 – Example of a TEBC routed on cable tray Figure 11 – Illustration of connection point to a rack from a TEBC Figure 12 – Illustration of a bond connection from a cabinet to the cabinet door Figure 13 – A mesh-BN with equipment cabinets, frames, racks and CBN bonded together Figure 14 – A mesh-IBN having a single point of connection Figure 15 – Illustrative views of typical ground rods Figure 16 – Illustrations of a vertical and horizontal electrolytic ground rod Figure 17 – Illustrative view of a concrete-encased electrode Figure 18 – Illustrative view of a ground radial electrode Figure 19 – Illustrative example of ground enhancement materials surrounding a grounding conductor and a ground rods Figure 20 – Radius bend illustration Figure 21 – Illustrative example view of a site grounding electrode system Figure 22 – Illustration of a parallel ground rod installation Figure 23 – Illustration of a guyed tower grounding example Figure 24 – Illustration of guy wire grounding Figure 25 – Illustration of a monopole tower grounding example Figure 26 – Illustrative view of a wooden pole grounding example Figure 27 – Illustrative view of a cabinet grounding system Figure 28 – Illustrative rooftop tower example Figure 29 – Illustrative view of roof-mounted antenna mast grounding with a supplemental grounding electrode system Figure 30 – Illustrative view of side-mounted antenna grounding using copper strap down conductor

Figure 31 – Illustration of a fence bonding example Figure 32 – Illustrative view of a fence fabric and deterrent wiring bonding example Figure 33 – Illustrative view of a generator grounding example Figure 34 – Electrical protection for operator-type equipment positions

List of Tables

Table 1 –TBB conductor size vs length iv

FOREWORD

(This foreword is not part of this Standard)

This Standard was developed by Telecommunications Industry Association (TIA) Subcommittee

TR-42.16.

Approval of Standard This Standard was approved by TIA Subcommittee TR-42.16, TIA Engineering Committee TR-42, and the American National Standards Institute (ANSI).

ANSI/TIA reviews standards every 5 years. At that time, standards are reaffirmed, withdrawn, or revised according to the submitted updates. Updates to be included in the next revision should be sent to the committee chair or to ANSI/TIA.

Contributing organizations More than 60 organizations within the telecommunications industry contributed their expertise to the development of this Standard (including manufacturers, consultants, end users, and other organizations).

Documents superseded This Standard replaces ANSI-J-STD-607-A, published in October, 2002.

Significant technical changes Significant technical changes and additions from the previous edition include:

• Bonding and grounding requirements for “generic” premises. Requirements for specific types of premises (e.g., commercial buildings, residential) can be found in corresponding TR-42 developed premises standards.

Relationship to other TIA standards and documents The following are related standards regarding various aspects of structured cabling that were developed and are maintained by Engineering Committee TIA TR-42. A diagram of the relationship between the TIA cabling standards is illustrated in figure 1.

a) Generic Telecommunications Cabling for Customer Premises (ANSI/TIA-568-C.0);

b) Commercial Building Telecommunications Cabling Standard (ANSI/TIA-568-C.1);

c) Balanced Twisted-Pair Telecommunications Cabling and Components Standard

(ANSI/TIA 568 C.2);

d) Optical Fiber Cabling Components Standard (ANSI/TIA-568-C.3);

e) Broadband Coaxial Cabling and Components Standard (ANSI/TIA-568-C.4);

f) Commercial Building Standard for Telecommunications Pathways and Spaces (TIA-569-B);

g) Residential Telecommunications Infrastructure Standard (ANSI/TIA-570-B);

h) Administration Standard for Commercial Telecommunications Infrastructure

(ANSI/TIA/EIA-606-A);

i) Customer-Owned Outside Plant Telecommunications Infrastructure Standard

(ANSI/TIA-758-B);

j) Building Automation Systems Cabling Standard (ANSI/TIA/EIA-862-A);

k) Telecommunications Infrastructure Standard for Data Centers (ANSI/TIA-942); and,

l) Telecommunications Infrastructure Standard for Industrial Premises (ANSI/TIA-1005).

v

Figure 1 – Relationship between TIA cabling standards

The following documents may be useful to the reader:

a) National Electrical Safety Code® (NESC®) (ANSI/IEEE C2-2007)

b) National Electrical Code® (NEC®) (ANSI/NFPA-70-2011)

Other references are listed in annex F.

