Text version
Fort Benning, Georgia
Solicitation Number
W912HN-18-R-3013
Flight Control Tower Volume 4 of 4: Specification Divisions 27 - 33, Appendices
PN 55112
August 2018
U.S. ARMY ENGINEER DISTRICT, SAVANNAH
CORPS OF ENGINEERS
100 WEST OGLETHORPE AVENUE
SAVANNAH, GEORGIA 31401-3640
US Army Corps of Engineers Savannah District
Fl i ght Cont r ol Tower 18R3013 Ft . Benni ng, GA
PROJECT TABLE OF CONTENTS
DI VI SI ON 01 - GENERAL REQUI REMENTS
01 11 00 SUMMARY OF WORK
01 32 01. 00 10 PROJECT SCHEDULE
01 33 00 SUBMI TTAL PROCEDURES
01 33 29 SUSTAI NABI LI TY REPORTI NG
01 35 26 GOVERNMENTAL SAFETY REQUI REMENTS
01 42 00 SOURCES FOR REFERENCE PUBLI CATI ONS
01 45 00. 00 10 QUALI TY CONTROL
01 45 00. 15 10 RESI DENT MANAGEMENT SYSTEM CONTRACTOR MODE( RMS CM)
01 45 35 SPECI AL I NSPECTI ONS
01 50 00 TEMPORARY CONSTRUCTI ON FACI LI TI ES AND CONTROLS
01 57 19 TEMPORARY ENVI RONMENTAL CONTROLS
01 74 19 CONSTRUCTI ON AND DEMOLI TI ON WASTE MANAGEMENT
01 78 00 CLOSEOUT SUBMI TTALS
01 78 23 OPERATI ON AND MAI NTENANCE DATA
01 91 00. 15 TOTAL BUI LDI NG COMMI SSI ONI NG
DI VI SI ON 03 - CONCRETE
03 30 00 CAST- I N- PLACE CONCRETE
DI VI SI ON 04 - MASONRY
04 20 00 UNI T MASONRY
DI VI SI ON 05 - METALS
05 05 23. 16 STRUCTURAL WELDI NG
05 12 00 STRUCTURAL STEEL
05 21 00 STEEL JOI ST FRAMI NG
05 30 00 STEEL DECKS
05 40 00 COLD- FORMED METAL FRAMI NG
05 50 13 MI SCELLANEOUS METAL FABRI CATI ONS
05 51 00 METAL STAI RS
DI VI SI ON 06 - WOOD, PLASTI CS, AND COMPOSI TES
06 10 00 ROUGH CARPENTRY
06 20 00 FI NI SH CARPENTRY
06 41 16. 00 10 PLASTI C- LAMI NATE- CLAD ARCHI TECTURAL CABI NETS
06 61 16 SOLI D SURFACI NG FABRI CATI ONS
DI VI SI ON 07 - THERMAL AND MOI STURE PROTECTI ON
07 05 23 PRESSURE TESTI NG AN AI R BARRI ER SYSTEM FOR AI R TI GHTNESS
07 13 53 ELASTOMERI C SHEET WATERPROOFI NG
07 21 13 BOARD AND BLOCK I NSULATI ON
07 21 16 MI NERAL FI BER BLANKET I NSULATI ON
07 22 00 ROOF AND DECK I NSULATI ON
07 27 10. 00 10 BUI LDI NG AI R BARRI ER SYSTEM
07 27 19. 01 SELF- ADHERI NG AI R BARRI ERS
07 27 26 FLUI D- APPLI ED MEMBRANE AI R BARRI ERS
07 41 63 FABRI CATED ROOF PANEL ASSEMBLI ES
07 42 13 METAL WALL PANELS
07 57 13 SPRAYED POLYURETHANE FOAM ( SPF) ROOFI NG
07 60 00 FLASHI NG AND SHEET METAL
PROJECT TABLE OF CONTENTS Page 1
07 84 00 FIRESTOPPING
07 92 00 JOI NT SEALANTS
DI VI SI ON 08 - OPENI NGS
08 11 13 STEEL DOORS AND FRAMES
08 14 00 WOOD DOORS
08 44 00 CURTAI N WALL AND GLAZED ASSEMBLI ES
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 88 58 AI R TRAFFI C CONTROL TOWER CAB GLASS
08 91 00 METAL WALL AND DOOR LOUVERS
DI VI SI ON 09 - FI NI SHES
09 06 00 SCHEDULES FOR FI NI SHES
09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD
09 29 00 GYPSUM BOARD
09 30 10 CERAMI C, QUARRY, AND GLASS TI LI NG
09 51 00 ACOUSTI CAL CEI LI NGS
09 65 00 RESI LI ENT FLOORI NG
09 67 23. 13 STANDARD RESI NOUS FLOORI NG
09 69 13 RI GI D GRI D ACCESS FLOORI NG
09 90 00 PAI NTS AND COATI NGS
DI VI SI ON 10 - SPECI ALTI ES
10 14 00. 10 EXTERI OR SI GNAGE
10 14 00. 20 I NTERI OR SI GNAGE
10 26 00 WALL PROTECTI ON
10 28 13 TOI LET ACCESSORI ES
10 44 43. 00 37 FI RE EXTI NGUI SHER ACCESSORI ES
10 51 13 METAL LOCKERS
DI VI SI ON 12 - FURNI SHI NGS
12 24 13 ROLLER WI NDOW SHADES
12 35 13. 00 37 AI R TRAFFI C CONTROL CASEWORK
12 48 13 ENTRANCE FLOOR MATS AND FRAMES
DI VI SI ON 13 - SPECI AL CONSTRUCTI ON
13 48 00 SEI SMI C PROTECTI ON FOR MI SCELLANEOUS EQUI PMENT
13 48 00. 00 10 SEI SMI C PROTECTI ON FOR MECHANI CAL EQUI PMENT
DI VI SI ON 14 - CONVEYI NG EQUI PMENT
14 21 23 ELECTRI C TRACTI ON PASSENGER ELEVATORS
DI VI SI ON 21 - FI RE SUPPRESSI ON
21 12 00 STANDPI PE SYSTEMS
21 13 13. 00 10 WET PI PE SPRI NKLER SYSTEM, FI RE PROTECTI ON
21 30 00 FI RE PUMPS
DI VI SI ON 22 - PLUMBI NG
22 00 00 PLUMBI NG, GENERAL PURPOSE
PROJECT TABLE OF CONTENTS Page 2
DI VI SI ON 23 - HEATI NG, VENTI LATI NG, AND AI R CONDI TI ONI NG ( HVAC)
23 00 00 AI R SUPPLY, DI STRI BUTI ON, VENTI LATI ON, AND EXHAUST SYSTEMS
23 05 93 TESTI NG, ADJUSTI NG, AND BALANCI NG FOR HVAC
23 07 00 THERMAL I NSULATI ON FOR MECHANI CAL SYSTEMS
23 09 00 I NSTRUMENTATI ON AND CONTROL FOR HVAC
23 09 13 I NSTRUMENTATI ON AND CONTROL DEVI CES FOR HVAC
23 09 23. 01 LONWORKS DI RECT DI GI TAL CONTROL FOR HVAC AND OTHER
BUI LDI NG CONTROL SYSTEMS
23 11 25 FACI LI TY GAS PI PI NG
23 23 00 REFRI GERANT PI PI NG
23 52 00 HEATI NG BOI LERS
23 57 10. 00 10 FORCED HOT WATER HEATI NG SYSTEMS USI NG WATER AND STEAM
HEAT EXCHANGERS
23 64 10 WATER CHI LLERS, VAPOR COMPRESSI ON TYPE
23 64 26 CHI LLED, CHI LLED- HOT, AND CONDENSER WATER PI PI NG SYSTEMS
23 82 02. 00 10 UNI TARY HEATI NG AND COOLI NG EQUI PMENT
DI VI SI ON 25 - I NTEGRATED AUTOMATI ON
25 05 11 CYBERSECURI TY FOR FACI LI TY- RELATED CONTROL SYSTEMS
25 08 10 UTI LI TY MONI TORI NG AND CONTROL SYSTEM TESTI NG
DI VI SI ON 26 - ELECTRI CAL
26 05 19. 10 10 I NSULATED WI RE AND CABLE
26 05 48. 00 10 SEI SMI C PROTECTI ON FOR ELECTRI CAL EQUI PMENT
26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM
26 28 01. 00 10 COORDI NATED POWER SYSTEM PROTECTI ON
26 29 23 VARI ABLE FREQUENCY DRI VE SYSTEMS UNDER 600 VOLTS
26 32 14. 00 10 DI ESEL- GENERATOR SET, STATI ONARY 15- 300 KW, STANDBY
APPLICATIONS
