B.08.03 Amendment 0003 DRAWINGS DOC FOR W912ER20R0013 - 474512 ATCT UD 2.4 JORDAN 25 Jan 22_1215.pdf

PDF 3 MB Posted

Attached to
Construct Air Traffic Control Tower - Undisclosed location, Hashemite Kingdom of Jordan
Solicitation number
W912ER22R0006
Issued by

About this file

This document summarizes a federal contract opportunity notice for the construction of an air traffic control tower in Jordan. The U.S. Army Corps of Engineers Transatlantic Middle East District is soliciting bids to design and build a new 12-story air traffic control tower with cab and balcony floors on a reinforced concrete pile foundation with a steel superstructure and precast concrete facade. The project scope includes construction of an elevator, catwalk, fire detection and suppression systems, HVAC, emergency power, utilities and site improvements. The facility must support a radar approach control system and comply with DoD antiterrorism requirements. The contract value is estimated between $10-25 million. The response deadline is not provided. Interested offerors should visit the site. The NAICS code is 236220 and the small business size standard is $39.5 million. The period of performance is 750 calendar days from notice to proceed.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

G-012

T-603 JR-474512A-T-603-03 3 AM 0003 INTERCOM RISER DIAGRAM

FIRST FLOOR

0 mm

SECOND FLOOR

3200 mm

THIRD FLOOR

6400 mm

FOURTH FLOOR

9600 mm

FIFTH FLOOR

12800 mm

SIXTH FLOOR

16000 mm

SEVENTH FLOOR

19200 mm

EIGHTH FLOOR

22400 mm

NINTH FLOOR

25600 mm

TENTH FLOOR

28800 mm

BALCONY

34385 mm

CAB FLOOR

36700 mm

TOP OF STL

41340 mm

INTERIOR

LOBBY

A D

ELEV PIT

-1800 mm

COBSTRUCTION

WARNING LIGHT

ELEVENTH FLOOR

32000 mm

A.9

35 T.O.X

36100 mm

A-421

B

RECESS FLR

-750 mm

FIRST FLOOR

0 mm

SECOND FLOOR

3200 mm

THIRD FLOOR

6400 mm

A D G

A-310

PRECAST CONC

ACCENT, PC-2

PRECAST CONC

PANELS, PC-1

RAPCON

EXTERIOR

LOBBY

A.9

SEE 5/A501 FOR SIMILAR DETAIL

B

RECESS FLR

-750 mm

RAISED ACCESS FLOOR

SYSTEM.

FIRST FLOOR

0 mm

SECOND FLOOR

3200 mm

THIRD FLOOR

6400 mm

FOURTH FLOOR

9600 mm

FIFTH FLOOR

12800 mm

SIXTH FLOOR

16000 mm

SEVENTH FLOOR

19200 mm

EIGHTH FLOOR

22400 mm

NINTH FLOOR

25600 mm

TENTH FLOOR

28800 mm

BALCONY

34385 mm

CAB FLOOR

36700 mm

TOP OF STL

41340 mm

1 2

4 53

ELEVENTH FLOOR

32000 mm

CONTROL

CAB

MECH

BREAK /

READY RM

UPPER EQUIP

RM.

LOWER

EQUIP RM

OFFICE

OFFICE

OFFICE

OFFICE

CONF

MECH

T.O.X 36100 mm

A-312

A-312

A-312

A-310

A-310

RECESS FLR

-750 mm

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E

File Path:

Plot Date:

M

AR

K D

ES

C

R

IP

TI

O

N

UNLESS OTHERWISE NOTED, LINEAR

DIMENSIONS SHOWN ARE IN MILLIMETERS.

PL

O

T D

AT

E:

FI

LE

N

AM

E:

US

A rm y

Co rp s of

E ng in ee rs M id dl e Ea st D is tri ct

C:\Users\n0enasl3\Documents\JR-474512A-A-DM-ATCT_AMD 03_n0enasl3.rvt

1/25/2022 11:17:36 AM

1/

/2

:1 7:

AM

A-301

BU

IL

D

IN

G S

EC

TI

O N

S

U D

.4

, J O

R D

AN

SF

J

SF

J

SF

L

SF

L

-2

9-

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

(A

TC

T)

JR

-4

A

J.

R

AN

EY

, C H

IE

F

JR

-4

2A -A

-3

-0

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

W

IN

C H

ES

TE

R , V

A.

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

1:100

10m2m 8m6m4m0m

1 : 1002 BUILDING SECTION

1 : 1003 BUILDING SECTION

R

EV

IS

ED

I. A

.W .A

M

EN

M

EN

T

JA

N

1 : 1001 Section 4

GENERAL NOTES

1. SEE A-001 FOR FORE RATING REQUIREMENT FOR STEEL FRAMING,

FLOOR DECK, ROOF DECK.

2. ALL CONCEALED STEEL FRAMINGS RECEIVE SPRAY ON FIRE

0 mm

G

PRECAST CONCRETE

PANEL, 50 mm CONT FOAM

INSULATION / AIR BARRIER,

20 GA META STUDS 400 mm

OC BATT INSULATION, 16

mm GWB. TOTAL R-20 MIN

MEMBERANE WATER PROOFING

AROUND BUILDING PERIMETER.

OVERLAP WITH FOUNDATION

WATER PROOFING

A-501

SCHEDULED CEILING

STRUCTURAL STEEL

FRAMING WITH 2 HOUR

FIRE PROOFING. SEE

STRUCTURAL

BRACING. SEE

STRUCTURAL

STRAP ANCHOR AND

SUBFRAMING / SUPPORT

BY PRECAST PANEL

FABRICATOR, TYP

GRAVEL AROUND

BUILDING PERIMETER.

SLOPE BOTTOM TO

PROVID POSITIVE

DRAIN.

FIRST FLOOR

0 mm

SECOND FLOOR

3200 mm

LOW ROOF

3550 mm

WRAP UP MEMBERANE WATER

PROOFING AS INDICATED.

ATTACHED TO STUDS

FIRST FLOOR

0 mm

SECOND FLOOR

3200 mm

THIRD FLOOR

6400 mm

A-603

SCHEDULED DOOR

CONCRETE SLAB SEE

STRUCTURAL

SCHEDULED CEILING TYP

SEE 1/A-502 FOR TYPICAL

DETAILS

ALUMINUM FRAMED WINDOW

SYSTEM - TYP

OPP HAND

A-311

PRECAST CONCRETE

WALL PANEL BEYOND

STRUCT SLAB SEE

STRUCTURAL DWGS

COMPRESSIBLE FILLER

AT OUTDOOR STOOP

JOINT, TYP.

SEE STRUCTURAL FOR

FOUNDATION DETAILS

TENTH FLOOR

28800 mm

CAB FLOOR

36700 mm

TYP PRECAST EXTERIOR

WALL SEE DETAIL 1/A311

FOR NOTES

50 MM INSULATED BLANK OFF PANEL

BY LOUVER MANUFACTURER

SCHEDULED CEILING TYP

STRUCT FLOOR SLAB TYP

STRUCTURAL STEEL FRAMING W/ 2

HOURS FIRE PROOFING

ALUMINUM FRAMED WINDOW

SYSTEM,

TYP

ACCESS FLOORING

SEE 1/A311 FOR DETAIL, TYP

GFRC DECO BEYOND.

SEE A-201 FOR DETAIL

ELEVENTH FLOOR

32000 mm

A-311

T.O.X 36100 mm

EXPOSED BRACING TO HAVE 2 HOUR

INTUMENSCENT COATING, TYPICAL FOR

ALL W3 LOCATIONS.

BALCONY

34385 mm

13 MM GWB ON 92 MM MTL STUDS

FRAMING, TYP

SEE MECH FOR DUCT OPENING

SIZE AND LOCATIONS.

A-311

A-311

SIM

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S D

R

AW

N B

Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E

File Path:

Plot Date:

M

AR

K D

ES

C

R

IP

TI

O

N

UNLESS OTHERWISE NOTED, LINEAR

DIMENSIONS SHOWN ARE IN MILLIMETERS.

PL

O

T D

AT

E:

FI

LE

N

AM

E:

US

A rm y

Co rp s of

E ng in ee rs M id dl e Ea st D is tri ct

C:\Users\n0enasl3\Documents\JR-474512A-A-DM-ATCT_AMD 03_n0enasl3.rvt

12/30/2021 11:44:36 AM

/3

0/ 2 0

:4 4:

3 6

AM

A-310

W

AL

L

SE

C

TI

O N

S

U D

.4

, J O

R D

AN

SF

J

SF

J

SF

L

SF

L

-2

9-

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

(A

TC

T)

JR

-4

A

J.

R

AN

EY

, C H

IE

F

JR

-4

2A -A

-3

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

W

IN

C H

ES

TE

R , V

A.

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

1 : 251 WALL SECTION 1

1 : 252 WALL SECTION 2

1 : 253 WALL SECTION 3

1:20

2m0.4m 1.6m1.2m0.8m0m

AM

D #3

D at e

F

A

G

C

K

A-402 3

C

B

FD

TOILET

MEN

WOMEN

A-402

A-402

FD

FD

A

B

C

3B

4K

1300 2876

I

C

K

A

K

SEALANT

2082 mm TP-1 W/

MFR STANDARD DR.

NO FLOOR OFFSET.

A

C

L

L

B

L

MOP SINK

2 305 86

A F-G

B C

3'

4" M

AX

K

1 152 10

67 TO BOTTOM OF

REFLECTIVE

SURFACE

I

E

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E

File Path:

Plot Date:

M

AR

K D

ES

C

R

IP

TI

O

N

UNLESS OTHERWISE NOTED, LINEAR

DIMENSIONS SHOWN ARE IN MILLIMETERS.

PL

O

T D

AT

E:

FI

LE

N

AM

E:

US

A rm y

Co rp s of

E ng in ee rs M id dl e Ea st D is tri ct

C:\Users\n0enasl3\Documents\JR-474512A-A-DM-ATCT_AMD 03_n0enasl3.rvt

1/18/2022 2:28:38 PM

1/

/2

2:

:3

PM

A-401

EN

LA

R G

ED

R

ES

TR

O O

M P

LA

N

S

U D

.4

, J O

R D

AN

SF

J

SF

J

SF

L

SF

L

-2

9-

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

(A

TC

T)

JR

-4

A

J.

R

AN

EY

, C H

IE

F

JR

-4

2A -A

-4

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

W

IN

C H

ES

TE

R , V

A.

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

1 : 253 ACCESSIBLE TOILET 104

1 : 255 WOMENS RESTROOM 503 AND MENS RESTROOM 505

1 : 254 TOILET ROOMS 1003

TOILET ACCESSORY SCHEDULE

TYPE

MARK DESCRIPTION

A SURFACE MOUNTED MULTI-ROLL TOILET

TISSUE DISPENSER

B SURFACE MOUNTED PAPER TOWEL

DISPENSER AND WASTE RECEPTACLE

C SURFACE MOUNTED SOAP DISPENSER

E SURFACE MOUNTED SANITARY NAPKIN

DISPOSAL

F 1066 MM GRAB BAR

G 914 MM GRAB BAR

H HEAVY DUTY SHELF & MOP HOLDER

I SURFACE MOUNTED DOUBLE ROBE

HOOK

J CURTAIN ROD, CURTAIN AND HOOKS

K MIRROR WITH STAINLESS STEEL

CHANNEL FRAME

L FULL LENGTH STAINLESS STEEL

CHANNEL FRAMED MIRROR

M SURFACE MOUNTED SHOWER SOAP

DISPENSER

1 : 501 TYPICAL MOUNTING HEIGHTS

1:20

2m0.4m 1.6m1.2m0.8m0m

GENERAL NOTES:

1. SLOPE FLOOR TO FLOOR DRAIN 1% AT ALL TOILET ROOMS.

R

EV

IS

ED

I. A

.W .A

M

EN

M

EN

T

JA

N

FLOOR SLOPE 1% TO FD

FLOOR SLOPE 2% TO FD

B

K

BASE PB-1

PAINT PT-5

C

GF

K

B

BASE PB-1

PAINT PT-5

NOTE: ROOM 1003 PLUMBING WALL ELEVATION

IS SIMILAR EXCEPT WITHOUT "F" AND "G".