Annexes Annexes A through F are informative and not considered a requirement of this Standard.

vi

Introduction

General Telecommunications, as used in this Standard, refers to the transmission of all forms of information (e.g., voice, data, video, security, audio, industrial, building control). Telecommunications equipment used to support these wide varieties of systems that rely on the electronic transport of information require an effective building infrastructure. This infrastructure encompasses spaces, pathways, cables, connecting hardware, and a bonding and grounding system. For reliable operation of any telecommunications equipment or system, bonding and grounding (earthing) is essential – regardless of the cabling technology or media. This Standard focuses on the bonding and grounding portion of this infrastructure.

NOTE – The North American term “grounding” that is used in this Standard is equivalent to the international term “earthing”.

The bonding and grounding approach in this Standard is intended to work in concert with premises cabling specified within TIA Engineering Committee TR-42. The requirements specified in this Standard in conjunction with a basic understanding of bonding and grounding concepts and methodologies will aid in achieving a reliable solution when applied to telecommunications installations.

Several sources of bonding and grounding information exist within the telecommunications industry.

For example, the NEC® specifies requirements regarding the safety aspects of bonding and grounding of equipment and systems. Yet another example is that of ATIS 0600318, Electrical Protection Applied to Telecommunications Network Plant at Entrances to Customer Structures or Buildings, which provides information on bonding and grounding to support electrical protection considerations.

Purpose The purpose of this Standard is to enable and encourage the planning, design, and installation of generic telecommunications bonding and grounding systems within premises with or without prior knowledge of the telecommunications systems that will subsequently be installed. While primarily intended to provide direction for the design of new buildings, this Standard may be used for existing building renovations or retrofit treatment. Design requirements and choices are provided to enable the designer to make informed design decisions.

Stewardship Telecommunications infrastructure affects raw material consumption. The infrastructure design and installation methods also influence product life and sustainability of electronic equipment life cycling.

These aspects of telecommunications infrastructure impact our environment. Since building life cycles are typically planned for decades, technological electronic equipment upgrades are necessary. The telecommunications infrastructure design and installation process magnifies the need for sustainable infrastructures with respect to building life, electronic equipment life cycling and considerations of effects on environmental waste. Telecommunications designers are encouraged to research local building practices for a sustainable environment and conservation of fossil fuels as part of the design process.

Specification of criteria Two categories of criteria are specified; mandatory and advisory. The mandatory requirements are designated by the word "shall"; advisory requirements are designated by the words "should”, "may", or "desirable" which are used interchangeably in this Standard.

Mandatory criteria generally apply to protection, performance, administration and compatibility; they specify minimally acceptable requirements. Advisory criteria are presented when their attainment may enhance the general performance of the cabling system in all its contemplated applications.

A note in the text, table, or figure is used for emphasis or offering informative suggestions, or providing additional information.

vii

Metric equivalents of United States (US) customary units The units in this Standard are metric or US customary with soft conversion to the other.

Life of this Standard This Standard is a living document. The criteria contained in this Standard are subject to revisions and updating as warranted by advances in building construction techniques and telecommunications technology.

1 SCOPE

This Standard specifies requirements for a generic telecommunications bonding and grounding infrastructure and its interconnection to electrical systems and telecommunications systems. This Standard may also be used as a guide for the renovation or retrofit of existing systems.

