Amendment 0001 to answer questions received regarding this RFQ.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| W912DW18Q0099_Amendment_0002.pdf | ||
| W912DW18Q0099.pdf | ||
| Limited_Source_Justification_-_redacted.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USA ENGINEER DISTRICT, SEATTLE
MONIQUE PAANO
PH: 206-764-6084 FAX: 206-764-6817
MONIQUE.A.PAANO@USACE.ARMY.MIL
SEATTLE WA
W68MD981705801
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
W912DW18Q0099
Libby Dam (LD) System Control Console (SCC)/Programmable Logic Controller (PLC) Annunciation/S-Board Materials, Libby, MT
The purpose of this amendment is to answ er questions received in response to this RFQ. All other terms and conditions remain unchanged.
Closing date and time remain the same at 21 Sep 2018 by 10:00 AM Pacif ic Time.
See continuation sheet for Q&A.
1. CONTRACT ID CODE PAGE OF PAGES
J 1 3
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 19-Sep-2018
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street , County, State and Zip Code) X W912DW18Q0099
X 9B. DATED (SEE ITEM 11)
04-Sep-2018
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
19-Sep-2018
CODE
USA ENGINEER DISTRICT, SEATTLE
ATTN: CENWS-CT
4735 EAST MARGINAL WAY SOUTH, BLDG. 1202
SEATTLE WA 98134-2388
W912DW 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE W912DW
FACILITY CODECODE
EMAIL:TEL:
W912DW18Q0099
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
(End of Summary of Changes)
The following items are applicable to this modification:
CONTINUATION PAGE
Q1: Items 24-29 - please advise the secondary amps/voltage for the PTR/CTR respectively. (example
PTR:120 requires a secondary voltage number)
A1: Item 24, Input:0-150V AC, PTR 1200/1, phase voltage 110.8 VAC secondary at 133,000 kV primary
Item 25, Input:0-150V AC, PTR 14,400/120, 120 VAC L-L secondary
Item 26, Input: 0-5A AC (6000/5 CTs)
Item 27; Inputs:0-150V AC, PTR 14,400/120, 120VAC L-L secondary and 0-5A AC, CTR 6000/5
Item 28; Input:0-150V AC, PTR 14,400/120, 120 VAC L-L secondary
Item 29; 0-150V AC, PTR 14,400/120, 120VAC L-L secondary and 0-5A AC, CTR 6000/5
Q2: Item 29 - 4H4XXZ33UXXXXBB - currently specified as model ACP3 with MV-832. Model ACP3 is obsolete. We would like to quote model ACP4 without MV-832 as it is not required on the model ACP4. Is this acceptable?
A2: 4H4XXZ33UXXXXBB is the part number provided to us from the manufacturer for our application along with the following description: BG-241 Red enhanced display, 3 phase 3 wire Varmeter with Phase Shifter, Scale: 150-0-150 AC Megavars.
Please provide part as specified, including external phase shifter. Proposed variation from the specifications is not acceptable.
Q3: Item 30 - 4S4XXBBUXXXXBB - part number is missing the 6th digit: Input type - please advise correct part number. Should this be an F to match the part number in item 28? Please confirm.
A3: Item 30; Input:0-150V AC, PTR 1200/1, phase voltage 110.8 VAC secondary at 133,000 kV primary, correct part number: 4H4XXFBBUXXXXBB
Q4: Item 111 Qty 6000 - Allied Wire and Cable EPR/CPE 12-5C
Will the customer accept 12 gauge, 7 strand, tinned copper, XHHW/CPE 600V Tray?
A4: Provide as specified.
W912DW18Q0099
Q5: Item 115 Qty 4500 - Allied Wire and Cable EPR/CPE 16-4C The 16 AWG has a 10,000 ft min. Will the customer accept 14 AWG?
A5: Provide as specified.
Q6: Item 116 Qty 7000 - Allied Wire and Cable EPR/CPE 16-7C The 16 AWG has a 10,000 ft min. Will the customer accept 14 AWG?
A6: Provide as specified.
Q7: Item 117 - Qty 3000 - Allied Wire and Cable EPR/CPE 16-12C
A7: Provide as specified.
Q8: Item 118 - Allied Wire and Cable 168815-18 This part number is obsolete. Will the customer accept this:
18AWG 2pr 7str tinned copper XLP insulated Blk & Wht pairs Indiv & overall alum foil shld Blk CPE Jkt 600V 90C Tray Cable
A8: Provide Allied Wire and Cable EPR/CPE 18-2P-SPOS or equivalent.
Q9: Item 119 - Allied Wire and Cable SIS-16-7T Please specify color.
A9: Provide gray color.
End Q&A