This document summarizes a draft solicitation for HVAC repair services at Fort Benning, Georgia. The U.S. Army Corps of Engineers Savannah District is seeking a firm-fixed price contract for repair and replacement of HVAC systems in Buildings 3405 and 3425, including modifications to sleeping bays, classrooms, and administrative areas. Work may include installing new equipment, ductwork, piping, pumps, air handlers and controls to improve system operation. The North American Industry Classification System code is 238220. Responses are due September 12, 2022. The period of performance is 840 calendar days from notice to proceed. The acquisition is unrestricted and offers a HUBZone price evaluation preference. The estimated value is between $10-25 million. Offerors must have an active role in the Procurement Integrated Enterprise Environment system to submit bids electronically.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
7 5/8", 11 5/8"
/8
SECTION
(2) #5
SPAN
ELEVATION
8" (MIN. BRG.)
LINTEL ML1
LINTEL
DESIGNATION
ML1
ML2
LINTEL TYPE
(NOMINAL DIMENSION)
8" HIGH CMU LINTEL
MASONRY OPENING
MAX. SPAN (FT) UNLESS
NOTED OTHERWISE
MINIMUM END
BEARING (INCHES)
84'-0"
MASONRY LINTEL SCHEDULE
LINTEL NOTES:
1. UNLESS OTHERWISE SHOWN, SELECT LINTEL TO SUIT INDICATED MASONRY OPENING AT OR
BELOW MAXIMUM ALLOWABLE SPAN INDICATED. LINTEL TYPE IS AT CONTRACTORS OPTION
EXCEPT AS NOTED OR DETAILED.
2. PROVIDE LINTELS @ ALL NEW PENETRATIONS OF INTERIOR MASONRY WALLS. COORDINATE
SIZE & LOCATION OF OPENINGS WITH APPROPRIATE TRADE.
3. REFER TO ARCHITECTURAL AND MECHANICAL DRAWINGS FOR OPENING SIZES.
4. MASONRY USED FOR LINTELS SHALL MATCH THAT OF THE ADJACENT WALL.
LOOSE STEEL ANGLE LINTEL SCHEDULE
LINTEL
DESIGNATION STEEL ANGLE SIZE
MASONRY OPENING
MAXIMUM SPAN (FT)
MINIMUM END
BEARING (INCHES)
SL1 L3 1/2 x 3 1/2 x 1/4 5'-0 4
LINTEL NOTES:
1. ALL LINTELS EXPOSED TO EXTERIOR SHALL BE HOT-DIPPED GALVANIZED.
2. REFER TO ARCHITECTURAL AND MECHANICAL DRAWINGS FOR OPENING SIZES.
8" HIGH PRECAST 6'-0" 8
SECTION
(2) #5, TOP
LINTEL ML2
/8
7 5/8"
(2) #5, BOT.
#3 TIES @ 6"oc
CLR.
3/4"
SIZE = 2' - 0" x 2' - 0"
EXIST. OPNG. (DIMS.
V.I.F., MAX OPNG.
EXIST. ELEV.
CONC. SLAB &
DECK (4" TOTAL
THK.)
EXIST. BEAM -
TO REMAIN)EXIST. BEAM -
TO REMAIN)
EXIST. ELEV. CONC.
SLAB & DECK (4"
TOTAL THK.)
NEW L4x4x3/8, (2)
SIDES OF OPNG.
(V.I.F. OPNG. DIMS.
FOR LENGTHS OF
L4x4
NEW 2 1/2" CONC.
(LW) & 1 1/2" DECK (20
GA.). NEW DECK
PROFILE SHALL
MATCH EXIST. DECK
PROFILE (V.I.F.)
(2) 3/8" DIA. EPOXY ANCHORS
BETWEEN VERT. LEG OF L4x4
& EXIST. SLAB. EMBED. &
EPOXY 2 1/2" INTO EXIST. CONC.
CENTER ANCHOR IN WIDTH
OF 4" THK. FLUTE LOCATIONS.
PROVIDE 12" BETWEEN
ANCHORS (EA. SIDE)
NEW CONC. FINISH
SHALL MATCH
EXIST. CONC.
ADJACENT TO INFILL
ROOF LOAD
HANGAR
HANGER
NOTE:
IN NO CASE SHALL THE LOAD EXCEED THE
LOAD ENVELOPE CREATED BY THE STATED
COLLATERAL LOADS.
1/8"
TYP
FIELD WELD 2 ANGLES FROM TOP
OR BOTTOM CHORD PANEL POINT
TO CONCENTRATED LOAD
LOCATION. (ONE ANGLE EA SIDE
OF JOIST CHORDS) MIN. REQ'D
ANGLE SIZES ARE AS FOLLOWS
JOIST DEPTH
8" TO 24"
26" TO 48"
52" TO 72"
ANGLE SIZE
L1-1/2x1-1/2x3/16 L2x2x3/16 L3x3x1/4
MODIFICATION IS TYP FOR ALL JOISTS
SUPPORTING LOAD FROM TOP OR
BOTTOM CHORD BETWEEN PANEL PTS
VERIFY LOC & NO OF LOADS W/ ARCH,
MECH, PLUMB, & ELEC DWGS. ANGLES
NOT REQ'D FOR CONCENTRATED LOADS
LESS THAN 100 LBS.
NOTE:
TOUCH UP FIELD WELDS W/ PAINT AS REQ'D
TO MATCH SHOP PRIMER.EXIST. SUPPORT BEAM
CUT & REMOVE DECK
WITHIN OPENING AFTER
FRAMING IS COMPLETED
COPED ENDS FOR
ANGLES (TYP)
CHANNEL C8x11.5 OR ANGLE FRAME L6x3 1/2x5/16
(LLV) TURNED DOWN TO
FORM PERIMETER OF
OPNG.
SLAB OPNG. COORD.
SIZE & LOCATION w/
APPLICABLE TRADE
CONTRACTOR
2"
ANGLE
BEARING
CHANNEL
CONNECTION
CL
SUPPORT
D E
C K
S P
A N
NOTES:
USE L6x3 1/2x5/16 WHEN OPNG SIZE EXCEEDS 1'-6" AND IS LESS THAN 3'-8". USE C8x11.7 WHEN OPNG IS BETWEEN 3'-8" AND 12'-0".
3/4"
EXIST. SUPPORT BEAM
EXIST. ROOF JOIST OR BEAM
(JOIST AS SHOWN). COORD.
SIZE, SPA., & SPAN DIR. IN
FIELD. AT JOIST LOCATIONS,
REFER TO C5/S-501 FOR NEW
WEB REINF. REQUIREMENT
WITHIN JOIST AT L4x4 SUPPORT
ANGLES (BETWEEN JOISTS)
EXIST. ROOF DECK.
- TO REMAIN (ROOF MAT'L
ABOVE DECK NOT SHOWN
FOR CLARITY, V.I.F.)
EXIST MECH. EQUIP. CURB - TO
REMAIN. CONTRACTOR TO
REMOVE METAL COPING ALONG
LENGTH OF CURB AND VERIFY
CONDITION AND CONSTRUCTION
OF CURB (ASSUMED WOOD 2x).
NOTIFY EOR IF ROT IS
OCCURRING OR CONSTRUCTION
TYPE DIFFERS PRIOR TO
SUPPORT INSTALL.
NEW L4x4x5/16x6" LG (GALV) @ EA. POST LOCATION w/ (3)
1/4" DIAMETER LAG SCREWS
(SS) BETWEEN L4x4 & EXIST 2x. EMBED SCREWS 2 1/2"
(MIN.) INTO EXIST. 2X.
COORD. SPA. w/ MECH EQUIP.
MECH. EQUIP. RAILS. COORD.
w/ MANUF. FOR SIZE & CONN.
TO SUPPORT FRAME
HSS3x0.250 POST (GALV.)
w/ 1/2" CAP PL. CENTER
ON CURB (WIDTH) BELOW
& C8 FRAME (ABOVE)
C8x11.5 MECH. EQUIP. SUPPORT
FRAME (GALV.). CENTER ON
EQUIP RAILS. COORD. PLAN
& RAIL DIMS. w/ MECH EQUIP.
3/16
POST TO
L4x4 (TYP.)
3/16
C8 TO
1/2" CAP PL
3/16
C8 FLANGE
TO C8
FLANGE,
TOP & BOT.
(M
A X
B
O T
S
T L
T O
T /E
X
IS
T C
U R
B
EXIST. STEEL ANGLE FRAME
(BETWEEN JOISTS/BEAMS)
BELOW EXIST. CURB LOCATIONS.
CONTRACTOR SHALL FIELD
VERIFY EXIST. ANGLE LOCATION
& SIZE. IF ANGLE FRAME
PRESENT, NOTIFY EOR WITH SIZE
OF ANGLES FOR SUPPORT
VERIFY. IF EXIST. ANGLE NOT
PRESENT, PROVIDE NEW L4x4x3/8
SUPPORT ANGLES. CENTER
BELOW CURB & SPAN BETWEEN
EXIST. JOISTS/BEAMS
VARIES, V.I.F.VARIES, V.I.F.
EQUIPMENT LOCATION (ROOM)
MAXIMUM
WEIGHT (lbs)
ERV ROOF 1500
AHU
(MECHANICAL ROOM @ EA.
BUNK AREA - 217A, 317A)
AHU (H-1)
(MECHANICAL ROOM -
A219, E219)
ERV (H-1) (MECHANICAL ROOM -
A219, E219)
NOTE: COORDINATE WITH MECHANICAL SHEETS M-601 AND
M-602 FOR ACTUAL EQUIPMENT WEIGHTS (PER PROVIDED
EQUIPMENT CUT SHEETS)
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N F
IL
E
N A
M E
F
IL
E N
U M
B E
R
S-501
S T
R U
C T
U R
A L
D E
T A
IL
S
F O
R T
B E
N N
IN
G
G
E O
R G
IA
S
A V
A N
N A
H D
IS
T
R
IC
T W
O
G L
E T
H O
R P
E A
V E
S A
V A
N N
A H
G
E O
R G
IA
S R
IC
C
I
S R
IC
C
I
A H
A U
T M
A N
S S
A P
S F
O R
D
A U
G U
S T
W H
N -2
-B
-4
READY TO ADVERTISE (RTA)
B U
IL
D
IN
G
H
E A
T
IN
G
V E
N T
IL
A
T
IO
N
A
IR
C
O N
D
IT
IO
N
IN
G
H
V A
C
R E
P A
IR
P
BLDG 3425
SCALE: 1" = 1'-0"
D1
LINTEL DETAILS AND SCHEDULES
SCALE: 3/4" = 1'-0"
F5
FLOOR FRAMING - EXISTING SLAB INFILL (NO EXISTING
SUPPORT FRAME, 24"x24" (MAX.) EXISTING OPENING)
SCALE: 1" = 1'-0"
C5
JOIST MODIFICATION AT CONCENTRATED LOADS
SCALE: 1" = 1'-0"
A1
CHANNEL OR ANGLE FRAMED SLAB OPENING
SCALE: 3/4" = 1'-0"
A5
MECHANICAL EQUIPMENT SUPPORT DETAIL (AT EXISTING
CURB)
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
/1
/2
SCALE: 1" = 1'-0"
F8
MAXIMUM EQUIPMENT WEIGHT (MAXIMUM)