2 NORMATIVE REFERENCES

The following standards contain provisions that, through reference in this text, constitute provisions of this Standard. At the time of publication, the editions indicated were valid. All standards are subject to revision, and parties to agreements based on this Standard are encouraged to investigate the possibility of applying the most recent editions of the standards indicated below. The American National Standards Institute (ANSI) and the Telecommunications Industry Association (TIA) maintain registers of currently valid national standards published by them.

a) ANSI/IEEE 1100, 2005, Recommended Practice for Powering and Grounding Electronic Equipment

b) ANSI/IEEE C2, 2007, National Electrical Safety Code (NESC®)

c) ANSI/NECA/BICSI-607, 2010, Telecommunications Bonding and Grounding Planning and Installation Methods for Commercial Buildings

d) ANSI/NFPA-70, 2008, National Electrical Code (NEC®)

e) ANSI/ATIS 0600333, Grounding And Bonding Of Telecommunications Equipment

f) ANSI/ATIS 0600334, 2008, Electrical Protection Of Communications Towers And

Associated Structures

g) ANSI/TIA-568-C.0, 2008, Generic Telecommunications Cabling for Customer Premises

h) ANSI/TIA/EIA-606-A, 2007, Administration Standard for the Telecommunications

Infrastructure of Commercial Buildings

i) FIPS PUBS 94, 1983, Guideline on Electrical Power for ADP Installations, 1983 (USA

Federal Information Processing Standards Publications)

j) ITU-T K.27, 1996, Bonding Configuration And Earthing Inside A Telecommunication

Building

3 DEFINITIONS

3.1 General

For the purpose of this Standard the following definitions, acronyms, abbreviations and units of measure apply.

3.2 Definition of terms

For the purposes of this Standard, the following definitions apply:

access floor: A system consisting of completely removable and interchangeable floor panels that are supported on adjustable pedestals or stringers (or both) to allow access to the area beneath.

access provider: The operator of any facility that is used to convey telecommunications signals to and from a customer premises.

administration: The method for labeling, identification, documentation and usage needed for installation, moves, additions and changes of the telecommunications infrastructure.

backbone: A facility (e.g. pathway, cable or bonding conductor) for cabling Subsystem 2 and Cabling Subsystem 3.

bonding: The joining of metallic parts to form an electrically conductive path.

bonding conductor: A conductor that joins metallic parts to form an electrically conductive path.

bonding conductor for telecommunications: A conductor that interconnects the telecommunications bonding infrastructure to the building's service equipment (power) ground.

bonding network (telecommunications): A set of interconnected conductive structures that provides a low impedance path for the associated telecommunications infrastructure.

building backbone: 1) Pathways or cabling between telecommunications service entrance rooms, equipment rooms, telecommunications rooms, or telecommunications enclosures within a building.

2) Cabling for interconnecting telecommunications spaces from the telecommunications entrance facility to a horizontal cross-connect within a building.

cabinet: A container that may enclose connection devices, terminations, apparatus, wiring, and equipment.

cable: An assembly of one or more insulated conductors or optical fibers, within an enveloping sheath.

cable sheath: A covering over the optical fiber or conductor assembly that may include one or more metallic members, strength members, or jackets.

cabling: A combination of all cables, jumpers, cords, and connecting hardware.

Cabling Subsystem 1: Cabling from the equipment outlet to Distributor A, Distributor B, or Distributor C.

Cabling Subsystem 2: Cabling between Distributor A and either Distributor B or Distributor C (if Distributor B is not implemented).

Cabling Subsystem 3: Cabling between Distributor B and Distributor C.

campus: The buildings and grounds having legal contiguous interconnection.

coaxial cable: A telecommunications cable consisting of a round center conductor surrounded by a dielectric surrounded by a concentric cylindrical conductor (shield) and an optional insulating sheath.

commercial building: A building or portion thereof that is intended for office use.

common bonding network: The set of metallic components that are interconnected to form the principle means for effectively bonding equipment inside a building to the grounding electrode system computer room: An architectural space whose primary function is to accommodate data processing equipment.

conduit: (1) A raceway of circular cross-section. (2) A structure containing one or more ducts.

customer premises: Building(s), grounds and appurtenances (belongings) under the control of the customer.

Distributor A: Optional connection facility in a hierarchical star topology that is cabled between the equipment outlet and Distributor B or Distributor C.

Distributor B: Optional intermediate connection facility in a hierarchical star topology that is cabled to Distributor C.

