This solicitation is for the design and construction of an Attack Aviation Battalion Complex to be located at Fort Riley, Kansas. Work includes an aircraft hangar, maintenance shops, administrative space, parts and tool storage, hazardous materials storage, petroleum storage, ground support equipment storage, covered vehicle storage, apron pavements, cyber security, building systems, fire protection, antiterrorism measures, and energy monitoring. Supporting facilities comprise site development, utilities, lighting, paving, parking, storm drainage, landscaping and signage. Self-contained heating and air conditioning will be provided. Required utility connections consist of electric distribution, generation and transmission, natural gas, water, wastewater and central systems. The solicitation was issued by the Department of the Army Corps of Engineers Kansas City District.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL STRUCTURAL NOTES
I. APPLICABLE CODES:
A. ACI 301, SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS.
B. ASCE 7-16, MINIMUM DESIGN LOADS AND ASSOCIATED CRITERIA FOR BUILDINGS AND
OTHER STRUCTURES, WITH SUPPLEMENT NUMBER 1.
C. AWS D1.1 STRUCTURAL WELDING CODE, STEEL, 2020.
D. IBC, INTERNATIONAL BUILDING CODE, IBC 2021.
E. SP-66 (204), ACI DETAILING MANUAL.
F. ACI 318/318R-19, BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE.
G. TMS 402-16 BUILDING CODE FOR MASONRY STRUCTURES.
H. AISC STEEL CONSTRUCTION MANUAL, 15TH EDITION AND AISC 360-16 SPECIFICATION FOR
STRUCTUAL STEEL BUILDINGS.
I. AISI S100-16 NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD FORMED STEEL
STRUCTURAL MEMBERS, WITH SUPPLEMENT NUMBER 2.
J. UFC 1-200-01, 04 FEBRUARY 2023, DOD BUILDING CODE (GENERAL BUILDING
REQUIREMENTS).
K. UFC 3-301-01, 11 APRIL 2023, STRUCTURAL ENGINEERING.
L. UFC 4-010-01, W/ CHANGE 2, 30 JULY 2022, DOD MINIMUM ANTI-TERRORISM STANDARDS
FOR BUILDINGS.
II. DESIGN LOADS
A. RISK CATEGORIES
1. RISK CATEGORY= II (UNO)
2. RISK CATEGORY FOR HANGAR (MAINTENANCE BAY , AIRCRAFT PARTS SUPPLY
ROOMS 152 & 152A AND ADMIN / SHOPS AREA) = III
B. DEAD LOAD (IN ADDITION TO FRAMING SELF WEIGHT)
1. ROOF DEAD LOAD (NOT INCLUDING COLLATERAL DEAD LOAD):
a. MAINTENANCE BAY (INCLUDING AIRCRAFT PARTS SUPPLY ROOMS 152 &
152A) = 10 PSF
b. ADMIN / SHOPS AREA = 10 PSF
c. GSE / ASIOE OPEN COVERED STORAGE = 5 PSF
d. HAZMAT / POL BUILDINGS = 10 PSF
e. FIRE PUMP BUILDING = 10 PSF
2. COLLATERAL DEAD LOAD APPLIED TO BEAM AND JOIST BOTTOM CHORDS (NOT
USED WITH ANY UPLIFT LOAD CASES):
a. ABOVE MEP ROOMS IN ADMIN / SHOPS AREA = 20 PSF
b. ABOVE MB AND AIRCRAFT PARTS SUPPLY ROOM = 20 PSF
c. ALL OTHER AREAS = 10 PSF
d. ALL MEP & FP EQUIPMENT LOADS GREATER THAN 100 LBS HAVE BEEN
CONSIDERED SEPARATE FROM THE COLLATERAL LOADS LISTED ABOVE
3. SECOND FLOOR OF ADMIN / SHOPS AREA (EXCLUDING MEP ROOMS) = 66 PSF,
WHICH INCLUDES 15 PSF CONCRETE OVERPOUR ALLOWANCE
4. SECOND FLOOR MEP ROOMS OF ADMIN / SHOPS AREA = 86 PSF, WHICH
INCLUDES 15 PSF CONCRETE OVERPOUR ALLOWANCE AND 20 PSF FOR
ALLOWANCE FOR 4” CONCRETE HOUSEKEEPING PADS
5. ARMS VAULTS 8” CONCRETE ROOFS IN ADMIN / SHOPS AREA = 115 PSF
C. LIVE LOAD (UNREDUCIBLE, UNO)
1. ROOF LIVE LOAD = 20 PSF (REDUCIBLE)
2. A 300 LB CONCENTRATED LOAD APPLIED TO OPEN WEB STEEL ROOF JOIST
BOTTOM CHORD PANEL POINTS (AT ALL PANEL POINTS, BUT NOT ACTING
CONCURRENTLY)
3. 10 TON CAPACITY OVERHEAD BRIDGE CRANES IN HANGAR MAINTENANCE BAY –
REFER TO S-131 FOR CRANE COVERAGE AREA
4. 2 TON CAPACITY OVERHEAD CRANE IN HANGAR ADMIN / SHOPS AREA – REFER TO
S-131 FOR SPECIFIC CRANE COVERAGE AREA
5. RADIO ANTENNA PLATFORM ON ROOF OF ADMIN / SHOPS AREA = 250 PSF
(UNREDUCIBLE)
6. MECHANICAL AND ELECTRICAL ROOMS AND PLATFORMS = 125 PSF
7. FIRST FLOORS = 125 PSF (UNO)
8. HANGAR MAINTENANCE BAY CONCRETE SLAB-ON GRADE: PER SECTION 6-4.1.1 OF
UFC 4-211-01 (UH-60).
