UNITED STATES ARMY CORPS OF ENGINEERS
BALTIMORE DISTRICT
UNITED STATES ARMY WAR COLLEGE
SPECIFICATIONS
VOLUME 2
CONTRACT N4008015D0452 / TASK W912DR18F0343
90% SUBMITTAL
AUGUST 2, 2019
CONTACT:
Todd A. Whaley, PE 703.329.2797 twhaley@wileywilson.com
USACE US Army War College 218110
DIVISION 01 -
PROJECT TABLE OF CONTENTS
GENERAL REQUIREMENTS
01 11 00 SUMMARY OF WORK
01 14 00 WORK RESTRICTIONS
01 22 00.00 10 PRICE AND PAYMENT PROCEDURES
01 30 00 ADMINISTRATIVE REQUIREMENTS
01 32 01.00 10 PROJECT SCHEDULE
01 33 00 SUBMITTAL PROCEDURES
01 33 29 SUSTAINABILITY REPORTING
01 35 26 GOVERNMENTAL SAFETY REQUIREMENTS
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00.00 10 QUALITY CONTROL
01 45 00.15 10 RESIDENT MANAGEMENT SYSTEM CONTRACTOR MODE (RMS CM)
01 45 35 SPECIAL INSPECTIONS
01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS
01 57 19 TEMPORARY ENVIRONMENTAL CONTROLS
01 74 19 CONSTRUCTION AND DEMOLITION WASTE MANAGEMENT
01 78 00 CLOSEOUT SUBMITTALS
01 78 23 OPERATION AND MAINTENANCE DATA
01 91 00.15 TOTAL BUILDING COMMISSIONING
DIVISION 02 - EXISTING CONDITIONS
02 41 00 DEMOLITION AND DECONSTRUCTION
DIVISION 03 - CONCRETE
03 11 13.00 10 STRUCTURAL CAST-IN-PLACE CONCRETE FORMING
03 15 00.00 10 CONCRETE ACCESSORIES
03 20 00.00 10 CONCRETE REINFORCING
03 30 00.00 10 CAST-IN-PLACE CONCRETE
03 35 00.00 10 CONCRETE FINISHING
03 39 00.00 10 CONCRETE CURING
03 45 00 PRECAST ARCHITECTURAL CONCRETE
DIVISION 04 - MASONRY
04 20 00 UNIT MASONRY
DIVISION 05 - METALS
05 12 00 STRUCTURAL STEEL
05 30 00 STEEL DECKS
05 40 00 COLD-FORMED METAL FRAMING
05 50 13 MISCELLANEOUS METAL FABRICATIONS
05 51 00 METAL STAIRS
05 51 33 METAL LADDERS
05 52 00 METAL RAILINGS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 10 00 ROUGH CARPENTRY
06 41 16.00 10 PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS
06 61 16 SOLID SURFACING FABRICATIONS
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
PROJECT TABLE OF CONTENTS Page 1
07 05 23 PRESSURE TESTING AN AIR BARRIER SYSTEM FOR AIR TIGHTNESS
07 11 13 BITUMINOUS DAMPPROOFING
07 13 53 ELASTOMERIC SHEET WATERPROOFING
07 14 00 FLUID-APPLIED WATERPROOFING
07 21 13 BOARD AND BLOCK INSULATION
07 21 16 MINERAL FIBER BLANKET INSULATION
07 22 00 ROOF AND DECK INSULATION
07 27 10.00 10 BUILDING AIR BARRIER SYSTEM
07 27 19.01 SELF-ADHERING AIR BARRIERS
07 27 26 FLUID-APPLIED MEMBRANE AIR BARRIERS
07 42 13 METAL WALL PANELS
07 42 63 FABRICATED WALL PANEL ASSEMBLIES
07 54 19 POLYVINYL-CHLORIDE ROOFING
07 60 00 FLASHING AND SHEET METAL
07 81 00 SPRAY-APPLIED FIREPROOFING
07 84 00 FIRESTOPPING
07 92 00 JOINT SEALANTS
DIVISION 08 - OPENINGS
08 11 13 STEEL DOORS AND FRAMES
08 11 16 ALUMINUM DOORS AND FRAMES
08 14 00 WOOD DOORS
08 31 00 ACCESS DOORS AND PANELS
08 33 23 OVERHEAD COILING DOORS
08 34 73 SOUND CONTROL DOOR ASSEMBLIES
08 41 13 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
08 44 00 CURTAIN WALL AND GLAZED ASSEMBLIES
08 51 13 ALUMINUM WINDOWS
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
DIVISION 09 - FINISHES
09 22 00 SUPPORTS FOR GYPSUM BOARD
09 29 00 GYPSUM BOARD AND PLASTER
09 30 10 CERAMIC, QUARRY, AND GLASS TILING
09 51 00 ACOUSTICAL CEILINGS
09 62 38 STATIC-CONTROL FLOORING
09 65 00 RESILIENT FLOORING
09 68 00 CARPETING
09 72 00 WALLCOVERINGS
09 84 20 ACOUSTICAL WALL PANELS
09 90 00 PAINTS AND COATINGS
DIVISION 10 - SPECIALTIES
10 14 00.10 EXTERIOR SIGNAGE
10 14 00.20 INTERIOR SIGNAGE
10 14 53 TRAFFIC SIGNAGE
10 21 13 TOILET COMPARTMENTS
10 22 39 FOLDING PANEL PARTITIONS
10 26 00 WALL AND DOOR PROTECTION
10 28 13 TOILET ACCESSORIES
10 44 16 FIRE EXTINGUISHERS
10 51 13 SOLID PLASTIC LOCKERS
10 56 13 STEEL SHELVING
10 56 26 MOBILE STORAGE SHELVING
PROJECT TABLE OF CONTENTS Page 2
DIVISION 11 – EQUIPMENT
11 13 19.13 LOADING DOCK LEVELERS
11 40 00 FOODSERVICE EQUIPMENT
DIVISION 12 - FURNISHINGS
12 24 13 ROLLER WINDOW SHADES
12 36 00 COUNTERTOPS
12 48 13 ENTRANCE FLOOR MATS AND FRAMES
12 61 13 UPHOLSTERED AUDIENCE SEATING
12 93 00 SITE FURNISHINGS
DIVISION 14 - CONVEYING EQUIPMENT
14 21 23 ELECTRIC TRACTION PASSENGER ELEVATORS
14 42 00 WHEELCHAIR LIFTS
DIVISION 21 - FIRE SUPPRESSION
21 12 00 STANDPIPE SYSTEMS
21 13 13.00 10 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION
21 30 00 FIRE PUMPS
DIVISION 22 - PLUMBING
22 00 00 PLUMBING, GENERAL PURPOSE
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS
TESTING, ADJUSTING, AND BALANCING FOR HVAC
