TIA-569-C May 2012

Telecommunications Pathways and Spaces

ANSI/TIA-569-C-2012

APPROVED: MAY 3, 2012

NOTICE

TIA Engineering Standards and Publications are designed to serve the public interest through eliminating misunderstandings between manufacturers and purchasers, facilitating interchangeability and improvement of products, and assisting the purchaser in selecting and obtaining with minimum delay the proper product for their particular need. The existence of such Standards and Publications shall not in any respect preclude any member or non-member of TIA from manufacturing or selling products not conforming to such Standards and Publications. Neither shall the existence of such Standards and Publications preclude their voluntary use by Non-TIA members, either domestically or internationally.

Standards and Publications are adopted by TIA in accordance with the American National Standards Institute (ANSI) patent policy. By such action, TIA does not assume any liability to any patent owner, nor does it assume any obligation whatever to parties adopting the Standard or Publication.

This Standard does not purport to address all safety problems associated with its use or all applicable regulatory requirements. It is the responsibility of the user of this Standard to establish appropriate safety and health practices and to determine the applicability of regulatory limitations before its use.

(From Project No. 3-4817-RV3-E-1, formulated under the cognizance of the TIA TR-42 Telecommunications Cabling Systems, TR-42.3 Subcommittee on Commercial Building Telecommunications Pathways and Spaces (569).

Published by

TELECOMMUNICATIONS INDUSTRY ASSOCIATION

Standards and Technology Department 2500 Wilson Boulevard

Arlington, VA 22201 U.S.A.

PRICE: Please refer to current Catalog of

TIA TELECOMMUNICATIONS INDUSTRY ASSOCIATION STANDARDS

AND ENGINEERING PUBLICATIONS

or call IHS, USA and Canada

(1-877-413-5187) International (303-397-2896) or search online at http://www.tiaonline.org/standards/catalog/

All rights reserved Printed in U.S.A.

NOTICE OF COPYRIGHT

This document is copyrighted by the TIA.

Reproduction of these documents either in hard copy or soft copy (including posting on the web) is prohibited without copyright permission. For copyright permission to reproduce portions of this document, please contact the TIA Standards Department or go to the TIA website (www.tiaonline.org) for details on how to request permission. Details are located at:

http://www.tiaonline.org/standards/catalog/info.cfm#copyright or

Telecommunications Industry Association Technology & Standards Department

2500 Wilson Boulevard, Suite 300 Arlington, VA 22201 USA

+1.703.907.7700

Organizations may obtain permission to reproduce a limited number of copies by entering into a license agreement. For information, contact

IHS

15 Inverness Way East

Englewood, CO 80112-5704 or call

USA and Canada (1.800.525.7052) International (303.790.0600)

NOTICE OF DISCLAIMER AND LIMITATION OF LIABILITY

The document to which this Notice is affixed (the “Document”) has been prepared by one or more Engineering Committees or Formulating Groups of the Telecommunications Industry Association (“TIA”). TIA is not the author of the Document contents, but publishes and claims copyright to the Document pursuant to licenses and permission granted by the authors of the contents.

TIA Engineering Committees and Formulating Groups are expected to conduct their affairs in accordance with the TIA Engineering Manual (“Manual”), the current and predecessor versions of which are available at http://www.tiaonline.org/standards/procedures/manuals/TIA’s function is to administer the process, but not the content, of document preparation in accordance with the Manual and, when appropriate, the policies and procedures of the American National Standards Institute (“ANSI”). TIA does not evaluate, test, verify or investigate the information, accuracy, soundness, or credibility of the contents of the Document. In publishing the Document, TIA disclaims any undertaking to perform any duty owed to or for anyone.

If the Document is identified or marked as a project number (PN) document, or as a standards proposal (SP) document, persons or parties reading or in any way interested in the Document are cautioned that: (a) the Document is a proposal;

(b) there is no assurance that the Document will be approved by any Committee of TIA or any other body in its present or any other form; (c) the Document may be amended, modified or changed in the standards development or any editing process.

The use or practice of contents of this Document may involve the use of intellectual property rights (“IPR”), including pending or issued patents, or copyrights, owned by one or more parties. TIA makes no search or investigation for IPR.

When IPR consisting of patents and published pending patent applications are claimed and called to TIA’s attention, a statement from the holder thereof is requested, all in accordance with the Manual. TIA takes no position with reference to, and disclaims any obligation to investigate or inquire into, the scope or validity of any claims of IPR. TIA will neither be a party to discussions of any licensing terms or conditions, which are instead left to the parties involved, nor will TIA opine or judge whether proposed licensing terms or conditions are reasonable or non-discriminatory. TIA does not warrant or represent that procedures or practices suggested or provided in the Manual have been complied with as respects the Document or its contents.

If the Document contains one or more Normative References to a document published by another organization (“other SSO”) engaged in the formulation, development or publication of standards (whether designated as a standard, specification, recommendation or otherwise), whether such reference consists of mandatory, alternate or optional elements (as defined in the TIA Engineering Manual, 4th edition) then (i) TIA disclaims any duty or obligation to search or investigate the records of any other SSO for IPR or letters of assurance relating to any such Normative Reference; (ii) TIA’s policy of encouragement of voluntary disclosure (see Engineering Manual Section 6.5.1) of Essential Patent(s) and published pending patent applications shall apply; and (iii) Information as to claims of IPR in the records or publications of the other SSO shall not constitute identification to TIA of a claim of Essential Patent(s) or published pending patent applications.

TIA does not enforce or monitor compliance with the contents of the Document. TIA does not certify, inspect, test or otherwise investigate products, designs or services or any claims of compliance with the contents of the Document.