26 36 00. 00 10 AUTOMATI C TRANSFER SWI TCH AND BY- PASS/ I SOLATI ON SWI TCH
26 41 00 LI GHTNI NG PROTECTI ON SYSTEM
26 51 00 I NTERI OR LI GHTI NG
DI VI SI ON 27 - COMMUNI CATI ONS
27 05 14. 00 10 CABLE TELEVI SI ON PREMI SES DI STRI BUTI ON SYSTEM
27 10 00 BUI LDI NG TELECOMMUNI CATI ONS CABLI NG SYSTEM
27 51 23. 10 I NTERCOMMUNI CATI ON SYSTEM
DI VI SI ON 28 - ELECTRONI C SAFETY AND SECURI TY
28 10 05 ELECTRONI C SECURI TY SYSTEMS ( ESS)
28 31 76 I NTERI OR FI RE ALARM AND MASS NOTI FI CATI ON SYSTEM
DI VI SI ON 31 - EARTHWORK
31 00 00 EARTHWORK
31 63 29 DRI LLED CONCRETE PI ERS AND SHAFTS
DI VI SI ON 32 - EXTERI OR I MPROVEMENTS
32 01 19 FI ELD MOLDED SEALANTS FOR SEALI NG JOI NTS I N RI GI D
PAVEMENTS
32 11 16 BASE COURSE FOR RI GI D PAVI NG
32 11 23 AGGREGATE AND/ OR GRADED- CRUSHED AGGREGATE BASE COURSE
32 13 13. 06 PORTLAND CEMENT CONCRETE PAVEMENT FOR ROADS AND SI TE
PROJECT TABLE OF CONTENTS Page 3
FACILITIES
32 16 13 CONCRETE SI DEWALKS AND CURBS AND GUTTERS
32 17 24. 00 10 PAVEMENT MARKI NGS
32 31 13. 53 HI GH- SECURI TY CHAI N LI NK FENCES AND GATES
32 92 19 SEEDING
32 92 23 SODDING
DI VI SI ON 33 - UTI LI TI ES
33 08 55 COMMI SSI ONI NG OF FUEL FACI LI TY SYSTEMS
33 11 00 WATER DI STRI BUTI ON
33 30 00 SANI TARY SEWERS
33 52 10 SERVI CE PI PI NG, FUEL SYSTEMS
33 56 10 FACTORY- FABRI CATED FUEL STORAGE TANKS
33 71 02 UNDERGROUND ELECTRI CAL DI STRI BUTI ON
33 82 00 TELECOMMUNI CATI ONS OUTSI DE PLANT ( OSP)
- - End of Pr oj ect Tabl e of Cont ent s - -
PROJECT TABLE OF CONTENTS Page 4
SECTI ON TABLE OF CONTENTS
DI VI SI ON 27 - COMMUNI CATI ONS
SECTI ON 27 05 14. 00 10
CABLE TELEVI SI ON PREMI SES DI STRI BUTI ON SYSTEM
04/06
PART 1 GENERAL
1. 1 REFERENCES
1. 2 SUMMARY
1. 3 SUBMI TTALS
1. 4 QUALI FI CATI ONS
1. 4. 1 Mi ni mum Cont r act or Qual i f i cat i ons
1. 4. 2 Mi ni mum Manuf act ur er Qual i f i cat i ons
1. 5 DELI VERY, STORAGE, AND HANDLI NG
1. 6 ENVI RONMENTAL REQUI REMENTS
1. 7 EXTRA MATERI ALS
PART 2 PRODUCTS
2. 1 MATERI ALS AND EQUI PMENT
2. 1. 1 Coaxi al Cabl e
2. 1. 2 CATV Out l et s
2. 1. 3 Out l et Boxes
PART 3 EXECUTI ON
3. 1 I NSTALLATI ON
3. 1. 1 Hor i zont al Cabl e I nst al l at i on
3. 1. 2 Ri ser Cabl e I nst al l at i on
3. 1. 3 Cabl es
3. 1. 4 Pul l Cor ds
3. 2 TERMI NATI ONS
3. 3 GROUNDI NG
3. 4 TESTI NG
3. 5 OPERATI ON AND MAI NTENANCE MANUALS
- - End of Sect i on Tabl e of Cont ent s - -
SECTI ON 27 05 14. 00 10 Page 1
SECTI ON 27 05 14. 00 10
CABLE TELEVI SI ON PREMI SES DI STRI BUTI ON SYSTEM
04/06
PART 1 GENERAL
1. 1 REFERENCES
The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.
NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)
NFPA 70 ( 2017; ERTA 1- 2 2017; TI A 17- 1; TI A 17- 2;
TI A 17- 3; TI A 17- 4; TI A 17- 5; TI A 17- 6;
TI A 17- 7; TI A 17- 8; TI A 17- 9; TI A 17- 10;
TI A 17- 11; TI A 17- 12; TI A 17- 13; TI A
17- 14) Nat i onal El ect r i cal Code
1. 2 SUMMARY
Pr ovi de a cabl e TV pr emi ses di st r i but i on syst em consi st i ng of coaxi al cabl es and connect i ng har dwar e t o t r anspor t t el evi s i on s i gnal s t hr oughout t he bui l di ng t o user l ocat i ons as i ndi cat ed. Submi t det ai l dr awi ngs i ncl udi ng a compl et e l i s t of equi pment and mat er i al and cont ai ni ng compl et e wi r i ng and schemat i c di agr ams and ot her det ai l s r equi r ed t o demonst r at e t hat t he syst em has been coor di nat ed and wi l l f unct i on pr oper l y as a syst em. Dr awi ngs shal l i ncl ude ver t i cal r i ser di agr ams, equi pment r ack and panel det ai l s , el evat i on dr awi ngs of t el ecommuni cat i ons c l oset wal l s, out l et f ace pl at e det ai l s f or each out l et conf i gur at i on, and descr i pt i ons and t ypes of cabl es, condui t s, and cabl e t r ays, i f used. Dr awi ngs shal l show pr oposed l ayout and anchor age of equi pment and appur t enances, and equi pment r el at i onshi p t o ot her par t s of t he wor k i ncl udi ng c l ear ance f or mai nt enance and oper at i on.
1. 3 SUBMITTALS
Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;
submi t t al s not havi ng a " G" desi gnat i on ar e f or i nf or mat i on onl y. When used, a desi gnat i on f ol l owi ng t he " G" desi gnat i on i dent i f i es t he of f i ce t hat wi l l r evi ew t he submi t t al f or t he Gover nment . Submi t t al s wi t h an " S" ar e f or i ncl usi on i n t he Sust ai nabi l i t y eNot ebook, i n conf or mance t o Section 01 33 29 SUSTAI NABI LI TY REPORTI NG. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:
SD- 02 Shop Dr awi ngs
Cabl e TV Pr emi ses Di st r i but i on Syst em; G, RO Installation ; G, RO
SD- 03 Pr oduct Dat a
CATV Out l et s; G, RO Spar e Par t s.
SECTI ON 27 05 14. 00 10 Page 2
Test Pl an; G, RO Qualifications
SD- 06 Test Repor t s
Testing
SD- 07 Cer t i f i cat es
Mat er i al s and Equi pment
SD- 08 Manuf act ur er ' s I nst r uct i ons
Manuf act ur er ' s Recommendat i ons
SD- 10 Oper at i on and Mai nt enance Dat a
Oper at i on and Mai nt enance Manual s; G, RO
1. 4 QUALIFICATIONS
Submi t pr oof of t he qual i f i cat i ons of t he Cont r act or , I nst al l er s, and Manuf act ur er s t hat wi l l per f or m t he wor k, and pr ovi de t he speci f i ed products.
