Contract 27975 – Water Control Structure Underwater Inspection: S – 252D Culvert Underwater
UW-1
S-252D Inspection Underwater Component
1. Underwater Inspection Summary & Recommendations
The underwater inspection was led by Mary Ellen Maurer, P.E., of Infrastructure Engineers on February 3, 2015.
The Overall Inspection Rating – Underwater Component:
C-3: There are nine C-3 deficiencies that need monitoring.
1. The pipe culvert has up to 100% coating failure and moderate corrosion with flaking up to 1/16” throughout.
2. The barrel ends have knife edging.
3. Perforations are present at the pipe ends, up to 3’ long by 2’ wide.
4. The gate coating is failing and areas of light surface corrosion up to 1” in diameter are present.
5. The staff gauge and hardware have surface corrosion, pitting up to 1/16”, and section loss up to 1/16”.
6. The steel cross beams beneath the stilling well walkway have corrosion, coating failure and minor pitting up to 1/32”.
7. The timber walkway hardware has corrosion and up to 30% section loss.
8. The steel cross bracing hardware has moderate corrosion and up to 10% section loss.
9. The top of the barrel on the west side, behind the gate has corrosion and perforations up to 1/4” in diameter.
UW-2
Explanation of Recommendations – Underwater Component:
1. US51/DS 51/US 114/US115/DS115/US 151, C-3: Clean and coat all corroded areas.
2. US51/DS 51/ US115/DS115, C-3: Repair/replace knife edged areas.
3. US51/DS 51/ US115/DS115, C-3: Repair/replace perforated areas.
4. US 151, C-3: Clean gate of corrosion and coat.
5. US 60/DS 60, C-3: Clean and coat corroded areas of staff gauge.
6. US 114, C-3: Clean and coat steel cross bracing.
7. US 59, C-3: Clean and coat timber walkway hardware.
8. US 59, C-3: Clean and coat steel bracing connection hardware.
9. US 51, C-3: Clean and coat corroded areas of barrel, repair/replace perforations.
Approach:
The recommendations above may require dewatering.
UW-3
2. Water Elevations
During the underwater inspection, the water elevations were as follows:
Headwater = 26.25’ NGVD Tailwater = 26.1’ NGVD
3. Project Team
The underwater inspection team was led by Mary Ellen Maurer, P.E. The project personnel, their organization, and their responsibilities are as follows:
Individual Company Role Responsibilities
Mary Ellen Maurer, P.E. Infrastructure Engineers Inc.
Professional Engineer
Oversee team & work products
Taylor White, E.I.,C.B.I. Infrastructure Engineers Inc.
Dive Supervisor Monitor diver & dive equipment
Kyle Rankin, C.B.I. Infrastructure Engineers Inc.
Diver 1 Perform dive inspection
Bill Gehry Infrastructure Engineers Inc.
Diver 2 (standby) Standby for dive inspection
David Stump Jr.,E.I. Infrastructure Engineers Inc.
Dive Tender Tend to lines for diver
Bumpy Courson Florida Trophy Gator
Alligator Trapper Provide protection for diver
Melissa Courson Florida Trophy Gator
Alligator Trapper Provide protection for diver
UW-4
4. Rating Scales
Rating Scale used for the Overall Structure Rating
The overall structure is rated from C-1 to C-5 Critical, based on the impact and extent of the deficiencies, and on the timeframe and involvement of the recommended corrective actions.
Overall Rating
Description for the Overall Structure Application
C1 All old deficiencies noted from the previous inspection have been corrected.
Applied when no further action is recommended for the structure.
C2 Most old deficiencies noted from the previous inspection have been corrected.
Applied when the overall recommendation is to monitor minor deficiencies. Deficiencies will generally be re-evaluated at the next five-year inspection of the structure.
C3 Deficiencies have been identified and/or several old deficiencies noted in the last inspection have not been corrected.
Applied when the overall recommendation is to correct deficiencies.
C4 Serious deficiencies exist that if not immediately corrected may lead to or cause deterioration of the structure.
Applied when the overall recommendation is to correct serious deficiencies that if not corrected in a timely manner will impact the operation of the structure.
