This document summarizes a federal contract opportunity notice for the construction of an air traffic control tower in Jordan. The U.S. Army Corps of Engineers Transatlantic Middle East District is soliciting bids to design and build a new 12-story air traffic control tower with cab and balcony floors on a reinforced concrete pile foundation with a steel superstructure and precast concrete facade. The project scope includes construction of an elevator, catwalk, fire detection and suppression systems, HVAC, emergency power, utilities and site improvements. The facility must support a radar approach control system and comply with DoD antiterrorism requirements. The contract value is estimated between $10-25 million. The response deadline is not provided. Interested offerors should visit the site. The NAICS code is 236220 and the small business size standard is $39.5 million. The period of performance is 750 calendar days from notice to proceed.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
G-012
T-603 JR-474512A-T-603-03 3 AM 0003 INTERCOM RISER DIAGRAM
FIRST FLOOR
0 mm
SECOND FLOOR
3200 mm
THIRD FLOOR
6400 mm
FOURTH FLOOR
9600 mm
FIFTH FLOOR
12800 mm
SIXTH FLOOR
16000 mm
SEVENTH FLOOR
19200 mm
EIGHTH FLOOR
22400 mm
NINTH FLOOR
25600 mm
TENTH FLOOR
28800 mm
BALCONY
34385 mm
CAB FLOOR
36700 mm
TOP OF STL
41340 mm
INTERIOR
LOBBY
A D
ELEV PIT
-1800 mm
COBSTRUCTION
WARNING LIGHT
ELEVENTH FLOOR
32000 mm
A.9
35 T.O.X
36100 mm
A-421
B
RECESS FLR
-750 mm
FIRST FLOOR
0 mm
SECOND FLOOR
3200 mm
THIRD FLOOR
6400 mm
A D G
A-310
PRECAST CONC
ACCENT, PC-2
PRECAST CONC
PANELS, PC-1
RAPCON
EXTERIOR
LOBBY
A.9
SEE 5/A501 FOR SIMILAR DETAIL
B
RECESS FLR
-750 mm
RAISED ACCESS FLOOR
SYSTEM.
FIRST FLOOR
0 mm
SECOND FLOOR
3200 mm
THIRD FLOOR
6400 mm
FOURTH FLOOR
9600 mm
FIFTH FLOOR
12800 mm
SIXTH FLOOR
16000 mm
SEVENTH FLOOR
19200 mm
EIGHTH FLOOR
22400 mm
NINTH FLOOR
25600 mm
TENTH FLOOR
28800 mm
BALCONY
34385 mm
CAB FLOOR
36700 mm
TOP OF STL
41340 mm
1 2
4 53
ELEVENTH FLOOR
32000 mm
CONTROL
CAB
MECH
BREAK /
READY RM
UPPER EQUIP
RM.
LOWER
EQUIP RM
OFFICE
OFFICE
OFFICE
OFFICE
CONF
MECH
T.O.X 36100 mm
A-312
A-312
A-312
A-310
A-310
RECESS FLR
-750 mm
US Army Corps of Engineers ®
SHEET ID
US
A
RM
Y
CO
RP
S O
F
EN
G
IN
EE
RS
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E
File Path:
Plot Date:
M
AR
K D
ES
C
R
IP
TI
O
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
PL
O
T D
AT
E:
FI
LE
N
AM
E:
US
A rm y
Co rp s of
E ng in ee rs M id dl e Ea st D is tri ct
C:\Users\n0enasl3\Documents\JR-474512A-A-DM-ATCT_AMD 03_n0enasl3.rvt
1/25/2022 11:17:36 AM
1/
/2
:1 7:
AM
A-301
BU
IL
D
IN
G S
EC
TI
O N
S
U D
.4
, J O
R D
AN
SF
J
SF
J
SF
L
SF
L
-2
9-
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
(A
TC
T)
JR
-4
A
J.
R
AN
EY
, C H
IE
F
JR
-4
2A -A
-3
-0
M
ID
D
LE
E
AS
T D
IS
TR
IC
T
W
IN
C H
ES
TE
R , V
A.
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
1:100
10m2m 8m6m4m0m
1 : 1002 BUILDING SECTION
1 : 1003 BUILDING SECTION
R
EV
IS
ED
I. A
.W .A
M
EN
M
EN
T
JA
N
1 : 1001 Section 4
GENERAL NOTES
1. SEE A-001 FOR FORE RATING REQUIREMENT FOR STEEL FRAMING,
FLOOR DECK, ROOF DECK.
2. ALL CONCEALED STEEL FRAMINGS RECEIVE SPRAY ON FIRE
0 mm
G
PRECAST CONCRETE
PANEL, 50 mm CONT FOAM
INSULATION / AIR BARRIER,
20 GA META STUDS 400 mm
OC BATT INSULATION, 16
mm GWB. TOTAL R-20 MIN
MEMBERANE WATER PROOFING
AROUND BUILDING PERIMETER.
OVERLAP WITH FOUNDATION
WATER PROOFING
A-501
SCHEDULED CEILING
STRUCTURAL STEEL
FRAMING WITH 2 HOUR
FIRE PROOFING. SEE
STRUCTURAL
BRACING. SEE
STRUCTURAL
STRAP ANCHOR AND
SUBFRAMING / SUPPORT
BY PRECAST PANEL
FABRICATOR, TYP
GRAVEL AROUND
BUILDING PERIMETER.
SLOPE BOTTOM TO
PROVID POSITIVE
DRAIN.
FIRST FLOOR
0 mm
SECOND FLOOR
3200 mm
LOW ROOF
3550 mm
WRAP UP MEMBERANE WATER
PROOFING AS INDICATED.
ATTACHED TO STUDS
FIRST FLOOR
0 mm
SECOND FLOOR
3200 mm
THIRD FLOOR
6400 mm
A-603
SCHEDULED DOOR
CONCRETE SLAB SEE
STRUCTURAL
SCHEDULED CEILING TYP
SEE 1/A-502 FOR TYPICAL
DETAILS
ALUMINUM FRAMED WINDOW
SYSTEM - TYP
OPP HAND
A-311
PRECAST CONCRETE
WALL PANEL BEYOND
STRUCT SLAB SEE
STRUCTURAL DWGS
COMPRESSIBLE FILLER
AT OUTDOOR STOOP
JOINT, TYP.
SEE STRUCTURAL FOR
FOUNDATION DETAILS
TENTH FLOOR
28800 mm
CAB FLOOR
36700 mm
TYP PRECAST EXTERIOR
WALL SEE DETAIL 1/A311
FOR NOTES
50 MM INSULATED BLANK OFF PANEL
BY LOUVER MANUFACTURER
SCHEDULED CEILING TYP
STRUCT FLOOR SLAB TYP
STRUCTURAL STEEL FRAMING W/ 2
HOURS FIRE PROOFING
ALUMINUM FRAMED WINDOW
SYSTEM,
TYP
ACCESS FLOORING
SEE 1/A311 FOR DETAIL, TYP
GFRC DECO BEYOND.
SEE A-201 FOR DETAIL
ELEVENTH FLOOR
32000 mm
A-311
T.O.X 36100 mm
EXPOSED BRACING TO HAVE 2 HOUR
INTUMENSCENT COATING, TYPICAL FOR
ALL W3 LOCATIONS.
BALCONY
34385 mm
13 MM GWB ON 92 MM MTL STUDS
FRAMING, TYP
SEE MECH FOR DUCT OPENING
SIZE AND LOCATIONS.
A-311
A-311
SIM
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S D
R
AW
N B
Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E
File Path:
Plot Date:
M
AR
K D
ES
C
R
IP
TI
O
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
PL
O
T D
AT
E:
FI
LE
N
AM
E:
US
A rm y
Co rp s of
E ng in ee rs M id dl e Ea st D is tri ct
C:\Users\n0enasl3\Documents\JR-474512A-A-DM-ATCT_AMD 03_n0enasl3.rvt
12/30/2021 11:44:36 AM
/3
0/ 2 0
:4 4:
3 6
AM
A-310
W
AL
L
SE
C
TI
O N
S
U D
.4
, J O
R D
AN
SF
J
SF
J
SF
L
SF
L
-2
9-
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
(A
TC
T)
JR
-4
A
J.
R
AN
EY
, C H
IE
F
JR
-4
2A -A
-3
M
ID
D
LE
E
AS
T D
IS
TR
IC
T
W
IN
C H
ES
TE
R , V
A.
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
1 : 251 WALL SECTION 1
1 : 252 WALL SECTION 2
1 : 253 WALL SECTION 3
1:20
2m0.4m 1.6m1.2m0.8m0m
AM
D #3
D at e
F
A
G
C
K
A-402 3
C
B
FD
TOILET
MEN
WOMEN
A-402
A-402
FD
FD
A
B
C
3B
4K
1300 2876
I
C
K
A
K
SEALANT
2082 mm TP-1 W/
MFR STANDARD DR.
NO FLOOR OFFSET.
A
C
L
L
B
L
MOP SINK
2 305 86
A F-G
B C
3'
4" M
AX
K
1 152 10
67 TO BOTTOM OF
REFLECTIVE
SURFACE
I
E
US Army Corps of Engineers ®
SHEET ID
US
A
RM
Y
CO
RP
S O
F
EN
G
IN
EE
RS
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E
File Path:
Plot Date:
M
AR
K D
ES
C
R
IP
TI
O
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
PL
O
T D
AT
E:
FI
LE
N
AM
E:
US
A rm y
Co rp s of
E ng in ee rs M id dl e Ea st D is tri ct
C:\Users\n0enasl3\Documents\JR-474512A-A-DM-ATCT_AMD 03_n0enasl3.rvt
1/18/2022 2:28:38 PM
1/
/2
2:
:3
PM
A-401
EN
LA
R G
ED
R
ES
TR
O O
M P
LA
N
S
U D
.4
, J O
R D
AN
SF
J
SF
J
SF
L
SF
L
-2
9-
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
(A
TC
T)
JR
-4
A
J.
R
AN
EY
, C H
IE
F
JR
-4
2A -A
-4
M
ID
D
LE
E
AS
T D
IS
TR
IC
T
W
IN
C H
ES
TE
R , V
A.
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
1 : 253 ACCESSIBLE TOILET 104
1 : 255 WOMENS RESTROOM 503 AND MENS RESTROOM 505
1 : 254 TOILET ROOMS 1003
TOILET ACCESSORY SCHEDULE
TYPE
MARK DESCRIPTION
A SURFACE MOUNTED MULTI-ROLL TOILET
TISSUE DISPENSER
B SURFACE MOUNTED PAPER TOWEL
DISPENSER AND WASTE RECEPTACLE
C SURFACE MOUNTED SOAP DISPENSER
E SURFACE MOUNTED SANITARY NAPKIN
DISPOSAL
F 1066 MM GRAB BAR
G 914 MM GRAB BAR
H HEAVY DUTY SHELF & MOP HOLDER
I SURFACE MOUNTED DOUBLE ROBE
HOOK
J CURTAIN ROD, CURTAIN AND HOOKS
K MIRROR WITH STAINLESS STEEL
CHANNEL FRAME
L FULL LENGTH STAINLESS STEEL
CHANNEL FRAMED MIRROR
M SURFACE MOUNTED SHOWER SOAP
DISPENSER
1 : 501 TYPICAL MOUNTING HEIGHTS
1:20
2m0.4m 1.6m1.2m0.8m0m
GENERAL NOTES:
1. SLOPE FLOOR TO FLOOR DRAIN 1% AT ALL TOILET ROOMS.
R
EV
IS
ED
I. A
.W .A
M
EN
M
EN
T
JA
N
FLOOR SLOPE 1% TO FD
FLOOR SLOPE 2% TO FD
B
K
BASE PB-1
PAINT PT-5
C
GF
K
B
BASE PB-1
PAINT PT-5
NOTE: ROOM 1003 PLUMBING WALL ELEVATION
IS SIMILAR EXCEPT WITHOUT "F" AND "G".
