VISITING QUARTERS & APF COMPANION
JOINT BASE CHARLESTON, SC
Solicitation Number F4199-11-P-1300
AFMC/AFPC NO: 133003
APF COMPANION PROJECT NO: DKFX 98-3011
SPECIFICATIONS VOL. 2
RTA Design Submittal October 10, 2014
AIR FORCE MATERIAL COMMAND / AIR FORCE PERSONNEL CENTER
LACKLAND AIR FORCE BASE
SAN ANTONIO, TEXAS
Submitted by:
LEE & SAKAHARA ARCHITECTS AIA, INC.
Architecture, Planning, Interiors 6280 South Valley View, Suite 116
Las Vegas, Nevada 89118 Tel: 702‐270‐6600
(THIS PAGE INTENTIONALLY LEFT BLANK)
Visiting Quarters PROJECT TABLE OF CONTENTS Charleston AFB, S. Carolina TOC - 1
PROJECT TABLE OF CONTENTS
DIVISION 01 - GENERAL REQUIREMENTS
01 11 00 SUMMARY OF WORK
01 14 00 WORK RESTRICTIONS
01 30 00 ADMINISTRATIVE REQUIREMENTS
01 32 01.00 10 PROJECT SCHEDULE
01 33 00 SUBMITTAL PROCEDURES
01 33 29 LEED(TM) DOCUMENTATION
01 35 26 GOVERNMENT SAFETY REQUIREMENTS
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00.00 10 QUALITY CONTROL
01 45 00.10 10 QUALITY CONTROL SYSTEM (QCS)
01 45 35 SPECIAL INSPECTION FOR SEISMIC-RESISTING SYSTEMS
01 45 37 SPECIAL INSPECTION FOR PROGRESSIVE COLLAPSE RESISTING SYSTEMS
01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS
01 50 10 ENVIRONMENTAL (JBC)
01 54 00 GREEN PROCUREMENT (JBC)
01 56 39 TEMPORARY TREE AND PLANT PROTECTION
01 57 20 WASTE MANAGEMENT (JBC)
01 57 23 TEMPORARY STORM WATER POLLUTION CONTROL
01 57 50 TEMPORARY ENVIRONMENTAL CONTROLS (JBC)
01 58 00 PROJECT IDENTIFICATION
01 78 00 CLOSEOUT SUBMITTALS
01 78 23 OPERATION AND MAINTENANCE DATA
01 81 19 CONSTRUCTION INDOOR AIR QUALITY (IAQ) MANAGEMENT
DIVISION 02 - EXISTING DONDITIONS
02 41 00 DEMOLITION AND DECONSTRUCTION
02 82 14.00 10 ASBESTOS HAZARD CONTROL ACTIVITIES
02 82 33.13 20 REMOVAL-CONTROL AND DISPOSAL OF PAINT WITH LEAD
DIVISION 03 - CONCRETE
03 11 18 UNDERSLAB VAPOR BARRIER
03 30 00 CAST-IN-PLACE CONCRETE
03 36 10 POLYMER MODIFIED CEMENTIITOUS SKIMCOATING OF ABRADED CONCRETE
03 36 20 CONCRETE STAINING AND SEALING
03 45 00 PRECAST ARCHITECTURAL CONCRETE
03 60 00 GROUTING
DIVISION 04 - MASONRY
04 21 13 BRICK MASONRY
04 22 00 CONCRETE UNIT MASONRY
04 72 20 PRECAST CONCRETE STONE MASONRY TRIM
DIVISION 05 - METALS
05 12 00 STRUCTURAL STEEL FRAMING
05 31 00 STEEL DECKING
05 40 00 COLD-FORMED METAL FRAMING
Charleston AFB, S. Carolina TOC - 2
05 44 00 COLD-FORMED METAL TRUSSES
05 50 00 METAL FABRICATIONS
05 51 00 METAL STAIRS
05 51 20 TRASH ENCLOSURE GATES
05 52 12 STEEL PIPE AND TUBE RAILINGS
05 73 00 DECORATIVE METAL RAILINGS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 10 53 MISCELLANEOUS ROUGH CARPENTRY
06 16 00 SHEATHING
06 20 24 INTERIOR FINISH CARPENTRY
06 22 22 EXTERIOR ARCHITECTURAL FIBER CEMENT TRIM
06 41 12 WOOD-VENEER AND PLASTIC LAMINATE FACED ARCHITECTURAL CABINETS
06 61 16 SOLID SURFACE FABRICATIONS
06 64 00 PLASTIC PANELING
06 74 13 FIBERGLASS REINFORCED GRATINGS
DIVISION 07 - THERMAL & MOISTURE PROTECTION
07 11 50 SELF ADHERED HIGH PERFORMANCE UNDERLAYMENT (SAHP)
07 19 00 WATER REPELLENTS
07 21 00 THERMAL INSULATION
07 24 19 WATER-DRAINAGE EXTERIOR INSULATION AND FINISH SYSTEM (EIFS)
07 27 29 AIR-BARRIER COATINGS
07 42 14 EXTERIOR STONE FACED ALUMINUM HONEYCOMB PANELS
07 54 23 THERMOPLASTIC POLYOLEFIN (TPO) ROOFING
07 61 20 STRUCTURAL STANDING SEAM METAL ROOF
07 62 00 SHEET METAL FLASHING AND TRIM
07 71 00 ROOF SPECIALTIES
07 71 27 BELLOWS TYPE ROOF EXPANSION JOINTS
07 72 00 ROOF ACCESSORIES
07 72 23 BOXED CORNER LOUVER PENTHOUSES
07 84 13 PENETRATION FIRESTOPPING
07 84 46 FIRE-RESISTIVE JOINT SYSTEMS
07 92 00 JOINT SEALANTS
07 95 01 EXPANSION CONTROL JOINTS
DIVISION 08 - OPENINGS
08 11 13 HOLLOW METAL DOORS AND FRAMES
08 14 16 FLUSH WOOD DOORS
08 31 13 ACCESS DOORS AND FRAMES
08 32 14 SLIDING ALUMINUM-FRAMED GLASS DOORS
08 34 73 SOUND CONTROL DOOR ASSEMBLIES
08 38 23 FOOD SERVICE TRAFFIC DOORS
08 41 13 ALUMINUM FRAMED ENTRANCES AND STOREFRONTS
08 42 29 SLIDING AUTOMATIC ALUMINUM ENTRANCES
08 51 13 ALUMINUM WINDOWS
08 71 00 DOOR HARDWARE
08 80 00 GLAZING
08 83 08 SILVERED MIRRORS
08 91 18 FIXED LOUVERS
08 95 17 ALUMINUM LAUNDRY WALL VENT CAPS
Charleston AFB, S. Carolina TOC - 3
DIVISION 09 - FINISHES
09 21 16 GYPSUM BOARD SHAFT WALL SYSTEMS
09 22 17 NON LOAD BEARING METAL FRAMING
09 22 26 CONVENTIONAL AND WALL-TO-WALL DRYWALL AND PLASTER SUSPENSION
SYSTEMS
09 24 00 PORTLAND CEMENT PLASTERING
09 29 00 GYPSUM BOARD
09 30 00 TILING
09 30 33 STONE TILING
09 51 23 ACOUSTICAL TILE CEILINGS
09 65 13 RESILIENT BASE AND ACCESSORIES
09 65 16 RECYCLED RUBBER COMPOSITE SHEET ATHLETIC FLOORING
09 68 13 TILE CARPETING
09 68 16 SHEET CARPETING
09 75 10 SOLID SURFACING WALL CLADDING
09 75 16 STONE BASE
09 91 13 EXTERIOR PAINTING
09 91 23 INTERIOR PAINTING
09 93 00 STAINING AND TRANSPARENT FINISHING
DIVISION 10 - SPECIALTIES
10 14 25 SIGNAGE
10 21 13 SOLID POLYMER TOILET COMPARTMENTS
10 22 13 WIRE MESH PARTITIONS
10 22 39 MANUALLY OPERABLE ACOUSTICAL PANEL PARTITIONS
10 26 00 WALL SURFACE PROTECTION
10 28 00 TOILET, BATH, AND LAUNDRY ACCESSORIES