9. ARMS ROOM FLOOR = 150 PSF
10. ARMS ROOM ROOF = 100 PSF
11. SECOND FLOOR OF ADMIN / SHOPS AREA = 80 PSF (UNO) - UNREDUCIBLE
12. ALSE SHOP AND STORAGE ROOMS (210 & 211) = 125 PSF
13. ELEVATOR LOBBIES = 100 PSF (UNREDUCIBLE)
14. STAIRS = 100 PSF (UNREDUCIBLE) AND A 300 LB POINT LOAD ACTING ON 4 SQUARE
INCHES
D. SNOW LOAD
1. GROUND SNOW, Pg = 20 PSF
2. IMPORTANCE FACTOR, Is = 1.0 (UNO)
3. IMPORTANCE FACTOR FOR HANGAR (MAINTENANCE BAY, AIRCRAFT PARTS
SUPPLY ROOMS 152 &152A AND ADMIN / SHOPS AREA), Is = 1.1
4. MINIMUM ROOF SNOW LOAD, Pm = 20 PSF (UNO)
5. MINIMUM ROOF SNOW LOAD FOR HANGAR (MAINTENANCE BAY, AIRCRAFT PARTS
SUPPLY ROOMS 152 & 152A AND ADMIN / SHOPS AREA), Pm = 22 PSF
6. THERMAL FACTOR, Ct = 1.0 (UNO); Ct = 1.2 (CANOPIES AND GSE / ASIOE OPEN
COVERED STORAGE)
7. EXPOSURE FACTOR Ce = 1.0
8. SNOW DRIFT LOADS – REFER TO S-641 & S-641A
9. UNBALANCED SNOW LOADS – REFER TO S-641 & S-641A
E. WIND LOAD
1. BASIC WIND SPEED (3 SECOND GUST) = 111 MPH (UNO)
2. BASIC WIND SPEED (3 SECOND GUST) FOR HANGAR (MAINTENANCE BAY, AIRCRAFT
PARTS SUPPLY ROOMS 152 & 152A AND ADMIN / SHOPS AREA) = 120 MPH
3. OVERALL EXPOSURE CATEGORY = C
4. TOPOGRAPHIC FACTOR, Kzt = 1.0
5. DIRECTIONALITY FACTOR, Kd = 0.85
6. INTERNAL PRESSURE COEFFICIENT, Gcpi = +/- 0.18 (UNO)
7. INTERNAL PRESSURE COEFFICIENT FOR GSE / ASIOE OPEN COVERED STORAGE,
Gcpi = 0
8. WIND LOADING TO HANGAR MAINTENANCE BAY IS DETERMINED PER SECTION 2-4.6
OF UFC 3-301-01
9. INTERNAL PRESSURE COEFFICIENT FOR HANGAR MAINTENANCE BAY,AIRCRAFT
PARTS SUPPLY ROOMS 152 & 152A AND DEMISING WALL BETWEEN MAINTENANCE
BAY AND ADMIN / SHOPS AREA Gcpi = +/- 0.44 (CONSIDERING LARGE VOLUME
REDUCTION FACTOR)
10. GROSS WIND PRESSURES FOR COMPONENTS AND CLADDING DESIGN – REFER TO
S-640 AND S-640A.