G
F
BASE PB-1
PAINT PT-5
C
K
300W X 300D DOUBLE
TIER LOCKERS
BASE PB-1
PAINT PT-5
B
K
TILE CWT-2
BASE PB-1
TILE CWT-1
PAINT PT-5
300W X 300D
DOUBLE TIER
LOCKERS
BASE AS
SCHEDULED
PAINT PT-5
K
C
BASE PB-2
PAINT PT-5
300W X 300D
DOUBLE TIER
LOCKERS
BASE PB-2
PAINT PT-5
SHOWER WITH CURTAIN
ROD
TILE CWT-1
TILE CWT-2
TILE CWT-2
BASE PB-1
PAINT PT-5
TILE CWT-1
BASE PB-2
PAINT PT-5
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S D
R
AW
N B
Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E
File Path:
Plot Date:
M
AR
K D
ES
C
R
IP
TI
O
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
PL
O
T D
AT
E:
FI
LE
N
AM
E:
US
A rm y
Co rp s of
E ng in ee rs M id dl e Ea st D is tri ct
C:\Users\n0enasl3\Documents\JR-474512A-A-DM-ATCT_AMD 03_n0enasl3.rvt
1/10/2022 5:48:36 PM
1/
/2 0 2
5:
:3
PM
A-402
R
ES
TR
O
O M
/ L O
C
KE
R R
O O
M E
LE
VA
TI
O
N S
U D
.4
, J O
R D
AN
SF
J
SF
J
SF
L
SF
L
-2
9-
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
(A
TC
T)
JR
-4
A
J.
R
AN
EY
, C H
IE
F
JR
-4
2A -A
-4
M
ID
D
LE
E
AS
T D
IS
TR
IC
T
W
IN
C H
ES
TE
R , V
A.
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
1 : 502 SOUTH ELEV RM 104
1 : 503 EAST ELEV RM 104
1 : 501 NORTH ELEV RM 104
1 : 5010 SOUTH ELEV RM 503
1 : 508 NORTH ELEV RM 503
1 : 5011 WEST ELEV RM 503
1 : 505 EAST ELEV RM 505
1 : 504 NORTH ELEV RM 505
1 : 509 EAST ELEV RM 503
1:50
5m1m 4m3m2m0m
TOILET ACCESSORY SCHEDULE
TYPE
MARK DESCRIPTION
A SURFACE MOUNTED MULTI-ROLL TOILET
TISSUE DISPENSER
B SURFACE MOUNTED PAPER TOWEL
DISPENSER AND WASTE RECEPTACLE
C SURFACE MOUNTED SOAP DISPENSER
E SURFACE MOUNTED SANITARY NAPKIN
DISPOSAL
F 1066 MM GRAB BAR
G 914 MM GRAB BAR
H HEAVY DUTY SHELF & MOP HOLDER
I SURFACE MOUNTED DOUBLE ROBE
HOOK
J CURTAIN ROD, CURTAIN AND HOOKS
K MIRROR WITH STAINLESS STEEL
CHANNEL FRAME
L FULL LENGTH STAINLESS STEEL
CHANNEL FRAMED MIRROR
M SURFACE MOUNTED SHOWER SOAP
DISPENSER
AM
D #3
D at e
GENERAL NOTE
1. SEE I-602 FOR INTERIOR FINISHES DETAILS.
1 : 506 SOUTH ELEV RM 505
CONTROL
CAB
6" UP
6"
UP
SURFACE MTD
DIFFUSER, REFER
TO MECH DWGS
ACCESS FLOORING
PEDESTAL, TYP
EDGE OF SLAB
(6)- 50 mm CONDUIT
SLEEVES THRU SLAB
(6) - 100 mm CONDUITS
FROM LEVEL
BELOW
PROVIDE (6) - 50 mm
GROMMETS IN TILE
PROVIDE (6) - 50 mm
GROMMETS IN TILE
ROOF HATCH WITH
PULL DOWN LADDER
ABOVE
BOOK SHELVING
05 07 06 07 05
15 05
04 10
16 16
GROUND
FLIGHT DATA
LO
C
AL
SUPERVISOR
16A
2 3
7 6
CAB.1
CAB.3
CAB.B CAB.DCAB.A CAB.E
CAB.2
CAB.C
CAB EQUIPMENT TABLE
ID NAME
NIC
01 COFFEE NIC
02 MICRO
03 U.C. REFRIGERATOR NIC
04 LIGHT GUN WITH CHARGER
PROVIDER
05 ATISI / A FAS (24" MORNITOR, KEY BOARD)
06 FLIGHT STRIP BAY
07 EIVS (CONTROL, SPEAKER, JACK BOX)
08 FDIO MONITOR AND PRTR
09 GROUND RAMP LIGHT CTRL
10 VHF / UHF MULTI-CHANNEL RADIO CONTROL PANEL
12 AIRFIELD LIGHT CONTROL
13 PIDP (DBRITE KEYBOARD)
14 DBRITE MONITOR
15 ADMINISTRATIVE CPU
16 PHONE
17 INTERCOM / DOOR RELEASE
18 LAND MOBILE RADIO W/ CHARGER
16A CRASH PHONE
QTY
20 SUP CONSOLE
21 OUTER PERIMETER CONSOLE
22 COFFEE COUNTER
GENERATOR MONITOR
NIWC
REMOTE STATUS INDICTOR
JACK BOX U.C.
16B RJAF PHONE 3
05A ADOC (24" MORNITOR, KEY BOARD) 4
GFGI
CAB GLASS MULLION ROUTING TABLE
ID DESCRIPTION OF UTILITY
1 100 mm COMM CONDUIT FOR NIWC USE COMM
2 NOT ASSIGNED
3 NOT ASSSIGNED
4 100 mm COMM CONDUIT FOR NIWC
COORDINATION
5 65 mm SPRINKLER PIPE AND UP TO 2 FIRE DETN CONDUITS
7 NOT ASSIGNED
8 75 mm ROOF DRAIN PIPE
COMM
6 ELEC CONDUIT
FP
ELEC
PLUMBING
NOTES:
1. 50mm COMM CONDUITS AT MULLION 1 AND 4 REQUIRED BY UFC 4-133-01 SECTION 4-1.2.17.1 AND FIG. 4-2.
2. ALL MULLIONS' INSIDE SPACE RESERVED FOR ADD'L NIWC COMM ROUNTING TO ROOF.
3. SEE 12 / A-603 FOR DETAIL. COORDINATE WITH ENGINEERING DRAWINGS FOR ROUTING INFORMATION.
4. LIGHTNING PROTECTION SYSTEM CONNECTORS (2) ARE ROUTED IN CONDUIT ON BUILDING EXTERIOR.
5. NIWC IS NAVAL INFORMATION WAREFARE CENTER, WHICH WILL INSTALL AIR TRAFFIC CONTROL
EQUIPMENT.
NIWC
NIWC
NIWC
NIWC
NIWC
NIWC
NIWC
NIWC
NIWC
NIWC
NIWC
NIWC
NIWC
NIWC
NIWC
NIWC
NIWC
NIWC
NIWC
NIWC
CPCI
US Army Corps of Engineers ®
SHEET ID
US
A
RM
Y
CO
RP
S O
F
EN
G
IN
EE
RS
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E
File Path:
Plot Date:
M
AR
K D
ES
C
R
IP
TI
O
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
PL
O
T D
AT
E:
FI
LE
N
AM
E:
US
A rm y
Co rp s of
E ng in ee rs M id dl e Ea st D is tri ct
C:\Users\n0enasl3\Documents\JR-474512A-A-DM-ATCT_AMD 03_n0enasl3.rvt
1/21/2022 11:54:51 AM
1/
/2
:5 4:
AM
A-422
C
AB
P
LA
N A
N D
V
IE
W
U D
.4
, J O
R D
AN
SF
L
SF
L
SF
L
-2
9-
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
(A
TC
T)
JR
-4
A
J.
R
AN
EY
, C H
IE
F
JR
-4
2A -A
-4
-0
M
ID
D
LE
E
AS
T D
IS
TR
IC
T
W
IN
C H
ES
TE
R , V
A.
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
1 : 254 ENLARGED CAB LAYOUT
R
EV
IS
ED
I. A
.W .A
M
EN
M
EN
T
JA
N
CAB CONSOLE AND EQUIPMENT BY PROVIDED
AND INSTALLED BY NIWC. FINAL LAYOUT SHALL
BE COORDINATED WITH GOVERNMENT INSTALLER
1 2 3
127 127
300 900
250 400 250
NOTE: SEE SCHEDULE FOR
DOORS REQUIRE LOUVER
NOTE: SEE SCHEDULE FOR
DOORS REQUIRE LOUVER
S1 (Not Used) S2
84 14
916 1040 51
127786127
1" INSULATED
GLAZING -
TEMPERED
A B
AS SCHED.
AS
S
C H
ED
50 50
AS SCHED.
AS
S
C H
ED
50 50
1. VERIFY ALL CONCRETE OPENINGS IN THE FIELD PRIOR TO FABRICATION OF DOORS AND
FRAMES.
2. ALL UNDERCUT DOOR REQUIREMENTS FOR VARYING CARPET THICKNESS, TILE
FLOORING ETC. SHALL BE VARIED AND PROPERLY COORDINATED WITH THE FINISH
SCHEDULE.
3. ALL STEEL DOORS & FRAMES TO BE SHOP PRIMED AND FIELD PAINTED SLATE GRAY
EXCEPT FOR THE PREFINISHED ALUMN FRAMES.
K L2 L3 L4 L5 L1
L6 L7
W1
W3 / W4
(NOTE: OVERALL DIMENSIONS
ARE OPENING SIZE. )
OPERABLE SASH
SPANDREL GLAZING
@ W3 WINDOWS ONLY
1" INSULATED
GLAZING -
TEMPERED
EQ 711 EQ
EQ
EQ
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S D
R
AW
N B
Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E
File Path:
Plot Date:
M
AR
K D
ES
C
R
IP
TI
O
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
PL
O
T D
AT
E:
FI
LE
N
AM
E:
US
A rm y
Co rp s of
E ng in ee rs M id dl e Ea st D is tri ct
C:\Users\n0enasl3\Documents\JR-474512A-A-DM-ATCT_AMD 03_n0enasl3.rvt
1/10/2022 3:10:45 PM
1/
/2 0 2
3:
:4
PM
A-602
D O
O R
W
IN
D O
W A
N D
L O
U
VE
R S
C H
ED
U
LE
S
U D
.4
, J O
R D
AN
SF
L
SF
L
SF
L
-2
9-
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
(A
TC
T)
JR
-4
A
J.
R
AN
EY
, C H
IE
F
JR
-4
2A -A
-6
M
ID
D
LE
E
AS
T D
IS
TR
IC
T
W
IN
C H
ES
TE
R , V
A.
