The purpose of this Amendment is to revise Specifications as described herein.
SEE SF30 BLOCK 14 CONTINUATION PAGE FOR DETAILS.
1. CONTRACT ID CODE PAGE OF PAGES
J 1 2
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 04-May-2011
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W912ES-11-R-0001
X 9B. DATED (SEE ITEM 11)
12-Apr-2011
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
03-May-2011
CODE
CONTRACTING DIVISION
USACE - ST PAUL
180 5TH STREET EAST
SUITE 700
ST. PAUL MN 55101-1678
W912ES 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
W912ES-11-R-0001
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SPECIFICATION CHANGES
Note: Additions are shown as underlined.
Section 46 07 53.13, PACKAGED WASTEWATER TREATMENT EQUIPMENT, AERATION, has been revised as follows:
a. Paragraph 2.3, STEEL CONSTRUCTION, is revised to read as follows:
“The WWTP shall be built of ¼-inch minimum thickness structural grade steel plate and shall be designed to withstand normal soil pressures when installed below grade and hydrostatic pressures when installed above grade.Required welding shall be in accordance the American Welding Society's Structural Welding Code (AWS D1.1/D1.1M)and AWWA D100. All welded structural members shall be joined by electric arc welding with fillets of adequate section for the joint involved. Welds shall be continuous inside and out where required for sectional strength or water tightness. The structural components shall be joined by welding as described above and meet AISC welded joint specifications. All necessary bulkheads shall be factory installed. The entire WWTP shall be installed on minimum 8" steel I-beams to keep the plant off the ground and concrete. The connection of the I-beams to the concrete and the I-beams to the WWTP shall be a positive connection. The contractor shall design these connections. Acceptable connections shall include bolted connections, anchor bolts, and welded connections. Anchor bolts installed in concrete shall be stainless steel. Other positive connections designed by the contractor can also be proposed.”
b. Paragraph 2.5, EQUALIZATION TANK , is revised to read as follows:
“The equalization tank shall have a minimum capacity of 10,000 gallons.
The equalization tank shall allow for a constant flow through the plant by equalizing flow surges that may be incurred during peak flow times.
The tank shall contain a duplex set of progressing cavity pumps to transfer the sewage to the aeration tank at a constant rate. The constant rate shall be adjustable based on the flow coming into the tank or at the Operator's direction. An emergency overflow will be provided between the equalization and aeration chamber.
The tank shall have aeration diffuser(s) to provide adequate air to prevent the occurrence of anaerobic conditions. Diffused air shall be provided by the plant blower system.
Liquid level sensors will regulate the pumps and blower/motor unit. Controls will be provided in the plant control panel.
The contractor can provide alternate methods for metering the flow from the equalization basin. System shall be designed by the contractor and any alternate method of flow control needs to be equivalent to the progressing cavity pumps and also adjustable.”
(End of Summary of Changes)