1. 4. 1 Mi ni mum Cont r act or Qual i f i cat i ons
Wor k under t hi s sect i on shal l be per f or med, and equi pment shal l be f ur ni shed and i nst al l ed, by a qual i f i ed Cont r act or as def i ned her ei n. The Cont r act or shal l have a mi ni mum of t wo year s of exper i ence i n t he i nst al l at i on and t est i ng of coaxi al cabl e- based TV di st r i but i on syst ems and equi pment . I nst al l er s assi gned t o t he i nst al l at i on of t hi s syst em or i t s component s shal l have a mi ni mum of t wo year s of exper i ence i n t he i nst al l at i on of t he speci f i ed coaxi al cabl e and component s.
1. 4. 2 Mi ni mum Manuf act ur er Qual i f i cat i ons
The equi pment and har dwar e pr ovi ded under t hi s cont r act shal l be pr oduct s of manuf act ur er s t hat have a mi ni mum of t wo year s of exper i ence i n pr oduci ng t he t ypes of syst ems and equi pment speci f i ed.
1. 5 DELI VERY, STORAGE, AND HANDLI NG
Pr ot ect equi pment del i ver ed and pl aced i n st or age f r om t he weat her , humi di t y and t emper at ur e var i at i on, di r t and dust or ot her cont ami nant s.
1. 6 ENVI RONMENTAL REQUI REMENTS
Connect i ng har dwar e shal l be r at ed f or oper at i on under ambi ent condi t i ons of 32 t o 140 degr ees F and i n t he r ange of 0 t o 95 per cent r el at i ve humi di t y, non-condensing.
1. 7 EXTRA MATERI ALS
Submit spar e par t s dat a f or each di f f er ent i t em of mat er i al and equi pment speci f i ed, af t er appr oval of det ai l dr awi ngs, not l at er t han 2 mont hs pr i or t o t he dat e of benef i c i al occupancy. The dat a shal l i ncl ude a compl et e l i s t of par t s, t ool s, t est equi pment and suppl i es, wi t h cur r ent uni t pr i ces and sour ce of suppl y, and a l i s t of spar e par t s r ecommended f or st ocki ng.
SECTI ON 27 05 14. 00 10 Page 3
Pr ovi de t he f ol l owi ng addi t i onal mat er i al s r equi r ed f or f aci l i t y st ar t up:
a. 10 of each t ype of connect or used.
b. 10 of each t ype of cover pl at e, wi t h connect or .
PART 2 PRODUCTS
2. 1 MATERI ALS AND EQUI PMENT
Pr ovi de mat er i al s and equi pment whi ch ar e t he st andar d pr oduct s of a manuf act ur er r egul ar l y engaged i n t he manuf act ur e of t he pr oduct s and t hat ar e t he manuf act ur er ' s l at est st andar d desi gn t hat has been i n sat i sf act or y use f or at l east one year pr i or t o i nst al l at i on. Wher e mat er i al s or equi pment ar e speci f i ed t o conf or m, be const r uct ed or t est ed t o meet speci f i c r equi r ement s, submi t cer t i f i cat i on t hat t he i t ems pr ovi ded conf or m t o such r equi r ement s. Cer t i f i cat i on by a nat i onal l y r ecogni zed t est i ng l abor at or y t hat a r epr esent at i ve sampl e has been t est ed t o meet t he r equi r ement s, or a publ i shed cat al og speci f i cat i on st at ement t o t he ef f ect t hat t he i t em meet s t he r ef er enced st andar d, i s accept abl e as evi dence t hat t he i t em conf or ms. Compl i ance wi t h t hese r equi r ement s does not r el i eve t he Cont r act or f r om compl i ance wi t h ot her r equi r ement s of t he speci f i cat i ons.
Mat er i al s and equi pment shal l conf or m t o t he r espect i ve publ i cat i ons and ot her r equi r ement s speci f i ed bel ow and t o t he appl i cabl e r equi r ement s of NFPA 70. Cabl es shal l be l abel ed on bot h ends wi t h c i r cui t number , r oom number , or ot her appr opr i at e mar ki ng al l owi ng f or cor r ect i dent i f i cat i on of t he cabl e and i t s dest i nat i on. Each f acepl at e shal l be l abel ed wi t h i t s f unct i on and a uni que number t o i dent i f y t he cabl e r un.
2. 1. 1 Coaxi al Cabl e
Coaxi al cabl e shal l be RG- 6/ U, quad shi el d. Cabl e shal l be l abel - ver i f i ed. Cabl e j acket shal l be f act or y mar ked at r egul ar i nt er val s i dent i f y i ng cabl e t ype. Cabl e shal l be r at ed CMP, CMR, or CMG i n accor dance wi t h NFPA 70. I nt er connect i ng cabl es shal l be cabl e assembl i es consi st i ng of RG- 6/ U coaxi al cabl e wi t h mal e connect or s at each end, pr ovi ded i n l engt hs det er mi ned by equi pment l ocat i ons as shown.
2. 1. 2 CATV Out l et s
Pr ovi de f l ush mount ed, 75- ohm, F- Type connect or out l et s r at ed f r om 5 t o 1000 MHz i n st andar d el ect r i cal out l et boxes wi t h mount i ng f r ame.
Facepl at es pr ovi ded shal l be i vor y i mpact r esi st ant pl ast i c.
2. 1. 3 Out l et Boxes
El ect r i cal boxes f or cabl e t el evi s i on out l et s shal l be 4- 11/ 16 i nch squar e by 2- 1/ 8 i nches deep wi t h mi ni mum 3/ 8 i nch deep si ngl e or t wo gang pl ast er r i ng as shown. Condui t s shal l be mi ni mum 1 i nch.
PART 3 EXECUTI ON
3. 1 INSTALLATION
I nst al l syst em component s and appur t enances i n accor dance wi t h NFPA 70, manuf act ur er ' s i nst r uct i ons and as shown. Submi t r ecor d dr awi ngs f or t he i nst al l ed cabl e syst em showi ng t he l ocat i ons of cabl e t er mi nat i ons, i ncl udi ng out l et s, and l ocat i on and r out i ng of cabl es. The i dent i f i er f or each t er mi nat i on and cabl e shal l appear on t he dr awi ngs. Pr ovi de necessar y i nt er connect i ons, ser vi ces, and adj ust ment s r equi r ed f or a compl et e cabl e
SECTI ON 27 05 14. 00 10 Page 4 t el evi s i on di st r i but i on syst em, r eady t o connect t o ext er nal t el evi s i on s i gnal sour ces. Penet r at i ons i n f i r e- r at ed const r uct i on shal l be f i r est opped i n accor dance wi t h Sect i on 07 84 00 FI RESTOPPI NG. I nst al l condui t s, out l et s, r aceways, and wi r i ng i n accor dance wi t h Sect i on 26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM. Cabl es and out l et s shal l be i ndi v i dual l y l abel ed and mar ked. Cabl es shal l not be i nst al l ed i n t he same cabl e t r ay, ut i l i t y pol e compar t ment , or f l oor t r ench compar t ment wi t h ac power cabl es. Cabl es not i nst al l ed i n condui t or wi r eways shal l be pr oper l y secur ed and neat i n appear ance and, i f i nst al l ed i n pl enums or ot her spaces used f or envi r onment al ai r , shal l compl y wi t h NFPA 70 r equi r ement s f or t hi s t ype of i nst al l at i on.
3. 1. 1 Hor i zont al Cabl e I nst al l at i on
The r at ed cabl e pul l i ng t ensi on shal l not be exceeded. Cabl e shal l not be st r essed such t hat t wi st i ng, st r et chi ng or k i nki ng occur s. Cabl e shal l not be spl i ced. Cabl e not i n a wi r eway shal l be suspended a mi ni mum of 8 i nches above cei l i ngs by cabl e suppor t s no gr eat er t han 60 i nches apar t . Cabl e shal l not be r un t hr ough st r uct ur al member s or i n cont act wi t h pi pes, duct s, or ot her pot ent i al l y damagi ng i t ems. Pl acement of cabl e par al l el t o power conduct or s shal l be avoi ded, i f possi bl e; a mi ni mum separ at i on of 12 inches shal l be mai nt ai ned when such pl acement cannot be avoi ded. Cabl es shal l be t er mi nat ed unl ess shown ot her wi se. Mi ni mum bendi ng r adi us shal l not be exceeded dur i ng i nst al l at i on or once i nst al l ed. Cabl e t i es shal l not be excessi vel y t i ght ened such t hat t he t r ansmi ssi on char act er i s t i cs of t he cabl e ar e al t er ed.