24 24
26 26
31 31
27x 27x
35 35
39 39
42 42
C.L
C.LD.L
D.L
F.L
F.L
J.L
J.L
K.L
K.L
M.L
M.L
Px.L
Px.L
S.L
S.L C.R
C.R D.R
D.R
F.R
F.R
J.R
J.R
K.R
K.R
M.R
M.R
Px.R
Px.R
S.R
S.R
MECHANICAL
H120
CORRIDOR
H113
CORRIDOR
G102
CORRIDOR
H101
CORRIDOR
H105
CORRIDOR
H109CLASSROOM
H121
STORAGE
H122
STORAGE
H123
STORAGE
H124
ELECTRICAL
H125
STORAGE
H126
ALCOVE
H127
CLASSROOM
H128
STORAGE
H129
STORAGE
H130
STORAGE
H131
ELECTRICAL
H132
STORAGE
H133
ALCOVE
H134
CORRIDOR
H135
CLASSROOM
H136
STORAGE
H137
CLASSROOM
H138
STORAGE
H139
SICK CALL
H140
STORAGE
H141
CLASSROOM
H142
STORAGE
H143
CLASSROOM
H144
STORAGE
H145
COMM
H135A
/MATCHLINE - A1 AD161 /MATCHLINE - A1 AD161
M
A T
C H
L
IN
E
A
A D
M
A T
C H
L
IN
E
A
A D
/MATCHLINE - A1 AD154 /MATCHLINE - A1 AD155
M
A T
C H
L
IN
E
A
A D
M
A T
C H
L
IN
E
A
A D
MECHANICAL
H120
2 2
DRAWING SHEET NOTES
GENERAL SHEET NOTES
A. REFER TO SHEET A-001 FOR GENERAL DEMOLITION NOTES.
B. CONTRACTOR IS TO ANTICIPATE WORK AT ALL THRU-WALL AND FLOOR
PENETRATIONS. EXISTING OPENINGS ARE TO BE USED WHERE POSSIBLE AND
INCREASE/DECREASE IN SIZE AS REQUIRED. PROVIDE NEW OPENINGS WHERE
EXISTING OPENINGS ARE NOT PRESENT. SIZE OF OPENING TO BE
DETERMINED BY PENETRATING ELEMENT, INCLUDING BUT NOT LIMITED TO
DUCT, PIPING, AND THEIR REQUIRED ACCESSORIES. COORDINATE OPENING
SIZE AND LOCATION USING MECHANICAL AND ELECTRICAL DRAWINGS.
C. REFER TO ELECTRICAL ('E' SERIES SHEETS) FOR INFORMATION REGARDING
REMOVAL AND SALVAGE OF AFFECTED DEVICES.
D. REFER TO FIRE PROTECTION ('F' SERIES SHEETS) FOR INFORMATION
REGARDING REMOVAL AND SALVAGE OF AFFECTED CEILING MOUNTED
DEVICES.
E. ALL FINISHES ARE EXISTING TO REMAIN UNO
F. DIMENSIONS SHOW AT GYPSUM BOARD DEMOLITION ARE ASSUMED EXTENTS
OF CEILING TO BE REMOVED TO COMPLETE WORK. CONTRACTOR TO REMOVE
GYPSUM CEILING AS NECESSARY TO COMPLETE WORK.
G. UNO, REMOVE AND SALVAGE FOR POSSIBLE RE-USE EXISTING SUSPENEDED
ACOUSTICAL CEILING TILE AND GRID AS REQUIRED TO PERFORM HVAC WORK
ABOVE. REMOVE TO NEAREST FULL TILE. WATER DAMAGED CEILING TILE AT
EXISTING FAN POWERED VAV EQUIPMENT LOCATIONS ARE TO BE DISCARDED.
COORDINATE EXISTING FAN POWERED VAV EQUIPMENT LOCATIONS AND
EXTENTS OF ADDITIONAL HVAC WORK WITH MECHANICAL DRAWINGS.
H. UNO, REMOVE AND DISCARD CEILING ACCESS PANELS THAT ARE AFFECTED
BY THE DEMOLISHING OF GYPSUM BOARD CEILING TO ACCOMMODATE THE
HVAC SCOPE OF WORK.
I. CONTRACTOR TO LIMIT EXTENT OF WORK AT CEILING-TO-WALL AND CEILING-
TO-COLUMN TRANSITIONS TO 6" BELOW FINISHED CEILING.
CEILING DEMOLITION LEGEND
2' x 2' ACT CEILING
RETURN AIR GRILLE
SUPPLY AIR GRILLE
EXHAUST AIR GRILLE
GYP. BD. CEILING
EXISTING TO
REMAIN
TO BE
REMOVED
EXISTING TO REMAIN
WORK TO BE REMOVED
ASSUMED AREA OF SUSPENDED ACCOUSTICAL CEILING TILE
SYSTEM TO BE REMOVED AND SALVAGED FOR REINSTALLATION.
AREA SHOWN IS APPROXIMATE. REFER TO GENERAL NOTE ABOVE.
CEILING ACCESS PANEL
REFER TO MECHANICAL, ELECTRICAL, AND FIRE PROTECTION DRAWINGS FOR
FIXTURE/DEVICE INFORMATION.
MASONRY WALL CONSTRUCTION
GYPSUM BOARD ON METAL STUD CONSTRUCTION
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N F
IL
E
N A
M E
F
IL
E N
U M
B E
R
KEY PLAN
A-1
A-2
B-1
B-2
E-1
E-2
D-1
D-2
C-2C-1
F
G
H
PLAN NORTH
AD162
F
IR
S T
F L
O O
R C
E
IL
IN
G
D E
M O
L
IT
IO
N
P L
A N
A
R E
A H
F O
R T
B E
N N
IN
G
G
E O
R G
IA
S
A V
A N
N A
H D
IS
T
R
IC
T W
O
G L
E T
H O
R P
E A
V E
S A
V A
N N
A H
G
E O
R G
IA
R .F
U S
S N
E R
M H
A Y
N E
S
A H
A U
T M
A N
J K
O L S
H O
R N
A U
G U
S T
W H
N -2
-B
-4
READY TO ADVERTISE (RTA)
B U
IL
D
IN
G
H
E A
T
IN
G
V E
N T
IL
A
T
IO
N
A
IR
C
O N
D
IT
IO
N
IN
G
H
V A
C
R E
P A
IR
P
BLDG 3425
0 4' 8' 16'SCALE: 1/8" = 1'-0"
A1
FIRST FLOOR CEILING DEMOLITION PLAN - AREA H
1 NO FINISHED CEILING THIS SPACE, OPEN TO STRUCTURE ABOVE.
2 EXISTING CEILING MOUNTED OPERABLE PARTITION TRACK IN BULKHEAD TO
REMAIN. 1
R E
V
IS
E D
I N
A C
C O
R D
A N
C E
W
IT
H A
M E
N D
M E
N T
/1
/2
08/17/2022
EXP: 12/31/2023
1/2 1/21/2
/2
/2
1/2 1/21/2
S S
1/2 1/2
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
10 10
V.L
V.L
W.L
W.L
Y.L
Y.L
Z.L
Z.L
CC.L
CC.L
DD.L
DD.L
EE.L
EE.L
FF.L
FF.L
STAIR #3
A201
JANITOR
A202
RESTROOM
A203A
SHOWERS
A203B
SLEEPING BAY
A207
DRILL SGT
A208
TOILET
A209
SHOWER
A210
STAIR #4
A215
ELECTRICAL
A218
0.5 0.5
/MATCHLINE - A1 A-115
M
A T
C H
L
IN
E
A
A -1
/MATCHLINE - A1 A-115
A-502
A6
SLEEPING BAY
SECURE AREA
MECHANICAL
A217A
11' - 3" +/-
DRAWING SHEET NOTES
GENERAL SHEET NOTES
A. REFER TO SHEET A-001 FOR GENERAL DEMOLITION NOTES.
B. ALL FINISHES ARE EXISTING TO REMAIN UNO
C. CONTRACTOR IS TO ANTICIPATE WORK AT ALL THRU-WALL AND FLOOR
PENETRATIONS. EXISTING OPENINGS ARE TO BE USED WHERE POSSIBLE AND
INCREASE/DECREASE IN SIZE AS REQUIRED. PROVIDE NEW OPENINGS WHERE
EXISTING OPENINGS ARE NOT PRESENT. SIZE OF OPENING TO BE
DETERMINED BY PENETRATING ELEMENT, INCLUDING BUT NOT LIMITED TO
DUCT, PIPING, AND THEIR REQUIRED ACCESSORIES. COORDINATE OPENING
SIZE AND LOCATION USING MECHANICAL AND ELECTRICAL DRAWINGS.
D. ALL THRU-WALL PENETRATIONS AT RATED ASSEMBLIES ARE TO BE SEALED
TIGHT TO MAINTAIN CONTINUITY OF RATED PARTITION. PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM.
E. AT RATED PARITIONS, INFILL UN-USED OPENINGS LEFT BY DEMOLITION OF
EXISTING WORK USING TYPE 'X' (FIRE RESISTANT) GYPSUM BOARD AND METAL
STUD, UL ASSEMBLY U419 OR EQUIVILANT. PARTITION THICKNESS TO MATCH
EXISTING ADJACENT.
NEW WORK LEGEND
EXISTING TO REMAIN
NEW WORK
MASONRY WALL CONSTRUCTION
GYPSUM BOARD ON METAL STUD CONSTRUCTION
1/2 HOUR RATING
1 HOUR RATING
2 HOUR RATING
SMOKE PARTITION
PRESUMED LOCATIONS OF FIRE RATINGS. REFER TO G-SERIES SHEETS FOR
ADDITIONAL INFORMATION.
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N F
IL
E
N A
M E
F
IL
E N
U M
B E
R
KEY PLAN
A-1
A-2
B-1
B-2
E-1
E-2
D-1
D-2
C-2C-1
F
G
H
PLAN NORTH
A-114
S E
C O
N D
F L
O O
R P
L A
N
A R
E A
A -1
F O
R T
B E
N N
IN
G
G
E O
R G
IA
S
A V
A N
N A
H D
IS
T
R
IC
T W
O
G L
E T
H O
R P
E A
V E
S A
V A
N N
A H
G
E O
R G
IA
R .F
U S
S N
E R
M H
A Y
N E
S
A H
A U
T M
A N
J K
O L S
H O
R N
A U
G U
S T
W H
N -2
-B
-4
READY TO ADVERTISE (RTA)
B U
IL
D
IN
G
H
E A
T
IN
G
V E
N T
IL
A
T
IO
N
A
IR
C
O N
D
IT
IO
N
IN
G
H
V A
C
R E
P A
IR
P
BLDG 3425
SCALE: 1/8" = 1'-0"
A1
SECOND FLOOR PLAN - AREA A-1
0 4' 8' 16'
1 NEW MECHANICAL EQUIPMENT ON NEW OR MODIFIED CONCRETE
HOUSEKEEPING PAD. (REFER 'M' DRAWINGS). SEE F8/S-501 FOR MAXIMUM
EQUIPMENT WEIGHT TABLE.
2 INFILL EXISTING FLOOR OPENINGS IN RATED CONCRETE FLOOR SYSTEM NOT
RE-USED AS A RESULT OF WORK ASSOCIATED WITH THE SCOPE OF WORK.