THERMAL INSULATION FOR MECHANICAL SYSTEMS
23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC
23 09 13 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC
23 09 23.02 BACNET DIRECT DIGITAL CONTROL FOR HVAC AND OTHER BUILDING
CONTROL SYSTEMS
23 11 25 FACILITY GAS PIPING
23 21 23 HYDRONIC PUMPS
23 52 00 HEATING BOILERS
23 64 10 WATER CHILLERS, VAPOR COMPRESSION TYPE
23 64 26 CHILLED AND HOT WATER PIPING SYSTEMS
DIVISION 25 - INTEGRATED AUTOMATION
25 05 11 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS
25 08 10 UTILITY MONITORING AND CONTROL SYSTEM TESTING
25 10 10 UTILITY MONITORING AND CONTROL SYSTEM (UMCS) FRONT END
AND INTEGRATION
DIVISION 26 - ELECTRICAL
26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS
26 08 00 APPARATUS INSPECTION AND TESTING
26 11 16 SECONDARY UNIT SUBSTATION
26 20 00 INTERIOR DISTRIBUTION SYSTEM
26 23 00 MAIN SWITCHBOARD
26 26 00 POWER DISTRIBUTION UNITS
26 28 01.00 10 COORDINATED POWER SYSTEM PROTECTION
26 28 05 ARC-FLASH STUDY
PROJECT TABLE OF CONTENTS Page 3
26 29 23 VARIABLE FREQUENCY DRIVE SYSTEMS UNDER 600 VOLTS
26 32 13.00 20 SINGLE OPERATION GENERATOR SETS
26 32 33.00 10 UNINTERRUPTIBLE POWER SUPPLY (UPS) SYSTEM
26 36 00.00 10 AUTOMATIC TRANSFER SWITCH AND BY-PASS/ISOLATION SWITCH
26 41 00 LIGHTNING PROTECTION SYSTEM
26 51 00 INTERIOR LIGHTING
26 56 00 EXTERIOR LIGHTING
DIVISION 27 - COMMUNICATIONS
27 05 14.00 10 CABLE TELEVISION PREMISES DISTRIBUTION SYSTEM
27 13 23.00 40 COMMUNICATIONS OPTICAL BACKBONE CABLING
27 21 10.00 40 FIBER OPTIC DATA TRANSMISSION SYSTEM
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 08 10 ELECTRONIC SECURITY SYSTEM ACCEPTANCE TESTING
28 31 49 CARBON MONOXIDE DETECTORS
28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM
DIVISION 31 - EARTHWORK
31 00 00 EARTHWORK
31 05 19 GEOTEXTILE
31 11 00 CLEARING AND GRUBBING
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 05 33 LANDSCAPE ESTABLISHMENT
32 11 23 AGGREGATE BASE COURSES
32 12 16 HOT-MIX ASPHALT (HMA) FOR ROADS
32 13 13.06 PORTLAND CEMENT CONCRETE PAVEMENT FOR ROADS AND SITE
FACILITIES
32 31 13 CHAIN LINK FENCES AND GATES
32 92 19 SEEDING
DIVISION 33 - UTILITIES
33 11 00 WATER UTILITY DISTRIBUTION PIPING
33 30 00 SANITARY SEWERAGE
33 40 00 STORM DRAINAGE UTILITIES
33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS Page 4
SECTION 14 21 23
ELECTRIC TRACTION PASSENGER ELEVATORS
05/16
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)
ASCE 7 (2017) Minimum Design Loads for Buildings and Other Structures
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2015; Errata 1 2015; Errata 2 2016) Structural Welding Code - Steel
ASME INTERNATIONAL (ASME)
ASME A17.1/CSA B44 (2016) Safety Code for Elevators and Escalators
ASME A17.2 (2017) Guide for Inspection of Elevators, Escalators, and Moving Walks Includes Inspection Procedures for Electric Traction and Winding Drum Elevators, Hydraulic Elevators, and Escalators and Moving Walks
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE C62.41 (1991; R 1995) Recommended Practice on Surge Voltages in Low-Voltage AC Power Circuits
INTERNATIONAL CODE COUNCIL (ICC)
ICC IBC (2018) International Building Code
NATIONAL ELEVATOR INDUSTRY, INC. (NEII)
NEII-1 (2000; R thru 2017) Building Transportation Standards and Guidelines, including the Performance Standards Matrix for New Elevator Installation
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 101 (2018; TIA 18-1; TIA 18-2; TIA 18-3) Life Safety Code
NFPA 70 (2017; ERTA 1-2 2017; TIA 17-1; TIA 17-2;
SECTION 14 21 23 Page 1
TIA 17-3; TIA 17-4; TIA 17-5; TIA 17-6;
TIA 17-7; TIA 17-8; TIA 17-9; TIA 17-10;
TIA 17-11; TIA 17-12; TIA 17-13; TIA
17-14; TIA 17-15; TIA 17-16; TIA 17-17 )
National Electrical Code
NFPA 70E (2018; TIA 18-1; TIA 81-2) Standard for Electrical Safety in the Workplace
NFPA 72 (2016; Errata 1 2018) National Fire Alarm and Signaling Code
U.S. DEPARTMENT OF DEFENSE (DOD)
UFC 3-560-01 (2017) Operations and Maintenance:
Electrical Safety
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines
1.2 Related Requirements
Refer to Section 01 33 29 - Sustainable Design Requirements for LEED v4 BD+C, relative to building product criteria and disclosure of sustainability information for applicable products covered in this section and the related submittal requirements.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.