ALL WARRANTIES, EXPRESS OR IMPLIED, ARE DISCLAIMED, INCLUDING WITHOUT LIMITATION, ANY AND ALL WARRANTIES CONCERNING THE ACCURACY OF THE CONTENTS, ITS FITNESS OR APPROPRIATENESS FOR A PARTICULAR PURPOSE OR USE, ITS MERCHANTABILITY AND ITS NONINFRINGEMENT OF ANY THIRD PARTY’S INTELLECTUAL PROPERTY RIGHTS. TIA EXPRESSLY DISCLAIMS ANY AND ALL RESPONSIBILITIES FOR THE ACCURACY OF THE CONTENTS AND MAKES NO REPRESENTATIONS OR WARRANTIES REGARDING THE CONTENT’S COMPLIANCE WITH ANY APPLICABLE STATUTE, RULE OR REGULATION, OR THE SAFETY OR HEALTH EFFECTS OF THE CONTENTS OR ANY PRODUCT OR SERVICE REFERRED TO IN THE DOCUMENT OR

PRODUCED OR RENDERED TO COMPLY WITH THE CONTENTS.

TIA SHALL NOT BE LIABLE FOR ANY AND ALL DAMAGES, DIRECT OR INDIRECT, ARISING FROM OR RELATING TO ANY USE OF THE CONTENTS CONTAINED HEREIN, INCLUDING WITHOUT LIMITATION ANY AND ALL INDIRECT, SPECIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES (INCLUDING DAMAGES FOR LOSS OF BUSINESS, LOSS OF PROFITS, LITIGATION, OR THE LIKE), WHETHER BASED UPON BREACH OF CONTRACT, BREACH OF WARRANTY, TORT (INCLUDING NEGLIGENCE), PRODUCT LIABILITY OR OTHERWISE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. THE FOREGOING NEGATION OF DAMAGES IS A FUNDAMENTAL ELEMENT OF THE USE OF THE CONTENTS HEREOF, AND THESE CONTENTS WOULD NOT BE

PUBLISHED BY TIA WITHOUT SUCH LIMITATIONS.

ANSI/TIA-569-C

i

TELECOMMUNICATIONS PATHWAYS AND SPACES

Table of Contents

FOREWORD ............................................................................................................................. x