6. ANALYSIS PROCEDURE = EQUIVALENT LATERAL FORCE
7. IMPORTANCE FACTOR, Ie = 1.0 (UNO)
8. IMPORTANCE FACTOR FOR HANGAR (MAINTENANCE BAY, AIRCRAFT PARTS SUPPLY
ROOMS 152 & 152A AND ADMIN / SHOPS AREA), Ie = 1.25
9. SEISMIC DESIGN CATEGORY, SDC = B
10. BASIC SEISMIC FORCE RESISTING SYSTEM:
a. HANGAR MAINTENANCE BAY = STEEL ORDINARY BRACED FRAMES (NOT
SPECIFICALLY DETAILED FOR SEISMIC RESISTANCE)
b. HANGAR ADMIN / SHOPS AREA = INTERMEDIATE REINFORCED MASONRY
SHEAR WALLS
c. AIRCRAFT PARTS SUPPLY ROOMS 152 & 152A = INTERMEDIATE
REINFORCED MASONRY SHEAR WALLS
d. GSE / ASIOE OPEN COVERED STORAGE = STEEL ORDINARY MOMENT
FRAMES (NOT SPECIFICALLY DETAILED FOR SEISMIC RESISTANCE)
e. HAZMAT / POL BUILDINGS = INTERMEDIATE REINFORCED MASONRY
SHEAR WALLS
f. FIRE PUMP BUILDING = STEEL ORDINARY BRACED AND MOMENT FRAMES
(NOT SPECIFICALLY DETAILED FOR SEISMIC RESISTANCE)
11. RESPONSE MODIFICATION FACTOR (R):
a. HANGAR MAINTENANCE BAY, R = 3
b. HANGAR ADMIN / SHOPS AREA, R = 3.5
c. AIRCRAFT PARTS SUPPLY ROOMS 152 & 152A, R = 3.5
d. GSE / ASIOE OPEN COVERED STORAGE , R = 3
e. HAZMAT / POL BUILDINGS, R = 3.5
f. FIRE PUMP BUILDING, R = 3
12. SEISMIC RESPONSE COEFFICIENT (Cs):
a. HANGAR MAINTENANCE BAY, Cs = 0.039
b. HANGAR ADMIN / SHOPS AREA, Cs = 0.033
c. AIRCRAFT PARTS SUPPLY ROOMS 152 & 152A, Cs = 0.033
d. GSE / ASIOE OPEN COVERED STORAGE , Cs = 0.031
e. HAZMAT / POL BUILDINGS, Cs = 0.027
f. FIRE PUMP BUILDING, Cs = 0.031
13. BASE SHEAR (V):
a. HANGAR MAINTENANCE BAY, V = 110 KIPS
b. HANGAR ADMIN / SHOPS AREA, V = 267 KIPS
c. AIRCRAFT PARTS SUPPLY ROOMS 152 & 152A, V = 12 KIPS
d. GSE / ASIOE OPEN COVERED STORAGE , V = COMPUTED BY PEMB SUPPLIER
e. HAZMAT / POL BUILDINGS, V = 3 KIPS EACH
f. FIRE PUMP BUILDING, V = COMPUTED BY PEMB SUPPLIER
G. ANTI-TERRORISM
1. PER UFC 04-010-01 DOD, MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS,
W/ CHANGE 2, 30 JULY 2022. THE HANGER MAINTENCE BAY, AIRCRAFT PARTS ROOMS
152 & 152A, AND THE FIRE PUMP BUILDING ARE LOW OCCUPANCY FOR AT/FP
CONSIDERATIONS.
III. GENERAL NOTES
A. DESIGN DRAWINGS SHOW INTENT OF REQUIRED CONSTRUCTION AND SPECIFIC
CONSTRUCTION AS NEEDED TO FACILITATE CLEAR DETAILING. FOR SPECIFIC CONDITIONS
NOT SHOWN, THE CONTRACTOR SHALL PROVIDE DETAILS OF CONSTRUCTION SIMILAR TO
THOSE SHOWN. VERIFY ALL EXISTING CONDITIONS, DIMENSIONS, AND ELEVATIONS PRIOR
TO COMMENCING WORK. IF DISCREPANCIES EXIST, NOTIFY THE CONTRACTING OFFICER IN
WRITING PRIOR TO COMMENCING WORK. CONTRACTOR SHALL MAKE NO DEVIATION FROM
THE CONTRACT DOCUMENTS WITHOUT WRITTEN APPROVAL FROM THE CONTRACTING
OFFICER.
B. THE CONTRACT DOCUMENTS REPRESENT THE FINISHED STRUCTURE AND DO NOT
INDICATE THE METHOD OR SEQUENCE OF CONSTRUCTION. THE CONTRACTOR SHALL
PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING
CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT ARE NOT LIMITED TO, TEMPORARY
BRACING AND/OR SHORING FOR LOADS AND STRUCTURE. TEMPORARY CONSTRUCTION
LOADING MAY INCLUDE AND ARE NOT LIMITED TO LATERAL LOADS, LOADS DUE TO
STOCKPILES OF MATERIAL, AND LOADS DUE TO CONSTRUCTION EQUIPMENT. SUCH
BRACING SHALL BE LEFT IN PLACE AS LONG AS REQUIRED FOR SAFETY AND UNTIL ALL
FRAMING INCLUDING ROOF DECK IS IN PLACE.
C. RELATIVE DATUM UTILIZED ON THE STRUCTURAL SHEETS: 100'-0" = FINISHED FLOOR.
ELEVATIONS SHOWN ON THE CIVIL SHEETS ARE BASED ON MEAN SEA LEVEL ELEVATION.
COORDINATE THE FINISHED FLOOR ELEVATION SHOWN ON THE STRUCTURAL SHEETS WITH
THE ELEVATION SHOWN ON THE CIVIL SHEETS.
D. THE CONTRACTOR SHALL PROTECT ALL EXISTING FACILITIES, STRUCTURES, AND UTILITY
LINES FROM ALL DAMAGE . DAMAGE TO ALL WORK SHALL BE REPAIRED TO THE
SATISFACTION OF THE CONTRACTING OFFICER AT THE CONTRACTOR'S EXPENSE.