REFER TO STRUCTURAL DRAWING (S-501) FOR INFILL DETAIL.
3 AT NEW DUCT PENETRATION THRU RATED FLOOR SLAB, PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM BASED ON
PENETRATING ELEMENT TYPE AND SIZE. REFER TO MECHANICAL DRAWINGS
FOR DUCT INFORMATION.
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
/1
/2
/2
/2
1/2 1/21/2
1/2 1/21/2 1/2 1/2 1/21/2 1/2
S S
1/2 1/2
12 12
13 13
14 14
15 15
16 16
17 17
19 19
21x 21x
22 22
23 23
24 24
25 25
26 26
V.L
V.L
W.L
W.L
Y.L
Y.L
Z.L
Z.L
CC.L
CC.L
DD.L
DD.L
EE.L
EE.L
FF.L
FF.L
STAIR #5
A206
JANITOR
A205
RESTROOM
A204A
SHOWERS
A204B
SLEEPING BAY
A211
DRILL SGT
A212
TOILET
A213
SHOWER
A214
STAIR #4
A215
COMM
A216
MECHANICAL
A217B
MECHANICAL
A219
21 21
/MATCHLINE - A1 A-114
/MATCHLINE - A1 A-116
/MATCHLINE - A1 A-114
A-502
A6
SIM
2 3
SLEEPING BAY
SECURE AREA
11' - 3" +/-
DRAWING SHEET NOTES
GENERAL SHEET NOTES
A. REFER TO SHEET A-001 FOR GENERAL DEMOLITION NOTES.
B. ALL FINISHES ARE EXISTING TO REMAIN UNO
C. CONTRACTOR IS TO ANTICIPATE WORK AT ALL THRU-WALL AND FLOOR
PENETRATIONS. EXISTING OPENINGS ARE TO BE USED WHERE POSSIBLE AND
INCREASE/DECREASE IN SIZE AS REQUIRED. PROVIDE NEW OPENINGS WHERE
EXISTING OPENINGS ARE NOT PRESENT. SIZE OF OPENING TO BE
DETERMINED BY PENETRATING ELEMENT, INCLUDING BUT NOT LIMITED TO
DUCT, PIPING, AND THEIR REQUIRED ACCESSORIES. COORDINATE OPENING
SIZE AND LOCATION USING MECHANICAL AND ELECTRICAL DRAWINGS.
D. ALL THRU-WALL PENETRATIONS AT RATED ASSEMBLIES ARE TO BE SEALED
TIGHT TO MAINTAIN CONTINUITY OF RATED PARTITION. PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM.
E. AT RATED PARITIONS, INFILL UN-USED OPENINGS LEFT BY DEMOLITION OF
EXISTING WORK USING TYPE 'X' (FIRE RESISTANT) GYPSUM BOARD AND METAL
STUD, UL ASSEMBLY U419 OR EQUIVILANT. PARTITION THICKNESS TO MATCH
EXISTING ADJACENT.
NEW WORK LEGEND
EXISTING TO REMAIN
NEW WORK
MASONRY WALL CONSTRUCTION
GYPSUM BOARD ON METAL STUD CONSTRUCTION
1/2 HOUR RATING
1 HOUR RATING
2 HOUR RATING
SMOKE PARTITION
PRESUMED LOCATIONS OF FIRE RATINGS. REFER TO G-SERIES SHEETS FOR
ADDITIONAL INFORMATION.
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N F
IL
E
N A
M E
F
IL
E N
U M
B E
R
KEY PLAN
A-1
A-2
B-1
B-2
E-1
E-2
D-1
D-2
C-2C-1
F
G
H
PLAN NORTH
A-115
S E
C O
N D
F L
O O
R P
L A
N
A R
E A
A -2
F O
R T
B E
N N
IN
G
G
E O
R G
IA
S
A V
A N
N A
H D
IS
T
R
IC
T W
O
G L
E T
H O
R P
E A
V E
S A
V A
N N
A H
G
E O
R G
IA
R .F
U S
S N
E R
M H
A Y
N E
S
A H
A U
T M
A N
J K
O L S
H O
R N
A U
G U
S T
W H
N -2
-B
-4
READY TO ADVERTISE (RTA)
B U
IL
D
IN
G
H
E A
T
IN
G
V E
N T
IL
A
T
IO
N
A
IR
C
O N
D
IT
IO
N
IN
G
H
V A
C
R E
P A
IR
P
BLDG 3425
SCALE: 1/8" = 1'-0"
A1
SECOND FLOOR PLAN - AREA A-2
0 4' 8' 16'
1 NEW MECHANICAL EQUIPMENT ON NEW OR MODIFIED CONCRETE
HOUSEKEEPING PAD. (REFER 'M' DRAWINGS). SEE F8/S-501 FOR MAXIMUM
EQUIPMENT WEIGHT TABLE.
2 INFILL EXISTING FLOOR OPENINGS IN RATED CONCRETE FLOOR SYSTEM NOT
RE-USED AS A RESULT OF WORK ASSOCIATED WITH THE SCOPE OF WORK.
REFER TO STRUCTURAL DRAWING (S-501) FOR INFILL DETAIL.
3 AT NEW DUCT PENETRATION THRU RATED FLOOR SLAB, PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM BASED ON
PENETRATING ELEMENT TYPE AND SIZE. REFER TO MECHANICAL DRAWINGS
FOR DUCT INFORMATION.
4 CONTRACTOR TO PROVIDE INDUSTRIAL WALL MOUNTED HOSE HOLDER.
COORDINATE WITH GOVERNMENT FOR LENGTH OF HOSE REQUIRED TO BE
STORED.
5 NEW GALVANIZED CURB COPING FULL LENGTH OF ROOF CURB.
6 EXISTING 10'-0"W x 8'-0"T OVERHEAD ACCESS DOOR AT SECOND FLOOR TO
REMAIN.
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
/1
/2
1/2 1/21/2 1/2
1/2 1/21/2
/2
/2
1/2 1/21/2
S S
1/2 1/2
27 27
28 28
30 30
32 32
33 33
27x 27x
36 36
37 37
V.L
V.L
W.L
W.L
Y.L
Y.L
Z.L
Z.L
CC.L
CC.L
DD.L
DD.L
EE.L
EE.L
FF.L
FF.L
STAIR #6
B201
JANITOR
B202
RESTROOM
B203A
SHOWERS
B203B
SLEEPING BAY
B207
DRILL SGT
B208
TOILET
B209
SHOWER
B210
STAIR #7
B215
COMM
B216
MECHANICAL
B217A
/MATCHLINE - A1 A-115
/MATCHLINE - A1 A-117
A-502
A6
SIM
SLEEPING BAY
SECURE AREA
11' - 3" +/-
DRAWING SHEET NOTES
GENERAL SHEET NOTES
A. REFER TO SHEET A-001 FOR GENERAL DEMOLITION NOTES.
B. ALL FINISHES ARE EXISTING TO REMAIN UNO
C. CONTRACTOR IS TO ANTICIPATE WORK AT ALL THRU-WALL AND FLOOR
PENETRATIONS. EXISTING OPENINGS ARE TO BE USED WHERE POSSIBLE AND
INCREASE/DECREASE IN SIZE AS REQUIRED. PROVIDE NEW OPENINGS WHERE
EXISTING OPENINGS ARE NOT PRESENT. SIZE OF OPENING TO BE
DETERMINED BY PENETRATING ELEMENT, INCLUDING BUT NOT LIMITED TO
DUCT, PIPING, AND THEIR REQUIRED ACCESSORIES. COORDINATE OPENING
SIZE AND LOCATION USING MECHANICAL AND ELECTRICAL DRAWINGS.
D. ALL THRU-WALL PENETRATIONS AT RATED ASSEMBLIES ARE TO BE SEALED
TIGHT TO MAINTAIN CONTINUITY OF RATED PARTITION. PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM.
E. AT RATED PARITIONS, INFILL UN-USED OPENINGS LEFT BY DEMOLITION OF
EXISTING WORK USING TYPE 'X' (FIRE RESISTANT) GYPSUM BOARD AND METAL
STUD, UL ASSEMBLY U419 OR EQUIVILANT. PARTITION THICKNESS TO MATCH
EXISTING ADJACENT.
NEW WORK LEGEND
EXISTING TO REMAIN
NEW WORK
MASONRY WALL CONSTRUCTION
GYPSUM BOARD ON METAL STUD CONSTRUCTION
1/2 HOUR RATING
1 HOUR RATING
2 HOUR RATING
SMOKE PARTITION
PRESUMED LOCATIONS OF FIRE RATINGS. REFER TO G-SERIES SHEETS FOR
ADDITIONAL INFORMATION.
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N F
IL
E
N A
M E
F
IL
E N
U M
B E
R
KEY PLAN
A-1
A-2
B-1
B-2
E-1
E-2
D-1
D-2
C-2C-1
F
G
H
PLAN NORTH
A-116
S E
C O
N D
F L
O O
R P
L A
N
A R
E A
B -1
F O
R T
B E
N N
IN
G
G
E O
R G
IA
S
A V
A N
N A
H D
IS
T
R
IC
T W
O
G L
E T
H O
R P
E A
V E
S A
V A
N N
A H
G
E O
R G
IA
R .F
U S
S N
E R
M H
A Y
N E
S
A H
A U
T M
A N
J K
O L S
H O
R N
A U
G U
S T
W H
N -2
-B
-4
READY TO ADVERTISE (RTA)
B U
IL
D
IN
G
H
E A
T
IN
G
V E
N T
IL
A
T
IO
N
A
IR
C
O N
D
IT
IO
N
IN
G
H
V A
C
R E
P A
IR
P
BLDG 3425
SCALE: 1/8" = 1'-0"
A1
SECOND FLOOR PLAN - AREA B-1
0 4' 8' 16'
1 NEW MECHANICAL EQUIPMENT ON NEW OR MODIFIED CONCRETE
HOUSEKEEPING PAD. (REFER 'M' DRAWINGS). SEE F8/S-501 FOR MAXIMUM
EQUIPMENT WEIGHT TABLE.
2 INFILL EXISTING FLOOR OPENINGS IN RATED CONCRETE FLOOR SYSTEM NOT
RE-USED AS A RESULT OF WORK ASSOCIATED WITH THE SCOPE OF WORK.
REFER TO STRUCTURAL DRAWING (S-501) FOR INFILL DETAIL.
3 AT NEW DUCT PENETRATION THRU RATED FLOOR SLAB, PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM BASED ON
PENETRATING ELEMENT TYPE AND SIZE. REFER TO MECHANICAL DRAWINGS
FOR DUCT INFORMATION.
4 CONTRACTOR TO PROVIDE INDUSTRIAL WALL MOUNTED HOSE HOLDER.
COORDINATE WITH GOVERNMENT FOR LENGTH OF HOSE REQUIRED TO BE
STORED.