C5 Major deficiencies exist such that the structural integrity of the structure will not likely withstand a major flood event.
Applied when the overall recommendation is to correct major deficiencies as soon as possible to restore structural integrity.
C5 Critical
Emergency deficiencies exist that must be addressed immediately. Deficiencies include those that impede operation of the structure or jeopardize public safety.
Applied when immediate repairs are recommended in order to restore operational capability or address public safety issues.
Generally the District would respond by dispatching its Field Station personnel to triage the deficiency (e.g., block access to the structure, reduced structure operating capacity) until repairs can be performed. Responding District design engineers would be altered to fast-track repairs if triage does not ameliorate the deficiencies.
Rating Scale used for Individual Deficiencies for a Structure:
C-1 = No Deficiencies Noted
C-2 = Monitor condition at next dive inspection, in five (5) years.
C-3 = Schedule repair/replacement, for routine items.
C-4 = Schedule repair/replacement, for safety items, or items that will hinder operation if not corrected.
C-5 = Repair/replace immediately, for structural items.
C-5 Critical = Repair/replace immediately, for operational items.
UW-5
5. Site Drawing The location(s) are marked in RED for each deficiency, C-2 and higher, identified from the underwater inspection of the structure. A legend is provided in RED listing the unique item number, C-rating (from C-5 Critical down to C-2), finding number & finding name.
Legend Item C-
Rating Finding No.
Finding Name
1 C-3 US 51
DS 51
Pipe Coating Failure
2 C-3 DS 51 Knife Edging
3 C-3 US 51
DS 51
Corrosion and Flaking
4 C-3 US 51
DS 51
Perforations
Rating Finding No.
Finding Name
5 C-3 US 151 Gate coating failure and surface corrosion
6 C-3 US 60
DS 60
Staff gauge corrosion
7 C-3 US 114 Corrosion and pitting on bracing
Rating Finding No.
Finding Name
8 C-3 US 59 Section loss and corrosion timber hardware
9 C-3 US 51 Bracing hardware corrosion
UW-6
6. Detailed Inspection Log
Findings and recommendations for elements rated C-3 and higher are detailed below.
Checklist No.:
US51/DS 51 – Coating Failure and surface corrosion
C-Rating:
C-3
Photo Description:
Coating failure and surface corrosion with flaking
Deficiency: The pipe interior/exterior has 100% coating failure and moderate corrosion.
Probable Cause: This deficiency is most likely due to exposure to an aggressive environment.
Recommendation: Clean and coat
UW-7
US51/DS51–
Perforations/Knife edging
C-Rating:
C-3
Photo Description:
Perforations and knife edging on barrel.
Deficiency: The barrel ends have knife edging and perforations on the top portion of the barrel from the 10 o’ clock position to the 1 o’ clock position, up to 3’ long by 2’ wide.
Probable Cause: This deficiency is most likely due to exposure and wear.
Recommendation: Repair/replace barrel ends
UW-8
US 151 – Coating Failure and Corrosion
C-Rating:
C-3
Photo Description:
Coating failure and corrosion on gate.
Deficiency: The gate surface has less than 5% coating failure and corrosion up to 1” in diameter.
Probable Cause: This deficiency is most likely due to exposure to an aggressive
Recommendation: Clean and coat the affected areas.
UW-9
US 60/DS 60 -
Corrosion
C-Rating:
C-3
Photo Description:
Corrosion on staff gauge.
Deficiency: The staff gauges and hardware have moderate surface corrosion with pitting up to 1/16” and section loss up to 1/16”.
Probable Cause: This deficiency is most likely due to exposure to an aggressive
UW-10
US 114 – Corrosion and pitting
C-Rating:
C-3
Photo Description:
Corrosion and pitting on steel cross bracing.
Deficiency: The timber walkway steel cross bracing has coating failure, light surface corrosion, and pitting up to 1/32”
Probable Cause: This deficiency is most likely due to exposure to an aggressive
UW-11
US 59 – Section loss and Corrosion
C-Rating:
C-3
Photo Description:
Corrosion and section loss on timber hardware.
Deficiency: The stilling well timber walkway hardware has moderate surface corrosion and up to 30% section loss.