E. THE CONTRACTOR SHALL ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR
ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING AND OTHER APPROPRIATE TRADE
DRAWINGS AND SUBCONTRACTORS PRIOR TO CONSTRUCTION.
F. JOB SAFETY AND CONSTRUCTION PROCEDURES ARE THE RESPONSIBILITY OF THE
CONTRACTOR.
G. DRAWINGS SHALL NOT BE SCALED FOR DIMENSIONS.
IV. FOUNDATION & SOIL DATA
A. FOUNDATIONS HAVE BEEN DESIGNED IN ACCORDANCE WITH REQUIREMENTS SET FORTH IN
THE GEOTECHNICAL REPORT TITLED AAB MAINTENANCE HANGAR FORT RILEY, KANSAS
FY2020, DATED APRIL 2020, PROJECT NUMBER 72687, PREPARED BY USACE, KANSAS CITY
DISTRICT.
B. THE FOUNDATION SYSTEMS FOR ALL BUILDINGS CONSIST OF SHALLOW FOUNDATIONS
(ISOLATED, COMBINED OR CONTINUOUS FOOTINGS).
C. THE CONTRACTOR SHALL OVEREXCAVATE 1'-4" OF SOIL BELOW ALL ISOLATED, COMBINED
AND CONTINUOUS BUILDING FOOTINGS FOR THE PROJECT, AND PLACE PROPERLY
COMPACTED SELECT GRANULAR MATERIAL PER SPECIFICATION SECTION 31 00 00. REFER
TO A6/S-510 FOR TYPICAL DETAIL.
D. IN ADDITION TO OVEREXCAVATION AND REPLACEMENT WITH SELECT GRANULAR MATERIAL,
ADDITIONAL SOIL IMPROVEMENT (DENSIFIED AGGREGATE PIERS) IS REQUIRED FOR ALL
ISOLATED, COMBINED FOOTINGS AND LOAD-BEARING WALL CONTINUOUS FOOTINGS FOR
THE HANGAR MAINTENANCE BAY, AIRCRAFT PARTS STORAGE ROOM AND ADMIN AREA.
REFER TO SPECIFICATION SECTION 31 00 00 FOR REQUIREMENTS FOR THIS ADDITIONAL
SOIL IMPROVEMENT (DENSIFIED AGGREGATE PIERS). REFER TO S-612 FOR THE LOCATIONS
OF THE FOOTINGS REQUIRING THIS ADDITIONAL SOIL IMPROVEMENT (DENSIFIED
AGGREGATE PIERS).
E. THE NON LOAD-BEARING CONTINUOUS WALL FOOTINGS IN THE AIRCRAFT PARTS STORAGE
ROOM AND ADMIN AREA DO NOT REQUIRE ADDITIONAL SOIL IMPROVEMENT BEYOND THE
OVEREXCAVATION AND REPLACEMENT WITH SELECT GRANULAR MATERIAL. REFER TO
S-612 FOR THE LOCATIONS OF THESE FOOTINGS.
F. THE NET ALLOWABLE SOIL BEARING CAPACITY FOR ISOLATED, COMBINED AND
CONTINUOUS FOOTINGS WITH THE ADDITIONAL SOIL IMPROVEMENT (DENSIFIED
AGGREGATE PIERS) AND OVEREXCAVATION AND REPLACEMENT WITH SELECT GRANULAR
FILL IS 6000 PSF, WITH THE EXCEPTION OF THE HANGAR MAINTENANCE BAY COMBINED
FOOTINS SHOWN ON S-610 AND THE TWO F1 FOOTINGS SHOWN ON S-112, WHICH IS 1500
PSF. THE NET ALLOWABLE SOIL BEARING CAPACITY FOR ISOLATED, COMBINED AND
CONTINUOUS FOOTINGS WITHOUT THE ADDITIONAL SOIL IMPROVEMENT (DENSIFIED
AGGREGATE PIERS) BUT WITH OVEREXCAVATION AND REPLACEMENT WITH SELECT
GRANULAR FILL IS 1500 PSF.
G. THE COEFFICIENT OF FRICTION (FOR SLIDING) BETWEEN THE SHALLOW SPREAD AND
CONTINUOUS FOOTINGS AND THE SELECT GRANULAR FILL BELOW IS 0.38.
H. THE MODULUS OF SUBGRADE REACTION FOR THE SOIL FOR SLAB-ON-GRADE DESIGN IS 100
PCI.
I. THE CONTRACTOR SHALL OVEREXCAVATE 2'-0" OF SOIL BELOW THE INTERIOR SLABS-ON-
GRADE, AND PLACE PROPERLY COMPACTED SELECT GRANULAR MATERIAL AND CAPILLARY
WATER BARRIER PER SPECIFICATION SECTION 31 00 00. REFER TO C4/S-511 FOR SUB-BASE
COMPOSITION UNDER THE SLAB-ON-GRADE. THE OVEREXCAVATION IS REQUIRED TO
PROVIDE "FIRM" FOUNDATION FOR THE SLAB-ON-GRADE AND TO MITIGATE UNCERTAINTY OF
SOFT MATERIALS THAT NEED TO BE REMOVED AND REPLACED WITH COMPACTED
ENGINEERED MATERIALS.