Distributor C: Central connection facility in a hierarchical star topology.

earth: See ground.

earthing: See grounding.

electromagnetic interference: Radiated or conducted electromagnetic energy that has an undesirable effect on electronic equipment or signal transmissions.

entrance facility (telecommunications): An entrance to a building for both public and private network service cables (including wireless) including the entrance point of the building and continuing to the entrance room or space.

entrance point (telecommunications): The point of emergence for telecommunications cabling through an exterior wall, a floor, or from a conduit.

equipment outlet: Outermost connection facility in a hierarchical star topology.

equipotential bonding: Bonding between metallic components to achieve a substantially equal potential.

exothermic weld: A method of permanently bonding two metals together by a controlled heat reaction resulting in a molecular bond.

grid: A collection of adjacent cells.

ground: A conducting connection, whether intentional or accidental, between an electrical circuit (e.g., telecommunications) or equipment and the earth, or to some conducting body that serves in place of earth.

grounding: The act of creating a ground.

grounding conductor: A conductor used to connect the grounding electrode to the building's main grounding busbar.

grounding electrode: A conductor, usually a rod, pipe or plate (or group of conductors) in direct contact with the earth for the purpose of providing a low-impedance connection to the earth.

grounding electrode conductor: The conductor used to connect the grounding electrode to the equipment grounding conductor, or to the grounded conductor of the circuit at the service equipment, or at the source of a separately derived system.

grounding electrode system: One or more grounding electrodes that are connected together.

grounding equalizer: The conductor that interconnects elements of the telecommunications grounding infrastructure infrastructure (telecommunications): A collection of those telecommunications components, excluding equipment, that together provide the basic support for the distribution of information within a building or campus.

Listed: Equipment included in a list published by an organization, acceptable to the authority having jurisdiction, that maintains periodic inspection of production of listed equipment, and whose listing states either that the equipment or material meets appropriate standards or has been tested and found suitable for use in a specified manner.

mesh bonding network: A bonding network to which all associated equipment (e.g., cabinets, frames, racks, trays, pathways) are connected using a bonding grid, which is connected to multiple points on the common bonding network.

pathway: A facility for the placement of telecommunications cable.

primary protector: The protector located at the building telecommunications entrance point.

primary protector grounding conductor: The conductor connecting the primary protector to ground.

protector: A device consisting of one or more protector units and associated mounting assemblies intended to limit abnormal voltages or currents on metallic telecommunications circuits.

secondary protector: A device that protects against electrical transients passed through the primary protector or generated within the customer premises.

sheath: See cable sheath.

shield: 1) A metallic layer placed around a conductor or group of conductors. 2) The cylindrical outer conductor with the same axis as the center conductor that together form a coaxial transmission line.

sleeve: An opening, usually circular, through the wall, ceiling, or floor to allow the passage of cables.

splice: A joining of conductors, meant to be permanent.

supplementary bonding grid: A set of conductors or conductive elements formed into a grid or provided as a conductive plate that is part of a bonding network.

telecommunications: Any transmission, emission, and reception of signs, signals, writings, images, and sounds, that is, information of any nature by cable, radio, optical, or other electromagnetic systems.

telecommunications bonding backbone: A conductor that interconnects the telecommunications main grounding busbar (TMGB) to the telecommunications grounding busbar (TGB).

telecommunications equipment bonding conductor: A conductor that connects the telecommunications main grounding busbar (TMGB) or telecommunications grounding busbar (TGB) to equipment racks or cabinets telecommunications grounding busbar (TGB): A common point of connection for telecommunications system and equipment bonding to ground, and located in the telecommunications room or equipment room.

telecommunications infrastructure: See infrastructure (telecommunications).

telecommunications main grounding busbar: A busbar placed in a convenient and accessible location and bonded by means of the bonding conductor for telecommunications, to the building service equipment (power) ground.

wire: An individually insulated solid or stranded metallic conductor.