5 NEW GALVANIZED CURB COPING FULL LENGTH OF ROOF CURB.
6 EXISTING ROOF FRAMING MEMBERS (OPEN WEB STEEL JOISTS OR STEEL
BEAMS - V.I.F., TO REMAIN) FOR SUPPORT OF NEW ROOF TOP MECHANICAL
EQUIPMENT. SEE DETAIL C5/S-501 FOR WEB REINFORCEMENT REQUIREMENTS
AT EXISTING JOISTS AND A5/S-501 FOR SUPPORT DETAIL BELOW MECHANICAL
EQUIPMENT CURB. 1
R E
V
IS
E D
I N
A C
C O
R D
A N
C E
W
IT
H A
M E
N D
M E
N T
/1
/2
/2
/2
1/2 1/21/2
S S
1/2 1/2
40 40
41 41
42 42
43 43
44 44
48x 48x
47 47
48 48
V.L
V.L
W.L
W.L
Y.L
Y.L
Z.L
Z.L
CC.L
CC.L
DD.L
DD.L
EE.L
EE.L
FF.L
FF.L
STAIR #8
B206
JANITOR
B205
RESTROOM
B204A
SHOWERS
B204B
SLEEPING BAY
B211
DRILL SGT
B212
TOILET
B213
SHOWER
B214
STAIR #7
B215
MECHANICAL
B217B
ELECTRICAL
B218
/MATCHLINE - A1 A-116
M
A T
C H
L
IN
E
A
A -1
A-502
A6
SIM
SLEEPING BAY
SECURE AREA
11' - 3" +/-
/-5
DRAWING SHEET NOTES
GENERAL SHEET NOTES
A. REFER TO SHEET A-001 FOR GENERAL DEMOLITION NOTES.
B. ALL FINISHES ARE EXISTING TO REMAIN UNO
C. CONTRACTOR IS TO ANTICIPATE WORK AT ALL THRU-WALL AND FLOOR
PENETRATIONS. EXISTING OPENINGS ARE TO BE USED WHERE POSSIBLE AND
INCREASE/DECREASE IN SIZE AS REQUIRED. PROVIDE NEW OPENINGS WHERE
EXISTING OPENINGS ARE NOT PRESENT. SIZE OF OPENING TO BE
DETERMINED BY PENETRATING ELEMENT, INCLUDING BUT NOT LIMITED TO
DUCT, PIPING, AND THEIR REQUIRED ACCESSORIES. COORDINATE OPENING
SIZE AND LOCATION USING MECHANICAL AND ELECTRICAL DRAWINGS.
D. ALL THRU-WALL PENETRATIONS AT RATED ASSEMBLIES ARE TO BE SEALED
TIGHT TO MAINTAIN CONTINUITY OF RATED PARTITION. PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM.
E. AT RATED PARITIONS, INFILL UN-USED OPENINGS LEFT BY DEMOLITION OF
EXISTING WORK USING TYPE 'X' (FIRE RESISTANT) GYPSUM BOARD AND METAL
STUD, UL ASSEMBLY U419 OR EQUIVILANT. PARTITION THICKNESS TO MATCH
EXISTING ADJACENT.
NEW WORK LEGEND
EXISTING TO REMAIN
NEW WORK
MASONRY WALL CONSTRUCTION
GYPSUM BOARD ON METAL STUD CONSTRUCTION
1/2 HOUR RATING
1 HOUR RATING
2 HOUR RATING
SMOKE PARTITION
PRESUMED LOCATIONS OF FIRE RATINGS. REFER TO G-SERIES SHEETS FOR
ADDITIONAL INFORMATION.
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N F
IL
E
N A
M E
F
IL
E N
U M
B E
R
KEY PLAN
A-1
A-2
B-1
B-2
E-1
E-2
D-1
D-2
C-2C-1
F
G
H
PLAN NORTH
A-117
S E
C O
N D
F L
O O
R P
L A
N
A R
E A
B -2
F O
R T
B E
N N
IN
G
G
E O
R G
IA
S
A V
A N
N A
H D
IS
T
R
IC
T W
O
G L
E T
H O
R P
E A
V E
S A
V A
N N
A H
G
E O
R G
IA
R .F
U S
S N
E R
M H
A Y
N E
S
A H
A U
T M
A N
J K
O L S
H O
R N
A U
G U
S T
W H
N -2
-B
-4
READY TO ADVERTISE (RTA)
B U
IL
D
IN
G
H
E A
T
IN
G
V E
N T
IL
A
T
IO
N
A
IR
C
O N
D
IT
IO
N
IN
G
H
V A
C
R E
P A
IR
P
BLDG 3425
SCALE: 1/8" = 1'-0"
A1
SECOND FLOOR PLAN - AREA B-2
0 4' 8' 16'
1 NEW MECHANICAL EQUIPMENT ON NEW OR MODIFIED CONCRETE
HOUSEKEEPING PAD. (REFER 'M' DRAWINGS). SEE F8/S-501 FOR MAXIMUM
EQUIPMENT WEIGHT TABLE.
2 INFILL EXISTING FLOOR OPENINGS IN RATED CONCRETE FLOOR SYSTEM NOT
RE-USED AS A RESULT OF WORK ASSOCIATED WITH THE SCOPE OF WORK.
REFER TO STRUCTURAL DRAWING (S-501) FOR INFILL DETAIL.
3 AT NEW DUCT PENETRATION THRU RATED FLOOR SLAB, PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM BASED ON
PENETRATING ELEMENT TYPE AND SIZE. REFER TO MECHANICAL DRAWINGS
FOR DUCT INFORMATION.
4 EXISTING ROOF FRAMING MEMBERS (OPEN WEB STEEL JOISTS OR STEEL
BEAMS - V.I.F., TO REMAIN) FOR SUPPORT OF NEW ROOF TOP MECHANICAL
EQUIPMENT. SEE DETAIL C5/S-501 FOR WEB REINFORCEMENT REQUIREMENTS
AT EXISTING JOISTS AND A5/S-501 FOR SUPPORT DETAIL BELOW MECHANICAL
EQUIPMENT CURB.
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
/1
/2
/2
/2
/2
1/21/2
/2
/2
/2
S S
1/2 1/2
44 44
45 45
48 48
49 49
50 50
A.L
A.L
B.L
B.L
E.L
E.L
G.L
G.L
H.L
H.L
K.L
K.L
N.L
N.L
Q.L
Q.L
R.L
R.L
T.L
T.L
V.L
V.L
W.L
W.L
X.L
X.L
Y.L
Y.L
AA.L
AA.L
S.L
S.L
STAIR #9
C201
JANITOR
C202
RESTROOM
C203A
SHOWER
C203B
SLEEPING BAY
C207
DRILL SGT
C208
TOILET
C209
SHOWER
C210
STAIR #10
C215
MECHANICAL
C217A
ELECTRICAL
C218
M
A T
C H
L
IN
E
A
A -1
/MATCHLINE - A1 A-126
/MATCHLINE - A1 A-117
A-502
A6
SIM
2 3
BELOW
SLEEPING BAY
SECURE AREA
SLEEPING BAY
SECURE AREA
11' - 10" +/- 1
5' - 0"
DRAWING SHEET NOTES
GENERAL SHEET NOTES
A. REFER TO SHEET A-001 FOR GENERAL DEMOLITION NOTES.
B. ALL FINISHES ARE EXISTING TO REMAIN UNO
C. CONTRACTOR IS TO ANTICIPATE WORK AT ALL THRU-WALL AND FLOOR
PENETRATIONS. EXISTING OPENINGS ARE TO BE USED WHERE POSSIBLE AND
INCREASE/DECREASE IN SIZE AS REQUIRED. PROVIDE NEW OPENINGS WHERE
EXISTING OPENINGS ARE NOT PRESENT. SIZE OF OPENING TO BE
DETERMINED BY PENETRATING ELEMENT, INCLUDING BUT NOT LIMITED TO
DUCT, PIPING, AND THEIR REQUIRED ACCESSORIES. COORDINATE OPENING
SIZE AND LOCATION USING MECHANICAL AND ELECTRICAL DRAWINGS.
D. ALL THRU-WALL PENETRATIONS AT RATED ASSEMBLIES ARE TO BE SEALED
TIGHT TO MAINTAIN CONTINUITY OF RATED PARTITION. PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM.
E. AT RATED PARITIONS, INFILL UN-USED OPENINGS LEFT BY DEMOLITION OF
EXISTING WORK USING TYPE 'X' (FIRE RESISTANT) GYPSUM BOARD AND METAL
STUD, UL ASSEMBLY U419 OR EQUIVILANT. PARTITION THICKNESS TO MATCH
EXISTING ADJACENT.
NEW WORK LEGEND
EXISTING TO REMAIN
NEW WORK
MASONRY WALL CONSTRUCTION
GYPSUM BOARD ON METAL STUD CONSTRUCTION
1/2 HOUR RATING
1 HOUR RATING
2 HOUR RATING
SMOKE PARTITION
PRESUMED LOCATIONS OF FIRE RATINGS. REFER TO G-SERIES SHEETS FOR
ADDITIONAL INFORMATION.
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N F
IL
E
N A
M E
F
IL
E N
U M
B E
R
KEY PLAN
A-1
A-2
B-1
B-2
E-1
E-2
D-1
D-2
C-2C-1
F
G
H
PLAN NORTH
A-118
S E
C O
N D
F L
O O
R P
L A
N
A R
E A
C -1
F O
R T
B E
N N
IN
G
G
E O
R G
IA
S
A V
A N
N A
H D
IS
T
R
IC
T W
O
G L
E T
H O
R P
E A
V E
S A
V A
N N
A H
G
E O
R G
IA
R .F
U S
S N
E R
M H
A Y
N E
S
A H
A U
T M
A N
J K
O L S
H O
R N
A U
G U
S T
W H
N -2
-B
-4
READY TO ADVERTISE (RTA)
B U
IL
D
IN
G
H
E A
T
IN
G
V E
N T
IL
A
T
IO
N
A
IR
C
O N
D
IT
IO
N
IN
G
H
V A
C
R E
P A
IR
P
BLDG 3425
SCALE: 1/8" = 1'-0"
A1
SECOND FLOOR PLAN - AREA C-1
0 4' 8' 16'
1 NEW MECHANICAL EQUIPMENT ON NEW OR MODIFIED CONCRETE
HOUSEKEEPING PAD. (REFER 'M' DRAWINGS). SEE F8/S-501 FOR MAXIMUM
EQUIPMENT WEIGHT TABLE.
2 INFILL EXISTING FLOOR OPENINGS IN RATED CONCRETE FLOOR SYSTEM NOT
RE-USED AS A RESULT OF WORK ASSOCIATED WITH THE SCOPE OF WORK.
REFER TO STRUCTURAL DRAWING (S-501) FOR INFILL DETAIL.
3 AT NEW DUCT PENETRATION THRU RATED FLOOR SLAB, PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM BASED ON
PENETRATING ELEMENT TYPE AND SIZE. REFER TO MECHANICAL DRAWINGS
FOR DUCT INFORMATION.
4 EXISTING TPO ROOF MEMBRANE OVER RIGID INSULATION TO REMAIN. PATCH
AND REPAIR ROOF SYSTEM PER MANUFACTURER'S INSTRUCTIONS AND
RECOMMENDATIONS AT REQUIRED LOCATIONS AFTER REMOVAL OF EXISTING
ROOF TOP MECHANICAL EQUIPMENT AND ASSOCIATED PIPING OR CONDUIT, AS
WELL AS LOCATIONS OF DAMAGE DURING CONSTRUCTION. PROVIDE RIGID
INSULATION INFILL TO MATCH EXISTING AS REQUIRED. CONTRACTOR IS TO
PROTECT MEMBRANE THROUGHOUT CONSTRUCTION FROM DAMAGE.