Designator codes are as follows: "AE" for Architect-Engineer; "DO" for District Office (Engineering Division or other organization in the District Office); "AO" for Area Office; "RO" for Resident Office.
Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING. Submit the following in accordance with Section 01 33 00:
SD-02 Shop Drawings
Elevator System; G, AE
Elevator Components; G, AE
Elevator Machine; G, AE
Elevator Controller; G, AE
Wiring Diagrams; G, AE
SD-03 Product Data
Elevator and Accessories; G, AE
SECTION 14 21 23 Page 2
Elevator Components; G, AE
Data Sheets; G, AE
Elevator Microprocessor Controller; G, AE
SD-05 Design Data
Emergency Power Systems
Heat Loads
Reaction Loads
SD-07 Certificates
Elevator Parts and Components Price Lists; G, RO
Warranty
Endorsement Letter
Welders' Qualifications
Elevator Controller Certification; G, RO
SD-10 Operation and Maintenance Data
Elevator, Data Package 4; G, RO
Maintenance Control Program (MCP); G, RO
Software and Documentation; G, RO
Submit in accordance with Section 01 78 23 OPERATION AND
MAINTENANCE DATA.
1.3.1 Additional LEED Requirements
LEED Submittals: Refer to Section 01 33 29 - Sustainable Design Requirements for LEED v4 BD+C and 01 33 29 ATTACH 3--LEED v4 Material Submittal Form for submittal requirements related to manufacturer's product disclosure of sustainability criteria for applicable building products covered in this section. Requirements for LEED product submittals may include environmental product declarations, health product declarations or other material ingredient reports, life cycle analysis, VOC content and emissions testing, recycled content, wood certification or bio-based content. Additionally, provide the location for each product's procurement, manufacture and extraction locations and distances from the project site.
1.3.2 Shop Drawing Requirements
Provide assembly and arrangement of elevators, accessories, and elevator components. Show location of elevator machine in elevator machine room (MR) or machinery space (MS). Show location of elevator controller in elevator machine room or elevator control room (CR). Provide details for materials and equipment, including but not limited to operating and signal
SECTION 14 21 23 Page 3 fixtures, doors, door and car frames, car enclosure, controllers, motors, guide rails and brackets, layout of hoistway in plan and elevation, and other layout information and clearance dimensions.
1.3.3 Product Data Requirements
Provide manufacturers' product data for all elevator components, including but not limited to the following: elevator controller, hoist machine and drive motor, design counterbalance, hoist ropes and shackles, overspeed governor, emergency braking system, car and hall fixture buttons and switches, cab, machine room, control room, and machinery space communication devices, door operator, door protection system, and car and counterweight roller guides and buffers. For data sheets, provide document identification number or bulletin number, published or copyrighted prior to the date of contract bid opening. Provide controller manufacturer's published procedures for performance of each and all testing required by ASME A17.1/CSA B44 .
1.3.4 Design Data
1.3.4.1 Reaction Loads
Provide calculations by registered professional engineer for reaction loads imposed on building by elevator system. Calculations must comply with ASCE 7 and ASME A17.1/CSA B44
1.3.4.2 Heat Loads
Provide calculations from elevator manufacturer, or by registered professional engineer, for total anticipated heat loads generated by all of the elevator equipment.
1.3.4.3 Emergency Power Systems
Where the facility does have an emergency power system, confirm the elevators that will be connected to the emergency power system. Confirm the complete emergency power system and sequence of operation for all elevators, including elevator sequential operation and operation of the elevator lobby manual selection switch. Provide wiring diagrams for building emergency power interface with elevator controls. For elevators not supplied by an emergency power system, provide manufacturers' product data for auxiliary power systems.
1.3.5 Welders' Requirements
Comply with AWS D1.1/D1.1M , Section 5. Include certified copies of field welders' qualifications. List welders' names with corresponding code marks to identify each welder's welding work
1.3.6 Maintenance Control Program (MCP)
For each elevator, prepare and provide a written Maintenance Control Program (MCP) that complies with ASME A17.1/CSA B44 Section 8.6, including written documentation that details the test procedures for each and every test that is required to be performed by ASME A17.1/CSA B44 . Assemble all MCP documentation, and supporting technical attachments, in a single MCP package and provide in both electronic and hard copy. Assemble entire hard copy MCP in 3-ring binders. For each elevator provided, the MCP must include only documentation and instruction that apply to the elevator
SECTION 14 21 23 Page 4 specified.
For each elevator, provide an additional, separate binder that includes all maintenance, repair, replacement, call back, and other records required by ASME A17.1/CSA B44 . The records binder must be kept in the elevator mechanical room, maintained by elevator maintenance and service personnel, and be available at all times to authorized personnel.
Provide detailed information regarding emergency service procedures and elevator installation company personnel contact information. Provide a listing of all tools to be provided to the Contracting Officer as components of the elevator system.
1.4 QUALITY ASSURANCE
1.4.1 Qualification
Provide a designed and engineered elevator system by an elevator contractor regularly engaged in the installation of elevator systems.
Provide elevator components manufactured by companies regularly engaged in the manufacture of elevator components. Utilize only licensed and certified elevator personnel for the installation, adjusting, testing, and servicing of the elevators.
1.4.1.1 Elevator Contractor's Elevator Technicians
For elevator installations in the United States, including United States territories, perform all elevator related work under the direct guidance of a state certified elevator technician with a minimum of three years of experience in the installation of elevator systems of the type and complexity specified in the contract documents. Provide an endorsement letter from the elevator manufacturer, certifying that the elevator specialist is qualified. All elevator technicians must carry a current certification issued by one of the following organizations:
a. National Association of Elevator Contractors (NAEC)
b. National Elevator Industry Education Program (NEIEP)
1.4.2 Manufacturers' Technical Support
Provide elevator components from manufacturers that provide factory training and online and live telephone elevator technical support to any elevator installation, service, and maintenance contractor. Provide elevator components from manufacturers that guarantee accessibility to all replacement and repair parts and components to any elevator installation, service, and maintenance contractor. Use only elevator component manufacturers that provide current published price lists for all elevator parts and components.