3. 1. 2 Ri ser Cabl e I nst al l at i on
The r at ed cabl e pul l i ng t ensi on shal l not be exceeded. Ri ser cabl e suppor t i nt er val s shal l be i n accor dance wi t h manuf act ur er ' s r ecommendat i ons.
Wher e i nst al l at i on pr ocedur es, or any par t t her eof , ar e r equi r ed t o be i n accor dance wi t h t he r ecommendat i ons of t he manuf act ur er of t he mat er i al bei ng i nst al l ed, pr i nt ed copi es of t hese r ecommendat i ons shal l be pr ovi ded pr i or t o i nst al l at i on. I nst al l at i on of t he i t em wi l l not be al l owed t o pr oceed unt i l t he r ecommendat i ons ar e r ecei ved and appr oved. Cabl e bend r adi us shal l not be l ess t han t en t i mes t he out s i de di amet er of t he cabl e dur i ng i nst al l at i on and once i nst al l ed. Maxi mum t ensi l e st r engt h r at i ng of t he cabl e shal l not be exceeded. Cabl e shal l not be spl i ced.
3. 1. 3 Cables
Cabl es shal l have a mi ni mum of 6 i nches of s l ack cabl e l oosel y coi l ed i nt o t he cabl e t el evi s i on out l et boxes. Mi ni mum manuf act ur er ' s bend r adi us shal l not be exceeded.
3. 1. 4 Pul l Cor ds
Pul l cor ds shal l be i nst al l ed i n condui t s ser vi ng t he cabl e t el evi s i on pr emi ses di st r i but i on syst em whi ch do not i ni t i al l y have cabl e i nst al l ed.
3. 2 TERMINATIONS
Cabl es and conduct or s shal l sweep i nt o t er mi nat i on ar eas; cabl es and conduct or s shal l not bend at r i ght angl es. Manuf act ur er ' s mi ni mum bendi ng r adi us shal l not be exceeded. Coaxi al cabl es shal l be t er mi nat ed wi t h appr opr i at e connect or s as r equi r ed. Cabl e shi el d conduct or shal l be gr ounded t o communi cat i ons gr ound at onl y one poi nt and shal l not make el ect r i cal cont act wi t h gr ound anywher e el se.
SECTI ON 27 05 14. 00 10 Page 5
3. 3 GROUNDING
The cabl e t el evi s i on di st r i but i on syst em gr ound shal l be i nst al l ed i n t he cabl e t el evi s i on ent r ance f aci l i t y and i n any auxi l i ar y c l oset i dent i f i ed i n Sect i on 26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM or ot her wi se i ndi cat ed.
Equi pment r acks shal l be connect ed t o t he el ect r i cal saf et y gr ound.
3. 4 TESTING
Submi t t est r epor t s i n bookl et f or m wi t h wi t ness s i gnat ur es ver i f y i ng execut i on of t est s. The cabl e syst em t est i ng document at i on shal l i ncl ude t he physi cal r out i ng and a t est r epor t f or each cabl e ( end- t o- end) f r om t he i nst al l ed out l et t o t he mai n t er mi nat i on poi nt . Test r epor t s shal l be submi t t ed wi t hi n 7 days af t er compl et i on of t est i ng. Mat er i al s and document at i on t o be f ur ni shed under t hi s speci f i cat i on ar e subj ect t o i nspect i ons and t est s.
a. Submi t a Test Pl an def i ni ng t he t est s r equi r ed t o ensur e t hat t he syst em meet s t echni cal , oper at i onal and per f or mance speci f i cat i ons, 60 days pr i or t o t he pr oposed t est dat e. The pl an shal l be appr oved bef or e t est i ng begi ns. The t est pl an shal l i dent i f y t he capabi l i t i es and f unct i ons t o be t est ed, and i ncl ude det ai l ed i nst r uct i ons f or t he set up and execut i on of each t est and pr ocedur es f or eval uat i on and document at i on of t he r esul t s.
b. Component s shal l be t er mi nat ed pr i or t o t est i ng.
c. Equi pment and syst ems wi l l not be accept ed unt i l t he r equi r ed i nspect i ons and t est s have been made, demonst r at i ng t hat t he cabl e t el evi s i on pr emi ses di st r i but i on syst em conf or ms t o t he speci f i ed r equi r ement s, and t hat t he r equi r ed equi pment , syst ems, and document at i on have been pr ovi ded.
d. Af t er i nst al l at i on of t he cabl e and bef or e connect i ng syst em component s, each cabl e sect i on shal l be end- t o- end t est ed usi ng a t i me domai n r ef l ect omet er ( TDR) t o det er mi ne shor t s, opens, k i nks, and ot her i mpedance di scont i nui t i es and t hei r l ocat i ons. Cabl e sect i ons showi ng adver se i mpedance di scont i nui t i es ( gr eat er t han 6 dB l oss) shal l be r epl aced at t he Cont r act or ' s expense.
e. Ther e shal l be no cabl e spl i ces bet ween syst em component s unl ess appr oved by t he Gover nment .
3. 5 OPERATI ON AND MAI NTENANCE MANUALS
Submi t commer ci al , of f - t he- shel f manual s f or oper at i on, i nst al l at i on, conf i gur at i on, and mai nt enance of pr oduct s pr ovi ded as a par t of t he cabl e t el evi s i on pr emi ses di st r i but i on syst em.
- - End of Sect i on - -
SECTI ON 27 05 14. 00 10 Page 6
SECTI ON TABLE OF CONTENTS
DI VI SI ON 27 - COMMUNI CATI ONS
SECTI ON 27 10 00
BUI LDI NG TELECOMMUNI CATI ONS CABLI NG SYSTEM
08/11
PART 1 GENERAL
1. 1 REFERENCES
1. 2 DEFI NI TI ONS
1. 2. 1 Campus Di st r i but or ( CD)
1. 2. 2 Bui l di ng Di st r i but or ( BD)
1. 2. 3 Fl oor Di st r i but or ( FD)
1. 2. 4 Tel ecommuni cat i ons Room ( TR)
1. 2. 5 Ent r ance Faci l i t y ( EF) ( Tel ecommuni cat i ons)
1. 2. 6 Equi pment Room ( ER) ( Tel ecommuni cat i ons)
1. 2. 7 Open Cabl e
1. 2. 8 Open Of f i ce
1. 2. 9 Pat hway
1. 3 SYSTEM DESCRI PTI ON
1. 4 SUBMI TTALS
1. 5 QUALI TY ASSURANCE
1. 5. 1 Shop Dr awi ngs
1. 5. 1. 1 Tel ecommuni cat i ons Dr awi ngs
1. 5. 1. 2 Tel ecommuni cat i ons Space Dr awi ngs
1. 5. 2 Tel ecommuni cat i ons Qual i f i cat i ons
1. 5. 2. 1 Tel ecommuni cat i ons Cont r act or
1. 5. 2. 2 Key Per sonnel
1. 5. 2. 3 Mi ni mum Manuf act ur er Qual i f i cat i ons
1. 5. 3 Test Pl an
1. 5. 4 Regul at or y Requi r ement s
1. 5. 5 St andar d Pr oduct s
1. 5. 5. 1 Al t er nat i ve Qual i f i cat i ons
1. 5. 5. 2 Mat er i al and Equi pment Manuf act ur i ng Dat e
1. 6 DELI VERY AND STORAGE
1. 7 ENVI RONMENTAL REQUI REMENTS
1. 8 WARRANTY
1. 9 MAI NTENANCE
1. 9. 1 Oper at i on and Mai nt enance Manual s
1. 9. 2 Recor d Document at i on
1. 9. 3 Spar e Par t s
PART 2 PRODUCTS
2. 1 COMPONENTS
2. 2 TELECOMMUNI CATI ONS PATHWAY
2. 3 TELECOMMUNI CATI ONS CABLI NG
2. 3. 1 Backbone Cabl i ng
2. 3. 1. 1 Backbone Copper
2. 3. 1. 2 Backbone Opt i cal Fi ber
2. 3. 2 Hor i zont al Cabl i ng
2. 3. 2. 1 Hor i zont al Copper