3.3 Abbreviations and acronyms

ac alternating current ACEG alternating current equipment ground AHJ authority having jurisdiction ANSI American National Standards Institute ATIS Alliance for Telecommunications Industry Solutions AWG American Wire Gage

BCT bonding conductor for telecommunications BN bonding network CBC coupled bonding conductor CBN common bonding network dc direct current EIA Electronic Industries Alliance EMI electromagnetic interference ENT electrical nonmetallic tubing EO equipment outlet ESD electrostatic discharge FCC Federal Communications Commission GE grounding equalizer HVAC heating, ventilating and air conditioning IACS International Annealed Copper Standard IBN isolated bonding network ITE information technology equipment ITU-T International Telecommunication Union- Telecommunication mesh-BN mesh bonding network mesh-IBN mesh isolated bonding network NEC® National Electrical Code® NECA National Electrical Contractors Association NESC® National Electrical Safety Code® NFPA National Fire Protection Association NRTL nationally recognized testing laboratory PDU power distribution unit RBC rack bonding conductor RF radio frequency RGB rack grounding busbar SPC single point connection SBG supplementary bonding grid TBB telecommunications bonding backbone TEBC telecommunications equipment bonding conductor TEF telecommunications entrance facility TGB telecommunications grounding busbar TIA Telecommunications Industry Association TMGB telecommunications main grounding busbar

3.4 Units of measure

ft feet, foot in inch kcmil thousand circular mil km kilometer m meter mm millimeter ohms-cm ohms centimeter V volt

4 REGULATORY

4.1 National requirements

This Standard is intended to conform to the National Electrical Code® (NEC®; ANSI/NFPA-70) and the National Electrical Safety Code® (NESC®; ANSI/IEEE C2).

4.2 Local code requirements

This Standard does not replace any code, either partially or wholly. Local code requirements shall be followed. The local code requirements should be reviewed with the local authority having jurisdiction (AHJ). The review should confirm the currently adopted code and edition and any exceptions to the code that are adopted by the governing authority (the AHJ). If no code has been adopted locally, consult with the fire marshal’s office to determine what agency is responsible for code enforcement in that geographic area.

5 OVERVIEW OF TELECOMMUNICATIONS BONDING AND GROUNDING SYSTEMS

5.1 General

The basic principles, components, and design of telecommunications bonding and grounding infrastructure specified in this Standard shall be followed amongst buildings of differing designs and structures.

NOTE – The requirements in this Standard differ from utility service provider requirements, which are specified in ATIS-0600313. ATIS-0600313 specifications support a robust level of service appropriate to a service provider. Users of this Standard are encouraged to refer to ATIS-0600313 where robust service requirements exist.

Bonding and grounding systems within a building are intended to have one electrical potential. While the bonding and grounding of the electrical service entrance is outside the scope of this Standard, coordination between electrical and telecommunications bonding and grounding systems is essential for the proper application of this Standard. For example, electrical room and associated electrical panelboard(s) are not part of the telecommunications infrastructure, but they are depicted in this Standard because they are integral to the telecommunications bonding and grounding system. See subclauses 7.2.1, 7.2.2, 7.3.1 and 7.3.2 for more information regarding bonding to electrical panelboards.

When installed, the lightning protection system should meet the requirements of the authority having jurisdiction (AHJ).

Where a tower or antenna is installed, the installation shall meet the bonding and grounding requirements of ANSI/ATIS 0600334. See annex B for information regarding bonding and grounding of towers and antennas.

5.2 Overview of the telecommunications bonding and grounding infrastructure

5.2.1 General

Within a building (see illustrative examples figure 2 and figure 3), the generic telecommunications bonding and grounding infrastructure originates at the electrical entrance facility ground and extends throughout the building. It includes the following major components:

a) telecommunications main grounding busbar (TMGB);

b) bonding conductor for telecommunications (BCT);

and may also include the following:

c) telecommunications bonding backbone (TBB);

d) telecommunications grounding busbar (TGB); and,

e) grounding equalizer (GE).

These telecommunications bonding and grounding components are intended to work with a building’s telecommunications pathways and spaces, installed cabling, and administration system.

Figure 2 – Illustrative example of a larger building

Figure 3 – Illustrative example of a smaller building

5.2.2 Telecommunications main grounding busbar (TMGB)

The TMGB serves as the dedicated extension of the building grounding electrode system for the telecommunications infrastructure. The TMGB also serves as the central attachment point for the TBB(s) and equipment. See subclauses 6.2.1 and 7.1.3.