J. REFER TO SPECIFICATION SECTION 31 00 00 FOR DESCRIPTION AND REQUIREMENTS
FOR BEARING MATERIALS.
K. ALL COMPACTED FILL INSTALLATION SHALL BE INSPECTED AND APPROVED BY A
REGISTERED GEOTECHNICAL ENGINEER RETAINED BY THE CONTRACTOR. THE
REGISTERED GEOTECHNICAL ENGINEER SHALL INSPECT AND APPROVE BEARING
MATERIALS PRIOR TO THE PLACEMENT OF CONCRETE.
L. MINIMUM ISOLATED, COMBINED AND CONTINUOUS INTERIOR FOOTING DEPTH BELOW
FINISHED FLOOR ELEVATION: 36 INCHES.
M. MINIMUM ISOLATED, COMBINED AND CONTINUOUS EXTERIOR FOOTING DEPTH BELOW
EXTERIOR GRADE FOR UNHEATED AND HEATED STRUCTURES FOR FROST / EXPANSIVE
SOIL: 36 INCHES.
N. UTILITY LINES ROUTED THROUGH EXTERIOR FOUNDATION WALLS OR INTERIOR CMU WALLS
ABOVE THE CONCRETE FOOTINGS AND BELOW THE CONCRETE SLAB-ON-GRADE MUST BE
LOCATED AND HAVE GALVANIZED STEEL PIPE SLEEVES PER A1/S-511
O. UTILITY LINES ROUTED UNDER ALL FOOTINGS MUST BE LOCATED AND HAVE GALVANIZED
STEEL PIPE SLEEVES PER A1/S-511.
P. WHERE UTILITY LINES RUN PARALLEL AND ADJACENT TO FOOTINGS WITH ADDITIONAL SOIL
IMPROVEMENT (DENSIFIED AGGREGATE PIERS) AND MUST BE PLACED IN THE DENSIFIED
AGGREGATE PIER "NON-DISTURBANCE ZONES" UTILIZING BOTH CRITERIA "A" AND CRITERIA
"B", SPECIAL BACKFILL REQUIREMENTS MUST BE MET PER SECTIONS A6/S-517 (CRITERIA "A")
AND E6/-517 (CRITERIA "B")
Q. WHERE UTILITY LINES RUN PERPENDICULAR AND UNDER FOOTINGS WITH ADDITIONAL SOIL
IMPROVEMENT (DENSIFIED AGGREGATE PIERS) AND CAUSE EXCAVATION OF ANY PORTION
OF THE DENSIFIED AGGREGATE PIER "NON-DISTURBANCE ZONE" AS DEFINED IN SECTION
A2/S-517, SPECIAL BACKFILL REQUIREMENTS MUST BE MET PER SECTION A2/S-517.
R. REFER TO DRAWING S-612 FOR LOADING TO FOOTINGS REQUIRING ADDITIONAL SOIL
INPROVEMENT (DENSIFIED AGGREGATE PIERS.)
V. REINFORCED CONCRETE
A. MATERIAL STRENGTHS:
1. CONCRETE COMPRESSIVE STRENGTH (fc) AT 28 DAYS AND EXPOSURE CLASSES:
2. REINFORCING STEEL:
DEFORMED BARS ASTM A615, GR. 60 KSI
DEFORMED TIES ASTM A615, GR. 60 KSI
WELDED WIRE REINFORCEMENT (FLAT SHEETS) ASTM A1064 OR ASTM A185
B. NOTES:
1. ALL CONCRETE OPERATIONS AND REINFORCEMENT SHALL BE IN ACCORDANCE
WITH THE LATEST ACI AND CRSI STANDARDS.
2. REFER TO ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS FOR
ADDITIONAL EMBEDDED ITEMS AND ACCESSORIES. NO CALCIUM CHLORIDE OR
OTHER DELETERIOUS SALTS ARE PERMITTED IN CONCRETE. NO ALUMINUM
EMBEDMENTS ARE PERMITTED. PROVIDE 3/4" CHAMFER AT ALL EXPOSED CORNERS.
3. FURNISH THE FOLLOWING SPECIFIED CONCRETE COVER ON REINFORCING BARS
UNO:
SLAB-ON-GRADE 1-1/2"
CONCRETE PEDESTALS 2" COVER ON TIES
FOOTINGS 3" COVER ON BOTTOM AND SIDES
FOUNDATION WALLS AND RETAINING WALLS 2" UNO
4. REFER TO THE SPECIFICATIONS FOR THE FINISH REQUIREMENTS FOR ALL CAST-IN-
PLACE CONCRETE ELEMENTS.
5. LONGITUDINAL REINFORCING IN THE FOUNDATION WALLS AND STRIP FOOTINGS
SHALL BE PLACED CONTINUOUS AT CORNERS AND INTERSECTIONS. MATCHING
CORNER BARS SHALL BE USED PER THE TYPICAL CONCRETE REINFORCEMENT
DETAILS ON THE CONTRACT DRAWINGS.