10 44 13 FIRE EXTINGUISHER CABINETS
10 51 13 METAL LOCKERS
DIVISION 11 - EQUIPMENT
11 05 13 COMMON MOTOR REQUIREMENTS FOR EQUIPMENT
11 40 20 FOODSERVICE EQUIPMENT
11 52 13 PROJECTION SCREENS
DIVISION 12 - FURNISHINGS
12 36 41 NATURAL STONE SLAB COUNTERTOPS
12 36 62 SIMULATED STONE (SOLID SURFACING) COUNTERTOPS
12 48 12 ROLLUP RAIL MATS WITH BRISTLE FILAMENT
12 93 20 BICYCLE RACKS
DIVISION 14 - CONVEYING SYSTEMS
14 24 00 HYDRAULIC ELEVATORS
14 91 20 LAUNDRY FACILITY CHUTES
DIVISION 21 - FIRE SUPPRESSION
21 12 00 STANDPIPE SYSTEMS
21 13 13.00 10 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION
21 30 00 FIRE PUMPS
Charleston AFB, S. Carolina TOC - 4
DIVISION 22 - PLUMBING
22 05 13 COMMON MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT
22 05 16 EXPANSION FITTINGS AND LOOPS FOR PLUMBING PIPING
22 05 17 SLEEVES AND SLEEVE SEALS FOR PLUMBING PIPING
22 05 18 ESCUTCHEONS FOR PLUMBING PIPING
22 05 19 METERS AND GAGES FOR PLUMBING PIPING
22 05 23 GENERAL-DUTY VALVES FOR PLUMBING PIPING
22 05 29 HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT
22 05 48 VIBRATION AND SEISMIC CONTROLS FOR PLUMBING PIPING AND EQUIPMENT
22 05 53 IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT
22 07 16 PLUMBING EQUIPMENT INSULATION
22 07 19 PLUMBING PIPING INSULATION
22 11 16 DOMESTIC WATER PIPING
22 11 19 DOMESTIC WATER PIPING SPECIALTIES
22 11 23 DOMESTIC WATER PUMPS
22 11 23.13 DOMESTIC-WATER PACKAGED BOOSTER PUMPS
22 12 23 FACILITY INDOOR POTABLE-WATER STORAGE TANKS
22 13 16 SANITARY WASTE AND VENT PIPING
22 13 19 SANITARY WASTE PIPING SPECIALTIES
22 14 13 FACILITY STORM DRAINAGE PIPING
22 14 23 STORM DRAINAGE PIPING SPECIALTIES
22 14 29 SUMP PUMPS
22 33 00 ELECTRIC, DOMESTIC-WATER HEATERS
22 34 00 PACKAGED DOMESTIC HOT WATER SYSTEM
22 35 00 DOMESTIC-WATER HEAT EXCHANGERS
22 41 00 RESIDENTIAL PLUMBING FIXTURES
22 45 00 EMERGENCY PLUMBING FIXTURES
DIVISION 23 - HEATING, VENTILATING AND AIR CONDITIONING
23 05 13 COMMON MOTOR REQUIREMENTS FOR HVAC EQUIPMENT
23 05 16 EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING
23 05 17 SLEEVES AND SLEEVE SEALS FOR HVAC PIPING
23 05 18 ESCUTCHEONS FOR HVAC PIPING
23 05 19 METERS AND GAGES FOR HVAC PIPING
23 05 23 GENERAL-DUTY VALVES FOR HVAC PIPING
23 05 29 HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
23 05 33 HEAT TRACING FOR HVAC PIPING
23 05 48 VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND EQUIPMENT
23 05 53 IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT
23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC
23 07 00 HVAC INSULATION
23 08 00 COMMISSIONING OF HVAC SYSTEMS
23 09 20 HVAC CONTROL SYSTEM
23 11 23 FACILITY NATURAL-GAS PIPING
23 21 13 HYDRONIC PIPING
23 21 13.13 UNDERGROUND HYDRONIC PIPING
23 21 16 HYDRONIC PIPING SPECIALTIES
23 21 23 HYDRONIC PUMPS
23 25 00 HVAC WATER TREATMENT
23 31 13 METAL DUCTS
23 33 00 AIR DUCT ACCESSORIES
23 34 23 HVAC POWER VENTILATORS
23 37 13 DIFFUSERS, REGISTERS, AND GRILLES
Charleston AFB, S. Carolina TOC - 5
23 51 00 BREECHINGS, CHIMNEYS, AND STACKS
23 64 26 ROTARY-SCREW WATER CHILLERS
23 72 00 AIR-TO-AIR ENERGY RECOVERY EQUIPMENT
23 82 19 FAN COIL UNITS
DIVISION 26 - ELECTRICAL
26 05 13 MEDIUM-VOLTAGE CABLES
26 05 19 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
26 05 26 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
26 05 29 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
26 05 33 RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
26 05 48 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS
26 05 53 IDENTIFICATION FOR ELECTRICAL SYSTEMS
26 13 00 MEDIUM-VOLTAGE SWITCHGEAR
26 22 00 LOW-VOLTAGE TRANSFORMERS
26 23 00 LOW-VOLTAGE SWITCHGEAR
26 24 16 PANELBOARDS
26 27 26 WIRING DEVICES
26 28 13 FUSES
26 28 16 ENCLOSED SWITCHES AND CIRCUIT BREAKERS
26 29 23 VARIABLE-FREQUENCY MOTOR CONTROLLERS
26 51 00 INTERIOR LIGHTING
26 56 00 EXTERIOR LIGHTING
DIVISION 27 - COMMUNICATIONS
27 11 00 COMMUNICATIONS EQUIPMENT ROOM FITTINGS
27 15 00 COMMUNICATIONS HORIZONTAL CABLING
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 13 31 TWO WIRED DOOR CHIMES
28 13 33 DOORBELL AND PHONE SIGNALERS FOR THE HEARING IMPAIRED
28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM
DIVISION 31 - EARTHWORK
31 10 00 SITE CLEARING
31 20 00 EARTH MOVING
31 31 16 SOIL TREATMENT FOR SUBTERRANEAN TERMITE CONTROL
31 50 00 EXCAVATION SUPPORT AND PROTECTION
31 62 13 CONCRETE PILES
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 12 16 ASPHALT PAVING
32 13 13 CONCRETE PAVING
32 13 73 CONCRETE PAVING JOINT SEALANTS
32 14 43 CONCRETE GRID PAVEMENTS
32 17 13 PARKING BUMPERS
32 17 23 PAVEMENT MARKINGS
32 92 00 TURF AND GRASSES
32 93 00 PLANTS
DIVISION 32 - UTILITIES
Charleston AFB, S. Carolina TOC - 6
33 05 00 COMMON WORK RESULTS FOR UTILITIES
33 11 00 WATER DISTRIBUTION
33 30 00 SANITARY SEWERS
33 41 00 STORM UTILITY DRAINAGE PIPING
33 70 02 ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND
APPENDICES
Appendix 1 - SUBMITTAL REGISTER
Appendix 2 - GEOTECHNICAL ENGINEERING REPORT: APF Companion