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
DOOR SCHEDULE
WT
DOOR
MAT
DOOR
FIRE
RATING
FRAME
HEAD THRESHOLD HDWR COMMENTSTYPE
SIZE
TYPE MATWIDTH HGHT THK
101 5 SCW 900 mm 2150 mm 50 mm 90 A HM 7/A-603 3/A-603 7 101A 1 HM 900 mm 2150 mm 50 mm 90 A HM 1/A-603 3/A-603 5 BLAST RESIST 102 1 HM 900 mm 2150 mm 50 mm A HM 1/A-603 3/A-603 4 LOUVER 103 4 HM 1200 mm 2150 mm 45 mm B HM 1/A-603 3/A-603 3 LOUVER 104 5 SCW 900 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 11 50 mm UNDERCUT 105 5 SCW 900 mm 2150 mm 50 mm 45 A HM 7/A-603 4/A-603 8 108 3 ALUM 50 mm S2 ALUM 2/A-603 4/A-603 2 SEE DOOR TYPE FOR SIZE, CIPHER LOCK 109 1 HM 900 mm 2150 mm 50 mm A HM 1/A-603 3/A-603 1A BLAST RESIST, CIPHER LOCK 110 4 SCW 1200 mm 2150 mm 45 mm A HM 7/A-603 9/A-603 1 STC 45 111 4 HM 1200 mm 2150 mm 45 mm B HM 1/A-603 3/A-603 3 201 5 SCW 900 mm 2150 mm 50 mm 90 A HM 7/A-603 9/A-603 7 202 5 SCW 900 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 6A 203 2 SCW 1200 mm 2150 mm 50 mm - A HM 7/A-603 9/A-603 14 301 5 SCW 900 mm 2150 mm 50 mm 90 A HM 7/A-603 9/A-603 7 302 2 SCW 1200 mm 2150 mm 50 mm - A HM 7/A-603 9/A-603 14 303 5 SCW 900 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 6A STC 45 304 5 SCW 900 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 6A STC 45 401 5 SCW 900 mm 2150 mm 50 mm 90 A HM 7/A-603 9/A-603 7 402 5 SCW 900 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 6A STC 45 403 2 SCW 1200 mm 2150 mm 50 mm - A HM 7/A-603 9/A-603 14 501 5 SCW 900 mm 2150 mm 50 mm 90 A HM 7/A-603 9/A-603 7 503 1 SCW 800 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 12 504 5 SCW 900 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 13 505 1 SCW 800 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 12 50 mm UNDERCUT 601 5 SCW 900 mm 2150 mm 50 mm 90 A HM 7/A-603 9/A-603 7 602 5 SCW 900 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 6A STC 45 603 2 SCW 1200 mm 2150 mm 50 mm - A HM 7/A-603 9/A-603 13 701 5 SCW 900 mm 2150 mm 50 mm 90 A HM 7/A-603 9/A-603 7 702 5 SCW 900 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 6A STC 45 703 2 SCW 1200 mm 2150 mm 50 mm - HM 7/A-603 9/A-603 13 801 5 SCW 900 mm 2150 mm 50 mm 90 A HM 7/A-603 9/A-603 7 802 1 SCW 914 mm 2032 mm 44 mm 45 A HM 7/A-603 9/A-603 8 901 5 SCW 900 mm 2150 mm 50 mm 90 A HM 7/A-603 9/A-603 7 902 1 SCW 914 mm 2032 mm 44 mm 45 A HM 7/A-603 9/A-603 8 905 5 SCW 900 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 6A STC 45 1001 5 SCW 900 mm 2150 mm 50 mm 90 A HM 7/A-603 9/A-603 7 1003 1 SCW 800 mm 2150 mm 50 mm 45 A HM 7/A-603 9/A-603 11 50 mm UNDERCUT 1006 5 SCW 900 mm 2150 mm 50 mm 45 B HM 7/A-603 9/A-603 13 1101A 1 HM 914 mm 2032 mm 44 mm 90 A HM 7/A-603 9/A-603 8A 1101B 1 SCW 914 mm 2032 mm 44 mm 90 A HM 1/A-603 9/A-603 14 RELEASE CONTROL, INTERCOM, STC 45 1102B 10 HM 900 mm 1828 mm 50 mm A HM 1/A-603 3/A-603 5 STC 45 (TYPE 10 IS LOWER SIZE THANTYPE 1)
1:50
5m1m 4m3m2m0m
DOOR TYPES
1 : 50
STOREFRONT TYPES
1 : 48
FRAME TYPES
LOUVER SCHEDULE
TYPE
MARK
ROUGH OPENING
COMMENTSWIDTH HEIGHT
K 2000 mm 1600 mm KNOCK OUT LOUVER WITH 50MM BLANK OFF L1 1610 mm 1250 mm LOUVER L2 850 mm 750 mm LOUVER L3 350 mm 350 mm LOUVER L4 1000 mm 1000 mm LOUVER L5 457 mm 203 mm LOUVER L6 500 mm 500 mm LOUVER L7 400 mm 400 mm LOUVER
WINDOW SCHEDULE
TYPE
MARK
ROUGH OPENING SILL
HEIGHT MODEL MATERIAL
DETAILS
COMMENTSWIDTH HEIGHT HEAD JAMB SILL
W1 600 MM 900 MM 1100 mm ALUM 5/A-603 SIM 5/A-603 1/A-502 W3 2100 MM 2150 MM 0'-0" AFF ALUM 5/A-603 SIM 5/A-603 1/A-502 LOW E GLAZING, STC 42
W4 2100 MM 2150 MM 0'-0" AFF ALUM 5/A-603 SIM 5/A-603 1/A-502 U=0.15, STC 42
AM
D #3
D at e
1 : 50
LOUVER TYPES
1 : 24
WINDOW TYPES
1100 mm SILL
HEIGHT AFF
US Army Corps of Engineers ®
SHEET ID
US
A
RM
Y
CO
RP
S O
F
EN
G
IN
EE
RS
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E
File Path:
Plot Date:
M
AR
K D
ES
C
R
IP
TI
O
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
PL
O
T D
AT
E:
FI
LE
N
AM
E:
US
A rm y
Co rp s of
E ng in ee rs M id dl e Ea st D is tri ct
C:\Users\n0enasl3\Documents\JR-474512A-A-DM-ATCT_AMD 03_n0enasl3.rvt
1/25/2022 11:30:37 AM
1/
/2
:3 0:
AM
A-606
FI
N
IS
H
S C
H
ED
U
LE
U D
.4
, J O
R D
AN
M
M C
M M
C
D H
-2
9-
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
(A
TC
T)
JR
-4
A
J.
R
AN
EY
, C H
IE
F
JR
-4
2A -A
-6
-0
M
ID
D
LE
E
AS
T D
IS
TR
IC
T
W
IN
C H
ES
TE
R , V
A.
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
wtwt ROOM NAME FLOOR BASE
WALL FINISH
CEILING COMMENTSNORTH EAST SOUTH WEST
101 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS
102 ELEC SEALED CONC. RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED
103 MECH SEALED CONC. RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED
104 TOILET PFT-1 PB-1 PT-5 PT-5 PT-5 PT-5 GYP. / PT-5 USE EPOXY PAINT ON ALL WALLS AND CEILING
105 COMM SEALED CONC. RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED
106 ELEVATOR VCT-2 - - -- - -
108 INTERIOR LOBBY CPT-1 RB-1 PT-1 PT-1 PT-1 PT-1 ACT-1 SEE SHEET I-101 FOR ACCENT WALL LOCATIONS 109 EXTERIOR LOBBY VCT-1 RB-2 PT-2 PT-2 PT-2 PT-2 ACT-1 SEE SHEET I-101 FOR ACCENT WALL LOCATIONS & FLOOR PATTERNS 110 RAPCON CPT-2 RB-1 AWP-1 AWP-1 AWP-1 AWP-1 ACT-2 PROVIDE ACOUSTIC WALL PANELS (AWP-1), FROM TOP OF CONSOLE TO CEILING. ACCESS FLOOR SYSTEM
111 FIRE COMMAND SEALED CONC. RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED
201 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS 202 CONF CPT-1 RB-1 PT-1 PT-1 PT-1 PT-1 ACT-1 SEE SHEET I-101 FOR ACCENT WALL LOCATIONS
203 COMM/ELEC SEALED CONC. RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED
204 LOBBY CPT-1 RB-1 PT-1 PT-1 PT-1 PT-1 ACT-1 SEE SHEET I-101 FOR ACCENT WALL LOCATIONS
206 ELEVATOR VCT-1
301 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS
302 COMM/ELEC SEALED CONC. RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED
303 OFFICE CPT-1 RB-1 PT-1 PT-1 PT-1 PT-1 ACT-1 SEE SHEET I-102 FOR ACCENT WALL LOCATIONS
304 JANITOR PFT-1 PB-1 PT-5 PT-5 PT-5 PT-5 ACT-1
305 LOBBY CPT-1 RB-1 PT-1 PT-1 PT-1 PT-1 ACT-1 SEE SHEET I-102 FOR ACCENT WALL LOCATIONS
306 ELEV. VCT-1
401 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS 402 OFFICE CPT-1 RB-1 PT-1 PT-1 PT-1 PT-1 ACT-1 SEE SHEET I-102 FOR ACCENT WALL LOCATIONS
403 COMM/ELEC SEALED CONC. RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED
404 LOBBY CPT-1 RB-1 PT-1 PT-1 PT-2 PT-1 ACT-1 SEE SHEET I-102 FOR ACCENT WALL LOCATIONS 501 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS 502 MEN PFT-1 PB-2 CWT-1/CWT-3/PT-4 CWT-1/CWT-3/PT-4 CWT-1/CWT-3/PT-4 CWT-1/CWT-3/PT-4 GYP. / PT-5 FULL HEIGHT TILE @ SHOW. SS-1 COUNTER TOP. TP-1 TOILET PARTITIONS. EPOXY PAINT ON ALL SURFACE 503 MEN PFT-1 PB-1 CWT-1/CWT-2/PT-4 CWT-1/CWT-2/PT-4 CWT-1/CWT-2/PT-4 CWT-1/CWT-2/PT-4 GYP. / PT-5 FULL HEIGHT TILE @ SHOW. SS-1 COUNTER TOP. TP-1 TOILET PARTITIONS. EPOXY PAINT ON ALL SURFACE
504 COMM/ELEC SEALED CONC. RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED
505 WOMEN PFT-1 PB-1 CWT-1/CWT-2/PT-5 CWT-1/CWT-2/PT-5 PT-5 PT-5 GYP. / PT-5 USE EPOXY PAINT ON ALL WALLS AND CEILING
506 ELEV. VCT-1
507 LOBBY CPT-1 RB-1 PT-1 PT-1 PT-2 PT-1 ACT-1 SEE SHEET I-102 FOR ACCENT WALL LOCATIONS 601 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS 602 OFFICE CPT-1 RB-1 PT-1 PT-2 PT-1/ PT-2 PT-1 ACT-1 SEE SHEET I-102 FOR ACCENT WALL LOCATIONS
603 COMM/ELEC SEALED CONC. PB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED
604 LOBBY CPT-1 RB-1 PT-1 PT-1 PT-2 PT-1 ACT-1 SEE SHEET I-102 FOR ACCENT WALL LOCATIONS
606 ELEV. VCT-1
701 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS
702 OFFICE CPT-1 RB-1 PT-1 PT-2 PT-1/ PT-2 PT-1 ACT-1
703 COMM/ELEC SEALED CONC. PB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED
704 LOBBY CPT-1 RB-1 PT-1 PT-1 PT-2 PT-1 ACT-1 SEE SHEET I-103 FOR ACCENT WALL LOCATIONS
706 ELEV. VCT-1
801 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS
802 LOWER EQUIP RM VCT-4 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED
806 ELEV. VCT-1
810 LOBBY CPT-1 RB-1 PT-1 PT-1 PT-2 PT-1 ACT-1 SEE SHEET I-103 FOR ACCENT WALL LOCATIONS 901 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS 902 UPPER EQUIP RM. VCT-4 RB-2 WC-1 WC-1 WC-1 WC-1 EXPOSED SEE SHEET I-103 FOR FLOOR PATTERN 903 LOBBY CPT-1 RB-1 PT-1 PT-1 PT-2 PT-1 ACT-1 SEE SHEET I-103 FOR ACCENT WALL LOCATIONS
906 ELEV. VCT-1
1001 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS
1002 BREAK / READY RM VCT-1 RB-2 PT-1/P-2 PT-1/P-2 PT-1/ PT-2 PT-1/P-2 ACT-1
1003 TOILET PFT-1 PB-1 PT-5 PT-5 PT-5 PT-5 ACT-1
1005 LOBBY CPT-1 RB-1 PT-1 PT-1 PT-1 PT-2 ACT-1
1006 ELEV CTRL SEALED CONC. PB-1 PT-1 PT-1 PT-1 PT-1 GYP.
1101 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS
1102 MECH SEALED CONC. RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED
1103 TOILET PFT-2 PB-2 PT-5 PT-5 PT-5 PT-5 ACT-1 USE EPOXY PAINT ON ALL WALLS
1201 CONTROL CAB CPT-2 RB-1 PT-4 PT-4 PT-4 PT-4 ACT-2 PROVIDE RAISED ACCESS FLOOR 600 MM
1202 MGR AREA CPT-2 RB-1 PT-4 PT-4 PT-4 PT-4 ACT-2
1203 STAIR VCT-3 RB-1 PT-1 PT-1 PT-1 PT-1 EXPOSED PROVIDE TR-1 ON RISERS AND STAIR TREADS
R
EV
IS
ED
I. A
.W .A
M
EN
M
EN
T
JA
N
1. REFER TO COLOR AND MATERIAL SCHEDULE FOR ACCEPTABLE ALTERNATE
MANUFACTURERS. COLORS AND PATTERNS MUST CLOSELY MATCH BASIS OF
DESIGN AND BE SUBMITTED FOR APPROVAL.