1 SCOPE

2 NORMATIVE REFERENCES

3 DEFINITIONS, ACRONYMS AND ABBREVIATIONS, UNITS OF MEASURE

3.1 General

3.2 Definitions

3.3 Acronyms and abbreviations

3.4 Units of measure

4 ENVIRONMENTAL COMPATIBILITY

5 DIVERSITY OF TELECOMMUNICATIONS FACILITIES

5.1 General

5.2 Access provider

5.3 Wireline/wireless

5.4 Entrance point

5.5 Entrance route

5.6 Building pathways

5.7 Building spaces

6 BUILDING SPACES

6.1 General

6.2 Temperature and humidity requirements

6.3 Common requirements for rooms

6.3.1 General

6.3.2 Security

6.3.3 Location

6.3.4 Access

6.3.5 Pathways

6.3.6 Design

6.3.6.1 Architectural

6.3.6.1.1 Plywood backboards

6.3.6.1.2 Ceiling

6.3.6.1.3 Treatment

6.3.6.1.4 Floor loading

6.3.6.1.5 Lighting

6.3.6.1.6 Door

6.3.6.1.7 Signage

6.3.6.1.8 Exterior windows

6.3.6.1.9 Seismic considerations

ii

6.3.6.2 Environmental

6.3.6.2.1 Temperature and humidity

6.3.6.2.2 Contaminants

6.3.6.2.3 Batteries

6.3.6.2.4 Vibration

6.3.6.3 Guidelines for other equipment

6.3.7 Fire protection

6.3.8 Water infiltration

6.3.9 Racks and cabinets

6.3.9.1 General

6.3.9.2 Equipment placement

6.3.9.3 Clearances

6.3.9.4 Cabinet cooling

6.3.9.5 Cabinet and rack height

6.3.9.6 Cabinet depth and width

6.3.9.7 Equipment mounting width

6.3.9.8 Mounting rails

6.3.9.9 Finish

6.3.9.10 Power strips

6.3.9.11 Cable management

6.3.9.12 Additional specifications

6.3.10 Equipment delivery

6.4 Distributor room

6.4.1 General

6.4.2 Location

6.4.3 Pathways

6.4.4 Design

6.4.4.1 Architectural

6.4.4.1.1 Size

6.4.4.1.2 Quantity

6.4.4.2 Environmental

6.4.4.2.1 Heating, ventilation and air conditioning (HVAC)

6.4.4.2.1.1 Continuous operation

6.4.4.2.1.2 Standby operation

6.4.4.2.1.3 Positive pressure

6.4.4.3 Electrical

6.4.4.3.1 Power

6.4.4.3.2 Standby power

6.4.4.3.3 Bonding and grounding

6.4.5 Small rooms

6.5 Entrance room or space

iii

6.5.1 General

6.5.2 Entrance facility

6.5.3 Location

6.5.4 Design

6.5.4.1 Architectural

6.5.4.1.1 General

6.5.4.1.2 Size

6.5.4.1.3 Quantity

6.5.4.2 Environmental

6.5.4.3 Electrical

6.5.4.3.1 Power

6.5.4.3.2 Bonding and grounding

6.6 Distributor enclosure

6.6.1 General

6.6.2 Location

6.6.3 Access

6.6.4 Pathways

6.6.5 Design

6.6.5.1 Architectural

6.6.5.1.1 Size and spacing

6.6.5.1.2 Interior provisioning

6.6.5.1.3 Lighting

6.6.5.1.4 Door

6.6.5.1.5 Signage

6.6.5.2 Environmental

6.6.5.3 Electrical

6.6.5.3.1 Power

6.6.5.3.2 Standby power

6.6.5.3.3 Bonding and grounding

6.6.6 Fire protection

6.7 Equipment outlets

6.7.1 General

6.7.2 Outlet density

6.7.3 Location

6.7.4 Installation

6.7.5 Outlet box

6.7.6 Low-voltage mounting bracket

6.7.7 Furniture

6.7.8 Poke-thru devices

6.7.8.1 General

6.7.8.1.1 Types

iv

6.7.8.1.1.1 Flush

6.7.8.1.1.2 Pedestal (raised, tombstone, monument)

6.7.8.1.2 Design and installation requirements

6.7.9 Patch panel system

6.7.10 Other connecting hardware

6.8 Splice box

6.8.1 Use of splice boxes

6.8.2 Design guidelines

7 ACCESS PROVIDER SPACES AND SERVICE PROVIDER SPACES

7.1 General

7.2 Location

7.3 Pathways

7.4 Design

7.4.1 Architectural

7.4.1.1 Partitions

7.4.1.2 Signage

7.4.2 Environmental

7.4.2.1 Heating, ventilation and air conditioning (HVAC)

7.4.2.1.1 General

7.4.2.1.2 Continuous operation

7.4.2.1.3 Standby operation

7.4.2.1.4 Positive pressure

7.4.2.2 Other mechanical fixtures

7.4.3 Electrical

7.4.3.1 Power

7.4.3.1.1 General

7.4.3.1.2 Standby power

7.4.3.2 Bonding and grounding

8 MULTI-TENANT BUILDING SPACES

8.1 General

8.2 Common distributor room

8.2.1 General

8.2.2 Location

8.2.3 Number and size of penetrations

8.2.4 Design

8.2.4.1 Architectural

8.2.4.1.1 General

8.2.4.1.2 Size

8.2.4.1.3 Quantity

8.2.4.2 Environmental

8.2.4.2.1 Standby operation

v

8.2.4.2.2 Positive pressure

8.2.4.3 Electrical

8.2.4.3.1 Power

8.2.4.3.1.1 General

8.2.4.3.1.2 Standby power

8.2.4.3.2 Bonding and grounding

8.2.5 Common pathways and spaces bypass

8.2.6 Campus pathways

9 BUILDING PATHWAYS

9.1 General

9.2 Types of building pathways

9.3 Pathway separation from EMI sources

9.3.1 Separation between telecommunications and power cables

9.3.1.1 General

9.3.1.2 Additional recommendations

9.3.2 Telecommunications pathway separation from lighting

9.3.3 Reducing noise coupling

9.4 Areas above ceilings

9.4.1 General

9.4.2 Design guidelines

9.4.2.1 Planning

9.4.2.2 Clearance

9.5 Access floor systems

9.5.1 General

9.5.2 Loading performance

9.5.3 Building structure

9.5.3.1 Depressed slab

9.5.3.2 Normal or partially depressed slab

9.5.4 Design guidelines

9.5.4.1 Service area service fittings

9.5.4.2 Minimum clearance

9.5.4.3 Cable management

9.5.5 Installation

9.5.5.1 Layout

9.5.5.2 Linkage to distributor room or distributor enclosure

9.6 Cable tray and cable runway

9.6.1 General design information and cable fill

9.6.1.1 Cable trays

9.6.1.2 Cable runway

9.6.2 Support

9.6.3 Installation

vi

9.6.3.1 General

9.6.3.2 Pathway termination

9.7 Non-continuous support

9.8 Conduit

9.8.1 Use of conduit

9.8.2 Design guidelines

9.8.2.1 Length

9.8.2.2 Bends

9.8.2.3 Pull tension

9.8.2.4 Pull boxes

9.8.2.4.1 Use of pull boxes

9.8.2.4.2 Design guidelines

9.8.2.5 Conduit runs to outlets

9.8.2.6 Pathway termination

9.8.2.7 Conduit to wall-mounted public telephone locations

9.8.2.8 Elevator telecommunications

9.8.2.9 Conduit to outdoor locations

9.8.3 Installation

9.8.3.1 Conduit termination

9.8.3.2 Pull strings

9.9 Furniture

9.9.1 Building interfaces

9.9.2 Floors

9.9.3 Ceilings

9.9.4 Pathway fill factor

9.9.5 Furniture pathway capacity

9.9.6 Access

9.9.7 Furniture pathway bend radius

9.9.8 Reducing pathway capacity at corners

9.9.9 Power/telecommunications separation

9.10 In-floor

9.10.1 Underfloor duct systems

9.10.1.1 General

9.10.1.2 Floor structure design

9.10.1.3 Design guidelines and procedures

9.10.1.3.1 System capacities

9.10.1.3.1.1 General requirements

9.10.1.3.1.2 Specific calculation method

9.10.1.3.2 Design and layout information

9.10.1.4 Feeder duct

9.10.1.4.1 General

vii

9.10.1.4.2 Trench duct or trench header

9.10.1.4.3 Supplementary feeder

9.10.1.5 Access unit or junction boxes

9.10.1.6 Installation

9.10.1.6.1 Single-level or two-level underfloor duct systems

9.10.1.6.2 Trench duct or trench header

9.10.1.7 Inserts for underfloor duct systems

9.10.1.7.1 Preset inserts

9.10.1.7.2 Afterset inserts

9.10.1.8 Service fittings

9.10.1.9 Floor boxes for single and multiple services