5.2.3 Bonding conductor for telecommunications (BCT)

The BCT bonds the TMGB to the service equipment (power) ground. See subclauses 6.3.3 and 7.4.2.

5.2.4 Telecommunications bonding backbone (TBB)

The TBB is a conductor that interconnects all TGBs with the TMGB. The intended function of a TBB is to reduce or equalize potential differences. A TBB is not intended to serve as the only conductor providing a ground fault current return path. The TBB originates at the TMGB extends throughout the building using the telecommunications backbone pathways, and connects to the TGBs in distributors.

See subclauses 6.3.2 and 7.4.3.

5.2.5 Telecommunications grounding busbar (TGB)

The TGB is the grounding connection point for telecommunications systems and equipment in the area served by a distributor. See subclauses 6.2.2 and 7.3.

5.2.6 Grounding equalizer (GE)

The GE is typically employed in a multistory building to interconnect multiple TBBs on the same floor.

See subclauses 6.3.4 and 7.4.4.

6 TELECOMMUNICATIONS BONDING AND GROUNDING COMPONENTS

6.1 General

This clause specifies components of the telecommunications bonding and grounding infrastructure.

Where the word “Listed” is used as a requirement for a component, the component shall be Listed to the applicable standard(s) through a nationally recognized testing laboratory (NRTL).

6.2 Busbars

6.2.1 Telecommunications main grounding busbar (TMGB)

The TMGB shall:

a) be a busbar provided with holes for use with correctly matched Listed lugs and hardware;

b) be made of copper, or copper alloys having a minimum of 95% conductivity when annealed as specified by the International Annealed Copper Standard (IACS);

c) have minimum dimensions of 6.35 mm (0.25 in) thick x 100 mm (4 in) wide and variable in length; and,

d) be Listed.

Figure 4 illustrates dimensions typical of a TMGB.

Figure 4 – Typical TMGB

6.2.2 Telecommunications grounding busbar (TGB)

The TGB shall:

a) be a busbar provided with holes for use with correctly matched Listed lugs and hardware;

b) be made of copper, or copper alloys having a minimum of 95% conductivity when annealed as specified by the IACS;

c) have minimum dimensions of 6.35 mm (0.25 in) thick x 50.8 mm (2 in) wide and variable in length; and,

d) be Listed.

Figure 5 illustrates dimensions typical of a TGB.

Figure 5 – Typical TGB

6.3 Conductors

6.3.1 General

All bonding and grounding conductors shall be copper and may be insulated. When conductors are insulated, they shall be Listed for the application. The size of the conductor is not intended to account for the reduction or control of electromagnetic interference (EMI). The grounding conductors shall not decrease in size as the grounding path moves closer to earth.

6.3.2 Sizing the telecommunications bonding backbone (TBB)

The minimum TBB conductor size shall be a No. 6 American Wire Gauge (AWG). The TBB should be sized at 2 kcmil per linear foot of conductor length up to a maximum size of 750 kcmil.

NOTE – The previous edition of this Standard sized the TBB conductor up to 3/0 AWG. This Standard allows the TBB conductor to be sized up to 750 kcmil. Bonding conductors used for telecommunications should be sized using engineered calculations.

Table 1 –TBB conductor size vs length

TBB/GE linear length m (ft)

TBB/GE size

(AWG)

less than 4 (13) 6 4 – 6 (14 – 20) 4 6 – 8 (21 – 26) 3

8 – 10 (27 – 33) 2 10 – 13 (34 – 41) 1 13 – 16 (42 – 52) 1/0 16 – 20 (53 – 66) 2/0 20 – 26 (67 – 84) 3/0 26 – 32 (85 – 105) 4/0

32 – 38 (106 – 125) 250 kcmil 38 – 46 (126 – 150) 300 kcmil 46 – 53 (151 – 175) 350 kcmil 53 – 76 (176 – 250) 500 kcmil 76 – 91 (251 – 300) 600 kcmil

Greater than 91 (301) 750 kcmil

6.3.3 Sizing the bonding conductor for telecommunications (BCT) The BCT shall be, as a minimum, the same size as the largest TBB.