2. THE METAL STAIRS SHALL BE PAINTED IN THE SAME COLOR AS THE HM DOOR
FRAMES.
NOTES:
3 3 3
MECH
FTEXTF
P,ER
S
75 0.5
MECH
TE
XT
LOC STAIRWAY
US Army Corps of Engineers ®
SHEET ID
US
A
RM
Y
CO
RP
S O
F
EN
G
IN
EE
RS
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E
File Path:
Plot Date:
M
AR
K D
ES
C
R
IP
TI
O
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
PL
O
T D
AT
E:
FI
LE
N
AM
E:
US
A rm y
Co rp s of
E ng in ee rs M id dl e Ea st D is tri ct
X:\REVIT PROJECTS\JORDAN\2018\JR-474512 - Air Traffic Control Tower, MSAB, Jordan\JR-474512A - AIR TRAFFIC CONTROL TOWER\JR-474512A-F-DM-ATCT-03.rvt
1/12/2022 12:16:16 PM
1/
/2
:1 6:
PM
FA-106
EL
EV
EN
TH
A N
D C
AT
W
AL
K
FL
O
O R
F
IR
E
PR
O
TE
C
TI
O N
P
LA
N S
U D
.4
, J O
R D
AN
R
D
IP
ER
T
SD
O
ED
EN
G M
IC
H
AE
LS
FE
BR
U
AR
Y2
R
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
(A
TC
T)
JR
-4
A
T.
S
TE
PH
EN
SO
N , C
H
IE
F
JR
-4
2A -F
A-
M
ID
D
LE
E
AS
T D
IS
TR
IC
T
W
IN
C H
ES
TE
R , V
A.
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
R
EV
IS
ED
I. A
.W .A
M
EN
D M
E N T
0 3
JA
N
1 : 502 CATWALK FIRE PROTECTION PLAN
1 : 501 ELEVENTH FLOOR FIRE PROTECTION PLAN
FROM FA/MNS
F
P
SFF
SECOND FLOOR
F P
S P
SMM
WF
CMEOL
THIRD & FOURTH FLOOR
(TYPICAL)
F P
S P
SMM
WF
EOL
FIFTH FLOOR
F P
S P
SMM
WF
CMEOL
SIXTH, SEVENTH
FLOOR (TYPICAL)
F P
S P
SMM
WF
NINTH FLOOR
HVAC
F P
S P
SMM
WF
EOL
TENTH FLOOR
F P
S P
SEOL
ELEVENTH FLOOR
F P
SEOL
CONTROL CAB & CATWALK
F P
SEOL
MMCMMMCMMMCMCM
MM
WF
CM
SOL
VALVE
ELEVATOR
CONTROL
,ER
FIRST FLOOR
EXTERIOR
ENCLOSURE
TO FA/MNS PANEL
FMM
FIRE PUMP
CONTROLLER
EOL SPD
SURGE
PROTECTION
DEVICE
MM
WF
MM
VT
MM
VT
MM
VT
MM
VT
MM
VT
MM MM MM
FIRE PUMP WATER
SUPPLY
VALVES
FIRE PUMP
ENCLOSURE
SPRINKLER
LOC
LOC RAA
TEXT TEXT MESSAGE
BLUE
BLUE INCANDESCENT LAMP
SILENCEABLE SPEAKER
~ ~ EOL
ELEVENTH FLOOR
CONTROL CAB & CATWALK
NAC SPEAKER CIRCUIT
~ ~ EOL
NAC SPEAKER CIRCUIT
SECOND THROUGH TENTH
FLOOR (TYPICAL)
FMCP
WP
WPWP
EOL
SPD
WP
NAC SPEAKER CIRCUIT
TEXT TEXT MESSAGE
LOC
LOC
LOC
LOC
LOC
LOC
LOC
LOC
P S
P
SFFMM
WF
MM
WF
MM
VT
MM
VT
EOL
P
S
EF-4
EOL
F
F
F P
S P
SMM
WF
EOL CM
EF-3
EIGHTH FLOOR
F
LOC
P S
TEXT TEXT MESSAGE
US Army Corps of Engineers ®
SHEET ID
US
A
RM
Y
CO
RP
S O
F
EN
G
IN
EE
RS
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E
File Path:
Plot Date:
M
AR
K D
ES
C
R
IP
TI
O
N
PL
O
T D
AT
E:
FI
LE
N
AM
E:
US
A rm y
Co rp s of
E ng in ee rs M id dl e Ea st D is tri ct
X:\REVIT PROJECTS\JORDAN\2018\JR-474512 - Air Traffic Control Tower, MSAB, Jordan\JR-474512A - AIR TRAFFIC CONTROL TOWER\JR-474512A-F-DM-ATCT-03.rvt
1/12/2022 12:13:41 PM
1/
/2
:1 3:
PM
FA-602
FI
R
E
AL
AR
M
R
IS
ER
D
IA
G
R
AM
U D
.4
, J O
R D
AN
R
D
IP
ER
T
SD
O
ED
EN
G M
IC
H
AE
LS
FE
BR
U
AR
Y2
R
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
(A
TC
T)
JR
-4
A
T.
S
TE
PH
EN
SO
N , C
H
IE
F
JR
-4
2A -F
A-
M
ID
D
LE
E
AS
T D
IS
TR
IC
T
W
IN
C H
ES
TE
R , V
A.
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
NTS1 FIRE ALARM RISER DIAGRAM
R
EV
IS
ED
I. A
.W .A
M
EN
D M
E N T
0 3
JA
N
A
SYMBOL KEY
SEE SUMP PUMPM SCHEDULE
SHEET P-601
CONDUCTIVITY PROBE FOR
PUMP INTERRUPT IN CASE
OF HIGH OIL STORAGE
LEVEL IN SUMP. INCLUDES
BRACKET FOR
INSTALLATION ON PUMP
DISCHARGER.
FLOAT SENSOR FOR HIGH
SUMP LEVEL ALARM.
A
B
C
B
C
40MM DISCHARGE UP
ELEVATOR SHAFT.
SEE FLOOR PLAN ON
P-101 FOR
CONTINUATION.
ELEVATOR SHAFT
POWER AND
SENSOR WIRING
PUMP
INTERRUPT/
ALARM PANEL:
220V/1PH/ 50HZ.
LOCATE IN
MECHANICAL
ROOM.
50MM DISCHARGE TO
STANDPIPE DRAIN IN
MECHANICAL ROOM
NOTES:
SUMP SHALL HAVE A MANHOLE
COVER PER ELEVATOR CODE BY G.C.
COORDINATE PIPE ROUTING WITH
ARCHITECTURAL, STRUCTURAL, AND
ELEVATOR CONTRACCTOR.
CHECK VALVE
FF
ELECTRICAL PLUG
TO OUTLET.
RP-1-47, SEE DIV.
50MM DIA. TO STORM
DRAIN. SEE PLANS
MANHOLE COVER
SCALE: NTS
ELEVATOR SUMP PUMP DETAILH
SCALE:
POINT OF USE WATER HEATER DETAIL
NTS
SINK
ANGLE STOP
CW SUPPLY
WITH SHUT-OFF
VALVEWIRING BY DIV. 26
HW TO
FIXTURE
COUNTER TOP
CW TO
FIXTURE
I
FAUCET
EWH
MOUNTED UNDER
COUNTER PER
MANUFACTURERS
REQUIREMENTS
SCALE: NTS
WATER FILTER ASSEMBLY
PIPING DIAGRAMK
15CW SUPPLY TO
HVAC EQUIPMENT.
PROVIDE FINAL
CONNECTION TO UNIT.
WATER
FILTER/STRAINER IN-
LINE (T-LIINE) 595
MICRON (MAXIMUM)
UNION
(TYP)
NOTE:
ASSEMBLY TO BE LOCATED NEAR SERVED
EQUIPMENT.
PLUMBING CONTRACTOR TO COORDINATE WITH
MECHANICAL CONTRACTOR FOR FINAL
CONNECTIONS.
FROM COLD WATER MAIN.
SEE PLANS.
15CW
15CW
15CW
SCALE:
POINT OF USE WATER HEATER DETAIL EWH-1
NTS
WIRING BY DIV. 26
J
EWH
WALL MOUNTED PER
MANUFACTURERS
REQUIREMENTS
CW SUPPLY
WITH SHUT-OFF
VALVE
CW TO
ABOVE
HW SUPPLY
WITH SHUT-OFF
VALVE
HW TO
ABOVE
US Army Corps of Engineers ®
SHEET ID
US
A
R M
Y
CO
RP
S
O F
EN
G
IN
EE
RS
D
R
AW
N B
Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E
File Path:
Plot Date:
M
AR
K D
ES
C
R
IP
TI
O
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
PL
O
T D
AT
E:
FI
LE
N
AM
E:
US
A rm y
Co rp s of
E ng in ee rs M id dl e Ea st D is tri ct
C:\Users\n0enmcc7\Documents\JR-474512A-P-DM-ATCT-03_n0enmcc7.rvt
1/18/2022 5:17:18 PM
1/
/2
5:
:1
PM
P-502
PL
U
M
BI
N G
D
ET
AI
LS
U D
.4
, J O
R D
AN
C
. C R
O
SB
IE
C . C
R O
SB
IE
K.
M
C
LE
LL
AN
FE
BR
U
AR
Y
R
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
(A
TC
T)
JR
-4
A
T.
S
TE
PH
EN
SO
N
JR
-4
2A -P
-5
-0
M
ID
D
LE
E
AS
T D
IS
TR
IC
T
W
IN
C H
ES
TE
R , V
A.
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
R
EV
IS
ED
I. A
.W .A
M
EN
D M
EN
T
0 3
JA
N
1ST FLOOR
2ND FLOOR
3RD FLOOR
4TH FLOOR
5TH FLOOR
6TH FLOOR
8TH FLOOR
9TH FLOOR
10TH FLOOR
11TH FLOOR
CATWALK LEVEL
CAB LEVEL
P-7
P-6
P-14P-8
P-5
P-5
P-6 P-1
P-1 P-4
SEE DOMESTIC
WATER RISER
DIAGRAM C/P-501
CONNECT TO
50CW
FOR CONTINUATION
SEE CIVIL SITE FOR
CONTINUATION
BOOSTER PUMP
ASSEMBLY. SEE
DETAIL E/P-501
EWH-2
40CW 20CW
50CW
PRESSURE
REGULATOR. SEE
SCHEDULE AND DETAIL
ON THIS SHEET
(TYPICAL)
PV-3
PV-5
PV-6
EWH-7
50CW
32CW
32CW
25CW
SHUT-OFF VALVE
(TYPICAL)
20HW
20CW
15CW
20CW
20CW
15CW
50CW
MECHANICAL 1002
PV-7
ROUTE PIPING BELOW COUNTER
20CW
15HW
P-1
PDI-B
PDI-A
20CW TO WALL
HYDRANTS. SEE
PLAN ON P-204.