G

F

BASE PB-1

PAINT PT-5

C

K

300W X 300D DOUBLE

TIER LOCKERS

BASE PB-1

PAINT PT-5

B

K

TILE CWT-2

BASE PB-1

TILE CWT-1

PAINT PT-5

300W X 300D

DOUBLE TIER

LOCKERS

BASE AS

SCHEDULED

PAINT PT-5

K

C

BASE PB-2

PAINT PT-5

300W X 300D

DOUBLE TIER

LOCKERS

BASE PB-2

PAINT PT-5

SHOWER WITH CURTAIN

ROD

TILE CWT-1

TILE CWT-2

TILE CWT-2

BASE PB-1

PAINT PT-5

TILE CWT-1

BASE PB-2

PAINT PT-5

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S D

R

AW

N B

Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E

File Path:

Plot Date:

M

AR

K D

ES

C

R

IP

TI

O

N

UNLESS OTHERWISE NOTED, LINEAR

DIMENSIONS SHOWN ARE IN MILLIMETERS.

PL

O

T D

AT

E:

FI

LE

N

AM

E:

US

A rm y

Co rp s of

E ng in ee rs M id dl e Ea st D is tri ct

C:\Users\n0enasl3\Documents\JR-474512A-A-DM-ATCT_AMD 03_n0enasl3.rvt

1/10/2022 5:48:36 PM

1/

/2 0 2

5:

:3

PM

A-402

R

ES

TR

O

O M

/ L O

C

KE

R R

O O

M E

LE

VA

TI

O

N S

U D

.4

, J O

R D

AN

SF

J

SF

J

SF

L

SF

L

-2

9-

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

(A

TC

T)

JR

-4

A

J.

R

AN

EY

, C H

IE

F

JR

-4

2A -A

-4

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

W

IN

C H

ES

TE

R , V

A.

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

1 : 502 SOUTH ELEV RM 104

1 : 503 EAST ELEV RM 104

1 : 501 NORTH ELEV RM 104

1 : 5010 SOUTH ELEV RM 503

1 : 508 NORTH ELEV RM 503

1 : 5011 WEST ELEV RM 503

1 : 505 EAST ELEV RM 505

1 : 504 NORTH ELEV RM 505

1 : 509 EAST ELEV RM 503

1:50

5m1m 4m3m2m0m

TOILET ACCESSORY SCHEDULE

TYPE

MARK DESCRIPTION

A SURFACE MOUNTED MULTI-ROLL TOILET

TISSUE DISPENSER

B SURFACE MOUNTED PAPER TOWEL

DISPENSER AND WASTE RECEPTACLE

C SURFACE MOUNTED SOAP DISPENSER

E SURFACE MOUNTED SANITARY NAPKIN

DISPOSAL

F 1066 MM GRAB BAR

G 914 MM GRAB BAR

H HEAVY DUTY SHELF & MOP HOLDER

I SURFACE MOUNTED DOUBLE ROBE

HOOK

J CURTAIN ROD, CURTAIN AND HOOKS

K MIRROR WITH STAINLESS STEEL

CHANNEL FRAME

L FULL LENGTH STAINLESS STEEL

CHANNEL FRAMED MIRROR

M SURFACE MOUNTED SHOWER SOAP

DISPENSER

AM

D #3

D at e

GENERAL NOTE

1. SEE I-602 FOR INTERIOR FINISHES DETAILS.

1 : 506 SOUTH ELEV RM 505

CONTROL

CAB

6" UP

6"

UP

SURFACE MTD

DIFFUSER, REFER

TO MECH DWGS

ACCESS FLOORING

PEDESTAL, TYP

EDGE OF SLAB

(6)- 50 mm CONDUIT

SLEEVES THRU SLAB

(6) - 100 mm CONDUITS

FROM LEVEL

BELOW

PROVIDE (6) - 50 mm

GROMMETS IN TILE

PROVIDE (6) - 50 mm

GROMMETS IN TILE

ROOF HATCH WITH

PULL DOWN LADDER

ABOVE

BOOK SHELVING

05 07 06 07 05

15 05

04 10

16 16

GROUND

FLIGHT DATA

LO

C

AL

SUPERVISOR

16A

2 3

7 6

CAB.1

CAB.3

CAB.B CAB.DCAB.A CAB.E

CAB.2

CAB.C

CAB EQUIPMENT TABLE

ID NAME

NIC

01 COFFEE NIC

02 MICRO

03 U.C. REFRIGERATOR NIC

04 LIGHT GUN WITH CHARGER

PROVIDER

05 ATISI / A FAS (24" MORNITOR, KEY BOARD)

06 FLIGHT STRIP BAY

07 EIVS (CONTROL, SPEAKER, JACK BOX)

08 FDIO MONITOR AND PRTR

09 GROUND RAMP LIGHT CTRL

10 VHF / UHF MULTI-CHANNEL RADIO CONTROL PANEL

12 AIRFIELD LIGHT CONTROL

13 PIDP (DBRITE KEYBOARD)

14 DBRITE MONITOR

15 ADMINISTRATIVE CPU

16 PHONE

17 INTERCOM / DOOR RELEASE

18 LAND MOBILE RADIO W/ CHARGER

16A CRASH PHONE

QTY

20 SUP CONSOLE

21 OUTER PERIMETER CONSOLE

22 COFFEE COUNTER

GENERATOR MONITOR

NIWC

REMOTE STATUS INDICTOR

JACK BOX U.C.

16B RJAF PHONE 3

05A ADOC (24" MORNITOR, KEY BOARD) 4

GFGI

CAB GLASS MULLION ROUTING TABLE

ID DESCRIPTION OF UTILITY

1 100 mm COMM CONDUIT FOR NIWC USE COMM

2 NOT ASSIGNED

3 NOT ASSSIGNED

4 100 mm COMM CONDUIT FOR NIWC

COORDINATION

5 65 mm SPRINKLER PIPE AND UP TO 2 FIRE DETN CONDUITS

7 NOT ASSIGNED

8 75 mm ROOF DRAIN PIPE

COMM

6 ELEC CONDUIT

FP

ELEC

PLUMBING

NOTES:

1. 50mm COMM CONDUITS AT MULLION 1 AND 4 REQUIRED BY UFC 4-133-01 SECTION 4-1.2.17.1 AND FIG. 4-2.

2. ALL MULLIONS' INSIDE SPACE RESERVED FOR ADD'L NIWC COMM ROUNTING TO ROOF.

3. SEE 12 / A-603 FOR DETAIL. COORDINATE WITH ENGINEERING DRAWINGS FOR ROUTING INFORMATION.

4. LIGHTNING PROTECTION SYSTEM CONNECTORS (2) ARE ROUTED IN CONDUIT ON BUILDING EXTERIOR.

5. NIWC IS NAVAL INFORMATION WAREFARE CENTER, WHICH WILL INSTALL AIR TRAFFIC CONTROL

EQUIPMENT.

NIWC

NIWC

NIWC

NIWC

NIWC

NIWC

NIWC

NIWC

NIWC

NIWC

NIWC

NIWC

NIWC

NIWC

NIWC

NIWC

NIWC

NIWC

NIWC

NIWC

CPCI

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E

File Path:

Plot Date:

M

AR

K D

ES

C

R

IP

TI

O

N

UNLESS OTHERWISE NOTED, LINEAR

DIMENSIONS SHOWN ARE IN MILLIMETERS.

PL

O

T D

AT

E:

FI

LE

N

AM

E:

US

A rm y

Co rp s of

E ng in ee rs M id dl e Ea st D is tri ct

C:\Users\n0enasl3\Documents\JR-474512A-A-DM-ATCT_AMD 03_n0enasl3.rvt

1/21/2022 11:54:51 AM

1/

/2

:5 4:

AM

A-422

C

AB

P

LA

N A

N D

V

IE

W

U D

.4

, J O

R D

AN

SF

L

SF

L

SF

L

-2

9-

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

(A

TC

T)

JR

-4

A

J.

R

AN

EY

, C H

IE

F

JR

-4

2A -A

-4

-0

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

W

IN

C H

ES

TE

R , V

A.

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

1 : 254 ENLARGED CAB LAYOUT

R

EV

IS

ED

I. A

.W .A

M

EN

M

EN

T

JA

N

CAB CONSOLE AND EQUIPMENT BY PROVIDED

AND INSTALLED BY NIWC. FINAL LAYOUT SHALL

BE COORDINATED WITH GOVERNMENT INSTALLER

1 2 3

127 127

300 900

250 400 250

NOTE: SEE SCHEDULE FOR

DOORS REQUIRE LOUVER

NOTE: SEE SCHEDULE FOR

DOORS REQUIRE LOUVER

S1 (Not Used) S2

84 14

916 1040 51

127786127

1" INSULATED

GLAZING -

TEMPERED

A B

AS SCHED.

AS

S

C H

ED

50 50

AS SCHED.

AS

S

C H

ED

50 50

1. VERIFY ALL CONCRETE OPENINGS IN THE FIELD PRIOR TO FABRICATION OF DOORS AND

FRAMES.

2. ALL UNDERCUT DOOR REQUIREMENTS FOR VARYING CARPET THICKNESS, TILE

FLOORING ETC. SHALL BE VARIED AND PROPERLY COORDINATED WITH THE FINISH

SCHEDULE.

3. ALL STEEL DOORS & FRAMES TO BE SHOP PRIMED AND FIELD PAINTED SLATE GRAY

EXCEPT FOR THE PREFINISHED ALUMN FRAMES.

K L2 L3 L4 L5 L1

L6 L7

W1

W3 / W4

(NOTE: OVERALL DIMENSIONS

ARE OPENING SIZE. )

OPERABLE SASH

SPANDREL GLAZING

@ W3 WINDOWS ONLY

1" INSULATED

GLAZING -

TEMPERED

EQ 711 EQ

EQ

EQ

US Army Corps of Engineers ®

SHEET ID

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S D

R

AW

N B

Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E

File Path:

Plot Date:

M

AR

K D

ES

C

R

IP

TI

O

N

UNLESS OTHERWISE NOTED, LINEAR

DIMENSIONS SHOWN ARE IN MILLIMETERS.

PL

O

T D

AT

E:

FI

LE

N

AM

E:

US

A rm y

Co rp s of

E ng in ee rs M id dl e Ea st D is tri ct

C:\Users\n0enasl3\Documents\JR-474512A-A-DM-ATCT_AMD 03_n0enasl3.rvt

1/10/2022 3:10:45 PM

1/

/2 0 2

3:

:4

PM

A-602

D O

O R

W

IN

D O

W A

N D

L O

U

VE

R S

C H

ED

U

LE

S

U D

.4

, J O

R D

AN

SF

L

SF

L

SF

L

-2

9-

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

(A

TC

T)

JR

-4

A

J.

R

AN

EY

, C H

IE

F

JR

-4

2A -A

-6

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

W

IN

C H

ES

TE

R , V

A.