Probable Cause: This deficiency is most likely due to exposure to an aggressive
UW-12
US 51 – Corrosion
C-Rating:
C-3
Photo Description:
Corrosion on bracing hardware.
Deficiency: The timber walkway bracing hardware has moderate corrosion.
Probable Cause: This deficiency is most likely due to exposure to an aggressive
UW-13
US 51 – Corrosion and perforations
C-Rating:
C-3
Photo Description:
Corrosion and perforations.
Deficiency: The barrel area behind the gate has surface corrosion and perforations up to ¼” in diameter.
Probable Cause: This deficiency is most likely due to exposure to an aggressive
7. Underwater Inspection Checklist
Underwater Field Notes
Structure: Distance US inspected: 50 feet
Date(s): Distance DS inspected: 50 feet
Start Time(s): Headwater Elevation: 26.25 NGVD
Finish Time(s): Tailwater Elevation: 26.1 NGVD
Overall Structure Rating: 3
Underwater Summary:
UPSTREAM:
Checklist Finding # C-Rating
Video
Real
Time Deficiency Probable Cause
Recommended
Corrective
Actions
US1 Slope Degradation/Stability
No Deficiencies Noted null null
US2 Condition of Rip-Rap (Loose/Seated)
No Deficiencies Noted null null
US3 Exposed Erosion Control Fabric (C1 if not exposed)
No Deficiencies Noted null null
US4 Evidence of Stone Displacement (For bedding stone) N/A
None by Design null null
US5 Channel Stabilization and Erosion Control 1 No Deficiencies Noted null null
US50 Structure-General Concrete Condition (Out of all concrete members at the structure, state which ones have deficiencies, and which are fine)
N/A
None by Design null null
a. Concrete Chemical Reaction (Sulfate attack?)
N/A Null null null
b. Concrete Cracks N/A Null null null
c. Concrete Spalling (Is rebar exposed?)
N/A Null null null
d. Concrete Structural Integrity N/A Null null null
e. Exposed Rebar Corrosion N/A Null null null
f. Offset (relative movement of opposing sides) N/A Null null null
g. Scaling N/A
Null null null
h. Undermining N/A Null null null
US51 Structure-General Metal Condition (Out of all metal members at the structure, state which ones have deficiencies, and which are fine) 3 13:04:20/
14:04:50
The barrel has coating failure throughout, surface corrosion and flaking up to 1/16", as well as knife edging and perforations at the barrel ends.
Exposure to an aggressive environment
Clean and coat affected areas
S-252D
2/3/2015
Finding Name
Underwater-Upstream Erosion Control
Underwater-Upstream General
UW-13
Checklist Finding # C-Rating
Video
Real
Time Deficiency Probable Cause
Recommended
Corrective
ActionsFinding Name
Underwater-Upstream Erosion Control a. Corrosion
Moderate with flaking up to 1/16"
Exposure to an aggressive environment
Clean and coat affected areas
b. Offset (relative movement of opposing sides) N/A null null null
c. Section Loss
Up to 3'W by 2'L, 100% loss in isolated areas up to 20' from the barrel ends
Exposure to an aggressive environment
Repair
d. Undermining N/A null null null
US52 Structure-General Timber Condition (Out of all timber members at the structure, state which ones have deficiencies, and which are fine)
None by design null null
a. Offset (relative movement of opposing sides) N/A Null null null
b. Pile Caps N/A Null null null
c. Rot N/A Null null null
d. Splitting N/A Null null null
e. Undermining N/A Null null null
US53 Structural Joints (e.g. Bolts, Welds)
No Deficiencies Noted null null
US54 Stop Log/Flashboard Channels (Including stop logs & flashboards) N/A None by Design null null
US55 Settlement (Settlement of structure?) N/A None by Design null null
US56 Shoaling/Scour (Shoaling=deposit of mat'l; Scour=removal of mat'l) N/A
None by Design null null
a. Shoaling/Scour Depth and Dimensions N/A Null null null
b. Upstream Foundation/Headwall N/A Null null null
c. Upstream Headway (Shoaling) N/A Null null null
d. Wingwalls N/A Null null null
US57 Fouling/Marine Growth N/A
None by Design null null
a. Type, Consistency, Thickness N/A Null null null
US58 Debris N/A
None by Design null null
US59 Stilling Wells (If 'NA', Why?)