Appendix 3 - LIMITED ASBESTOS AND LEAD PAINT SURVEY REPORT: JBC Building 362
Appendix 4 - GEOTECHNICAL ENGINEERING REPORT: NEW VISITORS QUARTERS (VQ)
Appendix 5 – ASBESTOS, LEAD PAINT AND VISUAL HAZARDOUS MATERIALS SURVEY REPORT
Appendix 6 – EXISTING POOL DRAWINGS (FOR INFORMATION ONLY)
Appendix 7 – RICKENBACKERs SLAT WALL INFORMATION
-- End of Project Table of Contents
Visiting Quarters GYPSUM BOARD SHAFT WALL SYSTEM Charleston AFB, S. Carolina 09 21 16 - 1
SECTION 09 21 16
GYPSUM BOARD SHAFT WALL SYSTEMS
PART 1 GENERAL
1.1 SUMMARY
A. Furnish and install gypsum board shaft wall systems as indicated on the drawings and specified.
B. Related Sections
1. Section 013329 “LEED Documentation”
2. Section 015400 “Green Procurement”
3. Section 015720 “Waste Management”
4. Section 018119 “Construction Indoor Air Quality”
1.2 SYSTEM DESCRIPTION
A. Gypsum board shaft wall systems shall have been are pretested assemblies of gypsum boards and other components designed for erection from room-side of shaft.
B. Fire-Resistance Ratings: Where indicated, provide materials and construction which are identical to those of assemblies, including those incorporating elevator door and other framing, whose fire resistance has been determined per ASTM E119 by a testing and inspecting organization acceptable to authorities having jurisdiction.
C. Sound Attenuation Performance: Provide gypsum board shaft systems designed and pretested to achieve a minimum STC Rating of 50.
1.3 SUBMITTALS
A. Product data from manufacturers for the gypsum board shaft wall system specified.
B. Product test reports indicating and interpreting test results relative to compliance of gypsum board shaft wall systems with fire resistance, and acoustical performance requirements.
C. Research reports or evaluation reports of the model code organization acceptable to authorities having jurisdiction which evidence system's compliance with requirements.
D. LEED Submittals: Submit all applicable Accountability Forms as required by LEED For New Construction for the following:
1. Product Data for Credit MR 4: For products having recycled content, documentation indicating percentages by weight of postconsumer and preconsumer recycled content. Include statement indicating cost for each product having recycled content.
2. Materials and Resources credit 5 - Regional Materials, Extracted, Processed & Manufactured Regionally
Charleston AFB, S. Carolina 09 21 16 - 2
3. Indoor Environmental Quality credit 4.1 - Low-Emitting Materials, Adhesives & Sealants
1.4 QUALITY ASSURANCE
A. Single Source Responsibility: Obtain products for gypsum board shaft wall systems from a single manufacturer for each type of system indicated.
PART 2 PRODUCTS
2.1 GYPSUM BOARD SHAFT WALL SYSTEMS
A. Manufacturers: Subject to compliance with specified requirements, provide products by one of the following (or equal):
1. Georgia Pacific Corporation.
2. Gold Bond Building Products Div., National Gypsum Co.
3. United States Gypsum Co.
B. Provide standard materials and components listed in manufacturer's published product literature for gypsum board shaft wall systems of type and application indicated.
1. Provide gypsum boards in maximum lengths available to eliminate or minimize end-to-end butt joints and in thickness required to produce assemblies complying with structural and other performance requirements.
2. Provide mold resisting panels on the interior surface of shafts.
MOLD RESISTANT GYPSUM PANEL SYSTEM
Panel Fasteners Joint Tape Joint Treatment Panel Source
5/8" Sheetrock Humitek regular, Firecode Core, or Firecode C Core Gypsum panels
Wood: 1 ¼” Type W drywall screws.
Steel: 1 ¼” Type S or S-12 drywall screw.
Sheetrock paper tape regular or Heavy
Sheetrock Setting Type, Lightweight Setting, Sheetrock Taping, Topping, or All-Purpose, Sheetrock Ready-Mixed Taping, Topping, or All- Purpose, or Sheetrock Lightweight All-Purpose or Ready-Mixed - Plus 3
United States Gyp. Co.
5/8" Georgia Pacific DensGuard Dens Armor Interior Guard Type X, Type T, or Type TG-C (Fire-Rated)
Wood: 1 ¼” Type W drywall screws.
Steel: 1 ¼” Type S or S-12 drywall screw.
Sheetrock paper tape regular or Heavy
Same as above Georgia Pacific
5/8" Gold Bond XP regular, Fire-Shield or Fire-Shield C gypsum wallboard
Wood: 1 ¼” Type W drywall screws.
Steel: 1 ¼” Type S or S- 12 drywall screw.
ProForm Joint Tape, ProForm Multi-Flex Tape Bead or Sta-Smooth HS Tape.
ProForm Multi-Use Joint Compound, All Purpose, Lite, Triple-T, Topping, or Easy Finish All Purpose, Light Weight, Topping, or Sta-Smooth, Lite, or HS Joint Compound. Or ProForm XP Joint Compound.
National Gypsum Co.
Charleston AFB, S. Carolina 09 21 16 - 3
C. Steel Framing: ASTM C 645, of profile, size, and base metal thickness required to produce assemblies complying with structural performance requirements, with sectional properties computed to conform with AISI "Specification for Design of Cold-Formed Steel Structural Members."