6. WHERE INDICATED ON THE DRAWINGS, PROVIDE AN INTENTIONALLY ROUGHENED
CONSTRUCTION JOINT BETWEEN CONCRETE SURFACES. PROVIDE 1/4" MINIMUM
AMPLITUDE AT EXISTING CONCRETE SURFACE AND A CONCRETE BONDING AGENT
PRIOR TO PLACING NEW CONCRETE.
7. ALL CONCRETE IS REINFORCED UNLESS SPECIFICALLY CALLED OUT AS
UNREINFORCED. REINFORCE ALL CONCRETE NOT OTHERWISE SHOWN WITH THE
SAME STEEL AS IN SIMILAR SECTIONS AND AREAS.
8. CONTRACTOR SHALL COORDINATE LOCATIONS OF ALL FLOOR DRAINS, FLOOR
FINISHES, CURBS, CONCRETE PADS, AND SLAB DEPRESSIONS WITH
ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS.
9. CONTRACTOR SHALL FIELD VERIFY DIMENSIONS AND LOCATIONS OF ALL OPENINGS,
PIPE SLEEVES, CURBS, ETC., AS REQUIRED WITH OTHER TRADES PRIOR TO PLACING
CONCRETE.
10. CONTRACTOR SHALL COORDINATE LOCATIONS OF INSERTS, WELDED PLATES, AND
OTHER ITEMS EMBEDDED IN CONCRETE WITH ARCHITECTURAL DRAWINGS,
MECHANICAL DRAWINGS, AND ELECTRICAL DRAWINGS AND OTHER TRADES.
11. ALL INTERIOR CONCRETE SLABS-ON-GRADE SHALL MEET THE FLATNESS AND
LEVELNESS REQUIREMENTS SPECIFIED IN SPECIFICATION SECTION 03 30 00. ALL
ELEVATED CONCRETE SLAB-ON-METAL DECK FLOORS SHALL MEET THE FLATNESS
REQUIREMENTS SPECIFIED IN SPECIFICATION SECTION 03 30 00
12. ALL REINFORCING BARS SHALL BE LAPPED AS SPECIFICALLY DETAILED ON THE
DRAWINGS. REFERENCE THE MISCELANEOUS LAP LENGTH SCHEDULE ON S-002
WHERE NOT SPECIFICALLY DETAILED ON THE DRAWINGS. ALL REINFORCING BARS
SHALL BE LAPPED USING THE TENSION LAPPED SPLICE LENGTHS PER ACI 318-14.
* HANGER MAINTENANCE BAY INTERIOR SLAB-ON-GRADE; MINIMUM 90 DAY CONCRETE FLEXURAL
STRENGTH = 550 PSI; MAXIMUM 90 DAY CONCRETE FLEXURAL STRENGTH = 650 PSI.
F. SEISMIC LOAD
1. SITE CLASS = D
2. SHORT PERIOD SPECTRAL RESPONSE ACCELERATION PARAMETER (FOR SITE
CLASS B), Ss = 0.09
3. SHORT PERIOD SPECTRAL RESPONSE ACCELERATION PARAMETER (ADJUSTED
FOR SITE CLASS D), Sds = 0.093
4. ONE SECOND PERIOD SPECTRAL RESPONSE ACCELERATION PARAMETER (FOR
SITE CLASS B), S1 = 0.05
5. ONE SECOND PERIOD SPECTRAL RESPONSE ACCELERATION PARAMETER
(ADJUSTED FOR SITE CLASS D), Sd1 = 0.087
VI. STRUCTURAL STEEL:
A. DESIGN CODE: SPECIFICATIONS FOR THE DESIGN, FABRICATION, AND ERECTION OF STRUCTURAL
STEEL FOR BUILDINGS (AISC).
B. MATERIAL STRENGTHS:
STRUCTURAL STEEL ROLLED W-SHAPES ASTM A992 (Fy = 50 KSI)
CHANNELS, ANGLES, & OTHER HOT ROLLED SHAPES ASTM A36
BASEPLATES AND ALL OTHER MISC. PLATES & BARS ASTM A36
RECTANGULAR OR SQUARE HSS ASTM A500 GR C (Fy = 50 KSI) OR
ASTM A1085 (Fy = 50 KSI) ROUND HSS ASTM A500 GR C (Fy = 46 KSI) OR
ASTM A1085 (Fy = 50 KSI)
CONNECTION BOLTS ASTM F3125 GR A325 WITH ASTM
F959 DTI WASHERS, OR ASTM F3125
GR F1852 TWIST-OFF BOLTING
ASSEMBLIES
ANCHOR RODS ASTM F1554 GR. 36
WELDING ELECTRODES E70
HEADED WELDING STUDS ASTM A29 OR ASTM A108
TYPE B (Fy = 51 KSI) DEFORMED BAR ANCHORS ASTM A496 (Fy = 70 KSI)
C. NOTES:
1. ALL STRUCTURAL STEEL AND THEIR CONNECTIONS SHALL BE DETAILED, FABRICATED,
AND ERECTED ACCORDING TO THE AMERICAN INSTITUTE OF STEEL CONSTRUCTION
(AISC) MANUAL OF STEEL CONSTRUCTION, 15TH EDITION.