CHILLED WATER MAKE-
UP. SEE DETAIL D/P-501.
PV-9
PV-8
P-9 P-9 P-9
PDI-A
PDI-A
20CW
20CW20CW
CRAC UNIT #1
(BY OTHERS)
CRAC UNIT #2
(BY OTHERS)
CRAC UNIT #3
(BY OTHERS)
CRAC UNIT #4
(BY OTHERS)
FILTER ASSEMBLY.
SEE DETAIL
K/P-502. (TYP.)
COORDINATE FINAL
CONNECTION WITH
HVAC CONTRACTOR
(TYP)
7TH FLOOR
P-9
20CW
25CW20CW
20CW
32CWP-4
20CW
EWH-6EWH-5EWH-4
20CW
20CW
20CW
P-1
15CW
EWH-1
20HW
20CW
20CW15HW
PDI-B
P-8
PV-2
15CWEWH-3
WATER PRESSURE REDUCING STATION
NTS
PRESSURE REDUCING
VALVE. SEE THIS SHEET
FOR SCHEDULE, SIZES,
AND LOCATIONS.
PRESSURE GUAGE
BALL VALVE
UNION
PRESSURE GUAGE
BALL VALVE
UNION
STRAINER
SEE PLAN AND
RISER DIAGRAM
FOR PIPE SIZES
SEE PLAN AND
RISER DIAGRAM
FOR PIPE SIZES
NOTE: PRESSURE REDUCING STATION TO BE
MOUNTED ABOVE CEILING OR IN JANITORS
CLOSET CEILING.PROVIDE ACCESS AS
REQUIRED. ALL PRV'S SHALL BE DROP TIGHT TYPE.
US Army Corps of Engineers ®
SHEET ID
US
A
R M
Y
CO
RP
S
O F
EN
G
IN
EE
RS
D
R
AW
N B
Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E
File Path:
Plot Date:
M
AR
K D
ES
C
R
IP
TI
O
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
PL
O
T D
AT
E:
FI
LE
N
AM
E:
US
A rm y
Co rp s of
E ng in ee rs M id dl e Ea st D is tri ct
C:\Users\n0enmcc7\Documents\JR-474512A-P-DM-ATCT-03_n0enmcc7.rvt
1/18/2022 5:18:03 PM
1/
/2
5:
:0
PM
P-902
H O
T
AN
D C
O
LD
W
AT
ER
S
YS
TE
M R
IS
ER
D
IA
G R
AM
U D
.4
, J O
R D
AN
C
. C R
O
SB
IE
C . C
R O
SB
IE
K.
M
C
LE
LL
AN
FE
BR
U
AR
Y
R
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
(A
TC
T)
JR
-4
A
T.
S
TE
PH
EN
SO
N
JR
-4
2A -P
-9
-0
M
ID
D
LE
E
AS
T D
IS
TR
IC
T
W
IN
C H
ES
TE
R , V
A.
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
HOT AND COLD WATER
SYSTEM RISER DIAGRAM
NO SCALE
WATER PRESSURE REDUCING VALVE (PRV) SCHEDULE
TAG
PRESSURE REQUIREMENTS
INCOMING OUTGOING
PV-3 445 kPa
PV-5 310 kPa
FLOW RATE
LPM
MAX. VELOCITY
PV-6 275 kPa19
345 kPa
220 kPa
FALL OFF
(MAX)
62 kPa
PV-7 240 kPa45
PV-8 345 kPa11
PV-9 11 380 kPa
R
EV
IS
ED
I. A
.W .A
M
EN
D M
EN
T
0 3
JA
N
2.3 MPS
2.3 MPS
2.3 MPS
2.3 MPS
2.3 MPS
2.3 MPS
55 kPa
55 kPa
55 kPa 55 kPa
55 kPa 255 kPa
290 kPa 325 kPa
185 kPa
SIZE
MM
PV-2 480 kPa11 2.3 MPS 55 kPa425 kPa 15
J
FACP
M
X HP
M
LPB-24
FAAP
FSCP
ELECTRICAL LEGEND
ABBREVIATIONS
FIRE ALARM CONTROL PANELFACPFACP
CONDUIT CONCEALED WHERE POSSIBLE.
LP3-5,6
NON-FUSED DISCONNECT SWITCH; "30A" DENOTES SWITCH
AMPERE RATING. MOUNT 1.5M AFF
S
S3
SM
SD
S
S3
SM
SD
SPS
LCA
A
ABOVE FINISHED FLOOR
AMPERE
AMPERE INTERRUPTING CAPACITY
CKT CIRCUIT
CONDUITC
CND CONDUCTOR
EP EXPLOSION PROOF
ABOVE FINISHED GRADE
GFCI
HZ HERTZ
HPS HIGH PRESSURE SODIUM
HORSEPOWERHP
GFI
AIC
AFF
AFG
HH HANDHOLE
EF EXHAUST FAN
AHU AIR HANDLING UNIT
ACCU AIR COOLED CONDENSING UNIT
GROUND FAULT INTERRUPTING
GOVERNMENT FURNISHED CONTRACTOR
INSTALLED
FO FIBER OPTIC
CE CONCRETE ENCASED
KVA KILOVOLT-AMPERE
KV KILOVOLT
M METERS
MH
PHASE
V
SN
VOLT
SOLID NEUTRAL
WIRE
TRANSFORMER
TYPICALTYP.
PLCS PLACES
KW KILOWATT
W
UNLESS NOTED OTHERWISEUNO
WEATHERPROOFWP
RM ROOM
MTD MOUNTED
PH, 0
MANHOLE
XFMR,T
TBB TELEPHONE OR DATA BACKBOARD
W/
W/O WITHOUT
WITH
GENERAL NOTES:
INCH
EQUIVALENT CONDUIT SIZE
mm
JUNCTION BOX
GROUND CONDUCTOR
GROUND ROD
WELDED GROUND CONNECTION
CIRCUIT BREAKER
TRANSFORMER
G
MOTOR, NUMBER INDICATES HP UNO
PANELBOARD (LIGHTING & POWER)
3/4
2 1/2
1 1/2 1 1/4
MH MANHOLE
THREE-WAY SWITCH (SEE NOMENCLATURE FOR SINGLE POLE SWITCH).
MANUAL MOTOR RATED SWITCH WITH THERMAL PROTECTION; "P" DENOTES RED JEWEL PILOT LIGHT.
G
SINGLE POLE SWITCH, 277V, MOUNTED 1.2 A.F.F. (EXCEPT AS NOTED), "WP" DENOTES WEATHERPROOF
SEALED HEAD BATTERY POWERED EMERGENCY LIGHT
3 1/2
MH
HH
DIMMER SWITCH (RATING AS INDICATED)
HOMERUN TO PANELBOARD. SYMBOL SHOWN INDICATES CIRCUITS NO. 5 AND 6
PNL. LP3. NUMBER OF ARROWHEADS INDICATES NUMBER OF CIRCUITS.
DUAL VOLTAGE SHAVER RECEPTACLE, 120/240 VOLT OUTPUT (W/DOUBLE WOUND ISOLATING
TRANSFORMER
EXTERIOR WALL-MOUNTED LIGHT FIXTURE,TYPE AS INDICATED,
MOUNT 2.7M ABOVE GRADE UNO
BOLTED GROUND CONNECTION, HIDDEN WITHIN OR
UNDER EQUIPMENT
POLE MOUNTED EXTERIOR LIGHT FIXTURE
120V, DUPLEX RECEPTACLE, NEMA 5-20R (AMERICAN STYLE), MOUNT .5M AFF, UNO
FIRE ALARM CONTROL PANEL
HANDHOLE
SINGLE POLE SWITCH W/PILOT LIGHT
13A, 240V, SWITCHED DUPLEX RECEPTACLE (BSI STD) MOUNT 0.5 AFF UNO.
F SUBSCRIPT INDICATES FLOOR MOUNTED, FLUSH. D SUBSCRIPT INDICATES 240V, 32A,
SWITCHED FLEX RECEPTACLE, W SUBSCRIPT INDICATES SINGLE 13A, 240V SWITCHED
RECEPTACLE. G SUBSCRIPT INDICATES GROUND FAULT INTERRUPTING (GFI)
15KV NON-FUSED LOAD INTERRUPTER SWITCH
15KV FUSED LOAD INTERRUPTER SWITCH
NUMBER OF FIXTURES AS INDICATED
ROLL-UP MOTOR / DOOR OPERATOR
HV
SV
HIGH VOLTAGE CABLE IN CONCRETE
ENCASED DUCTBANK
SECONDARY VOLTAGE CABLE IN CONCRETE
ENCASED DUCTBANK
FIRE ALARM ANNUNICIATOR PANEL
DUPLEX FLOOR BOX MOUNTED RECEPTACLE WITH TELEPHONE
FOAM SYSTEM CONTROL PANEL
LIGHTING CONTACTOR 'A'
LED LIGHT FIXTURE, TYPE AS INDICATED, SEE LIGHT FIXTURE SCHEDULE
N = NIGHT LIGHT ON UN-SWITCHED CIRCUIT, HOME RUN
EXIT SIGN, TYPE AS INDICATED. SEE LIGHT FIXTURE SCHEDULE
LED LIGHT FIXTURE, TYPE AS INDICATED. SEE LIGHT FIXTURE SCHEDULE
LED LIGHT FIXTURE, TYPE AS INDICATE. SEE LIGHT FIXTURE SCHEDULE
CABLE COLOR CODE
BROWNPHASE A
PHASE B
PHASE C
NEUTRAL
GROUND
NOTE: VERIFY COLOR CODING TO
COMPLY WITH LOCAL STANDARDS
BLACK
GRAY
BLUE
YELLOW/GREEN
! WARNING
Shock and Arc Flash Hazard Appropriate PPE Required
ARC FLASH WARNING LABEL
32A, 2P + E, 250V, IP44 SURFACE MOUNTED
SOCKET OUTLET WITH MATCHING PLUG
FOR CLOTHES DRYER
N
250V, NEMA L6-30R RECEPTACLE
(ATTACHED TO CABLE TRAY)
P POLE
A
CROSS REFERENCE
AWG TO MM2
16 1.5 14 2.5 12 4.0 10 6.0 8 10 6 16 4 25 2 35 1 50 1/0 55 2/0 70 3/0 95 4/0 120
300MCM 150
350MCM 185
500MCM 240
600MCM 300
1. ELECTRIC LEGEND IS GENERIC. NOT ALL ITEMS NOTED ARE IN THE PROJECT.
2. FINAL CIRCUIT BREAKER SETTINGS SHALL BE PER CONTRACTOR DEVELOPED AND
COR APPROVED SYSTEM COORDINATION STUDY.
3. COORDINATE FINAL LOCATION OF LIGHT FIXTURES WITH MECHANICAL EQUIPMENT
AND COMMUNICATION RACKS IN THE ROOM.
4. ALL FLOOR MOUNTED ELECTRICAL EQUIPMENT SHALL BE INSTALLED ON CONCRETE
PADS, PROTRUDING 100mm AFF.
5. MEASURED GROUND RESISTANCE SHALL BE 25 OHMS OR LESS.
6. ALL ELECTRICAL EQUIPMENT SHALL BE DESIGNED AND TESTED TO OPERATE AT 380/220V, 3P, 4W, 50HZ.
7. GROUND RING SHALL BE 120mm SQ BARE COPPER, INSTALLED 760mm BELOW GRADE, UNO.
8. MOUNT LIGHT SWITCHES 1.2M AFF, UNO.
9. MOUNT RECEPTACLES:
ALL ADMINSTRATIVE AREAS - 0.5M AFF, UNO.