SECTI ON 27 10 00 Page 1
2. 4 TELECOMMUNI CATI ONS SPACES
2. 4. 1 Backboar ds
2. 4. 2 Equi pment Suppor t Fr ame
2. 4. 3 Connect or Bl ocks
2. 4. 4 Cabl e Gui des
2. 4. 5 Pat ch Panel s
2. 4. 5. 1 Modul ar t o 110 Bl ock Pat ch Panel
2. 4. 5. 2 Fi ber Opt i c Pat ch Panel
2. 4. 6 Opt i cal Fi ber Di st r i but i on Panel
2. 5 TELECOMMUNI CATI ONS OUTLET/ CONNECTOR ASSEMBLI ES
2. 5. 1 Out l et / Connect or Copper
2. 5. 2 Opt i cal Fi ber Adapt er s( Coupl er s)
2. 5. 3 Opt i cal Fi ber Connect or s
2. 5. 4 Cover Pl at es
2. 6 GROUNDI NG AND BONDI NG PRODUCTS
2. 7 FI RESTOPPI NG MATERI AL
2. 8 MANUFACTURER' S NAMEPLATE
2. 9 FI ELD FABRI CATED NAMEPLATES
2. 10 TESTS, I NSPECTI ONS, AND VERI FI CATI ONS
2. 10. 1 Fact or y Reel Test s
PART 3 EXECUTI ON
3. 1 I NSTALLATI ON
3. 1. 1 Cabl i ng
3. 1. 1. 1 Open Cabl e
3. 1. 1. 2 Backbone Cabl e
3. 1. 1. 3 Hor i zont al Cabl i ng
3. 1. 2 Pat hway I nst al l at i ons
3. 1. 3 Ser v i ce Ent r ance Condui t , Under gr ound
3. 1. 4 Cabl e Tr ay I nst al l at i on
3. 1. 5 Wor k Ar ea Out l et s
3. 1. 5. 1 Ter mi nat i ons
3. 1. 5. 2 Cover Pl at es
3. 1. 5. 3 Cabl es
3. 1. 5. 4 Pul l Cor ds
3. 1. 6 Tel ecommuni cat i ons Space Ter mi nat i on
3. 1. 6. 1 Connect or Bl ocks
3. 1. 6. 2 Pat ch Panel s
3. 1. 6. 3 Equi pment Suppor t Fr ames
3. 1. 7 El ect r i cal Penet r at i ons
3. 1. 8 Gr oundi ng and Bondi ng
3. 2 LABELI NG
3. 2. 1 Label s
3. 2. 2 Cabl e
3. 2. 3 Ter mi nat i on Har dwar e
3. 3 FI ELD APPLI ED PAI NTI NG
3. 3. 1 Pai nt i ng Backboar ds
3. 4 FI ELD FABRI CATED NAMEPLATE MOUNTI NG
3. 5 TESTI NG
3. 5. 1 Tel ecommuni cat i ons Cabl i ng Test i ng
3. 5. 1. 1 I nspect i on
3. 5. 1. 2 Ver i f i cat i on Test s
3. 5. 1. 3 Per f or mance Test s
3. 5. 1. 4 Fi nal Ver i f i cat i on Test s
SECTI ON 27 10 00 Page 2
SECTI ON 27 10 00
BUI LDI NG TELECOMMUNI CATI ONS CABLI NG SYSTEM
08/11
PART 1 GENERAL
1. 1 REFERENCES
The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.
ASTM I NTERNATI ONAL ( ASTM)
ASTM D709 ( 2017) St andar d Speci f i cat i on f or Lami nat ed Ther moset t i ng Mat er i al s
ELECTRONI C COMPONENTS I NDUSTRY ASSOCI ATI ON ( ECI A)
ECI A EI A/ ECA 310- E ( 2005) Cabi net s, Racks, Panel s, and Associ at ed Equi pment
I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)
I EEE 100 ( 2000; Ar chi ved) The Aut hor i t at i ve Di ct i onar y of I EEE St andar ds Ter ms
I NSULATED CABLE ENGI NEERS ASSOCI ATI ON ( I CEA)
I CEA S- 83- 596 ( 2016) I ndoor Opt i cal Fi ber Cabl es
I CEA S- 90- 661 ( 2012) Cat egor y 3, 5, & 5e I ndi v i dual l y Unshi el ded Twi st ed Pai r I ndoor Cabl es f or Use i n Gener al Pur pose and LAN Communi cat i ons Wi r i ng Syst ems Techni cal Requirements
NATI ONAL ELECTRI CAL CONTRACTORS ASSOCI ATI ON ( NECA)
NECA/ BI CSI 568 ( 2006) St andar d f or I nst al l i ng Bui l di ng Tel ecommuni cat i ons Cabl i ng
NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)
ANSI / NEMA WC 66 ( 2013) Per f or mance St andar d f or Cat egor y 6 and Cat egor y 7 100 Ohm Shi el ded and Unshi el ded Twi st ed Pai r s
NEMA VE 1 ( 2017) Met al Cabl e Tr ay Syst ems
NEMA VE 2 ( 2006) Cabl e Tr ay I nst al l at i on Gui del i nes
NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)
NFPA 70 ( 2017; ERTA 1- 2 2017; TI A 17- 1; TI A 17- 2;
TI A 17- 3; TI A 17- 4; TI A 17- 5; TI A 17- 6;
TI A 17- 7; TI A 17- 8; TI A 17- 9; TI A 17- 10;
SECTI ON 27 10 00 Page 3
TI A 17- 11; TI A 17- 12; TI A 17- 13; TI A
17- 14) Nat i onal El ect r i cal Code
TELECOMMUNI CATI ONS I NDUSTRY ASSOCI ATI ON ( TI A)
TIA-1152 ( 2009) Requi r ement s f or Fi el d Test I nst r ument s and Measur ement s f or Bal anced Twi st ed- Pai r Cabl i ng
TIA-455-21 ( 1988a; R 2012) FOTP- 21 - Mat i ng Dur abi l i t y of Fi ber Opt i c I nt er connect i ng Devices
TIA-526-7 ( 2015a) OFSTP- 7 Measur ement of Opt i cal Power Loss of I nst al l ed Si ngl e- Mode Fi ber Cabl e Pl ant
TIA-568-C.0 ( 2009; Add 1 2010; Add 2 2012) Gener i c Tel ecommuni cat i ons Cabl i ng f or Cust omer Premises
TIA-568-C.1 ( 2009; Add 2 2011; Add 1 2012) Commer ci al Bui l di ng Tel ecommuni cat i ons Cabl i ng Standard
TIA-568-C.2 ( 2009; Er r at a 2010; Add 2 2014; Add 1 2016) Bal anced Twi st ed- Pai r Tel ecommuni cat i ons Cabl i ng and Component s Standards
TIA-568-C.3 ( 2008; Add 1 2011) Opt i cal Fi ber Cabl i ng Component s St andar d
TIA-569 ( 2015d) Commer ci al Bui l di ng St andar d f or Tel ecommuni cat i ons Pat hways and Spaces
TIA-606 ( 2017c) Admi ni st r at i on St andar d f or t he Tel ecommuni cat i ons I nf r ast r uct ur e
TIA-607 ( 2011b) Gener i c Tel ecommuni cat i ons Bondi ng and Gr oundi ng ( Ear t hi ng) f or Cust omer Premises
TIA/EIA-598 ( 2014d) Opt i cal Fi ber Cabl e Col or Codi ng
TIA/EIA-604-3 ( 2004b; R 2014) Fi ber Opt i c Connect or I nt er mat eabi l i t y St andar d ( FOCI S) , Type SC and SC- APC, FOCI S- 3
U. S. FEDERAL COMMUNI CATI ONS COMMI SSI ON ( FCC)
FCC Par t 68 Connect i on of Ter mi nal Equi pment t o t he Tel ephone Net wor k ( 47 CFR 68)
UNDERWRI TERS LABORATORI ES ( UL)
UL 1286 ( 2008; Repr i nt Feb 2015) Of f i ce Fur ni shi ngs
UL 1666 ( 2007; Repr i nt Jun 2012) Test f or Fl ame
SECTI ON 27 10 00 Page 4
Pr opagat i on Hei ght of El ect r i cal and Opt i cal - Fi ber Cabl es I nst al l ed Ver t i cal l y i n Shaf t s
UL 1863 ( 2004; Repr i nt Sep 2016) UL St andar d f or Saf et y Communi cat i on Ci r cui t Accessor i es
UL 444 ( 2008; Repr i nt Apr 2015) Communi cat i ons Cables
UL 467 ( 2013; Repr i nt Jun 2017) UL St andar d f or Saf et y Gr oundi ng and Bondi ng Equi pment
UL 50 ( 2015) UL St andar d f or Saf et y Encl osur es f or El ect r i cal Equi pment , Non- Envi r onment al Consi der at i ons
UL 514C ( 2014; Repr i nt Dec 2014) Nonmet al l i c Out l et Boxes, Fl ush- Devi ce Boxes, and Covers
UL 723 ( 2008; Repr i nt Dec 2017) Test f or Sur f ace Bur ni ng Char act er i st i cs of Bui l di ng Materials
UL 969 ( 2017) UL St andar d f or Saf et y Mar ki ng and Label i ng Syst ems
1. 2 DEFINITIONS
Unl ess ot her wi se speci f i ed or i ndi cat ed, el ect r i cal and el ect r oni cs t er ms used i n t hi s speci f i cat i on shal l be as def i ned i n TIA-568-C.1 , TIA-568-C.2 , TIA-568-C.3 , TIA-569 , TIA-606 and I EEE 100 and her ei n.