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

DOOR SCHEDULE

WT

DOOR

MAT

DOOR

FIRE

RATING

FRAME

HEAD THRESHOLD HDWR COMMENTSTYPE

SIZE

TYPE MATWIDTH HGHT THK

101 5 SCW 900 mm 2150 mm 50 mm 90 A HM 7/A-603 3/A-603 7 101A 1 HM 900 mm 2150 mm 50 mm 90 A HM 1/A-603 3/A-603 5 BLAST RESIST 102 1 HM 900 mm 2150 mm 50 mm A HM 1/A-603 3/A-603 4 LOUVER 103 4 HM 1200 mm 2150 mm 45 mm B HM 1/A-603 3/A-603 3 LOUVER 104 5 SCW 900 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 11 50 mm UNDERCUT 105 5 SCW 900 mm 2150 mm 50 mm 45 A HM 7/A-603 4/A-603 8 108 3 ALUM 50 mm S2 ALUM 2/A-603 4/A-603 2 SEE DOOR TYPE FOR SIZE, CIPHER LOCK 109 1 HM 900 mm 2150 mm 50 mm A HM 1/A-603 3/A-603 1A BLAST RESIST, CIPHER LOCK 110 4 SCW 1200 mm 2150 mm 45 mm A HM 7/A-603 9/A-603 1 STC 45 111 4 HM 1200 mm 2150 mm 45 mm B HM 1/A-603 3/A-603 3 201 5 SCW 900 mm 2150 mm 50 mm 90 A HM 7/A-603 9/A-603 7 202 5 SCW 900 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 6A 203 2 SCW 1200 mm 2150 mm 50 mm - A HM 7/A-603 9/A-603 14 301 5 SCW 900 mm 2150 mm 50 mm 90 A HM 7/A-603 9/A-603 7 302 2 SCW 1200 mm 2150 mm 50 mm - A HM 7/A-603 9/A-603 14 303 5 SCW 900 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 6A STC 45 304 5 SCW 900 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 6A STC 45 401 5 SCW 900 mm 2150 mm 50 mm 90 A HM 7/A-603 9/A-603 7 402 5 SCW 900 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 6A STC 45 403 2 SCW 1200 mm 2150 mm 50 mm - A HM 7/A-603 9/A-603 14 501 5 SCW 900 mm 2150 mm 50 mm 90 A HM 7/A-603 9/A-603 7 503 1 SCW 800 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 12 504 5 SCW 900 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 13 505 1 SCW 800 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 12 50 mm UNDERCUT 601 5 SCW 900 mm 2150 mm 50 mm 90 A HM 7/A-603 9/A-603 7 602 5 SCW 900 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 6A STC 45 603 2 SCW 1200 mm 2150 mm 50 mm - A HM 7/A-603 9/A-603 13 701 5 SCW 900 mm 2150 mm 50 mm 90 A HM 7/A-603 9/A-603 7 702 5 SCW 900 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 6A STC 45 703 2 SCW 1200 mm 2150 mm 50 mm - HM 7/A-603 9/A-603 13 801 5 SCW 900 mm 2150 mm 50 mm 90 A HM 7/A-603 9/A-603 7 802 1 SCW 914 mm 2032 mm 44 mm 45 A HM 7/A-603 9/A-603 8 901 5 SCW 900 mm 2150 mm 50 mm 90 A HM 7/A-603 9/A-603 7 902 1 SCW 914 mm 2032 mm 44 mm 45 A HM 7/A-603 9/A-603 8 905 5 SCW 900 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 6A STC 45 1001 5 SCW 900 mm 2150 mm 50 mm 90 A HM 7/A-603 9/A-603 7 1003 1 SCW 800 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 11 50 mm UNDERCUT 1006 5 SCW 900 mm 2150 mm 50 mm 45 B HM 7/A-603 9/A-603 13 1101A 1 HM 914 mm 2032 mm 44 mm 90 A HM 7/A-603 9/A-603 8A 1101B 1 SCW 914 mm 2032 mm 44 mm 90 A HM 1/A-603 9/A-603 14 RELEASE CONTROL, INTERCOM, STC 45 1102B 10 HM 900 mm 1828 mm 50 mm A HM 1/A-603 3/A-603 5 STC 45 (TYPE 10 IS LOWER SIZE THANTYPE 1)

1:50

5m1m 4m3m2m0m

DOOR TYPES

1 : 50

STOREFRONT TYPES

1 : 48

FRAME TYPES

LOUVER SCHEDULE

TYPE

MARK

ROUGH OPENING

COMMENTSWIDTH HEIGHT

K 2000 mm 1600 mm KNOCK OUT LOUVER WITH 50MM BLANK OFF L1 1610 mm 1250 mm LOUVER L2 850 mm 750 mm LOUVER L3 350 mm 350 mm LOUVER L4 1000 mm 1000 mm LOUVER L5 457 mm 203 mm LOUVER L6 500 mm 500 mm LOUVER L7 400 mm 400 mm LOUVER

WINDOW SCHEDULE

TYPE

MARK

ROUGH OPENING SILL

HEIGHT MODEL MATERIAL

DETAILS

COMMENTSWIDTH HEIGHT HEAD JAMB SILL

W1 600 MM 900 MM 1100 mm ALUM 5/A-603 SIM 5/A-603 1/A-502 W3 2100 MM 2150 MM 0'-0" AFF ALUM 5/A-603 SIM 5/A-603 1/A-502 LOW E GLAZING, STC 42

W4 2100 MM 2150 MM 0'-0" AFF ALUM 5/A-603 SIM 5/A-603 1/A-502 U=0.15, STC 42

AM

D #3

D at e

1 : 50

LOUVER TYPES

1 : 24

WINDOW TYPES

1100 mm SILL

HEIGHT AFF

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E

File Path:

Plot Date:

M

AR

K D

ES

C

R

IP

TI

O

N

UNLESS OTHERWISE NOTED, LINEAR

DIMENSIONS SHOWN ARE IN MILLIMETERS.

PL

O

T D

AT

E:

FI

LE

N

AM

E:

US

A rm y

Co rp s of

E ng in ee rs M id dl e Ea st D is tri ct

C:\Users\n0enasl3\Documents\JR-474512A-A-DM-ATCT_AMD 03_n0enasl3.rvt

1/25/2022 11:30:37 AM

1/

/2

:3 0:

AM

A-606

FI

N

IS

H

S C

H

ED

U

LE

U D

.4

, J O

R D

AN

M

M C

M M

C

D H

-2

9-

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

(A

TC

T)

JR

-4

A

J.

R

AN

EY

, C H

IE

F

JR

-4

2A -A

-6

-0

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

W

IN

C H

ES

TE

R , V

A.

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

wtwt ROOM NAME FLOOR BASE

WALL FINISH

CEILING COMMENTSNORTH EAST SOUTH WEST

101 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS

102 ELEC SEALED CONC. RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED

103 MECH SEALED CONC. RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED

104 TOILET PFT-1 PB-1 PT-5 PT-5 PT-5 PT-5 GYP. / PT-5 USE EPOXY PAINT ON ALL WALLS AND CEILING

105 COMM SEALED CONC. RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED

106 ELEVATOR VCT-2 - - -- - -

108 INTERIOR LOBBY CPT-1 RB-1 PT-1 PT-1 PT-1 PT-1 ACT-1 SEE SHEET I-101 FOR ACCENT WALL LOCATIONS 109 EXTERIOR LOBBY VCT-1 RB-2 PT-2 PT-2 PT-2 PT-2 ACT-1 SEE SHEET I-101 FOR ACCENT WALL LOCATIONS & FLOOR PATTERNS 110 RAPCON CPT-2 RB-1 AWP-1 AWP-1 AWP-1 AWP-1 ACT-2 PROVIDE ACOUSTIC WALL PANELS (AWP-1), FROM TOP OF CONSOLE TO CEILING. ACCESS FLOOR SYSTEM

111 FIRE COMMAND SEALED CONC. RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED

201 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS 202 CONF CPT-1 RB-1 PT-1 PT-1 PT-1 PT-1 ACT-1 SEE SHEET I-101 FOR ACCENT WALL LOCATIONS

203 COMM/ELEC SEALED CONC. RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED

204 LOBBY CPT-1 RB-1 PT-1 PT-1 PT-1 PT-1 ACT-1 SEE SHEET I-101 FOR ACCENT WALL LOCATIONS

206 ELEVATOR VCT-1

301 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS

302 COMM/ELEC SEALED CONC. RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED

303 OFFICE CPT-1 RB-1 PT-1 PT-1 PT-1 PT-1 ACT-1 SEE SHEET I-102 FOR ACCENT WALL LOCATIONS

304 JANITOR PFT-1 PB-1 PT-5 PT-5 PT-5 PT-5 ACT-1

305 LOBBY CPT-1 RB-1 PT-1 PT-1 PT-1 PT-1 ACT-1 SEE SHEET I-102 FOR ACCENT WALL LOCATIONS

306 ELEV. VCT-1

401 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS 402 OFFICE CPT-1 RB-1 PT-1 PT-1 PT-1 PT-1 ACT-1 SEE SHEET I-102 FOR ACCENT WALL LOCATIONS

403 COMM/ELEC SEALED CONC. RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED

404 LOBBY CPT-1 RB-1 PT-1 PT-1 PT-2 PT-1 ACT-1 SEE SHEET I-102 FOR ACCENT WALL LOCATIONS 501 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS 502 MEN PFT-1 PB-2 CWT-1/CWT-3/PT-4 CWT-1/CWT-3/PT-4 CWT-1/CWT-3/PT-4 CWT-1/CWT-3/PT-4 GYP. / PT-5 FULL HEIGHT TILE @ SHOW. SS-1 COUNTER TOP. TP-1 TOILET PARTITIONS. EPOXY PAINT ON ALL SURFACE 503 MEN PFT-1 PB-1 CWT-1/CWT-2/PT-4 CWT-1/CWT-2/PT-4 CWT-1/CWT-2/PT-4 CWT-1/CWT-2/PT-4 GYP. / PT-5 FULL HEIGHT TILE @ SHOW. SS-1 COUNTER TOP. TP-1 TOILET PARTITIONS. EPOXY PAINT ON ALL SURFACE

504 COMM/ELEC SEALED CONC. RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED

505 WOMEN PFT-1 PB-1 CWT-1/CWT-2/PT-5 CWT-1/CWT-2/PT-5 PT-5 PT-5 GYP. / PT-5 USE EPOXY PAINT ON ALL WALLS AND CEILING

506 ELEV. VCT-1

507 LOBBY CPT-1 RB-1 PT-1 PT-1 PT-2 PT-1 ACT-1 SEE SHEET I-102 FOR ACCENT WALL LOCATIONS 601 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS 602 OFFICE CPT-1 RB-1 PT-1 PT-2 PT-1/ PT-2 PT-1 ACT-1 SEE SHEET I-102 FOR ACCENT WALL LOCATIONS

603 COMM/ELEC SEALED CONC. PB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED

604 LOBBY CPT-1 RB-1 PT-1 PT-1 PT-2 PT-1 ACT-1 SEE SHEET I-102 FOR ACCENT WALL LOCATIONS

606 ELEV. VCT-1

701 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS

702 OFFICE CPT-1 RB-1 PT-1 PT-2 PT-1/ PT-2 PT-1 ACT-1

703 COMM/ELEC SEALED CONC. PB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED

704 LOBBY CPT-1 RB-1 PT-1 PT-1 PT-2 PT-1 ACT-1 SEE SHEET I-103 FOR ACCENT WALL LOCATIONS

706 ELEV. VCT-1

801 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS

802 LOWER EQUIP RM VCT-4 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED

806 ELEV. VCT-1

810 LOBBY CPT-1 RB-1 PT-1 PT-1 PT-2 PT-1 ACT-1 SEE SHEET I-103 FOR ACCENT WALL LOCATIONS 901 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS 902 UPPER EQUIP RM. VCT-4 RB-2 WC-1 WC-1 WC-1 WC-1 EXPOSED SEE SHEET I-103 FOR FLOOR PATTERN 903 LOBBY CPT-1 RB-1 PT-1 PT-1 PT-2 PT-1 ACT-1 SEE SHEET I-103 FOR ACCENT WALL LOCATIONS

906 ELEV. VCT-1

1001 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS

1002 BREAK / READY RM VCT-1 RB-2 PT-1/P-2 PT-1/P-2 PT-1/ PT-2 PT-1/P-2 ACT-1

1003 TOILET PFT-1 PB-1 PT-5 PT-5 PT-5 PT-5 ACT-1

1005 LOBBY CPT-1 RB-1 PT-1 PT-1 PT-1 PT-2 ACT-1

1006 ELEV CTRL SEALED CONC. PB-1 PT-1 PT-1 PT-1 PT-1 GYP.

1101 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS

1102 MECH SEALED CONC. RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED

1103 TOILET PFT-2 PB-2 PT-5 PT-5 PT-5 PT-5 ACT-1 USE EPOXY PAINT ON ALL WALLS

1201 CONTROL CAB CPT-2 RB-1 PT-4 PT-4 PT-4 PT-4 ACT-2 PROVIDE RAISED ACCESS FLOOR 600 MM

1202 MGR AREA CPT-2 RB-1 PT-4 PT-4 PT-4 PT-4 ACT-2

1203 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS

R

EV

IS

ED

I. A

.W .A

M

EN

M

EN

T

JA

N

1. REFER TO COLOR AND MATERIAL SCHEDULE FOR ACCEPTABLE ALTERNATE

MANUFACTURERS. COLORS AND PATTERNS MUST CLOSELY MATCH BASIS OF

DESIGN AND BE SUBMITTED FOR APPROVAL.