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
/1
/2
/2
/2
1/2 1/2
/2
/2
/2
S S
1/2 1/2
44 44
45 45
48 48
49 49
50 50
A.R
A.R
B.R
B.R
E.R
E.R
G.R
G.R
H.R
H.R
K.R
K.R
T.R
T.R
V.R
V.R
W.R
W.R
X.R
X.R
Y.R
Y.R
AA.R
AA.R
N.R
N.R
Q.R
Q.R
R.R
R.R
S.R
S.R
STAIR #11
C206
JANITOR
C205
RESTROOM
C204A
SHOWER
C204B
SLEEPING BAY
C211
DRILL SGT
C212
TOILET
C213
SHOWER
C214
STAIR #10
C215
COMM
C216
MECHANICAL
C217B
M
A T
C H
L
IN
E
A
A -1
/MATCHLINE - A1 A-126
/MATCHLINE - A1 A-120
A-502
A6
SIM
2 3
BELOW
SLEEPING BAY
SECURE AREA
SLEEPING BAY
SECURE AREA
5' - 0"
11' - 8" +/-1
DRAWING SHEET NOTES
GENERAL SHEET NOTES
A. REFER TO SHEET A-001 FOR GENERAL DEMOLITION NOTES.
B. ALL FINISHES ARE EXISTING TO REMAIN UNO
C. CONTRACTOR IS TO ANTICIPATE WORK AT ALL THRU-WALL AND FLOOR
PENETRATIONS. EXISTING OPENINGS ARE TO BE USED WHERE POSSIBLE AND
INCREASE/DECREASE IN SIZE AS REQUIRED. PROVIDE NEW OPENINGS WHERE
EXISTING OPENINGS ARE NOT PRESENT. SIZE OF OPENING TO BE
DETERMINED BY PENETRATING ELEMENT, INCLUDING BUT NOT LIMITED TO
DUCT, PIPING, AND THEIR REQUIRED ACCESSORIES. COORDINATE OPENING
SIZE AND LOCATION USING MECHANICAL AND ELECTRICAL DRAWINGS.
D. ALL THRU-WALL PENETRATIONS AT RATED ASSEMBLIES ARE TO BE SEALED
TIGHT TO MAINTAIN CONTINUITY OF RATED PARTITION. PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM.
E. AT RATED PARITIONS, INFILL UN-USED OPENINGS LEFT BY DEMOLITION OF
EXISTING WORK USING TYPE 'X' (FIRE RESISTANT) GYPSUM BOARD AND METAL
STUD, UL ASSEMBLY U419 OR EQUIVILANT. PARTITION THICKNESS TO MATCH
EXISTING ADJACENT.
NEW WORK LEGEND
EXISTING TO REMAIN
NEW WORK
MASONRY WALL CONSTRUCTION
GYPSUM BOARD ON METAL STUD CONSTRUCTION
1/2 HOUR RATING
1 HOUR RATING
2 HOUR RATING
SMOKE PARTITION
PRESUMED LOCATIONS OF FIRE RATINGS. REFER TO G-SERIES SHEETS FOR
ADDITIONAL INFORMATION.
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N F
IL
E
N A
M E
F
IL
E N
U M
B E
R
KEY PLAN
A-1
A-2
B-1
B-2
E-1
E-2
D-1
D-2
C-2C-1
F
G
H
PLAN NORTH
A-119
S E
C O
N D
F L
O O
R P
L A
N
A R
E A
C -2
F O
R T
B E
N N
IN
G
G
E O
R G
IA
S
A V
A N
N A
H D
IS
T
R
IC
T W
O
G L
E T
H O
R P
E A
V E
S A
V A
N N
A H
G
E O
R G
IA
R .F
U S
S N
E R
M H
A Y
N E
S
A H
A U
T M
A N
J K
O L S
H O
R N
A U
G U
S T
W H
N -2
-B
-4
READY TO ADVERTISE (RTA)
B U
IL
D
IN
G
H
E A
T
IN
G
V E
N T
IL
A
T
IO
N
A
IR
C
O N
D
IT
IO
N
IN
G
H
V A
C
R E
P A
IR
P
BLDG 3425
SCALE: 1/8" = 1'-0"
A1
SECOND FLOOR PLAN - AREA C-2
0 4' 8' 16'
1 NEW MECHANICAL EQUIPMENT ON NEW OR MODIFIED CONCRETE
HOUSEKEEPING PAD. (REFER 'M' DRAWINGS). SEE F8/S-501 FOR MAXIMUM
EQUIPMENT WEIGHT TABLE.
2 INFILL EXISTING FLOOR OPENINGS IN RATED CONCRETE FLOOR SYSTEM NOT
RE-USED AS A RESULT OF WORK ASSOCIATED WITH THE SCOPE OF WORK.
REFER TO STRUCTURAL DRAWING (S-501) FOR INFILL DETAIL.
3 AT NEW DUCT PENETRATION THRU RATED FLOOR SLAB, PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM BASED ON
PENETRATING ELEMENT TYPE AND SIZE. REFER TO MECHANICAL DRAWINGS
FOR DUCT INFORMATION.
4 EXISTING TPO ROOF MEMBRANE OVER RIGID INSULATION TO REMAIN. PATCH
AND REPAIR ROOF SYSTEM PER MANUFACTURER'S INSTRUCTIONS AND
RECOMMENDATIONS AT REQUIRED LOCATIONS AFTER REMOVAL OF EXISTING
ROOF TOP MECHANICAL EQUIPMENT AND ASSOCIATED PIPING OR CONDUIT, AS
WELL AS LOCATIONS OF DAMAGE DURING CONSTRUCTION. PROVIDE RIGID
INSULATION INFILL TO MATCH EXISTING AS REQUIRED. CONTRACTOR IS TO
PROTECT MEMBRANE THROUGHOUT CONSTRUCTION FROM DAMAGE.
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
/1
/2
/2
/2
1/2 1/21/2
S S
1/2 1/2
39 39
40 40
41 41
42 42
43 43
44 44
48x 48x
47 47
48 48
V.R
V.R
W.R
W.R
Y.R
Y.R
Z.R
Z.R
CC.R
CC.R
DD.R
DD.R
EE.R
EE.R
FF.R
FF.R
STAIR #12
D206
JANITOR
D205
RESTROOM
D204A
SHOWERS
D204B
SLEEPING BAY
D211
DRILL SGT
D212
TOILET
D213
SHOWER
D214
STAIR #13
D215
COMM
D216
MECHANICAL
D217B
ELECTRICAL
D218
/MATCHLINE - A1 A-121
/MATCHLINE - A1 A-119
M
A T
C H
L
IN
E
A
A -1
A-502
A6
SIM
BELOW
SLEEPING BAY
SECURE AREA
11' - 3" +/-
/- 5
DRAWING SHEET NOTES
GENERAL SHEET NOTES
A. REFER TO SHEET A-001 FOR GENERAL DEMOLITION NOTES.
B. ALL FINISHES ARE EXISTING TO REMAIN UNO
C. CONTRACTOR IS TO ANTICIPATE WORK AT ALL THRU-WALL AND FLOOR
PENETRATIONS. EXISTING OPENINGS ARE TO BE USED WHERE POSSIBLE AND
INCREASE/DECREASE IN SIZE AS REQUIRED. PROVIDE NEW OPENINGS WHERE
EXISTING OPENINGS ARE NOT PRESENT. SIZE OF OPENING TO BE
DETERMINED BY PENETRATING ELEMENT, INCLUDING BUT NOT LIMITED TO
DUCT, PIPING, AND THEIR REQUIRED ACCESSORIES. COORDINATE OPENING
SIZE AND LOCATION USING MECHANICAL AND ELECTRICAL DRAWINGS.
D. ALL THRU-WALL PENETRATIONS AT RATED ASSEMBLIES ARE TO BE SEALED
TIGHT TO MAINTAIN CONTINUITY OF RATED PARTITION. PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM.
E. AT RATED PARITIONS, INFILL UN-USED OPENINGS LEFT BY DEMOLITION OF
EXISTING WORK USING TYPE 'X' (FIRE RESISTANT) GYPSUM BOARD AND METAL
STUD, UL ASSEMBLY U419 OR EQUIVILANT. PARTITION THICKNESS TO MATCH
EXISTING ADJACENT.
NEW WORK LEGEND
EXISTING TO REMAIN
NEW WORK
MASONRY WALL CONSTRUCTION
GYPSUM BOARD ON METAL STUD CONSTRUCTION
1/2 HOUR RATING
1 HOUR RATING
2 HOUR RATING
SMOKE PARTITION
PRESUMED LOCATIONS OF FIRE RATINGS. REFER TO G-SERIES SHEETS FOR
ADDITIONAL INFORMATION.
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N F
IL
E
N A
M E
F
IL
E N
U M
B E
R
KEY PLAN
A-1
A-2
B-1
B-2
E-1
E-2
D-1
D-2
C-2C-1
F
G
H
PLAN NORTH
A-120
S E
C O
N D
F L
O O
R P
L A
N
A R
E A
D -2
F O
R T
B E
N N
IN
G
G
E O
R G
IA
S
A V
A N
N A
H D
IS
T
R
IC
T W
O
G L
E T
H O
R P
E A
V E
S A
V A
N N
A H
G
E O
R G
IA
R .F
U S
S N
E R
M H
A Y
N E
S
A H
A U
T M
A N
J K
O L S
H O
R N
A U
G U
S T
W H
N -2
-B
-4
READY TO ADVERTISE (RTA)
B U
IL
D
IN
G
H
E A
T
IN
G
V E
N T
IL
A
T
IO
N
A
IR
C
O N
D
IT
IO
N
IN
G
H
V A
C
R E
P A
IR
P
BLDG 3425
SCALE: 1/8" = 1'-0"
A1
SECOND FLOOR PLAN - AREA D-2
0 4' 8' 16'
1 NEW MECHANICAL EQUIPMENT ON NEW OR MODIFIED CONCRETE
HOUSEKEEPING PAD. (REFER 'M' DRAWINGS). SEE F8/S-501 FOR MAXIMUM
EQUIPMENT WEIGHT TABLE.
2 INFILL EXISTING FLOOR OPENINGS IN RATED CONCRETE FLOOR SYSTEM NOT
RE-USED AS A RESULT OF WORK ASSOCIATED WITH THE SCOPE OF WORK.
REFER TO STRUCTURAL DRAWING (S-501) FOR INFILL DETAIL.
3 AT NEW DUCT PENETRATION THRU RATED FLOOR SLAB, PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM BASED ON
PENETRATING ELEMENT TYPE AND SIZE. REFER TO MECHANICAL DRAWINGS
FOR DUCT INFORMATION.
4 EXISTING TPO ROOF MEMBRANE OVER RIGID INSULATION TO REMAIN. PATCH
AND REPAIR ROOF SYSTEM PER MANUFACTURER'S INSTRUCTIONS AND
RECOMMENDATIONS AT REQUIRED LOCATIONS AFTER REMOVAL OF EXISTING
ROOF TOP MECHANICAL EQUIPMENT AND ASSOCIATED PIPING OR CONDUIT, AS
WELL AS LOCATIONS OF DAMAGE DURING CONSTRUCTION. PROVIDE RIGID
INSULATION INFILL TO MATCH EXISTING AS REQUIRED. CONTRACTOR IS TO
PROTECT MEMBRANE THROUGHOUT CONSTRUCTION FROM DAMAGE.