2. STRUCTURAL STEEL SUPPLIER SHALL PROVIDE CONNECTIONS PER D4/S-520 AND D8/S-520 FOR
ALL SIMPLE SHEAR CONNECTIONS NOT SPECIFICALLY DETAILED ON THE DRAWINGS.
REFERENCE SPECIFICATION SECTION 05 12 00.
3. STRUCTURAL STEEL SHALL BE PRIME PAINTED OR GALVANIZED PER AS SPECIFIED IN THE
CONTRACT DOCUMENTS.
4. ALL WELDING SHALL BE DONE BY AMERICAN WELDING SOCIETY (AWS) CERTIFIED WELDERS.
5. COLUMN ANCHOR RODS SHALL BE POSITIVELY LOCATED USING 1/8" SHEET METAL TEMPLATES
FOR ALL COLUMN BASEPLATES. PROVISION SHALL BE MADE FOR ALL ANCHOR RODS TO BE
RIGIDLY HELD IN POSITION TO PREVENT MOVEMENT DURING CONCRETE PLACEMENT. ANCHOR
RODS SHALL NOT BE TIGHTENED PRIOR TO 14 DAYS FOLLOWING CONCRETE PLACEMENT.
6. THE STRUCTURAL STEEL PROVIDER SHALL COORDINATE THE BOTTOM OF BASEPLATE
ELEVATION WITH THE ACTUAL TOP OF CONCRETE ELEVATION.
7. FILLER BEAMS SHALL BE SPACED EQUALLY BETWEEN SUPPORTS UNLESS OTHERWISE NOTED
ON THE DRAWINGS.
8. PORTIONS OF THE STRUCTURE ARE NOT SELF SUPPORTING DURING ERECTION, FOR GRAVITY
AS WELL AS LATERAL LOADS. PROVIDE ANY TEMPORARY BRACING OR GUYS TO PROVIDE
LATERAL SUPPORT OF THE BUILDING AND INDIVIDUAL ELEMENTS UNTIL PERMANENT FRAME
AND DECK ARE COMPLETELY INSTALLED. THE VARIOUS ROOF DECKS AND ELEVATED
CONCRETE SLABS SERVE AS HORIZONTAL DIAPHRAGMS THAT DISTRIBUTE THE LATERAL WIND
AND SEISMIC FORCES HORIZONTALLY TO THE LATERAL FORCE RESISTING SYSTEMS. THE
LATERAL FORCE RESISTING SYSTEMS CARRY THE APPLIED LATERAL LOADS TO THE BUILDING
FOUNDATION.
9. THE ELEVATED CONCRETE SLAB-ON-METAL DECK FLOORS HAVE BEEN DESIGNED UTLIZING
UNSHORED CONSTRUCTION.
10. THE CONCRETE FOR THE ELEVATED CONCRETE SLAB-ON-METAL DECK FLOORS SHALL BE
INSTALLED PER THE "CONSTANT THICKNESS" METHOD; HOWEVER, THE CONCRETE THICKNESS
SPECIFIED CAN BE INCREASED LOCALLY TO SATISFY THE ELEVATED SLAB FLATNESS
REQUIREMENTS.
VII. STEEL ROOF DECK AND COMPOSITE FLOOR DECK
A. DESIGN CODE: STEEL DECK INSTITUTE DESIGN MANUAL FOR ROOF DECKS AND FLOOR DECKS (SDI
B. MATERIAL STRENGTHS: PER SDI SPECIFICATIONS.
NOTES:
1. STEEL ROOF DECK SHALL BE FABRICATED AND ERECTED ACCORDING TO SPECIFICATIONS
OF THE STEEL DECK INSTITUTE (SDI).
2. PROVIDE ALL RIDGE PLATES AND ALL OTHER ACCESSORIES REQUIRED FOR COMPLETE
INSTALLATION
3. ALLOWABLE STRESS BASED ON SDI AND AISI
4. MAXIMUM DEFLECTION DUE TO SUPERIMPOSED LOADS SHALL BE LIMITED TO L/240
5. STEEL ROOF DECK AND COMPOSITE FLOOR DECK SHALL BE GALVANIZED AND SHOP
PRIME COATED PER SPECIFICATION SECTION 05 30 00.
6. PROVIDE ROOF DECK CONSTRUCTION WHICH IS LISTED AND CONFORMS TO THE UL FIRE
RESISTANCE DIRECTORY AND BUILDING MATERIALS DIRECTORY. DECK ATTACHMENT SHALL
MEET A CLASS 1-90 UPLIFT RATING.
7. ALL METAL DECK SHALL BE FABRICATED AND INSTALLED FOR A MINIMUM THREE SPAN
CONDITION, UNO
8. DECKING CONTRACTOR SHALL COORDINATE DECK OPENING SIZES AND LOCATIONS WITH
ARCHITECTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS AND SHALL PROVIDE HEADER
MEMBERS AND REINFORCEMENT AS REQUIRED PER TYPICAL DETAILS.