2. THE METAL STAIRS SHALL BE PAINTED IN THE SAME COLOR AS THE HM DOOR

FRAMES.

NOTES:

3 3 3

MECH

FTEXTF

P,ER

S

75 0.5

MECH

TE

XT

LOC STAIRWAY

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E

File Path:

Plot Date:

M

AR

K D

ES

C

R

IP

TI

O

N

UNLESS OTHERWISE NOTED, LINEAR

DIMENSIONS SHOWN ARE IN MILLIMETERS.

PL

O

T D

AT

E:

FI

LE

N

AM

E:

US

A rm y

Co rp s of

E ng in ee rs M id dl e Ea st D is tri ct

X:\REVIT PROJECTS\JORDAN\2018\JR-474512 - Air Traffic Control Tower, MSAB, Jordan\JR-474512A - AIR TRAFFIC CONTROL TOWER\JR-474512A-F-DM-ATCT-03.rvt

1/12/2022 12:16:16 PM

1/

/2

:1 6:

PM

FA-106

EL

EV

EN

TH

A N

D C

AT

W

AL

K

FL

O

O R

F

IR

E

PR

O

TE

C

TI

O N

P

LA

N S

U D

.4

, J O

R D

AN

R

D

IP

ER

T

SD

O

ED

EN

G M

IC

H

AE

LS

FE

BR

U

AR

Y2

R

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

(A

TC

T)

JR

-4

A

T.

S

TE

PH

EN

SO

N , C

H

IE

F

JR

-4

2A -F

A-

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

W

IN

C H

ES

TE

R , V

A.

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

R

EV

IS

ED

I. A

.W .A

M

EN

D M

E N T

0 3

JA

N

1 : 502 CATWALK FIRE PROTECTION PLAN

1 : 501 ELEVENTH FLOOR FIRE PROTECTION PLAN

FROM FA/MNS

F

P

SFF

SECOND FLOOR

F P

S P

SMM

WF

CMEOL

THIRD & FOURTH FLOOR

(TYPICAL)

F P

S P

SMM

WF

EOL

FIFTH FLOOR

F P

S P

SMM

WF

CMEOL

SIXTH, SEVENTH

FLOOR (TYPICAL)

F P

S P

SMM

WF

NINTH FLOOR

HVAC

F P

S P

SMM

WF

EOL

TENTH FLOOR

F P

S P

SEOL

ELEVENTH FLOOR

F P

SEOL

CONTROL CAB & CATWALK

F P

SEOL

MMCMMMCMMMCMCM

MM

WF

CM

SOL

VALVE

ELEVATOR

CONTROL

,ER

FIRST FLOOR

EXTERIOR

ENCLOSURE

TO FA/MNS PANEL

FMM

FIRE PUMP

CONTROLLER

EOL SPD

SURGE

PROTECTION

DEVICE

MM

WF

MM

VT

MM

VT

MM

VT

MM

VT

MM

VT

MM MM MM

FIRE PUMP WATER

SUPPLY

VALVES

FIRE PUMP

ENCLOSURE

SPRINKLER

LOC

LOC RAA

TEXT TEXT MESSAGE

BLUE

BLUE INCANDESCENT LAMP

SILENCEABLE SPEAKER

~ ~ EOL

ELEVENTH FLOOR

CONTROL CAB & CATWALK

NAC SPEAKER CIRCUIT

~ ~ EOL

NAC SPEAKER CIRCUIT

SECOND THROUGH TENTH

FLOOR (TYPICAL)

FMCP

WP

WPWP

EOL

SPD

WP

NAC SPEAKER CIRCUIT

TEXT TEXT MESSAGE

LOC

LOC

LOC

LOC

LOC

LOC

LOC

LOC

P S

P

SFFMM

WF

MM

WF

MM

VT

MM

VT

EOL

P

S

EF-4

EOL

F

F

F P

S P

SMM

WF

EOL CM

EF-3

EIGHTH FLOOR

F

LOC

P S

TEXT TEXT MESSAGE

US Army Corps of Engineers ®

SHEET ID

US

A

RM

Y

CO

RP

S O

F

EN

G

IN

EE

RS

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E

File Path:

Plot Date:

M

AR

K D

ES

C

R

IP

TI

O

N

PL

O

T D

AT

E:

FI

LE

N

AM

E:

US

A rm y

Co rp s of

E ng in ee rs M id dl e Ea st D is tri ct

X:\REVIT PROJECTS\JORDAN\2018\JR-474512 - Air Traffic Control Tower, MSAB, Jordan\JR-474512A - AIR TRAFFIC CONTROL TOWER\JR-474512A-F-DM-ATCT-03.rvt

1/12/2022 12:13:41 PM

1/

/2

:1 3:

PM

FA-602

FI

R

E

AL

AR

M

R

IS

ER

D

IA

G

R

AM

U D

.4

, J O

R D

AN

R

D

IP

ER

T

SD

O

ED

EN

G M

IC

H

AE

LS

FE

BR

U

AR

Y2

R

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

(A

TC

T)

JR

-4

A

T.

S

TE

PH

EN

SO

N , C

H

IE

F

JR

-4

2A -F

A-

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

W

IN

C H

ES

TE

R , V

A.

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

NTS1 FIRE ALARM RISER DIAGRAM

R

EV

IS

ED

I. A

.W .A

M

EN

D M

E N T

0 3

JA

N

A

SYMBOL KEY

SEE SUMP PUMPM SCHEDULE

SHEET P-601

CONDUCTIVITY PROBE FOR

PUMP INTERRUPT IN CASE

OF HIGH OIL STORAGE

LEVEL IN SUMP. INCLUDES

BRACKET FOR

INSTALLATION ON PUMP

DISCHARGER.

FLOAT SENSOR FOR HIGH

SUMP LEVEL ALARM.

A

B

C

B

C

40MM DISCHARGE UP

ELEVATOR SHAFT.

SEE FLOOR PLAN ON

P-101 FOR

CONTINUATION.

ELEVATOR SHAFT

POWER AND

SENSOR WIRING

PUMP

INTERRUPT/

ALARM PANEL:

220V/1PH/ 50HZ.

LOCATE IN

MECHANICAL

ROOM.

50MM DISCHARGE TO

STANDPIPE DRAIN IN

MECHANICAL ROOM

NOTES:

SUMP SHALL HAVE A MANHOLE

COVER PER ELEVATOR CODE BY G.C.

COORDINATE PIPE ROUTING WITH

ARCHITECTURAL, STRUCTURAL, AND

ELEVATOR CONTRACCTOR.

CHECK VALVE

FF

ELECTRICAL PLUG

TO OUTLET.

RP-1-47, SEE DIV.

50MM DIA. TO STORM

DRAIN. SEE PLANS

MANHOLE COVER

SCALE: NTS

ELEVATOR SUMP PUMP DETAILH

SCALE:

POINT OF USE WATER HEATER DETAIL

NTS

SINK

ANGLE STOP

CW SUPPLY

WITH SHUT-OFF

VALVEWIRING BY DIV. 26

HW TO

FIXTURE

COUNTER TOP

CW TO

FIXTURE

I

FAUCET

EWH

MOUNTED UNDER

COUNTER PER

MANUFACTURERS

REQUIREMENTS

SCALE: NTS

WATER FILTER ASSEMBLY

PIPING DIAGRAMK

15CW SUPPLY TO

HVAC EQUIPMENT.

PROVIDE FINAL

CONNECTION TO UNIT.

WATER

FILTER/STRAINER IN-

LINE (T-LIINE) 595

MICRON (MAXIMUM)

UNION

(TYP)

NOTE:

ASSEMBLY TO BE LOCATED NEAR SERVED

EQUIPMENT.

PLUMBING CONTRACTOR TO COORDINATE WITH

MECHANICAL CONTRACTOR FOR FINAL

CONNECTIONS.

FROM COLD WATER MAIN.

SEE PLANS.

15CW

15CW

15CW

SCALE:

POINT OF USE WATER HEATER DETAIL EWH-1

NTS

WIRING BY DIV. 26

J

EWH

WALL MOUNTED PER

MANUFACTURERS

REQUIREMENTS

CW SUPPLY

WITH SHUT-OFF

VALVE

CW TO

ABOVE

HW SUPPLY

WITH SHUT-OFF

VALVE

HW TO

ABOVE

US Army Corps of Engineers ®

SHEET ID

US

A

R M

Y

CO

RP

S

O F

EN

G

IN

EE

RS

D

R

AW

N B

Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E

File Path:

Plot Date:

M

AR

K D

ES

C

R

IP

TI

O

N

UNLESS OTHERWISE NOTED, LINEAR

DIMENSIONS SHOWN ARE IN MILLIMETERS.

PL

O

T D

AT

E:

FI

LE

N

AM

E:

US

A rm y

Co rp s of

E ng in ee rs M id dl e Ea st D is tri ct

C:\Users\n0enmcc7\Documents\JR-474512A-P-DM-ATCT-03_n0enmcc7.rvt

1/18/2022 5:17:18 PM

1/

/2

5:

:1

PM

P-502

PL

U

M

BI

N G

D

ET

AI

LS

U D

.4

, J O

R D

AN

C

. C R

O

SB

IE

C . C

R O

SB

IE

K.

M

C

LE

LL

AN

FE

BR

U

AR

Y

R

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

(A

TC

T)

JR

-4

A

T.

S

TE

PH

EN

SO

N

JR

-4

2A -P

-5

-0

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

W

IN

C H

ES

TE

R , V

A.

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

R

EV

IS

ED

I. A

.W .A

M

EN

D M

EN

T

0 3

JA

N

1ST FLOOR

2ND FLOOR

3RD FLOOR

4TH FLOOR

5TH FLOOR

6TH FLOOR

8TH FLOOR

9TH FLOOR

10TH FLOOR

11TH FLOOR

CATWALK LEVEL

CAB LEVEL

P-7

P-6

P-14P-8

P-5

P-5

P-6 P-1

P-1 P-4

SEE DOMESTIC

WATER RISER

DIAGRAM C/P-501

CONNECT TO

50CW

FOR CONTINUATION

SEE CIVIL SITE FOR

CONTINUATION

BOOSTER PUMP

ASSEMBLY. SEE

DETAIL E/P-501

EWH-2

40CW 20CW

50CW

PRESSURE

REGULATOR. SEE

SCHEDULE AND DETAIL

ON THIS SHEET

(TYPICAL)

PV-3

PV-5

PV-6

EWH-7

50CW

32CW

32CW

25CW

SHUT-OFF VALVE

(TYPICAL)

20HW

20CW

15CW

20CW

20CW

15CW

50CW

MECHANICAL 1002

PV-7

ROUTE PIPING BELOW COUNTER

20CW

15HW

P-1

PDI-B

PDI-A

20CW TO WALL

HYDRANTS. SEE

PLAN ON P-204.