9.10.2 Cellular floor

9.10.2.1 Design guidelines and procedures

9.10.2.1.1 General design information

9.10.2.1.2 System capacities

9.10.2.1.2.1 General recommendations

9.10.2.1.2.2 Specific calculation method

9.10.2.1.3 Design and layout information

9.10.2.2 Distribution cells in cellular floor

9.10.2.2.1 Preset inserts

9.10.2.2.2 Blank cells

9.10.2.3 Feeder systems for cellular floor

9.10.2.3.1 Flush header duct

9.10.2.3.2 Header duct

9.10.2.3.3 Trench header

9.10.2.4 Layout of cellular floor

9.10.2.4.1 Distribution cells

9.10.2.4.2 Allocating distribution cells

9.10.2.4.3 Feeder

9.10.2.5 Installation of cellular floor systems

9.10.2.5.1 General

9.10.2.5.2 Header duct

9.10.2.5.3 Trench header

9.10.2.6 Service fittings for cellular floor

9.11 Perimeter raceways

9.11.1 Construction

9.11.2 Design and installation requirements

9.11.2.1 Surface raceway system sizing

9.11.2.1.1 Pathway sizing

9.11.2.1.2 Raceway fittings

9.11.2.1.3 Equipment outlets

viii

9.12 Vertical pathway – sleeves or conduits, slots

9.12.1 Sleeve or conduit quantity and configuration

9.12.2 Slot quantity and configuration

9.13 Utility columns

9.14 Partition cabling

9.15 In-wall cabling

9.16 Overfloor raceway

9.17 Curtain wall

9.18 Open ceiling

9.19 Structural columns

Annex A (normative) Firestopping

A.1 Scope

A.2 Terminology

A.3 Firestops

A.3.1 Introduction

A.3.2 Fire rated barriers

A.3.3 Penetrations

A.3.4 Evaluation of firestop systems

A.3.5 Qualification testing

A.3.6 Testing requirements for through-penetration firestops

A.3.7 Firestop ratings for through-penetration firestops

A.3.8 Guidelines for membrane-penetration firestops

A.3.9 Seismic considerations

A.3.10 Engineering judgments

A.4 Quality control considerations

A.5 Categories of firestop systems

A.5.1 Introduction

A.5.2 Mechanical systems

A.5.3 Nonmechanical systems

A.5.3.1 Putty

A.5.3.2 Caulk

A.5.3.3 Cementitious (cement-like) materials

A.5.3.4 Intumescent sheets

A.5.3.5 Intumescent wrap strips

A.5.3.6 Silicone foams

A.5.3.7 Premanufactured pillows

A.6 Design consideration checklist

Annex B (informative) Electromagnetic noise reduction guidelines for balanced twisted-pair cabling

B.1 General

B.2 Building cabling configurations and noise coupling conditions ix

B.3 Test configuration

B.4 Test results

B.5 Summary

Annex C (informative) Bibliography

List of Figures

Figure 1 – Relationship between relevant TIA standards ........................................................... xi

Figure 2 – Example of pathways and spaces in a single-tenant building ................................... xv

Figure 3 – Example of common pathways and spaces in a multi-tenant building ..................... xvi

Figure 4 – Elements of generic cabling topology

Figure 5 – Typical distributor room

Figure 6 – Typical shallow room

Figure 7 – Dimensions for furniture equipment outlet opening

Figure 8 – Example of an access provider or service provider space

Figure 9 – Example of pathways and spaces in a multi-tenant building

Figure 10 – Example of a common distributor room

Figure 11 – Cable tray design for reduced separation

Figure 12 – Access floor system minimum clearances

Figure 13 – Cable tray with 5.5 mm (0.22 in) diameter cables at 50% calculated fill

Figure 14 – Furniture pathway fill

Figure 15 – Underfloor duct layout

Figure 16 – Steel cellular floor

Figure 17 – Reduction of raceway capacity at sharp corners

Figure 18 – Typical office building pathway layout

Figure 19 – Typical sleeve and slot installations

Figure 20 – Mechanical firestops

Figure 21 – Test configuration for noise immunity measurements

List of Tables

Table 1 – Conduit sizes

Table 2 – Temperature and humidity requirements for telecommunications spaces

Table 3 – Floor space

Table 4 – Splice box sizing

Table 5 – Summary of access provider spaces and service provider spaces

Table 6 – Recommended separation from power wiring for balanced twisted pair cabling

Table 7 – Pull box sizing

Table 8 – Noise reduction factors under different test variables x

FOREWORD

(This foreword is not considered part of this Standard.)

This Standard was developed by TIA Subcommittee TR-42.3.

Approval of this Standard

This Standard was approved by TIA Subcommittee TR-42.3, TIA Engineering Committee TR-42, and the American National Standards Institute (ANSI).

ANSI/TIA reviews standards every 5 years. At that time, standards are reaffirmed, withdrawn, or revised according to the submitted updates. Updates to be included in the next revision should be sent to the committee chair or to ANSI/TIA.

Contributing organizations

More than 40 organizations within the telecommunications industry (including manufacturers, consultants, end users and other organizations) contributed their expertise to the development of this Standard.

Documents superseded

This Standard replaces TIA-569-B dated October, 2004, and its addendum. Content specific to commercial building pathways and spaces can be found in ANSI/TIA-568-C.1. Content specific to outside plant entrance facilities, including entrance points and entrance pathways, can be found in ANSI/TIA-758-B. References to earlier versions of this Standard may require further reference to these documents.

Relationship to other TIA standards and documents

The following are related standards regarding various aspects of structured cabling that were developed and are maintained by Engineering Committee TIA TR-42. Figure 1 shows the schematic relationship between TIA telecommunications cabling standards.

Generic Telecommunications Cabling for Customer Premises (ANSI/TIA-568-C.0);

Commercial Building Telecommunications Cabling Standard (ANSI/TIA-568-C.1);

Balanced Twisted-Pair Telecommunications Cabling and Components Standard

(ANSI/TIA-568-C.2);

Optical Fiber Cabling Components Standard (ANSI/TIA-568-C.3);

Residential Telecommunications Infrastructure Standard (ANSI/TIA-570-B);

Administration Standard for Commercial Telecommunications Infrastructure

(ANSI/TIA/EIA-606-A);

Generic Telecommunications Bonding and Grounding (Earthing) for Customer Prem-ises (ANSI/TIA-607-B);

Customer-owned Outside Plant Telecommunications Infrastructure Standard

(ANSI/TIA-758-B);

Building Automation Systems Cabling Standard for Commercial Buildings

(ANSI/TIA/-862-A);

Telecommunications Infrastructure Standard for Data Centers (ANSI/TIA-942); and xi

Telecommunications Infrastructure Standard for Industrial Premises

(ANSI/TIA-1005).