1. 2. 1 Campus Di st r i but or ( CD)
A di st r i but or f r om whi ch t he campus backbone cabl i ng emanat es.
( I nt er nat i onal expr essi on f or mai n cr oss- connect ( MC) . )
1. 2. 2 Bui l di ng Di st r i but or ( BD)
A di st r i but or i n whi ch t he bui l di ng backbone cabl es t er mi nat e and at whi ch connect i ons t o t he campus backbone cabl es may be made. ( I nt er nat i onal expr essi on f or i nt er medi at e cr oss- connect ( I C) . )
1. 2. 3 Fl oor Di st r i but or ( FD)
A di st r i but or used t o connect hor i zont al cabl e and cabl i ng subsyst ems or equi pment . ( I nt er nat i onal expr essi on f or hor i zont al cr oss- connect ( HC) . )
1. 2. 4 Tel ecommuni cat i ons Room ( TR)
An encl osed space f or housi ng t el ecommuni cat i ons equi pment , cabl e, t er mi nat i ons, and cr oss- connect s. The r oom i s t he r ecogni zed cr oss- connect bet ween t he backbone cabl e and t he hor i zont al cabl i ng.
1. 2. 5 Ent r ance Faci l i t y ( EF) ( Tel ecommuni cat i ons)
An ent r ance t o t he bui l di ng f or bot h pr i vat e and publ i c net wor k ser vi ce
SECTI ON 27 10 00 Page 5 cabl es ( i ncl udi ng wi r el ess) i ncl udi ng t he ent r ance poi nt at t he bui l di ng wal l and cont i nui ng t o t he equi pment r oom.
1. 2. 6 Equi pment Room ( ER) ( Tel ecommuni cat i ons)
An envi r onment al l y cont r ol l ed cent r al i zed space f or t el ecommuni cat i ons equi pment t hat ser ves t he occupant s of a bui l di ng. Equi pment housed t her ei n i s consi der ed di st i nct f r om a t el ecommuni cat i ons r oom because of t he nat ur e of i t s compl exi t y.
1. 2. 7 Open Cabl e
Cabl i ng t hat i s not r un i n a r aceway as def i ned by NFPA 70. Thi s r ef er s t o cabl i ng t hat i s " open" t o t he space i n whi ch t he cabl e has been i nst al l ed and i s t her ef or e exposed t o t he envi r onment al condi t i ons associ at ed wi t h t hat space.
1. 2. 8 Open Of f i ce
A f l oor space di v i s i on pr ovi ded by f ur ni t ur e, moveabl e par t i t i ons, or ot her means i nst ead of by bui l di ng wal l s.
1. 2. 9 Pathway
A physi cal i nf r ast r uct ur e ut i l i zed f or t he pl acement and r out i ng of t el ecommuni cat i ons cabl e.
1. 3 SYSTEM DESCRI PTI ON
The bui l di ng t el ecommuni cat i ons cabl i ng and pat hway syst em shal l i ncl ude per manent l y i nst al l ed backbone and hor i zont al cabl i ng, hor i zont al and backbone pat hways, ser vi ce ent r ance f aci l i t i es, wor k ar ea pat hways, t el ecommuni cat i ons out l et assembl i es, condui t , r aceway, and har dwar e f or spl i c i ng, t er mi nat i ng, and i nt er connect i ng cabl i ng necessar y t o t r anspor t t el ephone and dat a ( i ncl udi ng LAN) bet ween equi pment i t ems i n a bui l di ng.
The hor i zont al syst em shal l be wi r ed i n a st ar t opol ogy f r om t he t el ecommuni cat i ons wor k ar ea t o t he f l oor di st r i but or or campus di st r i but or at t he cent er or hub of t he st ar . The backbone cabl i ng and pat hway syst em i ncl udes i nt r abui l di ng and i nt er bui l di ng i nt er connect i ng cabl i ng, pat hway, and t er mi nal har dwar e. The i nt r abui l di ng backbone pr ovi des connect i v i t y f r om t he f l oor di st r i but or s t o t he bui l di ng di st r i but or s or t o t he campus di st r i but or and f r om t he bui l di ng di st r i but or s t o t he campus di st r i but or as r equi r ed. The backbone syst em shal l be wi r ed i n a st ar t opol ogy wi t h t he campus di st r i but or at t he cent er or hub of t he st ar . The i nt er bui l di ng backbone syst em pr ovi des connect i v i t y bet ween t he campus di st r i but or s and i s speci f i ed i n Sect i on 33 82 00 TELECOMMUNI CATI ONS OUTSI DE PLANT ( OSP) .
Pr ovi de t el ecommuni cat i ons pat hway syst ems r ef er enced her ei n as speci f i ed i n Sect i on 26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM.
1. 4 SUBMITTALS
Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;
submi t t al s not havi ng a " G" desi gnat i on ar e f or i nf or mat i on onl y. When used, a desi gnat i on f ol l owi ng t he " G" desi gnat i on i dent i f i es t he of f i ce t hat wi l l r evi ew t he submi t t al f or t he Gover nment . Submi t t al s wi t h an " S" ar e f or i ncl usi on i n t he Sust ai nabi l i t y eNot ebook, i n conf or mance t o Section 01 33 29 SUSTAI NABI LI TY REPORTI NG. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:
SECTI ON 27 10 00 Page 6
SD- 02 Shop Dr awi ngs
Tel ecommuni cat i ons dr awi ngs; G, RO
Tel ecommuni cat i ons Space Dr awi ngs; G, RO
I n addi t i on t o Sect i on 01 33 00 SUBMI TTAL PROCEDURES, pr ovi de shop dr awi ngs i n accor dance wi t h par agr aph SHOP DRAWI NGS.
SD- 03 Pr oduct Dat a
Tel ecommuni cat i ons cabl i ng ( backbone and hor i zont al ) ; G, RO
Pat ch panel s; G, RO
Tel ecommuni cat i ons out l et / connect or assembl i es; G, RO
Equi pment suppor t f r ame; G, RO Connect or bl ocks; G, RO
Spar e Par t s; G, RO
Submi t t al s shal l i ncl ude t he manuf act ur er ' s name, t r ade name, pl ace of manuf act ur e, and cat al og model or number . I ncl ude per f or mance and char act er i st i c cur ves. Submi t t al s shal l al so i ncl ude appl i cabl e f eder al , mi l i t ar y, i ndust r y, and t echni cal soci et y publ i cat i on r ef er ences. Shoul d manuf act ur er ' s dat a r equi r e suppl ement al i nf or mat i on f or c l ar i f i cat i on, t he suppl ement al i nf or mat i on shal l be submi t t ed as speci f i ed i n par agr aph REGULATORY REQUI REMENTS and as r equi r ed i n Sect i on
01 33 00 SUBMI TTAL PROCEDURES.