CHILLED WATER MAKE-

UP. SEE DETAIL D/P-501.

PV-9

PV-8

P-9 P-9 P-9

PDI-A

PDI-A

20CW

20CW20CW

CRAC UNIT #1

(BY OTHERS)

CRAC UNIT #2

(BY OTHERS)

CRAC UNIT #3

(BY OTHERS)

CRAC UNIT #4

(BY OTHERS)

FILTER ASSEMBLY.

SEE DETAIL

K/P-502. (TYP.)

COORDINATE FINAL

CONNECTION WITH

HVAC CONTRACTOR

(TYP)

7TH FLOOR

P-9

20CW

25CW20CW

20CW

32CWP-4

20CW

EWH-6EWH-5EWH-4

20CW

20CW

20CW

P-1

15CW

EWH-1

20HW

20CW

20CW15HW

PDI-B

P-8

PV-2

15CWEWH-3

WATER PRESSURE REDUCING STATION

NTS

PRESSURE REDUCING

VALVE. SEE THIS SHEET

FOR SCHEDULE, SIZES,

AND LOCATIONS.

PRESSURE GUAGE

BALL VALVE

UNION

PRESSURE GUAGE

BALL VALVE

UNION

STRAINER

SEE PLAN AND

RISER DIAGRAM

FOR PIPE SIZES

SEE PLAN AND

RISER DIAGRAM

FOR PIPE SIZES

NOTE: PRESSURE REDUCING STATION TO BE

MOUNTED ABOVE CEILING OR IN JANITORS

CLOSET CEILING.PROVIDE ACCESS AS

REQUIRED. ALL PRV'S SHALL BE DROP TIGHT TYPE.

US Army Corps of Engineers ®

SHEET ID

US

A

R M

Y

CO

RP

S

O F

EN

G

IN

EE

RS

D

R

AW

N B

Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E

File Path:

Plot Date:

M

AR

K D

ES

C

R

IP

TI

O

N

UNLESS OTHERWISE NOTED, LINEAR

DIMENSIONS SHOWN ARE IN MILLIMETERS.

PL

O

T D

AT

E:

FI

LE

N

AM

E:

US

A rm y

Co rp s of

E ng in ee rs M id dl e Ea st D is tri ct

C:\Users\n0enmcc7\Documents\JR-474512A-P-DM-ATCT-03_n0enmcc7.rvt

1/18/2022 5:18:03 PM

1/

/2

5:

:0

PM

P-902

H O

T

AN

D C

O

LD

W

AT

ER

S

YS

TE

M R

IS

ER

D

IA

G R

AM

U D

.4

, J O

R D

AN

C

. C R

O

SB

IE

C . C

R O

SB

IE

K.

M

C

LE

LL

AN

FE

BR

U

AR

Y

R

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

(A

TC

T)

JR

-4

A

T.

S

TE

PH

EN

SO

N

JR

-4

2A -P

-9

-0

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

W

IN

C H

ES

TE

R , V

A.

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

HOT AND COLD WATER

SYSTEM RISER DIAGRAM

NO SCALE

WATER PRESSURE REDUCING VALVE (PRV) SCHEDULE

TAG

PRESSURE REQUIREMENTS

INCOMING OUTGOING

PV-3 445 kPa

PV-5 310 kPa

FLOW RATE

LPM

MAX. VELOCITY

PV-6 275 kPa19

345 kPa

220 kPa

FALL OFF

(MAX)

62 kPa

PV-7 240 kPa45

PV-8 345 kPa11

PV-9 11 380 kPa

R

EV

IS

ED

I. A

.W .A

M

EN

D M

EN

T

0 3

JA

N

2.3 MPS

2.3 MPS

2.3 MPS

2.3 MPS

2.3 MPS

2.3 MPS

55 kPa

55 kPa

55 kPa 55 kPa

55 kPa 255 kPa

290 kPa 325 kPa

185 kPa

SIZE

MM

PV-2 480 kPa11 2.3 MPS 55 kPa425 kPa 15

J

FACP

M

X HP

M

LPB-24

FAAP

FSCP

ELECTRICAL LEGEND

ABBREVIATIONS

FIRE ALARM CONTROL PANELFACPFACP

CONDUIT CONCEALED WHERE POSSIBLE.

LP3-5,6

NON-FUSED DISCONNECT SWITCH; "30A" DENOTES SWITCH

AMPERE RATING. MOUNT 1.5M AFF

S

S3

SM

SD

S

S3

SM

SD

SPS

LCA

A

ABOVE FINISHED FLOOR

AMPERE

AMPERE INTERRUPTING CAPACITY

CKT CIRCUIT

CONDUITC

CND CONDUCTOR

EP EXPLOSION PROOF

ABOVE FINISHED GRADE

GFCI

HZ HERTZ

HPS HIGH PRESSURE SODIUM

HORSEPOWERHP

GFI

AIC

AFF

AFG

HH HANDHOLE

EF EXHAUST FAN

AHU AIR HANDLING UNIT

ACCU AIR COOLED CONDENSING UNIT

GROUND FAULT INTERRUPTING

GOVERNMENT FURNISHED CONTRACTOR

INSTALLED

FO FIBER OPTIC

CE CONCRETE ENCASED

KVA KILOVOLT-AMPERE

KV KILOVOLT

M METERS

MH

PHASE

V

SN

VOLT

SOLID NEUTRAL

WIRE

TRANSFORMER

TYPICALTYP.

PLCS PLACES

KW KILOWATT

W

UNLESS NOTED OTHERWISEUNO

WEATHERPROOFWP

RM ROOM

MTD MOUNTED

PH, 0

MANHOLE

XFMR,T

TBB TELEPHONE OR DATA BACKBOARD

W/

W/O WITHOUT

WITH

GENERAL NOTES:

INCH

EQUIVALENT CONDUIT SIZE

mm

JUNCTION BOX

GROUND CONDUCTOR

GROUND ROD

WELDED GROUND CONNECTION

CIRCUIT BREAKER

TRANSFORMER

G

MOTOR, NUMBER INDICATES HP UNO

PANELBOARD (LIGHTING & POWER)

3/4

2 1/2

1 1/2 1 1/4

MH MANHOLE

THREE-WAY SWITCH (SEE NOMENCLATURE FOR SINGLE POLE SWITCH).

MANUAL MOTOR RATED SWITCH WITH THERMAL PROTECTION; "P" DENOTES RED JEWEL PILOT LIGHT.

G

SINGLE POLE SWITCH, 277V, MOUNTED 1.2 A.F.F. (EXCEPT AS NOTED), "WP" DENOTES WEATHERPROOF

SEALED HEAD BATTERY POWERED EMERGENCY LIGHT

3 1/2

MH

HH

DIMMER SWITCH (RATING AS INDICATED)

HOMERUN TO PANELBOARD. SYMBOL SHOWN INDICATES CIRCUITS NO. 5 AND 6

PNL. LP3. NUMBER OF ARROWHEADS INDICATES NUMBER OF CIRCUITS.

DUAL VOLTAGE SHAVER RECEPTACLE, 120/240 VOLT OUTPUT (W/DOUBLE WOUND ISOLATING

TRANSFORMER

EXTERIOR WALL-MOUNTED LIGHT FIXTURE,TYPE AS INDICATED,

MOUNT 2.7M ABOVE GRADE UNO

BOLTED GROUND CONNECTION, HIDDEN WITHIN OR

UNDER EQUIPMENT

POLE MOUNTED EXTERIOR LIGHT FIXTURE

120V, DUPLEX RECEPTACLE, NEMA 5-20R (AMERICAN STYLE), MOUNT .5M AFF, UNO

FIRE ALARM CONTROL PANEL

HANDHOLE

SINGLE POLE SWITCH W/PILOT LIGHT

13A, 240V, SWITCHED DUPLEX RECEPTACLE (BSI STD) MOUNT 0.5 AFF UNO.

F SUBSCRIPT INDICATES FLOOR MOUNTED, FLUSH. D SUBSCRIPT INDICATES 240V, 32A,

SWITCHED FLEX RECEPTACLE, W SUBSCRIPT INDICATES SINGLE 13A, 240V SWITCHED

RECEPTACLE. G SUBSCRIPT INDICATES GROUND FAULT INTERRUPTING (GFI)

15KV NON-FUSED LOAD INTERRUPTER SWITCH

15KV FUSED LOAD INTERRUPTER SWITCH

NUMBER OF FIXTURES AS INDICATED

ROLL-UP MOTOR / DOOR OPERATOR

HV

SV

HIGH VOLTAGE CABLE IN CONCRETE

ENCASED DUCTBANK

SECONDARY VOLTAGE CABLE IN CONCRETE

ENCASED DUCTBANK

FIRE ALARM ANNUNICIATOR PANEL

DUPLEX FLOOR BOX MOUNTED RECEPTACLE WITH TELEPHONE

FOAM SYSTEM CONTROL PANEL

LIGHTING CONTACTOR 'A'

LED LIGHT FIXTURE, TYPE AS INDICATED, SEE LIGHT FIXTURE SCHEDULE

N = NIGHT LIGHT ON UN-SWITCHED CIRCUIT, HOME RUN

EXIT SIGN, TYPE AS INDICATED. SEE LIGHT FIXTURE SCHEDULE

LED LIGHT FIXTURE, TYPE AS INDICATED. SEE LIGHT FIXTURE SCHEDULE

LED LIGHT FIXTURE, TYPE AS INDICATE. SEE LIGHT FIXTURE SCHEDULE

CABLE COLOR CODE

BROWNPHASE A

PHASE B

PHASE C

NEUTRAL

GROUND

NOTE: VERIFY COLOR CODING TO

COMPLY WITH LOCAL STANDARDS

BLACK

GRAY

BLUE

YELLOW/GREEN

! WARNING

Shock and Arc Flash Hazard Appropriate PPE Required

ARC FLASH WARNING LABEL

32A, 2P + E, 250V, IP44 SURFACE MOUNTED

SOCKET OUTLET WITH MATCHING PLUG

FOR CLOTHES DRYER

N

250V, NEMA L6-30R RECEPTACLE

(ATTACHED TO CABLE TRAY)

P POLE

A

CROSS REFERENCE

AWG TO MM2

16 1.5 14 2.5 12 4.0 10 6.0 8 10 6 16 4 25 2 35 1 50 1/0 55 2/0 70 3/0 95 4/0 120

300MCM 150

350MCM 185

500MCM 240

600MCM 300

1. ELECTRIC LEGEND IS GENERIC. NOT ALL ITEMS NOTED ARE IN THE PROJECT.

2. FINAL CIRCUIT BREAKER SETTINGS SHALL BE PER CONTRACTOR DEVELOPED AND

COR APPROVED SYSTEM COORDINATION STUDY.

3. COORDINATE FINAL LOCATION OF LIGHT FIXTURES WITH MECHANICAL EQUIPMENT

AND COMMUNICATION RACKS IN THE ROOM.

4. ALL FLOOR MOUNTED ELECTRICAL EQUIPMENT SHALL BE INSTALLED ON CONCRETE

PADS, PROTRUDING 100mm AFF.

5. MEASURED GROUND RESISTANCE SHALL BE 25 OHMS OR LESS.

6. ALL ELECTRICAL EQUIPMENT SHALL BE DESIGNED AND TESTED TO OPERATE AT 380/220V, 3P, 4W, 50HZ.

7. GROUND RING SHALL BE 120mm SQ BARE COPPER, INSTALLED 760mm BELOW GRADE, UNO.

8. MOUNT LIGHT SWITCHES 1.2M AFF, UNO.

9. MOUNT RECEPTACLES:

ALL ADMINSTRATIVE AREAS - 0.5M AFF, UNO.

ALL INDUSTRIAL & SHOP AREAS - 1.2 AFF, UNO.