Common

Standards

ANSI/TIA-568-C.0

(Generic)

Premises

Standards

ANSI/TIA-568-C.1

(Commercial)

ANSI/TIA-568-C.2

(Balanced twisted-pair)

TIA-569

(Pathways and spaces)

ANSI/TIA-570

(Residential)

Component

Standards

ANSI/TIA-568-C.3

(Optical fiber)

ANSI/TIA-606

(Administration)

ANSI/TIA-942

(Data centers)

ANSI/TIA-568-C.4

(Coaxial)

Figure 1 – Relationship between relevant TIA standards

ANSI/TIA-1005

(Industrial)

ANSI/TIA-607

(Bonding and grounding

[earthing])

ANSI/TIA-1179

(Healthcare)

ANSI/TIA-758

(Outside plant)

ANSI/TIA-862

(Building automation systems)

Figure 1 – Relationship between relevant TIA standards

The following documents may be useful to the reader:

National Electrical Safety Code® (IEEE C2-2007); and

National Electrical Code® (NEC®) (NFPA 70-2011)

Useful supplements to this Standard are the following BICSI documents: the Telecommunica-tions Distribution Methods Manual, the Outside Plant Design Manual, and the Information Transport Systems Installation Methods Manual. These manuals provide practices and meth-ods by which many of the requirements of this Standard are implemented.

xii

Other references are listed in Annex C.

Annexes

This Standard has three annexes. Annex A is normative and considered a requirement of this Standard. Annexes B and C are informative and not considered a requirement of this Standard.

Introduction

This Standard recognizes three fundamental concepts related to telecommunications and build-ings:

Buildings are dynamic. Over the life of a building, remodeling is more the rule than the exception. This Standard recognizes, in a positive way, that change takes place.

Building telecommunications systems and media are dynamic. Over the life of a building, both telecommunications equipment and media change. This Standard recognizes this fact by maintaining independence from specific vendor equipment and media.

Telecommunications is comprised of more than just voice and data. Telecommunica-tions also encompasses many other building systems including environmental con-trol, security, audio, television, sensing, alarms and paging. Indeed, telecommunica-tions embraces all wired and wireless means of conveying information within build-ings.

This Standard also recognizes an important precept: in order to have a building successfully designed, constructed, and provisioned for telecommunications, it is imperative that the tele-communications design be incorporated during the preliminary architectural design phase, and reviewed throughout construction.

Both architectural and telecommunications terminology are used in this Standard, which may cause some difficulty to readers experienced in one area but perhaps not in the other. The reader can reduce confusion by remembering that this Standard does not standardize the media or equipment; it only standardizes the pathways and spaces up to and within buildings into which telecommunications media and equipment are placed.

This Standard recognizes the evolving nature of building tenant needs, the building’s inherent limitations in adapting to changing tenant needs once the building has been constructed, and the special attention to telecommunications pathways and spaces design necessitated during the initial planning stages of new building designs.

This Standard recognizes that floor space is occupied by each tenant, which usually occurs af-ter the building has been provisioned. In a multi-tenant building the build out design of the ten-ant space may include telecommunications pathways and spaces, in addition to the base build-ing design, to accommodate distinct tenant needs. It is expected that, at the time of occupancy, individual tenants will design their telecommunications infrastructure in conformance with ANSI/TIA-569-C and the relevant premises standard (see figure 1). As a result, the build-out design may also include pathways and spaces to support a two-level cabling hierarchy for each tenant.

Multi-tenant buildings have life cycles that mirror that of single-tenant buildings. Many buildings are over 100 years old. Over time, these older buildings have become severely challenged to support escalating demands on their pathways and spaces as a result of tenants’ ever increas-ing needs for telecommunications connectivity.

xiii

Telecommunications pathways and spaces in multi-tenant buildings are further challenged by the phased nature of their use. After the building is constructed and the first group of tenants move in, the tenant’s telecommunications needs may immediately cause modifications to the building. Over a span of years, as tenants cycle through the building, evolving tenant needs will continue to force the building to adapt to the demands of its tenants.

Although the scope is limited only to the telecommunications aspect of building design, this Standard significantly influences the design of other building services, such as electrical power and HVAC. It also sets minimum requirements for the size of telecommunications spaces.

Stewardship

Telecommunications infrastructure affects raw material consumption. The infrastructure design and installation methods also influence product life and sustainability of electronic equipment life cycling. These aspects of telecommunications infrastructure impact our environment. Since building life cycles are typically planned for decades, technological electronic equipment up-grades are necessary. The telecommunications infrastructure design and installation process magnifies the need for sustainable infrastructures with respect to building life, electronic equip-ment life cycling and considerations of effects on environmental waste. Telecommunications designers are encouraged to research local building practices for a sustainable environment and conservation of fossil fuels as part of the design process.

Purpose

The purpose of this Standard is to standardize specific pathway and space design and construc-tion practices in support of telecommunications media and equipment within buildings.

Expected usefulness

A principal goal of this Standard is to be useful to the building owners and occupants who oth-erwise would live with the daily problems associated with buildings that are not properly de-signed and constructed to support telecommunications. A properly designed and constructed facility is adaptable to change over the life of the facility. Owners and occupants should assume that better telecommunications facilities are constructed through the use of this Standard. In-deed, part of the expected usefulness of this Standard is that it be referenced in documents such as bid requests, specifications, and contracts leading up to the construction of the facilities.

This Standard should also prove useful to the team that is responsible for delivering a well-designed facility to the owner – the architects, engineers, and the construction industry. A good understanding of this Standard by this team will significantly reduce unforeseen problems asso-ciated with the telecommunications infrastructure. Two organizations, in particular, are lauded for their supportive role as this Standard was initially developed – the American Institute of Ar-chitects (AIA) and the Construction Specifications Institute (CSI).

Other organizations will also benefit from an understanding of the Standard. In particular, the Building Owners and Managers Association (BOMA), BICSI, a telecommunications association, and the International Facility Management Association (IFMA) will find this Standard closely aligned with their goals for good building design and construction.

This Standard generally makes no specific recommendations among the design alternatives available for telecommunications pathways and spaces. For example, the choice between a conduit system versus a tray system is not delineated. It is up to the telecommunications de-signer to properly select among the alternatives based upon the applications at hand and the constraints imposed. Readers, especially end users and owners, should ensure that qualified designers of telecommunications pathways and spaces are selected to implement this standard.

xiv

Specification of criteria

Two categories of criteria are specified; mandatory and advisory. The mandatory requirements are designated by the word "shall"; advisory requirements are designated by the words "should”, "may", or "desirable", which are used interchangeably in this Standard.