1.4.3 Operation and Maintenance Data
Assemble all shop drawing and product data material into O&M Data Packages in accordance with Article SUBMITTALS. Provide two complete O&M Data Packages in hard copy and two complete electronic O&M data packages on separate CDs, in PDF format. Provide all O&M Data Packages to Contracting Officer. Include controller diagnostic documentation and software as required under Article CONTROL EQUIPMENT.
SECTION 14 21 23 Page 5
1.4.4 Wiring Diagrams
Provide complete wiring diagrams and sequence of operations, which show electrical connections and functions of elevator systems. Provide one set (11 inch by 17 inch minimum size) of wiring diagrams, with individual sheets laminated in plastic and assembled in binder, to be stored in the machine room or control room cabinet. Provide one additional hard copy set and two complete electronic sets on separate CDs, in PDF format.
Provide all wiring diagram sets to the Contracting Officer. Coded diagrams are not acceptable unless fully identified.
1.4.5 Machine Room/Control Room Cabinet
For storage of O&M Data Packages and Wiring Diagrams, provide locking metal cabinet with a minimum size of 20 inch W by 12 inch D by 30 inch H.
Cabinet must be sized large enough to accommodate all O&M Data and hardware required in paragraphs OPERATION AND MAINTENANCE DATA and WIRING DIAGRAMS. Secure cabinet to machine room or control room wall.
1.5 NEW INSTALLATION SERVICE
Provide elevator warranty service in accordance with the manufacturer's maintenance plan, warranty requirements, and applicable safety codes, for a period of 12 months after the date of acceptance by Contracting Officer. Perform this work during regular working hours. Provide supplies and parts to keep elevator system in operation. Perform service only by factory trained personnel. Provide Bi-weekly services to include repairs, adjustments, greasing, oiling, and cleaning. Provide service log in elevator machine room or control room cabinet and update Bi-weekly, throughout the one-year warranty period.
Provide 24-hour emergency service, with one hour on-site response time, during this period without additional cost to the Government.
1.5.1 Periodic Elevator Certification Inspection and Testing
Provide elevator mechanic to support QEI Certified Elevator Inspector in the periodic six-month and the annual Category 1 elevator certification inspection and testing. Perform Category 1 inspection and testing no greater than 30 days prior to the end of the warranty period. Perform all elevator certification testing in the presence of QEI Certified Elevator Inspector.
In conjunction with the testing noted above, test systems for Emergency Power Operation, Earthquake Emergency Operation, and Hospital Emergency Commandeering Service Operation, as applicable. Schedule so that testing does not interfere with building operations.
1.6 FIRE PROTECTION SYSTEM
Coordinate interface between building fire protection system and elevator controls.
Additional fire protection requirements are located in: Section 21 13 13.00 10 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION; and Section
26 20 00 INTERIOR DISTRIBUTION SYSTEM.
SECTION 14 21 23 Page 6
1.6.1 Fire Sprinklers
Provide fire sprinklers in accordance with all applicable safety codes and with Section 21 13 13.00 10 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION.
Provide shutoff valve, check valve, and non-adjustable, zero time-delay flow switch, in each sprinkler line immediately outside of each machine room, control room, and hoistway, as applicable. Provide inspectors' test valve for periodic testing of flow switch and shunt trip disconnect.
Pipe sprinkler piping serving these spaces in a series manner with no laterals. Locate inspectors' test connection at the end of pipe runs such that operation of the test connection will purge air from system piping.
1.6.2 Shunt Trip Disconnect
Provide flow switches specified in paragraph FIRE SPRINKLERS to comply with ASME A17.1/CSA B44 and NFPA 72 for shunt trip of the main line power supply. For each elevator, provide control wiring connecting the flow switch to a shunt trip equipped circuit breaker located in the elevator machine room or control room. Upon flow of water, flow switch will instantaneously cause opening of the shunt-trip circuit breaker and remove power from the elevator. Flow switch must also send a signal to fire alarm control panel to indicate water flow condition.
PART 2 PRODUCTS
2.1 General Requirements
LEED v4 Material and Product Requirements: Refer to Section 01 33 29 - Sustainable Design Requirements for LEED v4 BD+C, relative to manufacturers' sustainable materials criteria for all applicable products covered in this section.
2.2 ELEVATOR DESCRIPTION
Provide elevator system that complies with ASME A17.1/CSA B44 in its entirety, ASME A17.2 in its entirety, and additional requirements specified herein. Provide elevator system that meets or exceeds the NEII-1 Ride Quality Performance Standards Matrix (RQPSM). For elevator speeds of 500 fpm and higher, comply with the RQPSM "High Performance" criteria.
For elevator speeds 350 fpm, up to but not including 500 fpm, comply with the RQPSM "Intermediate Performance" criteria.
Provide and install elevators in accordance with 36 CFR 1191 - ABAAS, ICC IBC , IEEE C62.41 , NFPA 70 and NFPA 101 requirements.
2.2.1 Elevator Design Parameters
2.2.1.1 Elevator No.Two - Larger Size and Capacity "C3" Freight Loading
a. Type: Geared
b. Rated load: 4500 lb.
c. Rated Speed: 350 fpm
d. Car Door Type: Two -speed, horizontally sliding.
e. Car Door Opening Width:4 ft.-0 in.
SECTION 14 21 23 Page 7
2.2.1.2 Elevator No.One
a. Type: Geared
b. Rated load: 3500 lb.
c. Rated Speed: 350 fpm
d. Car Door Type: Single speed side slide, horizontally sliding.
e. Car Door Opening Width: 3 ft.-6 in. minimum.
2.2.2 Cab Enclosure and Hoistway Entrance Assemblies
Provide finishes as listed below:
a. Floor; vinyl sheet tile.
b. Walls; Provide prefinished painted steel shell with raised wall panels and brushed stainless steel reveals. Provide textured metal, 5WL pattern stainless steel on raised plywood panels. Provide each cab wall with equally spaced and equally sized wall panels. All wall panel fasteners must be concealed.