10. ALL CIRCUITS SHALL CONTAIN EQUIPMENT GROUND CONDUCTOR.

11. ALL ELECTRICAL INSTALLATION SHALL BE PER NATIONAL ELECTRIC CODE NFPA 70 (NEC).

12. ALL SERVICE ENTRANCE CONDUITS / DUCTS WITH CABLES SHALL BE SEALED AT BOTH ENDS WITH APPROPRIATE SEALER. ALL EMPTY CONDUITS SHALL BE CLEANED, PROVIDED WITH PULL-WIRE

AND CAPPED.

13. ALL PANEL SCHEDULES / DIRECTORIES SHALL BE TYPED WRITTEN IN ENGLISH AND SHALL BE COMPLETE.

14. ALL CONDUIT PENETRATIONS THRU FIRE RATED WALLS SHALL BE SEALED / FIRE STOPPED.

15. ALL ELECTRICAL PANELS IN ADDITTION TO SERVICE ENTRANCE EQUIPMENT (MDP) SHALL BE PROTECTED

WITH SURGE PROTECTIVE DEVICE (SPD).

16. EMERGENCY LIGHTS (BATTERY PACKS) AND EXIT SIGNS IN EACH AREA SHALL BE CONNECTED TO THE

UNSWITCHED LEG OF THE LIGHTING CIRCUIT OF THAT RESPECTIVE AREA.

17. ALL STAIRWELL LIGHTING SHALL BE FED FROM UN-SWITCHED CIRCUITS.

18. LIGHTNING PROTECTION SYSTEM SHALL BE PER NFPA 780.

19. FLOOR MOUNTED POWER RECEPTACLES SHALL BE INSTALLED WITHIN A COMMON FLOOR BOX

FOR THE COMMUNICATIONS RECEPTACLES AND INSTALLED LOCATION SHALL BE COORDINATED

WITH THE FURNITURE PLAN FOR THAT ROOM / AREA.

20. CONTRACTOR SHALL PROVIDE A PERMANENT STENCIL ON EVERY RECEPTACLE AND LIGHT SWITCH TO INDICATE THE CORRESPONDING PANELBOARD AND CIRCUIT BREAKER THAT DEVICE IS SERVICED FROM.

21. ALL EQUIPMENT, SUCH AS, MSBs, MCCs, MDPs SHALL BE PROVIDED WITH AMP, VOLT & KWH METERING.

22. ALL RECEPTACLES IN WET AREAS PER NEC SHALL BE PROTECTED WITH 30ma GFCIs.

23. ALL UNDERGROUND AND/OR UNDER SLAB GROUND WIRE/CABLE CONNECTIONS SHALL BE EXOTHERMIC WELD.

24. COMPLETE FIRE ALARM SYSTEM DESIGN SHALL BE DESIGNED AND DEVELOPED BY A REGISTERED FIRE PROTECTION ENGINEER AND IN COMPLIANCE WITH THE REQUIREMENTS OF THE FIRE ALARM

SPECIFICATIONS PROVIDED.

25. ALL EXTERIOR MOUNTED DEVICES AND JUNCTION BOXES SHALL BE NEMA TYPE 3, MIN OR EQUIVALENT IP RATED.

26. LIGHTING FIXTURE DETAILS ARE GENERIC AND FOR INFORMATION ONLY. OPERATING VOLTAGE RATING

AND LAMP WATTAGE SHALL COMPLY WITH THE DESIGN AND LOCAL VOLTAGE RATINGS.

27. MINIMUM SIZE CONDUIT SHALL BE 20 MM (3/4"), UNO.

28. ALL LIGHTING (INTERIOR & EXTERIOR) SHALL BE LED TYPE.

29. CIRCUIT BREAKERS 1000 A AND LARGER SHALL BE PROVIDED WITH GROUND FAULT PROTECTION PER NEC.

30. PROVIDE CABLE COLOR CODE LABEL IN EACH MDP/SWITCHBOARD/PANEL.

31. PROVIDE ARC FLASH WARNING LABEL AT EACH MDP/SWITCHBOARD/PANEL.

32. WITH USE OF 4 POLE ATS GENERATOR NEUTRAL SHALL BE GROUNDED AT THE GENERATOR (SOURCE).

33. ALL ELECTRICALLY OPERATED MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH DISCONNECT SWITCH IN

COMPLIANCE WITH NEC REQUIREMENTS.

US Army Corps of Engineers ®

SHEET ID

US

A

R M

Y C

O

RP

S O

F

EN

G

IN

EE

RS

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E

File Path:

Plot Date:

M

AR

K D

ES

C

R

IP

TI

O

N

UNLESS OTHERWISE NOTED, LINEAR

DIMENSIONS SHOWN ARE IN MILLIMETERS.

PL

O

T D

AT

E:

FI

LE

N

AM

E:

US

A rm y

Co rp s of

E ng in ee rs M id dl e Ea st D is tri ct

C:\Users\N0ENFSCD\Documents\JR-474512A-E-DM-ATCT-03_N0ENFSCD.rvt

1/7/2022 10:32:33 AM

1/ 7/

:3

2:

AM

E-001

G

EN

ER

AL

L

EG

EN

D

A N

D A

BB

R

EV

IA

TI

O

N S

U D

.4

, J O

R D

AN

SE

N

AY

AT

U

LL

A

SD

O

ED

EN

M M

O

ST

AG

H

IM

FE

BR

U

AR

Y2

R

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

(A

TC

T)

JR

-4

A

T.

S

TE

PH

EN

SO

N , C

H

IE

F

JR

-4

2A -E

-0

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

W

IN

C H

ES

TE

R , V

A.

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

R

EV

IS

E D I.A

.W .A

M

EN

D M

EN

T

JA

N

NOTES:

1. EXISTING ATCT: EXISTING JORDAN AIR FORCE (JAF) ATCT

SHALL REMAIN IN SERVICE, AS A BACK-UP TO THE NEW

ATCT, EVEN AFTER THE NEW ATCT BECOMES OPERATIONAL.

2. RADAR APPROACH CONTROL (RAPCON): DATA FROM

EXISTING ON-BASE RAPCON ARE RECEIVED AT THE

EXISTING JAF ATCT. CONTRACTOR SHALL BE RESPONSIBLE

TO PROVIDE AND INSTALL NECESSARY CABLES (COPPER

OR OPTIC FIBER) FROM THE EXISTING ATCT TO THE NEW

ATCT, IN ORDER TO DUPLICATE RAPCON DATA AT THE NEW

ATCT. CONTRACTOR IS EXPECTED TO USE EXISTING

AIRFIELD LIGHTING (AFL) CONTROL CABLE RACEWAY

(DUCTBANK) SYSTEM, WHICH CONNECTS ALL FOUR AFL

VAULTS (A, B, C, AND D) TO THE EXISTING ATCT,

COMMUNICATION DUCTBANK SYSTEM PROVIDED UNDER

UD 2.4-PACKAGE 2 (FLIGHTLINE) PROJECT AND THE NEW

COMMUNICATIONS DUCTBANK SYSTEM BEING PROVIDED

UNDER THIS CONTRACT. CONTRACTOR SHALL BE

RESPONSIBLE TO ENSURE THAT RAPCON DATA BEING

RECEIVED AT JAF ATCT IS ALSO RECEIVED AT THE NEW

ATCT, ACCEPTABLE TO US AIRFORCE ATCT OPERATORS.

3. AFL CONTROL CABLE: EXISTING FIBER OPTIC AFL CONTROL

CABLES CONNECT ALL FOUR AFL VAULTS (A, B, C, AND D)

TO MIMIC PANEL(S) ATJAF ATCT. CONTRACTOR SHALL BE

RESPONSIBLE TO PROVIDE AND INSTALL FIBER OPTIC AFL

CONTROL CABLE CONNECTING VAULTS A, B, C, AND D TO

A NEW AIRPORT LIGHTING CONTROL AND MONITORING

SYSTEM (ALCMS) PANEL AT THE NEW ATCT. EXISTING

AFL CONTROLS AND DISPLAYS AT JAF ATCT SHALL REMAIN

OPERATIONAL AND WOULD BE CONSIDERED AS BACK-UP

TO THE ALCMS AT THE NEW ATCT.

4. AIRPORT LIGHTING CONTROL AND MONITORING SYSTEM

(ALCMS) FAA L-890 PANEL: CONTRACTOR SHALL PROVIDE

AND INSTALL AN ADVANCE MONITORING, TOUCH SCREEN,

PLUG AND PLAY STATE OF THE ART ALCMS INSIDE THE ATCT

CAB. ALCMS SHALL DISPLAY ALL FEATURES ASSOCIATED

WITH THE UD 2.4 AIRFIELD, TO INCLUDE BUT NOT LIMITED TO,

BOTH RUNWAYS, ASSOCIATED TAXIWAYS AND APRONS.

UNIT SHALL BE PROGRAMMABLE, BE ABLE TO DISPLAY

EXISTING AND FUTURE AIRFIELD EXPANSION. ALCMS

DISPLAY SHALL BE MIN, 36 INCH (DIAGONAL). SYSTEM

SHALL COMPRISE OF COMMERCIALLY AVAILABLE, NON-

PROPRIETARY COMPONENTS. CONTRACTOR SHALL BE

RESPONSIBLE FOR PROVIDING COMPLETE AND USABLE

SYSTEM.

5. BEACON: EXISTING UD 2.4 AIRFIELD BEACON IS LOCATED

ON THE ROOF OF JAF ATCT AND SHALL REMAIN IN PLACE

AND OPERATIONAL. CONTRACTOR SHALL BE RESPONSIBLE

FOR EXTENDING BEACON CONTROLS FROM JAF ATCT TO

THE NEW ATCT CAB UTILIZING EXISTING AND NEW

COMMUNICATION RACEWAY SYSTEM BETWEEN THE TWO

ATCTS. BEACON SHALL BE ABLE TO BE OPERATED

(CONTROLLED) FROM JAF AND THE NEW ATCT.

US Army Corps of Engineers ®

SHEET ID

US

A

R M

Y C

O

RP

S O

F

EN

G

IN

EE

RS

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E

File Path:

Plot Date:

M

AR

K D

ES

C

R

IP

TI

O

N

UNLESS OTHERWISE NOTED, LINEAR

DIMENSIONS SHOWN ARE IN MILLIMETERS.

PL

O

T D

AT

E:

FI

LE

N

AM

E:

US

A rm y

Co rp s of

E ng in ee rs M id dl e Ea st D is tri ct

C:\Users\N0ENFSCD\Documents\JR-474512A-E-DM-ATCT-03_N0ENFSCD.rvt

1/12/2022 4:52:46 PM

1/

/2

4:

:4

PM

E-002

G

EN

ER

AL

N O

TE

S

U D

.4

, J O

R D

AN

SE

N

AY

AT

U

LL

A

SD

O

ED

EN

M M

O

ST

AG

H

IM

FE

BR

U

AR

Y2

R

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

(A

TC

T)

JR

-4

A

T.

S

TE

PH

EN

SO

N , C

H

IE

F

JR

-4

2A -E

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

W

IN

C H

ES

TE

R , V

A.

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

R

EV

IS

E D I.A

.W .A

M

EN

D M

EN

T

JA

N

FD

S

MS

M

J J

J

ATS

MDP

FCU-1.2

FCU-1.1

CU-1

EF-1

EF-2DOMESTIC WATER

BOOSTER PUMP

LP1-7

LP

T

LP1-9

LP1-11

LP1-30

LP1-28

MDP-10

LP1-26

LP1-15

LP1-13

LP13-2 LP13-4

LP13-6

LP13-8

FA

C

P

LP13

INSTALL 2-50mm EMPTY CONDUITS

WITH PULL WIRE FROM PANEL TO

BELOW RAISED FLOOR.