3 13:54:55
Moderate surface corrosion and section loss of timber hardware. Light surface corrosion, pitting, and coating failure on steel cross bracing.
Exposure to an aggressive environment
Clean and coat affected areas
a. Corrosion, Joint Damage N/A null null null
UW-14
Real
Time Deficiency Probable Cause
Recommended
Corrective
ActionsFinding Name
Underwater-Upstream Erosion Control b. General Condition N/A null null null
c. Stilling Well Pier-Connections N/A null null null
d. Stilling Well Pier-Support (Support posts)
Moderate surface corrosion and section loss of timber hardware. Light surface corrosion, pitting, and coating failure on steel cross bracing.
Exposure to an aggressive environment
Clean and coat affected areas
e. Stilling Well Intake Lines (Stilling well pipes) N/A null null null
US60 Underwater Controls/Instruments
3 13:48:10
Moderate surface corrosion on staff gauge steel mount and hardware, with pitting and section loss up to
1/16"
Exposure to an aggressive environment
Clean and coat affected areas
a. Fastening System in Suitable Condition
3 13:48:10
Moderate surface corrosion on staff gauge steel mount and hardware, with pitting and section loss up to
1/16"
Exposure to an aggressive environment
Clean and coat affected areas
b. Proper Location and Alignment N/A Null null null
US61 Fenders (Fenders for structure;
e.g. for boat locks) N/A None by Design null null
US100 Wingwalls N/A
None by Design null null
US101 Buttresses (Support arms for wall)
N/A None by Design null null
a. Alkali-Silica or Chemical Reaction of Concrete N/A Null null null
b. Construction Joint Condition N/A Null null null
c. Cracking (Type and Size) N/A Null null null
d. Erosion N/A Null null null
e. Offset/Faulting (Relative Movement of Opposing Sides) N/A Null null null
f. Reinforcement Corrosion N/A Null null null
g. Spalling or Pop out N/A Null null null
US102 Abutments (Abutment walls are parallel to the flow) N/A None by Design null null
US103 Retention Walls N/A
None by Design null null
US104 Headwall (Head walls are perpendicular to the flow) N/A
None by Design null null
US105 Expansion Joints/Construction Joints (Use here if deficiency is not associated with the components listed) N/A
None by Design null null
Underwater-Upstream Structural
Components
UW-15
Real
Time Deficiency Probable Cause
Recommended
Corrective
ActionsFinding Name
Underwater-Upstream Erosion Control US106 Sheet Piles and Bulkheads N/A
None by Design null null
a. Concrete Condition N/A Null null null
b. Concrete Pile N/A Null null null
c. Condition of Coating Products N/A Null null null
d. Corrosion N/A Null null null
e. Deadman Condition N/A Null null null
f. Joint or Knuckle Condition N/A Null null null
g. Pile Cap N/A Null null null
h. Sheet Pile N/A Null null null
i. Timber Pile N/A Null null null
j. Undermining N/A Null null null
US107 Wales/Tie Backs (hardware) (Used with sheetpile) N/A
None by Design null null
US108 Intake Bays N/A
None by Design null null
US109 Piers/Ballasts (Pier walls that separate the bays) N/A None by Design null null
US110 Foundations (Underneath the structure) N/A None by Design null null
US111 Weir/Weir Crest N/A
None by Design null null
a. Alkali-Silica or Chemical Reaction of Concrete N/A Null null null
b. Cracking (Type and Size) N/A Null null null
c. Erosion N/A Null null null
d. Offset/Faulting (Relative Movement of Opposing Sides) N/A Null null null
e. Reinforcement Corrosion N/A Null null null
f. Spalling or Pop out N/A Null null null
US112 Baffles N/A
None by Design null null
a. Alkali-Silica or Chemical Reaction of Concrete N/A Null null null
b. Construction Joint Condition N/A Null null null
c. Cracking (Type and Size) N/A Null null null
d. Erosion N/A Null null null
e. Offset/Faulting (Relative Movement of Opposing Sides) N/A Null null null
f. Reinforcement Corrosion N/A Null null null
g. Spalling or Pop out N/A Null null null
US113 Underwater Apron Slabs N/A None by Design null null
UW-16
Real
Time Deficiency Probable Cause
Recommended
Corrective
ActionsFinding Name
Underwater-Upstream Erosion Control US114 Structural Support, Bracing or Frames (For other structural components)
3 13:54:55
Moderate surface corrosion and section loss of timber hardware. Light surface corrosion, pitting, and coating failure on steel cross bracing.