Wall trim; stainless steel.
Accessories; Provide hand rails on full length of back wall and side walls of elevator cab.
c. Car doors, car door returns, and wall reveals; stainless steel.
d. Ceilings; Provide manufacturers standard island type metal ceiling in brushed stainless steel finish with LED type downlights.
e. Hoistway Entrance Assembly Material and Finishes; stainless steel.
2.3 ELEVATOR OPERATION
ASME A17.1/CSA B44 , Introduction, Section 3, Definitions.
2.3.1 Group Automatic Operation
Provide Group Automatic Operation. If a car is taken out of service, or fails to respond to a landing call within a predetermined adjustable time limit of approximately 40 to 180 seconds, transfer calls to another car until out-of-service car is returned to the system.
2.4 SPECIAL OPERATION AND CONTROL
Provide the following special operations and control systems.
2.4.1 Keys for Elevator Key Switches
Provide a minimum of twelve keys per unique cylinder used on all key switches for a single elevator. If there is more than one elevator, additional keys will not be required unless there are additional unique lock cylinders. Provide keys with brass or fiberglass tags marked "PROPERTY OF THE U.S. GOVERNMENT" on one side with function of key or
SECTION 14 21 23 Page 8 approved code number on the other side.
2.4.1.1 Protocol
Key Protocol:
a. Fan speed, cab and work lighting must be a toggle switch for each located behind a locked service panel located on the COP and the service panel door shall be designed with elevator certificate window that will accommodate a 4 inch X 6 inch operating certificate with cert window in door.
b. EX511 Key should operate Buzzer reset/Loss of communication (located at the fire recall level).
c. EX512 Key should open the locked service panel door on the Car Operating Panel (COP) and the Stop/Parking (located inside the locked service panel door on the COP).
d. EX513 Key should operate Independent service (located on the COP available to the public (not behind the locked service panel door.
e. EX514 Key should operate Inspection/Access Enable (located inside the locked service panel and at the top and bottom terminal landings.
Locate switch in the lobby wall, 6 feet above floor level and within 12 inches of elevator hoistway entrance frame.
f. EX516 Key should operate Hospital Commandeering/Car to Lobby If supplied (located in the cab on the COP and at every landing hall call station).
g. FEOK1 Key should operate Fire Service (phase 1 and 2) and Fire Department Key Lock Box to be located at the fire recall level within 20” of the door jamb at a height of 6’.
2.4.2 Firefighters' Emergency Operation (FEO)
Provide FEO equipment and signaling devices. The designated level for the FEO Phase I key operated switch is the First floor level. In the FEO Phase I fixture, provide FEO Operating Instructions.
2.4.2.1 Firefighters' Emergency Operation (FEO) Key Box
Provide flush mounted, locking, FEO Key Box of a minimum size of 5 inch W by 9 inch H by 1.5 inch D. Install at a height of 6 feet above floor level and directly above the FEO Phase I key switch. Provide box equipped with lock that uses the FEO K1 key.
2.4.3 Hoistway Access Operation
Provide hoistway access operation with switches at top and bottom terminal landings. Locate switch 6 feet above floor level, within 12 inches of elevator hoistway entrance frame or with the ferrule exposed when located in the elevator entrance frame.
2.4.4 In-Car Inspection Operation
Provide In-Car Inspection Operation.
SECTION 14 21 23 Page 9
2.4.5 Independent Service
Provide exposed key-operated switch in car operating panel to enable independent service and simultaneously disable in-car signals and landing-call responses. Provide indicator lights that automatically illuminate during independent service. For duplex or group operation, if one car is removed from group another car will respond to its hall calls.
2.4.6 Selective Door Operation
For elevator with one or more rear openings at same level as front opening, provide full-selective operation with car and door operating buttons clearly marked for front and rear openings, front and rear car button for each such floor, and front and rear "DOOR OPEN" and "DOOR CLOSE" buttons. Only door for which the button was operated opens or closes.
2.4.7 Elevator Emergency Power Operation
Provide elevator emergency power operation for all elevators. Coordinate power supply and control wiring to accomplish initiation and operation of elevators on emergency power.
2.5 ELEVATOR DRIVE MACHINE, HOIST MOTOR, AND DRIVE MOTOR
Provide elevator drive machine, hoist motor, and motor drive system that is designed to be installed in an elevator machine room (MR) or an elevator machinery space. The elevator machine, motor, and drive configuration and installation design must be mechanically and electrically interchangeable with a minimum of two other elevator manufacturer's drive machines that are readily available in the elevator industry. Paint or finish ferrous surfaces with a minimum of one coat of manufacturer applied rust- inhibiting paint.
Design the elevator drive system so that the hoist motor amperage does not exceed the motor data tag full load amperage in any operating condition, exclusive of acceleration and deceleration. Provide elevator hoist motor that is designed with Class F insulation and rated for 120 starts/hr.
Design the elevator drive system to limit Total Harmonic Distortion to a maximum of 5 percent. No single harmonic may exceed 3 percent.
Provide an elevator drive machine designed for and provided with stranded steel wire rope for elevator suspension and counterbalance. The minimum acceptable diameter of suspension and counterweight ropes is 3/8 inches.
Aramid fiber ropes, coated steel ropes, and non-circular coated steel belts may not be used for elevator suspension or counterbalance.
The elevator drive machine must be equipped with machine manufacturer's designed and installed standard means for the manual release of the driving-machine brake.
2.5.1 Manufacturer's Factory Training and Technical Support
Provide an elevator drive machine from a manufacturer that provides comprehensive factory training and technical support for installation, adjustment, service, and maintenance of the drive system. The training and support must be identified as available to any licensed elevator contractor. Provide verification of an established and documented training schedule, with pricing, for factory training classes that have
SECTION 14 21 23 Page 10 been provided for a minimum period of one year prior to contract award date.