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
/1
/2
1/2 1/21/2 1/2
/2
/2
1/2 1/21/2
S S
1/2 1/2
27 27
28 28
30 30
32 32
33 33
27x 27x
36 36
37 37
38 38
V.R
V.R
W.R
W.R
Y.R
Y.R
Z.R
Z.R
CC.R
CC.R
DD.R
DD.R
EE.R
EE.R
FF.R
FF.R
STAIR #14
D201
JANITOR
D202
RESTROOM
D203A
SHOWERS
D203B
SLEEPING BAY
D207
DRILL SGT
D208
TOILET
D209
SHOWER
D210
STAIR #13
D215
COMM
D216
ELECTRICAL
D218
MECHANICAL
D217A
/MATCHLINE - A1 A-122
/MATCHLINE - A1 A-120
A-502
A6
SIM
SLEEPING BAY
SECURE AREA
11' - 3" +/-
DRAWING SHEET NOTES
GENERAL SHEET NOTES
A. REFER TO SHEET A-001 FOR GENERAL DEMOLITION NOTES.
B. ALL FINISHES ARE EXISTING TO REMAIN UNO
C. CONTRACTOR IS TO ANTICIPATE WORK AT ALL THRU-WALL AND FLOOR
PENETRATIONS. EXISTING OPENINGS ARE TO BE USED WHERE POSSIBLE AND
INCREASE/DECREASE IN SIZE AS REQUIRED. PROVIDE NEW OPENINGS WHERE
EXISTING OPENINGS ARE NOT PRESENT. SIZE OF OPENING TO BE
DETERMINED BY PENETRATING ELEMENT, INCLUDING BUT NOT LIMITED TO
DUCT, PIPING, AND THEIR REQUIRED ACCESSORIES. COORDINATE OPENING
SIZE AND LOCATION USING MECHANICAL AND ELECTRICAL DRAWINGS.
D. ALL THRU-WALL PENETRATIONS AT RATED ASSEMBLIES ARE TO BE SEALED
TIGHT TO MAINTAIN CONTINUITY OF RATED PARTITION. PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM.
E. AT RATED PARITIONS, INFILL UN-USED OPENINGS LEFT BY DEMOLITION OF
EXISTING WORK USING TYPE 'X' (FIRE RESISTANT) GYPSUM BOARD AND METAL
STUD, UL ASSEMBLY U419 OR EQUIVILANT. PARTITION THICKNESS TO MATCH
EXISTING ADJACENT.
NEW WORK LEGEND
EXISTING TO REMAIN
NEW WORK
MASONRY WALL CONSTRUCTION
GYPSUM BOARD ON METAL STUD CONSTRUCTION
1/2 HOUR RATING
1 HOUR RATING
2 HOUR RATING
SMOKE PARTITION
PRESUMED LOCATIONS OF FIRE RATINGS. REFER TO G-SERIES SHEETS FOR
ADDITIONAL INFORMATION.
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N F
IL
E
N A
M E
F
IL
E N
U M
B E
R
KEY PLAN
A-1
A-2
B-1
B-2
E-1
E-2
D-1
D-2
C-2C-1
F
G
H
PLAN NORTH
A-121
S E
C O
N D
F L
O O
R P
L A
N
A R
E A
D -1
F O
R T
B E
N N
IN
G
G
E O
R G
IA
S
A V
A N
N A
H D
IS
T
R
IC
T W
O
G L
E T
H O
R P
E A
V E
S A
V A
N N
A H
G
E O
R G
IA
R .F
U S
S N
E R
M H
A Y
N E
S
A H
A U
T M
A N
J K
O L S
H O
R N
A U
G U
S T
W H
N -2
-B
-4
READY TO ADVERTISE (RTA)
B U
IL
D
IN
G
H
E A
T
IN
G
V E
N T
IL
A
T
IO
N
A
IR
C
O N
D
IT
IO
N
IN
G
H
V A
C
R E
P A
IR
P
BLDG 3425
SCALE: 1/8" = 1'-0"
A1
SECOND FLOOR PLAN - AREA D-1
0 4' 8' 16'
1 NEW MECHANICAL EQUIPMENT ON NEW OR MODIFIED CONCRETE
HOUSEKEEPING PAD. (REFER 'M' DRAWINGS). SEE F8/S-501 FOR MAXIMUM
EQUIPMENT WEIGHT TABLE.
2 INFILL EXISTING FLOOR OPENINGS IN RATED CONCRETE FLOOR SYSTEM NOT
RE-USED AS A RESULT OF WORK ASSOCIATED WITH THE SCOPE OF WORK.
REFER TO STRUCTURAL DRAWING (S-501) FOR INFILL DETAIL.
3 AT NEW DUCT PENETRATION THRU RATED FLOOR SLAB, PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM BASED ON
PENETRATING ELEMENT TYPE AND SIZE. REFER TO MECHANICAL DRAWINGS
FOR DUCT INFORMATION.
4 CONTRACTOR TO PROVIDE INDUSTRIAL WALL MOUNTED HOSE HOLDER.
COORDINATE WITH GOVERNMENT FOR LENGTH OF HOSE REQUIRED TO BE
STORED.
5 NEW GALVANIZED CURB COPING FULL LENGTH OF ROOF CURB.
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
/1
/2
1/2 1/21/2 1/2
/2
/2
1/2 1/21/2 S S
1/2 1/2
12 12
13 13
14 14
15 15
16 16
17 17
19 19
21x 21x
22 22
23 23
24 24
25 25
26 26
V.R
V.R
W.R
W.R
Y.R
Y.R
Z.R
Z.R
CC.R
CC.R
DD.R
DD.R
EE.R
EE.R
FF.R
FF.R
STAIR #15
E206
JANITOR
E205
RESTROOM
E204A
SHOWERS
E204B
SLEEPING BAY
E211
DRILL SGT
E212
TOILET
E213
SHOWER
E214
STAIR #16
E215
COMM
E216
ELECTRICAL
E218
MECHANICAL
E217B
MECHANICAL
E219
21 21
/MATCHLINE - A1 A-123
/MATCHLINE - A1 A-121
/MATCHLINE - A1 A-123
A-502
A6
SIM
SLEEPING BAY
SECURE AREA
11' - 3" +/-
/- 5
2 3
DRAWING SHEET NOTES
GENERAL SHEET NOTES
A. REFER TO SHEET A-001 FOR GENERAL DEMOLITION NOTES.
B. ALL FINISHES ARE EXISTING TO REMAIN UNO
C. CONTRACTOR IS TO ANTICIPATE WORK AT ALL THRU-WALL AND FLOOR
PENETRATIONS. EXISTING OPENINGS ARE TO BE USED WHERE POSSIBLE AND
INCREASE/DECREASE IN SIZE AS REQUIRED. PROVIDE NEW OPENINGS WHERE
EXISTING OPENINGS ARE NOT PRESENT. SIZE OF OPENING TO BE
DETERMINED BY PENETRATING ELEMENT, INCLUDING BUT NOT LIMITED TO
DUCT, PIPING, AND THEIR REQUIRED ACCESSORIES. COORDINATE OPENING
SIZE AND LOCATION USING MECHANICAL AND ELECTRICAL DRAWINGS.
D. ALL THRU-WALL PENETRATIONS AT RATED ASSEMBLIES ARE TO BE SEALED
TIGHT TO MAINTAIN CONTINUITY OF RATED PARTITION. PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM.
E. AT RATED PARITIONS, INFILL UN-USED OPENINGS LEFT BY DEMOLITION OF
EXISTING WORK USING TYPE 'X' (FIRE RESISTANT) GYPSUM BOARD AND METAL
STUD, UL ASSEMBLY U419 OR EQUIVILANT. PARTITION THICKNESS TO MATCH
EXISTING ADJACENT.
NEW WORK LEGEND
EXISTING TO REMAIN
NEW WORK
MASONRY WALL CONSTRUCTION
GYPSUM BOARD ON METAL STUD CONSTRUCTION
1/2 HOUR RATING
1 HOUR RATING
2 HOUR RATING
SMOKE PARTITION
PRESUMED LOCATIONS OF FIRE RATINGS. REFER TO G-SERIES SHEETS FOR
ADDITIONAL INFORMATION.
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N F
IL
E
N A
M E
F
IL
E N
U M
B E
R
KEY PLAN
A-1
A-2
B-1
B-2
E-1
E-2
D-1
D-2
C-2C-1
F
G
H
PLAN NORTH
A-122
S E
C O
N D
F L
O O
R P
L A
N
A R
E A
E -2
F O
R T
B E
N N
IN
G
G
E O
R G
IA
S
A V
A N
N A
H D
IS
T
R
IC
T W
O
G L
E T
H O
R P
E A
V E
S A
V A
N N
A H
G
E O
R G
IA
R .F
U S
S N
E R
M H
A Y
N E
S
A H
A U
T M
A N
J K
O L S
H O
R N
A U
G U
S T
W H
N -2
-B
-4
READY TO ADVERTISE (RTA)
B U
IL
D
IN
G
H
E A
T
IN
G
V E
N T
IL
A
T
IO
N
A
IR
C
O N
D
IT
IO
N
IN
G
H
V A
C
R E
P A
IR
P
BLDG 3425
SCALE: 1/8" = 1'-0"
A1
SECOND FLOOR PLAN - AREA E-2
0 4' 8' 16'
1 NEW MECHANICAL EQUIPMENT ON NEW OR MODIFIED CONCRETE
HOUSEKEEPING PAD. (REFER 'M' DRAWINGS). SEE F8/S-501 FOR MAXIMUM
EQUIPMENT WEIGHT TABLE.
2 INFILL EXISTING FLOOR OPENINGS IN RATED CONCRETE FLOOR SYSTEM NOT
RE-USED AS A RESULT OF WORK ASSOCIATED WITH THE SCOPE OF WORK.
REFER TO STRUCTURAL DRAWING (S-501) FOR INFILL DETAIL.
3 AT NEW DUCT PENETRATION THRU RATED FLOOR SLAB, PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM BASED ON
PENETRATING ELEMENT TYPE AND SIZE. REFER TO MECHANICAL DRAWINGS
FOR DUCT INFORMATION.
4 CONTRACTOR TO PROVIDE INDUSTRIAL WALL MOUNTED HOSE HOLDER.
COORDINATE WITH GOVERNMENT FOR LENGTH OF HOSE REQUIRED TO BE
STORED.
5 NEW GALVANIZED CURB COPING FULL LENGTH OF ROOF CURB.
6 EXISTING 10'-0"W x 8'-0"T OVERHEAD ACCESS DOOR AT SECOND FLOOR TO
REMAIN.