Exposure to an aggressive environment
Clean and coat affected areas
a. Corrosion (Light, Moderate, Heavy)
Moderate Exposure to an aggressive environment
Clean and coat affected areas
b. Flaking, Peeling, Blisters N/A Null null null
c. Pitting
Moderate Exposure to an aggressive environment
Clean and coat affected areas
d. Protective Coating Condition
Moderate Exposure to an aggressive environment
Clean and coat affected areas
e. Section Loss
Moderate Exposure to an aggressive environment
Clean and coat affected areas
f. Surface Area (% Damaged) N/A Null null null
US115 Culverts Interior (Include exterior of culvert, if it can be seen)
3 14:04:50
The barrel has coating failure throughout, surface corrosion and flaking up to 1/16", as well as knife edging and perforations at the barrel ends.
Exposure to an aggressive environment
Clean and coat affected areas
US116 Risers (Culvert risers) N/A
None by design null null
US151 Gate Condition
3 13:30:10
The gate has less than
5% coating failure and corrosion up to 1" in diameter
Exposure to an aggressive environment
Clean and coat affected areas
a. Alignment, Indications of Bowing or Buckling N/A null null null
b. Cathodic protection anodes N/A null null null
c. Corrosion (Light, Moderate, Heavy)
The gate has less than
5% coating failure and corrosion up to 1" in diameter
Exposure to an aggressive environment
Clean and coat affected areas
d. Gate Anchorage N/A null null null
e. Gate seal condition 1 null null null
f. Greasers N/A null null null
g. Indications of Stress or Structural Deterioration N/A null null null
h. Operability N/A null null null
Underwater-Upstream Gates
UW-17
Real
Time Deficiency Probable Cause
Recommended
Corrective
ActionsFinding Name
Underwater-Upstream Erosion Control i. Pitting (% Penetration Into Metal) N/A null null null
j. Protective Coating Condition (Flaking, Peeling, Blisters)
The gate has less than
5% coating failure and corrosion up to 1" in diameter
Exposure to an aggressive environment
Clean and coat affected areas
k. Rivet, Weld Seam, or Bolt Condition N/A null null null
l. Section Loss N/A null null null
m. Surface Area (% Damaged) N/A null null null
US152 Gate Guides and Gate Control (Includes rails and, depending on type of gate, roller wheels, gate stem, ballast or bladder and their connections)
No Deficiencies Noted null null
a. Abrasion Damage Due to Operation N/A null null null
b. Alignment, Indications of Bowing or Buckling N/A null null null
c. Corrosion N/A null null null
d. Gate Control Anchorage N/A null null null
e. Indications of Stress or Structural Deterioration N/A null null null
f. Protective Coating Condition (Flaking, Peeling, Blisters) N/A null null null
g. Rivet, Weld Seam, or Bolt Condition N/A null null null
h. Section Loss N/A null null null
i. Structural Steel Condition N/A null null null
US153 Gate Seal Condition (Gaskets, Seal Ride, and Mating Surfaces) 1 No Deficiencies Noted null null
US154 Cathodic Protection (Use this for the entire structure, including gates, wingwalls, metal culverts, platforms, etc.)