The elevator drive system must be identified as available for purchase and installation by any licensed elevator contractor. All drive system related components, parts, diagnostic tools, and software must be available for purchase, installation, and use by any licensed elevator contractor; "exchange-only" provisions for the purchase of spare parts are not acceptable.
2.5.2 Ascending Car Overspeed and Unintended Car Movement Protection
Provide elevator Ascending Car Overspeed and Unintended Car Movement Protection means that is designed to act directly upon, and apply a retarding force to, the elevator suspension ropes. In addition to the requirements of ASME A17.1/CSA B44 , the means must be designed to detect and stop movement of the elevator suspension ropes that occurs as a result of loss of traction between the suspension ropes and the elevator machine drive sheave.
2.6 CONTROL EQUIPMENT
Enclose all elevator control equipment in factory-primed and baked-enamel coated sheet-metal cabinets with ventilation louvers and removable or hinged doors. Mount cabinets at a height of 10 inches above machine room or control room finish floor.
2.6.1 Motor Control Equipment
Provide variable voltage with silicon controlled rectifier (SCR) or Variable-Frequency Variable Voltage (VVVF) alternating current (ac) drive control.
2.6.1.1 Electrical Isolation Protection
Provide individual isolation transformers and individual choke reactors for each individual hoist motor. Provide filtering to maintain harmonic distortion below IEEE C62.41 standards as measured at the elevator machine room or control room disconnect.
2.6.2 Elevator Microprocessor Controller
For each individual elevator controller, and for each group controller, provide a microprocessor controller that complies with the following paragraphs. Provide controller(s) package that includes all hardware and software required for the installation, maintenance, and service of the elevator, in its' entirety. Provide verification of technical support service that the controller manufacturer provides to any licensed elevator installation, service, and maintenance company.
Provide an elevator controller from a manufacturer that provides comprehensive factory training to include controller installation, adjustment, service, and maintenance. The training must be identified as available to any licensed elevator contractor. Provide verification of an established and documented training schedule, with pricing, for factory training classes that manufacturer has provided for a minimum period of one year prior to contract award date.
The elevator controller must be identified as available for purchase and
SECTION 14 21 23 Page 11 installation by any licensed elevator contractor. All components, parts, diagnostic tools, and software must be available for purchase and installation and use by any licensed elevator contractor; "exchange-only" provisions for the purchase of spare parts are not acceptable. The elevator controller manufacturer must publish an industry competitive price listing for all controller parts, diagnostic tools, and software.
Provide verification of telephone and internet based technical support service that the elevator controller manufacturer provides to any licensed elevator installation, service, and maintenance company at an industry competitive price. The service must include live telephone based technical support for installation, adjustment, maintenance, and troubleshooting of the elevator controller and related elevator components. The service must be available during standard working hours.
Provide an elevator controller that is designed to automatically reestablish normal elevator operation following any temporary loss of power, regardless of duration.
2.6.2.1 Elevator Controller Interface Cabinet
For each individual elevator microprocessor controller, provide a separate elevator control cabinet with an integrated human interface system. For group elevator installations, a single cabinet and interface system with full access to each elevator controller may be utilized. The separate controller interface cabinet must be supplied by the elevator controller manufacturer and include a minimum 12 inch wide keyboard and a minimum 10 inch monitor. The elevator controller interface cabinet must comply with arc-flash protection requirements of NFPA 70E and UFC 3-560-01 .
2.6.2.1.1 Elevator Microprocessor Human Interface
The interface system must provide complete elevator controller interface capability and must include the elevator controller manufacturer's comprehensive package of installation and diagnostic software. The microprocessor interface system must provide unrestricted access to all parameters, all levels of adjustment, and all flags necessary for installation, adjustment, maintenance, and troubleshooting of each elevator and for the elevator group. All software programming must be stored in non-volatile memory. The elevator controller fault log must provide non-volatile memory fault log storage of all faults, trouble calls, and fault history for a minimum of one year and the ability to download or print the fault log. The controller interface must also provide the capability to display and diagnose trouble calls, faults, and shutdowns. Expiring software, degrading operation, and "key" access controls are not acceptable.
2.6.2.2 Software and Documentation
Provide three copies of the manufacturer's maintenance and service diagnostic software, with complete software documentation, that will enable the same level of unrestricted access to all controllers of the same make and model, regardless of the installation date or location.
Provide signed certification, from the manufacturer's corporate headquarters, that guarantees that the microprocessor software and access system will not terminate the unlimited and unrestricted access at any future date.
SECTION 14 21 23 Page 12
2.6.2.3 Elevator Controller Certification
For elevator installations in the United States, including United States territories, provide an elevator microprocessor controller that has a current certificate of safety code compliance issued by the Technical Standards and Safety Authority (TSSA), Toronto, Canada.
2.7 OPERATING PANELS, SIGNAL FIXTURES, AND COMMUNICATIONS CABINETS
For all panels and fixtures, provide identical and uniform fixture design, material, finish, and components for all elevators. For all panels and fixtures, legibly and indelibly identify all buttons and all operating positions for each device. Use engraving and backfilling, or photo etching, for button and switch designations. Do not use attached signs.
Provide elevator manufacturers' standard grade for all key switches unless otherwise specified. All illuminating panels and fixture components must utilize LED lighting for energy efficiency.
2.7.1 Car and Hall Buttons
For all cab and landing fixture buttons, provide industry-standard, vandal resistant push buttons with positive-stop assembly design. Buttons must be minimum 3/4 inch diameter, satin-finish stainless steel, with illuminating LED halo.
2.7.2 Passenger Car-Operating Panel
Provide each car with one car operating panel that contain operation controls and communication devices. Provide exposed, flush mounted buttons for the controls identified in subparagraph PASSENGER CONTROLS.
Provide a lockable service cabinet for the controls listed in subparagraph SERVICE CONTROLS. Use engraving and backfilling or photo etching for button and switch designations. Do not use attached signs.