6.3.4 Sizing the grounding equalizer (GE)

The GE shall be, as a minimum, the same size as the largest TBB.

6.4 Connectors

All bonding and grounding connectors shall be Listed for the application.

NOTE – Connectors are Listed for the application (e.g., above ground, direct buried, bonding to the metal frame of a building).

The surface of all bonding and grounding connectors used on a TMGB and a TGB shall be of a material that provides an electro-chemical potential of <30x10-2 V between connector and grounding busbar.

6.5 Identification

6.5.1 Conductors

The BCT, each TBB, and each GE, shall be green or marked with a distinctive green color.

6.5.2 Labels

Labels shall be nonmetallic and include the information depicted in figure 6.

Figure 6 – Label for bonding and grounding conductors

7 DESIGN REQUIREMENTS

7.1 General

All exposed cables in a telecommunications facility shall be bonded to ground as close as practical to the point of entrance. This includes bonding to ground the cable shields and metallic sheath members according to manufacturer’s installation instructions.

Where the building backbone telecommunications cabling incorporates a shield or metallic member, this shield or metallic member shall be bonded to the telecommunications main grounding busbar (TMGB) or the telecommunications grounding busbar (TGB) where the cables are terminated or where pairs are “broken out” from the cable sheath.

When secondary protection is provided, the secondary protector grounding conductor shall be connected to the nearest TMGB or TGB using the shortest grounding conductor practical.

Grounding through the equipment alternating current (ac) power cord does not meet the intent of this Standard. It is intended that the information technology equipment (ITE) be provided a supplementary and specific ground path for the equipment over and above the required ac or direct current (dc) power ground path. While the ac or dc powered equipment typically has a power cord that contains a grounding/bonding wire, the integrity of this path to ground cannot be easily verified. Rather than relying wholly on the ac or dc power cord grounding/bonding wire, it is desirable that equipment be grounded in a verifiable “supplementary” manner as described in this Standard.

NOTE – Many types of equipment do not require individual bonding conductors and as such do not have an attachment point for bonding conductors. Equipment that does not have attachment points for bonding conductors may be bonded either through the equipment rail or the power cord. Refer to the manufacturer’s documentation for guidelines.

Short metallic pathways (e.g., wall and floor sleeves, J-hooks) are not required to be bonded.

Additionally, this Standard does not require bonding of the steel bars of a reinforced concrete building.

See ANSI/NECA/BICSI-607 for installation information on telecommunications bonding and grounding.

7.1.1 Telecommunications entrance facility (TEF)

The TEF is the entrance point (room or space within a building) where:

a) the telecommunications facilities enter;

b) the joining of campus and building backbone facilities takes place; and,

c) the grounding of these facilities is accomplished.

The TEF may also include antenna cable entrances (see annex B), and electronic equipment serving telecommunications functions.

It is desirable that all utilities enter the building in close proximity to each other.

7.1.2 Distributors (see ANSI/TIA-568-C.0)

Distributor C shall contain either a TMGB or a minimum of one TGB. Distributor A and Distributor B shall contain a minimum of one TGB. The TMGB and the TGB shall be located within the Distributor so as to provide the greatest flexibility and accessibility for telecommunications system grounding (minimizing practical lengths and number of bends of bonding conductors to the TGB).

7.1.3 Computer rooms

Each computer room shall contain a TGB (or TMGB when specified in the design) and should also contain a supplementary bonding network that is bonded (and thus becomes grounded) to the TGB or TMGB. This supplementary bonding network may be in a form as identified in subclause 7.7 but is typically a mesh-bonding network (mesh-BN).

Typically, the ITE cabinets and racks within the computer room are arranged into a holistic (single system block) mesh-BN by manufacturer’s equipment design, user deployment guidelines, or both.

For computer rooms, the holistic mesh-BN is a recommended practice since it simplifies installation procedures, most ITE is powered by ac branch circuits, and most ITE employed for a computer room is suitable for placement directly into the common bonding network (CBN).