ALL INDUSTRIAL & SHOP AREAS - 1.2 AFF, UNO.
10. ALL CIRCUITS SHALL CONTAIN EQUIPMENT GROUND CONDUCTOR.
11. ALL ELECTRICAL INSTALLATION SHALL BE PER NATIONAL ELECTRIC CODE NFPA 70 (NEC).
12. ALL SERVICE ENTRANCE CONDUITS / DUCTS WITH CABLES SHALL BE SEALED AT BOTH ENDS WITH APPROPRIATE SEALER. ALL EMPTY CONDUITS SHALL BE CLEANED, PROVIDED WITH PULL-WIRE
AND CAPPED.
13. ALL PANEL SCHEDULES / DIRECTORIES SHALL BE TYPED WRITTEN IN ENGLISH AND SHALL BE COMPLETE.
14. ALL CONDUIT PENETRATIONS THRU FIRE RATED WALLS SHALL BE SEALED / FIRE STOPPED.
15. ALL ELECTRICAL PANELS IN ADDITTION TO SERVICE ENTRANCE EQUIPMENT (MDP) SHALL BE PROTECTED
WITH SURGE PROTECTIVE DEVICE (SPD).
16. EMERGENCY LIGHTS (BATTERY PACKS) AND EXIT SIGNS IN EACH AREA SHALL BE CONNECTED TO THE
UNSWITCHED LEG OF THE LIGHTING CIRCUIT OF THAT RESPECTIVE AREA.
17. ALL STAIRWELL LIGHTING SHALL BE FED FROM UN-SWITCHED CIRCUITS.
18. LIGHTNING PROTECTION SYSTEM SHALL BE PER NFPA 780.
19. FLOOR MOUNTED POWER RECEPTACLES SHALL BE INSTALLED WITHIN A COMMON FLOOR BOX
FOR THE COMMUNICATIONS RECEPTACLES AND INSTALLED LOCATION SHALL BE COORDINATED
WITH THE FURNITURE PLAN FOR THAT ROOM / AREA.
20. CONTRACTOR SHALL PROVIDE A PERMANENT STENCIL ON EVERY RECEPTACLE AND LIGHT SWITCH TO INDICATE THE CORRESPONDING PANELBOARD AND CIRCUIT BREAKER THAT DEVICE IS SERVICED FROM.
21. ALL EQUIPMENT, SUCH AS, MSBs, MCCs, MDPs SHALL BE PROVIDED WITH AMP, VOLT & KWH METERING.
22. ALL RECEPTACLES IN WET AREAS PER NEC SHALL BE PROTECTED WITH 30ma GFCIs.
23. ALL UNDERGROUND AND/OR UNDER SLAB GROUND WIRE/CABLE CONNECTIONS SHALL BE EXOTHERMIC WELD.
24. COMPLETE FIRE ALARM SYSTEM DESIGN SHALL BE DESIGNED AND DEVELOPED BY A REGISTERED FIRE PROTECTION ENGINEER AND IN COMPLIANCE WITH THE REQUIREMENTS OF THE FIRE ALARM
SPECIFICATIONS PROVIDED.
25. ALL EXTERIOR MOUNTED DEVICES AND JUNCTION BOXES SHALL BE NEMA TYPE 3, MIN OR EQUIVALENT IP RATED.
26. LIGHTING FIXTURE DETAILS ARE GENERIC AND FOR INFORMATION ONLY. OPERATING VOLTAGE RATING
AND LAMP WATTAGE SHALL COMPLY WITH THE DESIGN AND LOCAL VOLTAGE RATINGS.
27. MINIMUM SIZE CONDUIT SHALL BE 20 MM (3/4"), UNO.
28. ALL LIGHTING (INTERIOR & EXTERIOR) SHALL BE LED TYPE.
29. CIRCUIT BREAKERS 1000 A AND LARGER SHALL BE PROVIDED WITH GROUND FAULT PROTECTION PER NEC.
30. PROVIDE CABLE COLOR CODE LABEL IN EACH MDP/SWITCHBOARD/PANEL.
31. PROVIDE ARC FLASH WARNING LABEL AT EACH MDP/SWITCHBOARD/PANEL.
32. WITH USE OF 4 POLE ATS GENERATOR NEUTRAL SHALL BE GROUNDED AT THE GENERATOR (SOURCE).
33. ALL ELECTRICALLY OPERATED MECHANICAL EQUIPMENT SHALL BE PROVIDED WITH DISCONNECT SWITCH IN
COMPLIANCE WITH NEC REQUIREMENTS.
US Army Corps of Engineers ®
SHEET ID
US
A
R M
Y C
O
RP
S O
F
EN
G
IN
EE
RS
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E
File Path:
Plot Date:
M
AR
K D
ES
C
R
IP
TI
O
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
PL
O
T D
AT
E:
FI
LE
N
AM
E:
US
A rm y
Co rp s of
E ng in ee rs M id dl e Ea st D is tri ct
C:\Users\N0ENFSCD\Documents\JR-474512A-E-DM-ATCT-03_N0ENFSCD.rvt
1/7/2022 10:32:33 AM
1/ 7/
:3
2:
AM
E-001
G
EN
ER
AL
L
EG
EN
D
A N
D A
BB
R
EV
IA
TI
O
N S
U D
.4
, J O
R D
AN
SE
N
AY
AT
U
LL
A
SD
O
ED
EN
M M
O
ST
AG
H
IM
FE
BR
U
AR
Y2
R
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
(A
TC
T)
JR
-4
A
T.
S
TE
PH
EN
SO
N , C
H
IE
F
JR
-4
2A -E
-0
M
ID
D
LE
E
AS
T D
IS
TR
IC
T
W
IN
C H
ES
TE
R , V
A.
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
R
EV
IS
E D I.A
.W .A
M
EN
D M
EN
T
JA
N
NOTES:
1. EXISTING ATCT: EXISTING JORDAN AIR FORCE (JAF) ATCT
SHALL REMAIN IN SERVICE, AS A BACK-UP TO THE NEW
ATCT, EVEN AFTER THE NEW ATCT BECOMES OPERATIONAL.
2. RADAR APPROACH CONTROL (RAPCON): DATA FROM
EXISTING ON-BASE RAPCON ARE RECEIVED AT THE
EXISTING JAF ATCT. CONTRACTOR SHALL BE RESPONSIBLE
TO PROVIDE AND INSTALL NECESSARY CABLES (COPPER
OR OPTIC FIBER) FROM THE EXISTING ATCT TO THE NEW
ATCT, IN ORDER TO DUPLICATE RAPCON DATA AT THE NEW
ATCT. CONTRACTOR IS EXPECTED TO USE EXISTING
AIRFIELD LIGHTING (AFL) CONTROL CABLE RACEWAY
(DUCTBANK) SYSTEM, WHICH CONNECTS ALL FOUR AFL
VAULTS (A, B, C, AND D) TO THE EXISTING ATCT,
COMMUNICATION DUCTBANK SYSTEM PROVIDED UNDER
UD 2.4-PACKAGE 2 (FLIGHTLINE) PROJECT AND THE NEW
COMMUNICATIONS DUCTBANK SYSTEM BEING PROVIDED
UNDER THIS CONTRACT. CONTRACTOR SHALL BE
RESPONSIBLE TO ENSURE THAT RAPCON DATA BEING
RECEIVED AT JAF ATCT IS ALSO RECEIVED AT THE NEW
ATCT, ACCEPTABLE TO US AIRFORCE ATCT OPERATORS.
3. AFL CONTROL CABLE: EXISTING FIBER OPTIC AFL CONTROL
CABLES CONNECT ALL FOUR AFL VAULTS (A, B, C, AND D)
TO MIMIC PANEL(S) ATJAF ATCT. CONTRACTOR SHALL BE
RESPONSIBLE TO PROVIDE AND INSTALL FIBER OPTIC AFL
CONTROL CABLE CONNECTING VAULTS A, B, C, AND D TO
A NEW AIRPORT LIGHTING CONTROL AND MONITORING
SYSTEM (ALCMS) PANEL AT THE NEW ATCT. EXISTING
AFL CONTROLS AND DISPLAYS AT JAF ATCT SHALL REMAIN
OPERATIONAL AND WOULD BE CONSIDERED AS BACK-UP
TO THE ALCMS AT THE NEW ATCT.
4. AIRPORT LIGHTING CONTROL AND MONITORING SYSTEM
(ALCMS) FAA L-890 PANEL: CONTRACTOR SHALL PROVIDE
AND INSTALL AN ADVANCE MONITORING, TOUCH SCREEN,
PLUG AND PLAY STATE OF THE ART ALCMS INSIDE THE ATCT
CAB. ALCMS SHALL DISPLAY ALL FEATURES ASSOCIATED
WITH THE UD 2.4 AIRFIELD, TO INCLUDE BUT NOT LIMITED TO,
BOTH RUNWAYS, ASSOCIATED TAXIWAYS AND APRONS.
UNIT SHALL BE PROGRAMMABLE, BE ABLE TO DISPLAY
EXISTING AND FUTURE AIRFIELD EXPANSION. ALCMS
DISPLAY SHALL BE MIN, 36 INCH (DIAGONAL). SYSTEM
SHALL COMPRISE OF COMMERCIALLY AVAILABLE, NON-
PROPRIETARY COMPONENTS. CONTRACTOR SHALL BE
RESPONSIBLE FOR PROVIDING COMPLETE AND USABLE
SYSTEM.
5. BEACON: EXISTING UD 2.4 AIRFIELD BEACON IS LOCATED
ON THE ROOF OF JAF ATCT AND SHALL REMAIN IN PLACE
AND OPERATIONAL. CONTRACTOR SHALL BE RESPONSIBLE
FOR EXTENDING BEACON CONTROLS FROM JAF ATCT TO
THE NEW ATCT CAB UTILIZING EXISTING AND NEW
COMMUNICATION RACEWAY SYSTEM BETWEEN THE TWO
ATCTS. BEACON SHALL BE ABLE TO BE OPERATED
(CONTROLLED) FROM JAF AND THE NEW ATCT.
US Army Corps of Engineers ®
SHEET ID
US
A
R M
Y C
O
RP
S O
F
EN
G
IN
EE
RS
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E
File Path:
Plot Date:
M
AR
K D
ES
C
R
IP
TI
O
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
PL
O
T D
AT
E:
FI
LE
N
AM
E:
US
A rm y
Co rp s of
E ng in ee rs M id dl e Ea st D is tri ct
C:\Users\N0ENFSCD\Documents\JR-474512A-E-DM-ATCT-03_N0ENFSCD.rvt
1/12/2022 4:52:46 PM
1/
/2
4:
:4
PM
E-002
G
EN
ER
AL
N O
TE
S
U D
.4
, J O
R D
AN
SE
N
AY
AT
U
LL
A
SD
O
ED
EN
M M
O
ST
AG
H
IM
FE
BR
U
AR
Y2
R
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
(A
TC
T)
JR
-4
A
T.
S
TE
PH
EN
SO
N , C
H
IE
F
JR
-4
2A -E
M
ID
D
LE
E
AS
T D
IS
TR
IC
T
W
IN
C H
ES
TE
R , V
A.
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
R
EV
IS
E D I.A
.W .A
M
EN
D M
EN
T
JA
N
FD
S
MS
M
J J
J
ATS
MDP
FCU-1.2
FCU-1.1
CU-1
EF-1
EF-2DOMESTIC WATER
BOOSTER PUMP
LP1-7
LP
T
LP1-9
LP1-11
LP1-30
LP1-28
MDP-10
LP1-26
LP1-15
LP1-13
LP13-2 LP13-4
LP13-6
LP13-8
FA
C
P
LP13
INSTALL 2-50mm EMPTY CONDUITS
WITH PULL WIRE FROM PANEL TO
BELOW RAISED FLOOR.