Mandatory criteria generally apply to protection, performance, administration and compatibility;

they specify minimally acceptable requirements. Advisory criteria are presented when their at-tainment may enhance the general performance of the cabling system in all its contemplated applications.

A note in the text, table, or figure is used for emphasis or offering informative suggestions, or providing additional information.

Metric equivalents of US customary units

The units of measure in this Standard are metric or US customary with soft conversion between the two.

Life of this Standard

This Standard is a living document. The criteria contained in this Standard are subject to revi-sions and updating as warranted by advances in building construction techniques and telecom-munications technology.

Basic building elements

Telecommunications has an impact on most every area within and between buildings. Because of this, and the additional fact that the useful life of a building may span many decades, it is im-portant that the design and construction of new or remodeled buildings be performed with an objective of avoiding obsolescence. When a building is designed with its life cycle in mind, the resulting building will be responsive to the many changes that occur in both telecommunications media and systems over the life of the building.

Figure 2 illustrates the relationships between the major telecommunications pathway and space elements within a building. The list of these elements that follow the figure describes the char-acteristics of each element; numbers are keyed to respective sections within this Standard.

Figure 3 is a representative model of the various functional elements that comprise multi-tenant pathways and spaces in a building; this is not intended to be an all inclusive representation. It depicts the relationship between the elements and how they are configured to create a total sys-tem.

xv

Figure 2 – Example of pathways and spaces in a single-tenant building

Description Clause or subclause

Description Clause or subclause

1 Wireless service entrance pathway

6.5.2 7 Distributor enclosure 6.6

2 Entrance room 6.5 8 Service entrance pathway 6.5.2 3 Building pathways 9 9 Diversity of entrance routes 5.5 4 Distributor room 6.3.10 10 Distributor room 6.3.10 5 Access provider space, service provider space

11 Equipment outlet 6.6

6 Entrance room 6.5 12 Equipment outlet location 6.7.3 xvi d

Figure 3 – Example of common pathways and spaces in a multi-tenant building

Description Clause or subclause

Description Clause or subclause

1 Wireless service entrance pathway

6.5.2 5 Entrance room 6.5

2 Entrance room 6.5 6 Service entrance pathway 6.5.2 3 Common building pathways

7 Diversity of entrance routes

5.5

4 Access provider space, service provider space

8 Common distributor room

8.2

1 SCOPE

This standard specifies requirements for telecommunications pathways and spaces.

NOTE – The diversity of services currently available, coupled with the continual addition of new services, means that there may be cases where limitations to de-sired performance occur. When applying specific applications to the infrastruc-ture described in this Standard, the user is cautioned to consult application standards, regulations, equipment vendors, and system and service suppliers for applicability, limitations, and ancillary requirements.

2 NORMATIVE REFERENCES

The following standards contain provisions which, through reference in this text, constitute pro-visions of this Standard. At the time of publication, the editions indicated were valid. All stand-ards are subject to revision, and parties to agreements based on this standard are encouraged to investigate the possibility of applying the most recent editions of the standards indicated be-low. ANSI and TIA maintain registers of currently valid national standards published by them.

ANSI C95.2-1999, Standard for Radio Frequency Energy and Current Flow Symbols

ANSI/IEEE 1100-2005, IEEE Recommended Practice for Powering and Grounding Electronic Equipment (IEEE Emerald Book)

ANSI/TIA-607-B 2011, Generic Telecommunications Bonding and Grounding (Earth-ing) for Customer Premises

ANSI/NEMA OS 1-2008, Sheet-Steel Outlet Boxes, Device Boxes, Covers, and Box Supports

ANSI/NFPA 13 2010, Standard for the Installation of Sprinkler Systems

ANSI/TIA-568-C.0 2009, Generic Telecommunications Cabling for Customer Prem-ises

ANSI/TIA-568-C.2 2009, Balanced Twisted-Pair Telecommunications Cabling and Components Standard

ANSI/TIA-758-B 2011, Customer-owned Outside Plant Telecommunications Infra-structure Standard

ANSI/UL 1479 2003, Standard for Fire Tests of Through-Penetration Firestops

ASHRAE, Thermal Guidelines for Data Processing Environments, Second Edition, ASHRAE, 2011 Thermal Guidelines for Data Processing Environments – Expanded Data Center Classes and Usage Guidance, 2011

ASTM E119-10b 2010, Standard Test Methods for Fire Tests of Building Construc-tion and Materials

ASTM E814-10 2010, Standard Test Method for Fire Tests of Penetration Firestop Systems

ATIS 0600336 2009, Engineering Requirements for a Universal Telecom Framework

BICSI Telecommunications Distribution Methods Manual (TDMM), 12th Edition, 2009

CISCA Recommended Test Procedures for Access Floors, 2007

EIA/ECA-310-E 2005, Cabinets, Racks, Panels, and Associated Equipment

FCC OET Bulletin 65, Evaluating Compliance with FCC Guidelines for Human Expo-sure to Radio Frequency Electromagnetic Fields, Edition 97-01

IEC 61000-4-4 2004, Electromagnetic Compatibility (EMC) – Part 4-4: Testing and Measurement Techniques – Electrical Fast Transient/Burst Immunity Test

NEMA VE 2-2006, Cable Tray Installation Guidelines

NFPA 70 2011, National Electrical Code© (NEC©)

3 DEFINITIONS, ACRONYMS AND ABBREVIATIONS, UNITS OF MEASURE

3.1 General

The generic definitions in this clause have been formulated for use by the entire family of tele-communications infrastructure standards. Specific requirements are found in the normative clauses of this Standard.