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
/1
/2
/2
/2
1/2 1/21/2
S S
1/2 1/2
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
10 10
V.R
V.R
W.R
W.R
Y.R
Y.R
Z.R
Z.R
CC.R
CC.R
DD.R
DD.R
EE.R
EE.R
FF.R
FF.R
STAIR #17
E201
JANITOR
E202
RESTROOM
E203A
SHOWERS
E203B
SLEEPING BAY
E207
DRILL SGT
E208
TOILET
E209
SHOWER
E210
STAIR #16
E215
COMM
E216
MECHANICAL
E217A
ELECTRICAL
E218
ELECTRICAL
E220
GROOMING
E221
TOILET
E221A
TOILET
E221B
SHOWER /
LOCKERS
E221C
0.5 0.5
/MATCHLINE - A1 A-122
M
A T
C H
L
IN
E
A
A -1
/MATCHLINE - A1 A-122
A-502
A6
SIM
SLEEPING BAY
SECURE AREA
11' - 3" +/-
DRAWING SHEET NOTES
GENERAL SHEET NOTES
A. REFER TO SHEET A-001 FOR GENERAL DEMOLITION NOTES.
B. ALL FINISHES ARE EXISTING TO REMAIN UNO
C. CONTRACTOR IS TO ANTICIPATE WORK AT ALL THRU-WALL AND FLOOR
PENETRATIONS. EXISTING OPENINGS ARE TO BE USED WHERE POSSIBLE AND
INCREASE/DECREASE IN SIZE AS REQUIRED. PROVIDE NEW OPENINGS WHERE
EXISTING OPENINGS ARE NOT PRESENT. SIZE OF OPENING TO BE
DETERMINED BY PENETRATING ELEMENT, INCLUDING BUT NOT LIMITED TO
DUCT, PIPING, AND THEIR REQUIRED ACCESSORIES. COORDINATE OPENING
SIZE AND LOCATION USING MECHANICAL AND ELECTRICAL DRAWINGS.
D. ALL THRU-WALL PENETRATIONS AT RATED ASSEMBLIES ARE TO BE SEALED
TIGHT TO MAINTAIN CONTINUITY OF RATED PARTITION. PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM.
E. AT RATED PARITIONS, INFILL UN-USED OPENINGS LEFT BY DEMOLITION OF
EXISTING WORK USING TYPE 'X' (FIRE RESISTANT) GYPSUM BOARD AND METAL
STUD, UL ASSEMBLY U419 OR EQUIVILANT. PARTITION THICKNESS TO MATCH
EXISTING ADJACENT.
NEW WORK LEGEND
EXISTING TO REMAIN
NEW WORK
MASONRY WALL CONSTRUCTION
GYPSUM BOARD ON METAL STUD CONSTRUCTION
1/2 HOUR RATING
1 HOUR RATING
2 HOUR RATING
SMOKE PARTITION
PRESUMED LOCATIONS OF FIRE RATINGS. REFER TO G-SERIES SHEETS FOR
ADDITIONAL INFORMATION.
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N F
IL
E
N A
M E
F
IL
E N
U M
B E
R
KEY PLAN
A-1
A-2
B-1
B-2
E-1
E-2
D-1
D-2
C-2C-1
F
G
H
PLAN NORTH
A-123
S E
C O
N D
F L
O O
R P
L A
N
A R
E A
E -1
F O
R T
B E
N N
IN
G
G
E O
R G
IA
S
A V
A N
N A
H D
IS
T
R
IC
T W
O
G L
E T
H O
R P
E A
V E
S A
V A
N N
A H
G
E O
R G
IA
R .F
U S
S N
E R
M H
A Y
N E
S
A H
A U
T M
A N
J K
O L S
H O
R N
A U
G U
S T
W H
N -2
-B
-4
READY TO ADVERTISE (RTA)
B U
IL
D
IN
G
H
E A
T
IN
G
V E
N T
IL
A
T
IO
N
A
IR
C
O N
D
IT
IO
N
IN
G
H
V A
C
R E
P A
IR
P
BLDG 3425
SCALE: 1/8" = 1'-0"
A1
SECOND FLOOR PLAN - AREA E-1
0 4' 8' 16'
1 NEW MECHANICAL EQUIPMENT ON NEW OR MODIFIED CONCRETE
HOUSEKEEPING PAD. (REFER 'M' DRAWINGS). SEE F8/S-501 FOR MAXIMUM
EQUIPMENT WEIGHT TABLE.
2 INFILL EXISTING FLOOR OPENINGS IN RATED CONCRETE FLOOR SYSTEM NOT
RE-USED AS A RESULT OF WORK ASSOCIATED WITH THE SCOPE OF WORK.
REFER TO STRUCTURAL DRAWING (S-501) FOR INFILL DETAIL.
3 AT NEW DUCT PENETRATION THRU RATED FLOOR SLAB, PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM BASED ON
PENETRATING ELEMENT TYPE AND SIZE. REFER TO MECHANICAL DRAWINGS
FOR DUCT INFORMATION.
4 EXISTING ROOF FRAMING MEMBERS (OPEN WEB STEEL JOISTS OR STEEL
BEAMS - V.I.F., TO REMAIN) FOR SUPPORT OF NEW ROOF TOP MECHANICAL
EQUIPMENT. SEE DETAIL C5/S-501 FOR WEB REINFORCEMENT REQUIREMENTS
AT EXISTING JOISTS AND A5/S-501 FOR SUPPORT DETAIL BELOW MECHANICAL
EQUIPMENT CURB.
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
/1
/2
1/2
1/2 1/2
1/2
S S
1/2 1/2
13 13
14 14
15 15
16 16
19 19
22 22
23 23
24 24
26 26
C.L
C.LD.L
D.L
F.L
F.L
J.L
J.L
K.L
K.L
M.L
M.L
Px.L
Px.L
U.L
U.L
W.L
W.L
S.L
S.L C.R
C.R D.R
D.R
F.R
F.R
J.R
J.R
K.R
K.R
M.R
M.R
U.R
U.R
W.R
W.R
Px.R
Px.R
S.R
S.R
/MATCHLINE - A1 A-126 /MATCHLINE - A1 A-126
/MATCHLINE - A1 A-115 /MATCHLINE - A1 A-122
/MATCHLINE - A1 A-123/MATCHLINE - A1 A-114
/MATCHLINE - A1 A-124
VIF
5' - 9"
VIF
5' - 9"
VIF
5' - 9" VIF
5' - 9"
VIF
5' - 9"
VIF
18' - 4"
A4
A-501
TYP
A4
A-501
SIM
OPEN AIR
HALLWAY
DRAWING SHEET NOTES
GENERAL SHEET NOTES
A. REFER TO SHEET A-001 FOR GENERAL DEMOLITION NOTES.
B. ALL FINISHES ARE EXISTING TO REMAIN UNO
C. CONTRACTOR IS TO ANTICIPATE WORK AT ALL THRU-WALL AND FLOOR
PENETRATIONS. EXISTING OPENINGS ARE TO BE USED WHERE POSSIBLE AND
INCREASE/DECREASE IN SIZE AS REQUIRED. PROVIDE NEW OPENINGS WHERE
EXISTING OPENINGS ARE NOT PRESENT. SIZE OF OPENING TO BE
DETERMINED BY PENETRATING ELEMENT, INCLUDING BUT NOT LIMITED TO
DUCT, PIPING, AND THEIR REQUIRED ACCESSORIES. COORDINATE OPENING
SIZE AND LOCATION USING MECHANICAL AND ELECTRICAL DRAWINGS.
D. ALL THRU-WALL PENETRATIONS AT RATED ASSEMBLIES ARE TO BE SEALED
TIGHT TO MAINTAIN CONTINUITY OF RATED PARTITION. PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM.
E. AT RATED PARITIONS, INFILL UN-USED OPENINGS LEFT BY DEMOLITION OF
EXISTING WORK USING TYPE 'X' (FIRE RESISTANT) GYPSUM BOARD AND METAL
STUD, UL ASSEMBLY U419 OR EQUIVILANT. PARTITION THICKNESS TO MATCH
EXISTING ADJACENT.
NEW WORK LEGEND
EXISTING TO REMAIN
NEW WORK
MASONRY WALL CONSTRUCTION
GYPSUM BOARD ON METAL STUD CONSTRUCTION
1/2 HOUR RATING
1 HOUR RATING
2 HOUR RATING
SMOKE PARTITION
PRESUMED LOCATIONS OF FIRE RATINGS. REFER TO G-SERIES SHEETS FOR
ADDITIONAL INFORMATION.
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N F
IL
E
N A
M E
F
IL
E N
U M
B E
R
KEY PLAN
A-1
A-2
B-1
B-2
E-1
E-2
D-1
D-2
C-2C-1
F
G
H
PLAN NORTH
A-125
R O
O F
P L
A N
A
R E
A G
F O
R T
B E
N N
IN
G
G
E O
R G
IA
S
A V
A N
N A
H D
IS
T
R
IC
T W
O
G L
E T
H O
R P
E A
V E
S A
V A
N N
A H
G
E O
R G
IA
R .F
U S
S N
E R
M H
A Y
N E
S
A H
A U
T M
A N
J K
O L S
H O
R N
A U
G U
S T
W H
N -2
-B
-4
READY TO ADVERTISE (RTA)
B U
IL
D
IN
G
H
E A
T
IN
G
V E
N T
IL
A
T
IO
N
A
IR
C
O N
D
IT
IO
N
IN
G
H
V A
C
R E
P A
IR
P
BLDG 3425
SCALE: 1/8" = 1'-0"
A1
ROOF PLAN - AREA G
0 4' 8' 16'
1 EXISTING TPO ROOF MEMBRANE OVER RIGID INSULATION TO REMAIN. PATCH
AND REPAIR ROOF SYSTEM PER MANUFACTURER'S INSTRUCTIONS AND
RECOMMENDATIONS AT REQUIRED LOCATIONS AFTER REMOVAL OF EXISTING
ROOF TOP MECHANICAL EQUIPMENT AND ASSOCIATED PIPING OR CONDUIT, AS
WELL AS LOCATIONS OF DAMAGE DURING CONSTRUCTION. PROVIDE RIGID
INSULATION INFILL TO MATCH EXISTING AS REQUIRED. CONTRACTOR IS TO
PROTECT MEMBRANE THROUGHOUT CONSTRUCTION FROM DAMAGE.
2 NEW MECHANICAL EQUIPMENT ON NEW OR MODIFIED CONCRETE
HOUSEKEEPING PAD. (REFER 'M' DRAWINGS). SEE F8/S-501 FOR MAXIMUM
EQUIPMENT WEIGHT TABLE.
3 NEW MECHANICAL EQUIPMENT ON MODIFIED EXISTING ROOF CURB. REFER TO
'M' DRAWINGS FOR NEW EQUIPMENT INFORMATION AND REFER TO
STRUCTURAL DRAWING (S-501) FOR EQUIPMENT SUPPORT DETAIL AND DETAIL
F8/S-501 FOR MAXIMUM EQUIPMENT WEIGHT TABLE.
4 NEW GALVANIZED CURB COPING FULL LENGTH OF ROOF CURB.
5 EXISTING ROOF FRAMING MEMBERS (OPEN WEB STEEL JOISTS OR STEEL
BEAMS - V.I.F., TO REMAIN) FOR SUPPORT OF NEW ROOF TOP MECHANICAL
EQUIPMENT. SEE DETAIL C5/S-501 FOR WEB REINFORCEMENT REQUIREMENTS
AT EXISTING JOISTS AND A5/S-501 FOR SUPPORT DETAIL BELOW MECHANICAL
EQUIPMENT CURB.