D. Gypsum Shaftwall Board: ASTM C 442, Type X liner panel or coreboard designed for shaft wall construction, with moisture-resistant paper facings.
E. Gypsum Wallboard: ASTM C 36, Type X, 1 inch thick, tapered and featured edges for prefilling.
F. Trim Accessories: Provide cornerbeads, edge trim and control joints of material and, for edge trim, shapes complying with ASTM C 1047 and gypsum board shaft wall manufacturer's recommendations.
G. Gypsum Wallboard Joint Treatment Materials: Provide materials complying with ASTM C 475, ASTM C 840, recommendations of gypsum board shaft wall manufacturer for the application indicated.
H. Miscellaneous Materials: Provide auxiliary materials for gypsum board shaft wall systems of the type and grade recommended by the manufacturer of the system and as follows:
1. Laminating Adhesive: Special adhesive or joint compound recommended for laminating gypsum boards of type indicated.
2. Gypsum Board Screws: ASTM C 1002.
3. Runner Fasteners: Low-velocity tool-driven fasteners of type, size and material required to withstand loading conditions imposed on shaft wall system without exceeding allowable design stress of runner, fastener or structural substrate.
4. Concealed Acoustical Sealant: As Specified in Section 07920.
5. Spot Grout: ASTM C 475, setting-type joint compound of type recommended for spot grouting hollow metal door frames.
6. Sound Attenuation Blankets: Unfaced mineral fiber blanket insulation produced by combining mineral fibers of type described below with thermosetting resins to comply with ASTM C 665 for Type I (blankets without membrane facing).
PART 3 EXECUTION
3.1 INSTALLATION OF GYPSUM BOARD SHAFT WALL SYSTEMS
A. Install gypsum board shaft wall systems to comply with performance and other requirements indicated as well as with manufacturer's installation instructions.
B. At penetrations in shaft wall, maintain fire rating of entire shaft wall assembly by installing supplementary fire protection behind boxes containing wiring devices, and similar items.
C. Isolate shaft wall system from transfer of structural loading to system, both horizontally and vertically. Provide slip type joints to attain lateral support and avoid axial loading.
Charleston AFB, S. Carolina 09 21 16 - 4
D. Seal gypsum board shaft walls at perimeter of each section which abuts other work and at joints and penetrations within each section. Install acoustical sealant to withstand dislocation by air pressure differential between shaft and external spaces; comply with manufacturer's instructions and ASTM C 919.
-- End of Section --
Visiting Quarters NON LOAD BEARING METAL FRAMING Charleston AFB, S. Carolina 09 22 17 - 1
SECTION 09 22 17
NON LOAD BEARING METAL FRAMING
PART 1 – GENERAL
1.1 SECTION INCLUDES:
A. Light gage metal stud framing for gypsum board attachment at interior walls and partitions.
B. Related backing and bridging.
C. Furring at structural steel framing, masonry and concrete construction for gypsum board attachment.
1.2 RELATED SECTIONS
A. Section 013329 “LEED Documentation”
B. Section 015400 “Green Procurement”
C. Section 015720 “Waste Management”
D. Section 018119 “Construction Indoor Air Quality”
1.3 REFERENCES
A. Metal Lath/Steel Framing Association (ML/SFA) - Specifications for Metal Lathing and
Furring.
1.4 SUBMITTALS
A. Product Data: Metal framing 18 gage and heavier.
B. LEED Submittals: Submit all applicable Accountability Forms as required by LEED For
New Construction for the following:
1. Product Data for Credit MR 4: For products having recycled content, documentation indicating percentages by weight of postconsumer and preconsumer recycled content. Include statement indicating cost for each product having recycled content.
2. Materials and Resources credit 5 - Regional Materials, Extracted, Processed & Manufactured Regionally
3. Indoor Environmental Quality credit 4.1 - Low-Emitting Materials, Adhesives & Sealants
1.5 DELIVERY, STORAGE AND HANDLING
A. Delivery: In original unopened packaging or bundles, with manufacturer's labels intact and legible.
Charleston AFB, S. Carolina 09 22 17 - 2
B. Storage: For metal studs, in enclosed shelter providing protection from damage and exposure to weather, elevated above soil and concrete on wood sleepers.
C. Handling: Promptly remove damaged or deteriorated products from site.
1.5 PROJECT CONDITIONS
A. Environmental Conditions: In cold weather and during plaster and gypsum board application and finishing, maintain temperature within building between 55 degrees F and 70 degrees F.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Acceptable Manufacturers: Products of the manufacturers listed below will be acceptable.
Equivalent products of other manufacturers will be considered in accordance with the "or equal" provision specified in the General Terms and Conditions.
1. California Expanded Metal Products Co. (CEMCO). City of Industry, CA (818)
369-3564.
2. National Gypsum Co. (Gold Bond). Charlotte, NC (704) 365-7315 or (800) 628-
4662; local sales office, Long Beach, CA (310) 435-4465.
3. Western Metal Lath Co., La Mirada, CA (310) 944-6117 or (714) 523-2160).
4. Delta-Star, Inc., Belmont, CA (800) 892·8673.
2.2 LIGHT GAGE METAL FRAMING, GENERAL
A. Light Gage Metal Framing, General:
1. Provide metal gage as indicated on the Drawings.
2. Comply with framing manufacturers published criteria for span and metal gage.
Provide not less than gage indicated on the Drawings nor less than recommended gage for L/360 deflection of framing, whichever is greater.
3. Provide 16 gage studs typically at the following locations:
a. Walls with case work or walls with wall-mounted equipment.
b. Studs at door and window jambs and at door headers.
4. Provide not less than 25 gage studs elsewhere.
2.3 LIGHT GAGE METAL FRAMING, 18 GAGE AND LIGHTER
A. Framing Members (Studs/Joists): ASTM C 645, minimum yield strength 33 ksi, types, and sizes as indicated on Drawings, gage as indicated on Drawings and as required to meet span and deflection limitations, punched web unless otherwise indicated, with screw-type flanges.
Charleston AFB, S. Carolina 09 22 17 - 3
B. Tracks, Sills and Headers: Unpunched channels sized for stud flanges, gage the same as studs unless otherwise noted. Under structural framing members and decking, provide deflection track at head of partition, as indicated on the Drawings.
C. Flexible Top Track: UL-listed and labeled assembly.
1. Specified Manufacturer: Metal-Lite., Anaheim, CA (800/886-6824).
2. Acceptable Manufacturers: None identified. Equivalent products of other manufacturers will be considered in accordance with the "or equal" provision specified in the General Terms and Conditions.
3. Flexible Head Track: The System as manufactured by Metal-Lite, Inc., comply with California Building Code (CBC) Section 702 and approved by OSHPD, system number to suit fire rating of wall or partition and to suit installation conditions, as indicated on the Drawings. System shall consist of minimum 16 gage galvanized sheet steel components with formed steel channels with slotted flanges and with pop-up tabs in the web.