N/A
None by Design null null
US155 Condition of Operator/Actuator Components(Includes limit switches, position indicator switches, and manatee systems)
N/A
None by Design null null
US156 Emergency Closure Gates N/A
None by Design null null
a. Abrasion Damage Due to Operation N/A null null null
b. Alignment, Indications of Bowing or Buckling N/A null null null
c. Cathodic protection anodes N/A null null null
d. Condition of Actuator or Actuator Components N/A null null null
e. Corrosion N/A null null null
f. Gate Anchorage N/A null null null
g. Gate Guides and Gate Control N/A null null null
h. Gate Seal Condition (Gasket and Mating Surfaces) N/A null null null
UW-18
Real
Time Deficiency Probable Cause
Recommended
Corrective
ActionsFinding Name
Underwater-Upstream Erosion Control i. Greasers N/A null null null
j. Indications of Stress or Structural Deterioration N/A null null null
k. Operability N/A null null null
l. Protective Coating Condition (Flaking, Peeling, Blisters) N/A null null null
m. Rivet, Weld Seam, or Bolt Condition N/A null null null
n. Section Loss N/A null null null
o. Structural Steel Condition N/A null null null
US157 Navigation Lock Gates N/A
None by Design null null
a. Buoyancy Tanks N/A null null null
b. Gate Anchorage N/A null null null
c. Gate supports N/A null null null
d. Hinge and pintel housing N/A null null null
e. Locking Mechanism N/A null null null
f. Operability N/A null null null
g. Protective Coating Condition N/A null null null
h. Staunching Devices N/A null null null
DOWNSTREAM:
Checklist Finding # C-Rating
Video
Real
Time
Deficiency Probable Cause Recommended
Corrective
Actions
DS1 Slope Degradation/Stability
No Deficiencies Noted null null
DS2 Condition of Rip-Rap (Loose/Seated)
No Deficiencies Noted null null
DS3 Exposed Erosion Control Fabric (C1 if not exposed)
No Deficiencies Noted null null
DS4 Evidence of Stone Displacement (For bedding stone) N/A
None by Design null null
DS5 Channel Stabilization and Erosion Control N/A
None by Design null null
DS50 Structure-General Concrete Condition (Out of all concrete members at the structure, state which ones have deficiencies, and which are fine)
N/A
None by Design null null
a. Concrete Chemical Reaction (Sulfate attack?)
N/A null null null
b. Concrete Cracks N/A null null null
c. Concrete Spalling (Is rebar exposed?)
N/A null null null
d. Concrete Structural Integrity N/A null null null
Underwater-Downstream General
Underwater-Downstream Erosion Control
Finding Name
UW-19
Real
Time Deficiency Probable Cause
Recommended
Corrective
ActionsFinding Name
Underwater-Upstream Erosion Control e. Exposed Rebar Corrosion N/A null null null
f. Offset (relative movement of opposing sides) N/A null null null
g. Scaling N/A null null null
h. Undermining N/A null null null
DS51 Structure-General Metal Condition (Out of all metal members at the structure, state which ones have deficiencies, and which are fine) 3 13:04:20
The barrel has coating failure throughout, surface corrosion and flaking up to 1/16", as well as knife edging and perforations at the barrel ends.
Exposure to an aggressive environment
Clean and coat affected areas
a. Corrosion
Moderate with flaking up to 1/16"
Exposure to an aggressive environment
Clean and coat affected areas
b. Offset (relative movement of opposing sides) N/A null null null
c. Section Loss
Up to 3'W by 2'L, 100% loss in isolated areas up to 20' from the barrel ends
Exposure to an aggressive environment
Clean and coat affected areas
d. Undermining N/A null null null
DS52 Structure-General Timber Condition (Out of all timber members at the structure, state which ones have deficiencies, and which are fine)
N/A
None by Design null null
a. Offset (relative movement of opposing sides) N/A null null null
b. Pile Caps N/A null null null
c. Rot N/A null null null
d. Splitting N/A null null null
e. Undermining N/A null null null
DS53 Structural Joints (e.g. Bolts, Welds) N/A
None by Design null null
DS54 Stop Log/Flashboard Channels (Including stop logs & flashboards) N/A None by Design null null
DS55 Settlement (Settlement of structure?) N/A None by Design null null
DS56 Shoaling/Scour (Shoaling=deposit of mat'l; Scour=removal of mat'l) N/A
None by Design null null
a. Downstream Foundation/Headwall N/A null null null
b. Downstream Sedimentation (Shoaling) N/A null null null
c. Shoaling/Scour Depth and Dimensions N/A null null null
d. Wingwalls N/A None by Design null null
DS57 Fouling/Marine Growth N/A None by Design null null
UW-20
Real
Time Deficiency Probable Cause
Recommended
Corrective
ActionsFinding Name
Underwater-Upstream Erosion Control a. Type, Consistency, Thickness N/A null null null
DS58 Debris N/A None by Design null null
DS59 Stilling Wells (If 'NA', Why?)