2.7.2.1 Passenger Controls
In addition to ASME A17.1/CSA B44 requirements, provide the following operating controls, identified as indicated:
a. LED illuminating car-call buttons identified to correspond to landings served by the elevator.
b. "DOOR OPEN" and "DOOR CLOSE" buttons. For front and rear openings at the same floor, include the identification "F" and "R" for each opening.
c. Red, illuminating "ALARM" button.
d. Key-operated "Independent Service" switch.
e. "Help" communication device to include communication between elevator cab and elevator machine room or control room.
2.7.2.2 Service Controls
In addition to ASME A17.1/CSA B44 requirements, provide the following operating controls, identified as indicated:
a. Provide a key-operated, three-position switch for "In car Inspection
SECTION 14 21 23 Page 13
Operation" and "Hoistway Access". The center switch position will provide normal, automatic operation.
b. "Car Light" switch.
c. "Car Fan" switch with two speed settings identified.
d. 120-volt ac 60 Hz single-phase duplex electrical outlet of ground-fault-circuit-interrupt (GFCI) design.
2.7.2.3 Certificate Window
Provide a minimum 4 inch wide by 6 inch high certificate window for elevator inspection certificate. Locate window in the Service Controls door of the Car Operating Panel.
2.7.2.4 Emergency Signaling Devices
Provide an audible signaling device, operable from the Car Operating Panel button marked "ALARM". The audible signaling device must have a sound pressure rating between 80 and 90 dBA at 10 ft. Provide battery backup power capable of operating the audible signaling device for at least one hour.
2.7.3 Elevator In-Car Position Indicators
For all elevators, provide illuminating LED position indicator in the Car Operating Panel.
2.7.4 Elevator In-Car Direction Indicators
For 2-stop elevator installations, provide visual direction indicators and audible car arrival signal in the elevator car door jamb, in accordance with ABA Standards. Visual indicators must be visible from the hall call fixture.
2.7.5 Hall Call Landing Fixtures
Provide a hall call fixture adjacent to each elevator. Provide a single push-button for terminal landings and dual push-buttons, up and down, at intermediate landings.
2.7.5.1 Designated Landing Hall Call Fixture
2.7.5.1.1 Location of COMMUNICATION MEANS FAILURE (CMF) Visual Signal
When required by ASME A17.1/CSA B44 , provide an elevator CMF audible and illuminating signal, and reset switch, in the FEO Designated Landing hall call fixture. Mount the signal and reset switch at a minimum of 7 inches above the "UP" hall call button.
2.7.5.1.2 COMMUNICATION MEANS FAILURE (CMF) Visual and Audible Signal Operation
Provide a CMF visual and audible signal system that conforms to ASME A17.1/CSA B44 . Provide continuous verification of operability of the telephone line and immediate activation of audible and visual signals when verification means determines that the telephone line is not functioning.
Provide illumination of visual signal at one second intervals. Provide a
SECTION 14 21 23 Page 14 minimum of 65 dBA audible signal at 30 second intervals.
2.7.5.1.3 Firefighters' Emergency Operation Phase I Switch and Visual Signal
When required by ASME A17.1/CSA B44 , provide an elevator Firefighters' Emergency Operation Phase I switch and illuminating visual signal in the FEO Designated Landing hall call fixture. Provide FEO Phase I visual signal that is designed with intermittent, flashing, illumination when actuated by the machine room, control room, or hoistway fire alarm initiating device. Locate FEO Phase I key switch above the CMF visual signal with a minimum of 6 inches vertical between the centerlines of the CMF signal and the FEO Phase I key switch. Locate FEO Phase I visual signal directly above the Phase I switch. In addition, locate Elevator Corridor Call Station Pictograph at top of hall call fixture.
2.7.6 Elevator Car Position and Direction Indicators and Car Arrival Signal
For elevator installations with three or more stops, provide a separate hall landing fixture that includes the visual elevator position indicator, visual direction indicators, and audible car arrival signal, in accordance with ABA Standards.
2.7.7 Designated Landing Elevator Identification Fixture
For duplex and group elevator installations, provide a separate elevator identification fixture for each elevator, with identification engraved and backfilled with a contrasting color. Number elevators from left to right, as seen during primary approach from building main entrance to elevator lobby. For multiple elevator groups, begin numbering with group that is closest to the building main entrance.
2.7.8 Emergency or Standby Power
When emergency or standby power is provided for elevator operation, provide an elevator emergency power visual indicator that conforms to ASME A17.1/CSA B44 . Locate the visual signal in the Firefighters Emergency Operation fixture for each simplex elevator and for each elevator group. When an emergency power selector switch is required, provide switch in a separate, flush mounted fixture located at the designated level, in view of all elevator entrances.
2.8 CAR DOOR EQUIPMENT
2.8.1 Car Door Operator - Linear Type
Provide linear type elevator door operator equipment and circuitry that is designed and installed as discreet communication. Serial communication must not be used for this system.
2.8.2 Infra-red Curtain Unit
Provide Infra-red Curtain Unit (ICU) with multiple infra-red beams that protect to the full height and width of the door opening. Provide door nudging operation.
SECTION 14 21 23 Page 15
2.9 PASSENGER ELEVATOR GUIDES, PLATFORM, AND ENCLOSURE
2.9.1 Roller Guides
Provide coil-spring loaded roller guide assemblies in adjustable mountings on each side of car and counterweight frames in accurate alignment at top and bottom of frames.
2.9.2 Car Enclosure Wall Panels, Return Panels, Doors, Entrance Columns, and Transom
Provide 14 Gauge minimum stainless steel cab wall panels and entrance components. Use same material and finish for all hoistway and car entrance assemblies. Apply sound-deadening material on exterior of all cab wall panels.
2.9.3 Car Enclosure Top
Provide reinforced, 12 gauge minimum steel car enclosure top. Provide hinged emergency exit with lock that complies with the seismic risk zone 2 or greater design requirements of ASME A17.1/CSA B44 . Locate emergency exit hinge towards the rear of the elevator cab. Design and configure the elevator cab interior ceiling to provide convenient and unobstructed access to, and use of, emergency exit from inside the elevator cab.