4. Flute cover plates: Flanged galvanized sheet steel, formed to suit~ profile of decking flutes.
5. Mineral wool fire stopping insulation: As specified in Section 07840 - Firestopping and Smoke Seals.
D. Finish: Hot dipped galvanized, ASTM A 653/A 653M, G60 (Z180).
C. Screws: As recommended or required by manufacturer, self-drilling, self-tapping in accordance with manufacturer's recommendations and ML/SFA specifications.
2.4 LIGHT GAGE METAL FRAMING, 16 GAGE AND HEAVIER
A. 16 Gage and Heavier Studs: ASTM C 645, minimum yield strength 33 ksi, types, sizes as indicated on Drawings, punched web unless otherwise indicated, with screw-type flanges.
B. Finish: Hot dipped galvanized, ASTM A 653/A 653M, G60 (Z180).
C. Standard Structural Steel Shapes and Plates: As specified in Section 05505 -
Miscellaneous Metal Fabrications.
D. Fabricated Steel Items: As specified in Section 05505 - Miscellaneous Metal
Fabrications, ASTM A 283, grade optional.
E. Flat-Rolled Carbon Steel Sheets: ASTM A 611.
F. Cold-Rolled Carbon Steel Sheets: ASTM A 366.
G. Other Fasteners: Provide all bolts, nuts, screws, clips, washers and any other fastenings necessary for proper erection of items specified herein. See Section 05090 - Anchors and Fasteners for additional requirements.
2.5 ACCESSORIES
A. Acoustical Vinyl Foam Tape: Norseal V730 by Norton Tape Division, or approved equal.
Charleston AFB, S. Carolina 09 22 17 - 4
B. Backing Plates: 16 gage galvanized sheet metal covering full width of stud spacing by 4-inches wide minimum, for attachment and support of products to be attached to framing.
PART 3 - EXECUTION
3.1 LIGHT GAGE METAL FRAMING ERECTION
A. Track Installation: Place and align tracks in configurations shown.
1. Secure top, bottom and side tracks at maximum 24-inches on center to structure using fasteners as specified in Section 05090- Anchors and Fasteners.
2. Provide flexible head track as indicated on Drawings, to prevent transfer to non-load bearing framing.
B. Studs and Joists Installation: Install studs/joists at 16-inches on center typically, unless otherwise indicated. Studs at gypsum board walls and partitions shall be placed so that their flanges point in the same direction.
1. Do not splice studs and joists.
2. Provide studs not more than 2-inches from each corner of wall or abutting construction.
3. Place 18 gage and heavier studs with bottom bearing solidly on bottom of track to transfer axial loads from stud to underlying structure.
4. Double studs adjacent to doors and openings and securely attach to top and bottom track either by welding or screws, and to door head tracks with clip angles. Locate additional studs not more than 2 inches from door and window frames, abutting partitions or partition corners. Above door and window openings place a section of track with a clip angle at each end horizontally, and attach securely to the adjacent vertical studs.
a. Install cut-to-Iength studs at the location of vertical joints and at standard spacing over the door frame header extending to the ceiling track.
b. At corner of stud walls provide three studs minimum. Locate studs to provide surfaces for attachment of all interior and exterior facings.
5. Coordinate erection of studs/joists with installation of service utilities to minimize discontinuity in framing. Align stud web openings.
6. Maintain clearance under building structural members to avoid deflection transfer to non-load bearing framing.
7. Brace studs/joists to make rigid with steel channel bridging.
a. Provide bridging in accordance with manufacturer's recommendations, installed in the "punch outs" of their studs.
b. Steel channels shall be in longest possible lengths, lapped 12-inches and wire tied at joints.
c. Install interlocking bridging member through stud web openings at studs
7-feet 6 inches in length or greater.
Charleston AFB, S. Carolina 09 22 17 - 5
d. At partitions/walls to receive ceramic tile or stone finish, provide 3/4-inch channel horizontal stiffener at no more than 5 feet o.c. vertically. Weld stiffeners to each stud.
e. Provide 7/8 inch hat shaped channel at mid-point of stud area above ceilings where gypsum board is not applied.
f. Provide additional 3/4-inch channel 6 inches above door head and extending two stud spaces beyond jamb studs.
8. At acoustically insulated partitions, install specified continuous strip of vinyl foam tape between floor and floor track, between ceiling and ceiling track, and at underside of steel deck and where partition vertical edges abut walls and surfaces of different materials.
C. Built-in Components: Provide framed openings for all built-in and recessed components.
1. Coordinate erection of framing with installation of bucks, anchors, backing, blocking, plumbing, mechanical and electrical components to provide necessary clearances and supports.
2. Coordinate erection of framing with requirements for door and window frame supports and attachments.
D. Backing Installation: Install stud track or sheet metal backing as indicated and as necessary to support all products attached to wall or ceiling after completion of finish surface, including toilet and bath accessories, plumbing and electrical fixtures, electrical panels, toilet partitions, casework, hardware, handrails and trim.
1. Coordinate precise locations of backing with Work specified in other Sections.
2. Plates shall be not lighter than 16 gage x 6 inches wide, and of such lengths as to span minimum of 3 studs.
3. Weld or bolt backing plates rigidly to studs as indicated on the Drawings and shown on reviewed shop drawings.
4. Weld or bolt plates at top and bottom of each stud crossing.
5. Paint bare surfaces of plates and welds with metal primer after installation.
E. Openings and Recesses: Provide framed openings for all recessed components.
Coordinate installation of framing with requirements for door and window frame supports and attachments.
F. Bracing Installation: Install bracing at studs/joists to make rigid. Do not install cross bracing at double stud walls and partitions unless acceptable to Contracting Officer, to preserve acoustical quality of assembly.
Visiting Quarters CONVENTIONAL AND WALL-TO-WALL DRYWALL Charleston AFB, S. Carolina AND PLASTER SUSPENSION SYSTEMS
09 22 26 - 1
SECTION 09 22 26
CONVENTIONAL AND WALL-TO-WALL DRYWALL AND PLASTER SUSPENSION SYSTEMS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General Conditions and other Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Conventional metal support systems as indicated and/or described.
2. Wall-to-wall drywall and plaster suspension system.
B. Regulatory Requirements: Comply with the requirements of the local authorities having jurisdiction.
C. Related Sections:
1. Section 013329 “LEED Documentation”
2. Section 015400 “Green Procurement”
3. Section 015720 “Waste Management”
4. Section 018119 “ Construction Indoor Air Quality (IAQ) Management”
1.3 ACTION SUBMITTALS
A. Shop Drawings: Submit drawings showing framing, connection details, accessories and anchorage. Indicate location of assemblies and size and spacing of framing components.