SD- 06 Test Repor t s
Tel ecommuni cat i ons cabl i ng t est i ng; G, RO
SD- 07 Cer t i f i cat es
Tel ecommuni cat i ons Cont r act or Qual i f i cat i ons; G, RO
Key Per sonnel Qual i f i cat i ons; G, RO
Manuf act ur er Qual i f i cat i ons; G, RO
Test pl an; G, RO
SD- 09 Manuf act ur er ' s Fi el d Repor t s
Fact or y r eel t est s; G, RO
SD- 10 Oper at i on and Mai nt enance Dat a
Tel ecommuni cat i ons cabl i ng and pat hway syst em Dat a Package 5; G, RO
SD- 11 Cl oseout Submi t t al s
Recor d Document at i on; G, RO
SECTI ON 27 10 00 Page 7
1. 5 QUALI TY ASSURANCE
1. 5. 1 Shop Dr awi ngs
I n except i on t o Sect i on 01 33 00 SUBMI TTAL PROCEDURES, submi t t ed pl an dr awi ngs shal l be a mi ni mum of 11 by 17 i nches i n s i ze usi ng a mi ni mum scal e of 1/ 8 i nch per f oot , except as speci f i ed ot her wi se. I ncl ude wi r i ng di agr ams and i nst al l at i on det ai l s of equi pment i ndi cat i ng pr oposed l ocat i on, l ayout and ar r angement , cont r ol panel s, accessor i es, pi pi ng, duct wor k, and ot her i t ems t hat must be shown t o ensur e a coor di nat ed i nst al l at i on. Wi r i ng di agr ams shal l i dent i f y c i r cui t t er mi nal s and i ndi cat e t he i nt er nal wi r i ng f or each i t em of equi pment and t he i nt er connect i on bet ween each i t em of equi pment . Dr awi ngs shal l i ndi cat e adequat e c l ear ance f or oper at i on, mai nt enance, and r epl acement of oper at i ng equi pment devi ces. Submi t t al s shal l i ncl ude t he namepl at e dat a, s i ze, and capaci t y. Submi t t al s shal l al so i ncl ude appl i cabl e f eder al , mi l i t ar y, i ndust r y, and t echni cal soci et y publ i cat i on r ef er ences.
1. 5. 1. 1 Tel ecommuni cat i ons Dr awi ngs
Pr ovi de r egi st er ed communi cat i ons di st r i but i on desi gner ( RCDD) appr oved, dr awi ngs i n accor dance wi t h TIA-606 . The i dent i f i er f or each t er mi nat i on and cabl e shal l appear on t he dr awi ngs. Dr awi ngs shal l depi ct f i nal t el ecommuni cat i ons i nst al l ed wi r i ng syst em i nf r ast r uct ur e i n accor dance with TIA-606 . The dr awi ngs shoul d pr ovi de det ai l s r equi r ed t o pr ove t hat t he di st r i but i on syst em shal l pr oper l y suppor t connect i v i t y f r om t he EF t el ecommuni cat i ons and ER t el ecommuni cat i ons, CD' s, and FD' s t o t he t el ecommuni cat i ons wor k ar ea out l et s. Pr ovi de a pl ast i c l ami nat ed schemat i c of t he as- i nst al l ed t el ecommuni cat i ons cabl e syst em showi ng cabl i ng, CD' s, BD' s, FD' s, and t he EF and ER f or t el ecommuni cat i ons keyed t o f l oor pl ans by r oom number . Mount t he l ami nat ed schemat i c i n t he EF t el ecommuni cat i ons space as di r ect ed by t he Cont r act i ng Of f i cer . The f ol l owi ng dr awi ngs shal l be pr ovi ded as a mi ni mum:
a. T1 - Layout of compl et e bui l di ng per f l oor - Bui l di ng Ar ea/ Ser v i ng Zone Boundar i es, Backbone Syst ems, and Hor i zont al Pat hways. Layout of compl et e bui l di ng per f l oor . The dr awi ng i ndi cat es l ocat i on of bui l di ng ar eas, ser vi ng zones, ver t i cal backbone di agr ams, t el ecommuni cat i ons r ooms, access poi nt s, pat hways, gr oundi ng syst em, and ot her syst ems t hat need t o be v i ewed f r om t he compl et e bui l di ng per spect i ve.
b. T2 - Ser vi ng Zones/ Bui l di ng Ar ea Dr awi ngs - Dr op Locat i ons and Cabl e I dent i f i cat i on ( I D’ S) . Shows a bui l di ng ar ea or ser vi ng zone. These dr awi ngs show dr op l ocat i ons, t el ecommuni cat i ons r ooms, access poi nt s and det ai l cal l out s f or common equi pment r ooms and ot her congest ed areas.
c. T4 - Typi cal Det ai l Dr awi ngs - Facepl at e Label i ng, Fi r est oppi ng, Amer i cans wi t h Di sabi l i t i es Act ( ADA) , Saf et y, Depar t ment of Tr anspor t at i on ( DOT) . Det ai l ed dr awi ngs of symbol s and t ypi cal s such as f acepl at e l abel i ng, f acepl at e t ypes, f acepl at e popul at i on i nst al l at i on pr ocedur es, det ai l r acki ng, and r aceways.
1. 5. 1. 2 Tel ecommuni cat i ons Space Dr awi ngs
Pr ovi de T3 dr awi ngs i n accor dance wi t h TIA-606 t hat i ncl ude t el ecommuni cat i ons r ooms pl an v i ews, pat hway l ayout ( cabl e t r ay, r acks, l adder - r acks, et c. ) , mechani cal / el ect r i cal l ayout , and cabi net , r ack, backboar d and wal l el evat i ons. Dr awi ngs shal l show l ayout of appl i cabl e
SECTI ON 27 10 00 Page 8 equi pment i ncl udi ng i ncomi ng cabl e st ub or connect or bl ocks, bui l di ng pr ot ect or assembl y, out goi ng cabl e connect or bl ocks, pat ch panel s and equi pment spaces and cabi net / r acks. Dr awi ngs shal l i ncl ude a compl et e l i s t of equi pment and mat er i al , equi pment r ack det ai l s , pr oposed l ayout and anchor age of equi pment and appur t enances, and equi pment r el at i onshi p t o ot her par t s of t he wor k i ncl udi ng c l ear ance f or mai nt enance and oper at i on.
Dr awi ngs may al so be an enl ar gement of a congest ed ar ea of T1 or T2 drawings.
1. 5. 2 Tel ecommuni cat i ons Qual i f i cat i ons
Wor k under t hi s sect i on shal l be per f or med by and t he equi pment shal l be pr ovi ded by t he appr oved t el ecommuni cat i ons cont r act or and key per sonnel .
Qual i f i cat i ons shal l be pr ovi ded f or : t he t el ecommuni cat i ons syst em cont r act or , t he t el ecommuni cat i ons syst em i nst al l er , and t he super v i sor ( i f di f f er ent f r om t he i nst al l er ) . A mi ni mum of 30 days pr i or t o i nst al l at i on, submi t document at i on of t he exper i ence of t he t el ecommuni cat i ons cont r act or and of t he key per sonnel .
1. 5. 2. 1 Tel ecommuni cat i ons Cont r act or
The t el ecommuni cat i ons cont r act or shal l be a f i r m whi ch i s r egul ar l y and pr of essi onal l y engaged i n t he busi ness of t he appl i cat i ons, i nst al l at i on, and t est i ng of t he speci f i ed t el ecommuni cat i ons syst ems and equi pment . The t el ecommuni cat i ons cont r act or shal l demonst r at e exper i ence i n pr ovi di ng successf ul t el ecommuni cat i ons syst ems wi t hi n t he past 3 year s of s i mi l ar scope and si ze. Submi t document at i on f or a mi ni mum of t hr ee and a maxi mum of f i ve successf ul t el ecommuni cat i on syst em i nst al l at i ons f or t he t el ecommuni cat i ons cont r act or .
1. 5. 2. 2 Key Per sonnel
Pr ovi de key per sonnel who ar e r egul ar l y and pr of essi onal l y engaged i n t he busi ness of t he appl i cat i on, i nst al l at i on and t est i ng of t he speci f i ed t el ecommuni cat i ons syst ems and equi pment . Ther e may be one key per son or mor e key per sons pr oposed f or t hi s sol i c i t at i on dependi ng upon how many of t he key r ol es each has successf ul l y pr ovi ded. Each of t he key per sonnel shal l demonst r at e exper i ence i n pr ovi di ng successf ul t el ecommuni cat i ons syst ems wi t hi n t he past 3 year s.
Super vi sor s and i nst al l er s assi gned t o t he i nst al l at i on of t hi s syst em or any of i t s component s shal l be Bui l di ng I ndust r y Consul t i ng Ser vi ces I nt er nat i onal ( BI CSI ) Regi st er ed Cabl i ng I nst al l er s, Techni c i an Level .