LP13-10

MDP-11

LP

MDP-3

MECH

ELEC

INTERIOR

LOBBY

STAIR

TOILET

EXTERIOR

LOBBY

RAPCON

FIRE

COMMAND

LP1-27

LP13-11

LP1-29

LP13-14

LP13-9

LP1-17

EWH-2

LP13-12

(MT. 0.5M

BELOW CEILING)

CCTV

P-1, P-2

LP1-14LP1-20

M

LP1-19

SP-1

SERVICE

ENTRANCE

CIRCUIT BREAKER

A

A

B

B

RECESSED

PULL BOX

WITH HINDGED

COVER (TYP 2)

E-108

E-108

Sim

C D

LP13

RACU-1

RACU-2

LP13-20

LP1-35

LP1-33

LP1-31

WH-3

WH-2

WH-1

ELEV

COMM

DOOR STRIKE

PWR. MT. ABOVE

CEILING. TYP 3 LOC.

FCU-2 SPF-1

LP2

LP2-2

LP3-1

LP2-4

LP2-8

LP2-7

CONF

LOBBY

STAIR

COMM/ELEC

A B

C D

ELEV

FIRST FLOOR

SECOND FLOOR

DROP CEILING

RAISED FLOOR

4-50mm EMPTY CONDUITS

WITH PULL WIRE

(TYP TOP AND BOTTOM)

PULL BOX NOTE:

INSTALL RECESSED PULL BOX WITH HINDGED

COVER 600mm H, 400mm W, 100mm DEEP, 1.5M AFF.

PROVIDE 4-50mm EMPTY CONDUITS RUNS TO ABOVE

DROP CEILING AND BELOW RAISED FLOOR.

US Army Corps of Engineers ®

SHEET ID

US

A

R M

Y C

O

RP

S O

F

EN

G

IN

EE

RS

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E

File Path:

Plot Date:

M

AR

K D

ES

C

R

IP

TI

O

N

UNLESS OTHERWISE NOTED, LINEAR

DIMENSIONS SHOWN ARE IN MILLIMETERS.

PL

O

T D

AT

E:

FI

LE

N

AM

E:

US

A rm y

Co rp s of

E ng in ee rs M id dl e Ea st D is tri ct

C:\Users\N0ENFSCD\Documents\JR-474512A-E-DM-ATCT-03_N0ENFSCD.rvt

1/12/2022 1:38:19 PM

1/

/2

1:

:1

PM

E-108

FI

R

ST

A

N D

S

EC

O N

D F

LO

O

R P

O W

ER

P

LA

N

S

U D

.4

, J O

R D

AN

SE

N

AY

AT

U

LL

A

SD

O

ED

EN

M M

O

ST

AG

H

IM

FE

BR

U

AR

Y2

R

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

(A

TC

T)

JR

-4

A

T.

S

TE

PH

EN

SO

N , C

H

IE

F

JR

-4

2A -E

-1

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

W

IN

C H

ES

TE

R , V

A.

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

1 : 501 FIRST FLOOR POWER PLAN

1 : 502 SECOND FLOOR POWER PLAN

N.T.S.3 PULL BOX SECTION

1:50

5m1m 4m3m2m0m

R

EV

IS

E D I.A

.W .A

M

EN

D M

EN

T

JA

N

LP11-4

LP11-6

MDP-8

LP11 LP11-2

MECH

LP11-8

DOAU-1

AHU-1

AHU-2

STACKED

UNITS

LP11-20 LP11-14 LP11-11

EF-7

A B

C D

M Sw

M Sw

LP11-26

EF

-8

M Sw

LP11-28

EF-5

STAIRWAY

MECH

LP12

A B

LP12-6

LP12-17 CCTV

C D

MDP-9DOOR STRIKE

PWR. MT. ABOVE

DOOR HEIGHT

US Army Corps of Engineers ®

SHEET ID

US

A

R M

Y C

O

RP

S O

F

EN

G

IN

EE

RS

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E

File Path:

Plot Date:

M

AR

K D

ES

C

R

IP

TI

O

N

UNLESS OTHERWISE NOTED, LINEAR

DIMENSIONS SHOWN ARE IN MILLIMETERS.

PL

O

T D

AT

E:

FI

LE

N

AM

E:

US

A rm y

Co rp s of

E ng in ee rs M id dl e Ea st D is tri ct

C:\Users\N0ENFSCD\Documents\JR-474512A-E-DM-ATCT-03_N0ENFSCD.rvt

1/12/2022 1:54:00 PM

1/

/2

1:

:0

PM

E-113

EL

EV

EN

TH

F

LO

O R

A N

D B

AL

C

O N

Y

PO

W

ER

P

LA

N S

U D

.4

, J O

R D

AN

SE

N

AY

AT

U

LL

A

SD

O

ED

EN

M M

O

ST

AG

H

IM

FE

BR

U

AR

Y2

R

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

(A

TC

T)

JR

-4

A

T.

S

TE

PH

EN

SO

N , C

H

IE

F

JR

-4

2A -E

-1

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

W

IN

C H

ES

TE

R , V

A.

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

1 : 501 ELEVENTH FLOOR POWER PLAN

1 : 502 BALCONY POWER PLAN

1:50

5m1m 4m3m2m0m

R

EV

IS

E D I.A

.W .A

M

EN

D M

EN

T

JA

N

ATCT ELECTRIC ROOM 1ST FLOOR (RM. 102)

250AT

400 AF

250AT

400 AF

60AT

100AF

80AT

100 AF

80AT

100 AF

2000A,380/220V, 3 PH, 4W, 50 HZ, 30,000 AIC BUS

1 2 3 4 5

CH-1 CH-2 LP1

(1ST

FLOOR)

LP3

(3RD

FLOOR)

TOTAL EST. CONN. LOAD : 715.2 KVA

TOTAL EST. DEM. LOAD : 643.7 KVA

150AT

225 AF

6 7 8

LP8

(8TH

FLOOR)

LP6

(6TH

FLOOR)

9 10 11 12 13

SP

AC

E

LP9

(9TH

FLOOR)

LP11

11TH

FLOOR)

LP12

(CAB)

LPT

(COMM

1ST

FLOOR)

LP13

CONF.

ROOM

(1 ST

FLOOR)

100AT

125 AF

14 15 16

1400AT

2000 AF

A B C D E F G H I J K

200AT

225 AF

175AT

225 AF

50AT

100 AF

40AT

100 AF

SPD

NOTE 2

G

TO UDS T3-11

(1000KVA,

11KV - 380/220V,

3P, 4W, 50HZ)

GENERATOR (STAND-BY)

750 KVA,380/220V, 3 P,4W, 50HZ

SKID MOUNTED, WEATHERPROOF

ENCLOSURE WITH DAY TANK

LP2

(2ND

FLOOR)

(14.6 KVA)

LP4

(4TH

FLOOR)

(14.4 KVA)

LP5

(5TH

FLOOR)

(15.7 KVA)

LP10

(10TH

FLOOR)

(12.6 KVA)

ATS

4P- 1600A

(RM. 102)

400A

NEMA 3

(142 KVA)

400A

NEMA 3

(142 KVA)

LP7

(7TH

FLOOR)

(10.6 KVA)

LOWER

EQUIPT.

ROOM

UPPER

EQUIPT.

ROOM

RAPCON

1500AT

2000 AF

MAIN DISTRIBUTION PANEL (MDP)

(SWITCHBOARD)

4 SETS:

(4-240MM SQ +

1-120MM SQ G

IN 4-103MM C

+ 2-103MM C SPARE)

4-16MM SQ +1 -6MM

SQ G IN 27MM C

4-10MM SQ + 1-6MM

SQ G IN 20MM C

4-10MM SQ + 1-6MM

SQ G IN 20MM C

4-10MM SQ + 1-6MM

SQ G IN 20MM C

4-10MM SQ + 1-6MM

SQ G IN 20MM C

VD

.0

VD

.0

VD

.2

SP

AC

E

SP

AC

E

SP

AC

E

SP

AC

E

NOTE 6

NOTE 7

MDP FEEDER CABLE SCHEDULE

FDR # EQUIP. CABLE AND CONDUIT SIZE

A

B

C

D

E

F

G

H

I

J

K

CH-1 3-240MM SQ + 1-25MM SQ G IN 103MM C

CH-2 3-240MM SQ + 1-25MM SQ G IN 103MM C

LP1 4-35MM SQ +1-10MM SQ G IN 35MM C

LP3 4-35MM SQ +1-10MM SQ G IN 35MM C

LP6

LP8

LP9

LP11

LP12

LP-T

LP13

4-35MM SQ +1-10MM SQ G IN 35MM C

4-70MM SQ +1-25MM SQ G IN 53MM C

4-150MM SQ +1-25MM SQ G IN 78MM C

4-120MM SQ +1-16MM SQ G IN 63MM C

4-25MM SQ +1-6MM SQ G IN 35MM C

4-10MM SQ +1-6MM SQ G IN 20MM C

4-55MM SQ +1-16MM SQ G IN 53MM C

35.5

35.8

31.6

52.0

90.2

65.8

28.5

9.6

54.8

DEM

KVA

US Army Corps of Engineers ®

SHEET ID

US

A

R M

Y C

O

RP

S O

F

EN

G

IN

EE

RS

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E

File Path:

Plot Date:

M

AR

K D

ES

C

R

IP

TI

O

N

UNLESS OTHERWISE NOTED, LINEAR

DIMENSIONS SHOWN ARE IN MILLIMETERS.

PL

O

T D

AT

E:

FI

LE

N

AM

E:

US

A rm y

Co rp s of

E ng in ee rs M id dl e Ea st D is tri ct

C:\Users\N0ENFSCD\Documents\JR-474512A-E-DM-ATCT-03_N0ENFSCD.rvt

1/7/2022 10:44:39 AM

1/ 7/

:4

4:

AM

E-602

O N

E

LI

N E

D

IA

G R

AM

U D

.4

, J O

R D

AN

SE

N

AY

AT

U

LL

A

SD

O

ED

EN

M M

O

ST

AG

H

IM

FE

BR

U

AR

Y2

R

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

(A

TC

T)

JR

-4

A

T.

S

TE

PH

EN

SO

N , C

H

IE

F

JR

-4

2A -E

-6

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

W

IN

C H

ES

TE

R , V

A.

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

N.T.S.1 POWER ONE LINE DIAGRAM

NOTES:

1. REFER TO SHEET E-001 FOR LEGEND AND GENERAL NOTES.

2. INSTALL SPD PER MANUFACTURERS INSTRUCTIONS.

3. INSTALL ARC FLASH HAZARD SIGN ON OUTSIDE OF MDP.

4. MDP SHALL BE PROVIDED WITH KWH METERING TO INCLUDE

VOLTMETER, AMPMETER, POWER FACTOR METER, WATT METER

AND WATT HOUR METER.

5. PROVIDE FRAMED MDP ONE LINE DIAGRAM IN ELECTRIC ROOM.

6. CONTRACTOR'S OPTION: SERVICE ENTRANCE RATED ATS WITH

BUILT-IN CIRCUIT BREAKER MAY BE PROVIDED IN PLACE OF A

SEPARATE CIRCUIT BREAKER, PROVIDED IT COMPLIES WITH MEANS

OF DISCONNECT REQUIREMENTS PER NEC.

7. PROVIDE ARC FLASH REDUCTION PER NFPA 70, ART 240.87.

R

EV

IS

E D I.A

.W .A

M

EN

D M

EN

T

JA

N

C

KT

N

O

. TRIP

AMPS

N O

PO

LE

S

LOAD SERVED LOAD-V.A.

A0 B0 C0

LOAD-V.A.

A0 B0 C0

LOAD SERVED

PANELBOARD MOUNTED

AMP. MAIN LUGS (OR) AMP. TRIP

CIRCUIT BREAKER TYPE VOLTS PHASE WIRE

TOTAL CONN. LOAD KVA. % DEMAND = ESTIMATED DEMAND LOAD

TOTAL CONN. LOAD

PER PHASE (KVA): A0 B0 C0

WIRE

MM²

CONDUIT

MM C

KT

N O

.TRIP

AMPS

N O

PO

LE

SWIRE

MM²

CONDUIT

MM

GND

MM²

AMP. BUS

GND

MM²

HZ

SYM. A.I.C. MIN.