B. Product Data: Submit manufacturer's catalog data for each item proposed for installation.
C. Certificates: Furnish manufacturer's certification that materials meet or exceed Specification requirements.
D. LEED Submittals: Submit all applicable Accountability Forms as required by LEED For New Construction for the following:
1. Product Data for Credit MR 4: For products having recycled content, documentation indicating percentages by weight of postconsumer and preconsumer recycled content. Include statement indicating cost for each product having recycled content.
2. Materials and Resources credit 5 - Regional Materials, Extracted, Processed & Manufactured Regionally
3. Indoor Environmental Quality credit 4.1 - Low-Emitting Materials, Adhesives & Sealants
09 22 26 - 2
1.4 QUALITY ASSURANCE
A. Coordinate with related Work to provide blocking for items mounted on finished surfaces and to provide allowances for pipes and other items inside partitions and walls.
B. Tolerances: Install walls and partitions on straight lines, plumb, free of twists or other defects, and contacting a 10 foot straightedge for its entire length at any location within a 1/8 inch tolerance. Install horizontal framing level within a tolerance of 1/8 inch in 12 feet in any direction.
1.5 DELIVERY, STORAGE AND HANDLING
A. All materials shall be delivered in their original unopened packages and stored protected from damage. Do not store material directly on grade. Provide adequate support to prevent bowing of material prior to installation.
B. Store welding electrodes in accordance with AWS D12.1.
PART 2 - PRODUCTS
2.1 CONVENTIONAL DRYWALL AND PLASTER SUSPENSION SYSTEMS
A. Provide products manufactured by one of following (or equal):
1. Dale/Incor.
2. Dietrich Industries, Inc.
3. Marino/Wade.
4. Camco
5. Current members of Steel Stud Manufacturers Association (SSMA).
B. Light Gage Metal Framing:
1. Metal framing shall be formed from corrosion resistant-steel conforming to requirements of ASTM A653, 33 ksi minimum.
2. Metal framing shall be zinc coated in conformance to requirements of ASTM A926, G60.
3. Metal framing shall be manufactured in conformance to ASTM C645.
4. Install metal framing according to ASTM C1007, Standard Specification for Installation of Load-Bearing (Transverse and Axial) Steel Studs and Related Accessories.
C. Studs: SSMA, ICBO ER-4943P, minimum yield 33 ksi, hot-dipped galvanized or electro galvanized sheet steel, G-60, C Stud type, punched web (except tracks and joists), C-shaped, sizes required to conform to details and scheduled wall thicknesses. Studs shall be rolled from new steel sheet and shall not be produced from re-rolled steel. Stud flanges shall not be less than 1-5/16 inch wide; track flanges, not less than 1-1/4 inch wide.
1. Wall Framing and Furring for Plaster and Mortar Beds: Studs and tracks shall be 18 gage minimum, unless otherwise indicated.
2. Wall Framing and Furring for Gypsum Wallboard: Studs and tracks shall be 20 gage minimum, unless otherwise indicated.
09 22 26 - 3
3. Load-Bearing Studs: Studs and members thicker than 18 gage (0.0438 inch) shall conform to ASTM C 995.
4. Stud gages indicated on Drawings or specified are the minimum. Where required stud height and/or loads exceed code requirements or manufacturer's recommendations, provide heavier gage studs and/or decrease stud spacing as necessary to conform to code requirements.
D. Suspended and Furred Ceiling Systems and Wall Furring: Suspended ceiling framing system shall support finished ceiling, light fixtures, air diffusers, and accessories, as required. suspension system shall provide a maximum deflection of L/240. Carrying channels shall be fabricated from minimum 0.0548 inch thick cold-rolled steel, 1-1/2 inch wide x 7/16 inch deep. Carrying channels for supports under ducts shall be 2 inches in size as specified. Carrying channels shall be fabricated from hot-dip galvanized coated sheet.
1. Plaster Ceilings: Cross furring members shall conform to ASTM C 645, and shall be fabricated from cold-rolled steel, 3/4 inch wide x 7/16 inch deep. Furring members shall be fabricated from hot-dip galvanized coated sheet.
2. Gypsum Wallboard Ceilings: Furring members shall be fabricated from cold-rolled steel, 7/8 inch x 2-9/16 inches. Furring members shall be fabricated from hot-dip galvanized coated sheet.
E. Framed Ceilings: Framed ceiling framing system shall support finished ceiling, light fixtures, air diffusers, and accessories, as required. suspension system shall provide a maximum deflection of L/240.
1. Plaster and Gypsum Wallboard Ceilings: Ceiling joists shall conform to ASTM C 645, hot-dip galvanized coated steel, C-shaped, unpunched, 20 gage minimum thickness, unless noted otherwise.
F. Framing Accessories: Provide all standard related accessories including floor and ceiling tracks, clips, web stiffeners, anchors, and similar items, of same manufacture as each type of stud specified, and as required for a complete installation.
G. Splay Wires and Compression Struts: Approved manufacturers acceptable to manufacturer of ceiling grids, gages and types as required by building codes for ceiling types and weights specified.
1. Vertical Compression Strut: Provide USG Donn Compression Post, or equal, with the manufacturer’s standard corrosion inhibiting finish and of the types and designs complying with requirements of authorities having jurisdiction and CBC Seismic Zone 4 requirements. provide base attachment clip for connection of vertical strut to main beams.
H. Wires: Soft-annealed galvanized steel wire, 8 gage for hanger wires and 16 gage for framing unless otherwise specified.
I. Fasteners: Wafer-head screws, self-drilling type for 20 gage metal and heavier. ASTM C954 self-drilling, self-tapping screws, Type S-12 pan head, 1/2 inch long.
J. Fire Rated Acoustical Foam Tape: Compressible, closed cell polyvinyl chloride foam with pressure sensitive adhesive, in rolls with protective release liner on non-adhesive face, 6 pounds per cubic foot density, 1 inch wide x not less than 1/4 inch thick, self-
09 22 26 - 4 extinguishing, UL 94 recognized, Norseal V740FR, manufactured by Norton Performance Plastics Corporation, or equal.
K. Zinc-Rich Paint: Conform to Fed Spec DOD-P-21035A, Z.R.C. "Cold Galvanizing Compound", manufactured by ZRC Products Company. Provide for touch-up of galvanized surfaces.
L. Steel Backing Plates: Provide a minimum 4 inch wide by l6 gage steel, or sections of studs and stud track welded or fastened to web of studs, except as otherwise indicated.
Apply shop coat of metal primer.
M. Anchorage Devices Powder Actuated: Minimum 0.177 inch diameter by 1-7/16 inch long fasteners in regular concrete and 0.145 inch diameter by 1-1/8 inch long fasteners in lightweight concrete. Allowable shear and tension values as permitted in ICBO Report No. 2388, 1639 or 1147, reduced to 80 percent.
N. Anchorage Devices, Drilled Expansion Anchors: Minimum 3/8 inch diameter with 2-1/4 inch embedment. Allowable shear and tension values as permitted in ICBO Report No.