LP13-10
MDP-11
LP
MDP-3
MECH
ELEC
INTERIOR
LOBBY
STAIR
TOILET
EXTERIOR
LOBBY
RAPCON
FIRE
COMMAND
LP1-27
LP13-11
LP1-29
LP13-14
LP13-9
LP1-17
EWH-2
LP13-12
(MT. 0.5M
BELOW CEILING)
CCTV
P-1, P-2
LP1-14LP1-20
M
LP1-19
SP-1
SERVICE
ENTRANCE
CIRCUIT BREAKER
A
A
B
B
RECESSED
PULL BOX
WITH HINDGED
COVER (TYP 2)
E-108
E-108
Sim
C D
LP13
RACU-1
RACU-2
LP13-20
LP1-35
LP1-33
LP1-31
WH-3
WH-2
WH-1
ELEV
COMM
DOOR STRIKE
PWR. MT. ABOVE
CEILING. TYP 3 LOC.
FCU-2 SPF-1
LP2
LP2-2
LP3-1
LP2-4
LP2-8
LP2-7
CONF
LOBBY
STAIR
COMM/ELEC
A B
C D
ELEV
FIRST FLOOR
SECOND FLOOR
DROP CEILING
RAISED FLOOR
4-50mm EMPTY CONDUITS
WITH PULL WIRE
(TYP TOP AND BOTTOM)
PULL BOX NOTE:
INSTALL RECESSED PULL BOX WITH HINDGED
COVER 600mm H, 400mm W, 100mm DEEP, 1.5M AFF.
PROVIDE 4-50mm EMPTY CONDUITS RUNS TO ABOVE
DROP CEILING AND BELOW RAISED FLOOR.
US Army Corps of Engineers ®
SHEET ID
US
A
R M
Y C
O
RP
S O
F
EN
G
IN
EE
RS
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E
File Path:
Plot Date:
M
AR
K D
ES
C
R
IP
TI
O
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
PL
O
T D
AT
E:
FI
LE
N
AM
E:
US
A rm y
Co rp s of
E ng in ee rs M id dl e Ea st D is tri ct
C:\Users\N0ENFSCD\Documents\JR-474512A-E-DM-ATCT-03_N0ENFSCD.rvt
1/12/2022 1:38:19 PM
1/
/2
1:
:1
PM
E-108
FI
R
ST
A
N D
S
EC
O N
D F
LO
O
R P
O W
ER
P
LA
N
S
U D
.4
, J O
R D
AN
SE
N
AY
AT
U
LL
A
SD
O
ED
EN
M M
O
ST
AG
H
IM
FE
BR
U
AR
Y2
R
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
(A
TC
T)
JR
-4
A
T.
S
TE
PH
EN
SO
N , C
H
IE
F
JR
-4
2A -E
-1
M
ID
D
LE
E
AS
T D
IS
TR
IC
T
W
IN
C H
ES
TE
R , V
A.
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
1 : 501 FIRST FLOOR POWER PLAN
1 : 502 SECOND FLOOR POWER PLAN
N.T.S.3 PULL BOX SECTION
1:50
5m1m 4m3m2m0m
R
EV
IS
E D I.A
.W .A
M
EN
D M
EN
T
JA
N
LP11-4
LP11-6
MDP-8
LP11 LP11-2
MECH
LP11-8
DOAU-1
AHU-1
AHU-2
STACKED
UNITS
LP11-20 LP11-14 LP11-11
EF-7
A B
C D
M Sw
M Sw
LP11-26
EF
-8
M Sw
LP11-28
EF-5
STAIRWAY
MECH
LP12
A B
LP12-6
LP12-17 CCTV
C D
MDP-9DOOR STRIKE
PWR. MT. ABOVE
DOOR HEIGHT
US Army Corps of Engineers ®
SHEET ID
US
A
R M
Y C
O
RP
S O
F
EN
G
IN
EE
RS
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E
File Path:
Plot Date:
M
AR
K D
ES
C
R
IP
TI
O
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
PL
O
T D
AT
E:
FI
LE
N
AM
E:
US
A rm y
Co rp s of
E ng in ee rs M id dl e Ea st D is tri ct
C:\Users\N0ENFSCD\Documents\JR-474512A-E-DM-ATCT-03_N0ENFSCD.rvt
1/12/2022 1:54:00 PM
1/
/2
1:
:0
PM
E-113
EL
EV
EN
TH
F
LO
O R
A N
D B
AL
C
O N
Y
PO
W
ER
P
LA
N S
U D
.4
, J O
R D
AN
SE
N
AY
AT
U
LL
A
SD
O
ED
EN
M M
O
ST
AG
H
IM
FE
BR
U
AR
Y2
R
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
(A
TC
T)
JR
-4
A
T.
S
TE
PH
EN
SO
N , C
H
IE
F
JR
-4
2A -E
-1
M
ID
D
LE
E
AS
T D
IS
TR
IC
T
W
IN
C H
ES
TE
R , V
A.
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
1 : 501 ELEVENTH FLOOR POWER PLAN
1 : 502 BALCONY POWER PLAN
1:50
5m1m 4m3m2m0m
R
EV
IS
E D I.A
.W .A
M
EN
D M
EN
T
JA
N
ATCT ELECTRIC ROOM 1ST FLOOR (RM. 102)
250AT
400 AF
250AT
400 AF
60AT
100AF
80AT
100 AF
80AT
100 AF
2000A,380/220V, 3 PH, 4W, 50 HZ, 30,000 AIC BUS
1 2 3 4 5
CH-1 CH-2 LP1
(1ST
FLOOR)
LP3
(3RD
FLOOR)
TOTAL EST. CONN. LOAD : 715.2 KVA
TOTAL EST. DEM. LOAD : 643.7 KVA
150AT
225 AF
6 7 8
LP8
(8TH
FLOOR)
LP6
(6TH
FLOOR)
9 10 11 12 13
SP
AC
E
LP9
(9TH
FLOOR)
LP11
11TH
FLOOR)
LP12
(CAB)
LPT
(COMM
1ST
FLOOR)
LP13
CONF.
ROOM
(1 ST
FLOOR)
100AT
125 AF
14 15 16
1400AT
2000 AF
A B C D E F G H I J K
200AT
225 AF
175AT
225 AF
50AT
100 AF
40AT
100 AF
SPD
NOTE 2
G
TO UDS T3-11
(1000KVA,
11KV - 380/220V,
3P, 4W, 50HZ)
GENERATOR (STAND-BY)
750 KVA,380/220V, 3 P,4W, 50HZ
SKID MOUNTED, WEATHERPROOF
ENCLOSURE WITH DAY TANK
LP2
(2ND
FLOOR)
(14.6 KVA)
LP4
(4TH
FLOOR)
(14.4 KVA)
LP5
(5TH
FLOOR)
(15.7 KVA)
LP10
(10TH
FLOOR)
(12.6 KVA)
ATS
4P- 1600A
(RM. 102)
400A
NEMA 3
(142 KVA)
400A
NEMA 3
(142 KVA)
LP7
(7TH
FLOOR)
(10.6 KVA)
LOWER
EQUIPT.
ROOM
UPPER
EQUIPT.
ROOM
RAPCON
1500AT
2000 AF
MAIN DISTRIBUTION PANEL (MDP)
(SWITCHBOARD)
4 SETS:
(4-240MM SQ +
1-120MM SQ G
IN 4-103MM C
+ 2-103MM C SPARE)
4-16MM SQ +1 -6MM
SQ G IN 27MM C
4-10MM SQ + 1-6MM
SQ G IN 20MM C
4-10MM SQ + 1-6MM
SQ G IN 20MM C
4-10MM SQ + 1-6MM
SQ G IN 20MM C
4-10MM SQ + 1-6MM
SQ G IN 20MM C
VD
.0
VD
.0
VD
.2
SP
AC
E
SP
AC
E
SP
AC
E
SP
AC
E
NOTE 6
NOTE 7
MDP FEEDER CABLE SCHEDULE
FDR # EQUIP. CABLE AND CONDUIT SIZE
A
B
C
D
E
F
G
H
I
J
K
CH-1 3-240MM SQ + 1-25MM SQ G IN 103MM C
CH-2 3-240MM SQ + 1-25MM SQ G IN 103MM C
LP1 4-35MM SQ +1-10MM SQ G IN 35MM C
LP3 4-35MM SQ +1-10MM SQ G IN 35MM C
LP6
LP8
LP9
LP11
LP12
LP-T
LP13
4-35MM SQ +1-10MM SQ G IN 35MM C
4-70MM SQ +1-25MM SQ G IN 53MM C
4-150MM SQ +1-25MM SQ G IN 78MM C
4-120MM SQ +1-16MM SQ G IN 63MM C
4-25MM SQ +1-6MM SQ G IN 35MM C
4-10MM SQ +1-6MM SQ G IN 20MM C
4-55MM SQ +1-16MM SQ G IN 53MM C
35.5
35.8
31.6
52.0
90.2
65.8
28.5
9.6
54.8
DEM
KVA
US Army Corps of Engineers ®
SHEET ID
US
A
R M
Y C
O
RP
S O
F
EN
G
IN
EE
RS
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E
File Path:
Plot Date:
M
AR
K D
ES
C
R
IP
TI
O
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
PL
O
T D
AT
E:
FI
LE
N
AM
E:
US
A rm y
Co rp s of
E ng in ee rs M id dl e Ea st D is tri ct
C:\Users\N0ENFSCD\Documents\JR-474512A-E-DM-ATCT-03_N0ENFSCD.rvt
1/7/2022 10:44:39 AM
1/ 7/
:4
4:
AM
E-602
O N
E
LI
N E
D
IA
G R
AM
U D
.4
, J O
R D
AN
SE
N
AY
AT
U
LL
A
SD
O
ED
EN
M M
O
ST
AG
H
IM
FE
BR
U
AR
Y2
R
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
(A
TC
T)
JR
-4
A
T.
S
TE
PH
EN
SO
N , C
H
IE
F
JR
-4
2A -E
-6
M
ID
D
LE
E
AS
T D
IS
TR
IC
T
W
IN
C H
ES
TE
R , V
A.
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
N.T.S.1 POWER ONE LINE DIAGRAM
NOTES:
1. REFER TO SHEET E-001 FOR LEGEND AND GENERAL NOTES.
2. INSTALL SPD PER MANUFACTURERS INSTRUCTIONS.
3. INSTALL ARC FLASH HAZARD SIGN ON OUTSIDE OF MDP.
4. MDP SHALL BE PROVIDED WITH KWH METERING TO INCLUDE
VOLTMETER, AMPMETER, POWER FACTOR METER, WATT METER
AND WATT HOUR METER.
5. PROVIDE FRAMED MDP ONE LINE DIAGRAM IN ELECTRIC ROOM.
6. CONTRACTOR'S OPTION: SERVICE ENTRANCE RATED ATS WITH
BUILT-IN CIRCUIT BREAKER MAY BE PROVIDED IN PLACE OF A
SEPARATE CIRCUIT BREAKER, PROVIDED IT COMPLIES WITH MEANS
OF DISCONNECT REQUIREMENTS PER NEC.
7. PROVIDE ARC FLASH REDUCTION PER NFPA 70, ART 240.87.
R
EV
IS
E D I.A
.W .A
M
EN
D M
EN
T
JA
N
C
KT
N
O
. TRIP
AMPS
N O
PO
LE
S
LOAD SERVED LOAD-V.A.
A0 B0 C0
LOAD-V.A.