N/A
None by Design null null
a. Corrosion, Joint Damage N/A null null null
b. General Condition N/A null null null
c. Stilling Well Pier-Connections N/A null null null
d. Stilling Well Pier-Support (Support posts) N/A null null null
e. Stillwell Intake Lines (Stilling well pipes) N/A null null null
DS60 Underwater Controls/Instruments
3 13:48:10
Moderate surface corrosion on staff gauge steel mount and hardware, with pitting and section loss up to
1/16"
Exposure to an aggressive environment
Clean and coat affected areas
a. Fastening System in Suitable Condition
Moderate surface corrosion on staff gauge steel mount and hardware, with pitting and section loss up to
1/16"
Exposure to an aggressive environment
Clean and coat affected areas
b. Proper Location and Alignment N/A null null null
DS61 Fenders (Fenders for structure;
e.g. for boat locks) N/A null null null
DS100 Wingwalls N/A
None by Design null null
DS101 Buttresses (Support arms for wall)
N/A None by Design null null
a. Alkali-Silica or Chemical Reaction of Concrete N/A null null null
b. Construction Joint Condition N/A null null null
c. Cracking (Type and Size) N/A null null null
d. Erosion N/A null null null
e. Offset/Faulting (Relative Movement of Opposing Sides) N/A null null null
f. Reinforcement Corrosion N/A null null null
g. Spalling or Pop out N/A null null null
DS102 Abutments (Abutment walls are parallel to the flow) N/A None by Design null null
DS103 Retention Walls N/A
None by Design null
DS104 Headwall (Head walls are perpendicular to the flow)
N/A None by Design null
Underwater-Downstream Structural
Components
UW-21
Real
Time Deficiency Probable Cause
Recommended
Corrective
ActionsFinding Name
Underwater-Upstream Erosion Control DS105 Expansion Joints/Construction Joints (Use here if deficiency is not associated with the components listed) N/A
None by Design null null
DS106 Sheet Piles and Bulkheads N/A
None by Design null null
a. Concrete Condition N/A null null null
b. Concrete Pile N/A null null null
c. Condition of Coating Products N/A null null null
d. Corrosion N/A null null null
e. Deadman Condition N/A null null null
f. Joint or Knuckle Condition N/A null null null
g. Pile Cap N/A null null null
h. Sheet Pile N/A null null null
i. Timber Pile N/A null null null
j. Undermining N/A null null null
DS107 Wales/Tie Backs (hardware) (Used with sheetpile) N/A
None by Design null null
DS108 Discharge Bays N/A
None by Design null null
DS109 Piers (Pier walls that separate the bays) N/A None by Design null null
DS110 Foundations (Underneath the structure) N/A None by Design null null
DS111 Weir/Weir Crest N/A
None by Design null null
a. Alkali-Silica or Chemical Reaction of Concrete N/A null null null
b. Cracking (Type and Size) N/A null null null
c. Erosion N/A null null null
d. Offset/Faulting (Relative Movement of Opposing Sides) N/A null null null
e. Reinforcement Corrosion N/A null null null
f. Spalling or Pop out N/A null null null
DS112 Baffles N/A
None by Design null null
a. Alkali-Silica or Chemical Reaction of Concrete N/A null null null
b. Construction Joint Condition N/A null null null
c. Cracking (Type and Size) N/A null null null
d. Erosion N/A null null null
e. Offset/Faulting (Relative Movement of Opposing Sides) N/A null null null
UW-22
Real
Time Deficiency Probable Cause
Recommended
Corrective
ActionsFinding Name
Underwater-Upstream Erosion Control f. Reinforcement Corrosion N/A null null null
g. Spalling or Pop out N/A null null null
DS113 Underwater Apron Slabs N/A
None by Design null null
DS114 Structural Support, Bracing or Frames (For other structural components) N/A None by Design null null
a. Corrosion (Light, Moderate, Heavy) N/A null null null
b. Flaking, Peeling, Blisters N/A null null null
c. Pitting N/A null null null
d. Protective Coating Condition N/A null null null
e. Section Loss N/A null null null
f. Surface Area (% Damaged) N/A null null null
DS115 Culverts Interior (Include exterior of culvert, if it can be seen)
3 14:04:50
The barrel has coating failure throughout, surface corrosion and flaking up to 1/16", as well as knife edging and perforations at the barrel ends.