1372, 2895 or 4627, reduced to 80 percent.
2.2 WALL TO WALL DRYWALL AND PLASTER SUSPENSION SYSTEMS (WWDPSS)
A. WWDPSS shall be as manufactured by USG (United States Gysum Company, USG Interiors), or equal, in compliance with applicable ASTM Standards.
B. OTHER Acceptable Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to , the following:
1. American Gypsum.
2. CertainTeed Corp.
3. Georgia-Pacific Gypsum LLC.
4. Lafarge North America Inc.
5. National Gypsum Company.
6. PABCO Gypsum.
7. Temple-Inland.
C. Drywall Suspension Systems – Commercial quality, cold-rolled steel, hot dipped galvanized finish.
1. Main Tees: Fire-Rated Heavy Duty classification 1.617” high x 144” long, integral reversible splice with knurled face. (DGL-26 15/16” Face and 1-1/2” high)
2. Cross Members: Fire-Rated members with knurled face. Cross Tees: DGLW-424 cross tee1-1/2” high x 48” long with 1-1/2” wide face; quick release cross tee ends for positive locking and removability without tools
3. Accessory Cross Tees: Cross tees must have knurled faces and quick release cross tee ends for positive locking and removability without tools.
DGL-224 Fire-Rated 1-1/2” high x 24” long with 15/16” face DGL-324 Fire-Rated 1-1/2” high x 36” long with 15/16” face DGL-424 Fire-Rated 1-1/2” high x 48” long with 15/16” face DGL-824 Non Fire-Rated 1-1/2” high x 96” long with 15/16” face DGLW-224 Fire-Rated 1-1/2” high x 24” long with 1-1/2” face
09 22 26 - 5
DGLW-424 Fire-Rated 1-1/2” high x 48” long with 1-1/2” face
4. Wall Moldings: Single web with knurled face
(DGWM-16 1” x 1” x 144” long wall molding) (DGCM-27 144” x 1-5/8” x 1” x 1” channel molding)
5. Accessories: As standard with the manufacturer.
6. Wire: Hanger Wire (12 ga.), galvanized or as noted on drawings
D. USG Drywall Wall-to-Wall Suspension Systems – Commercial quality, cold-rolled steel, hot dipped galvanized finish for use in corridars and short span applications.
1. Main Tees: Fire-Rated Heavy Duty classification, integral reversible splice with 1- 1/2” knurled face.
2. Wall Moldings: Single web with knurled face.
PART 3 - EXECUTION
3.1 CONVENTIONAL SUPPORT INSTALLATION
A. Walls and Partitions: Install materials as recommended by the product manufacturer.
1. Fasten floor runners for exterior walls and interior partitions to concrete slab with required power driven fasteners. Spacing of fasteners not to exceed 24 inches on center. Fasten ceiling runners to structure as indicated on the drawings.
2. Sound insulated walls and partitions: Embed floor runner tracks in two beads of acoustical sealant or two runs of compressible tape seal. Install top track nested into slotted track system, in same manner for full height of walls. Where wall ends abutting concrete, masonry, or steel set end studs in two beads of acoustical sealant or two tape seals and secure at 4-foot centers vertically.
3. Space studs not over 16 inch on center unless indicated otherwise. Studs shall be located approximately 2 inches from door frame jambs, abutting partitions and partition corners, except those providing support for door and window openings.
4. Furnish and install manufacturer's standard floor track. Fasten track to floor by means of 1/4 inch x 1-1/4 inch Star "Dryvin" hammer drive anchors or 3/16 inch x 1 inch round head, "Rawl-Drives" one-piece expansion bolts spaced not to exceed 3 feet, and installed in drilled holes in slab, or to wood joist with nails as indicated. Track may be fastened to concrete floor slabs with, power-driven fasteners.
5. Studs shall be seated squarely in track with stud web and flanges abutting track web, plumbed and securely fastened with sheet metal screws, to flanges or web of both floor and top tracks. Provide 4 screws per stud.
6. Where there is no suspended ceiling, tops of stud walls shall be provided with track and shoes and be fastened as specified for floors. Welding of studs to ceiling track will not be permitted except where bearing studs are installed.
09 22 26 - 6
7. Over metal doorframes, install a cut-to-length section of runner track, with flanges slit and web-bent to allow flanges to overlap adjacent vertical studs, and securely fasten to studs. At doorjambs, extend studs continuous to structure above.
8. Bridging, or horizontal bracing of 1-1/2 inch, cold-rolled channels shall be fastened in a manner to prevent stud rotation. Bridging shall be furnished as follows: walls up to 10 feet high, one row at mid-height; walls exceeding 10 feet high, bridging or bracing rows spaced not to exceed 5 feet on center.
9. Wind bracing shall be fastened where indicated on Drawings. Minimum size of strap shall be as indicated on Drawings. Track where strap terminates shall be anchored as indicated on Drawings.
B. Gypsum Wallboard Ceiling Suspension and Framing: Suspended ceiling system framing shall be installed in accordance with ASTM C 754, and as follows.
1. Hangers shall be spaced not more than 48 inches along runner channels and 36 inches in other direction or 42 inches in both directions unless otherwise indicated. Locations of hanger wires shall be coordinated with other Work.
Hangers at ends of runner channels shall be located not more than 6 inches from walls. Hanger wire shall be fastened to structural elements with required fasteners. Sags or twists, which develop in suspended system, shall be adjusted.
Damaged or faulty parts shall be replaced.
2. Main Runners: Hanger wires shall be double strand saddle-tied to runner channels and ends of hanger wire shall be twisted three times around itself. Main runners shall be located to within 6 inches of parallel wall to support ends of cross furring. Main runners shall not come in contact with abutting masonry or concrete walls. Where main runners are spliced, ends shall be overlapped 12 inches with flanges of channels interlocked, and shall be securely tied at each end of splice with wire looped twice around channels.
3. Furring channels shall be fastened to runner channels and to structural supports at each crossing with tie wire, hairpin clips, or required fastenings. Furring channels shall be located within 2 inches of parallel walls and beams, and shall be cut 1/2 inch short of abutting walls.
4. Ceiling Openings: Support members shall be provided as required at ceiling openings for access panels, recessed light fixtures, and air supply or exhaust.
Support members shall be not less than 1-1/2 inch main runner channels and vertically installed suspension wires or straps shall be located to provide at least minimum support specified for furring and wallboard attachment. Intermediate structural members not a part of structural system, shall be provided for attachment or suspension of support members.
5. Light fixtures and air diffusers shall be supported directly from suspended ceiling runners. Wires shall be provided at required locations to support weight of recessed or surface mounted light fixtures and air diffusers.
6. Control Joints: Ceiling control joints for expansion and contraction shall be located where indicated on drawings. A control joint or intermediate blocking shall be installed where ceiling framing members change direction.