3.2 Definitions

For the purposes of this Standard, the following definitions apply.

ablative: The development of a hard char that resists the erosion of fire and flames; a charac-teristic of a firestop when exposed to fire.

access floor: A system consisting of completely removable and interchangeable floor panels that are supported on adjustable pedestals or stringers (or both) to allow access to the area be-neath.

access provider: The operator of any facility that is used to convey telecommunications sig-nals to and from a customer premises.

access unit: A location that allows entry into the pathway system.

administration: The method for labeling, identification, documentation and usage needed for installation, moves, additions and changes of the telecommunications infrastructure.

balance: The ratio of the differential signal output at either end of any pair to a common mode signal input, at either end of the same or a different pair, and vice versa, under specified termi-nation conditions.

barrier (architectural): Architectural structures or assemblies.

blank cell: The hollow space of a cellular metal or cellular concrete floor unit without factory installed fittings.

bonding: The joining of metallic parts to form an electrically conductive path.

building automation system: Equipment and telecommunications infrastructure that supports monitoring, control, operation and management of building services.

building core: A three-dimensional space permeating one or more floors of the building and used for the extension and distribution of utility services (e.g., elevators, washrooms, stairwells, mechanical and electrical systems, and telecommunications) throughout the building.

bundled cable: An assembly of two or more cables continuously bound together to form a sin-gle unit.

cabinet: A container that may enclose connection devices, terminations, apparatus, wiring, and equipment.

cable: An assembly of one or more insulated conductors or optical fibers, within an enveloping sheath.

cable sheath: A covering over the optical fiber or conductor assembly that may include one or more metallic members, strength members, or jackets.

Cabling Subsystem 1: Cabling from the equipment outlet to Distributor A, Distributor B, or Dis-tributor C.

Cabling Subsystem 2: Cabling between Distributor A and either Distributor B or Distributor C (if Distributor B is not implemented).

Cabling Subsystem 3: Cabling between Distributor B and Distributor C.

NOTE – See figure 4 for an illustration of the generic cabling topology for Cabling Subsystem 1, Cabling Subsystem 2, Cabling Subsystem 3, Distributor A, Distrib-utor B, Distributor C, an optional consolidation point and the equipment outlet.

Figure 2 – Functional elements that comprise a generic cabling system

D C

Cabling

Subsystem 3

Cabling

Subsystem 2

Cabling

Subsystem 1

Cabling

Subsystem 1

Cabling

Subsystem 3

D BD B

D A D A

EO EOEOEOEOEO EOEO

Cabling

Subsystem 2

Cabling

Subsystem 1

Cabling

Subsystem 1

D C

D A

EOEO EO

Legend:

EO Equipment outlet

D A Distributor A

D B Distributor B

D C Distributor C

Optional cabling

Optional consolidation point

Figure 4 – Elements of generic cabling topology campus: The buildings and grounds having legal contiguous interconnection.

cell: A single raceway of a cellular or underfloor duct system.

cellular floor: A floor distribution method in which cables pass through floor cells, constructed of steel or concrete to provide a ready-made raceway for distribution of power and telecommu-nications cables.

cementitious firestop: A firestopping material that is mixed with water, similar in appearance to mortar.

channel: The end-to-end transmission path between two points at which application-specific equipment is connected.

coaxial cable: A telecommunications cable consisting of a round center conductor surrounded by a dielectric surrounded by a concentric cylindrical conductor (shield) and an optional insulat-ing sheath.

common distributor room: A distributor room that services tenants in a multi-tenant building.

conduit: (1) A raceway of circular cross-section. (2) A structure containing one or more ducts.

NOTE – For the purposes of this Standard the term conduit includes electrical metallic tubing (EMT) or electrical non-metallic tubing (ENT) conduit sizes: For the purposes of this Standard, conduit sizes are designated according to metric designator and trade size as shown in table 1.

Table 1 – Conduit sizes

Metric designator Trade size

16 ½

21 ¾

27 1

35 1¼

41 1½

53 2

63 2½

78 3

91 3½

103 4

129 5

155 6 connecting hardware: A device providing mechanical cable terminations.

consolidation point: A connection facility within Cabling Subsystem 1 for interconnection of cables extending from building pathways to the equipment outlet.

cross-connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.

cross-connection: A connection scheme between cabling runs, subsystems, and equipment using patch cords or jumpers that attach to connecting hardware on each end.

dew point: the temperature to which air must be cooled (assuming constant air pressure and moisture content) to reach a relative humidity of 100% (i.e., saturation).

distribution duct: A raceway placed within or just below the finished floor and used to extend the wires or cables to a specific service area.

Distributor A: Optional connection facility in a hierarchical star topology that is cabled between the equipment outlet and Distributor B or Distributor C.

Distributor B: Optional intermediate connection facility in a hierarchical star topology that is cabled to Distributor C.

Distributor C: Central connection facility in a hierarchical star topology.

NOTE – See figure 4 for an illustration of the generic cabling topology for Cabling Subsystem 1, Cabling Subsystem 2, Cabling Subsystem 3, Distributor A, Distrib-utor B, Distributor C, an optional consolidation point and the equipment outlet.

distributor enclosure: A case or housing designed to contain Distributor A, Distributor B or Distributor C.

distributor room: An enclosed architectural space designed to contain Distributor A, Distribu-tor B or Distributor C.

dry-bulb temperature: The temperature of air measured by a thermometer freely exposed to the air but shielded from radiation (e.g. sunlight, radiant heat) and moisture.

duct: 1) A single enclosed raceway for conductors or cables (see also conduit, raceway). 2) A single enclosed raceway for wires or cables usually used in soil or concrete. 3) An enclosure, generally part of the HVAC system of a building, in which air is moved.

elastomeric firestop: A firestopping material resembling rubber.

electromagnetic interference: Radiated or conducted electromagnetic energy that has an un-desirable effect on electronic equipment or signal transmissions.

embedded duct: A duct fully enclosed inside a floor or a wall.

entrance facility (telecommunications): An entrance to a building for both public and private network service cables (including wireless) including the entrance point of the building and con-tinuing to the entrance room or space.

entrance point (telecommunications): The point of emergence for telecommunications ca-bling through an exterior wall, a floor, or from a conduit.

entrance room or space (telecommunications): A space in which the joining of inter or intra building telecommunications facilities takes place.

NOTE - An entrance room may also serve as a distributor room.

equipment outlet: Outermost connection facility in a hierarchical star topology.