Exposure to an aggressive environment
Clean and coat affected areas
DS151 Gate Condition N/A
None by Design null null
a. Cathodic protection anodes N/A null null null
b. Corrosion (Light, Moderate, Heavy) N/A null null null
c. Gate Anchorage N/A null null null
d. Gate seal condition N/A null null null
e. Greasers N/A null null null
f. Indications of Stress or Structural Deterioration N/A null null null
g. Operability N/A null null null
h. Pitting (% Penetration Into Metal) N/A null null null
i. Protective Coating Condition (Flaking, Peeling, Blisters) N/A null null null
j. Rivet, Weld Seam, or Bolt Condition N/A null null null
k. Section Loss N/A null null null
l. Straight, Aligned, Indications of Bowing or Buckling N/A null null null
m. Surface Area (% Damaged) N/A null null null
DS152 Gate Guides and Gate Control (Includes rails and, depending on type of gate, roller wheels, gate stem, ballast or bladder and their connections)
N/A
None by Design null null
Underwater-Downstream Gates
UW-23
Real
Time Deficiency Probable Cause
Recommended
Corrective
ActionsFinding Name
Underwater-Upstream Erosion Control a. Abrasion Damage Due to Operation N/A null null null
b. Corrosion N/A null null null
c. Gate Anchorage N/A null null null
d. Indications of Stress or Structural Deterioration N/A null null null
e. Protective Coating Condition (Flaking, Peeling, Blisters) N/A null null null
f. Rivet, Weld Seam, or Bolt Condition N/A null null null
g. Section Loss N/A null null null
h. Straight, Aligned, Indications of Bowing or Buckling N/A null null null
i. Structural Steel Condition N/A null null null
DS153 Gate Seal Condition (Gaskets, Seal Ride, and Mating Surfaces) N/A
None by Design null null
DS154 Cathodic Protection (Use this for the entire structure, including gates, wingwalls, metal culverts, platforms, etc.)
N/A
None by Design null null
DS155 Condition of Operator/Actuator Components(Includes limit switches, position indicator switches, and manatee systems)
N/A
None by Design null null
DS156 Emergency Closure Gates N/A
None by Design null null
a. Abrasion Damage Due to Operation N/A null null null
b. Cathodic protection anodes N/A null null null
c. Condition of Actuator or Actuator Components N/A null null null
d. Corrosion N/A null null null
e. Gate Anchorage N/A null null null
f. Gate Guides and Gate Control N/A null null null
g. Gate Seal Condition (Gasket and Mating Surfaces) N/A null null null
h. Greasers N/A null null null
i. Indications of Stress or Structural Deterioration N/A null null null
j. Operability N/A null null null
k. Protective Coating Condition (Flaking, Peeling, Blisters) N/A null null null
l. Rivet, Weld Seam, or Bolt Condition N/A null null null
m. Section Loss N/A null null null
n. Straight, Aligned, Indications of Bowing or Buckling N/A null null null
o. Structural Steel Condition N/A null null null
UW-24
Real
Time Deficiency Probable Cause
Recommended
Corrective
ActionsFinding Name
Underwater-Upstream Erosion Control DS157 Navigation Lock Gates N/A
None by Design null null
a. Buoyancy Tanks N/A null null null
b. Gate Anchorage N/A null null null
c. Gate supports N/A null null null
d. Hinge and pintel housing N/A null null null
e. Locking Mechanism N/A null null null
f. Operability N/A null null null
g. Protective Coating Condition N/A null null null
h. Staunching Devices N/A null null null
Underwater-Comments DS1000 Additional Items & Comments
N/A
None by Design null null
UW-25
| USJRB SOUTH S-252D |
| USJRB SOUTH S-252D REV |