2.9.4 Car Door
Provide 16 gauge minimum stainless steel car doors of sandwich construction with flush surfaces on car and landing sides. Provide a minimum of 2 door guide assemblies per door panel, one guide at leading and one at trailing door edge with guides in the sill groove their entire length of travel.
2.9.5 Car Entrance Sill
Provide one piece cast nickel silver, stainless steel, or white bronze entrance sill(s). Set sills level and flush with floor finish. Use same material for hoistway and car entrance sills.
2.9.6 Cab Finish Floor
Provide cab finish floor with top of finish floor flush with the cab sill.
2.9.7 Car Fan
Provide 2-speed fan for car enclosure forced ventilation. Fan must be mounted in the car enclosure top.
2.9.8 Car Lighting
Utilize LED lighting for elevator car interior illumination. Provide a minimum of 10 foot-candles, measured at all areas of the car enclosure floor. Provide automatic car lighting operation that will turn off car lights after 3 minutes of inactivity. Car lights must automatically turn on upon actuation of an elevator car or hall call.
2.9.9 Car Protection Pads and Hooks
Provide fire retardant, hanging car protection pads that provide
SECTION 14 21 23 Page 16 protection for all car interior wall panels. Provide permanently installed studs in car that are designed for hanging the car protection pads in the car.
2.10 PASSENGER ELEVATOR HOISTWAY DOORS AND ENTRANCES
Provide hoistway entrance assemblies with a minimum 1-1/2 hour fire rating. Use same material and finish for all hoistway and car entrance assemblies.
2.10.1 Hoistway Entrance Frames
Provide 14 gage minimum stainless steel hoistway entrance frames. Solidly grout uprights of entrance ways to height of 5 feet.
2.10.2 Hoistway Entrance Sills
Provide one-piece cast nickel silver, stainless steel, or white bronze entrance sills. Set top of landing sill flush with top of finish floor.
Solidly grout under full length of sill. Use same material for all hoistway and car entrance sills.
2.10.3 Hoistway Entrance Doors
Provide stainless steel non-vision construction hoistway entrance doors with flush surfaces on car and landing sides. Provide a minimum of 2 door guide assemblies per door panel, one guide at leading edge and one at trailing edge with guides in the sill groove the entire length of door travel. Use same material and finish for all hoistway and car entrance assemblies.
2.10.4 Hoistway Entrance Door Track Dust Covers
Provide sheet metal hoistway door track dust covers at each landing. Dust covers must cover top and hoistway side of door locks and door roller tracks, and extend the full width of the door track and associated hardware. Dust cover sections will not exceed 3 feet in length.
2.11 HOISTWAY EQUIPMENT
2.11.1 Car and Counterweight Guide Rails and Fastenings
Provide T-section type guide rails for car and counterweight. Paint rail shanks with one coat of black enamel.
2.11.2 Pit Equipment and Support Channels
Provide rail-to-rail pit channels to serve as mounting surface for main guide rails and counterweight guide rails. In addition, pit channels will serve as mounting surfaces for car and counterweight buffers. Method of installation of channels, brackets and buffer mounts will be such that pit waterproofing is not punctured.
2.11.3 Pit "STOP" Switch
Provide push-to-stop/pull-to-run type pit "STOP" switch.
SECTION 14 21 23 Page 17
2.11.4 Traveling Cables
Suspend traveling cables by means of self-tightening webbed devices or internal suspension members. At least one travel cable shall contain a minimum of eight (8) shielded twisted pair and one (1) coaxial cable for The Owner's use. Provide a separate junction box on the cartop and at the controller that is clearly identified as "Security and Communication Wiring and Coaxial Cable". All unused conductors shall be neatly coiled and stored within the junction boxes.
2.11.5 Hoistway Pit Ladder
Provide continuous horizontal rungs for the full height of the pit ladder.
PART 3 EXECUTION
3.1 INSTALLATION
Install in accordance with DOD design criteria, contract specifications, manufacturer's instructions, NEII-1 Building Transportation Standards and Guidelines, and all applicable building and safety code requirements.
3.1.1 Structural Members and Finish Materials
Do not cut or alter structural members. Do not alter finish materials from manufacturer's original design. Restore any damaged or defaced work to original condition.
3.1.2 Miscellaneous Requirements
Provide recesses, cutouts, slots, holes, patching, grouting, and refinishing to accommodate elevator installation. Use core drilling to drill all new holes in concrete. Finish work to be straight, level, and plumb. During installation, protect machinery and equipment from dirt, water, or mechanical damage. At completion, clean all work and spot paint.
3.2 FIELD QUALITY CONTROL
The Contractor will provide and utilize a third-party licensed and certified Qualified Elevator Inspector (QEI) to conduct elevator pre-acceptance inspection and testing. The QEI must perform inspections and witness tests to ensure that the installation conforms to all applicable safety codes and contract requirements. The QEI will be directly employed by the Contractor and independent of the elevator contractor.
Upon completion, the QEI must provide written test data for all ASME A17.1/CSA B44 Acceptance Tests and written certification that the elevator is complete and ready for final Acceptance Inspection, Testing, and Commissioning.
3.3 ACCEPTANCE INSPECTION, TESTING AND COMMISSIONING
When elevator system installation is complete and ready for final inspection, notify Contracting Officer that elevator system is ready for Acceptance Inspection, Testing, and Commissioning. Provide QEI certification specified in Article FIELD QUALITY CONTROL.
Contracting Officer will obtain the services of a third-party QEI
SECTION 14 21 23 Page 18
Certified Elevator Inspector. The QEI must utilize an Elevator Acceptance Inspection Form to record the results of inspection and all testing and to identify safety code and contract deficiencies. Specific values must be provided for all tests required by ASME A17.1/CSA B44 , ASME A17.2 , and contract documents. Upon completion of inspection and testing, the QEI must sign a copy of the completed forms and provide to the Contracting Officer. Within 2 weeks of the inspection, the QEI must also prepare a formal inspection report, including all test results and deficiencies.
Upon successful completion of inspection and testing, the QEI will complete, sign, and provide a certificate of compliance with
ASME A17.1/CSA B44 .
3.3.1 Acceptance…