A0 B0 C0
LOAD SERVED
PANELBOARD MOUNTED
AMP. MAIN LUGS (OR) AMP. TRIP
CIRCUIT BREAKER TYPE VOLTS PHASE WIRE
TOTAL CONN. LOAD KVA. % DEMAND = ESTIMATED DEMAND LOAD
TOTAL CONN. LOAD
PER PHASE (KVA): A0 B0 C0
WIRE
MM²
CONDUIT
MM C
KT
N O
.TRIP
AMPS
N O
PO
LE
SWIRE
MM²
CONDUIT
MM
GND
MM²
AMP. BUS
GND
MM²
HZ
SYM. A.I.C. MIN.
SUPPLIED FROM:KVA
AMP. MAIN BREAKER W/
WALL
380/220 3 4 50
350 16 6 27
3RD FLOOR
MDP
10,000LP3
LP2 (2ND FLOOR)
LIGHTING120 4 4 20
LIGHTING120 4 4 20
LIGHTING120 4 4 20
EWH-3130 6 6 20
LP4 (4TH FLOOR)
RECEPTACLES (303)
RECEPTACLES (103)
RECEPTACLES (TOILET)
FCU-3
420 4 1 20
420 4 1 20
420 4 1 20
620 6 1 30
SPARE 1 20_ _ _2000
2000 SPARE 1 20_ _ _
SPARE
SPARE
47.5 80
8516 7166 7366 9000 7600 7000
38.0
18.3 14.8 14.4
20 6 10 3 30
SPACE SPACE
C
KT
N
O
. TRIP
AMPS
N O
PO
LE
S
LOAD SERVED LOAD-V.A.
A0 B0 C0
LOAD-V.A.
A0 B0 C0
LOAD SERVED
PANELBOARD MOUNTED
AMP. MAIN LUGS (OR) AMP. TRIP
CIRCUIT BREAKER TYPE VOLTS PHASE WIRE
TOTAL CONN. LOAD KVA. % DEMAND = ESTIMATED DEMAND LOAD
TOTAL CONN. LOAD
PER PHASE (KVA): A0 B0 C0
WIRE
MM²
CONDUIT
MM C
KT
N O
.TRIP
AMPS
N O
PO
LE
SWIRE
MM²
CONDUIT
MM
GND
MM²
AMP. BUS
GND
MM²
HZ
SYM. A.I.C. MIN.
SUPPLIED FROM:KVA
AMP. MAIN BREAKER W/
WALL
380/220 3 4 50
120 4 4 20
2ND FLOOR
LP3
10,000LP2
120 4 4 20
LIGHTING
LIGHTING
LIGHTING120 4 4 20
SFP-1
1200 RECEPTACLES
RECEPTACLES
RECEPTACLES
FCU-2
20 204 4 1
20 204 4 1
20 204 4 1
20 306 6 120 4 4 20 1000
SPARE2000
2000 SPARE
SPARE_ _ _ 2000
SPARE_ _ _
SPARE_ _ _
21.1 80
3150 3600 3450 5200 2800 2800
16.9
8.4 6.4 6.3
SPACE
SPACE
US Army Corps of Engineers ®
SHEET ID
US
A
R M
Y C
O
RP
S O
F
EN
G
IN
EE
RS
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E
File Path:
Plot Date:
M
AR
K D
ES
C
R
IP
TI
O
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
PL
O
T D
AT
E:
FI
LE
N
AM
E:
US
A rm y
Co rp s of
E ng in ee rs M id dl e Ea st D is tri ct
C:\Users\N0ENFSCD\Documents\JR-474512A-E-DM-ATCT-03_N0ENFSCD.rvt
1/7/2022 10:45:33 AM
1/ 7/
:4
5:
AM
E-605
PA
N
EL
S
C H
ED
U
LE
S
U D
.4
, J O
R D
AN
SE
N
AY
AT
U
LL
A
SD
O
ED
EN
M M
O
ST
AG
H
IM
FE
BR
U
AR
Y2
R
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
(A
TC
T)
JR
-4
A
T.
S
TE
PH
EN
SO
N , C
H
IE
F
JR
-4
2A -E
-6
M
ID
D
LE
E
AS
T D
IS
TR
IC
T
W
IN
C H
ES
TE
R , V
A.
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
R
EV
IS
E D I.A
.W .A
M
EN
D M
EN
T
JA
N
C
KT
N
O
. TRIP
AMPS
N O
PO
LE
S
LOAD SERVED LOAD-V.A.
A0 B0 C0
LOAD-V.A.
A0 B0 C0
LOAD SERVED
PANELBOARD MOUNTED
AMP. MAIN LUGS (OR) AMP. TRIP
CIRCUIT BREAKER TYPE VOLTS PHASE WIRE
TOTAL CONN. LOAD KVA. % DEMAND = ESTIMATED DEMAND LOAD
TOTAL CONN. LOAD
PER PHASE (KVA): A0 B0 C0
WIRE
MM²
CONDUIT
MM C
KT
N O
.TRIP
AMPS
N O
PO
LE
SWIRE
MM²
CONDUIT
MM
GND
MM²
AMP. BUS
GND
MM²
HZ
SYM. A.I.C. MIN.
SUPPLIED FROM:KVA
AMP. MAIN BREAKER W/
WALL
380/220 3 4 50
120 4 4 20
4TH FLOOR
LP3
10,000LP4
120 4 4 20
120 4 4 20
LIGHTING
LIGHTING
LIGHTING
SPF-2
1000 RECEPTACLES
RECEPTACLES
RECEPTACLES
FCU-4
20 204 4 1
20 204 4 1
20 204 4 1
20 306 6 120 4 4 20 1000
SPARE
SPARE
SPARE
SPARE
SPARE120
20.8 80
3150 3250 3450 5000 2800 3000
16.6
8.2 6.1 6.5
SPACE
SPACE
C
KT
N
O
. TRIP
AMPS
N O
PO
LE
S
LOAD SERVED LOAD-V.A.
A0 B0 C0
LOAD-V.A.
A0 B0 C0
LOAD SERVED
PANELBOARD MOUNTED
AMP. MAIN LUGS (OR) AMP. TRIP
CIRCUIT BREAKER TYPE VOLTS PHASE WIRE
TOTAL CONN. LOAD KVA. % DEMAND = ESTIMATED DEMAND LOAD
TOTAL CONN. LOAD
PER PHASE (KVA): A0 B0 C0
WIRE
MM²
CONDUIT
MM C
KT
N O
.TRIP
AMPS
N O
PO
LE
SWIRE
MM²
CONDUIT
MM
GND
MM²
AMP. BUS
GND
MM²
HZ
SYM. A.I.C. MIN.
SUPPLIED FROM:KVA
AMP. MAIN BREAKER W/
WALL
380/220 3 4 50
5TH FLOOR
LP6
10,000LP5
120 4 4 20
120 4 4 20
120 4 4 20
LIGHTING
LIGHTING
LIGHTING
FCU-5
600 RECEPTACLES
RECEPTACLES
RECEPTACLES
EWH-1
20 204 4 1
20 204 4 1
20 204 4 1
27 506 16 3
120 4 4 20 3200
RECEPTACLES 20 204 4 1
SPARE120
SPARE120
_ _2000
SPARE
SPARE
40.6 80
3350 2300 2300 10200 11200 11200
32.5
13.6 13.5 13.5
SPACE
SPACE
US Army Corps of Engineers ®
SHEET ID
US
A
R M
Y C
O
RP
S O
F
EN
G
IN
EE
RS
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E
File Path:
Plot Date:
M
AR
K D
ES
C
R
IP
TI
O
N
UNLESS OTHERWISE NOTED, LINEAR
DIMENSIONS SHOWN ARE IN MILLIMETERS.
PL
O
T D
AT
E:
FI
LE
N
AM
E:
US
A rm y
Co rp s of
E ng in ee rs M id dl e Ea st D is tri ct
C:\Users\N0ENFSCD\Documents\JR-474512A-E-DM-ATCT-03_N0ENFSCD.rvt
1/7/2022 10:46:21 AM
1/ 7/
:4
6:
AM
E-606
PA
N
EL
S
C H
ED
U
LE
S
U D
.4
, J O
R D
AN
SE
N
AY
AT
U
LL
A
SD
O
ED
EN
M M
O
ST
AG
H
IM
FE
BR
U
AR
Y2
R
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
(A
TC
T)
JR
-4
A
T.
S
TE
PH
EN
SO
N , C
H
IE
F
JR
-4
2A -E
-6
M
ID
D
LE
E
AS
T D
IS
TR
IC
T
W
IN
C H
ES
TE
R , V
A.
AI
R
T R
AF
FI
C C
O N
TR
O
L
TO
W
ER
R
EV
IS
E D I.A
.W .A
M
EN
D M
EN
T
JA
N
C
KT
N
O
. TRIP
AMPS
N O
PO
LE
S
LOAD SERVED LOAD-V.A.
A0 B0 C0
LOAD-V.A.
A0 B0 C0
LOAD SERVED
PANELBOARD MOUNTED
AMP. MAIN LUGS (OR) AMP. TRIP
CIRCUIT BREAKER TYPE VOLTS PHASE WIRE
TOTAL CONN. LOAD KVA. % DEMAND = ESTIMATED DEMAND LOAD
TOTAL CONN. LOAD
PER PHASE (KVA): A0 B0 C0
WIRE
MM²
CONDUIT
MM C
KT
N O
.TRIP
AMPS
N O
PO
LE
SWIRE
MM²
CONDUIT
MM
GND
MM²
AMP. BUS
GND
MM²
HZ
SYM. A.I.C. MIN.
SUPPLIED FROM:KVA
AMP. MAIN BREAKER W/
WALL
380/220 3 4 50
6TH FLOOR
MDP
10,000LP6
A0
120 4 4 20
120 4 4 20
LP5 (5TH FLOOR)
LIGHTING
LIGHTING
LP7 (7TH FLOOR)
RECEPTACLES
RECEPTACLES
SPARE
20 204 4 1
20 204 4 1
_ 20120 4 4 20 LIGHTING
130 6 6 20 FCU-6
SPARE
SPARE
10833 3533
10833
10833
SPARE2000 _ _
59.1 80
12183 13083 13283 5733 5533 6533
47.3
20.7 18.6 19.8
35 10 6 20
20 6 10 40
SPACE SPACE
SPARE
SPARE
C
KT
N
O
. TRIP
AMPS
N O
PO
LE
S
LOAD SERVED LOAD-V.A.
A0 B0 C0
LOAD-V.A.
A0 B0 C0
LOAD SERVED
PANELBOARD MOUNTED
AMP. MAIN LUGS (OR) AMP. TRIP
CIRCUIT BREAKER TYPE VOLTS PHASE WIRE
TOTAL CONN. LOAD KVA. % DEMAND = ESTIMATED DEMAND LOAD
TOTAL CONN. LOAD
PER PHASE (KVA): A0 B0 C0
WIRE
MM²
CONDUIT
MM C
KT
N O
.TRIP
AMPS
N O
PO
LE
SWIRE
MM²
CONDUIT
MM
GND
MM²
AMP. BUS
GND
MM²
HZ
SYM. A.I.C. MIN.
SUPPLIED FROM:KVA
AMP. MAIN BREAKER W/
WALL
380/220 3 4 50
7TH FLOOR
LP6
10,000LP7
A0
120 4 4 20
120 4 4 20
120 4 4 20
LIGHTING
LIGHTING
LIGHTING
RECEPTACLES
RECEPTACLES
RECEPTACLES
20 204 4 1
20 204 4 1
20 204 4 1
120 4 4 20 LIGHTING
201___SPARE500
201___SPARE
201___SPARE
FCU-7
SPARE___
15.2 80
650 4250 2450 1700 3000 3000
12.2
2.4 7.3 5.5
6 6 20
SPACE SPACE
US Army Corps of Engineers ®
SHEET ID
US
A
R M
Y C
O
RP
S O
F
EN
G
IN
EE
RS
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
G
2 3 4 5 6 7 8 9 10
F
E
D
C
B
A
D
AT
E
File Path:
Plot Date:
M
AR
K D
ES
C