09 22 26 - 7
a. Interior Ceilings With Perimeter Relief: Control joints shall be installed so linear dimensions between control joints shall not exceed 50 feet in either direction or more than 2500 square feet in area.
b. Interior Ceilings Without Perimeter Relief: Control joints shall be installed so linear dimensions between control joints shall not exceed 30 feet in either direction nor more than 900 square feet in area.
C. Splay Wires and Compression Struts: Install as detailed and as required to prevent upward and sideward motion under seismic conditions, as required by code.
D. Suspension Under Ducts: For hangers spaced at 4 to 5-1/2 foot centers, provide 6 gage hanger wires with minimum 2 inch runner channels spaced at maximum 48 inch centers.
For greater spans, design system for live load of l0 pounds per square foot of area plus dead load and provide a detail in Shop Drawings.
E. Furring: Provide framing for horizontal furring as shown or required. Conform to above requirements as applicable.
3.2 WALL-TO-WALL INSTALLATION
A. Examine substrates and adjoining construction and conditions under which Work is to be installed. Do not proceed with Work until unsatisfactory conditions are corrected.
B. Standard reference: Install grid members in accordance with ASTM C636, CISCA installation standards, and other applicable references.
C. Manufacturer’s reference: Install in accordance with manufacturer’s current printed recommendations.
D. Drawing reference: Install in accordance with approved shop drawings and locate ceiling in accordance with main tee dimensions relative to elevations.
E. Install in accordance with reference standards and manufacturer's instructions.
F. Corridor (Wall-to-Wall) Applications:
1. Hanger Wire Installation: Secure hanger wires to upper structural elements and space hangers so that each hanger wire supports a maximum of 16 sq. ft.
2. Space main tee members as required by span and deflection design load.
3. Install trim, and similar accessories as necessary and as applicable to meet project requirements where indicated on drawings.
4. Install Control Joints at locations of properly detailed control joints, including additional cross tees as necessary, per direction of architect and/or design professional.
5. Finish boards as described to achieve ‘Level of Finish’ specified.
Visiting Quarters PORTLAND CEMENT PLASTERING Charleston AFB, S. Carolina 09 24 00 - 1
SECTION 09 24 00
PORTLAND CEMENT PLASTERING
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Furnish and install portland cement plastering as indicated on the drawings and specified.
B. Related Sections
1. Section 013329 “LEED Documentation”
2. Section 015400 “Green Procurement”
3. Section 015720 “Waste Management”
4. Section 018119 “Construction Indoor Air Quality”
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product indicated.
B. LEED Submittals:
1. Product Data for Credit MR 4: For products having recycled content, documentation indicating percentages by weight of postconsumer and preconsumer recycled content. Include statement indicating cost for each product having recycled content.
2. Product Data for Credit IEQ 4.1: For sealants, documentation including printed statement of VOC content.
3. Materials and Resources credit 5 - Regional Materials, Extracted, Processed & Manufactured Regionally
1.4 SECTION REQUIREMENTS
A. Submittals: Product Data and finish Samples.
PART 2 - PRODUCTS
2.1 LATH
A. Expanded-Metal Lath: ASTM C 847, galvanized, flat or self-furring as indicated, 3.4-lb/sq. yd. weight.
B. Flat Rib Lath: ASTM C 847, galvanized, rib depth of not more than 1/8 inch and 3.4-lb/sq. yd. weight.
C. 3/8-Inch Rib Lath: ASTM C 847, galvanized, 4-lb./sq. yd. weight.
2.2 ACCESSORIES
A. Comply with ASTM C 1063 and coordinate depth of accessories with thicknesses and number of plaster coats required:
Charleston AFB, S. Carolina 09 24 00 - 2
1. Zinc and Zinc-Coated (Galvanized) Accessories:
a. Foundation Weep Screed: Fabricated from hot-dip galvanized-steel sheet, ASTM A 653/A 653M, G60 (Z180) zinc coating.
b. Cornerite: Fabricated from metal lath with ASTM A 653/A 653M, G60 (Z180), hot-dip galvanized zinc coating.
c. Cornerbeads: Small-nose style, fabricated from zinc
d. Casing Beads: Square-edge style, fabricated from zinc with expanded flanges.
e. Control Joints: Fabricated from zinc; one-piece-type, M-shaped configuration; with perforated flanges.
B. Fiber for Base Coat: Alkaline-resistant glass or polypropylene fibers, 1/2 inch (13 mm) long, free of contaminants, manufactured for use in portland cement plaster.
C. Bonding Compound: ASTM C 932.
D. Fasteners for Attaching Metal Lath to Substrates: Complying with ASTM C 1063.
E. Sound Attenuation Blankets: ASTM C 665, Type I (blankets without membrane facing).
F. Acoustical Sealant: As specified in Division 07 Section "Joint Sealants"
2.3 PORTLAND CEMENT PLASTER
A. Portland Cement: ASTM C 150, Type II.
1. Color for Finish Coats: White.
B. Plastic Cement: ASTM C 1328.
C. Lime: ASTM C 206, Type S; ASTM C 207, Type S.
D. Sand Aggregate: ASTM C 897.
E. Acrylic-Based Finish Coatings: Factory-mixed acrylic-emulsion coating systems, formulated with colorfast mineral pigments and fine aggregates; for use over portland cement plaster base coats. Include manufacturer's recommended primers and sealing topcoats for acrylic-based finishes.
2.4 PLASTER MIXES
A. Base-Coat Mix: equal parts portland cement and plastic cement; comply with
ASTM C 926.
B. Job-Mixed Finish Coat: equal parts portland cement and masonry cement or plastic cement; comply with ASTM C 926.
C. Factory-Prepared Finish-Coat Mixes: For ready-mixed finish-coat plasters or acrylic-based finish coatings; comply with manufacturer's written instructions.
Charleston AFB, S. Carolina 09 24 00 - 3
PART 3 - EXECUTION
3.1 INSTALLATION
A. Fire-Resistance-Rated Assemblies: Install components according to requirements for design designations from listing organization and publication indicated on Drawings.
B. Install metal lath and accessories according to ASTM C 1063.
1. Partition Framing and Vertical Furring: Install flat diamond-mesh or flat rib lath.
2. Flat-Ceiling and Horizontal Framing: Install flat diamond-mesh or flat rib lath.
3. Install lath-type, external-corner reinforcement at exterior locations.
4. Install cornerbead at interior and exterior locations.
C. Apply bonding compound on unit masonry and concrete plaster bases.
D. Apply, and cure plaster materials and finishes to comply with ASTM C 926. Apply three coats. Apply sand finish.
Visiting Quarters GYPSUM BOARD Charleston AFB, S. Carolina 09 29 00 - 1
SECTION 09 29 00
GYPSUM BOARD
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Interior gypsum board.
B. Related Sections:
1. Section 013329 “LEED Documentation”
2. Section 015400 “Green Procurement”
3. Section 015720 “Waste Management”
4.…