NOTE – See figure 4 for an illustration of the generic cabling topology for Cabling Subsystem 1, Cabling Subsystem 2, Cabling Subsystem 3, Distributor A, Distrib-utor B, Distributor C, an optional consolidation point and the equipment outlet.

feeder duct: See header duct.

fire resistance rating: The time in hours or fraction thereof that a material or assembly of ma-terials will withstand the passage of flame and the transmission of heat when exposed to fire under specified conditions of test and performance criteria.

firestop: A fire-rated material, device, or assembly of parts installed in a penetration of a fire-rated barrier.

firestop seals: See firestop system.

firestop system: A specific construction consisting of the material(s) (firestop penetration seals) that fill the opening in the wall or floor assembly and any items that penetrate the wall or floor, such as cables, cable trays, conduit, ducts, pipes, and any termination devices, such as electrical outlet boxes, along with their means of support.

firestopping: The process of installing listed, fire-rated materials into penetrations in fire-rated barriers to reestablish the fire-resistance rating of the barrier.

flush duct: A duct accessible by a cover that is even with the surface it is mounted in.

furniture cluster: A contiguous group of work areas, typically including space divisions, work surfaces, storage, and seating.

ground: A conducting connection, whether intentional or accidental, between an electrical cir-cuit (e.g., telecommunications) or equipment and the earth, or to some conducting body that serves in place of earth.

grounding: the act of creating a ground.

handhole: A structure similar to a small maintenance hole in which it is expected that a person cannot enter to perform work.

header duct (trenchduct, feeder duct): A raceway of rectangular cross-section placed within the floor to tie distribution duct(s) or cell(s) to the distributor room.

hybrid cable: An assembly of two or more cables, of the same or different types or categories, covered by one overall sheath.

in-floor pathway: A raceway within a floor structure.

infrastructure (telecommunications): A collection of those telecommunications components, excluding equipment, that together provide the basic support for the distribution of information within a building or campus.

innerduct: A nonmetallic raceway, usually circular, placed within a larger raceway.

insert: An opening into the distribution duct or cell, from which the wires or cables emerge.

insert, afterset: An insert installed after the installation of the concrete floor slab or other floor-ing material.

insert, preset: An insert installed prior to the installation of the concrete floor slab or other flooring material.

interconnection: A connection scheme that employs connecting hardware for the direct con-nection of a cable to another cable without a patch cord or jumper.

intumescent firestop: A firestopping material that expands under the influence of heat.

jumper: 1) An assembly of twisted pairs without connectors, used to join telecommunications circuits/links at the cross-connect. 2) A length of optical fiber cable with a connector plug on each end.

junction box: A location in the pathway system that allows transition of pathways and access to cables.

link: A transmission path between two points, not including equipment and cords.

listed: Equipment included in a list published by an organization, acceptable to the authority having jurisdiction, that maintains periodic inspection of production of listed equipment, and whose listing states either that the equipment or material meets appropriate standards or has been tested and found suitable for use in a specified manner.

main distribution panel (electrical): The primary point of distribution for electrical services within a facility.

maintenance hole (telecommunications): A vault located in the ground or earth as part of an underground duct system and used to facilitate placing, connecting, and maintaining cables as well as the placing of associated equipment, in which it is expected that a person will enter to perform work.

media (telecommunications): Wire, cable, or conductors used for telecommunications.

multi-user telecommunications outlet assembly: A grouping in one location of several tele-communications outlet/connectors.

optical fiber: Any filament made of dielectric materials that guides light.

optical fiber cable: An assembly consisting of one or more optical fibers.

outlet box (telecommunications): A housing used to hold telecommunications out-let/connectors.

outlet/connector (telecommunications): The fixed connector in an equipment outlet.

outside plant: Telecommunications infrastructure designed for installation exterior to buildings.

patch cord: 1) A length of cable with a plug on one or both ends. 2) A length of optical fiber cable with a connector on each end.

patch panel: A connecting hardware system that facilitates cable termination and cabling ad-ministration using patch cords.

pathway: A facility for the placement of telecommunications cable.

permanent link: A test configuration for a link excluding test cords and patch cords.

plenum: A compartment or chamber to which one or more air ducts are connected and that forms part of the air distribution system.

poke-thru device: An assembly that allows through-penetration of floor decking with telecom-munication cables, or power, or both, while maintaining the fire rating integrity of the floor.

pull box: A housing located in a pathway run used to facilitate the placing of wire or cables.

pull tension: The pulling force that can be applied to a cable.

raceway: Any enclosed channel designed for holding wires or cables.

rack: Supporting frame equipped with side mounting rails to which equipment and hardware are mounted.

rack unit: Vertical mounting space of 1.75 in (44.45 mm) for cabinets or racks compliant with IEC 60297 or CEA-310-E.

screed line: The line to which poured concrete is leveled.

service area: A building space containing one or more equipment outlets (e.g., a work area or a coverage area).

service entrance: See entrance facility (telecommunications).

service fitting: An outlet box to house the connections for telecommunications in the service area. See also insert.

service provider: The operator of any service that furnishes telecommunications content (transmissions) delivered over access provider facilities.

sheath: See cable sheath.

slab on grade: Concrete floor placed directly on soil, without basement or crawlspace.

sleeve: An opening, usually circular, through the wall, ceiling, or floor to allow the passage of cables.

slot: An opening through a wall, floor, or ceiling, usually rectangular, to allow the passage of cables.

space (telecommunications): An area used for housing the installation and termination of tel-ecommunications equipment and cable.

suspended ceiling: A ceiling that creates an area or space between the ceiling material and the structure above.

telecommunications: Any transmission, emission, and reception of signs, signals, writings, images, and sounds, that is, information of any nature by cable, radio, optical, or other electro-magnetic systems.

telecommunications entrance facility: See entrance facility (telecommunications).

telecommunications entrance room or space: See entrance room or space (telecommu-nications).

telecommunications infrastructure: See infrastructure (telecommunications).

telecommunications outlet: An assembly of components consisting of one or more connect-ors mounted on a faceplate, housing or supporting bracket.

transverse conversion loss: A ratio, expressed in dB, of the measured common mode volt-age on a pair relative to the differential mode voltage on…