Submi t document at i on of cur r ent BI CSI cer t i f i cat i on f or each of t he key personnel.
I n l i eu of BI CSI cer t i f i cat i on, super vi sor s and i nst al l er s assi gned t o t he i nst al l at i on of t hi s syst em or any of i t s component s shal l have a mi ni mum of 3 year s exper i ence i n t he i nst al l at i on of t he speci f i ed copper and f i ber opt i c cabl e and component s. They shal l have f act or y or f act or y appr oved cer t i f i cat i on f r om each equi pment manuf act ur er i ndi cat i ng t hat t hey ar e qual i f i ed t o i nst al l and t est t he pr ovi ded pr oduct s. Submi t document at i on f or a mi ni mum of t hr ee and a maxi mum of f i ve successf ul t el ecommuni cat i on syst em i nst al l at i ons f or each of t he key per sonnel . Document at i on f or each key per son shal l i ncl ude at l east t wo successf ul syst em i nst al l at i ons pr ovi ded t hat ar e equi val ent i n syst em si ze and i n const r uct i on compl exi t y t o t he t el ecommuni cat i ons syst em pr oposed f or t hi s sol i c i t at i on. I ncl ude speci f i c exper i ence i n i nst al l i ng and t est i ng t el ecommuni cat i ons syst ems and pr ovi de t he names and l ocat i ons of at l east t wo pr oj ect i nst al l at i ons
SECTI ON 27 10 00 Page 9 successf ul l y compl et ed usi ng opt i cal f i ber and copper t el ecommuni cat i ons cabl i ng syst ems. Al l of t he exi st i ng t el ecommuni cat i ons syst em i nst al l at i ons of f er ed by t he key per sons as successf ul exper i ence shal l have been i n successf ul f ul l - t i me ser vi ce f or at l east 18 mont hs pr i or t o t he i ssuance dat e f or t hi s sol i c i t at i on. Pr ovi de t he name and r ol e of t he key per son, t he t i t l e, l ocat i on, and compl et ed i nst al l at i on dat e of t he r ef er enced pr oj ect , t he r ef er enced pr oj ect owner poi nt of cont act i nf or mat i on i ncl udi ng name, or gani zat i on, t i t l e, and t el ephone number , and gener al l y, t he r ef er enced pr oj ect descr i pt i on i ncl udi ng syst em si ze and const r uct i on compl exi t y.
I ndi cat e t hat al l key per sons ar e cur r ent l y empl oyed by t he t el ecommuni cat i ons cont r act or , or have a commi t ment t o t he t el ecommuni cat i ons cont r act or t o wor k on t hi s pr oj ect . Al l key per sons shal l be empl oyed by t he t el ecommuni cat i ons cont r act or at t he dat e of i ssuance of t hi s sol i c i t at i on, or i f not , have a commi t ment t o t he t el ecommuni cat i ons cont r act or t o wor k on t hi s pr oj ect by t he dat e t hat t he bi d was due t o t he Cont r act i ng Of f i cer .
Not e t hat onl y t he key per sonnel appr oved by t he Cont r act i ng Of f i cer i n t he successf ul pr oposal shal l do wor k on t hi s sol i c i t at i on' s t el ecommuni cat i ons syst em. Key per sonnel shal l f unct i on i n t he same r ol es i n t hi s cont r act , as t hey f unct i oned i n t he of f er ed successf ul exper i ence. Any subst i t ut i ons f or t he t el ecommuni cat i ons cont r act or ' s key per sonnel r equi r es appr oval f r om The Cont r act i ng Of f i cer .
1. 5. 2. 3 Minimum Manuf act ur er Qual i f i cat i ons
Cabl i ng, equi pment and har dwar e manuf act ur er s shal l have a mi ni mum of 3 year s exper i ence i n t he manuf act ur i ng, assembl y, and f act or y t est i ng of component s whi ch compl y wi t h TIA-568-C.1 , TIA-568-C.2 and TIA-568-C.3 .
1. 5. 3 Test Pl an
Pr ovi de a compl et e and det ai l ed t est pl an f or t he t el ecommuni cat i ons cabl i ng syst em i ncl udi ng a compl et e l i s t of t est equi pment f or t he component s and accessor i es f or each cabl e t ype speci f i ed, 60 days pr i or t o t he pr oposed t est dat e. I ncl ude pr ocedur es f or cer t i f i cat i on, val i dat i on, and t est i ng.
1. 5. 4 Regul at or y Requi r ement s
I n each of t he publ i cat i ons r ef er r ed t o her ei n, consi der t he advi sor y pr ovi s i ons t o be mandat or y, as t hough t he wor d, " shal l " had been subst i t ut ed f or " shoul d" wher ever i t appear s. I nt er pr et r ef er ences i n t hese publ i cat i ons t o t he " aut hor i t y havi ng j ur i sdi ct i on, " or wor ds of s i mi l ar meani ng, t o mean t he Cont r act i ng Of f i cer . Equi pment , mat er i al s, i nst al l at i on, and wor kmanshi p shal l be i n accor dance wi t h t he mandat or y and advi sor y pr ovi s i ons of NFPA 70 unl ess mor e st r i ngent r equi r ement s ar e speci f i ed or i ndi cat ed.
1. 5. 5 St andar d Pr oduct s
Pr ovi de mat er i al s and equi pment t hat ar e pr oduct s of manuf act ur er s r egul ar l y engaged i n t he pr oduct i on of such pr oduct s whi ch ar e of equal mat er i al , desi gn and wor kmanshi p. Pr oduct s shal l have been i n sat i sf act or y commer ci al or i ndust r i al use f or 2 year s pr i or t o bi d openi ng. The 2- year per i od shal l i nc l ude appl i cat i ons of equi pment and mat er i al s under s i mi l ar c i r cumst ances and of s i mi l ar s i ze. The pr oduct shal l have been on sal e on
SECTI ON 27 10 00 Page 10 t he commer ci al mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es dur i ng t he 2- year per i od. Wher e t wo or mor e i t ems of t he same cl ass of equi pment ar e r equi r ed, t hese i t ems shal l be pr oduct s of a s i ngl e manuf act ur er ; however , t he component par t s of t he i t em need not be t he pr oduct s of t he same manuf act ur er unl ess st at ed i n t hi s sect i on.
1. 5. 5. 1 Al t er nat i ve Qual i f i cat i ons
Pr oduct s havi ng l ess t han a 2- year f i el d ser vi ce r ecor d wi l l be accept abl e i f a cer t i f i ed r ecor d of sat i sf act or y f i el d oper at i on f or not l ess t han 6000 hour s, excl usi ve of t he manuf act ur er s ' f act or y or l abor at or y t est s, i s furnished.
1. 5. 5. 2 Mat er i al and Equi pment Manuf act ur i ng Dat e
Pr oduct s manuf act ur ed mor e t han 1 year pr i or t o dat e of del i ver y t o s i t e shal l not be used, unl ess speci f i ed ot her wi se.
1. 6 DELI VERY AND STORAGE
Pr ovi de pr ot ect i on f r om weat her , moi st ur e, ext r eme heat and col d, di r t , dust , and ot her cont ami nant s f or t el ecommuni cat i ons cabl i ng and equi pment pl aced i n st or age.
1. 7 ENVI RONMENTAL REQUI REMENTS
Connect i ng har dwar e shal l be r at ed f or oper at i on under ambi ent condi t i ons of 32 t o 140 degr ees F and i n t he r ange of 0 t o 95 per cent r el at i ve humi di t y, noncondensing.
1. 8 WARRANTY
The equi pment i t ems shal l be suppor t ed by ser vi ce or gani zat i ons whi ch ar e r easonabl y conveni ent t o t he equi pment i nst al l at i on i n or der t o r ender sat i sf act or y ser vi ce t o t he equi pment on a r egul ar and emer gency basi s dur i ng t he war r ant y per i od of t he cont r act .
1. 9 MAINTENANCE
1. 9. 1 Oper at i on and Mai nt enance Manual s
Commer ci al of f t he shel f manual s shal l be f ur ni shed f or oper at i on, i nst al l at i on, conf i gur at i on, and mai nt enance of pr oduct s pr ovi ded as a par t of t he t el…