SUPPLIED FROM:KVA

AMP. MAIN BREAKER W/

WALL

380/220 3 4 50

350 16 6 27

3RD FLOOR

MDP

10,000LP3

LP2 (2ND FLOOR)

LIGHTING120 4 4 20

LIGHTING120 4 4 20

LIGHTING120 4 4 20

EWH-3130 6 6 20

LP4 (4TH FLOOR)

RECEPTACLES (303)

RECEPTACLES (103)

RECEPTACLES (TOILET)

FCU-3

420 4 1 20

420 4 1 20

420 4 1 20

620 6 1 30

SPARE 1 20_ _ _2000

2000 SPARE 1 20_ _ _

SPARE

SPARE

47.5 80

8516 7166 7366 9000 7600 7000

38.0

18.3 14.8 14.4

20 6 10 3 30

SPACE SPACE

C

KT

N

O

. TRIP

AMPS

N O

PO

LE

S

LOAD SERVED LOAD-V.A.

A0 B0 C0

LOAD-V.A.

A0 B0 C0

LOAD SERVED

PANELBOARD MOUNTED

AMP. MAIN LUGS (OR) AMP. TRIP

CIRCUIT BREAKER TYPE VOLTS PHASE WIRE

TOTAL CONN. LOAD KVA. % DEMAND = ESTIMATED DEMAND LOAD

TOTAL CONN. LOAD

PER PHASE (KVA): A0 B0 C0

WIRE

MM²

CONDUIT

MM C

KT

N O

.TRIP

AMPS

N O

PO

LE

SWIRE

MM²

CONDUIT

MM

GND

MM²

AMP. BUS

GND

MM²

HZ

SYM. A.I.C. MIN.

SUPPLIED FROM:KVA

AMP. MAIN BREAKER W/

WALL

380/220 3 4 50

120 4 4 20

2ND FLOOR

LP3

10,000LP2

120 4 4 20

LIGHTING

LIGHTING

LIGHTING120 4 4 20

SFP-1

1200 RECEPTACLES

RECEPTACLES

RECEPTACLES

FCU-2

20 204 4 1

20 204 4 1

20 204 4 1

20 306 6 120 4 4 20 1000

SPARE2000

2000 SPARE

SPARE_ _ _ 2000

SPARE_ _ _

SPARE_ _ _

21.1 80

3150 3600 3450 5200 2800 2800

16.9

8.4 6.4 6.3

SPACE

SPACE

US Army Corps of Engineers ®

SHEET ID

US

A

R M

Y C

O

RP

S O

F

EN

G

IN

EE

RS

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E

File Path:

Plot Date:

M

AR

K D

ES

C

R

IP

TI

O

N

UNLESS OTHERWISE NOTED, LINEAR

DIMENSIONS SHOWN ARE IN MILLIMETERS.

PL

O

T D

AT

E:

FI

LE

N

AM

E:

US

A rm y

Co rp s of

E ng in ee rs M id dl e Ea st D is tri ct

C:\Users\N0ENFSCD\Documents\JR-474512A-E-DM-ATCT-03_N0ENFSCD.rvt

1/7/2022 10:45:33 AM

1/ 7/

:4

5:

AM

E-605

PA

N

EL

S

C H

ED

U

LE

S

U D

.4

, J O

R D

AN

SE

N

AY

AT

U

LL

A

SD

O

ED

EN

M M

O

ST

AG

H

IM

FE

BR

U

AR

Y2

R

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

(A

TC

T)

JR

-4

A

T.

S

TE

PH

EN

SO

N , C

H

IE

F

JR

-4

2A -E

-6

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

W

IN

C H

ES

TE

R , V

A.

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

R

EV

IS

E D I.A

.W .A

M

EN

D M

EN

T

JA

N

C

KT

N

O

. TRIP

AMPS

N O

PO

LE

S

LOAD SERVED LOAD-V.A.

A0 B0 C0

LOAD-V.A.

A0 B0 C0

LOAD SERVED

PANELBOARD MOUNTED

AMP. MAIN LUGS (OR) AMP. TRIP

CIRCUIT BREAKER TYPE VOLTS PHASE WIRE

TOTAL CONN. LOAD KVA. % DEMAND = ESTIMATED DEMAND LOAD

TOTAL CONN. LOAD

PER PHASE (KVA): A0 B0 C0

WIRE

MM²

CONDUIT

MM C

KT

N O

.TRIP

AMPS

N O

PO

LE

SWIRE

MM²

CONDUIT

MM

GND

MM²

AMP. BUS

GND

MM²

HZ

SYM. A.I.C. MIN.

SUPPLIED FROM:KVA

AMP. MAIN BREAKER W/

WALL

380/220 3 4 50

120 4 4 20

4TH FLOOR

LP3

10,000LP4

120 4 4 20

120 4 4 20

LIGHTING

LIGHTING

LIGHTING

SPF-2

1000 RECEPTACLES

RECEPTACLES

RECEPTACLES

FCU-4

20 204 4 1

20 204 4 1

20 204 4 1

20 306 6 120 4 4 20 1000

SPARE

SPARE

SPARE

SPARE

SPARE120

20.8 80

3150 3250 3450 5000 2800 3000

16.6

8.2 6.1 6.5

SPACE

SPACE

C

KT

N

O

. TRIP

AMPS

N O

PO

LE

S

LOAD SERVED LOAD-V.A.

A0 B0 C0

LOAD-V.A.

A0 B0 C0

LOAD SERVED

PANELBOARD MOUNTED

AMP. MAIN LUGS (OR) AMP. TRIP

CIRCUIT BREAKER TYPE VOLTS PHASE WIRE

TOTAL CONN. LOAD KVA. % DEMAND = ESTIMATED DEMAND LOAD

TOTAL CONN. LOAD

PER PHASE (KVA): A0 B0 C0

WIRE

MM²

CONDUIT

MM C

KT

N O

.TRIP

AMPS

N O

PO

LE

SWIRE

MM²

CONDUIT

MM

GND

MM²

AMP. BUS

GND

MM²

HZ

SYM. A.I.C. MIN.

SUPPLIED FROM:KVA

AMP. MAIN BREAKER W/

WALL

380/220 3 4 50

5TH FLOOR

LP6

10,000LP5

120 4 4 20

120 4 4 20

120 4 4 20

LIGHTING

LIGHTING

LIGHTING

FCU-5

600 RECEPTACLES

RECEPTACLES

RECEPTACLES

EWH-1

20 204 4 1

20 204 4 1

20 204 4 1

27 506 16 3

120 4 4 20 3200

RECEPTACLES 20 204 4 1

SPARE120

SPARE120

_ _2000

SPARE

SPARE

40.6 80

3350 2300 2300 10200 11200 11200

32.5

13.6 13.5 13.5

SPACE

SPACE

US Army Corps of Engineers ®

SHEET ID

US

A

R M

Y C

O

RP

S O

F

EN

G

IN

EE

RS

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E

File Path:

Plot Date:

M

AR

K D

ES

C

R

IP

TI

O

N

UNLESS OTHERWISE NOTED, LINEAR

DIMENSIONS SHOWN ARE IN MILLIMETERS.

PL

O

T D

AT

E:

FI

LE

N

AM

E:

US

A rm y

Co rp s of

E ng in ee rs M id dl e Ea st D is tri ct

C:\Users\N0ENFSCD\Documents\JR-474512A-E-DM-ATCT-03_N0ENFSCD.rvt

1/7/2022 10:46:21 AM

1/ 7/

:4

6:

AM

E-606

PA

N

EL

S

C H

ED

U

LE

S

U D

.4

, J O

R D

AN

SE

N

AY

AT

U

LL

A

SD

O

ED

EN

M M

O

ST

AG

H

IM

FE

BR

U

AR

Y2

R

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

(A

TC

T)

JR

-4

A

T.

S

TE

PH

EN

SO

N , C

H

IE

F

JR

-4

2A -E

-6

M

ID

D

LE

E

AS

T D

IS

TR

IC

T

W

IN

C H

ES

TE

R , V

A.

AI

R

T R

AF

FI

C C

O N

TR

O

L

TO

W

ER

R

EV

IS

E D I.A

.W .A

M

EN

D M

EN

T

JA

N

C

KT

N

O

. TRIP

AMPS

N O

PO

LE

S

LOAD SERVED LOAD-V.A.

A0 B0 C0

LOAD-V.A.

A0 B0 C0

LOAD SERVED

PANELBOARD MOUNTED

AMP. MAIN LUGS (OR) AMP. TRIP

CIRCUIT BREAKER TYPE VOLTS PHASE WIRE

TOTAL CONN. LOAD KVA. % DEMAND = ESTIMATED DEMAND LOAD

TOTAL CONN. LOAD

PER PHASE (KVA): A0 B0 C0

WIRE

MM²

CONDUIT

MM C

KT

N O

.TRIP

AMPS

N O

PO

LE

SWIRE

MM²

CONDUIT

MM

GND

MM²

AMP. BUS

GND

MM²

HZ

SYM. A.I.C. MIN.

SUPPLIED FROM:KVA

AMP. MAIN BREAKER W/

WALL

380/220 3 4 50

6TH FLOOR

MDP

10,000LP6

A0

120 4 4 20

120 4 4 20

LP5 (5TH FLOOR)

LIGHTING

LIGHTING

LP7 (7TH FLOOR)

RECEPTACLES

RECEPTACLES

SPARE

20 204 4 1

20 204 4 1

_ 20120 4 4 20 LIGHTING

130 6 6 20 FCU-6

SPARE

SPARE

10833 3533

10833

10833

SPARE2000 _ _

59.1 80

12183 13083 13283 5733 5533 6533

47.3

20.7 18.6 19.8

35 10 6 20

20 6 10 40

SPACE SPACE

SPARE

SPARE

C

KT

N

O

. TRIP

AMPS

N O

PO

LE

S

LOAD SERVED LOAD-V.A.

A0 B0 C0

LOAD-V.A.

A0 B0 C0

LOAD SERVED

PANELBOARD MOUNTED

AMP. MAIN LUGS (OR) AMP. TRIP

CIRCUIT BREAKER TYPE VOLTS PHASE WIRE

TOTAL CONN. LOAD KVA. % DEMAND = ESTIMATED DEMAND LOAD

TOTAL CONN. LOAD

PER PHASE (KVA): A0 B0 C0

WIRE

MM²

CONDUIT

MM C

KT

N O

.TRIP

AMPS

N O

PO

LE

SWIRE

MM²

CONDUIT

MM

GND

MM²

AMP. BUS

GND

MM²

HZ

SYM. A.I.C. MIN.

SUPPLIED FROM:KVA

AMP. MAIN BREAKER W/

WALL

380/220 3 4 50

7TH FLOOR

LP6

10,000LP7

A0

120 4 4 20

120 4 4 20

120 4 4 20

LIGHTING

LIGHTING

LIGHTING

RECEPTACLES

RECEPTACLES

RECEPTACLES

20 204 4 1

20 204 4 1

20 204 4 1

120 4 4 20 LIGHTING

201___SPARE500

201___SPARE

201___SPARE

FCU-7

SPARE___

15.2 80

650 4250 2450 1700 3000 3000

12.2

2.4 7.3 5.5

6 6 20

SPACE SPACE

US Army Corps of Engineers ®

SHEET ID

US

A

R M

Y C

O

RP

S O

F

EN

G

IN

EE

RS

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

G

2 3 4 5 6 7 8 9 10

F

E

D

C

B

A

D

AT

E

File Path:

Plot Date:

M

AR

K D

ES

C

R

IP

TI

O

N

UNLESS OTHERWISE NOTED, LINEAR

DIMENSIONS SHOWN ARE IN MILLIMETERS.

PL

O

T D

AT

E:

FI

LE

N

AM

E:

US

A rm y

Co rp s…