However, under certain circumstances such as a manufacturer’s requirement or access provider recommendations, the ITE may also be arranged into certain segregated “functional system blocks” of either mesh-BN, mesh isolated bonding network (mesh-IBN), or other form of bonding network (BN), within the same room. The supplementary bonding conductor network for the holistic or any segregated mesh-BN, mesh-IBN or other BN must also be directly bonded to the room’s TGB or TMGB since the BN must always be grounded. The BN may also provide for electromagnetic shielding in varying degrees based upon its design and installation.

A recommended augmentation to a BN (especially a mesh-BN) is a supplementary bonding grid (SBG). Upon installation and connection of the SBG to the BN (primary components are cabinets, racks and frames), the SBG becomes part of the overall BN. The SBG typically covers the entire computer room or a local area within a room.

The historical spacing for the SBG pattern is between 0.61 m to 1.22 m (2 ft to 4 ft) and was historically stated in Guideline on Electrical Power for ADP Installations, 1983 (USA Federal Information Processing Standards Publications - FIPS PUBS 94) to aid in reducing the effect of resonance on ac branch circuit equipment grounding conductors.

The minimum density of the bonding grid is 3 m (9.8 ft) centers or one that corresponds to the computer room cold-or-hot aisles and the aisles running perpendicular to the cold-and-hot aisles.

7.1.4 Cabinets and racks

Metallic enclosures, including telecommunications cabinets and racks, shall be bonded to the mesh- BN, TGB, or TMGB using a minimum sized conductor of No. 6 AWG.

Cabinets, racks, and other enclosures in computer rooms shall not be bonded serially; each shall have their own dedicated bonding conductor to the mesh-BN, TGB, or TMGB.

Equipment containing metallic parts in cabinets and racks shall be bonded to the telecommunications grounding system in accordance with the manufacturer instructions. Where instructions are not given, all bonding jumpers that ground installed equipment shall be a minimum sized conductor of No. 12 AWG. Rack grounding busbars (RGBs) are recommended for cabinets and racks that need to support multiple unit bonding conductors. There are three methods to bond the equipment located in the equipment rack or cabinet to the telecommunications bonding system, see figure 7.

Figure 7 – Example of three methods to bond equipment and racks to ground

7.1.5 Cable ladders, cable runways, conduits, pipes, and building steel In order to limit the potential difference between telecommunications conduits or between telecommunications conduits and power conduits, the telecommunications conduits shall be bonded to the TMGB/TGB. Additionally, to achieve the objectives of potential equalization, ensure that cable runway/ladder sections are bonded together and that they are bonded to the TMGB/TGB.

Where building steel is accessible and in the same room as the TMGB/TGB, the TMGB/TGB shall be bonded to building steel using a minimum sized conductor of No. 6 AWG. When practical, because of shorter distances and where horizontal steel members are permanently electrically bonded to vertical column members, the TMGB/TGB may be bonded to these horizontal members in lieu of the vertical column members. When the building steel is external to the room, but readily accessible, it should be bonded to the TMGB/TGB using a minimum sized conductor of No. 6 AWG. Building steel should be tested to verify its ground conductivity to earth.

NOTE – Modern building construction techniques will ground building steel to the main ac power entrance or another grounding source. Ensure that when working in existing buildings that the building steel is bonded to a suitable ground source (e.g., electrical power grounding electrode[s], building ground ring).

7.2 Telecommunications main grounding busbar (TMGB)

7.2.1 General

The length of the TMGB is not specified within this Standard. It is desirable that the busbar be electrotin-plated for reduced contact resistance. The busbar shall be cleaned and an anti-oxidant should be applied prior to fastening connectors to the busbar.

The desirable location of the TMGB is in the TEF. Typically, there should be a single TMGB per building.

NOTE – For buildings with more than one electrical service entrance, each of which serves telecommunications equipment, the user is urged to consult with a licensed engineer for guidance on locating the TMGB.

The TMGB shall be as close as practical to the panelboard (electrical power panel) and shall be installed to maintain clearances required by applicable electrical codes. A practical location for the TMGB is to the side of the panelboard (where provided). The vertical location of the TMGB should be determined by considering whether the bonding conductors are routed in an access floor or overhead cable support.