9. REFERENCE THE CONTRACT DRAWINGS FOR DECK TYPE, GAUGE, AND FASTENER SPACING.
SEE ROOF FRAMING SHEETS FOR MORE INFORMATION.
10. HANGING LOADS FROM ROOF DECK IS PROHIBITED.
VIII. STEEL JOISTS
A. STEEL JOISTS SHALL CONFORM TO THE 2020 STANDARD SPECIFICATIONS OF THE STEEL JOIST
INSTITUTE (SJI).
B. JOIST BRIDGING SIZE, SPACING, AND LOCATIONS SHALL BE DETERMINED BY THE JOIST SUPPLIER.
REFER TO THE CONTRACT DRAWINGS FOR ADDITIONAL REQUIREMENTS FOR LOCATION, SPACING AND
TYPE OF BRIDGING.
C. CONCENTRATED LOADS FROM MECHANICAL AND ELECTRICAL EQUIPMENT, AS WELL AS FROM
ARCHITECTURAL COMPONENTS, SHALL BE LOCATED AT JOIST PANEL POINTS WHERE PRACTICAL.
WHERE NOT PRACTICAL, EXTRA JOIST WEB MEMBERS SHALL BE FIELD LOCATED AND INSTALLED AT
LOCATIONS WHERE THE TOTAL CONCENTRATED LOADS FROM MECHANICAL AND ELECTRICAL
EQUIPMENT, AS WELL AS FROM ARCHITECTURAL COMPONENTS APPLIED BETWEEN JOIST PANEL
POINTS, EXCEED 100 POUNDS. REFER TO THE TYPICAL JOIST REINFORCING DETAIL A1/S-521 FOR
INSTALLATION OF THE EXTRA JOIST WEB MEMBERS (ANGLES). COORDINATE PROCUREMENT,
LOCATIONS, AND INSTALLATION OF EXTRA JOIST WEB MEMBERS WITH JOIST SUPPLIER. JOIST SUPPLIER SHALL DESIGN ALL JOISTS FOR A UNIFORM COLLATERAL VERTICAL DOWNWARD LOAD PER STRUCTURAL GENERAL NOTE II.B.2 APPLIED TO THE JOIST BOTTOM CHORD, IN COMBINATION WITH ALL
OTHER LOADS AS APPROPRIATE
D. JOISTS LOCATED ADJACENT ON BOTH SIDES OF STEEL COLUMNS, OR AT LOCATIONS DETERMINED BY
THE JOIST SUPPLIER, THAT ARE NOT FRAMED WITH STRUCTURAL STEEL MEMBERS RUNNING
PARALLEL TO THE JOISTS SHALL BE FIELD BOLTED AT JOIST BEARINGS.
E. THE JOIST SUPPLIER SHALL DESIGN ALL JOISTS FOR ALL LOADS SHOWN ON THE PLANS UTILIZING THE
APPROPRIATE LOAD COMBINATIONS FOR THE VARIOUS LOADS.
U .S
A
R M
Y C
O R
P S
O F
E N
G
IN
E E
R S
US Army Corps of Engineers
S O
L
IC
IT
A
T
IO
N N
O
D E
S
IG
N E
D B
Y
D E
S C
R
IP
T
IO
N
A
M A
R K
S
IZ
E
S U
B M
IT
T
E D
B Y
D A
T E
C O
N T
R A
C T
N O
C
H E
C K
E D
B Y
D R
A W
N B
Y
IS
S
U E
D A
T E
B
C
D
E
F
G
2 3 4 5 6 7 8 9 10
SHEET ID
File Path:
Plot Date:
R:\d0273859\_477687_Hangar_RVT20_S.rvt
1/29/2024 11:00:18 AM
S-001
S T
R U
C T
U R
A L G
E N
E R
A L N
O T
E S
F O
R T
R
IL
E Y
K
A N
S A
S
K A
N S
A S
C
IT
Y D
IS
T
R
IC
T J B
U S
H
IE
J .M
A X
W E
L L
A S
V
IT
A K
A S
V
IT
A K
J A
N U
A R
Y
W D
Q -2
-R
-4
S E
E C
O V
E R
P A
G E
F
IL
E N
A M
E
RTA
A T
T A
C K
A V
IA
T
IO
N
B A
T T
A L
IO
N C
O M
P L E
X
P
F Y
H a n g a r_
R V
T S
.r v t
PRODUCTION DATA 4PRODUCTION DATA 3
E
T
H S
T R
E E
T
K A
N S
A S
C
IT
Y M
O
A N
S I D
ITEM fc*
FREEZE THAW
EXPOSURE
CLASS
SULFATE
EXPOSURE
CLASS PERMEABILITY
CORROSION
PROTECTION
INTERIOR SLAB-ON-GRADE AND
ELEVATED SLABS
4.0 KSI F0 S0 W0 C1
ALL OTHER CONCRETE 4.5 KSI F1 S0 W0 C1
R e v is io n
J A
N
| Sheets |
| S-001 - STRUCTURAL GENERAL NOTES |