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
/1
/2
1/2
/2
/2
/2
/2
1/2
1/2
1/2
S S
1/2 1/2
27 27
31 31
27x 27x
35 35
36 36
39 39
41 41
42 42
43 43
45 45
C.L
C.LD.L
D.L
F.L
F.L
J.L
J.L
K.L
K.L
M.L
M.L
Px.L
Px.L
U.L
U.L
W.L
W.L
S.L
S.L C.R
C.R D.R
D.R
F.R
F.R
J.R
J.R
K.R
K.R
M.R
M.R
U.R
U.R
W.R
W.R
Px.R
Px.R
S.R
S.R
/MATCHLINE - A1 A-125 /MATCHLINE - A1 A-125
M
A T
C H
L
IN
E
A
A -1
M
A T
C H
L
IN
E
A
A -1
/MATCHLINE - A1 A-118 /MATCHLINE - A1 A-119
M
A T
C H
L
IN
E
A
A -1
M
A T
C H
L
IN
E
A
A -1
3 3
18' - 4" VIF
VIF
5' - 9"
VIF
5' - 9"
VIF
5' - 9" VIF
5' - 9"
A4
A-501
SIM
A4
A-501
SIM
TYP
4 4
SLEEPING BAY
SECURE AREA
SLEEPING BAY
SECURE AREA
5 5
11' - 10" +/- 11' - 8" +/-
DRAWING SHEET NOTES
GENERAL SHEET NOTES
A. REFER TO SHEET A-001 FOR GENERAL DEMOLITION NOTES.
B. ALL FINISHES ARE EXISTING TO REMAIN UNO
C. CONTRACTOR IS TO ANTICIPATE WORK AT ALL THRU-WALL AND FLOOR
PENETRATIONS. EXISTING OPENINGS ARE TO BE USED WHERE POSSIBLE AND
INCREASE/DECREASE IN SIZE AS REQUIRED. PROVIDE NEW OPENINGS WHERE
EXISTING OPENINGS ARE NOT PRESENT. SIZE OF OPENING TO BE
DETERMINED BY PENETRATING ELEMENT, INCLUDING BUT NOT LIMITED TO
DUCT, PIPING, AND THEIR REQUIRED ACCESSORIES. COORDINATE OPENING
SIZE AND LOCATION USING MECHANICAL AND ELECTRICAL DRAWINGS.
D. ALL THRU-WALL PENETRATIONS AT RATED ASSEMBLIES ARE TO BE SEALED
TIGHT TO MAINTAIN CONTINUITY OF RATED PARTITION. PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM.
E. AT RATED PARITIONS, INFILL UN-USED OPENINGS LEFT BY DEMOLITION OF
EXISTING WORK USING TYPE 'X' (FIRE RESISTANT) GYPSUM BOARD AND METAL
STUD, UL ASSEMBLY U419 OR EQUIVILANT. PARTITION THICKNESS TO MATCH
EXISTING ADJACENT.
NEW WORK LEGEND
EXISTING TO REMAIN
NEW WORK
MASONRY WALL CONSTRUCTION
GYPSUM BOARD ON METAL STUD CONSTRUCTION
1/2 HOUR RATING
1 HOUR RATING
2 HOUR RATING
SMOKE PARTITION
PRESUMED LOCATIONS OF FIRE RATINGS. REFER TO G-SERIES SHEETS FOR
ADDITIONAL INFORMATION.
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N F
IL
E
N A
M E
F
IL
E N
U M
B E
R
KEY PLAN
A-1
A-2
B-1
B-2
E-1
E-2
D-1
D-2
C-2C-1
F
G
H
PLAN NORTH
A-126
R O
O F
P L
A N
A
R E
A H
F O
R T
B E
N N
IN
G
G
E O
R G
IA
S
A V
A N
N A
H D
IS
T
R
IC
T W
O
G L
E T
H O
R P
E A
V E
S A
V A
N N
A H
G
E O
R G
IA
R .F
U S
S N
E R
M H
A Y
N E
S
A H
A U
T M
A N
J K
O L S
H O
R N
A U
G U
S T
W H
N -2
-B
-4
READY TO ADVERTISE (RTA)
B U
IL
D
IN
G
H
E A
T
IN
G
V E
N T
IL
A
T
IO
N
A
IR
C
O N
D
IT
IO
N
IN
G
H
V A
C
R E
P A
IR
P
BLDG 3425
SCALE: 1/8" = 1'-0"
A1
ROOF PLAN - AREA H
0 4' 8' 16'
1 EXISTING TPO ROOF MEMBRANE OVER RIGID INSULATION TO REMAIN. PATCH
AND REPAIR ROOF SYSTEM PER MANUFACTURER'S INSTRUCTIONS AND
RECOMMENDATIONS AT REQUIRED LOCATIONS AFTER REMOVAL OF EXISTING
ROOF TOP MECHANICAL EQUIPMENT AND ASSOCIATED PIPING OR CONDUIT, AS
WELL AS LOCATIONS OF DAMAGE DURING CONSTRUCTION. PROVIDE RIGID
INSULATION INFILL TO MATCH EXISTING AS REQUIRED. CONTRACTOR IS TO
PROTECT MEMBRANE THROUGHOUT CONSTRUCTION FROM DAMAGE.
2 NEW MECHANICAL EQUIPMENT ON NEW OR MODIFIED CONCRETE
HOUSEKEEPING PAD. (REFER 'M' DRAWINGS). SEE F8/S-501 FOR MAXIMUM
EQUIPMENT WEIGHT TABLE.
3 NEW MECHANICAL EQUIPMENT ON MODIFIED EXISTING ROOF CURB. REFER TO
'M' DRAWINGS FOR NEW EQUIPMENT INFORMATION AND REFER TO
STRUCTURAL DRAWING (S-501) FOR EQUIPMENT SUPPORT DETAIL AND DETAIL
F8/S-501 FOR MAXIMUM EQUIPMENT WEIGHT TABLE.
4 NEW GALVANIZED CURB COPING FULL LENGTH OF ROOF CURB.
5 EXISTING ROOF FRAMING MEMBERS (OPEN WEB STEEL JOISTS OR STEEL
BEAMS - V.I.F., TO REMAIN) FOR SUPPORT OF NEW ROOF TOP MECHANICAL
EQUIPMENT. SEE DETAIL C5/S-501 FOR WEB REINFORCEMENT REQUIREMENTS
AT EXISTING JOISTS AND A5/S-501 FOR SUPPORT DETAIL BELOW MECHANICAL
EQUIPMENT CURB.
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
/1
/2
/2
/2
1/2 1/21/2
S S
1/2 1/2
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
10 10
V.L
V.L
W.L
W.L
Y.L
Y.L
Z.L
Z.L
CC.L
CC.L
DD.L
DD.L
EE.L
EE.L
FF.L
FF.L
STAIR #3
A301
JANITOR
A302
RESTROOM
A303A
SHOWERS
A303B
SLEEPING BAY
A307
DRILL SGT
A308
TOILET
A309
SHOWER
A310
STAIR #4
A315
MECHANICAL
A317A
ELECTRICAL
A318
0.5 0.5
/MATCHLINE - A1 A-128
M
A T
C H
L
IN
E
A
A -1
/MATCHLINE - A1 A-128
A-502
A6
SIM
SLEEPING BAY
SECURE AREA
11' - 3" +/-
DRAWING SHEET NOTES
GENERAL SHEET NOTES
A. REFER TO SHEET A-001 FOR GENERAL DEMOLITION NOTES.
B. ALL FINISHES ARE EXISTING TO REMAIN UNO
C. CONTRACTOR IS TO ANTICIPATE WORK AT ALL THRU-WALL AND FLOOR
PENETRATIONS. EXISTING OPENINGS ARE TO BE USED WHERE POSSIBLE AND
INCREASE/DECREASE IN SIZE AS REQUIRED. PROVIDE NEW OPENINGS WHERE
EXISTING OPENINGS ARE NOT PRESENT. SIZE OF OPENING TO BE
DETERMINED BY PENETRATING ELEMENT, INCLUDING BUT NOT LIMITED TO
DUCT, PIPING, AND THEIR REQUIRED ACCESSORIES. COORDINATE OPENING
SIZE AND LOCATION USING MECHANICAL AND ELECTRICAL DRAWINGS.
D. ALL THRU-WALL PENETRATIONS AT RATED ASSEMBLIES ARE TO BE SEALED
TIGHT TO MAINTAIN CONTINUITY OF RATED PARTITION. PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM.
E. AT RATED PARITIONS, INFILL UN-USED OPENINGS LEFT BY DEMOLITION OF
EXISTING WORK USING TYPE 'X' (FIRE RESISTANT) GYPSUM BOARD AND METAL
STUD, UL ASSEMBLY U419 OR EQUIVILANT. PARTITION THICKNESS TO MATCH
EXISTING ADJACENT.
NEW WORK LEGEND
EXISTING TO REMAIN
NEW WORK
MASONRY WALL CONSTRUCTION
GYPSUM BOARD ON METAL STUD CONSTRUCTION
1/2 HOUR RATING
1 HOUR RATING
2 HOUR RATING
SMOKE PARTITION
PRESUMED LOCATIONS OF FIRE RATINGS. REFER TO G-SERIES SHEETS FOR
ADDITIONAL INFORMATION.
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N F
IL
E
N A
M E
F
IL
E N
U M
B E
R
KEY PLAN
A-1
A-2
B-1
B-2
E-1
E-2
D-1
D-2
C-2C-1
F
G
H
PLAN NORTH
A-127
T H
IR
D
F L
O O
R P
L A
N
A R
E A
A -1
F O
R T
B E
N N
IN
G
G
E O
R G
IA
S
A V
A N
N A
H D
IS
T
R
IC
T W
O
G L
E T
H O
R P
E A
V E
S A
V A
N N
A H
G
E O
R G
IA
R .F
U S
S N
E R
M H
A Y
N E
S
A H
A U
T M
A N
J K
O L S
H O
R N
A U
G U
S T
W H
N -2
-B
-4
READY TO ADVERTISE (RTA)
B U
IL
D
IN
G
H
E A
T
IN
G
V E
N T
IL
A
T
IO
N
A
IR
C
O N
D
IT
IO
N
IN
G
H
V A
C
R E
P A
IR
P
BLDG 3425
SCALE: 1/8" = 1'-0"
A1
THIRD FLOOR PLAN - AREA A-1
0 4' 8' 16'
1 NEW MECHANICAL EQUIPMENT ON NEW OR MODIFIED CONCRETE
HOUSEKEEPING PAD. (REFER 'M' DRAWINGS). SEE F8/S-501 FOR MAXIMUM
EQUIPMENT WEIGHT TABLE.
2 INFILL EXISTING FLOOR OPENINGS IN RATED CONCRETE FLOOR SYSTEM NOT
RE-USED AS A RESULT OF WORK ASSOCIATED WITH THE SCOPE OF WORK.
REFER TO STRUCTURAL DRAWING (S-501) FOR INFILL DETAIL.
3 AT NEW DUCT PENETRATION THRU RATED FLOOR SLAB, PROVIDE
APPROPRIATE THRU PENETRATION FIRESTOPPING SYSTEM BASED ON
PENETRATING ELEMENT TYPE AND SIZE.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .